Sie sind auf Seite 1von 147

BASICS OF PROTECTION SYSTEMS

Important considerations when design protection system

Important considerations when design protection system.

1. Types of fault and abnormal Conditions to be protected against


2. Quantities available for measurement
3. Types of protection available
4. Speed
5. Fault position discrimination
6. Dependability / reliability
7. Security / stability
8. Overlap of protections
9. Phase discrimination / selectivity
10. CT’s and VT’s ratio required
11. Auxiliary supplies
12. Back-up protection
13. Cost
14. Duplication of protection
Types of protection
A - Fuses
For LV Systems, Distribution Feeders and Transformers, VT’s, Auxiliary
Supplies

B - Over current and earth fault


Widely used in All Power Systems
1. Non-Directional
2. Directional.

C - DIFFERENTIAL
For feeders, Bus-bars, Transformers, Generators etc
1. High Impedance
2. Low Impedance
3. Restricted E/F
4. Biased
5. Pilot Wire

D - Distance
For transmission and sub-transmission lines and distribution feeders, also used as back-up
protection for transformers and generators without signaling with signaling to provide unit
protection e.g.:
1. Time-stepped distance protection
2. Permissive underreach protection (PUP)
3. Permissive overreach protection (POP)
4. Unblocking overreach protection (UOP)
5. Blocking overreach protection (BOP)
6. Power swing blocking
7. Phase comparison for transmission lines
8. Directional comparison for transmission lines

E - Miscellaneous:
1. Under and over voltage
2. Under and over frequency
3. A special relay for generators, transformers, motors etc.
4. Control relays: auto-reclose, tap change control, etc.
5. tripping and auxiliary relays

Speed
Fast operation: minimizes damage and danger
Very fast operation: minimizes system instability discrimination and security can be costly to
achieve.
Examples:
1. differential protection
2. differential protection with digital signaling
3. distance protection with signaling
4. directional comparison with signaling

Fault position discrimination


Power system divided into protected zones must isolate only the faulty equipment or section

Dependability / reliability
Protection must operate when required to Failure to operate can be extremely damaging and
disruptive Faults are rare. Protection must operate even after years of inactivity Improved by
use of:
1. Back-up Protection and
2. duplicate Protection

Security / Stability
Protection must not operate when not required to e.g. due to:
1. Load Switching
2. Faults on other parts of the system
3. Recoverable Power Swings

Overlap of protections
1. No blind spots
2. Where possible use overlapping CTs
Phase discrimination / selectivity
Correct indication of phases involved in the fault Important for Single Phase Tripping and
auto-Reclosing applications

Current and voltage transformers


These are an essential part of the Protection Scheme. They must be suitably specified to meet
the requirements of the protective relays.
1A and 5A secondary current ratings, Saturation of current transformers during heavy fault
conditions should not exceed the limits laid down by the relay manufacturer.
Current transformers for fast operating protections must allow for any offset in the current
waveform. Output rating under fault conditions must allow for maximum transient offset. This
is a function of the system X/R ratio.
Current Transformer Standards/Classes:
British Standards: 10P, 5P, X
IEC: 10P, SP, TPX, TPY, TPZ
American: C, T.
Location of CTs should, if possible, provide for overlap of protections. Correct connection of
CTs to the protection is important. In particular for directional, distance, phase comparison and
differential protections. VT’s may be Electromagnetic or Capacitor types. Busbar VT’s:
Special consideration needed when used for Line Protection.

Auxiliary supplies

Required for:
1. Tripping circuit breakers
2. Closing circuit breakers
3. Protection and trip relays
• AC. auxiliary supplies are only used on LV and MV systems.
• DC. auxiliary supplies are more secure than ac supplies.
• Separately fused supplies used for each protection.
• Duplicate batteries are occasionally provided for extra security.
• Modern protection relays need a continuous auxiliary supply.
• During operation, they draw a large current which increases due to operation of
output elements.
Relays are given a rated auxiliary voltage and an operative auxiliary voltage range.
the rated value is marked on the relay. Refer to relay documentation for details of operative
range. it is important to make sure that the range of voltages which can appear at the relay
auxiliary supply terminals is within the operative range.
IEC recommended values (IEC 255-6):
Rated battery voltages:
12, 24, 48, 60, 11 0, 125, 220, 250, 440
Preferred operative range of relays:
80 to 10% of voltage rated
AC. component ripple in the dc supply:
<10% of voltage rated
COST
The cost of protection is equivalent to insurance policy against damage to plant, and loss of
supply and customer goodwill.
Acceptable cost is based on a balance of economics and technical factors. Cost of protection
should be balanced against the cost of potential hazards there is an economic limit on what can
be spent.

Minimum cost:
Must ensure that all faulty equipment is isolated by protection
Other factors:
1. Speed
2. Security/Stability
3. Sensitivity:
Degree of risk in allowing a low level fault to develop into a more severe fault
4. Reliability

Total cost should take account of:


1. Relays, schemes and associated panels and panel wiring
2. Setting studies
3. Commissioning
4. CT’s and VT’s
5. Maintenance and repairs to relays
6. Damage repair if protection fails to operate
7. Lost revenue if protection operates unnecessarily

Distribution systems
1. Large number of switching and distribution points, transformers and feeders.
2. Economics often overrides technical issues
3. Protection may be the minimum consistent with - statutory safety regulations
4. Speed less important than on transmission systems
5. Back-up protection can be simple and is often inherent in the main protection.
6. Although important, the consequences of maloperation or failure to operate are less
serious than for transmission systems.

Transmission systems
1. Emphasis is on technical considerations rather than economics
2. Economics cannot be ignored but is of secondary importance compared with the need
for highly reliable, fully discriminative high speed protection
3. Higher protection costs justifiable by high capital cost of power system elements
protected.
4. Risk of security of supply should be reduced to the lowest practical levels
5. High speed protection requires unit protection
6. Duplicate protections used to improve reliability
7. Single phase tripping and auto-reclose may be required to maintain system stability
Basic of protection system
Introduction
The purpose of an electrical power generation system is to distribute energy to a multiplicity of
points for diverse applications.
The system should be designed and managed to deliver this energy to the utilization points
with both reliability and economy.
As these two requirements are largely opposed, it is instructive to look at the relationship
between the reliability of a system and its cost and value to the consumer, which is shown in
Figure 1.

Figure 1 Relationship between reliability of supply,


its cost and value to the consumer.
It is important to realize that the system is viable only between the cross-over points A
and B. The diagram illustrates the significance of reliability in system design, and the necessity
of achieving sufficient reliability.
On the other hand, high reliability should not be pursued as an end in itself, regardless of cost,
but should rather be balanced against economy, taking all factors into account.
Security of supply can be bettered by improving plant design, increasing the spare capacity
margin and arranging alternative circuits to supply loads. Sub-division of the system into
zones, each controlled by switchgear in association with protective gear, provides flexibility
during normal operation and ensures a minimum of dislocation following a breakdown.
The greatest threat to a secure supply is the shunt fault or short circuit, which imposes a sudden
and sometimes violent change on system operation.
The large current which then flows, accompanied by the localized release of a considerable
quantity of energy, can cause fire at the fault location, and mechanical damage throughout the
system, particularly to machine and transformer windings. Rapid isolation of the fault by the
nearest switch-gear will minimize the damage and disruption caused to the system.

A power system represents a very large capital investment. To maximize the return on this
outlay, the system must be loaded as much as possible. For this reason it is necessary not only
to provide a supply of energy which is attractive to prospective users by operating the system
within the range AB (Figure 1.1), but also to keep the system in full operation as far as
possible continuously, so that it may give the best service to the consumer, and earn the most.
Revenue for the supply authority. Absolute freedom from failure of the plant and system
network cannot be guaranteed.
The risk of a fault occurring, however slight for each item, is multiplied by the number of such
items which are closely associated in an extensive system, as any fault produces repercussions
throughout the net-work. When the system is large, the chance of a fault occurring and the
disturbance that a fault would bring are both so great that without equipment to remove faults
the system will become, in practical terms, inoperable.
The object of the system will be defeated if adequate provision for fault clearance is not made.
Nor is the installation of switchgear alone sufficient; discriminative protective gear, designed
according to the characteristics and requirements of the power system, must be provided to
control the switchgear.
A system is not properly designed and managed if it is not adequately protected. This is the
measure of the importance of protective systems in modern practice and of the responsibility
vested in the protection engineer.

Fundamentals of protection practice

This is a collective term which covers all the equipment used for detecting, locating and
initiating the removal of a fault from the power system. Relays are extensively used for
major protective functions, But the term also covers direct-acting A.C. trips and fuses.

In addition to relays the term includes all accessories such as current and voltage
transformers, shunts, D.C. and A.C. wiring and any other devices relating to the protective
relays.

In general, the main switchgear, although fundamentally protective in its function,


is excluded from the term 'protective gear', as are also common services, such as the
station battery and any other equipment required to secure operation of the circuit breaker.

In order to fulfil the requirements of discriminative protection with the optimum


speed for the many different configurations, operating conditions and construction features
of power systems, it has been necessary to develop many types of relay which respond to
various functions of the power system quantities.

For example, observation simply of the magnitude of the fault current suffices in
some cases but measurement of power or impedance may be necessary in others. Relays
frequently measure complex functions of the system quantities, which are only readily
expressible by mathematical or graphical means.

In many cases it is not feasible to protect against all hazards with any one relay. Use
is then made of a combination of different types of relay which individually protect against
different risks. Each individual protective arrangement is known as a 'protection system';
while the whole coordinated combination of relays is called a 'protection scheme'.
Reliability
The need for a high degree of reliability is discussed in Section 1. Incorrect operation can
be attributed to one of the following classifications:

a. Incorrect design.
b. Incorrect installation.
c. Deterioration.
d. Protection performance

1. Design
This is of the highest importance. The nature of the power system condition which is being
guarded against must be thoroughly understood in order to make an adequate design.
Comprehensive testing is just as important, and this testing should cover all aspects of the
protection, as well as reproducing operational and environmental conditions as closely as
possible. For many protective systems, it is necessary to test the complete assembly of
relays, current transformers and other ancillary items, and the tests must simulate fault
conditions realistically.

2. Installation.
The need for correct installation of protective equipment is obvious, but the complexity
of the interconnections of many systems and their relation-ship to the remainder of the
station may make.

Difficult the checking of such correctness. Testing is therefore necessary; since it


will be difficult to reproduce all fault conditions correctly, these tests must be directed to
proving the installation. This is the function of site testing, which should be limited to such
simple and direct tests as will prove the correctness of the connections and freedom from
damage of the equipment.

No attempt should be made to 'type test' the equipment or to establish complex


aspects of its technical performance;

3. Deterioration in service.
After a piece of equipment has been installed in perfect condition, deterioration may take
place which, in time, could interfere with correct functioning. For example, contacts may
become rough or burnt owing to frequent operation, or tarnished owing to atmospheric
contamination; coils and other circuits may be open-circuited, auxiliary components may
fail, and mechanical parts may become clogged with dirt or corroded to an extent that may
interfere with movement.

One of the particular difficulties of protective relays is that the time between
operations may be measured in years, during which period defects may have developed
unnoticed until revealed by the failure of the protection to respond to a power system
fault. For this reason, relays should be given simple basic tests at suitable intervals in
order to check that their ability to operate has not deteriorated.
Testing should be carried out without disturbing permanent connections. This can
be achieved by the provision of test blocks or switches.
Draw-out relays inherently provide this facility; a test plug can be inserted between
the relay and case contacts giving access to all relay input circuits for injection. When
temporary disconnection of panel wiring is necessary, mistakes in correct restoration of
connections can be avoided by using identity tags on leads and terminals, clip-on leads for
injection supplies, and easily visible double-ended clip-on leads where 'jumper
connections' are required.
The quality of testing personnel is an essential feature when assessing reliability
and considering means for improvement. Staff must be technically competent and
adequately trained, as well as self-disciplined to proceed in a deliberate manner, in which
each step taken and quantity measured is checked before final acceptance.
Important circuits which are especially vulnerable can be provided with continuous
electrical super-vision; such arrangements are commonly applied to circuit breaker trip
circuits and to pilot circuits.

4. Protection performance
The performance of the protection applied to large power systems is frequently assessed
numerically. For this purpose each system fault is classed as an incident and those which
are cleared by the tripping of the correct circuit breakers and only those are classed as
'correct'.
The percentage of correct clearances can then be determined.
This principle of assessment gives an accurate evaluation of the protection of the system
as a whole, but it is severe in its judgment of relay performance, in that many relays are
called into operation for each system fault, and all must behave correctly for a correct
clearance to be recorded.

On this basis, a performance of 94 % is obtainable by standard techniques.


Complete reliability is unlikely ever to be achieved by further improvements in
construction. A very big step, however, can be taken by providing duplication of
equipment or 'redundancy'. Two complete sets of equipment are provided, and arranged so
that either by itself can carry out the required function. If the risk of an equipment failing is
x/unit, the resultant risk, allowing for redundancy, is x2. Where x is small the resultant risk
(x2) may be negligible.
It has long been the practice to apply duplicate protective systems to bus-bars, both
being required to operate to complete a tripping operation, that is, a 'two-out-of-two'
arrangement. In other cases, important circuits have been provided with duplicate main
protection schemes, either being able to trip independently, that is, a 'one-out-of-two'
arrangement. The former arrangement guards against unwanted operation, the latter
against failure to operate.
These two features can be obtained together by adopting a 'two-out-of-three'
arrangement in which three basic systems are used and are interconnected so that the
operation of any two will complete the tripping function.

Such schemes have already been used to a limited extent and application of the
principle will undoubtedly increase. Probability theory suggests that if a power network
were protected throughout on this basis, a protection performance of 99.98 % should be
attainable.

This performance figure requires that the separate protection systems be completely
independent; any common factors, such as, for instance, common current transformers or
tripping batteries, will reduce the overall performance to a certain extent.

Selectivity.
Protection is arranged in zones, which should cover the power system completely, leaving
no part unprotected. When a fault occurs the protection is required to select and trip only
the nearest circuit breakers. This property of selective tripping is also called
'discrimination' and is achieved by two general methods:

1. Time graded systems.

Protective systems in successive zones are arranged to operate in times which are graded
through the sequence of equipments so that upon the occurrence of a fault, although a
number of protective equipments respond, only those relevant to the faulty zone complete
the tripping function. The others make incomplete operations and then reset.

