Beruflich Dokumente
Kultur Dokumente
BABCOCK BOILER
UAN WEST 1 TO 6
Operation Manual
Table of Contents
A. BOILER 1 TO 6 :
1. TECHNICAL DATA
2. START UP PROCEDURE
i. COLD
ii. WARM
iii. HOT
3. FIRING SYSTEM
i. NATURAL GAS
ii. CRUDE OIL
i. NORMAL
ii. EMERGENCY SHUT DOWN
6. INTER LOCKS
i. Cold Start : it may be classified either boiler evaporator & superheater temperature as
environment level or start up after periodical inspection or overhauling.
ii. Warm Start : after down time of 24 hours, the boiler pressure of approx. 10 bars and
evaporator & superheater temperature approx. 180 oC.
iii. Hot Start : after a downtime of 8 hours, the boiler pressure approx. 40 bars and
evaporator & superheater temperature approx. 300 oC. If necessary, boiler will be re-fed as
low water level. The FW temperature amounts to approx. 100 o C.
Before start up the boiler check that the following items are fulfilled: -
i.All maintenance or inspection works at boiler or auxiliaries has to be completed and all work
permits must be cancelled.
ii. Combustion chamber, flue gas passes and flue gas ducts are cleaned and all manholes are
closed.
iii. Boiler drum cleaned and both manholes are properly tied. Level indicators are cleaned.
iv. The soot blowers should be in their retracted position.
v. All auxiliaries of the unit must be ready for operation e.g. all oil levels at pumps, motors and
gears are checked and topped up.
vi. All dampers, vanes etc. are greased.
vii. All safety instructions have to be checked about proper and exact functioning e.g. safety &
relief valves.
viii. All by pass valves in regulating loops should be closed and all regulating valves checked
about proper working conditions.
ix. All chemical analysis has to be in working order, cation filters are regenerated etc.
x. The isolating valves of all indications or transmitters impulse line must be open.
xi. All electric breakers should be in working place.
xii. The T.V. cameras for boiler furnace and drum level indication are ready for service but the
furnace camera kept in operation before 1st burner fire.( N / A )
xiii. Check waste water drain pumps and grease pots are filled
xiv. Check service water pumps; related water basin & over head tank.
xv. Check instrument air compressors , dryers & reserve tank.
xvi. Check service air compressors & reserve tank.
xvii. Check emergency diesel air compressors.
xviii. Check make up water pumps
xix. Check instrument air supplied all consumers.
xx. Power supplied to burners cubicle HB1-4 switch ON.
6
2 – 1. . PREPARATION TO START UP: -
a. CONDITION OF THE MOTERIZE VALVE
PRE – CONDITIONS: ONE FW PUMP INSERVICE & THE FOLLOWING MOTORIZED VALVES C.V ARE IN
WORKING POSITION.
Conditions:-
5. Open inlet valve of both LP gas red. station NN2G1 & NN7G1.
6. Closed valve in nitrogen and vent lines.
7. Fill LP gas red. Station and waiting for press. equalization ~ 6.0 bar,
• by opening the by pass valve NN3G4 and NN8G4.
8. Open natural gas quick closing valve (NN8G401, NN3G401) by pressing the hand levers.
• An switch ON the Stop valve
9. Check proper function of LP gas red. Station valves.
• by opening the vent valve ( NN5G1, NN10G1) pressure drop,
• and watch press. after red. Station valve at ~ 3.9 bar and 4.0 bars respectively;
• then close the vent valves.
10. Open outlet valve of LP gas red. Station (NN3G1, NN8G1).
11. Check the position of natural gas control valve (NN20G401.
• It must be close position.
12. Open the natural gas relief valve, NN34G801 from TCR desk.
13. Circuit breakers of Cooling air fans working position.
• and EM. Push button released & Select Switches in TCR position.
