Sie sind auf Seite 1von 1

2 3 4 5 6 7

NOTES

LINES PIPING SYMBOLS NOTES:- GENERAL


A

LINES IDENTIFICATION

PROCESS/UTILITY LINE
BASKET STRAINER
ELECTRICAL LINE GATE VALVE
B BURIED
INSTRUMENT GAS/ FLAME ARRESTOR
PNEUMATIC LINE 1. HIGH POINT VENT AND LOW POINT DRAIN NOT SHOWN ON P&ID SHALL BE SHOWN ON PIPING
GLOBE VALVE
ISOMETRIC / GENERAL ARRANGEMENT DRAWINGS .
ELECTRICAL TRACED LINE ANGLE VALVE
ST STEAM TRAP
2. ALL SAFETY VALVES DISCHARGE & EQUIPMENT DEPRESSURIZING LINES SHALL BE FREE DRAINING
CHECK VALVE
X X X CAPILLARY LINE ANGLE BALL VALVE TO VENT HEADER AND HAVE NO POCKETS UPTO AND INCLUDING HEADERS.

UNION
VENDOR LIMIT LINE
BUTTERFLY VALVE ANGLE CHOKE VALVE 3. ALL ISOLATION VALVES IN TAPPINGS OF INSTRUMENTS (SUCH AS PRESSURE, LEVEL AND FLOW

SWITCHES) CAUSING SHUTDOWN SHALL BE LOCKED OPEN.


CENTER LINE
INSULATION JOINT
PLUG VALVE ANGLE CONTROL VALVE 4. LINE NUMBERS SHALL BE INDICATED AS PER LINE LEGEND.
L L L L
HYDRAULIC LINE

5. ALL INSTRUMENTS SHALL BE PROVIDED WITH ISOLATION VALVES FOR MAINTENANCE PURPOSE.
FUTURE THREE WAY VALVE
B ADAPTER (TUBING PIPE) IT SHOULD BE ENSURED THAT THESE VALVES SHALL BE EASILY ACCESSIBLE.
BALL VALVE
o o o
SS TUBING (PROCESS)
THREE WAY CONTROL VALVE
NEEDLE VALVE 6. DRAINS OF LEVEL INSTRUMENTS (NON-SOUR SERVICES) SHALL BE PIPED TO NEAREST DECK
FLOW ELEMENT ORIFICE/
DRAIN FUNNEL WITH 1/2" TUBE PIPE.
SCOPE OF WORK/LINE RATING
RESTRICTION ORIFICE
CHANGE (WITH PIPING SPEC.
CONTINUOUS DRAIN
DESIGNATION) SPRING LOADED VALVE 7. FOR PUMPS HANDLING SWEET LIQUID, CASING VENTS, DRAINS AND BASE PLATE DRAINS SHALL
TURBINE METER
VANES CONTROL VALVE BE PIPED WITH VALVE TO NEAREST DECK DRAIN FUNNEL. CASING DRAINS AND VENT FOR

DIAPHRAGM VALVE PUMPS IN SOUR SERVICE SHALL BE PIPED TO CLOSED DRAIN HEADER RESPECTIVELY.

LOCALLY MOUNTED POSITIVE DISPLACEMENT METER HAND OPER. VANES VALVE


8. PROTECTION AGAINST GALVANIC CORROSION TO BE PROVIDED WHEREVER REQUIRED BETWEEN

CONTROL VALVE DISSIMILAR MATERIALS.


EXPANSION JOINT
LOCAL PURGED ROTAMETER
9. ALL VENT GAS PIPING SHALL BE FREE DRAINING WITH NO POCKETS.
SILENCER

JOHANUSMIRECFT
CONTROL VALVE WITH HAND WHEEL

PANEL MOUNTED / S 10. ALL LIQUID SAMPLE POINTS EXCEPT FOR WELL FLUID SAMPLES SHALL BE TAKEN FROM CENTER OF
SONIC METER OPEN DECK DRAIN
CENTRAL CONTROL PANEL THE PIPE. WELL FLUID SAMPLES SHALL BE TAKEN FROM VERTICAL PORTION OF THE PIPE. ALL GAS
SELF ACTUATED PCV (DOWN STREAM) (WITH LIQUID SEAL)
SAMPLES SHALL BE TAKEN FROM TOP OF THE PIPE.

