DATA TRAFO T1

Merk : LEPPER DOMINIT


Type : SDOR 40000/170
Output on All Tap : 40000 KVA
Operation : Continuous
Serial No : 12185462
Year : 1979 IEC 76
Kind of Transf. : 3 phase Power Transformer
Fequency : 50 Hz
Cooling : ONAN
Total Weight : 77 Tons
Transport Weight : 50 Tons
Weight of Oil : 18.5 Tons
Core and Coil : 39 Tons
Volume of oil : 20500 Litres
Max.Ambient Temp : 35 o
Temp. Rise Oil/Winding : 60/65 K
Duration of Short Circuit : 3 Sec.
Vector Group : YNd5 BIL HV : 650 BIL LV : 95
On Load Tap Changer : Manufacture ASEA Type UZCRN 250/300
No Load Volt Full Load Amps
Tap No. HV LV HV LV Impendance
1 174.400 132 8,3
11/11A 155.000 11.800 149 1957 7,9
15 149,240 157 7,9
The tank is Designed to with stand 0,7 kp/cm
Internal Over Pressure And Full Vaccum
Year : 1979
Operated : 1982
OLTC ( ON-LOAD TAP CHANGER )
Merk : ASEA
Type : UZCRN 250 / 300
No. : 2254015
Tegangan : 150.000 –4+10x1940V, 3 phase, 50 Hz
Number of position : 15
Contac life : 500.000 operations
Motor – drive mechanism
Type : BUF – 2
Motor supply : 380 V, 3 phase, 50 Hz
Contactors : 220 V, 50 Hz
Position Transmitter : -
Heaating Element : 230 V
Nr. Of turn of the crank for each operation 23
Checking and Maintenance aft : 100.000 operations or at least every fifth year.
Inspection once a year.
DATA PMT TRAFO T1

Merk : ASEA
Type : HLR 170/2502.B2
No : 2250475
Order : L 8579.1928 -100
Voltage : 170 Kv
Insulation level : 750-325 Kv
Freqwensi : 50 Hz
Normal Current : 2500 A
Gas Pressure : 0,3 - 0,7 MPA
Mass.Incl.Oil : 3350 Kg
Mass of Oil : 270 Kg
Year of manufacture : 1979
Made in : ASEA SWEDEN
:
Operating device Type : BLG 352
No : 2250478
Order : L 8579.1928 -101

BREAKING CURRENT
Sys : 50 KA
Asyem : 58 KA
First - Pole - to clear factor : 1,5
Making Current : 125 KA
Short - time Current : 50 KA
Duration : 3S
Rules : IEC 56
Made in : ASEA SWEDEN

Das könnte Ihnen auch gefallen