14. Check all cooling air valves to photo cell are opened.
15. Start one of the cooling air fan. NK51A1 or NK52A1 from TCR desk.
• cool Air press. Low signal ‘ disappear ‘
nd
16. Select 2 Cooling air Fan NK52A1 to ‘AUTO’ position.
17. Tripped the running fan by pressing EM. Push button from local , Sel. ‘Auto’ stand by will take place
18. Release EM. Push button & Sel. he Fan NO. in AUTO position ;
nd st
• Press EM button of the 2 running fan, after tripped 1 one will take place.
20. Start of the FD fans from TCR desk on ‘AUTO’ program or ‘MAN’ Selection for purging.
[ Boiler purging means, clear the boiler furnace & down stream flue gas paths upto chimney inlet by a sufficient volume
of air to get rid ( make free) of undesirable elements in order to safe guard the equipment against any explosion]
PRECONDITIONS:-
Connecting the interlock setting of the boiler main protection & firing interlocks systems established.
• i. Emergency push buttons released.
• ii. Control air pressure > min.
• iii. Boiler release existing means that the following interlocks are fulfilled .
a) Furnace pressure < min.
b) Drum level between < HH & > LL
c) Fuel air ratio < HH
d) F.D. Fan 1 or 2 in operation.
e) All oil quick closing valves are closed.
f) All natural quick closing valves are closed.
g) No purge program existing or any burner in service.
14
Press push button “ Preventing ON’
Air dumpers of all burners will open.
22. when all burner dampers are in open position ;
start to open FD Fan vane
3
and bring the air flow to ~ 200,000 nm / h.
signal “Preventing running ' appears.
after 160 seconds signal ‘Preventing finish ‘will appears &
“ Ready for ignition” period will start . TIME SETTING 10 minutes.
3
reducing the air flow by closing FD fan vane to 15 %; with air flow of approx. 45,000 nm / h,
and burners ‘Ready for Ignition ‘signal will appears at each of the nine burners.
23. Starting the first burner from bottom row with natural gas burner.
PRECONDITIONS: -
o
29. When SH NO.1 steam out let temperature app. ~ 300 C press. about 5 bar,
• Then close step by step throttle all Super heaters drain valves according their metal
temperature.
• Keep an eye super heaters multi point metal temperature.
• After 30 min.
3
30. Increase the combustion air flow to 70,000 Nm / h also increase N.G. pressure to 0.7 bars, gas flow
approx. 4,000 Nm3 / h.
3 3
31. After 40 min. increase air flow 80, 00 Nm / h & gas press. to 0.8 bar (gas flow around 4300Nm /h).
32. 3 rd burner ‘8’ start : -
rd
• before start 3 burner, prepare the attemperators station for service to maintain required
temperature.( drain valves close , isolating valves opened & properly vented).
3
33. Air flow increase to 90,000Nm / h, adjust gas pressure to 0.6 bars, corresponding gas flow about 5,000
Nm3 / h.
• The fire rate must be kept in a limit, press. not more than & press. 1.5 bars / min.
o
• The super heater metal temp. normal increasing rate 5 C / min,
• FW and combustion control valves to ‘AUTO ‘(Gas, contr. valve & FD Fan vane).
40. when boiler load reach approx. 180 t / h,
nd
start the 2 FW pump.
3
41. when air flow reach approx. 170,000 Nm / h ,
nd
start the 2 FD Fan;
nd
then open 2 FD fan vane until, both fans are equalized,
nd
select the 2 FD Fan vane control to automatic position
42. Bring steam parameters of boiler up to operating values;
o
• press. 65 bars & temp. 490 C,
• by increasing the number of burners firing respectively with load.
17
CONDITIONS: -
i. At least one crude tank filled.
ii. One crude oil transfer pump running.
iii. one transfer pump selected to ‘AUTO’ start
iv. one service air compressor running
v. Boiler filled up to normal starting level.
vi. condensate pump running for mechanical sealing of the FW pump
vii. One feed water pump running.
1. Open hand isolating vale OUS 70G1 from service air main ring line to boiler.
2. Open hand isolating valve OUS70 G2 service air to atomizing air.
indication ‘Atomizing air pressure Low signal disappears.
