Title: TEST REPORT FOR RET 670 RELAY

EM/F/58/00
24.02.2011
PAGE 1 OF 4

TEST REPORT OF TRANSFORMER PROTECTION RELAY RET670


TESTING DATE
: 19/01/13
SERVICE
: Transformer-7
CURRENT/ VOLTAGE INJECTION UNIT NAME/ MODEL: DOBLE KIT/ F-6150
INJECTION UNIT SL No
: 061003858

GENERAL INFORMATION & DATA


TRANSFORMER DATA
Voltage Ratio

220 / 34.5 / 11.5


MVA
FL Current (A)

Vector Group
Protection CT Ratio
(Diff-600/1), (REF-500/1),
(StandbyEF-200/1)
1500/1
(Diff-2500/1), (REF3000/1), (standby400/1)

YNd11yn0
Metering CT Ratio

HV

130MVA

341A

600/1

LV1

80MVA

1339A

LV2

50MVA

2510A

Make

ABB

Software version

1.1Rev01

Auxiliary supply

220V DC

Serial Number

I0733014

Type

RET670

Rating

Ir=1A, Ur=110V, 50Hz

RELAY DETAILS

A. Differential Protection (87T) :1) Pick Up


Set Value
in Amps

Operated Value

HV SIDE

20%=0.2XIbase

0.1136

0.115

20%=0.2XIbase

0.1136

0.115

operated
operated

20%=0.2XIbase

0.1136

0.115

operated

LV1 SIDE

20%=0.2XIbase

0.29

0.291

operated

20%=0.2XIbase

0.29

0.291

operated

20%=0.2XIbase

0.29

0.291

operated

LV2 SIDE

Master Trip
operated or
Not

Setting in % of
Primary current

20%=0.2XIbase

0.5221

0.523

operated

20%=0.2XIbase

0.5221

0.523

operated

20%=0.2XIbase

0.5221

0.523

operated

PHASE

2) Stability
19/01/13

Indra/Nilesh/Murgan

M.DEVARAJULU

DATE

PERFORMED BY

CHECKED BY

Remarks

JSWEL
Doc. No:
Date:
Page:

Title: TEST REPORT FOR RET 670 RELAY

PHASE

HV

R-phase
R-phase
Y-phase
Y-phase
B-phase
B-phase

LV-1

0.568L0
0.568L0
0.568L240
0.568L240
0.568L120
0.568L120

1.449L210
1.449L195
1.449L90
1.449L75
1.449L330
1.449L315

EM/F/58/00
24.02.2011
PAGE 2 OF 4

HV

LV-2

0.217L0
0.217L0
0.217L240
0.217L240
0.217L120
0.217L120

REMARKS

1L180
1L150
1L60
1L30
1L300
1L270

STABLE
TRIP
STABLE
TRIP
STABLE
TRIP

3)Test Slope ( checked for (a) ES1=1.25,S2=30% & (b) ES1=1.0,S2=30%,ES2=1.5,S3=50%)


a)S2=30%
Current @ 1.3%
R-phase
Y-phase
B-phase

HV
0.738L0
0.738L240
0.738L120

LV-1
1.884L210
1.884L90
1.884L330

I1=443.3A
I2=547A
Id1=104A
Ib1=495

Current @ 1.5%
R-phase
Y-phase
B-phase

HV
0.852L0
0.852L240
0.852L120

LV-1
2.174L210
2.174L90
2.174L330

I11=511A
I22=642A
Id2=131A
Ib2=576A

Current @ 1.6%
R-phase
Y-phase
B-phase

HV
0.909L0
0.909L240
0.909L120

LV-1
2.319L210
2.319L90
2.319L330

I1=545
I2=810
Id1=265
Ib1=677

Current @ 1.8%
R-phase
Y-phase
B-phase

HV
1.021L0
1.021L240
1.021L120

LV-1
2.609L210
2.609L90
2.609L330

I11=613
I22=925
Id2=313
Ib2=769

HENCE S2=33% FOUND

b) S3=50%

HENCE S3=51% FOUND

4) Harmonic blocking
a) I2/I1
Phase
Setting
R-phase
Y-phase
B-phase

Operated
15

Remark

0.149/1,100/50Hz
0.149/1,100/50Hz
0.149/1,100/50Hz

b) I5/I1
19/01/13

Indra/Nilesh/Murgan

M.DEVARAJULU

DATE

PERFORMED BY

CHECKED BY

JSWEL
Doc. No:
Date:
Page:

Title: TEST REPORT FOR RET 670 RELAY

Phase
R-phase
Y-phase
B-phase

Setting

EM/F/58/00
24.02.2011
PAGE 3 OF 4

Operated
25

Remark

0.255/1,250/50Hz
0.255/1,250/50Hz
0.255/1,250/50Hz

B. HV Restricted Earth Fault Protection:PHASE

Setting in % of
Primary current

Set Value
in Amps

Operated Value

Master Trip
operated or
Not

40% X I base

200A

200.5 A ( 0.401A)

Operated

Remarks

C. LV Restricted Earth Fault Protection:PHASE

Setting in % of
Primary current

Set Value
in Amps

Operated Value

Master Trip
operated or
Not

40% X Ibase

1200A

0.397A

Operated

Operated Value
T(sec)

Master Trip
operated or
Not

Remarks

D. HV Timed Over Current (TOC) Protection:1) TOC1


PHASE

Setting in % of
Primary current

Set Value
in Amps

110%X Ibase

375A

2XIset

2.54

operated

110% X Ibase

375A

2XIset

2.54

operated

110% X Ibase

375A

2XIset

2.54

operated

PHASE

Setting in % of
Primary current

Set Value
in Amps

550%X Ibase

1875.5

550%X Ibase

550%X Ibase

I(A)

Remarks
Current
Injected in
all the
Phases.
Operating
as per NI
Curve

2) TOC2
Operated Value
T(sec)

Master Trip
operated or
Not

3.2L0

0.03

operated

1875.5

3.2L240

0.03

operated

1875.5

3.2L120

0.03

operated

I(A)

E. HV Residual Earth Fault Protection based on residual current (TEF-1):19/01/13

Indra/Nilesh/Murgan

M.DEVARAJULU

DATE

PERFORMED BY

CHECKED BY

Remarks

JSWEL
Doc. No:
Date:
Page:

Title: TEST REPORT FOR RET 670 RELAY

EM/F/58/00
24.02.2011
PAGE 4 OF 4

PHASE

Setting in % of
Primary current

Set Value
in Amps

Operated Value

20% x Ibase

68.2A

0.04

20% x Ibase

68.2A

0.04

20% x Ibase

68.2A

0.04

Master Trip
operated or
Not

Remarks

operated

F. HV Standby Earth Fault Protection:- CT Ratio:200/1


PHASE

Setting in % of
Primary current

Set Value
in Amps

Operated Value

Master Trip
operated or
Not

20% X Ibase

40A

0.22

operated

G. OVER EXCITATION:
PHASE
Setting in % of
V/Hz

Operated Value
V/Hz

Master Trip
operated or
Not

120%

79.26/48

Operated

120%

79.26/48

Operated

120%

79.26/48

Operated

19/01/13

Indra/Nilesh/Murgan

M.DEVARAJULU

DATE

PERFORMED BY

CHECKED BY