2. Unit systems.
It is possible to design protective systems which respond only to fault conditions lying
within a clearly defined zone. This 'unit protection' or 'restricted Protection' can be applied
throughout a power system and, since it does not involve time grading, can be relatively
fast in operation.

Unit protection is usually achieved by means of a comparison of quantities at the


boundaries of the zone. Certain protective systems derive their 'restricted' property from
the configuration of the power system and may also be classed as unit protection.
Whichever method is used, it must be kept in mind that selectivity is not merely a
matter of relay design.
It is a function of the correct co-ordination of current transformers and relays with a
suitable choice of relay settings, taking into account the possible range of such variables
as fault currents, maximum load current, system impedances and so on, where appropriate.

Zones of protection
Ideally, the zones of protection should overlap across the circuit breaker as shown in
Figure 2, the circuit breaker being included in both zones.
Figure 2. Location of current
transformers
on both sides of the circuit breaker.

For practical physical reasons, this ideal is not always achieved, accommodation for
current trans-formers being in some cases available only on one side of the circuit
breakers, as in Figure 3. This leaves a section between the current transformers and the
circuit breaker A within which a fault is not cleared by the operation of the protection that
responds. In Figure 3 a fault at F would cause the bus-bar protection to operate and open
the circuit breaker but the fault would continue to be fed through the feeder.
Figure 3 Location of current
transformers
on circuit side of the
circuit breaker.

The feeder protection, if of the unit type, would not operate, since the fault is
outside its zone. This problem is dealt. With by some form of zone extension, to operate
when opening the circuit breaker does not fully interrupt the flow of fault current. A time
delay is incurred in fault clearance, although by restricting this operation to occasions
when the bus-bar protection is operated the time delay can be reduced.

Figure 4 Overlapping zones of protection systems.

The point of connection of the protection with the power system usually defines the zone
and corresponds to the location of the current transformers. The protection may be of the
unit type, in which case the boundary will be a clearly defined and closed loop. Figure 4
illustrates a typical arrangement of overlapping zones.

Alternatively, the zone may be unrestricted; the start will be defined but the extent will
depend on measurement of the system quantities and will therefore be subject to variation,
owing to changes in system conditions and measurement errors.

Stability.

This term, applied to protection as distinct from power networks, refers to the ability of the
system to remain inert to all load conditions and faults external to the relevant zone. It is
essentially a term which is applicable to unit systems; the term 'discrimination' is the
equivalent expression applicable to non-unit systems.

Speed.
The function of automatic protection is to isolate faults from the power system in a very
much shorter time than could be achieved manually, even with a great deal of personal
supervision. The object is to safeguard continuity of supply by removing each disturbance
before it leads to widespread loss of synchronism, which would necessitate the shutting
down of plant.
Loading the system produces phase displacements between the voltages at different
points and therefore increases the probability that synchronism will be lost when the
system is disturbed by a fault. The shorter the time a fault is allowed to remain in the
system, the greater can be the loading of the system. Figure 1.5 shows typical relations
between system loading and fault clearance times for various types of fault.

It will be noted that phase faults have a more marked effect on the stability of the
system than does a simple earth fault and therefore require faster clearance.

It is not enough to maintain stability; unnecessary consequential damage must also


be avoided. The destructive power of a fault arc carrying a high current is very great; it can
burn through copper conductors or weld together core laminations in a transformer or
machine in a very short time. Even away from the fault arc itself, heavy fault currents can
cause damage to plant if they continue for more than a few seconds

Figure 5 Typical values of power that can be


transmitted as a function of fault clearance time.

It will be seen that protective gear must operate as quickly as possible; speed, however,
must be weighed against economy.

For this reason, distribution circuits for which the requirements for fast operation
are not very severe are usually protected by time-graded systems, but generating plant and
EHV systems require protective gear of the highest attainable speed; the only limiting
factor will be the necessity for correct operation.
Sensitivity
Sensitivity is a term frequently used when referring to the minimum operating current of a
complete protective system. A protective system is said to be sensitive if the primary
operating current is low.
When the term is applied to an individual relay, it does not refer to a current or
voltage setting but to the volt-ampere consumption at the minimum operating current.
A given type of relay element can usually be wound for a wide range of setting
currents; the coil will have an impedance which is inversely proportional to the square of
the setting current value, so that the volt-ampere product at any setting is constant.
This is the true measure of the input requirements of the relay, and so also of the
sensitivity. Relay power factor has some significance in the matter of transient
performance.
For D.C. relays the VA input also represents power consumption, and the burden is
therefore frequently quoted in watts.

Primary and back-up protection

The reliability of a power system has been discussed in earlier sections. Many factors may
cause protection failure and there is always some possibility of a circuit breaker failure.
For this reason, it is usual to supplement primary protection with other systems to 'back-
up' the operation of the main system and ensure that nothing can prevent the clearance of a
fault from the system.

Back-up protection may be obtained automatically as an inherent feature of the


main protection scheme, or separately by means of additional equipment.
Time graded schemes such as over current or distance protection schemes are
examples of those providing inherent back-up protection; the faulty section is normally
isolated discriminatively by the time grading, but if the appropriate relay fails or the
circuit breaker fails to trip, the next relay in the grading sequence will complete its
operation and trip the associated circuit breaker, thereby interrupting the fault circuit one
section further back. In this way complete back-up cover is obtained; one more section is
isolated than is desirable but this is inevitable in the event of the failure of a circuit
breaker.
Where the system interconnection is more complex, the above operation will be
repeated so that all parallel infeeds are tripped.

If the power system is protected mainly by unit schemes, automatic back-up protection is
not obtained, and it is then normal to supplement the main protection with time graded
over current protection, which will provide local back-up cover if the main protective
relays have failed, and will trip further back in the event of circuit breaker failure.
Such back-up protection is inherently slower than the main protection and,
depending on the power system configuration, may be less discriminative. For the most
important circuits the performance may not be good enough, even as a back-up protection,
or, in some cases, not even possible, owing to the effect of multiple infeeds. In these cases
duplicate high speed protective systems may be installed. These provide excellent mutual
back-up cover against failure of the protective equipment, but either no remote back-up
protection against circuit breaker failure or, at best, time delayed cover.

Breaker fail protection can be obtained by checking that fault current ceases within
a brief time interval from the operation of the main protection. If this does not occur, all
other connections to the bus bar section are interrupted, the condition being necessarily
treated as a bus bar fault. This provides the required back-up protection with the minimum
of time delay, and confines the tripping operation to the one station, as compared with the
alternative of tripping the remote ends of all the relevant circuits.
The extent and type of back-up protection which is applied will naturally be related
to the failure risks and relative economic importance of the system. For distribution
systems where fault clearance

Times are not critical, time delayed remote back-up protection is adequate but for
EHV systems, where system stability is at risk unless a fault is cleared quickly, local back-
up, as described above, should be chosen.

Ideal back-up protection would be completely independent of the main protection.


Current trans-formers, voltage transformers, auxiliary tripping relays, trip coils and D.C.
supplies would be duplicated. This ideal is rarely attained in practice. The following
compromises are typical:
a. Separate current transformers (cores and secondary windings only) are used
for each protective system, as this involves little extra cost or accommodation
compared with the use of common current transformers which would have to be
larger because of the combined burden.
b. Common voltage transformers are used because duplication would involve a
considerable increase in cost, because of the voltage transformers them-selves,
and also because of the increased accommodation which would have to be
provided. Since security of the VT output is vital, it is desirable that the supply
to each protection should be separately fused and also continuously supervised
by a relay which will give an alarm on failure of the supply and, where
appropriate, prevent an unwanted operation of the protection.
c. Trip supplies to the two protections should be separately fused. Duplication of
tripping batteries and of tripping coils on circuit breakers is sometimes
provided. Trip circuits should be continuously supervised.
d. It is desirable that the main and back-up protections (or duplicate main
protections) should operate on different principles, so that unusual events that
may cause failure of the one will be less likely to affect the other.

Definitions and Terminology

1.All-or-nothingrelay
A relay which is not designed to have any specified accuracy as to its operating value.

2. Auxiliaryrelay.
An all-or-nothing relay used to supplement the performance of another relay, by modifying
contact performance for example, or by introducing time delays.

3.Back-upprotection.
A protective system intended to supplement the main protection in case the latter should be
in-effective, or to deal with faults in those parts of the power system that are not readily
included in the operating zones of the main protection.

4.Biasedrelay.
A relay in which the characteristics are modified by the introduction of some quantity other
than the actuating quantity, and which is usually in opposition to the actuating quantity.

5.Burden.
The loading imposed by the circuits of the relay on the energizing power source or sources,
expressed as the product of voltage and current (volt-amperes, or watts if D.C) for a given
condition, which may be either at 'setting' or at rated current or voltage.

The rated output of measuring transformers, expressed in VA, is always at rated current or
voltage and it is important, in assessing the burden imposed by a relay, to ensure that the
value of burden at rated current is used.

6. Characteristic angle.
The phase angle at which the performance of the relay is declared. It is usually the angle at
which maximum sensitivity occurs.

7. Characteristic curve.
The curve showing the operating value of the characteristic quantity corresponding to various
values or combinations of the energizing quantities.

8. Characteristic quantity.
A quantity, the value of which characterizes the operation of the relay, e.g. current for an
over current relay, voltage for a voltage relay, phase angle for a directional relay, time for an
independent time delay relay, impedance for an impedance relay.

9. Characteristic impedance ratio (C.I. R.)


The maximum value of the System Impedance Ratio up to which the relay performance
remains within the prescribed limits of accuracy.

10. Check protective system.


An auxiliary protective system intended to prevent tripping due to inadvertent operation of
the main protective system.

11. Conjunctive test.


A test on a protective system including all relevant components and ancillary equipment
appropriately interconnected. The test may be parametric or specific.
a. Parametric conjunctive test.
A test to ascertain the range of values that may be assigned to each parameter when considered
in combination with other parameters, while still complying with the relevant performance
requirements.

b. Specific conjunctive test.


A test to prove the performance for a particular application, for which definite values are
assigned to each of the parameters.

12. Dependent time delay relay.


A time delay relay in which the time delay varies with the value of the energizing quantity.

13. Discrimination.
The quality whereby a protective system distinguishes between those conditions for which it
is intended to operate and those for which it shall not operate.

14. Drop-out.
A relay drops out when it moves from the energized position to the un-energized position.

15. Drop-out / pick ratio.


The ratio of the limiting values of the characteristic quantity at which the relay resets and
operates. This value is sometimes called the differential of the relay.

16. Earth fault protective system.


A protective system which is designed to respond only to faults to earth.

17. Earthing transformer.


A three-phase transformer intended essentially to provide a neutral point to a power system
for the purpose of Earthing.

18. Effective range


The range of values of the characteristic quantity or quantities, or of the energizing quantities to
which the relay will respond and satisfy the requirements concerning it, in particular those
concerning precision.

19. Effective setting


The 'setting' of a protective system including the effects of current transformers. The effective
setting can be expressed in terms of primary current or secondary current from the current
transformers and is so designated as appropriate.

20. Electrical relay


A device designed to produce sudden predetermined changes in one or more electrical
circuits after the appearance of certain conditions in the electrical circuit or circuits
controlling it.
NOTE: The term 'relay' includes all the ancillary equipment calibrated with the device.

21. Energizing quantity.


The electrical quantity, either current or voltage, which alone or in combination with other
energizing quantities, must be applied to the relay to cause it to function.

22. Independent time delay relay.


A time delay relay in which the time delay is independent of the energizing quantity.

21. Instantaneous relay.


A relay which operates and resets with no intentional time delay.
NOTE: All relays require some time to operate; it is possible, within the above definition, to
discuss the operating time characteristics of an instantaneous relay.

22. Inverse time delay relay.


A dependent time delay relay having an operating time which is an inverse function of the
electrical characteristic quantity.

23. Inverse time delay relay with definite minimum (I.D. M . T.)
A relay in which the time delay varies inversely with the characteristic quantity up to a
certain value, after which the time delay becomes substantially independent.

24. Knee-point e.m.f.


That sinusoidal e.m.f. applied to the secondary terminals of a current transformer, which,
when increased by 10 %, causes the exciting current to increase by 50%.

25. Main protection.


The protective system which is normally expected to operate in response to a fault in the
protected zone.

26. Measuring relay.


A relay intended to operate with a specified accuracy at one or more values of its
characteristic quantity.

27. Notching relay.


A relay which switches in response to a specific number of applied impulses.

28. Operating time.


With a relay de-energized and in its initial condition, the time which elapses between the
application of a characteristic quantity and the instant when the relay operates.

29. Operating time characteristic.


The curve depicting the relationship between different values of the characteristic quantity
applied to a relay and the corresponding values of operating time.

30. Operating value.


The limiting value of the characteristic quantity at which the relay actually operates.

31. Overshoot time.


The extent to which the condition that leads to final operation is advanced after the removal
of the energizing quantity, expressed as time at the rate of progress of the said condition
appropriate to the value of the energizing quantity that was initially applied.

32. Pick-up.
A relay is said to 'pick-up' when it changes from the un-energized position to the energized
position.

33. Pilot channel.


A means of interconnection between relaying points for the purpose of protection.

34. Protected zone.


The portion of a power system protected by a given protective system or a part of that
protective system.

35. Protective gear.


The apparatus, including protective relays, trans-formers and ancillary equipment, for use in
a protective system.

36. Protective relay.


A relay designed to initiate disconnection of a part of an electrical installation or to operate a
warning signal, in the case of a fault or other abnormal condition in the installation. A
protective relay may include more than one unit electrical relay and accessories.

37. Protective scheme.


The coordinated arrangements for the protection of one or more elements of a power system.
A protective scheme may comprise several protective systems.

38. Protective system.


A combination of protective gear designed to secure, under predetermined conditions,
usually abnormal, the disconnection of an element of a power system, or to give an alarm
signal, or both.

39. Rating.
The nominal value of an energizing quantity which appears in the designation of a relay. The
nominal value usually corresponds to the CT and VT secondary ratings.

40. Resetting value.


The limiting value of the characteristic quantity at which the relay returns to its initial
position.

41. Residua/ current.


The algebraic sum, in a multi-phase system, of all the line currents.
42. Residua/ voltage.
The algebraic sum, in a multi-phase system, of all the line-to-earth voltages.

