Sie sind auf Seite 1von 24

UL LISTED SHORT CIRCUIT RATINGS AND

IEC QUALIFIED SHORT CIRCUIT RATINGS


FOR FREEDOM NEMA, FREEDOM IEC AND
ADVANTAGE PRODUCTS

Published By:

J. K. Hastings
T. A. Wilsdon

CMS Name Approval Date Revision Date Revision No. Revision Control
465-1001 1/24/97 12/16/98 A This document must be modified through CMS.
UL LISTED SHORT CIRCUIT RATINGS AND
IEC QUALIFIED SHORT CIRCUIT RATINGS
FOR FREEDOM NEMA, FREEDOM IEC AND
ADVANTAGE PRODUCTS

(All statements made in this paper as to the UL listing of products with short
circuit levels and short circuit qualification to IEC are supported by UL files or
IEC test certificates.)

PURPOSE:
The purpose of this white paper is to present the short circuit qualifications for the Freedom and
Advantage product lines in a single document that can be used for marketing and sale of these
products worldwide. It is also intended to serve as a factual foundation for planning of tests at
higher levels as short circuit protection designs and starter designs advance.

IN BRIEF:

• The Freedom and Advantage product lines are fully listed to UL508. They meet and exceed
UL safety requirements.

• The Freedom and Advantage products have been tested with fuses and have passed the IEC
947-4-1 short circuit requirements for the mandatory “r” level currents and the optional “Iq”
level currents. IEC 947-4-1 TYPE 2 performance was observed and established.

• The Freedom and Advantage have been tested to IEC 947-4-1 TYPE 2 short circuit
requirements with the HMCP. Consult the attached chart to identify those protection devices
and starters that are qualified as TYPE 2 at the “r” and Iq short circuit levels.

• The Freedom and Advantage products are presently being tested with newly developed EF
style HMCP and thermal magnetic breaker designs. Look for these to be released in the near
future.

• Specified product ratings are shown in Table B, Pages 1 through 6.

• IEC makes no requirement for testing at 50 or 60 Hz. Results at either frequency qualify at the
other, however, certain customer sensitivities are recognized and some frequency-specific
testing is done on request.

BACKGROUND:

SHORT CIRCUIT TEST STANDARDS AND LEVELS

UL SHORT CIRCUIT TESTS

A UL listed starter must pass a “UL Standard short circuit” test. The test currents range from 5,000
amps to 85,000 amps depending on starter horsepower (kW). Fuses, HMCP, thermal mag
breakers can be used as the SCPD. A safe interruption is the criteria to pass. Damage to the
motor control components is allowed.

There are two levels of short circuit tests for UL listed products.

1. UL508 STANDARD SHORT CIRCUIT TESTS. THIS IS A MANDATORY TEST. Short circuit
currents levels are determined by UL508. (See Table A, Required Short Circuit Tests.)

2. UL508 HIGH FAULT TESTS. THIS IS AN OPTIONAL TEST. Short circuit current levels are
selected by the manufacturer.
IEC SHORT CIRCUIT TESTS

There are two levels of short circuit tests for products tested to IEC 947-4-1.

1. CONDITIONAL SHORT CIRCUIT CURRENT, “r”. THIS IS MANDATORY. Interruption levels


are defined in IEC 947-4-1. This is similar to the UL508 “Standard” short circuit test.

2. CONDITIONAL SHORT CIRCUIT CURRENT, “Iq”. THIS IS AN OPTIONAL TEST. Short


circuit current levels are selected by the manufacturer. This is similar to the UL508 “High
Fault” test.

DETERMINATION OF TYPE 1 OR TYPE 2 PERFORMANCE

Following the conditional short circuit tests at “r” and at “Iq”, the products are examined to
determine if the products meet TYPE 1 or TYPE 2 performance. TYPE 1 or TYPE 2 results can
be claimed at either “r”, or both r and Iq.

IEC 947-4-1 defines a TYPE 1 short circuit performance to be similar to UL508. It allows the
same level of damage to the control and requires the same level of personnel safety.