3. Bring anti – vibration rings into oil position on burner 7, 8 & 9.
4. Preparations before start of the 1st burner
5. Circuit breakers of crude oil booster pumps (NM21A1 & NM22A1) are working position.
6. One oil filter in normal position, other one cleaned & properly filled.
7. Open suction, discharge and minimum flow valves at each pump : -
(NM1G1,NM21G1,NM22G1NM23G1,NM24G1,NM25G1,NM26G1, NM34G1,NM34G2)
8. open hand valves ( NM27G1 & NM27G2) before & after relief valve
9. Close by pass valve (NM27G1) of the pressure relief valve.
10. Close crude oil control valve ( NM32G401
11. Open controller’s hand isolating valves (NM32G1 & NM32G2).
12. Close crude oil by pass valve (NM33G1).
13. Open hand isolating valve (NM31G1 & NM31G2) before & after crude oil start up valve.
14. Open crude oil flow meter isolating valves (NM34G1 & NM34G2).
15. Close by pass valve (NM35G1) of crude oil flow meter.
16. Close hand isolating valves (NM41G1 – 49G1) before each burner.
17. Close oil return valve (NM51G801).
18. Through by pass valve (NM52G1) throttled oil flow approx. 6 t / h.
19. open 2 turn by pass valve (NM92G1) of the atomizing steam trap.
20. open atomizing steam control station outlet valve (NM62G4).
21. close by pass valve (NM63G1 & G2) of the atomizing steam control valve
22. open 2 turn by pass valve (NM94G1) of the atomizing steam trap.
23. open slowly to 100 % isolating valve (NM62G1) infront reducing station.
watch pressure & temperature.
O
temperature after reducing station approx. 200 C.
open fully atomizing steam control station inlet & outlet valves (NM62G1 & G2 )
pressure approx. 13.5 bars.
24. Open steam trap isolating valves (NM91G1 & G3).
18
25. close atomizing steam trap by pass valves (NM92G1 & NM94G1).
26. Start crude oil booster pump ( NM21A1 or NM22A1) : -
Release EM. Push buttons both pumps (BM21& 22A1).
Selections are in TCR.
Start one pump deliver pressure approx. 23 bars.
Both pumps performance test will be carry out one by one.
Physically check that all oil & atomizing steam hoses are properly connected.
Open hand isolating valves at each burner.
After opening the atomizing steam hand isolating valves on burner 7, 8 , & 9 ‘Atomizing medium
Low ‘ signal must disappear.
Close by pass valve to oil return, watch oil flow will be 0 t / h.
Watch oil pressure before oil QCV of burner, approx. ~ 6.0 bar.
27. Both FD fans dampers & vanes check function by opening & closing.
i. Both FD fans oil level check.
ii. Open all hand operated dampers (NG30, 31,40,41,50 & 51G1) in the air ducks.
iii. EM push buttons released.
iv. Start one of the FD Fan from TCR on AUTO program
Select ‘AUTO’ program > Press release button & ON button of the fan > when running up
time of the starting FD Fan is over > damper will open automatically.
v. Press push button ‘ Preventing ON’
air dampers of the all burners will open, if they are not yet open.
vi. When above air dampers are open position
open air vane and check air flow.
3
Air flow > 200,000 Nm / h.
Signal ‘Preventing Running’ appears.
After 160 seconds signal ‘Preventing Finish’ will appear.
28. Air flow approx. 55,000 Nm3 / h.:
Start oil burner 8 from TCR and wait until the flame signal appears and damper is moving in the open
position.
29. Watch all figures (drum level, feed water tank level, temperature, flow, pressure, also feed water flow
through economizer.
30. when drum pressure reaches 2.5 to 3 bar - close vent valves of the drum & super heater.
31. increase air flow to 65,000 Nm3 / h.:
3
Start oil burner NO.7, after start burner NO.7, increase air flow to 80,000 Nm / h.