43. Setting.
The limiting value of a 'characteristic' or 'energizing' quantity at which the relay is designed
to operate under specified conditions.
Such values are usually marked on the relay and may be expressed as direct values,
percentages of rated values, or multiples.

44. Stability.
The quality whereby a protective system remains inoperative under all conditions other than
those for which it is specifically designed to operate.

45. Stability limits.


The R.M.S. value of the symmetrical component of the through fault current up to which the
protective system remains stable.

46. Starting relay.


A unit relay which responds to abnormal conditions and initiates the operation of other
elements of the protective system.

47. System impedance ratio (S./.R.).


The ratio of the power system source impedance to the impedance of the protected zone.

48. Through fault current.


The current flowing through a protected zone to a fault beyond that zone.

49. Time delay.


A delay intentionally introduced into the operation of a relay system.

50. Time delay relay.


A relay having an intentional delaying device.

51. Unit electrical relay.


A single relay which can be used alone or in combinations with others.

52. Unit protection.


A protection system which is designed to operate only for abnormal conditions within a
clearly defined zone of the power system.

53. Unrestricted protection.


A protection system which has no clearly defined zone of operation and which achieves
selective operation only by time grading.
Fault Definitions and:
For the purpose of this International Standard, the following definitions, some of them
based on IEC 60050(191), IEC 60050(212) and
IEC 60050(604) apply:

1- Fault
An unplanned occurrence or defect in an item which may result in one or more failures of
the item itself or of other associated equipment
[IEC 604-02-011
NOTE - In electrical equipment, a fault may or may not result in damage to the insulation
and failure of the equipment.

2- Non-damage fault
A fault which does not involve repair or replacement action at the point of the fault
NOTE - Typical examples are self-extinguishing arcs in switching equipment or general
overheating without paper carbonization.
[IEC 604-02-091

3- Damage fault
A fault which involves repair or replacement action at the point of the fault
[IEC 604-02-08, modified]

4- Incident
An event related to an internal fault which temporarily or permanently disturbs the normal
operation of an equipment [IEV 604-02-03, modified]
NOTE - Typical examples are gas alarms, equipment tripping or equipment leakage.

5- Failure
The termination of the ability of an item to perform a required function [IEC 191-04-01]

NOTE - In the electrical equipment, failure will result from a damage fault or incident
necessitating outage, repair or replacement of the equipment, such as internal breakdown,
rupture of tank, fire or explosion.

6- Electrical fault
a partial or disruptive discharge through the insulation.

7- Partial discharge
A discharge which only partially bridges the insulation between conductors. It may occur
inside the insulation or adjacent to a conductor
[IEC 212-01-34, modified]

NOTE 1 - Corona is a form of partial discharge that occurs in gaseous media around
conductors which are remote from solid or liquid insulation. This term is not to be used
as a general term for all forms of partial discharges.
NOTE 2 - X-wax is a solid material which is formed from mineral insulating oil as a
result of electrical discharges and which consists of polymerized fragments of the
molecules of the original liquid
[IEV 212-07-24, modified].
Comparable products may be formed from other liquids under similar conditions.

NOTE 3 - Sparking of low energy, for example because of metals or floating potentials,
is sometimes described as
Partial discharge but should rather be considered as a discharge of low energy.

8- Discharge (disruptive) .
The passage of an arc following the breakdown of the insulation
[IEC 604-03-38, modified]

NOTE 1 - Discharges are often described as arcing, breakdown or short circuits.


The more specific following terms are also used:
- spark over (discharge through the oil);
- puncture (discharge through the solid insulation);
- Flashover (discharge at the surface of the solid insulation);
- tracking (the progressive degradation of the surface of solid insulation
by local
Discharges to form conducting or partially conducting paths);
- sparking discharges which, in the conventions of physics, are local
Dielectric breakdowns of high ionization density or small arcs.

NOTE 2 - Depending on the amount of energy contained in the discharge, it will be


described as a discharge of low or high energy, based on the extent of damage observed
on the equipment .

9- Thermal fault
Excessive temperature rise in the insulation

NOTE - Typical causes are


- Insufficient cooling,
- Excessive currents circulating in adjacent metal parts (as a result of bad
Contacts, eddy currents, stray losses or leakage flux),
- Excessive currents circulating through the insulation (as a result of high
Dielectric losses), leading to a thermal runaway,
- overheating of internal winding or bushing connection lead.

10- Typical values of gas concentrations.


gas concentrations normally found in the equipment in service which have no symptoms
of failure, and which are over passed by only an arbitrary percentage of higher gas
contents, for example 10 % .
NOTE 1 - Typical values will differ in different types of equipment and in different
networks, depending on operating practices (load levels, climate, etc.).

NOTE 2 - Typical values, in many countries and by many users, are quoted as "normal
values", but this term has not been used here to avoid possible misinterpretations.

LIST OF DEVICE NUMBERS


2 Time delay starting or closing relay.
3 Checking or interlocking relay
21 Distance relay
25 Synchronizing or synchronism check relay
27 Under voltage relay
30 Annunciator relay
32 Directional power relay
37 Undercurrent or under power relay
40 Field failure relay
46 Reverse phase or phase balance current relay
49 Machine or transformer thermal relay
50 Instantaneous over current or rate-of-rise relay
51 A.c. time over current relay
52 A.c. circuit breaker
52a Circuit breaker auxiliary switch—normally open
52b Circuit breaker auxiliary switch—normally closed
55 Power factor relay
56 Field_application relay
59 Over voltage relay
60 Voltage or current balance relay
64 Earth fault protective relay
67 A.c. directional over current relay
68 Blocking relay
74 Alarm relay
76 D.c. over current relay
78 Phase angle measuring or out-of-step protective relay
79 A.c. reclosing relay
81 Frequency relay
83 Automatic selective control or transfer relay
85 Carrier or pilot wire receive relay
86 Locking-out relay
87 Differential protective relay
94 auxiliary tripping relay

IEEE device numbers and functions for switchgear apparatus

The devices in switching equipments are referred to by numbers, with appropriate suffix
letters when necessary, according to the functions they perform. These numbers are
based on a system adopted as standard for automatic switchgear by IEEE, and
incorporated in American
Standard C37.2-1979. This system is used in connection diagrams, in instruction books,
and in specifications.

Device Number Definition and function

1- 1 Master element
is the initiating device, such as a control switch, voltage relay, float switch etc., that serves
either irectly, or through such permissive devices as protective and time-delay relays, to
place an equipment
in or out of operation.

2- 2 Time-delay starting or closing relay


is a device that functions to give a desired amount of time delay before or after any point
of operation in a switching sequence or protective relay system, except as specifically
provided by device functions 48, 62 and 79 described later.

3- 3 Checking or interlocking relay


is a device that operates in response to the position of a number of other devices, (or to a
number of predetermined conditions), in an equipment to allow an operating sequence to
proceed,
to stop, or to provide a check of the position of these devices or of these conditions for any
purpose.

4- 4 Master contactor
is a device, generally controlled by device No. 1 or equivalent, and the required
permissive
and protective devices, that serve to make and break the necessary control circuits to
place an equipment into operation under the desired conditions and to take it out of
operation under
other or abnormal conditions.

5- 5 Stopping device
is a control device used primarily to shut down an equipment and hold it out of
operation. [This device may be manually or electrically actuated, but excludes the
function of
electrical lockout (see device function 86) on abnormal conditions.]

6- 6 Starting circuit breaker


is a device whose principal function is to connect a machine to its source of starting
voltage.

7- 7 Rate-of-rise relay
is a relay that functions on an excessive rate of rise of current.

8- 8 Control power disconnecting device


is a disconnecting device, such as a knife switch, circuit breaker, or pull-out fuse block,
used for the purpose of respectively connecting and disconnecting the source of control
power to and from the control bus or equipment.

9- 9 Reversing device
is used for the purpose of reversing a machine field or for performing any other
reversing
functions.

10- 10 Unit sequence switch


is used to change the sequence in which units may be placed in and out of service in
multiple-unit equipment.

11- 11 Multifunction device


is a device that performs three or more comparatively important functions that could
only be
designated by combining several of these device function numbers. All of the functions
performed by device 11 shall be defined in the drawing legend or device function list.

12- 12 Over speed device


is usually a direct connected speed switch that functions on machine over speed.

13- 13 Synchronous-speed device


such as a centrifugal speed switch, a slip frequency relay, a voltage relay, an
undercurrent relay, or any other type of device that operates at approximately the
synchronous speed of a
machine.

14- 14 Under speed device


functions when the speed of a machine falls below a pre-determined value.

15- 15 Speed or frequency matching device


functions to match and hold the speed or the frequency of a machine or of a system equal
to, or approximately equal to, that of another machine, source, or system.

16- 16 Reserved for future application

17- 17 Shunting or discharge switch


serves to open or to close a shunting circuit around any piece of apparatus (except a
resistor), such as a machine field, a machine armature, a capacitor, or a reactor.
Note: This excludes devices that perform such shunting operations as may be necessary
in the process of starting a machine by devices 6 or 42, or their equivalent, and also
excludes
device 73 function that serves for the switching of resistors.

18- 18 Accelerating or decelerating device


is used to close or to cause the closing of circuits that are used to increase or decrease the
speed of a machine.

19- 19 Starting-to-running transition


contactor is a device that operates to initiate or cause the automatic transfer of a machine
from the starting to the running power connection.

20- 20 Electrically operated valve


is an electrically operated, controlled, or monitored valve used in a fluid, air, gas, or
vacuum line.
Note: The function of the valve may be indicated by the use of the suffixes, see page 11.

21- 21 Distance relay


is a relay that functions when the circuit admittance, impedance, or reactance increases
or
decreases beyond a predetermined value.

22- 22 Equalizer circuit breaker


is a breaker that serves to control or to make and break the equalizer or the current
balancing
connections for a machine field, or for regulating equipment, in a multiple unit
installation.

23- 23 Temperature control device


Functions to raise or to lower the temperature of a machine or other apparatus, or of
any medium, when its temperature falls below or rises above a predetermined value.

Note: An example is a thermostat that switches on a space heater in a switchgear


assembly when the temperature falls to a desired value as distinguished from a device
that is used to provide automatic temperature regulation between close limits and would
be designated as 90T.

24- 24 Volts per hertz relay


is a relay that functions when the ratio of voltage to frequency exceeds a preset value.
The relay may have an instantaneous or a time characteristic.

25- 25 Synchronizing or synchronism check


device operates when two ac circuits are within the desired limits of frequency, phase
angle, or voltage to permit or to cause the paralleling of these two circuits.

26- 26 Apparatus thermal device


Functions when the temperature of the protected apparatus (other than the loadcarrying
windings of machines and transformers as covered by device function number 49) or of a
liquid or other medium exceeds a predetermined value; or when the temperature of the
protected apparatus or of any medium decreases below a predetermined value.

27- 27 Under voltage relay


is a relay that operates when its input voltage is less than a predetermined value.

28- 28 Flame detector


is a device that monitors the presence of the pilot or main flame in such apparatus as a
gas
turbine or a steam boiler.

29- 29 Isolating contactor


is used expressly for disconnecting one circuit from another for the purposes of
emergency
operation, maintenance, or test.

30 Annunciator relay
is a nonautomatically reset device that gives a number of separate visual indications
upon the functioning of protective devices and that may also be arranged to perform a
lock-out function.

31- 31 Separate excitation device


connects a circuit, such as the shunt field of a synchronous converter, to a source of
separate excitation during the starting sequence; or one which energizes the excitation
and ignition
circuits of a power rectifier.

32- 32 Directional power relay


is a relay that operates on a predetermined value of power flow in a given direction or
upon reverse power flow such as that resulting from the motoring of a generator upon
loss of its prime mover.
33- 33 Position switch
makes or breaks contact when the main device or piece of apparatus that has no device
function number reaches a given position.

34- 34 Master sequence device


is a device such as a motor operated multi contact switch, or the equivalent, or a
programming device, such as a computer, that establishes or determines the
operating sequence of the major devices in an equipment during starting
and stopping or during other sequential switching operations.

35- 35 Brush-operating or slip-ring short circuiting


device is used for raising, lowering or shifting the brushes of a machine; short-circuiting
its slip rings; or engaging or disengaging the contacts of a mechanical rectifier.

36- 36 Polarity or polarizing voltage device


operates, or permits the operation of, another device on a predetermined polarity only or
that
verifies the presence of a polarizing voltage in an equipment.

37- 37 Undercurrent or under power relay


functions when the current or power flow decreases below a predetermined value.

38- 38 Bearing protective device


Functions on excessive bearing temperature or on other abnormal mechanical conditions
associated with the bearing, such as undue wear, which may eventually result in excessive
bearing temperature or failure.
39- 39 Mechanical condition monitor
is a device that functions upon the occurrence of an abnormal mechanical condition
(except that associated with bearings as covered under device function 38), such as
excessive vibration, eccentricity, expansion, shock, tilting, or seal failure.

40- 40 Field relay


functions on a given or abnormally low value or failure of machine field current, or on
an excessive value of the reactive component of armature current in an ac machine
indicating abnormally low field excitation.

41- 41 Field circuit breaker


is a device that functions to apply or remove the field excitation of a machine.

42- 42 Running circuit breaker


is a device whose principal function is to connect a machine to its source of running or
operating voltage. This function may also be used for a device, such as a contactor, that is
used in series with a circuit breaker or other fault protecting means, primarily for
frequent opening and closing of the circuit.

43- 43 Manual transfer or selector device


is a manually operated device that transfers the control circuits in order to modify the
plan of operation of the switching equipment or of some of the devices.

44- 44 Unit sequence starting relay


is a relay that functions to start the next available unit in multiple unit equipment upon
the failure or nonavailability of the normally preceding unit.

45- 45 Atmospheric condition monitor


is a device that functions upon the occurrence of an abnormal atmospheric condition,
such as damaging fumes, explosive mixtures, smoke, or fire.

46- 46 Reverse-phase or phase-balance


current relay is a relay that functions when the polyphase currents are of reverse phase
sequence or when the polyphase currents are unbalanced or contain negative phase-
sequence
components above a given amount.

47- 47 Phase-sequence or phase-balance


voltage relay functions upon a predetermined value of polyphase voltage in the desired
phase sequence, or when the polyphase voltages are unbalanced, or when the negative
phase-sequence voltage exceeds a given amount.

48- 48 Incomplete sequence relay


is a relay that generally returns the equipment to the normal, or off, position and locks it
out if the normal starting, operating, or stopping sequence is not properly completed
within a predetermined time. If the device is used for alarm purposes only, it should
preferably
be designated as 48A (alarm).