IEC 947-4-1 defines a TYPE 2 short circuit performance. It requires that the control components
will be serviceable after they experience a short circuit event.

UL defines the TYPE 2 performance in UL508 “Subject E” (not to be confused with Type E starters
or Design E motors). Requirements are equivalent to IEC 947-4-1 TYPE 2.

“SHORT CIRCUIT PROTECTION DEVICES” (SCPD).

Four types of product are used.

1. FUSES

Fuses are available in several designs providing interruption with no current limiting capability
up to high current limiting capability and high fault interruption capability. Fuses consume the
internal elements during the interruption and thereby can provide fast response and current
limiting sufficient to protect motor control components as well as the motor feed wires. The
TYPE 2 protection level described in the IEC 947-4-1 performance specification for starters
was first accomplished using current limiting fuses. Not all fuses provide TYPE 2
protection. Fuse and control manufacturers publish information on fuses in combination with
specified starters that are witnessed by UL for TYPE 2 protection.

2. THERMAL MAGNETIC BREAKERS

A thermal magnetic breaker provides a fixed magnetic trip that responds to peak currents and
a thermal or electronic simulation of an inverse current-time thermal trip behavior. The
magnetic trip is intended for short circuit levels above 16 times the breaker rating while the
thermal behavior protects below the magnetic trip level. Some interchangeable trip units are
available with adjustable magnetic trips between 10X and 5X the breaker rating. The thermal
mag breakers offer less TYPE 2 capability than HMCP, however, the breaker’s higher
magnetic trip levels offer better high efficiency motor starting capability.
3. HMCP

These are circuit breakers with an adjustable magnetic trip designed specifically for motor
circuits. They do not have a thermal trip mechanism. The thermal protection for the circuit
wires that is typically provided by the bimetal in the thermal magnetic breakers, is provided by
the thermal or electronic behavior of the overload relay. By NEC code, the wires serving a
motor will always have a higher current limit than the motor. The overload relay protects the
motor and therefore provides thermal protection for the feed wires. The magnetic trip level of
the HMCP is set at 13X the adjustable set point. HMCP can be adjusted to trip at lower peak
currents than the fixed magnetic trip found in thermal magnetic breakers. The HMCP can
provide short circuit protection at lower current levels. For these reasons HMCP can provide
better protection for motor circuits and can only be used in combination with a listed contactor
and overload relay. The HMCP has demonstrated a better capability in achieving the TYPE 2
performance than thermal magnetic breakers.

4. HYBRID

In UL508 the construction Type E starter product listed under combination motor controller
defines the hybrid. They combine a highly current limiting breaker structure with a manual
disconnecting mechanism, and overload relay. Some designs include a magnetic contactor.
They contain an adjustable thermal trip for motor overload protection and some models offer
an adjustable magnetic trip to meet the requirement written for the HMCP products. Products
listed by UL meet the minimum UL508E requirements. Some claim IEC 947-4-1 TYPE 2 at
specific voltages and currents. Short circuit levels are dependent on current rating. At low
current ratings the resistance of the heater is sufficiently high to limit the let through current to
a level that provides “intrinsic self protection”. These products are sensitive to the available
short circuit current, the system voltage, and the current rating.

REQUIRED SHORT CIRCUIT TESTS

TABLE A
IEC 947-4-1 SHORT CIRCUIT
UL 508 STANDARD SHORT CIRCUIT TEST LEVELS TEST LEVELS
STANDARD
SHORT AC3 CONDITIONAL
CIRCUIT CURRENT TEST
NEMA TEST RATING Ie IN CURRENT “r”
HP KW SIZE CURRENT AMPS IN AMPS