32. Start burner NO.9, After the signal flame appears and the air damper open stop burner NO.8.
3
After stopping burner NO.8, reduce air flow to 65,000 Nm / h.
33. When drum pressure 10 – 15 bar start heating up steam lines.
34. Watch atomizing steam pressure & temperature before burner 7, 8 & 9.
35. Burner atomizing medium change over from air to atomizing steam : -
When atomizing steam pressure is higher than atomizing air pressure the non-return valves in
atomizing lines will be closed automatically by the atomizing steam pressure and the change over
period starts.
Closing all atomizing air valves starts within 10 minutes time delay. After the 10 minutes the
atomizing air valves will be closed automatically and the signal ‘Atomizing steam press Low Low ‘
disappears.
36. Start other burners and & watch all parameters , increase pressure and temperature of boiler by
correspondingly controlling oil flow and air flow respectively the number of burners in operation.
After pressing ‘ON ‘ button start the burner the “Ready “ signal disappearing oil lance will be inserted air
damper is moving into ignition position. When the oil lance is inserted the atomizing steam valve is opening for heat
up the oil lance and pushes the accumulated condensate out of the atomizing steam system. When the pre-purging
or pre-heat time is over and the air damper is in ignition position the power for the electric igniter is switch on and
the igniter starts move into the operation position. After igniter established the safety ignition time starts ( 5 second)
and the oil valve opens if the following criterias are fulfilled : -
19
i. air damper ignition position.
ii. Oil operation released
iii. No order ‘OFF’ appeared
iv. Air flow > min.
v. Atomizing steam valve open
vi. Oil lance inserted.
The fuel air mixture will ignite on the sparks of the igniter and fotocell must pick up the flame within the safety ignition time.
If this done, then the signal “Flame” will appear and the air damper is moving into operation.
After the expiry of the safety ignition time the igniter is retracted and the power switched off. If the fotocell is not picking up
the flame within the safety time the oil quick closing valve will close again and the signal oil burner distur-bance and oil
burner purge will be appearing.
The oil lance will be retracted.
The burner ‘OFF’ or disturbance signal has to be cancelled by pressing the burner ‘OFF’ push button.
3
Is no other gas or oil burner in operation the automatic furnace purge will start as soon as air flow is above 200,000 n m /
h.
When the preventing of the boiler is finished the burner may be re-started or steam purge. If you want to start oil burner,
press oil ‘ON’ button, if you want to steam purge the burner press the ‘OFF’ button.
Conditions:
at least one crude oil tank is filled.
one transfer pump is running
and one transfer pump selected to ‘AUTO’ position.
Crude oil line properly vented & an oil flow 5 to 10 t / h is circulating each boiler ( which
prevent that wax or other part of the oil can settle in the pipe & choke the strainers and
oil gun nozzles.
All valves should be in their normal operation condition.
All oil lances installed in the retracted position and atomizing steam hoses are
connected.
The nitrogen buffer system has to be filled with nitrogen, during normal operation the
pressure should be > 21 bars.
4. Hand valve before and after press. relief valves, NM27G1 – open, NM27G2 – open,
by pass valve of pressure relief valve NM28G1 – closed.
5. crude oil control valve NM32G401 open; and hand isolating valve NM32G2 open.
Crude oil control valve, by pass valve NM33G1 - close.
6. Hand operated isolating valve before and after the crude oil start-up valve NM31G1 and
NM31G2 – open.
7. crude oil flow meter before and after isolating valve NM34G1 and NM34G2 – open.
by pass valve NM35G1 of the flow meter – close.
8. Hand isolating valve before each burner NM41 to NM49G1 – close.
9. oil return pneumatic valve NM51G801 – close.
by pass valve NM52G1 to oil return –: throttle crude oil flow approx. 6 t / h.
10. by pass valve of steam trap of atomizing steam valve NM92G1 – open 2 turns.
