Sie sind auf Seite 1von 4

Lintel design

and detailing
Base lintel design on loading and aesthetics, but
always detail to prevent cracks and leaks

By Christine Beall

nlike arches, which carry masonry arches were invented, cor-

U
Figure 1. Corbeled arch created by natural
loads in compression, beled arches, vaults, and domes arching action of running bond masonry.
beams and lintels act as were used to span openings too 8 to 16 inches of masonry above the
flexural members spanning large for a single block of stone or top of the triangle.
horizontally between supports. length of timber. If arching action cannot be
Beams are primary supporting Lintels must be designed to carry assumed to occur because of inade-
members in a structure, but lintels their own weight, plus the weight quate height above the load trian-
usually are smaller members span- of the masonry inside the triangle gle, or because the masonry is not
ning and carrying only the loads formed by the line of arching laid in running bond, the lintel
immediately above window and action. This triangular area has must be sized to carry the full
door openings. Whether they’re sides at 45-degree angles to the lin- weight of the wall above it, includ-
made of steel, reinforced masonry, tel; therefore, its height is one-half ing that occurring outside the trian-
stone, concrete, or wood, lintels the span length (Figure 2). Outside gle. When arching action is
must resist compressive, bending, this area, the weight of the masonry assumed, the lintel requires tempo-
and shear stresses. and any uniform loads from the rary support until the mortar has
floor or roof above are assumed to cured enough to allow the masonry
Arching action be carried to the supporting abut- to bear its share of the load.
Masonry laid in running bond ments by natural arching. For this Arching action produces a hori-
creates a natural corbeled arch assumption to be true, however, the zontal thrust at each abutment
(Figure 1). In fact, before true arching action must be stabilized by

Figure 2. Arching action above a lintel determines area of load. Figure 3. Concentrated load distribution.
(Figure 2). The abutments, there-
fore, must have enough mass to
resist this force. If the opening is
near a corner or another opening,
or if a movement joint occurs at the
side of the opening, it also may be
necessary to size the lintel to carry
all of the loads above it, without
assuming any arching action in the
masonry.
Whether above or below the top
of the arching load triangle, con-
centrated loads are distributed as Figure 5. Reinforced brick lintels.
uniform loads along the base of a
triangle whose sides are at support a nominal 4-inch wythe of lintel sizes. Design tables also may
60-degree angles to the lintel masonry adequately. The bearing be used for concrete, precast con-
(Figure 3). length at each end of the lintel crete, natural stone, and cast stone
Once the total load on the lintel is should be at least 4 inches. lintels. Of course, simple engineer-
known, it can be sized to resist the Openings in concrete masonry ing analysis can be used in design-
calculated stresses. Deflection walls are spanned more commonly ing lintels of any material. Some
should be limited to 1/600 of the with U-shaped lintel blocks, rein- proprietary support systems also
span to avoid cracking the masonry. forced with deformed steel bars provide flexural strength for
and grouted. Standard brick also masonry lintels (see Masonry
Lintel types may be used to construct reinforced Construction, December 1991).
Structural steel shapes are com- masonry lintels, even though they Steel lintels should be hot-dip
monly used to span openings in do not have continuous channels galvanized for corrosion resistance.
brick masonry. Steel angles are the for horizontal steel. Reinforcement Field cuts and welds should be
simplest shapes and are suitable for can be added in bed joints or in a coated with a zinc-rich “galvaniz-
openings up to 8 feet wide, where widened and grouted collar joint ing” primer. Exposed surfaces also
superimposed loads are no more created by using half units (Fig. 5). may be painted but will then
than 5,000 pounds per lineal foot. Reinforced masonry lintels require periodic maintenance.
For wider openings or heavier should be the same width as the
wall they support, and should Accommodating movement
have a minimum bearing Building movement must be con-
length of one half the unit sidered in any type of construction,
length. Design aids have been and exterior walls are particularly
developed and published in subject to differential thermal,
technical notes by both the moisture, and structural move-
Brick Institute of America ments. Walls built of homogeneous
(BIA) (Refs. 1 and 2) and the materials generally experience less
National Concrete Masonry differential movement than those
Association (NCMA) (Refs. 3, combining dissimilar materials.
4, and 5). These can be used to Interior walls also experience less
select the appropriate amount movement than exterior walls
of reinforcing steel for brick or exposed to different thermal and
Figure 4. Steel lintels.
block lintels (see also “How to moisture environments on opposite
Design Reinforced Masonry sides.
Lintels,” Masonry Construction, Control joints in concrete mason-
loads, steel beams with suspended March 1991). ry and expansion joints in clay
plates can be used (Figure 4). Steel Steel and timber industry design masonry usually are recommended
angles should be a minimum of 1⁄4 manuals can be used to size lintels adjacent to windows and doors
inch thick. The horizontal leg of these materials. BIA Tech Note because walls are weakest at open-
should be at least 1⁄2 inches wide to 31B (Ref. 6) also contains design ings and therefore most vulnerable
tables for the most common steel to cracking from thermal and mois-
Figure 6. Lintel flashing details for single-wythe masonry.

