1) Which type of control system anticipates the load disturbances and takes control

before getting impacted?


Ans: - Feed forward control

2) A standard i/p convertor is given an input of 8ma.What would be the output?


a) 4ma----------- 3psi
8ma-------------- ? 8/4*3 = 6psi
Ans:- 6psi

3) Consider a PT100 RTD, what will be the resistance at 10 degree centigrade?


a) At zero degree centi PT100 will have a resistance of 100 ohms.
Rt= Ro( 1+ (alpha)(t)) . Rt= 101 ohms
Ans:- 101

4) The change in controller out[ut to the change in input of the controller is called?
A) gain

5) The following are the desirable charecterisitcs of a measurement system?


a) Fast response and fidelity
b) Fidelity and measurement lag
c) Fast response, dynamic error,measurement lag
d) Fast response and measurement lag

Ans:- C

6) Which contact is called “Fail Safe Contact”


a) Normally closed
b) Normally open
c) Semi open
d) None

Ans:- Normally closed

7) Small tank level has to be maintained at 50 cms. The pressure transmitter installed
to measure the tank level sends out the tank level to the control systems in terms
of pressure, which performs the calculation of comparing with the set point and
commands the valve to open or close. Consider the above process .Set point is
a) pressure
b) Liquid out flow
c) Level
d) 50cms
Ans:- Level

8) Consider the above process,Here the manipulated variable is ?


a) Liquid out flow
9) In a process the proportional gain is set too high value.What is the best possible
effect on the process variable?
a) large offset
b) stable loop
c) possible cycling
d) none
Ans:- possible cycling

10) Identify the logical operation..


A B X
0 0 0
0 1 1
1 0 1
1 1 0

Ans:- XOR

11) In a proportional integral controller , when the error is zero the controller output is
fixed at the value that the integral term had when the error went to zero.
a) true
b) false
c) depends on the Kp
d) none
Ans:- true.. because when error is zero the proportional and integral respsonses are
zero.Only the previous value remains.

12) Which type of controls is used in a application where noise is present but no offset
can be tolerated.
a) P only
b) PD
c) PI
d) PID

Ans:- PID

12) Ina aproportional control the gain is 1.5 and the process variable measured is 10%
above set point, the controller will signal the output to change by ………… % of
its full range.
A) Y1=Kp*Ep1… Y1=1.5*100=150
Y2= Kp* Ep2 …. Y2= 1.5* 110= 165. % change = (165-150)/ 150= 10%.
Ans : - 10%