11. Hand operated isolating valves before and after steam trap NM91G1 & G3 – open.
12. Atomizing steam control station outlet valve NM62G4 - open.
13. By pass valve of atomizing steam control valve NM63G1 & G2 – close.
by pass valve of the steam trap NM94G1 open 2 turns
isolating valve NM62G1, in front Red. Station –– open slowly to full.
isolating valve NM62G2 before Red. Station – open slowly.
and watch pressure and temp.
14. Temperature reaches after Red. Station approx. ~ 200 o C.
stepwise open valve NM62G2 fully and watch press. approx. 13.5 bar.
15. by pass valve of steam trap of atomizing Red. Station drain valve NM94 & 92G1 – close.
and watch temp. after Red. Station approx. 245 o C.
16. Release EM. Push buttons of both crude oil booster pumps.
22
Select booster pumps NM21, NM22A1 in the TCR position.
17. start one of the booster pumps from TCR.
and watch the crude oil control valve approx. 23 .00 bar.
18. Select stand by crude oil booster pump to ‘AUTO’, and check ‘AUTO’ start up.
trip the running pump by EM. push button.
stand by pump start automatically.
19. Repeat the same other crude oil booster pump.
20. make sure that, all oil and atomizing steam hoses are connected,
and open the oil hand isolating valve in front of each burner.
21. close by pass valve to oil return valve.
and watch oil flow, 0.0 t / h.
watch press. before oil quick stop valve of burners approx. 6 ~ 7 bar.
Note: -Start-up oil pressure is 7.0 bars.
23
A – 3. 1. BOILER FIRING SYSTEM CHANGE OVER
Conditions: - :
Boiler load 200 t / h, with 9 burners in operation.
HP Gas Red. Station in service.
LP Gas Red. Station in service.
7. stop crude oil burner NO. 9 , after purge time over & oil lance retracted :-
start gas burner NO. 9 , when ‘ FLAME’ signal appears,
increase the gas press. to approx. 0.6 bar ~ 0.7 bar, by opening gas control valve.
8. stop oil burner NO. 8, after purge time over & oil lance retracted :-
start gas burner NO. 8, when ‘FLAME’ signal appears, increase gas press.
Kept Natural gas Contr. Valve ‘AUTO’
9. stop oil burner NO. 5, after purge time over & oil lace retracted :-
start gas burner NO. 5, when ‘FLAME’ signal appears, increase gas press.
repeat the steps for next all other burners.
10. when the oil control valve NN32G401 has reach 20% opening position,-
change the control valve from ‘AUTO’ to ‘MANUAL’ position.
11. stop the next oil burner, after purging time over & oil lance retracted:-.
start the gas burner
12. when last oil burner remain in service, -
close the oil control valve manually,
and keep one oil burner on oil start – up valve; -
and keep one oil burner on oil start – up valve; -
watch the gas press. , not more than 1.0 bar.
13. stop the last oil burner ;-
when purge time over and oil lance retracted , -
the firing is completely changed to gas firing.
14. change 1st the position of stand by oil pump , which in ‘AUTO’ to ‘ Manual’ selection,-
then stop the crude oil running pump.
15. open the oil return valve.
16. close the atomizing steam valve.
17. close the hand isolating oil valves before each burner.
24
CONDITIONS: -
I. The boiler pressure is approx. 40 bar
II. All unit auxiliaries still are in service
SOOT BLOWER 7 TO 10
NV53G1, NV54G1, NV55G1, NV56G1
Select soot blowers in LOCAL , now it is able to operate the system from Locally by ‘ON ‘ button
• during local operation it is not possible to open the drain valve from TCR.
• When last soot blower has been operated the main steam valve can be closed from TCR , close push
button.
• After close the manual hand isolating valve
b. TIME SETTINGS: -
Air purge time of Boiler Furnace & with min. air flow
160 sec. Remarks
Fuel Gas press. 200,000 N m3 / h
Ready for ignition period 10 mins.
Opening time of oil burner QCV 2 sec.
Opening time of gas burner QCV 1.5 , 2 sec
Purge time of gas burner QC v/v 30 sec.