ture movements. To be most effec- Thermal and moisture ing upward through every other
tive, movement joints should sepa- protection core.
rate the masonry carried by the lin- Since any opening in a wall is an A more complicated but better
tel from that in the adjacent wall. opportunity for a leak, moisture detail is shown in Figure 6B. Here,
This ordinarily means locating protection at lintels is critical. In the flashing course is constructed
them at the end of the lintel. walls constructed of single-wythe with two 4-inch units so that the
In multistory buildings, sills and concrete block or through-wall hol- flashing can be turned up between
lintels must be the same length in low brick, only a thin face shell and them and then folded back to the
order for the joints to align vertical- a correspondingly thin mortar joint opposite face shell. The back edge
ly. If sills and lintels are of unequal separate the interior of the wall of the flashing should be folded to
lengths, some alternative detailing from rain and wind. Moisture that Figure 7. Lintel flashing details for masonry
is needed to align movement joints penetrates the exterior face flows veneer walls.
with the opening and avoid an off- down through the open
set. cores of the units and
A piece of flashing placed under must be redirected back to
the lintel bearing area prevents the outside just as it is in
bond between the steel and the cavity walls.
masonry and allows slippage to Flashing should be
occur without cracking. A backer located above reinforced
rod or bond-breaker tape and masonry lintels as well as
sealant should be used in the joint steel lintels. In single-
at the front edge of the lintel wythe walls, there are sev-
because mortar at this location will eral ways to install flash-
crack and spall. ing. With standard units,
Alternatively, reinforced masonry metal throughwall flash-
lintels can be designed as continu- ing can be installed as
ous bond beams across several shown in Figure 6A. The
openings, allowing greater flexibili- back leg of the flashing is
ty in the location of movement turned up to prevent
joints away from the windows and water from flowing
doors. Even in 4-inch veneer walls toward the inside, and
carried on steel angle lintels, weep holes or cotton
installing joint reinforcement in the wicks can be used to drain
courses just above and below the moisture. If the first
opening can strengthen the wall course of units above the
section against movement cracks; lintel is laid with face-shell
this way, control and expansion bedding, the cotton wicks
joints can be placed in less notice- should be spaced at 16
able locations. inches on center, extend-
prevent moisture from flowing lintel flashing should extend behind
toward the inside. the sheathing or be lapped under-
Figure 6C shows the Flashing neath the building paper so that its
Block1™ design developed by top edge is not exposed (Figure 7B).
NCMA researchers, with integral Air and vapor movement also
weep hole slots and a reglet for the should be controlled, but the exact
back leg of the flashing. (Because location and installation of air barri-
this is a new design, check avail- ers and vapor retarders may vary
ability before specifying Flashing slightly depending on environmen-
Block™.) Single-wythe clay mason- tal conditions and type of construc-
ry walls can be similarly detailed, tion. Generally, however,
as can walls with one-piece precast foil-backed gypsum board is not
concrete or stone lintels. Unless adequate because the joints cannot
solidly grouted, single-wythe walls be sealed.
generally are more suitable in drier Flashing should be turned up at
climates. the end of lintels to form an end
Single-wythe walls insulated only dam, and all joints should be
with loose-fill perlite or vermiculite lapped and sealed. If stainless steel
will have a thermal bridge at the or copper flashing is used with gal-
flashing and lintel courses, where vanized steel lintels, the
the thermal resistance is lower than two metals must be isolated to
the rest of the wall. In climates prevent galvanic corrosion. A piece
where high thermal resistance is of 15-pound, asphalt-impregnated
required, or where condensation of roofing felt provides the required
moisture vapor may be a problem, separation.
higher performance is achieved
with continuous insulation located References
at the inside face of the wall. When 1. “Reinforced Brick Masonry, Flexural
Design,” BIA Technical Notes on Brick
required, vapor retarders should be Construction, Number 1 7A, Brick
located on the warm side of the Institute of America, 11490 Commerce
wall. Air barriers also may be Park Dr., Reston, VA 22091.
required in some instances to mini- 2. “Reinforced Brick and Tile Lintels,” BIA
Technical Notes on Brick Construction,
mize condensation. Number 17H, BIA.
Masonry cavity and veneer walls 3. “Concrete Masonry Lintels,”
require that flashing at lintels NCMA-TEK 25, National Concrete
extend from the exterior face of the Masonry Association, P.O. Box 781,
masonry across the cavity and into Herndon, VA 22070.
the backing wall. Where masonry 4. “Concrete Masonry Lintels,”
NCMA-TEK 25A, NCMA.
forms the backing wythe, the flash-
5. “Lintels for Concrete Masonry,” NCMA-
ing should be turned up and insert- TEK 81, NCMA.
ed into a mortar joint (Figure 7A). If 6. “Structural Steel Lintels,” BIA Technical
the window or door frame bridges Notes on Brick Construction, Number
the cavity, soft joints should allow 31B, BIA.
for any potential differential deflec- Christine Beall is an architect and consul-
tant in Austin, Texas, and a regular con-
tion or shortening of the two tributor to this magazine.
wythes. Air and vapor movement
also should be controlled carefully
to prevent heat loss or condensa-
tion. Insulation in the
wall cavity should continue
below as well as above the flashing
to reduce thermal bridging.
Where masonry veneers are con- PUBLICATION #M930106
structed with wood or metal stud Copyright 1993, The Aberdeen Group
backing walls, the back leg of the All rights reserved

Das könnte Ihnen auch gefallen