1 - 1.5 .7 - 1.1 NEMA 00 1,000 0 - 16 1,000


2 - 50 1.4 - 37.3 NEMA 3 5,000 16 - 63 3,000
51 - 200 39 - 149 NEMA 5 10,000 63 - 125 5,000
201 - 400 150 - 298 NEMA 6 18,000 125 - 315 10,000
401 - 600 299 - 447 NEMA 7 30,000 315 - 630 18,000
601 - 900 448 - 671 NEMA 8 42,000 630 - 1000 30,000
901 - 1600 672 - 1193 NEMA 9 85,000 1000 - 1600 42,000
1601-More 1194-More 100,000
125,000
150,000
200,000
FUSES UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM NEMA WITH C306 5,000A 5,000A 5,000A 5,000A 5,000A 10,000A 10,000A18,000 30,000A 42,000A 85,000A 600V
UL508 STANDARD SHORT 600V 600V 600V 600V 600V 600V 600V A 600V 600V
CIRCUIT 600V
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE TYPE 1 TYPE 1 TYPE 1
TYPE 2 1
IEC 947 REQUIRED SHORT 1000A 3000A 3000A 5000A 10,000A 10,000A 18,000A 18,000 30,000A 42,000A
CIRCUIT 600V 600V 600V 600V 600V 600V 600V A 600V 600V
CURRENT LEVEL "r" 600V
IEC 947 TYPE 1 OR TYPE 2 AT "r" TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE TYPE 1 TYPE 1
CURRENT 1
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200,300 450 550 700 700 860 1200
11 27 52
QUALIFIED AT UL STANDARD 5,000A 5,000A 5,000A 5,000A 10,000A 10,000A 10,000A 18,000 18,000A 30,000A 30,000A 30,000A 42,000A
SHORT CIRCUIT LEVEL 600V 600V 600V 600V 600V 600V 600V A 600V 600V 600V 600V 600V
600V
IEC 947 REQUIRED SHORT 1000 A 3000A 3000A 5000A 5000A 10,000A 10,000A 18,000 18,000A 30,000A 30,000A 30,000A 42,000A
CIRCUIT 600V 600V 600V 600V 600V 600V 600V A 600V 600V 600V 600V 600V
CURRENT LEVEL "r" 600V
IEC 947 TYPE 1 OR TYPE 2 AT "r" TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
CURRENT 1
CONTACTOR ONLY. IEC STARTERS ARE NOT
CATALOGED.
HMCP with C306 TEST LISTED SHORT-CIRCUIT CURRENT AND VOLTAGE LEVELS BY SIZE FOR BOTH NEMA & I.E.C. DEVICES
CERTIFICATE
OR UL FILE
NUMBER
FREEDOM NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9