49- 49 Machine or transformer thermal


relay is a relay that functions when the temperature of a machine armature winding or
other load-carrying winding or element of a machine or power transformer exceeds a
redetermined
value.

50- 50 Instantaneous over current relay


is a relay that functions instantaneously on an excessive value of current.

51- 51 Ac time over current relay


is a relay with either a definite or inverse time characteristic that functions when the ac
input current exceeds a predetermined value, and in which the input current and
operating time are independently related or inversely related through a substantial
portion of the performance range.

52- 52 Ac circuit breaker


is a device that is used to close and interrupt an ac power circuit under normal
conditions
or to interrupt this circuit under fault or emergency conditions.

53- 53 Exciter or dc generator relay


is a relay that forces the dc machine field excitation to build up during starting or that
functions when the machine voltage has built up to a given value.

54- 54 Turning gear engaging device


is an electrically operated, controlled, or monitored device that functions to cause the
turning gear to engage (or disengage) the machine shaft.

55- 55 Power factor relay


is a relay that operates when the power factor in an ac circuit rises above or falls below a
predetermined value.

56- 56 Field application relay


is a relay that automatically controls the application of the field excitation to an ac motor
at
some predetermined point in the slip cycle.

57- 57 Short-circuiting or grounding device


is a primary circuit switching device that functions to short circuit or ground a circuit in
response to automatic or manual means.

58- 58 Rectification failure relay


is a device that functions if a power recitifier fails to conduct or block properly.

59- 59 Over voltage relay


is a relay that operates when its input voltage is higher than a predetermined value.

60- 60 Voltage or current balance relay


is a relay that operates on a given difference in voltage, or current input or output,
of two circuits.

61- 61 Density switch or sensor


is a device that operates on a given value, or a given rate of change, of gas density.

62- 62 Time-delay stopping or opening relay


is a time-delay relay that serves in conjunction with the device that initiates the
shutdown, stopping, or opening operation in an automatic sequence or protective relay
system.

63- 63 Pressure switch


is a switch that operates on given values, or on a given rate of change, of pressure.
64- 64 Ground detector relay
is a relay that operates upon failure of machine or other apparatus insulation to ground,
or on flashover of a dc machine to ground.

Note: This function is assigned only to a relay which detects the flow of current from the
frame of a machine or enclosing case or structure of a piece of apparatus to ground, or
detects a ground on a normally ungrounded winding or circuit. It is not applied to a
device connected in the secondary neutral of a current transformer, or in the secondary
neutral of current transformers, connected in the power circuit of a normally grounded
system.

65- 65 Governor
is the assembly of fluid, electrical, or mechanical control equipment used for regulating
the flow of water, steam, or other media to the prime mover for such purposes as
starting, holding speed or load, or stopping.

66- 66 Notching or jogging device


Functions to allow only a specified number of operations of a given device or equipment,
or a specified number of successive operations within a given time of each other. It is also
a device that functions to energize a circuit periodically or for fractions of specified time
intervals, or that is used to permit intermittent acceleration or jogging of a machine at
low speeds for mechanical positioning.

67- 67 Ac directional over current relay


is a relay that functions on a desired value of ac over current flowing in a predetermined
direction.

68- 68 Blocking relay


is a relay that initiates a pilot signal for blocking of tripping on external faults in a
transmission line or in other apparatus under predetermined conditions, or that
cooperates
with other devices to block tripping or to block reclosing on an out-of-step condition or
on power swings.

69- 69 Permissive control device


is generally, a two-position device that in one position permits the closing of a circuit
breaker, or the placing of an equipment into operation, and in the other position prevents
the circuit breaker or the equipment from being operated.
70- 70 Rheostat
is a variable resistance device used in an electric circuit which is electrically operated or
has other electrical accessories, such as auxiliary, position, or limit switches.

71- 71 Level switch


is a switch that operates on given values, or on a given rate of change, of level.
72- 72 Dc circuit breaker
is used to close and interrupt a dc power circuit under normal conditions or to interrupt
this
circuit under fault or emergency conditions.

73- 73 Load-resistor contactor


is used to shunt or insert a step of load limiting, shifting, or indicating resistance in a
power circuit, or to switch a space heater in circuit, or to switch a light, or regenerative
load resistor of a power rectifier or other machine in and out of circuit.

74- 74 Alarm relay


is a relay other than an annunciator, as covered under device function 30, that is used to
operate, or that operates in connection with, a visual or audible alarm.

75- 75 Position changing mechanism


is a mechanism that is used for moving a main device from one position to another in an
equipment; for example, shifting a removable circuit breaker unit to and from the
connected, disconnected, and test positions.

76-76 Dc over current relay


is a relay that functions when the current in a dc circuit exceeds a given value.
77- 77 Telemetering device
is a transmitter used to generate and transmit to a remote location an electrical signal
representing a measured quantity, or a receiver used to receive the electrical signal from
a remote transmitter and convert the signal to represent the original measured quantity.
78- 78 Phase-angle measuring or out-of step
protective relay is a relay that functions at a predetermined phase angle between two
voltages, or between two currents, or between voltage and current.

79- 79 Ac reclosing relay


is a relay that controls the automatic reclosing and locking out of an ac circuit
interrupter.

80- 80 Flow switch


is a switch that operates on given values, or on a given rate of change, of flow.

81- 81 Frequency relay


is a relay that responds to the frequency of an electrical quantity, operating when
the frequency or rate of change of frequency exceeds or is less than a predetermined
value.

82 82 Dc load-measuring reclosing relay


is a relay that controls the automatic closing and reclosing of a dc circuit interrupter,
generally in response to load circuit conditions.
83- 83 Automatic selective control or transfer relay
is a relay that operates to select automatically between certain sources or conditions in
an
equipment or that performs a transfer operation automatically.

84- 84 Operating mechanism


is the complete electrical mechanism or servomechanism, including the operating
motor, solenoids, position switches, etc., for a tap changer, induction regulator,
or any similar piece of apparatus that otherwise has no device function number.

85 Carrier or pilot-wire receiver relay


Is a relay that is operated or restrained by a signal used in connection with carrier-
current or dc pilot-wire fault directional relaying.

86- 86 Lockout relay


is an electrically operated hand or electrically reset auxiliary relay that is operated upon
the occurrence of abnormal conditions to maintain associated equipment or devices out
of service until it is reset.

87- 87 Differential protective relay


is a protective relay that functions on a percentage, or phase angle, or other quantitative
difference between two currents or some other electrical quantities.

88- 88 Auxiliary motor or motor generator


is a device used for operating auxiliary equipment, such as pumps, blowers, exciters,
rotating magnetic amplifiers, etc.

89- 89 Line switch


is used as a disconnecting, load interrupter, or isolating switch in an ac or dc power
circuit. (Thisdevice function number is normally not necessary unless the switch is
electrically operated or has electrical accessories, such as an auxiliary switch, a magnetic
lock, etc.)

90- 90 Regulating device


functions to regulate a quantity or quantities, such as voltage, current, power, speed,
frequency, temperature, and load, at a certain value or between certain (generally close)
limits for machines, tie lines, or other apparatus.

91- 91 Voltage directional relay


is a relay that operates when the voltage across an open circuit breaker or contactor
exceeds a given value in a given direction.
92- 92 Voltage and power directional relay
is a relay that permits or causes the connection of two circuits when the voltage difference
between them exceeds a given value in a predetermined direction and causes these two
circuits to be disconnected from each other when the power flowing between them
exceeds a given value in the opposite direction.

93- 93 Field-changing contactor


Functions to increase or decrease, in one step, the value of field excitation on a machine.

94- 94 Tripping or trip-free relay


Functions to trip a circuit breaker, contactor, or equipment, or to permit immediate
tripping by other devices; or to prevent immediate reclosing of a circuit interrupter
if it should open automatically, even though its closing circuit is maintained closed.
95- 95
96- 96
97- 97
98- 98
99- 99
Used only for specific applications on individual installations where none of the assigned
numbered functions from 1 to 94 is suitable.

IEEE device numbers

Supervisory control and indication.


A similar series of numbers, prefixed by the letters RE (for “remote”) shall be used
for the interposing relays performing functions that are controlled directly from the
supervisory
system. Typical examples of such device functions are: RE1, RE5 and RE94.

Note: The user of the “RE” prefix for this purpose in place of the former 200 series of
numbers now makes it possible to obtain increased flexibility of the device function
numbering system. For example, in pipeline pump stations, the numbers 1 through
99
are applied to device functions that are associated with the over-all station
operation. A similar series of numbers,
starting with 101 instead of 1, are used for those device functions that are associated
with unit 1; a similar series starting with 201 for device functions that are associated
with unit
2; and so on, for each unit in these installations.

Devices performing more than one function


If one device performs two relatively important functions in an equipment so that it is
desirable to identify both of these functions, this may be done by using a double
function
number and name such as:
50/51 Instantaneous and Time Over current
relay.

Suffix numbers
If two or more devices with the same function number and suffix letter (if used) are
present
in the same equipment, they may be distinguished by numbered suffixes as for
example,
52X-1, 52X-2 and 52X-3, when necessary.

Suffix letters
Suffix letters are used with device function numbers for various purposes. In order to
prevent
possible conflict each suffix letter should have only one meaning in an individual
equipment. All other words should use the abbreviations as contained in American
Standard Z32.13-1950, or latest revision thereof, or should use some other distinctive
abbreviation, or be written out in full each time they are used.
The meaning of each single suffix letter, or combination of letters, should be clearly
designated in the legend on the drawings or publications applying to the equipment.
In cases where the same suffix (consisting of one letter or a combination of letters)
has different meanings in the same equipment, depending upon the device function
number with which is used, then the complete device function number with which it
is used, the complete device function number with its suffix letter or letters and its
corresponding function name should be listed in the legend in each case, as follows:
90V, Voltage regulator. Lower case (small) suffix letters are used in practically all
instances on electrical diagrams for the auxiliary, position, and limit switches. Capital
letters are generally used for all other suffix letters.
The letters should generally form part of the device function designation, are usually
written
directly after the device function number, as for example, 52CS, 71W, or 49D. When
it
is necessary to use two types of suffix letters in connection with one function number,
it is
often desirable for clarity to separate them by a slanted line or dash, as for example,
20D/CS or 20D-CS. The suffix letters which denote parts of the main device, and
those which cannot or need not form part of the device function designation, are
generally written directly below the device function number on drawings, as for
example, or .
52/CC or 43/A

Auxiliary devices Separate auxiliary devices Actuating quantities


These letters indicate the condition or electrical quantity to which the device
responds, or the medium in which it is located, such as:
Main devices
These letters denote the location of the main device in the circuit, or the type of
circuit in
which the device is used or the type of circuit or apparatus with which it is associated,
when
this is necessary, such as:
X
Y – Auxiliary relay 1)
Z
R – Raising relay
L – Lowering relay
O – Opening relay or contactor
C – Closing relay or contactor
CS – Control switch
CL – Auxiliary relay, open (energized when main device is in open position)
OP – Auxiliary relay, open (energized when main device is in open position)
U – “Up” position-switch relay
D – “Down” position-switch relay
PB – Push button
1) In the control of a circuit breaker with so-called
X-Y relay control scheme, the X relay is the device whose main contacts are used to
energize
the closing coil or the device which in some other manner, such as by the release of
stored energy, causes the breaker to close.
The contacts of the Y relay provide the antipump feature for the circuit breaker.
A – Air or Amperes or Alternating
C – Current
D – Direct or Discharge
E – Electrolyte
F – Frequency, or Flow, or Fault
H – Explosive
J – Differential
L – Level, or Liquid
P – Power, or Pressure
PF – Power factor
Q – Oil
S – Speed, or Suction, or Smoke
T – Temperature
V – Voltage, Volts, or Vacuum
VAR – Reactive power
VB – Vibration
W – Water, or Watts
A – Alarm or Auxiliary power
AN – Anode
B – Battery, or Blower, or Bus
BK – Brake
BL – Block (Valve)
BP – Bypass
BT – Bus tie
C – Capacitor, or Condenser, or Compensator, or Carrier current, or Case, or
Compressor
CA – Cathode
CH – Check (Valve)
D – Discharge (Valve)
E – Exciter
F – Feeder, or Field, or Filament, or Filter, or Fan
G – Generator, or Ground2)
H – Heater, or Housing
L – Line, or Logic
M – Motor, or Metering
N – Network, or Neutral 2)
P – Pump, or Phase comparison
R – Reactor, or Rectifier, or Room
S – Synchronizing, or Secondary, or
Strainer, or Sump, or Suction (Valve)
T – Transformer, or Thyratron
TH – Transformer (high-voltage side)
TL – Transformer (low-voltage side)
TM – Telemeter
U – Unit
2) Suffix “N” is generally used in preference to “G” for devices connected in the
secondary neutral of current transformers, or in the secondary of a current
transformer whose primary winding is located in the neutral of a machine or power
transformer, except in the case of transmission line relaying, where the suffix “G” is
more commonly used for those relays which operate on ground faults.

Main device parts


These letters denote parts of the main device, divided in the two following categories:

1. All parts, except auxiliary contacts, position switches, limit switches, and torque
limit
switches.

2. All auxiliary contacts and positioning and limit switches


for such devices and equipment as circuit breakers, contactors, valves and rheostats
and contacts of relays. These are designated as follows:

Standard reference positions of some typical devices are as follows:


BK – Brake
C – Coil, or Condenser, or Capacitor
CC – Closing coil
HC – Holding coil
M – Operating motor
MF – Fly-ball motor
ML – Load-limit motor
MS – Speed adjusting, or Synchronizing
motor
S – Solenoid
SI – Seal-in
TC – Trip coil
V – Valve
a – Contact that is open when the main device is in the standard reference position,
commonly referred to as the nonoperated or reenergized position and that closes
when the device assumes the opposite position.
b – Contact that is closed when the main device is in the standard reference position,
commonly referred to as the nonoperated or deenergized position, and that opens
when the device assumes the opposite position.
aa – Contact that is open when the operating mechanism of the main device is in the
nonoperated position and that closes when the operating mechanism assumes the
opposite position.
bb – Contact that is closed when the operating mechanism of the main device is in
the nonoperated position and that opens when the operating mechanism assumes the
opposite position.