Safety time gas burner 3 sec.
Safety time of oil burner 5 sec.
First stage burner oil purge 60 sec. Alarm Setting
2nd stage burner oil purge 90 sec.
Safety time photo Photocell 1 sec.
Closing time ( time ) QCV gas 1 sec.
Closing time QCV crude oil 1 sec.
Time delay NM21P01 3 sec.
Time delay NM22P01 3 sec.
Time delay NM16l03 ( Boiler Drum) 1 sec.
Time delay Fuel / Air ratio 10 sec.
33
A. - 7. : BOILER ALARMS & PROTECTIONS: -
a. FLOW MEASUREMENTS:
b. LEVEL MEASUREMENTS: -
HH = +320 mm Z = HH = +320 mm
NA16L03 Boiler drum level
LL = - 320 mm Z = LL = - 320 mm
H = + 100 mm
NA16 L01 Boiler drum level
L = - 100 mm
RH03 L01 HH =2940 mm Z = HH =2940 mm
RH03 L05 Feed water tank level LL = 700 mm Z = LL = 700 mm
RH03 L06 LL = 700 mm Z = LL = 700 mm
RH03 L07 LL = 700 mm Z = LL = 700 mm
H = 2800 mm
RH03 L08 Feed water tank level
L = 25OO MM
H = 13. 5 m. S = 10 m
RM33 L02 Cold cond. storage tank level
L = 10 , 0 m. Z = 1 , 0 m.
S = 1380 mm
RT01 L01 Waste drain basin level S = 1960 mm
Z = 2160 mm
RT01 L01 Grease switch 300 sec. time delay
H = 1800 mm
RU01 L01 Clean drain tank level
L = 1350 mm
RU01 L02 Clean drain tank level S = 1920 mm
RU01 L03 Clean drain tank level S = 1650 mm
RU01 L04 Clean drain tank level Z = 1420 mm
H = 1700 mm
VF10,30 & 50 L01 Service water Basin unit (1 - 2 )
L = 1100 mm Z = 900 mm
VF17, 37 & 57 L01 Service water elevated tank L L = 2900 mm
RZ16L01 Continuous blow down flash vessel- L H = 130 mm
34
c. PRESSURE MEASUREMENTS: -
e. TEMPERATURE MEASUREMENTS: -
1. Stop the pump and emergency push button pressed in or put in SWG position in TCR.
2. The 6.0 K.V. circuit breaker is racked out or in test position and the space heater MCB is switch off & tagged.
3. Discharge motorized valve and bypass manual valve are closed, 380 volt C.B. rack out and valves are chain
locked.
4. Suction manual valve closed and chain locked and strainer drain & vent valves are open.
5. Sealing water line valve to pump is closed.
6. Balancing line valve is closed and chain locked.
7. Minimum flow line valve is closed and chain locked.
8. AC / DC lube oil pumps are stopped and C.B's. are rack out or in SWG position in TCR, their EPB are pushed
in.
9. Open the pump body drain valve.
10. All instrument attachment to the pump are to be removed by IMD.
1. The Pump is stop and 6 K.V. C.B. is racked out and earthed.
2. AC / DC lube oil pump is off, E.P.B. is pushed in and put in SWG position in TCR.
3. Space heater MCB is switch off and tag.
4. Pump and motor to be decoupled by MMD
5. Lube oil line to motor to be removed by MMD.
6. All instrument attachment to motor to be removed by IMD.
1. Stop the fan and emergency push button is pressed in or put in SWG position in TCR.
2. 6.0 K.V. circuit breaker is racked out or in test position and the space heater MCB is switch off & tagged.
3. F.D. fan air damper and vane are in closed position and their 380 volts circuit breakers racked out.
1. Stop the fan and emergency push button pressed in or put in SWG position in TCR.
2. 380 volts circuit breaker is racked out or in test position and the space heater MCB switch is off & tagged.