UL508 STANDARD SHORT CMS460-1038 1,000A 5,000A 5,000A 5,000A 10,000 10,000 10,000 18,000 NO HMCP AVAILABLE ABOVE THIS
CIRCUIT E176513,VOL.. 480V 600V 600V 600V A 480V A 600V A 600V A 600V SIZE
LISTED BY VIRTUE OF 1 RPT.DATE:
PASSING THE HMCP HIGH 7/30/97
FAULT & STD TESTS ON
THERMAL-MAG BREAKERS
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
UL508 HIGH FAULT CURRENT E1491,VOL.3 100,000A 100,000 100,000 100,000 100,000 100,000A 100,000A 18,000A NO HMCP AVAILABLE ABOVE THIS
RPT.DATE: 480V A A A A 480V 480V 600V SIZE
480V 480V 480V 480V 25,000A 25,000A
6/19/75
25,000A 25,000A 25,000A 25,000A 600V 600V
600V 600V 600V 600V
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
FREEDOM IEC SIZE A, B, C,D E, F G, H, J K L, M N P, R, S T U V W X Z
AC3 Ie AT 480V 4.8, 7.8, 21, 27 34, 40, 65 86, 106 140 170,200 450 550 700 700 860 1200
11,14 52 ,300
UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1038 1000A 3000A 3000A 5000A 5000A 10,000A 10,000A 18,000A
REQUIRED STANDARD E176513,VOL.. 480V 480V 480V 480V 480V 480V 480V 480V
SHORT CIRCUIT CURRENT 1 RPT.DATE:
LEVEL "r" 7/30/97
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
TYPE 2 TYPE TYPE TYPE TYPE TYPE 2 TYPE 1 TYPE N/A N/A N/A N/A N/A
1 2 2 2 1
UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1038 100,000A 100,000 100,000 100,000 100,000 100,000A 100,000A 18,000A NO HMCP AVAILABLE ABOVE THIS
OPTIONAL SHORT CIRCUIT E176513,VOL.. 480V A A A A 480V 480V 600V SIZE
480V 480V 480V 480V 25,000A 25,000A
CURRENT LEVEL "Iq" 1 RPT.DATE:
25,000A 25,000A 25,000A 25,000A 600V 600V
7/30/97 600V 600V 600V 600V
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
TYPE 1
CMS460-1038 1,000A 3000A 5000A 25,000A 25,000A NO HMCP AVAILABLE ABOVE THIS
E176513,VOL.. 480V 480V 480V 480V 480V SIZE
1 RPT.DATE:
7/30/97
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
TYPE 2
HMCP with C316 TEST LISTED SHORT-CIRCUIT CURRENT AND VOLTAGE LEVELS BY SIZE FOR BOTH NEMA & I.E.C.
CERTIFICATE DEVICES
OR UL FILE
NUMBER
FREEDOM NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
UL508 STANDARD SHORT CMS460-1037 1,000A 5,000A 5,000A 5,000A 10,000 10,000A 10,000 18,000 NO HMCP AVAILABLE ABOVE THIS
CIRCUIT E176513,VOL.1 480V 600V 600V 600V A 480V 600V A 600V A 600V SIZE
LISTED BY VIRTUE OF RPT.DATE:
PASSING THE HMCP HIGH 7/30/97
FAULT & STD TESTS ON
THERMAL-MAG BREAKERS
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
UL508 HIGH FAULT CURRENT E1491,VOL. 3 100KA 100KA 100KA 100KA 100KA 18KA NO HMCP AVAILABLE ABOVE THIS
RPT.DATE: 25KA 25KA 480V 480V 480V 480V 480V 600V SIZE
6/19/75 600V 600V 25KA 25KA 25KA 25KA 25KA
600V 600V 600V 600V 600V
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
FREEDOM IEC SIZE A, B, E, F G, H, J K L, M N P, R, S T U V W X Z
C,D
AC3 Ie AT 480V 4.8, 7.8, 21, 27 34, 40, 65 86, 106 140 170,20 450 550 700 700 860 1200
11,14 52 0,300
UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1037 1,000A 3000A 3000A 5000A 5000A 10,000A 10,000 18,000 NO HMCP AVAILABLE ABOVE THIS
REQUIRED STANDARD SHORT E176513,VOL.1 480V 480V 480V 480V 480V 480V A A SIZE
CIRCUIT CURRENT LEVEL "r" RPT.DATE: 480V 480V
7/30/97
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
