A.

INPUT DATA
1.GROUND RESISTIVITY(OHM-M) 59.32
2.SURFACE RESISTIVITY(OHM-M) 3000
3.FAULT CURRENT(AMP) 65000
4.FAULT DURATION(SEC) 1
5.ZERO SEQUENCE CURRENT(AMP) 21666.67
6.SYSTEM GROWTH FACTOR 1
7. THICKNESS OF CONCCRETE/CRUSHED ROCK(M) 0
8.LENGTH OF AREA(M) 550
9.BREADTH OF AREA(M) 550
11. DEPTH OF BURIAL OF GROUND MAT(M) 0.6
12. LENGTH OF GROUND ROD(M) 3
13. NUMBER OF GROUND RODS 0

B.RESULTS AS PER IEEE80

1. REQUIRED MIN .CROSS SECTIONAL AREA OF CONDUCTOR(SQ.MM) 919.43


2. ADOPTED CROSS SECTION OF THE CONDUCTORS(SQMM0 1256.64
3. CALCULATED LENGTH OF GROUNDINDG CONDUCTORS(M) 69384.42
4.CALCULATED OPTIMUM SPACING BETWEEN THE CONDUCTORS(M) 8.86
5.TOLERABLE STEP POTENTIAL FOR A 50KG PERSON(V) 157.29
6.CALCULATED STEP POTENTIAL(V) 148.38
7.TOLERABLE MESH POTENTIAL FOR A 50KG PERSON (V) 126.32
8.CALCULATED MESH POTENTIAL(V) 126.28
9. CALCULATED GRID RESISTANCE(OHM) 0.05
10. ADOPTED SPACING OF CONDUCTORS(M) 8.00
11.REVISED TOTAL LENGTH(M) 76725.00
12, REVISED STEP POTENTIAL(V) 151.33
13. REVISED MESH POTENTIAL(V) 111.74
14, REVISED GROUND RESISTANCE(OHM) 0.05