1. Stop the pump and pressed in the emergency push button or put in SWG position in TCR.
2. 380 volts circuit breaker racked out or in test position and space heater MCB switch off & tag.
3. Suction and discharge manual valves are closed and chain locked.
4. Open the pump drain and vent.
1. The superheater attemperators spray water to be isolated is in by-pass position (by-pass valve is open).
2. Both isolating valves (inlet and outlet) are closed and chain locked.
3. The spray water control valve 380 volts motor circuit breaker is racked out or in test position.
4. Drain valve after the control valve must be opened.
1. Stop the pump and pressed in the emergency push button or put in SWG position in TCR.
2. Its 380 volts circuit breaker is racked out or in test position and the space heater MCB is switch off & tagged.
3. The Discharge manual valves is closed and chain locked.
O
1. Boiler is shut down, drained and vented. Boiler temperature is 50 C
2. All feedwater pumps are out of service. Isolated according to the above isolation procedure.
3. Both F.D. fans are out of service. Isolated according to the above isolation procedure.
4. LP Gas reducing stations 1 and 2 are out of service, isolated and purge by Nitrogen gas.
5. The cooling air fans are out of service and isolated according to procedure stated above.
6. Fuel oil pumps are out of service and isolated.
7. The H.P. steam valve and its by-pass are closed, chain locked and their motors C.B’s. are switch off.
8. The H.P. steam interconnection valve and its by-pass are closed, chain locked and their motors C.B’s. are
switch off.
9. F.W. interconnection valve and its by-pass are closed, chain locked and their motors C.B’s. are switch off.
10. Make-up water valve to feed water tank is closed, chain locked and their motors C.B’s. are switch off.
38
Process plants operate maximum days of the month to cover the overall costs. The remaining days of the
month operate to make profit. If the process is down for some days, then the company cannot cover the costs
and no profit has been made. So, respective persons must quickly and successfully solve any problems that
occur. Sometimes the problems occur during startup, sometimes just after a maintenance turn-around, and
sometimes unexpectedly during usual operation.
A trouble – shooting problem is one sometimes occurs that is unexpected to such an extent that it is perceived
that some corrective action may be needed. The trouble occurs somewhere in a system that consists of various
pieces of interacting equipment run by the people. The corrective action requires may be:
Now a days widely use and familiar with the word ‘trouble shooting’.
Trouble shooting is the process used to diagnose the fault safely & efficiently, decide on corrective action and
prevent the fault from reoccurring.
a) exhibit symptoms of deviations from the expected: the symptoms may suggest fault on the plant or they
might be caused by trouble upstream or downstream. The symptoms may be false and misleading
because they result from faulty instrument or incorrect sampling. These kinds of symptoms might not
reflect the real problem.
b) the tight time constraints related to safety and economics. The symptoms indicative of a potential
explosion or major leak in the system. We should initiate immediate shut-down and emergency
procedure.
c) The process configuration constrains a trouble shooter. The process is fabricated in a given way. The
valves, lines and instruments are in fixed locations. We may want to measure or sample, but no easy
way is available We have to work within the existing process system.
d) sometimes the cause of the problem is people. Someone may not have followed the expected
procedure and was unwilling to admit error. Someone may open the bypass valve in the belief that ‘the
process operates better that way’. The alarm may have turn OFF. The orifice plate may have been put
in backwards.
When emergencies arise, due to logical, physical or fault causes, analyze and identify the causes, decide on
the most applicable action, and proceed quickly. It is essential that an operator know the plant thoroughly to
handle emergencies. Proper knowledge of the plant not only will make it possible to act wisely but also will give
the operator the necessary confidence. Learn what constitutes safe practices and how they are applied to plant.
Do not shut down unless it is absolutely necessary, but do not hesitate to shut down rather than resort to unsafe
practices. When emergencies of this nature arise, quick and decisive action is important, and a through
knowledge of the plant and a pre-considered line of action are essential. Study the various means available
sources and utilize them in proper way.