Device Standard reference position


Power circuit breaker Main contacts open
Disconnecting switch Main contacts open
Load-break switch Main contacts open
Valve Closed position
Gate Closed position
Clutch Disengaged position
Turning gear Disengaged position
Power electrodes Maximum gap position
Rheostat Maximum resistance
position
Adjusting means 1) Low or Down position
Relay 2) Deenergized position
Contactor 2) Deenergized position
Relay (latched-in type)
Non-latched-in position
Contactor (latched-in type)
Main contacts open
Temperature relay 3) Lowest temperature
Level detector 3) Lowest level
Flow detector 3) Lowest flow
Speed switch 3) Lowest speed
Vibration detector 3) Minimum vibration
Pressure switch 3) Lowest pressure
Vacuum switch 3) Lowest pressure, i.e.,
highest vacuum
The simple designation “a” or “b” is used in all cases where there is no need to adjust
the
contacts to change position at any particular point in the travel of the main device or
where the part of the travel where the contacts change position is of no significance in
the control or operating scheme. Hence the “a” and “b” designations usually are
sufficient for circuit breaker auxiliary switches.
Note: If several similar auxiliary switches are present on the same device, they should
be designated numerically 1, 2, 3, etc. when necessary.

Other switches
These letters cover all other distinguishing
features or characteristics or conditions,
which serve to describe the use of the device
or its contacts in the equipment such as:

Device Standard reference position


1) These may be speed, voltage, current, load, or similar adjusting devices comprising
rheostats, springs, levers, or other components for the purpose.

2) These electrically operated devices are of the non-latched-in type, whose contact
position is dependent only upon the degree of energization of the operating or
restraining or holding
coil or coils which may or may not be suitable for continuous energization. The
deenergized
position of the device is that with all coils deenergized.

3) The energizing influences for these devices are considered to be, respectively,
rising
temperature, rising level, increasing flow, rising speed, increasing vibration, and
increasing
pressure.

A – Accelerating, or Automatic
B – Blocking, or Back-up
C – Close, or Cold
D – Decelerating, or Detonate, or Down, or
Disengaged
E – Emergency, or Engaged
F – Failure, or Forward
H – Hot, or High
HR – Hand reset
HS – High speed
L – Left, or Local, or Low, or Lower, or
Leading
M – Manual
OFF – Off
ON – On
P – Polarizing
R – Right, or Raise, or Reclosing, or Receiving, or Remote, or Reverse
S – Sending, or Swing
T – Test, or Trip, or Trailing
TDC – Time-delay closing
TDO – Time-delay opening

Relay contact systems

Relay contact systems

a. Self-reset.
The contacts remain operated only while the controlling quantity is applied,
returning to their original condition when it is removed.

b. Hand or electrical reset.


These contacts remain in the operated position after the controlling quantity is
removed. They can be reset either by hand or by an auxiliary electromagnetic element.
The majority of protective relay elements have self-reset contact systems, which, if
it is so desired, can be made to give hand reset output contacts by the use of auxiliary
elements.
Hand or electrically reset relays are used when it is necessary to maintain a signal
or a lock-out condition. Contacts are shown on diagrams in the position corresponding to
the un-operated or de-energized condition regardless of the continuous service condition
of the equipment. For example, a voltage supervising relay, which is continually picked-
up, would still be shown in the de-energized condition.
A 'make' contact is one that closes when the relay picks up, whereas a 'break'
contact is one that is closed when the relay is un-energized and opens when the relay picks
up. Examples of these conventions and variations are shown in Figure 6.
Figure 6 indications of contacts on diagrams.

A protective relay is usually required to trip a circuit breaker, the tripping


mechanism of which may be a solenoid with a plunger acting directly on the mechanism
latch or, in the case of air-blast or pneumatically operated breakers, an electrically operated
valve. The relay may energize the tripping coil directly, or, according to the coil rating, and
the number of circuits to be energized, may do so through the agency of another multi-
channel auxiliary relay.
The power required by the trip coil of the circuit breaker may range from up to 50
watts, for a small 'distribution' circuit breaker, to 3000 watts for a large extra-high-voltage
circuit breaker.
The basic trip circuit is simple, being made up of a hand-trip control switch and the
contacts of the protective relays in parallel to energize the trip coil from a battery, through
a normally open auxiliary switch operated by the circuit breaker. This auxiliary switch is
needed to open the trip circuit when the circuit breaker opens, since the protective relay
contacts will usually be quite incapable of performing the interrupting duty. The auxiliary
switch will be adjusted to close as early as possible in the closing stroke, to make the
protection effective in case the breaker is being closed on to a fault.

Protective relays are precise measuring devices, the contacts of which should not be
expected to perform large making and breaking duties. Attracted armature relays, which
combine many of the characteristics of measuring devices and contactors,
Occupy an intermediate position and according to their design and consequent
closeness to one or other category, may have an appreciable contact capacity.
Most other types of relay develop an effort which is independent of the position of
the moving system.
At setting, the electromechanical effort is absorbed by the controlling force, the
margin for operating the contacts being negligibly small. Not only does this limit the
'making' capacity of the contacts, but if more than one contact pair is fitted any slight
misalignment may result in only one contact being closed at the minimum operating value,
there being insufficient force to compress the spring of the first contact to make, by the
small amount required to permit closure of the second.
For this reason, the provision of multiple contacts on such elements is undesirable.
Although two contacts can be fitted, care must be taken in their alignment, and a small
tolerance in the closing value of operating current may have to be allowed between them.
These effects can be reduced by providing a small amount of 'run-in' to contact make in
the relay behavior, by special shaping of the active parts.
For the above reasons it is often better to use inter-posing contactor type elements
which do not have the same limitations, although some measuring relay elements are
capable of tripping the smaller types of circuit breaker directly. These may be small
attracted armature type elements fitted in the same case as the measuring relay.
In general, static relays have discrete measuring and tripping circuits, or modules.
The functioning of the measuring modules will not react on the tripping modules. Such a
relay is equivalent to a sensitive electromechanical relay with a tripping contactor, so that
the number or rating of outputs has no more significance than the fact that they have been
provided.
For larger switchgear installations the tripping power requirement of each circuit
breaker is considerable, and, further, two or more breakers may have to be tripped by one
protective system.
There may also be remote signaling requirements, interlocking with other functions
(for example auto-reclosing arrangements), and other control functions to be performed.
These various operations are carried out by multi-contact tripping relays, which are
energized by the protection relays and provide the necessary number of adequately rated
output contacts.
Operation indicators.
As a guide for power system operation staff, protective systems are invariably
provided with indicating devices. In British practice these are called 'flags', whereas in
America they are known as 'targets'. Not every component relay will have one, as
indicators are arranged to operate only if a trip operation is initiated. Indicators, with very
few exceptions, are bi-stable devices, and may be either mechanically or electrically
operated. A mechanical indicator consists of a small shutter which is
Released by the protective relay movement to expose the indicator pattern, which,
on GEC Measurements relays, consists of a red diagonal stripe on a white background.
Electrical indicators may be simple attracted armature elements either with or
without contacts. Operation of the armature releases a shutter to expose an indicator as
above.
An alternative type consists of a small cylindrical permanent magnet magnetized
across a diameter, and lying between the poles of an electromagnet. The magnet, which is
free to rotate, lines up its magnetic axis with the electromagnet poles, but can be made to
reverse its orientation by the application of a field. The edge of the magnet is colored to
give the indication.

Relay tripping circuits.


Auxiliary contactors can be used to supplement protective relays in a number of ways:
a. Series sealing.
b. Shunt reinforcing.
c. Shunt reinforcement with sealing. These are illustrated in
Figure 7.
When such auxiliary elements are fitted, they can conveniently carry the operation
indicator, avoiding the need for indicators on the measuring elements.
Electrically operated indicators avoid imposing an additional friction load on the
measuring element, which would be a serious handicap for certain types. Another
advantage is that the indicator can operate only after the main contacts have closed.

Figure 7 Typical relay tripping circuits.

With indicators operated directly by the measuring elements, care must be taken to line up
their operation with the closure of the main contacts. The indicator must have operated by
the time the contacts make, but must not have done so more than marginally earlier.

This is to stop indication occurring when the tripping operation has not been
completed.

Ta. Series sealing.


The coil of the series contactor carries the trip current initiated by the protective
relay, and the contactor closes a contact in parallel with the protective relay contact.
This closure relieves the protective relay contact of further duty and keeps the tripping
circuit securely closed, even if chatter occurs at the main contact. Nothing is added to the
total tripping time, and the indicator does not operate until current is actually flowing
through the trip coil.
The main disadvantage of this method is that such series elements must have their
coils matched with the trip circuit with which they are associated.
The coils of these contactors must be of low impedance, with about
5 % of the trip supply voltage being dropped across them.
When used in association with high speed trip relays, which usually interrupt their own
coil current, the auxiliary elements must be fast enough to operate and release the flag
before their coil current is cut off.
This may pose a problem in design if a variable number of auxiliary elements (for
different phases and so on) may be required to operate in parallel to energize a common
tripping relay.

b. Shunt reinforcing.
Here the sensitive contacts are arranged to trip the circuit breaker and
simultaneously to energize the auxiliary unit, which then reinforces the contact which is
energizing the trip coil.
It should be noted that two contacts are required on the protective relay, since it is
not permissible to energize the trip coil and the reinforcing contactor in parallel. If this
were done, and more than one protective relay were connected to trip the same circuit
breaker, all the auxiliary relays would be energized in parallel for each relay operation and
the indication would be confused. The duplicate main contacts are frequently provided
As a three point arrangement to reduce the number of contact fingers.
Figure 8 Examples of trip circuit supervision.

c. Shunt reinforcement with sealing.


This is a development of the shunt reinforcing circuit to make it applicable to
relays with low torque movements or where there is a possibility of contact bounce for any
other reason.
Using the shunt reinforcing system under these circumstances would result in
chattering on the auxiliary unit, and the possible burning out of the contacts not only of
the sensitive element but also of the auxiliary unit. The chattering would only end when
the circuit breaker had finally tripped.
It will be seen that the effect of bounce is countered by means of a further contact
on the auxiliary unit connected as a retaining contact.
This means that provision must be made for releasing the sealing circuit when
tripping is complete; this is a disadvantage, because it is sometimes in-convenient to find a
suitable contact to use for this purpose.

Supervision of trip circuits.


The trip circuit extends beyond the relay enclosure and passes through more
components, such as fuses, links, relay contacts, auxiliary switch contacts and so on, and
in some cases through a considerable amount of circuit wiring with intermediate terminal
boards.
These complications, coupled with the importance of the circuit, have directed
attention to its supervision.
The simplest arrangement contains a healthy trip lamp, as shown in Figure 8(a).
The resistance in series with the lamp prevents the breaker being tripped by an
internal short circuit caused by failure of the lamp. This provides super-vision while the
circuit breaker is closed; a simple extension gives pre-closing supervision.
Figure 1.8(b) shows how, by the addition of a normally closed auxiliary switch and
a resistance unit, supervision can be obtained while the breaker is both open and closed.
I n either case, the addition of a normally open push-button contact in series with
the lamp will make the supervision indication available only when required.
Schemes using a lamp to indicate continuity are suitable for locally controlled
installations, but when control is exercised from a distance it is necessary to use a relay
system. Figure 8(c) illustrates such a scheme, which is applicable wherever a remote signal
is required.
With the circuit healthy either or both of relays A and B are operated and energize relay C.
Both A and B must reset to allow C to drop-off. Relays A and C are time-delayed by
copper slugs to prevent spurious alarms during tripping or closing operations. The
resistors are mounted separately from the relays and their values are chosen such that if any
one component is inadvertently short-circuited, a tripping operation will not take place.
The alarm supply should be independent of the tripping supply so that indication will be
obtained in the event of the failure of the tripping battery.
Classification and function of relays
A protection relay is a device that senses any change in the signal which it is receiving, usually from
a current and/or voltage source. If the magnitude of the incoming signal is outside a preset range,
the relay will operate, generally to close or open electrical contacts to initiate some further
operation, for example the tripping of a circuit breaker.

3.1 Classification:
Protection relays can be classified in accordance with the function which they carry out, their
construction, the incoming signal and the type of functioning.

3.1.1 General function:


Auxiliary.
Protection.
Monitoring.
Control.

3.1.2 Construction:
Electromagnetic.
Solid state.
Microprocessor.
Computerized.
Nonelectric (thermal, pressure ......etc.).

3.1.3 Incoming signal:


Current.
Voltage.
Frequency.
Temperature.
Pressure.
Velocity.
Others.
3.1.4 Type of protection
Over current.
Directional over current.
Distance.
Over voltage.
Differential.
Reverse power.
Other.
Figure 1 Armature-type relay
In some cases a letter is added to the number associated with the protection in order to
specify its place of location, for example G for generator, Τ for transformer etc.
Nonelectric relays are outside the scope of this book and therefore are not referred to.

3.2 Electromagnetic relays


Electromagnetic relays are constructed with electrical, magnetic and mechanical
components, have an operating coil and various contacts and are very robust and reliable.
The construction characteristics can be classified in three groups, as detailed below.

3 . 2 . 1 Attraction relays
Attraction relays can be supplied by AC or DC, and operate by the movement of a
piece of metal when it is attracted by the magnetic field produced by a coil. There are two
main types of relay in this class.
The attracted armature relay, which is shown in figure 1, consists of a bar or plate of
metal which pivots when it is attracted towards the coil.
The armature carries the moving part of the contact, which is closed or opened
according to the design when the armature is attracted to the coil. The other type is the piston or
solenoid relay, illustrated in Figure 2, in which α bar or piston is attracted axially within the field
of the solenoid. In this case, the piston also carries the operating contacts.
It can be shown that the force of attraction is equal to K1I2 - K2, where Κ1 depends upon the
number of turns on the operating solenoid, the air gap, the effective area and the reluctance of
the magnetic circuit, among other factors. K2 is the restraining force, usually produced by a
spring. When the relay is balanced, the resultant force is zero and therefore Κ112 = K2,

So that
I = K 2 / K1 =constant.
In order to control the value at which the relay starts to operate, the restraining tension
of the spring or the resistance of the solenoid circuit can be varied, thus modifying the
restricting force. Attraction relays effectively have no time delay and, for that reason, are
widely used when instantaneous operations are required.

