TECHNICAL EVALUATION SHEET-

HEAD SFU MCCB

Current setting knob for 60


to 100% of rated current.

QUALITY
Principle of Operation:-The Operating principle of circuit
breakers different from SFU.In conventional MCCB the mode
Principle of Operation:-The operation of an electric fuse of operation is twofolds,thermal for overload and
Based SFU Unit is based on intentionally inserting a weak electromagnetic for high currents. Higher Rating MCCB are
link into an electric circuit. In the event of an over-current this provided with Mircroprocessor based release for better fault
link will collapse first and thus protect the other circuit clearance
components.

Provides Protection for Over current,Earth fault &short circuit


and Single Phasing Protection when used for motoring
Provides protection for Over current Loads

Only current based discrimination is provided. Current and time discremination of Fault current is Possible

According to IEC 364, cables that are protected by fuse-links


have to be dimensioned on a 10 % higher current value than With Mccb the current rating can be set to a value which is
when protected by circuit breakers equal to maximum allowable current in the cable.

Double Insulation with Live parts and front parts from where
Live parts are protected by arclic sheet operation is carried complying to IEC

Positive isolation:- Operating Lever precisely indicate the


Physical Isolation is provided on the Removal of Fuses from position of contacts In compliance to IEC 60073 and IEC
both sides 60417-2
SAFETY

Pad lock can be provided on handle for Circuit isolation Pad lock can be provided on handle for Circuit isolation
during maintainence during maintainence

Low capital cost & initial cost. High Capital cost as compared to SFU .
MANAGEMENT

High Running cost as Fuses are required to be replaced


after interuption due to any electrical fault. MCCB can be reclosed again after clearing of electrical fault.

Due to thermal ageing in fuses may occur which influences


melting behaivour of Fuses in overload conditions. No such problems are faced in case of MCCB.