Voltage Regulation at motor terminals -33 kV O/H line with DOG

conductor

Base kVA 3150

Transformer ratio ; TR1 6.6 34.5


Transformer ratio ; TR2 33 6.9

Base kV 6.6 34.5 7.214


Motor Intake Bus Voltage (kV) 6.6
Motor rating (kW) 510

pf 0.9
efficiency 0.92

runing kVA 615.9420


Load factor 0.9
Actual runing kVA 554.3478

Starting kVA (7.2 times) 4434.7826


Starting power factor (lag) 0.3

Lump load (kVA) 150


no of runing motor 2
runing kVA +lump load 1258.6957

Fault current (kA) 31.5


in amp 31500
Impedance calculation

=Base kVA / (√3*


1 Source impedance ;Zs
6.6*Fault current)

Zs p.u. 0.00875
Zs= 0.00874798796276856i
2 Cable impedance
km/ohm R= 0.06 ohm
km/ohm X= 0.093 ohm
Zc1 (km/ohm) R+jX
0.110675 ohm
Cable Length (km) 1
=Zc1*Base kVA /
Zc1 (p.u.) (1000*(Base kV)^2)
pu value 0.072314 pu
R= 0.004339
X= 0.006725
Zc1= 0.00433884297520661+0.00672520661157025i

3 Transformer
kVA 3150
% imp 6.25
pu value Zt1 0.062500 pu
0.0625i

4 OHL imp / km Assuming Resistance and


R (ohm)= 0.3412 Reactance of DOG conductor to
X (ohm)= 0.724 be 2 times that of PANTHER
condoctor
Z (ohm)= 0.3412+0.724i condoctor
Length (km) 15
FOR CONVERTING IN PU
MULTIPLICATION BY= 0.039697542533081
pu value Ztl R= 0.013544801512287 pu
X= 0.028741020793951
0.0135448015122873+0.0287410207939509i
Zctl(ABS.)= 0.0318
5 Transformer
kVA 3150
% imp 6.25
Base kV 7.214
0.057183
pu value Zt2 0.0571833648393195i pu

7 Cable impedance ; Zc2


km/ohm R= 0.06 ohm
km/ohm X= 0.093 ohm
(km/ohm) Z= 0.110675 ohm
Length (km) 0.15
=Zc1*Base kVA /
1000*(Base kV)^2
FOR CONVERTING IN PU
MULTIPLICATION BY= 0.009080 pu
R= 0.000544809373894
X= 0.000844454529536 Zs 6.6kV
Zc2 0.000544809373894461+0.000844454529536415i

8 Motor Cable impedance ; Zc3 Zc1


km/ohm R= 0.21 ohm
km/ohm X= 0.089 ohm
(km/ohm) Z= 0.228081 ohm
Length (km) 0.05 Zt1
=Zc1*Base kVA /
1000*(Base kV)^2
Zc3 0.000636
0.000269
0.000635610936210205+0.000269377968203373i
Zc3(ABS.)= 0.0007

Eq. imp up to 6.6kV intake Bus Ztl


Zpu=Zs+Zc1+ Zt1+ Ztl+Zt2+ Zc2
9 R= 0.01843 pu
X= 0.16474 pu
Z1= 0.0184284538613884+0.16474pu
Z1(ABS.)= 0.1658 pu Zt2

imp of runing motor+ lamp load multiplicatio


n factor to
change in
pu
10 2.09492848020489
Zc2
R= 1.8854 Zc3
X= 0.9132
Z= 1.8854356321844+0.913158153915835i 315
Z2 Zc2(ABS.)= 2.0949 R R S

multiplicatio
n factor to
change in
pu
11 imp of starting motor 0.710294117647059
R= 0.2131 pu
X= 0.6776 pu
Z= 0.213088235294118+0.677577 pu
Z3 Zc3(ABS.)= 0.7103 pu
Zpu 3
Equivalent imp of starting m/c with lump load
R= 0.2137 Zc3 3
X= 0.6778

Z1= 0.213723846230328+0.677846781327593i

Zc3+Z3 Z(ABS.)= 0.7107 3


Z2
Zeq=(Zc3+Z3) ll Z2 Req 0.191963764198838 Z3 3
Xeq 0.389050531373864
Zeq
0.191963764198838+0.389050531373864i
0.4338

Voltage at Motor terminal= 5.21931057769566

Voltage Drop= 20.92%