3 . 2 . 2 Relays with moveable coils


This type of relay consists of a rotating movement with a small coil suspended or pivoted with
the freedom to rotate between the poles of a permanent magnet. The coil is restrained by two
springs which also serve as connections to carry the current to the coil.
The torque produced in the coil is given by:

T = B.l.a.N.i

Where:

T= torque
B = flux density
L =length of the coil
a = diameter of the coil
N = number of turns on the coil
i = current flowing through the coil

Figure 2 Solenoid-type relay


Figure 3 Inverse time characteristic
From the above equation it will be noted that the torque developed is proportional to the
current. The speed of movement is controlled by the damping action, which is proportional to
the torque. It thus follows that the relay has an inverse time characteristic similar to that
illustrated in Figure 3. The relay can be designed so that the coil makes a large angular
movement, for example 80º.

3 . 2 . 3 Induction relays
An induction relay works only with alternating current. It consists of an electromagnetic system
which operates on a moving conductor, generally in the form of a disc or cup, and functions
through the interaction of electromagnetic fluxes with the parasitic Fault currents which are
induced in the rotor by these fluxes. These two fluxes, which are mutually displaced both in
angle and in position, produce a torque that can be expressed by

T= Κ1.Φ1.Φ2 .sin θ,

Where Φ1 and Φ2 are the interacting fluxes and θ is the phase angle between Φ1 and Φ2. It
should be noted that the torque is a maximum when the fluxes are out of phase by 90º, and zero
when they are in phase.

Figure 4 Electromagnetic forces in induction relays


It can be shown that Φ1= Φ1sin ωt, and Φ2= Φ2 sin (ωt+ θ ) , where θ is the angle by
which Φ2 leads Φ1. Then:

dΦ1
iΦ1 α α Φ1 cosωt
dt
And

dΦ 1
i Φ1 α α Φ 1 cos ( ωt + θ )
dt
Figure 4 shows the interrelationship between the currents and the opposing forces. Thus:

F = ( F 1 - F 2 ) α (Φ2 iΦ1+ Φ1 iΦ2 )

∴ F α Φ2 Φ1 sin θ α T
Induction relays can be grouped into three classes as set out below.

Shaded-pole relay
In this case a portion of the electromagnetic section is short-circuited by means of a copper
ring or coil. This creates a flux in the area influenced by the short circuited section (the so-
called shaded section) which lags the flux in the nonshaded section, see Figure 5.

igure 5 Shaded-pole relay

Figure 6 Wattmetric-type relay


with the upper and lower coils fed by different values or, in some cases, with just one supply for the
top coil, which induces an out-of-phase flux in the lower coil because of the air gap. Figure 6
illust r ates a typical arrangement.

Cup-type relay

This type of relay has a cylinder similar to a cu which can rotate in the annular air gap between the
poles of the coils, and has a fixed central core, see Figure 7. The operation of this relay is very similar
to that

Figure 7Cup-type relay


Of an induction motor with salient poles for the windings of the stator. Configurations with
four or eight poles spaced symmetrically around the circumference of the cup are often used.
The movement of the cylinder is limited to a small amount by the contact and the stops. Α
special spring provides the restraining torque.

The torque is a function of the product of the two currents through the coils and the cosine of
the angle between them. The torque equation is

T= ( KI1I2 cos (θ12 – Φ) – Ks ),

Where K, .Κs and Φ are design constants, Ι1 and I2 are the currents through the two coils and
θ12 is the angle between I1 and I2.

In the first two types of relay mentioned above, which are provided with a disc, the inertia of
the disc provides the time-delay characteristic. The time delay can be increased by the addition
of a permanent magnet. The cup-type relay has a small inertia and is therefore principally used
when high speed operation is required, for example in instantaneous units.
2.Calculation of short circuit current

The current that flows through an element of a power system is a parameter which can be used to
detect faults, given the large increase in current flow when a short circuit occurs.
For this reason a review of the concepts and procedures for calculating fault currents will be
made in this chapter, together with some calculations illustrating the methods used.
Although the use of these short-circuit calculations in relation to protection settings will be-
considered in detail, it is important to bear in mind that these calculations are also required for
other applications, for example calculating the substation Earthing grid, the selection of
conductor sizes and for the specifications of equipment such as power-circuit breakers.

1 Mathematical derivation of fault currents


The treatment of electrical faults should be carried out as a function of time,
+
from the start of the event at time t = 0 until stable conditions are reached, and therefore it is
necessary to use differential equations when calculating these currents. In order to illustrate the
transient nature of the current,
consider an RL circuit as a simplified equivalent of the circuits in electricity-distribution
networks. This simplification is important because all the system equipment must be modeled in
some way in order to quantify the transient values which can occur during the fault condition.
For the circuit shown in Figure 1, the mathematical expression which defines the behaviour of
the current is:

e(t) = L di + Ri(t) 2.1

V max Sin (ω t + α )
R

Figure 1 RL, circuit for transient analysis study

This is a differential equation with constant coefficients, of which the solution is in two
parts:

ia (t ) : ih (t ) + ip (t )
Where:
ih(t) Is the solution of the homogeneous equation corresponding to the transient period and
ip(t) is the solution to the particular equation corresponding to the steady-state period.

By the use of differential equation theory, which will not be discussed in detail here, the
complete solution can be determined and expressed iii the following form:

Vmax
i(t ) = (Sin (ω t + α ) − Sin(α − Φ).e −( R / L) ) 2.2
Z

Where:

Z = R 2 + ω 2 L2

α = the closing angle which defines the point on the source sinusoidal voltage when the fault
occurs and

Φ = tan −1 (ωL / R )
It can be seen that, in eqn. 2.2, the first term varies sinusoidally, while the second
term decreases exponentially with a time constant of L/R. The latter term can be recognised
as the DC component of the current, and has an initial maximum
value when α − Φ = ±π / 2 , and zero value when Φ=α, see Figure 2.
It is impossible to predict at what point the fault will be applied on the sinusoidal cycle and
therefore what magnitude the DC component will reach. If the tripping of the circuit, owing
to a fault, takes place when the sinusoidal component is at its negative peak, the DC
component reaches its theoretical maximum value half a cycle later.
Figure 2 Variation of fault current with time

a (α–Φ) =0

b (α–Φ)=π/2

An approximate formula for calculating the effective value of the total asymmetric
current,
including the AC and DC components, with acceptable accuracy can be obtained from the
following expression:

I rms . asym = 2
I rms + I DC
2
2 .3
The fault current which results when an alternator is short circuited can easily be
analysed since this is similar to the case which has already been analysed, i.e. when voltage is,
applied to an RL circuit. The reduction in current from its value at the onset, owing to the
gradual decrease in the magnetic flux caused by the reduction of the e.m.f. of the induction
current, can be seen in Figure 3. This effect is known as armature reaction.
The physical situation that is presented to a generator, and which makes the
calculations quite difficult, can be interpreted as a reactance which varies with time.
Notwithstanding this, in the majority of practical applications it is possible to take account of
the variation of reactance in only three stages without producing significant errors. In Figure
4 it will be noted that the variation of current with time, 1(t), comes close to the three
discrete levels of current, I", 1 ' and I, the subtransient, transient and steady-state currents,
" '
respectively. The corresponding values of direct axis reactance are denoted by X d , X d and
Xd,

Figure 3 Transient short-circuit currents in


a synchronous generator

Figure 4 Variation of current with time during


a fault
Figure 5 Variation of generator reactance with
time during a fault
And the typical variation with, time for each of these is illustrated in
Figure 5.
To sum up, when calculating short-circuit currents it is necessary to take into account two
factors which could result in the currents varying with time:
the presence of the DC component;
the behaviour of the generator under short circuit conditions.

In studies of electrical protection some adjustment has to be made to the values of


instantaneous short circuit current calculated using subtransient reactance's which result in
higher values of current.
Time delay units can be set using the same values but, in some cases, short-circuit values
based on the transient reactance are used, depending on the operating speed of the protection
relays. Transient reactance values are generally used in stability studies.
Of necessity, switchgear specifications require reliable calculations of the short-
circuit levels which can be present on the electrical network. Taking into account the rapid
drop of the short-circuit current due to the armature reaction of the synchronous machines,
and the fact that extinction of an electrical arc is never achieved instantaneously, ANSI
Standards C37.010 and C37.5 recommend using different values of subtransient reactance
when calculating the so-called momentary and interrupting duties of switchgear.
Asymmetrical or symmetrical r.m.s. values can be defined depending on whether or
not the DC component is included. The peak values are obtained by multiplying the R.M.S.
values by 2 .

The asymmetrical values are calculated as the square root of the sum of the squares of
the DC component and the r.m.s. value of the AC current, i.e.:

= (0.9 2V / X d" ) 2 + (0.9V / X d" ) 2


I rms = I DC
2
+ I AC
2
2.4
The momentary current is used when specifying the closing current of switchgear.
Typically, the AC and DC components decay to 90% of their initial values after the first half
cycle. From this, the value of the r.m.s. current would then be:

. asym .clo sin g = + I AC .rms .sys


2 2
I rms I DC

= (0.9 2V / X d" ) 2 + (0.9V / X d" ) 2

= 1.56V / X d" = 1.56 I rms.sym 2.5

Usually, a factor of 1.6 is used by manufacturers and in international standards so that, in


general, this value should be used when carrying out similar calculations.
The peak value is obtained by arithmetically adding together the AC and DC
components. It should be noted that, in this case, the AC component is multiplied by a factor of
2 Thus:

I peak = I Dc + I AC
= (0.9 2V / Xd" ) + (0.9 2V / Xd" )

= 2.55 Irms.sym 2.6


When considering the specification for the switchgear-opening cur-rent, the so-called r.m.s.
value of interrupting current is used in which, again, the AC and DC components are taken into
account, and therefore:
Replacing the DC component by its exponential expression gives:

.asym . int = + I Ac.rms . int


2 2
I rms I DC

I rms . sym .int = ( 2 I rms . sym .int e − ( R / L ) ) 2 + I rms


2
. sym . int
= I rms.sym.int 2e −2( r / l )t + 1 2.7

I /I
The expression ( rms.asym. int rms . sys . int
) has been drawn for different
Values of X/R, and for different switchgear contact-separation times, in ANSI Standard
C37.5–1979. The multiplying factor graphs are reproduced in Figure 6

Figure 6 Multiplying factors for three-p hase and


line-to-earth faults (total current rating basis)
(from. IEEE Standard C37.5-1979; reproduced by
permission of the IEEE)

NOTE: Fed predominantly through two or more transformations or with external reactance in
series equal to or above 1.5 times generator subtransient reactance
As an illust r ation of the validity of the curves for any situation,
Consider a circuit breaker with a total contact-separation time of two c y c l e s o n e cycle
due to the relay and one related to the operation of the breaker mechanism. If the
frequency, f is 60 Hz and the ratio X/R
With this arrangement, voltage values of any three-phase system,
Va Vb and Vc can be represented thus:
Va =Vao + Va1 + Va2
Vb =Vbo + Vb1 + Vb2
Vc =Vco + Vc1 + Vc2

It can be demonstrated that:

V b= V ao+a 2V a1+aV a2
V c= V ao+aV a1+ a 2V a2

where a is a so called operator which gives a phase shift of 120° clockwise and a
multiplication of unit magnitude, i.e. a=1 ∠120 °,
and a 2 similarly gives a phase shift
of 240°, i.e. a 2=1 ∠240° Therefore,
the following matrix relationship can be established:

⎡Va ⎤ ⎡1 1 1 ⎤ ⎡Va 0 ⎤
⎢V ⎥ = ⎢1 a a 2 ⎥ × ⎢V ⎥
⎢ b⎥ ⎢ ⎥ ⎢ a1 ⎥
⎢⎣Vc ⎥⎦ ⎢⎣1 a a ⎥⎦ ⎢⎣Va 2 ⎥⎦
2

Inverting the matrix of coefficients:

⎡Va 0 ⎤ ⎡1 1 1 ⎤ ⎡V a ⎤
⎢V ⎥ = 1 ⎢1 a a 2 ⎥ × ⎢V ⎥
⎢ a1 ⎥ 3 ⎢ ⎥ ⎢ b⎥
⎢⎣Va 2 ⎥⎦ ⎢ ⎥
⎣1 a a ⎦ ⎢⎣Vc ⎥⎦
2

From the above matrix it can be deduced that:


1
Va 0 = (Va + Vb + Vc )
3
1
Va1 = (Va + aVb + a 2Vc )
3
1
Va 2 = (Va + a 2Vb + aVc )
3

The foregoing procedure can also be applied directly to currents, and gives:

I a = I a 0 + I a1 + I a 2
I b = I a 0 + a 2 I a1 + aI a 2
I b = I a 0 + a I a1 + a 2 I a 2
Therefore:

1
Ia0 = (Ia + Ib + Ic )
3
1
I a1 = ( I a + aI b + a 2 I c )
3
1
I a 2 = ( I a + a 2 I b + aI c )
3
In three-phase systems, the neutral current is equal to In = (Ia + Ib + Ic) and, therefore, l n= 3 I 0
By way of illustration, a three-phase unbalanced system is shown in Figure 8 together with the
associated symmetrical components.
2.1 Importance and construction of sequence networks

The impedance of a circuit in which only positive-sequence currents are circulating is


called the positive-sequence impedance and, similarly, those in which only negative and
zero-sequence currents flow are called the negative and zero-sequence impedances.
These sequence impedances are designated Z1, Z2 and Z0, respectively, and are used in
calculations involving symmetrical components.
Since generators are designed to supply balanced voltages, the generated voltages are of
positive sequence only.
Therefore, the positive-sequence network is composed of an e.m.f source in series with the
positive-sequence impedance. The negative and zero-sequence net-works do not contain
e.m.f but only include impedances to the flow of negative and zero-sequence currents,
respectively.
The positive- and negative-sequence impedances of overhead-line circuits are identical, as
are those of cables, being independent of the phase if the applied voltages are balanced.
The zero-sequence impedances of lines different from the positive and negative-sequence
impedances since the magnetic field creating the positive and negative-sequence currents is
different from that for the zero-sequence currents. The following ratios may be used in the
absence of detailed information. For a single-circuit line, Zo/Z1 = 2 when no earth wire is
present and 3.5 with an earth wire. For a double-circuit line Zo/Z1 = 5.5. For underground
cables Zo/Z1 can be taken as 1 to 1.25 for single core, and 3 to 5 for three-core cables:

For transformers, the positive and negative-sequence impedances are equal because in static
circuits these impedances are independent of the phase order, provided that the applied
voltages are balanced. The zero-sequence impedance is either the same as the other two
impedances, or infinite, depending on the transformer connections. The resistance of the
windings is much smaller and can generally be neglected in short-circuit calculations. When
modelling small generators and motors it may be necessary to take resistance into account.
However, for most studies only the reactance's of synchronous machines are used. Three
values of positive reactance are normally quoted-subt r ansient, transient and synchronous
reactance, denoted by X", Xd' and Xd. In fault studies the subtransient and transient reactance
of generators grid motors must be included as appropriate, depending on the machine
characteristics and fault clearance time.
Table 1 Typical per-unit reactance for three -phase synchronous machines

Type of
machine
X d" X d' Xd X2 X0
Turbine 2 pole 0.09 0.15 1.20 0.09 0.03
generator 4 pole 0.14 0.22 1.70 0.14 0.07

Salient with 0.20 0.30 1.25 0.20 0.18


pole dampers
generator without 0.28 0.30 1.20 0.35 0.12
dampers
X"= subtransient reactance; X'd =transient reactance; Xd=synchronous
reactance X.2=negative sequence reactance; X0=zero sequence reactance

The subtransient reactance is the reactance applicable at the onset of the fault occurrence.
Within 0.1 sec. the fault level falls to a value determined by the transient reactance and then
decays exponentially to a steady-state value determined by the synchronous reactance.
Typical per-unit reactance's for three phase synchronous machines are given in Table 1.
In connecting sequence networks together, the reference busbar for the positive- and
negative-sequence networks is the generator neutral which, in these networks, is at earth
potential so that only zero-sequence currents flow through the impedances between neutral
and earth. The reference busbar for zero-sequence networks is the earth point of the
generator. The current which flows in the impedance between the neutral and earth are three
times the zero-sequence current. Figure 2.9 illustrates the sequence networks for a generator.
The zero sequence networks carries only zero-sequence current in one phase which has an
impedance of Zo = 3Ζn + Zeo
The voltage and current components for each phase are obtained from the equations given
for the sequence networks. The equations for the components of voltage, corresponding to the
phase of the system, are obtained from the point an on phase a relative to the reference bus
bar, and can be deduced from Figure 2.9 as follows:

Va1 = E a − I a1 Z 1
Va 2 = − I a 2 Z 2
Va 0 = − I a 0 Z 0

Where
Εa = no load voltage to earth of the positive-sequence network
Z1 = positive-sequence impedance of the generator
Z2 = negative-sequence impedance of the generator
Zo= zero-sequence impedance of the generator (Zeo) plus three times the impedance to
earth
The above equations can be applied to any generator which carries unbalanced currents and
are the starting point for calculations for any type of fault. The same approach can be used
with equivalent power systems or applied to loaded generators, Ea then being the voltage
behind the reactance before the fault occurs.

2.2.2 Calculation of asymmetrical faults using symmetrical components


The positive, negative and zero-sequence network, carrying currents I1, I2 and Io
respectively, are connected together in a particular arrangement to represent a given
unbalanced fault condition. Consequently, in order to calculate fault 1 levels using the
method of symmetrical components, it is essential to determine the individual sequence
impedances and combine these to make up the correct sequence networks. Then, for each
.type of fault, the appropriate combination of sequence networks is formed in order to
obtain the relationships between fault currents and voltages.
Phase-to-earth fault
The conditions for a solid fault from line a to earth
are represented by the equations Ib=0, Ic =0 and V a =0,
Single phase fault connected to earth

As in the previous equations, it can easily be deduced


that I a1 = I a2 = I ao = Ea / (Z1 +Z 2 + Zo ). Therefore,
the sequence networks will be connected in series,
as indicated in Figure 2.10a. The current and voltage
conditions are the same when considering an open-circuit
fault in phases b and c, and thus the treatment
and connection of the sequence networks will be similar.

Phase-to-Phase fault
The conditions for a solid fault between
lines h and c are represented by the equations

I a = 0, I b = –I c and Vb = V c .
Equally, it can be shown that
I ao = 0 and I a1 = Ea /(Z 1 +Z 2 ) = I a2 .
For this case, with no zero-sequence current,
the zero-sequence network is not involved and the overall sequence network is composed
of the positive- and negative-sequence networks in parallel as indicated in Figure 2.10b.

Phase-to-Phase-to-earth fault

The conditions for a fault between lines b and c and earth are represented by the equations 1a = 0
and Vb=Vc =0. From these equations it can be proved that:

Ea
I a1 =
ZoZ2
Z1 +
Zo + Z2

The three sequence networks are connected in parallel


as shown in Figure 2.10c.

2.3 Equivalent impedances for a power system.


When it is necessary to study the effect of any change on
the power system, the system must first of all be represented
by its corresponding sequence impedances.
The equivalent positive- and negative-sequence impedances
can be calculated directly from:
Z= V2/P

Where:
Z = Equivalent positive and negative-sequence impedances
V =nominal phase-to-phase voltage
P = three-phase short circuit power
The equivalent zero-sequence of a system can be derived from the expressions of sequence
components referred to for a single-phase fault, i.e.

Ia1=Ia2=Ia3 = VLN/ (Z1 + Z2 + Z0)

Where:
VLN = the line-to-neutral voltage.

For lines and cables the positive and negative ímpedances are equal.
Thus, on the basis that the generator ímpedances are not significant in most distribution-network
fault studies, it may be assumed that overall
Ζ2 = Z1 which simplifies the calculations.
Thus, the above formula reduces to Ia = 3I0 = 3 VLN / (2Z1 + Zo),
Where VLN = line-to-neutral voltage and Zo= (3VLN / Ia) - 2Z1

3 Supplying the current and voltage signals to protection systems


In the presence of a fault the current transformers (CTs) circulate current proportional to the fault
current to the protection equipment without distinguishing between the vectorial magnitudes of
the Sequence components.
Figure 10 Connection of sequence networks for a3ymmetrical faults
a Phase-to-earth fault
b Phase-to-phase fault
c Double phase-to-earth fault

Therefore, in the majority of cases, the relays operate on the basis of the corresponding values
of fault current and / or voltages, regardless of the values of the sequence components. It is
very important to emphasise that, given this, the advantage of using symmetrical components
is that they facilitate the calculation of fault levels even though the relays in the majority of
cases do not distinguish between the various values of the symmetrical components.
Figure 11a Currents and voltages for various types of faults
Figure 11b Currents and voltages for various types of faults
a Sequence currents for different types of fault
b Sequence voltages for different types of fault

In Figure 11a & b the positive and negative sequence values of current and voltage for
different faults are shown together with the summated values of current and voltage.
Relays usually only operate using the summated values in the right-hand columns.
However, relays are available which can operate with specific values of some of the
sequence components.
In these cases there must be methods for obtaining these components, and this is
achieved by using filters which produce the mathematical operations of the resultant
equations to resolve the matrix for voltages and for currents.
Although these filters can be constructed for electromagnetic elements, the growth of
electronics has led to their being used increasingly in logic circuits. Among the relays which
require this type of filter in order to operate are those used ιn negative-sequence and earth-
fault protection.

3.Current and voltage transformers

Current or voltage instrument transformers are necessary for isolating the protection,
control and measurement equipment from the high voltages of a power system, and for
supplying the equipment with the appropriate values of current and voltage - generally these
are 1A or 5Α for the current coils, and 120 V for the voltage coils.
The behavior of current and voltage transformers during and after the occurrence of a
fault is critical in electrical protection since errors in the signal from a transformer can cause
maloperation of the relays.
In addition, factors such as the transient period and saturation must be taken into account
when selecting the appropriate transformer.
When only voltage or current magnitudes are required to operate a relay then the relative
direction of the current flow in the transformer windings is not important. However, the
polarity must be kept in mind when the relays compare the sum or difference of the currents.

1- Voltage transformers:
With voltage transformers (VTs) it is essential that the voltage from the secondary
winding should be as near as possible proportional to the primary voltage.
In order to achieve this, VTs are designed in such a way that the voltage drops in the
windings are small and the flux density in the core is well below the saturation value so that
the magnetization current is small; in this way magnetization impedance is obtained which is
practically constant over the required voltage range. The secondary voltage of a VT is usually
110 or 120 V with corresponding line-to-neutral values. The majority of protection relays have
nominal voltages of 110 or 63.5 V, depending on whether their connection is line-to-line or
line-to-neutral.
Figure 1 Voltage transformer equivalent circuits

Figure 2 Vector diagram for voltage transformer

1.1 Equivalent circuits

VTs can be considered as small power transformers so that their equivalent circuit is
the same as that for power transformers, as shown in Figure 1a. The magnetization branch
can be ignored and the equivalent circuit then reduces to that shown in Fig 1b.
The vector diagram for a VT is given in Figure.2, with the length of the voltage
drops increased for clarity. The secondary voltage Vs lags the voltage Vp/n and is smaller
in magnitude. In spite of this, the nominal maximum errors are relatively small. VTs have
an excellent transient behaviour and accurately reproduce abrupt changes in. the primary
voltage.
1.2 Errors

When used for measurement instruments, for example for billing and control
purposes, the accuracy of a VT is important, especially for those values close to the
nominal system voltage.
Notwithstanding this, although the precision requirements of a VT for protection
applications are not so high at nominal voltages, owing to the problems of having to cope
with a variety of different relays, secondary wiring burdens and the uncertainty of
system parameters, errors should he contained within narrow limits over a wide range of
possible voltages under fault conditions.
This range should be between 5 and 173% of the nominal primary voltage for VTs
connected between line and earth.
Referring to the circuit in Figure 1a, errors in a VT are clue to differences in
magnitude and phase between Vp/n, and Vs. These consist of the errors under open-circuit
conditions when the load impedance Ζ B is infinite, caused by the drop in voltage from
the circulation of the magnetization current through the primary winding, and errors due to
voltage drops as a result of the load current IL flowing through both windings. Errors in
magnitude can be calculated from
Error V T = {(n Vs - Vp) / Vp} x 100%. If the error is positive, then the secondary voltage
exceeds the nominal value.

1.3 Burden
The standard burden for voltage transformer is usually expressed in volt-amperes (VΑ) at a
specified power factor.
Table 1 gives standard burdens based on ANSI Standard C57.1 3. Voltage transformers
are specified in IEC publication 1 8 6 Α by the precision class, and the value of volt-
amperes (VΑ).
The allowable error limits corresponding to different class values are shown in Table 2,
where Vn is the nominal voltage. The phase error is considered positive when the
secondary voltage leads the primary voltage. The voltage error is the percentage
difference between the voltage at the secondary terminals, V2, multiplied by the nominal
transformation ratio, and the primary voltages V1.

1.4 Selection of VTs


Voltage transformers are connected between phases, or between phase and earth.
The connection between phase and earth is normally used with groups of three single-
phase units connected in star at substations operating with voltages at about 34.5 kV or
higher, or when it is necessary to measure the voltage and power factor of each phase
separately.
The nominal primary voltage of a VT is generally chosen with the higher nominal
insulation voltage (kV) and the nearest service voltage in mind. The nominal secondary
voltages are generally standardized at 110 and 120 V. In order to select the nominal power of
a VT, it is usual to acid together all the nominal VΑ loadings of the apparatus connected to
Table 1 Standard burdens for voltage Transformer
Standard burden Characteristics for 120 V Characteristics for 69.3 V
and 60 Hz and 60 Hz
desig Volt- powe resistance( inductanc impedanc resistanc inductanc impedanc
n ampere r Ω) e e e e e
s facto (H) (Ω) (Ω) (H) (Ω)
r
W
12.5 0.10 115.2 3.040 1152 38.4 1.010 384
Χ 25.0 0.70 403.2 1.090 575 134.4 0.364 192
Υ 75.0 0.85 163.2 0.268 192 54.4 0.089 64
Ζ 200.0 0.85 61.2 0.101 72 20.4 0.034 24
ΖΖ 400.0 0.85 31.2 0.0403 36 10.2 0.0168 12
Μ 35.0 0.20 82.3 1.070 411 27.4 0.356 137

Table 2 Voltage transformers error limits


Class Primary Voltage Phase error
voltage error (±min)
(±%)
0.1 0.1 0.5
0.2 0.2 10.0
0.5 0.5 20.0
1.0 1.0 40.0
0.8 Vn , 1.0
Vn and 1.2
Vn

0.1 1.0 40.0


0.2 1.0 40.0
0.5 0.5 Vn 1.0 40.0
1.0 2.0 80.0

0.1 0.2 80.0


0.2 2.0 80.0
0.5 Vn 2.0 80.0
1.0 3.0 120.0
Vn = nominal voltage
The VT secondary winding. In addition, it is important to take account of the voltage drops
in the secondary wiring, especially if the distance between the transformers and the relays is
large.
1.5 C a p a c i t o r v o l t a g e t r a n s f o r m e r s
In general, the size of an inductive VT is proportional to its nominal voltage and, for this
reason, the cost increases in a similar manner to that of a high voltage transformer. One
alternative, and a more economic solution, is to use a capacitor voltage transformer.
This device is effectively a capacitance voltage divider, and is similar to a resistive
divider in that the output voltage at the point of connection is affected by the load - in fact the
two parts of the divider taken together can be considered as the source impedance which
produces a drop in voltage when the load is connected.

Figure 4 Capacitor VT equivalent circuit

The capacitor divider differs from the inductive divider in that the equivalent impedance
of the source is capacitive and the .fact that this impedance can be compensated for by
connecting a reactance in series at the point of connection.
With an ideal reactance there are no regulation problems - however, in an actual
situation on a network, some resistance is always present. The divider can reduce the
voltage to a value which enables errors to be kept within normally acceptable limits. For
improved accuracy a high voltage capacitor is used in order to obtain a bigger voltage at
the point of connection, which can be reduced to a standard voltage using a relatively
inexpensive trans-former as shown in Figure 3.
Α simplified equivalent circuit of a capacitor VT is shown in Figure 4 in which Vi is
equal to the nominal primary voltage, C is the numerically equivalent impedance equal to (
C1 + C2 ), L is the resonance inductance, Ri represents the resistance of the primary winding
of transformer Τ plus the losses in C and L, and Ze is the magnetization impedance of
transformer Τ. Referred to the inter-mediate voltage, the resistance of the secondary circuit and

the load impedance are represented by


Rs' and
ZB' respectively, while Vs' and I s'
represent the
secondary voltage and current.