TYPE 1 TYPE TYPE TYPE TYPE TYPE 2 TYPE N/A
1 2 2 2 1
UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1037 25,000A 25,000 100,000 100,000 100,000 100,000A 100,00 18KA NO HMCP AVAILABLE ABOVE THIS
OPTIONAL SHORT CIRCUIT E176513,VOL.1 480V A A A A 480V 0A 600V SIZE
480V 480V 480V 480V 480V
CURRENT LEVEL "Iq" RPT.DATE:
7/30/97
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
TYPE 1
CMS460-1037 25,000A 25,000A 25,000A 25,000A NO HMCP AVAILABLE ABOVE THIS
E176513,VOL.1 480V 480V 480V 480V SIZE
RPT.DATE:
7/30/97
60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
TYPE 2
THERMAL-MAG BREAKERS UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM WITH C306 5,000A 5,000A 5,000A 5,000A 5,000A 10,000A 10,000A 18,000 30,000 42,000 85,000 A 600V
UL508 STANDARD SHORT 600V 600V 600V 600V 600V 600V 600V A 600V A 600V A 600V
CIRCUIT
UL508 SUBJECT E TYPE 1 OR TYPE1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
TYPE 2
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200,300 450 550 700 700 860 1200
11 27 52
QUALIFIED AT UL STANDARD 5,000A 5,000A 5,000A 5,000A 10,000A 10,000A 10,000A 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A
SHORT 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V
CIRCUIT LEVEL
IEC 947 REQUIRED SHORT 1000 A 3000A 3000A 5000A 5000A 10,000A 10,000A 18,000A 18,000A 30,000A 30,000A 30,000A 42000A
CIRCUIT 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V
CURRENT LEVEL "r"
IEC 947 TYPE 1 OR TYPE 2 AT "r" TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
CURRENT
CONTACTOR ONLY. IEC STARTERS ARE NOT
CATALOGED.
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200,300 450 550 700 700 860 1200
11 27 52
QUALIFIED AT UL STANDARD NOT NOT 5,000A 5,000A 10,000A 10,000A 10,000A 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A
SHORT LISTED LISTED 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V
CIRCUIT LEVEL
IEC 947 REQUIRED SHORT CIRCUIT 3000A 5000A 5000A 10,000A 10,000A 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A
CURRENT LEVEL "r" 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V
IEC 947 TYPE 1 OR TYPE 2 AT "r" TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
CURRENT
CONTACTOR ONLY. IEC STARTERS ARE NOT
CATALOGED.
HMCPS UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM WITH C306 5,000A 5,000A 5,000A 5,000A **
UL508 STANDARD SHORT 480V 480V 480V 480V
CIRCUIT *** NO HMCPS AVAILABLE ABOVE THIS CURRENT
UL508 SUBJECT E TYPE 1 OR TYPE 1 TYPE 1 TYPE 1 TYPE 1
TYPE 2
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200,300 450 550 700 700 860 1200
11 27 52
IEC 947 REQUIRED SHORT 1,000A 3,000A 3,000A 5,000A 5,000A 5,000A
CIRCUIT 480V 480V 480V 480V 480V 480V
CURRENT LEVEL "r" * NO HMCPS AVAILABLE ABOVE THIS CURRENT
IEC 947 TYPE 1 OR TYPE 2 AT "r" TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
CURRENT
* COMPLETION OF TYPE 2 CONFORMANCE TESTING IS PLANNED FOR APRIL, 1997.
** TESTING PLANNED FOR APRIL, 1997.
*** QUALIFIED BY VIRTUE OF PASSING THE 100,000A/480V HIGH FAULT TEST.
GMCP with C306 TEST LISTED SHORT-CIRCUIT CURRENT AND VOLTAGE LEVELS BY SIZE FOR BOTH NEMA & I.E.C. DEVICES
CERTIFICATE
OR UL FILE
NUMBER
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9