“When any problem arises, it might be some causes and several solutions in our hand, which one perfect and
applicable it is depending on experience & broad knowledge regarding the subject.”
39
In the processing plant several problems & difficulties are arising, all of them are not possible to add due to our
limitation; only some of them difficulties and their causes show bellows: -
A. Oil firing
A summary of the difficulties that may encountered in operating oil fired plant are as follows:-
1. Failure of the oil to flow to the pumps due to inactive venting of the tank.
2. Clogged strainers caused by sludge deposits in the tank
3. Failure of pumps to operate due to air leaks in the suction line.
4. Vapor formation in the pump suction line as a result of too high temp. in tank.
5. Oil too heavy to flow to the pumps because of insufficient heating
6. Faulty atomizing caused by:
a. too low an oil temperature.
b. carbon formation on burner trips.
c. worn burner trips
d. too low oil pressure.
e. insufficient steam or air.
7. Smoke, poor combustion, and flames striking furnace walls caused by:
a. faulty atomization of oil.
b. incorrect adjustment of air supply.
c. automatic control not functioning properly.
8. Fire hazard and unsightly appearance caused by leaks in the pump discharge line.
D. Incase of more then one burner tripping, put muster control immediately on Hand Control.
Reduce load according to still available burner load.
On the other hand following conditions can produce steam temperature abnormally high:
a. dirty furnace
b. Too much excess air
c. Lower than design feed water temperature.
d. Irregular ignition or delayed combustion.
e. Poorly adjust control equipments.
If temperature exceeds maximum allowed value reduce burner load immediately.
G. Failure of the fuel supply: - low capacity, too much primary/ combustion air and disturbance from blowing
soot may result in loss of ignition when fuel is burned in suspension. If the equipment is supplied with a flame
detector the fuel feed will be shut off automatically.
H. Safety valve leak: - even pressure lower than for which it is set, try to free it by operating the lift levers. If this
fails to stop the leak, the valve must be repaired or replaced. Never attempt to stop a leaking safety valve by
blocking or fighting the spring.
I. Gauge glass breaks: -shut off the flow of steam and water. While the gauge glass is out of service, check the
water level by using the try cock. Before inserting the new gauge glass, blow out the connections to make sure
that no broken pieces remain in the fitting, and check the glass and gasket for the correct length and size. Pull
up the packing slowly and not to tightly to avoid breaking the glass. When the new glass is in position, open the
top or steam valve first and allow the drain valve to remain open. This permits steam to circulate through the
glass, gradually heating the entire surface to a uniform temperature. Then partly open the lower valve. After the
water has reached the normal level, open the lower valve. After the water has reached the normal level, open
both valves all the way. When the lower valve is first opened, the glass is subjected to a vibration in temperature
that may result in breakage.
41
BURNER NOT FIRE
Possible Causes:
Corrective Action:
Possible Causes:
Corrective Action:
Possible Causes:
Corrective Action:
Possible Causes:
Corrective Action:
Possible Causes:
Corrective Action:
1. Clean lines connecting float tank to water jacket on 9.5, 10 & 15 HP models.
2. Remove and clean pump intake strainer screen. Clean lines from water jacket to pump.
3. Repair or replace check valves.
4. Replace shaft seal and “O” ring in pump.
5. Adjust pump impeller.
6. With pump running, carefully loosen hex nut on angle check valve to bleed air from system. Tighten hex
nut when water starts escaping.
7. If vapor lock is caused by leaking check valves, replace check valves. If vapor lock is caused by too
high a temperature in the return tank, check all steam traps for proper operation and repair as required.
Possible Causes:
Corrective Action:
Possible Causes:
Corrective Action:
1. Clean burners.
2. Replace operating pressure switch.
3. De-scale boiler or replace plugged water tube assembly.
4. Remove soot from tubes by means of soot blowers.
5. Improper fuel air ration.
6. Fuel oil / gas caloric values are poor for improper combustion.
Possible Causes:
1. Gaskets deteriorated.
2. Fittings improperly aligned.
Corrective Action: