Beruflich Dokumente
Kultur Dokumente
Date: 13.03.2011
Operator: Vishveswar Dutt
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
Table of contents
Project 1
Project Cover 1
Table of contents 2
Luminaire parts list 3
Battery Room
Summary 4
MV Room
Summary 5
Transformer-1
Summary 6
Transformer-2
Summary 7
LV Swgr Room
Summary 8
Laydown Area
Summary 9
Control Room
Summary 10
Corridor
Summary 11
Kitchen
Summary 12
Pump Room
Summary 13
Page 2
Project 1
13.03.2011
Page 3
Project 1
13.03.2011
2.55 m
260 220
260
240 240
220
280 280
280 280
260
260 280 280
260 280
240 240
280 260
280
280 280 280
260
260
220
240 260 240
260
0.00
0.00 4.75 m
Height of Room: 5.200 m, Mounting Height: 4.500 m, Light loss factor: Values in Lux, Scale 1:34
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.266, Ceiling / Working Plane: 2.341.
Specific connected load: 23.78 W/m² = 9.46 W/m²/100 lx (Ground area: 12.11 m²)
Page 4
Project 1
13.03.2011
MV Room / Summary
240 17.00 m
300
180 14.18
300
240
300
360 240
360 360
300 360 360 360
300
240
240
0.00
0.00 5.79 10.85 m
Height of Room: 4.200 m, Mounting Height: 4.285 m, Light loss factor: Values in Lux, Scale 1:219
0.80
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.354, Ceiling / Working Plane: 0.184.
Specific connected load: 6.67 W/m² = 2.30 W/m²/100 lx (Ground area: 170.10 m²)
Page 5
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
Transformer-1 / Summary
5.35 m
220 220
200
240
200 240 240
260 260 260
220 220
240 260
240
200
0.00
0.00 4.80 m
Height of Room: 4.650 m, Mounting Height: 4.650 m, Light loss factor: Values in Lux, Scale 1:69
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.934, Ceiling / Working Plane: 0.603.
Specific connected load: 11.21 W/m² = 4.79 W/m²/100 lx (Ground area: 25.68 m²)
Page 6
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
Transformer-2 / Summary
5.30 m
220
240 240
240 260
220 260
240
240 260
260 240
260
240
220
240
260
260 260
220
240
200 240 200
220
0.00
0.00 4.80 m
Height of Room: 4.650 m, Mounting Height: 4.650 m, Light loss factor: Values in Lux, Scale 1:69
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.940, Ceiling / Working Plane: 0.606.
Specific connected load: 11.32 W/m² = 4.80 W/m²/100 lx (Ground area: 25.44 m²)
Page 7
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
11.80 m
250 250
200
300
250
250 350 350
300 350
350 350
250
250 350
350
350 300
350
250
250 350
350
350 300
300 250
200
250
0.00
0.00 6.60 m
Height of Room: 4.200 m, Mounting Height: 4.285 m, Light loss factor: Values in Lux, Scale 1:152
0.80
Specific connected load: 7.28 W/m² = 2.57 W/m²/100 lx (Ground area: 77.88 m²)
Page 8
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
160 19.00 m
180 180
200
200
200
220
220 220
220 220
220 220
200
200
180
180
160
160
0.00
0.00 5.30 m
Height of Room: 8.000 m, Mounting Height: 8.000 m, Light loss factor: Values in Lux, Scale 1:245
0.80
Specific connected load: 10.72 W/m² = 5.60 W/m²/100 lx (Ground area: 100.70 m²)
Page 9
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
5.00 m
350 280
280 350
420 420
420
350 420
490 490 350
490
490 420
490
490
420 490
490 420 350
490
490 490
420
420
350 420 420
350
350
0.00
0.00 6.60 m
Height of Room: 3.700 m, Mounting Height: 3.700 m, Light loss factor: Values in Lux, Scale 1:65
0.80
Specific connected load: 11.45 W/m² = 2.90 W/m²/100 lx (Ground area: 33.00 m²)
Page 10
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
Corridor / Summary
200 1.30 m
220 220
220
200 180
160 180 200 220 160
220 220
0.00
0.00 7.00 m
Height of Room: 3.700 m, Mounting Height: 3.800 m, Light loss factor: Values in Lux, Scale 1:51
0.80
Workplane:
Height: 0.760 m
Grid: 64 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.943, Ceiling / Working Plane: 0.448.
Specific connected load: 27.80 W/m² = 13.71 W/m²/100 lx (Ground area: 9.10 m²)
Page 11
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
Kitchen / Summary
330 1.85 m
270
270 300
300
330
330 360 360
360
360
360
360
300 360 330
330
360 300
300 330 360
360 360 360
330
330
0.00
0.00 3.81 m
Height of Room: 3.700 m, Mounting Height: 3.800 m, Light loss factor: Values in Lux, Scale 1:28
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.691, Ceiling / Working Plane: 0.282.
Specific connected load: 17.88 W/m² = 5.55 W/m²/100 lx (Ground area: 7.05 m²)
Page 12
Project 1
13.03.2011
Operator
Telephone
Fax
e-Mail
160 19.20 m
160 160 160
200
200 200
240 240 160
240 200 200 240
240
240 240 240 240 240
240 240 240
240 240
240
160 240 240 240 200
240 240 240
200 240 240 160
240 240 240
240
240 200
200 200 200
160
160 160 160 120
0.00
0.00 40.05 m
Height of Room: 12.000 m, Light loss factor: 0.80 Values in Lux, Scale 1:287
Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.432, Ceiling / Working Plane: 0.244.
Specific connected load: 5.02 W/m² = 2.63 W/m²/100 lx (Ground area: 768.96 m²)
Page 13