UL508 STANDARD SHORT CMS460-1036 1,000A 5,000A 5,000A 5,000A GMCP PRODUCT NOT AVAILABLE ABOVE THIS SIZE
CIRCUIT E176513,VOL. 480V 480V 480V 480V
LISTED BY VIRTUE OF 1
PASSING THE GMCP HIGH
FAULT
60Hz 60Hz 60Hz 60Hz
UL508 HIGH FAULT E176513,VOL. 42,000A 42,000 42,000 42,000A 480V
CURRENT 1 480V A 480V A 480V
60Hz 60Hz 60Hz 60Hz
FREEDOM IEC SIZE A, B, C,D E, F G, H, J K L, M N P, R, S T U V W X Z
AC3 Ie AT 480V 4.8, 7.8, 11,14 21, 27 34, 40, 65 86, 140 170,200, 450 550 700 700 860 1200
52 106 300
UL 508,sub E, (I.E.C. 947-4-1) CMS460-1036 1,000A 3,000A 3,000A 5,000A GMCP PRODUCT NOT AVAILABLE ABOVE
- REQUIRED STANDARD E176513,VOL. 480V 480V 480V 480V THIS SIZE
SHORT CIRCUIT CURRENT 1
LEVEL "r"
60Hz 60Hz 60Hz 60Hz
TYPE 2 TYPE 2 TYPE 2 TYPE 2
UL 508,sub E, (I.E.C. 947-4-1) CMS460-1036 42,000A 42,000 42,000 42,000A
- OPTIONAL SHORT CIRCUIT E176513,VOL. 480V A A 480V
CURRENT LEVEL "Iq" 1 480V 480V
60Hz 60Hz 60Hz 60Hz
TYPE 1
CMS460-1036 1,000A 3,000A 3,000A 5,000A
E176513,VOL. 480V 480V 480V 480V
1
60Hz 60Hz 60Hz 60Hz
TYPE 2
HMCPE UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM WITH C306 NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS
UL508 STANDARD SHORT TIME.
CIRCUIT
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200, 450 550 700 700 860 1200
11 27 52 300
QUALIFIED AT UL STANDARD SHORT NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS
CIRCUIT LEVEL AND IEC TIME.
CONDITIONAL "r" LEVEL
IEC 947 REQUIRED SHORT 1,000 3,000 3,000 5,000 10,000 10,000 18,000 18,000 30,000
CIRCUIT
CURRENT LEVEL "r"
IEC 947 TYPE 1 OR TYPE 2 AT "r" NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS
CURRENT TIME.
FUSES HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE.
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2
PERFORMANCE.
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM NEMA WITH C306 100KA 100KA 100KA 100KA 100KA 100KA 100KA 100KA 42KA 85KA 600V
UL508 HIGH FAULT CURRENT 600V 600V 600V 600V 600V 600V 600V 600V 600V
UL 508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 1 TYPE 1 TYPE TYPE
TYPE 2 1 1
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170, 200, 450 550 700 700 860 1200
11 27 52 300
Iq SHORT CIRCUIT 100KA 100KA 100KA 100KA 100KA 100KA 100KA 100KA 100KA 100KA 100KA 42KA
QUALIFICATION 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V
LEVEL
IEC 947 TYPE 1 OR TYPE 2 AT Iq TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 1 TYPE 1 TYPE TYPE TYPE TYPE 1
LEVEL 1 1 1
THERMAL-MAG BREAKERS HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE.
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2
PERFORMANCE.
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM NEMA WITH C306 SAME AS HMCP 18,000A 30,000A 42,000A 85,000A 600V
600V 600V 600V
UL508 HIGH FAULT CURRENT
UL508 SUBJECT E TYPE 1 OR UL LISTED BY ASSOCIATION WITH THE HMCP TESTS TYPE 1 TYPE 1 TYPE 1 TYPE 1
TYPE 2
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200,300 450 550 700 700 860 1200
11 27 52
Iq SHORT CIRCUIT SAME AS HMCP 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A
QUALIFICATION 600V 600V 600V 600V 600V 600V
LEVEL
IEC 947 TYPE 1 OR TYPE 2 AT Iq UL LISTED BY ASSOCIATION WITH THE HMCP TESTS TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
LEVEL
HMCPS HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE.
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2
PERFORMANCE.
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM NEMA WITH C306 100,000A 100,000 100,000 100,000
UL508 HIGH FAULT CURRENT 480V A A A
*
480V 480V 480V NO HMCPS AVAILABLE ABOVE THIS CURRENT
UL508 SUBJECT E TYPE 1 OR TYPE 1 TYPE 1 TYPE 1 TYPE 1
TYPE 2
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200, 450 550 700 700 860 1200
11 27 52 300
Iq SHORT CIRCUIT 100,000A 100,000 100,000 100,000
QUALIFICATION 480V A A A
*
LEVEL 480V 480V 480V NO HMCPS AVAILABLE ABOVE THIS CURRENT
IEC 947 TYPE 1 OR TYPE 2 AT Iq TYPE 1 TYPE 1 TYPE 1 TYPE 1
LEVEL

* HIGH FAULT TESTING AT 100,000A/480V TO BE COMPLETED IN APRIL, 1997.


HMCPE HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE.
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2
PERFORMANCE.
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
FREEDOM NEMA WITH C306 TESTING IS SUBJECT TO CONFIGURATION DECISION FOR
HMCPE, GMCP OR HMCPS. EXPLORATORY TESTING IS
UL508 HIGH FAULT CURRENT
PLANNED FOR 1997
UL508 SUBJECT E TYPE 1 OR
TYPE 2
FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N P, R, S T U V W X Z
C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200, 450 550 700 700 860 1200
11 27 52 300
Iq SHORT CIRCUIT TESTING IS SUBJECT TO CONFIGURATION DECISION FOR
QUALIFICATION LEVEL HMCPE, GMCP OR HMCPS. EXPLORATORY TESTING IS
PLANNED FOR 1997
IEC 947 TYPE 1 OR TYPE 2 AT Iq
LEVEL
FUSES UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 5,000A 5,000A 5,000A 10,000A 10,000A 18,000A
UL508 STANDARD SHORT SIZE 1L 5,000A 600V 600V 600V 600V 600V 600V
CIRCUIT # 600V NO ADVANTAGE
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 2 TYPE 2 TYPE 2 TYPE 2 AVAILABLE IN
IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A 3,000A 5,000A 10,000A 10,000A 18,000A THESE SIZES
CIRCUIT SIZE 1L 1,000A 600V 600V 600V 600V 600V 600V
CURRENT LEVEL "r" 600V
IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2

# Qualified Size 1 & 2 frame using 175A K5 fuse; Size 3 to 6 qualified by 3 cycle "ON" test.

HMCP UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 5,000A 5,000A 5,000A 10,000A 10,000A 18,000A
UL508 STANDARD SHORT SIZE 1L 5,000A 600V 600V 600V 600V 600V 600V
CIRCUIT * 600V NO ADVANTAGE
UL 508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 AVAILABLE IN
IEC 947 REQUIRED SHORT 10,000A 18000A THESE SIZES
CIRCUIT SEE HMCPS 480V 600V
CURRENT LEVEL "r"
IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 1

* Qualified Size 1 & 2 frame using 175A T/M breaker; Size 3 to 6 qualified by 3 cycle "ON" test.
THERMAL-MAG BREAKERS UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES
00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 5,000A 5,000A 5,000A 10,000A 10,000A 18,000A
UL508 STANDARD SHORT SIZE 1L 5,000A 600V 600V 600V 600V 600V 600V
CIRCUIT * 600V NO ADVANTAGE
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 AVAILABLE IN
IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A 3,000A 5,000A 10,000A 10,000A 18,000A THESE SIZES
CIRCUIT SIZE 1L 1,000A 600V 600V 600V 600V 600V 600V
CURRENT LEVEL "r" 600V
IEC 947 TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1

* Qualified Size 1 & 2 frame using 175A T/M breaker; Size 3 to 6 qualified by 3 cycle "ON" test.

HMCPS UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 5,000A 5,000A NO ADVANTAGE
UL508 STANDARD SHORT SIZE 1L 5,000A 600V 600V SEE HMCP AVAIL-ABLE IN THESE
CIRCUIT * 600V SIZES
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1
IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A 3,000A 5,000A ** ***
CIRCUIT SIZE 1L 1,000A 480V 480V 480V 5,000A 10,000A NO HMCPS AVAILABLE IN
CURRENT LEVEL "r" 480V 480V 480V THESE SIZES
IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2

* Qualified Size 1 & 2 frame using 175A T/M breaker; Size 3 to 6 qualified by 3 cycle "ON" test.
** Size 4 hp ratings 60hp max covered by 100A HMCPS.
*** Size 5 hp ratings up to and including 100hp covered by 150A HMCPS.
GMCP UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 5,000A 5,000A
UL508 STANDARD SHORT SIZE 1L 5,000A 480V 480V
CIRCUIT * 480V
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 NO GMCP AVAILABLE IN THESE SIZES
IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A 3,000A
CIRCUIT CURRENT LEVEL "r" SIZE 1L 1,000A 480V 480V
480V
IEC 947 TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1

* Qualified Size 1 & 2 frame using 175A T/M breaker.

