System overview (India / Jaipur)

-10°C... 70°C

String A Inverter
WAAREE 2 x Sunny Central SC 500MV-11
WS-230 Max. efficiency: 97.7 %
Module x String: European standard efficiency: 97.3 %
21 x 107 Max. AC power: 500.00 kVA
Inclination / Azimuth: Max. DC power (cos φ=1): 509.00 kW
25° / 0° Power factor (cos φ): 1.00

Technical data
Nominal power of PV-generator: 1033.62 kW Nominal power ratio: 98 %
Total number of modules: 4494 Yearly en. yield (approx.) *: 1744196.5 kWh
Total surface of PV-generator: 7505.0 m² Energy usability factor: 100.0 %
Number of inverters: 2 Performance Ratio (approx.) *: 82 %
Max. DC power (cos φ=1): 1018.00 kW Spec. energy yield (approx.) *: 1687 kWh/kWp
max. AC-Active power (cos φ=1): 1000.00 kW Cable losses (% in PV-Energy): Not considered
Inverter effectiveness: 97.1 %

Notes: Room for your comments

Signature '

* Important note: The calculation of the yield is based on estimated values and mathematical models. SMA is in no case liable for the real
yield, which can e.g. deviate due to contamination or different efficiencies of the modules.
V1.57