Sie sind auf Seite 1von 2

PW Cable Tray

TRAY SYSTEM NUMBER 4E03RS


RAIL CROSS SECTION
FLANGE
Aluminum A
1"

SIDE 4" RUNG


RAIL 5"

RUNG CROSS SECTION


1.00"

Legrand/Cablofil Classified by UL
[ [
0.97" trays marked with as equipment
CSA load class grounding
0.28" 0.28" have been tested conductors per
(loading, finish and NEC 392.7. (UL File
electrical) by UL to No. E60796)
CONNECTOR CSA standard
126 22.2 .

GENERAL INFORMATION ENGINEERING INFORMATION


TRAY WIDTH TRAY WEIGHT*
NEMA TRAY TYPE: Two Rail Ladder TRAY DESIGN: Construction and markings (IN.) (LBS./FT.)
are per the latest edition of NEMA
NEMA CLASS: 12B
Standards Pub. VE1, CSA C22.2 No. 126. 6 1.34
CSA CLASS: C
TRAY GROUNDING CAPABILITY: Classified
MATERIAL: Extruded aluminum as an equipment grounding conductor per 9 1.42
alloy 6063-T6 N.E.C. 392.7 with a maximum 1000 ampere
rating. UL Cross Sectional area: 0.60 in2 12 1.49
SIDE RAIL: 5" high with
1" top flange CONNECTORS: Supplied in pairs with 18 1.64
LOAD DEPTH: 4" hardware. Splice resistance is less than
0.00033 ohms. Standard hardware: 3/8 in. 24 1.79
BOTTOM: 1" wide box rung cadium plated with yellow zinc topcoat.
30 1.95
FINISH: Plain Stainless steel hardware is available upon
request. 36 2.10
CONSTRUCTION: Arc welded
MECHANICAL PROPERTIES:
TRAY SERIES: Series 1 (2" tangent) *Based on 9" rung spacing
One rail: I x-x = 1.6506in3 S x-x = 0.7076in4

SAFE LOAD DATA (LBS./FT.) / SUPPORT SPAN (FT.) / DEFLECTION (IN.)

6 8 10 12 14 16 18 20 22 24 26 28 30
300 0.27 169 0.47 108 0.74 75 1.06 53 1.39 39 1.75

CATALOG NUMBERING EXAMPLE: Legrand/Cablofil


09-4E03-0012-36 Phone 800-658-4641
618-566-3230
Width
06 – 6"
Fax 618-566-3250
Bottom Type Tray Length 09 – 9" 8319 State Route 4
06 – 6" Rung Spacing System 0010 – 10'-0" 12 – 12" Mascoutah, IL 62258 USA
09 – 9" Rung Spacing* 0012* – 12'-0" 18 – 18"
Number
12 – 12" Rung Spacing 0020 – 20'-0" 24 – 24"
18 – 18" Rung Spacing** 0024 – 24'-0" 30 – 30"
* Standard rung spacing * Standard 36 – 36" Publication Date: 3/10
for Series 1 Copyright © 2010 Legrand/Cablofil
** Not CUL Classified
PW Cable Tray
TRAY SYSTEM NUMBER 4E03VT
RAIL CROSS SECTION
FLANGE
Aluminum A
1"
5”
SIDE 4" RUNG
RAIL 5"

RUNG CROSS SECTION


1.00"

Legrand/Cablofil Classified by UL
[ [
0.97" trays marked with as equipment
CSA load class grounding
0.28" 0.28" have been tested conductors per
(loading, finish and NEC 392.7. (UL File
electrical) by UL to No. E60796)
CONNECTOR CSA standard
126 22.2 .

GENERAL INFORMATION ENGINEERING INFORMATION


TRAY WIDTH TRAY WEIGHT
NEMA TRAY TYPE: Ventilated/Trough TRAY DESIGN: Construction and markings (IN.) (LBS./FT.)
are per the latest edition of NEMA
NEMA CLASS: 12B
Standards Pub. VE1, CSA C22.2 No. 126. 6 1.50
CSA CLASS: C
TRAY GROUNDING CAPABILITY: Classified
MATERIAL: Extruded aluminum as an equipment grounding conductor per 9 1.65
alloy 6063-T6 N.E.C. 392.7 with a maximum 1000 ampere
rating. UL Cross Sectional area: 0.60 in2 12 1.80
SIDE RAIL: 5" high with
1" top flange CONNECTORS: Supplied in pairs with 18 2.10
LOAD DEPTH: 4" hardware. Splice resistance is less than
0.00033 ohms. Standard hardware: 3/8 in. 24 2.40
BOTTOM: 1" wide box rung cadmium-plated with yellow zinc topcoat.
30 2.71
FINISH: Plain Stainless steel hardware is available upon
request. 36 3.01
CONSTRUCTION: Arc welded
MECHANICAL PROPERTIES:
TRAY SERIES: Series 1 (2" tangent) One rail: I x-x = 1.6506in3 S x-x = 0.7076in4

SAFE LOAD DATA (LBS./FT.) / SUPPORT SPAN (FT.) / DEFLECTION (IN.)

6 8 10 12 14 16 18 20 22 24 26 28 30
300 0.27 169 0.47 108 0.74 75 1.06 53 1.39 39 1.75

CATALOG NUMBERING EXAMPLE: Legrand/Cablofil


VT-4E03-0012-36 Phone 800-658-4641
618-566-3230
Width
06 – 6"
Fax 618-566-3250
Bottom Type Tray Length 09 – 9" 8319 State Route 4
VT – Ventilated/Trough System 0010 – 10'-0" 12 – 12" Mascoutah, IL 62258 USA
0012* – 12'-0" 18 – 18"
Number
0020 – 20'-0" 24 – 24"
0024 – 24'-0" 30 – 30"
* Standard 36 – 36" Publication Date: 3/10
for Series 1 Copyright © 2010 Legrand/Cablofil

Das könnte Ihnen auch gefallen