C LOCAL,PANEL MOUNTED M ELECTRIC MOTOR S SAMPLE POINT


11. INSTRUMENT ISOLATION VALVES SHALL BE AS PER DETAILS GIVEN BELOW. ALL VALVES SHALL
SELF ACTUATED PCV (UP STREAM)
DIAPHRAGM SEAL BE AS PER APPROPRIATE PIPING/INST. SPECS. DIAPHRAGM SEAL ALSO AS PER SPECS. ALL TAKE

BACK PANEL MOUNTED PILOT TUBE OFF CONNECTIONS SHALL BE SW (SOCKET WELD) UNLESS OTHERWISE SPEIFIED.

HAND OPERATED VALVE RTU REMOTE TERMINAL UNIT


11.1
PI
BACK LOCAL PANEL VENTURI METER PI PI
INLET SIZE, INCHES 1/2" 1/2"
ORIFICE CODE LETTER INSTR. INSTR.
PISTON OPERATED VALVE 203 OUTLET SIZE, INCHES
24
PIPING 3/4" PIPING
SET PR, KG/CM2G 1-1/2"
COMPUTER FUNCTION DRAIN PLUGGED PSV
M 101

MOTOR OPERATED VALVE


(TYPICAL FOR PI,PT,PIC,PSH,PSL,PSHL)
COMPUTER LOCAL PANEL DRAIN FLANGED TAKE OFF CONNECTIONS- PIPING : 3/4", VESSELS : 1.5" FLANGED
ALL DIAPHRAGM SEAL TYPE INSTR. TO HAVE 1.5" FLANGED TAPPING.
SHUT DOWN VALVE RUPTURE DISC
11.2
DCS/DIDC STRAIGHTENING VANE (FLANGED)
INSTR. PIPING INSTR.
BALL CONTROL VALVE
SCRAPPER TEE/SPHERE REE

1/2"
FUNCTION BLOCK PI PI
D A ANALYSER

3/4"
*

3/4"
SP
SPECIALITY ITEM
INTERLOCK BUTTERFLY CONTROL VALVE
LO PI PI
3/4"
FILTER

1/2"
FLEXIBLE HOSE

1/2"
RUNNING LIGHT,LOCAL PILOT VALVE (XPV) 3/4"
LO
CAP (THREADED) RAIN CAP
SLOPE(DOWN WARD)
RUNNING LIGHT,PANEL 11.3

PIPING
INSTR.
HAMMER BLIND
BLIND FLANGE
I SHUT DOWN
RUNNING LIGHT,LOCAL PANEL 1/2"
SPECTACLE BLIND

CAP (WELDED)
FLANGE PDI
SOLENOID VALVE(2 WAY) LO/LC NORMALY LOCK OPEN INTERCHANGABLE TO LC PDI

REDUCER/EXPANDER MANIFOLD(PER SPECS.)


HOSE CONNECTION 1/2"
SOLENOID VALVE(3 WAY) LC/LO NORMALY LOCK CLOSE INTERCHANGABLE TO LO
N2 NITROGRN CATRIDGE
(TYPICAL FOR PDI,PDT,PDSH,PDSL,PDSHL)
E OFF/ON SKID OR SHOP FABRICATED
TAKE OF CONNECTION-PIPING : 3/4", VESSELS : 1.5" FLANGED
POSITIVE CHOKE
I SENIOR ORIFICE ESD/FSD VALVES

T-TYPE STRAINER

ADJUSTABLE CHOKE
NC NORMALY CLOSED
Y-TYPE STRAINER

CONTROL VALVE W/POSITIONER

NO NORMALLY OPEN
FUSIBLE PLUG

FOUR WAY VALVE

TS TEMPORARY STRAINER 0 28.02.06 ISSUED FOR BID RVG SG


QUICK EXHAUST VALVE
NO. DATE ISSUE BY CHD APPR.

OIL AND NATURAL GAS CORPORATION LTD.


VORTEX FLOW METER
OFFSHORE DESIGN SECTION, E & C DIVISION
F MR, MUMBAI

PIPING & INSTRUMENTATION DIAGRAM (P&ID)

FLOW SHEET & INSTRUMENT LEGEND

DEVELOPMENT OF C-SERIES STRUCTURE

DRAWING NO.- REV.


7045-OD-1002 0

S
JOHANUSMIRECFT