HMCPE UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE


LEVELS BY SIZE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE
UL508 STANDARD SHORT
CIRCUIT
UL508 SUBJECT E TYPE 1 OR NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS TIME.
TYPE 2
IEC 947 REQUIRED SHORT
CIRCUIT CURRENT LEVEL "r"
IEC 947 TYPE 1 OR TYPE 2
FUSES HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2
PERFORMANCE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 100,000 100,000 100,000 100,000 100,000A 100,000
UL508 HIGH FAULT CURRENT SIZE 1L 100,000 A 600V A 600V A 600V A 600V 600V A 600V
A 600V NO ADVANTAGE
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 AVAILABLE IN
IEC 947 REQUIRED SHORT SEE SIZE 1L 100,000 100,000 100,000 100,000 100,000A 100,000 THESE SIZES
CIRCUIT SIZE 1L 100,000 A A A A 600V A
CURRENT LEVEL Iq A 600V 600V 600V 600V 600V
600V
IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2

HMCP HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2
PERFORMANCE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 100,000 100,000 100,000 100,000 100,000A 100,000
UL508 HIGH FAULT CURRENT SIZE 1L 100,000 A 480V A 480V A 480V A 480V 480V A 480V
A 480V 25,000A 25,000A 50,000A 50,000A 50,000A 50,000A
25,000A 600V 600V 600V 600V 600V 600V NO ADVANTAGE
600V AVAILABLE IN
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 THESE SIZES
IEC 947 REQUIRED SHORT 100,000A 18,000A
CIRCUIT CURRENT LEVEL Iq SEE HMCPS 480V 600V
IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 1
THERMAL-MAG BREAKERS HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2
PERFORMANCE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 100,000 100,000 100,000 100,000 100,000A 100,000
UL508 HIGH FAULT CURRENT SIZE 1L 100,000 A 480V A 480V A 480V A 480V 600V A 600V
A 480V 35,000A 35,000A 35,000A 50,000A
35,000A 600V 600V 600V 600V
600V NO ADVANTAGE
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 AVAILABLE IN
IEC 947 REQUIRED SHORT SEE SIZE 1L 100,000 100,000 100,000 100,000 100,000A 100,000 THESE SIZES
CIRCUIT SIZE 1L 100,000 A 480V A 480V A 480V A 480V 600V A
CURRENT LEVEL Iq A 480V 35,000A 35,000A 35,000A 50,000A 600V
35,000A 600V 600V 600V 600V
600V
IEC 947 TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1
HMCPS HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2
PERFORMANCE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 50,000A 50,000A
UL508 HIGH FAULT CURRENT SIZE 1L 50,000A 600V 600V SEE HMCP NO HMCPS AVAILABLE IN THESE SIZES
600V
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1
IEC 947 REQUIRED SHORT SEE SIZE 1L 100,000 100,000 100,000 100,000 100,000A
CIRCUIT SIZE 1L 100,000 A 480V A 480V A 480V A 480V * 480V ** NO HMCPS AVAILABLE IN
CURRENT LEVEL Iq A 480V THESE SIZES
IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2

* 100 AMP HMCPS MAX (60HP)


** 150 AMP HMCPS MAX (100HP)

GMCP HIGH FAULT UL 508 SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq AND TYPE 2
PERFORMANCE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE SEE SIZE 1L 25,000A 25,000A
UL508 HIGH FAULT CURRENT SIZE 1L 25,000A 480V 480V
480V
UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1
IEC 947 REQUIRED SHORT SEE SIZE 1L 25,000A 25,000A NO GMCP AVAILABLE IN THESE SIZES
CIRCUIT CURRENT LEVEL Iq SIZE 1L 25,000A 480V 480V
480V
IEC 947 TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1
HMCPE HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2
PERFORMANCE
QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2
PERFORMANCE
NEMA SIZES 00 0 1 2 3 4 5 6 7 8 9
ADVANTAGE
UL508 HIGH FAULT CURRENT
UL508 SUBJECT E TYPE 1 OR NO PRODUCT AVAILABLE
TYPE 2
IEC 947 REQUIRED SHORT
CIRCUIT CURRENT LEVEL Iq
IEC 947 TYPE 1 OR TYPE 2

Das könnte Ihnen auch gefallen