Figure 5 Capacitor VT vector diagram


It can be seen that, with the exception of C, the circuit in Figure 4.4 is the same as the
equivalent circuit of a power transformer. Therefore, at the system frequency when C and L are
resonating and canceling out each other, under stable system conditions the capacitor VT acts
like a conventional transformer. Ri and R's are not large and, in addition, Ie is small
compared to I' s , so that the vector difference between Vi and V's which constitutes the error
in the capacitor VT, is very small.
This is illustrated in the vector diagram shown in Figure 4.5 which is drawn for a
power factor close to unity. The voltage error is the difference in magnitude between Vi and
V's, whereas the phase error is indicated by the angle θ. From the diagram it can be seen that,
for frequencies different from the resonant frequency, the values of EL and EC predominate,
causing serious errors in magnitude and phase.
Capacitor VTs display better transient behaviour than electro-magnetic VTs as the
inductive and capacitive reactance in series are large in relation to the load impedance
referred to the secondary voltage, and thus, when the primary voltage collapses, the secondary
voltage is maintained for some milliseconds because of the combination of the series and
parallel resonant circuits represented by L, C and the transformer T.

2 Current transformers
Although the performance required from a current transformer (CT) varies with the type of
protection, high grade CTs must always be used. Good quality CTs are more reliable and result
in less application problems and, in general, provide better protection.
Figure 6 Current transformer equivalent circuits
The quality of CTs is very important for differential protection schemes where the
operation of the relays is directly related to the accuracy of the CTs under fault
conditions as well as under normal load conditions.
CTs can become saturated at high current values caused by nearby faults; to avoid
this, care should be taken to ensure that under the most critical faults the CT operates on the
linear portion of the magnetization curve. In all these cases the CT should be a ble to
supply sufficient current so that the relay operates satisfactorily.
2.1 Equivalent circuit
An approximate equivalent circuit for a CT is given in Figure 4.6a,
Where n2ZH represents the primary impedance ZH referred to the secondary side, and the
secondary impedance is, ZL, Rm and Xm represent the losses and the excitation of the core.
The circuit in Figure 4.6a can be reduced to the arrangement shown in figure 4.6b where
ZH can be ignored, since it does not influence either the current IH/n or the voltage across Xm.
The current flowing through Xm is the excitation current Ιe.
The vector diagram, with the voltage drops exaggerated for clarity, is shown in Figure 4.7. In
general, ZL, is resistive and Ιe lags Vs by 90°, so that Ie is the principal source of error. Note that
the net effect of Ie is to make I lag and be much smaller than ΙH /n, the primary current referred
to the secondary side.
Figure 7 Vector diagram for the CT equivalent circuit
2.2 Errors
The causes of errors in a CT are quite different to those associated with VTs. In effect, the
primary impedance of a CT does not have the same influence
On the accuracy of the equipment it only adds an impedance in series with the line, which can
be ignored. The errors are principally due to the current which circulates through the
magnetizing branch.
The magnitude error is the difference in magnitude between ΙH / n and IL and is equal to Ir
the component of Ie in line with k (see Figure 7).
The phase error, represented by θ, is related to Iq the component of Ie which is in quadrature
with IL. The values of the magnitude and phase errors depend on the relative displacement
between Ie and IL, but neither of them can exceed the vectorial error it should be noted that a
moderate inductive load, with Ie and IL approximately in phase, has a small phase error and the
excitation component results almost entirely in an error in the magnitude.

2.3 AC saturation
CΤ errors result from excitation current, so much so that, in order to check if a CT is
functioning correctly, it is essential to measure or calculate the excitation curve. The
magnetization current of a CT depends on the cross section and length of the magnetic circuit,
the number of turns in the windings, and the magnetic characteristics of the material.
Thus, for a given CT, and referring to the equivalent circuit of Figure 4.6b, it can be seen
that the voltage across the magnetization impedance, Es, is directly proportional to the secondary
current. From this it can be concluded that, when the primary current and therefore the secondary
current is increased, these currents reach a point where the core commences to saturate and the
magnetization current becomes sufficiently high to produce an excessive error.

When investigating the behaviour of a CT, the excitation current should he measured at
various values of voltage the so-called secondary injection test. Usually, it is more convenient to
apply a variable voltage to the secondary winding, leaving the primary winding open-circuited.
Figure 4.8a shows the typical relationship between the secondary voltage and the excitation
current determined in this way.
In European standards the point Κp on the curve is called the saturation or knee point and
is defined as the point at which an increase in the excitation voltage of ten per cent produces an
increase of 50 % in the excitation current. This point is referred to in the ANSI / IEEE standards
as the intersection of the excitation curves with a 45° tangent line, as indicated in Figure 4.8b.
The European knee point is at a higher voltage than the ANSI/IEEE Knee point.

2.4 Burden
The burden of a CT is the value in ohms-of the impedance on the secondary side of the CT
due to the relays and the connections between the CT and the relays. By way of example, the
standard burdens for CTs with a nominal secondary current of 5 A are shown in Table 3, based
on ANSI Standard C57.13.
IEC Standard Publication 185(1987) specifies CTs by the class of accuracy followed by the
letter Μ or P, which denotes whether the transformer is suitable for measurement or protection
purposes, respectively. The current and phase-error limits for measurement and protection CTs
are given in Tables 4a and 4.4b. The phase error is considered positive when the secondary
current leads the primary current.
The current error is the percentage deviation of the secondary current, multiplied by the
nominal transformation ratio, from the primary current, i.e. {(CTR x Ι2) – I1} ÷ I1 (%), where I1
= primary current (A), I2 = secondary current (A) and CTR = current transformer transformation
ratio. Those CT classes marked with `ext' denote wide range (extended) current transformers
with a rated continuous current of 1.2 or 2 times the nameplate current rating.
2.5 Selection of CTs
When selecting a CT, it is important to ensure that the fault level and normal load
conditions do not result in saturation of the core and that

CT magnetization curves

Figure 8a CT magnetization curves


Figure 8b CT magnetization curves
a Defining the knee point in a CT excitation curve according to European
standards
b Typical excitation curves for a multi ratio class C CT (From IEEE
Standard C57.13-1978; reproduced by permission of the IEEE).
Table 4.3 Standard burdens for protection
CTs with 5 Α secondary current

Designation Resista nce Inductance Impedance Volt- Power


amps
(Ω) (mH) (Ω) factor
(at 5 A)
0.5
B-1 2.3 1.0 25 0.5
B-2 1.0 4.6 2.0 50 0.5

B-4 2.0 9.2 4.0 100 0.5

B-8 4.0 18.4 8.0 200 0.5

The errors do not exceed acceptable limits. These factors can be assessed from:
formulae;
CT magnetization curves;
CT classes of accuracy.
The first two meth ods provide precise facts for the selection of the CT. The third only
provides a qualitative estimation. The secondary voltage Ε in Figure 4.6U has to be
determined for all three methods. If the impedance of the magnetic circuit, Xm is high,
this can be removed from the equivalent circuit with little error' giving Es=Vs and thus:

Vs=IL (ZL+ZC+ZB) (1)

Where
Vs = r.m.s. voltage induced in the secondary winding
=maximum secondary current in amperes;
this can be determined by dividing the maximum
Fault current on the system by the transformer
turns ratio selected
ZB = e x t e r n a l impedance connected
ZL = impedance of the secondary winding
ZC =impedance of the connecting wiring
Use of the formula
This method utilizes the fundamental transformer equation:
Vs = 4.44.f. Α. N. Bmax.1 0 -8 V (2)
Where
f =frequency in Hz,
Α =cross-sectional area of core (cm2)
Ν =number of turns
Bmax =flux density (lines/cm2)

Table 4α Error limits for measurement current transformers


Class % current error at the given % phase error at the given proportion of the
proportion of rated current rated current shown below
shown below

2.0*1.2 1.000.500.20 0.10 2.0* 1.2 1.0 0.5 0.2 0.1 0.05
0.05

0.1 0.1 0.1 0.2 0.25 5 5 8 10


0.2 0.2 0.2 0.350.50 10 10 15 20
0.5 0.5 0.5 0.751.00 30 30 45 60
1.0 1.0 1.0 1.5 2.00 60 60 - 90 120 -
3.0 3.0 3.0 - - - _ 120 - 120 - - -

-
0.1 0.1 0.1 0.2 0.25 0.4 5 - 5 8 10 15
0.2 0.2 0.2 0.350.50 0.75 10 - 10 15 20 30
ext
0.5 0.5 0.5 0.751.00 1.5 30 - 30 45 60 90
ext
1.0 1.0 1.0 1.5 2.00 60 - 60 - 90 120 -
ext
3.0 3.0 - - 3.0 - - - 120 - - 120 - - -
ext
*ext = 200 %
Table 4b Error limits for protection current transformers

+/- percentage
Accuracy +/- Phase error
Current
Class (minutes)
ratio error
% Current 5 20 100 120 5 20 100 120
0.1 0.4 0.2 0.1 0.1 15 8 5 5
0.2 0.75 0.35 0.2 0.2 30 15 10 10
0.5 1.5 0.75 0.5 0.5 90 45 30 30
1.0 3 1.5 1.0 1.0 180 90 60 60

Total error for nominal error limit current and nominal load is five per cent for 5P and 5Ρ ext
CTs and ten per cent for 10P and 10P ext CTs.
The cross-sectional area of metal and the saturation flux density are sometimes difficult to
obtain.
The latter can be taken as equal to 100 000 lines/Cm2, which is a typical value for modern
transformers. To use the formula, V is determined from eqn. 4.1 and Bmax. is then calculated
using eqn. 2. If Bmax.
Exceeds the saturation density, there could be appreciable errors in the secondary current and
the CT selected would not be appropriate.
Example 1.
Assume that a CT with a ratio of 2000/5 is available, having a steel core of high
permeability, a cross-sectional area of 3.25 In cm2 and a secondary winding with a resistance of
0.31 Ω. The impedance of the relays, including connections, is 2 Ω. Determine whether the CT
would be saturated by a fault of 35 000 A at 50 Hz.
Solution
If the CT is not saturated, then the secondary current, IL, is
35 000x 5/2000=87.5 A. N= 2000/5 = 400 turns
And Vs=87.5x (0.31+2) =202.1 V. Using eqn. 4.2, Bmax, can now be calculated:
Bmax = 202.1X108/4.44X50X3.25X400=70 030 lines/ cm2
Since the transformer in this example has a steel core of high permeability, this relatively low
value of flux density should not result in saturation.
Using the magnetization curve
Typical CT excitation curves which are supplied by manufacturers state the r.m.s. current
obtained on applying an r.m.s. voltage to the secondary winding, with the primary winding open-
circuited.
The curves give the magnitude of the excitation current required order to obtain a specific
secondary voltage.
The method consists of producing a curve which shows the relationship between the
primary and secondary currents for one tap and specified load conditions, such as shown in
Figure 4.9.
Starting with any value of secondary current, and with the help of the magnetisation curves, the
value of the corresponding primary current can be determined. The process is summarized in the
following steps:
(a) Assume a value for IL.
(b) Calculate Vs in accordance with eqn. 4.1.
(c) Locate the value of Vs on the curve for the tap selected, and find the associated value of
the magnetization current, Ie.
(d) Calculate I H / n (=IL + Ie) and multiply this value by n to refer it to the primary side of the
CT.
(e) This provides one point on the curve of IL against IH, and the process is then repeated
to obtain other values of IL and the resultant values of IH. By joining the points together the
curve of IL against IH is obtained.

Figure 4.9 using the magnetization


curve
a - assume a value for IL.
b - Vs = I L ( Z L + Z C + Z B )
c - find I e from the curve
d - IH=n(I1,+ I e )
e - draw the point on the curve

This method incurs an error in calculating I H /n by adding I e and IL together


arithmetically and not vectorially, which implies not taking account of the load angle and
the magnetizations branch of the equivalent circuit. However, this error is not great and the
simplification snakes it easier to carry out the calculations.
After construction, the curve should be checked to confirm that the maximum
primary fault current is within the transformer saturation zone. If not, then it will be
necessary to repeat the process, changing the tap until the fault current is within the linear
part of the characteristic.
In practice it is not necessary to draw the complete curve because it is sufficient to
take the known fault current and refer to the secondary winding, assuming that there is no
saturation for the tap selected.
This converted value can be taken as IL initially for the process described earlier. If
the tap is found to be suitable after finishing the calculations, then a value of I H can be
obtained which is closer to the fault current.

Accuracy classes established by the ANSI standards


The ANSI accuracy class of a CT (Standard C57.13) is described by two symbols —
a letter and a nominal voltage; these define the capability of the CT.
C indicates that the transformation ratio can be calculated, and T indicates that the
transformation ratio can be determined by means of tests. The classification C includes
those CTs with uniformly distributed windings and other CTs with a dispersion flux which
has a negligible effect on the ratio, within defined limits.
The classification T includes those CTs with a dispersion flux which considerably
affects the transformation ratio.
For example, with a CT of class C—100 the ratio can be calculated, and the error should
not exceed ten per cent if the secondary current does not go outside the range of 1 to 20
times the nominal current and if the load does not exceed 1Ω (1Ω x 5 Ax 20=100 V) at a
minimum power factor of 0.5.
These accuracy classes are only applicable for complete windings. When considering a
winding provided with taps, each tap will have a voltage capacity proportionally smaller,
and in consequence it can only feed a portion of the load without exceeding the ten per cent
error limit. The permissible load is defined as ZB= (NP Vc) / 100, where ZB, is the
permissible load for a given tap of the CT, NP, is the fraction of the total number of turns
being used and Vc is the ANSI voltage capacity for the complete CT.

2.6 DC saturation
Up to now, the behavior of a CT has been discussed in terms of a steady state, without
considering the DC transient component of the
DC saturation is particularly significant in complex protection schemes since, in the case of
external faults, high fault currents circulate through the CTs.
If saturation occurs in different CTs associated with a particular relay arrangement,
this could result in the circulation of unbalanced secondary currents which would cause the
system to malfunction.
2.7 Precautions when working with CTs
Working with CTs associated with energized network circuits can be extremely hazardous. In
particular, opening the secondary circuit of a CT could result in dangerous over voltages
which might harm operational staff or lead to equipment being damaged, because the current
transformers are designed to be used in power circuits which have impedance much greater
than their own.
As a consequence, when secondary circuits are left open, the equivalent primary-circuit
impedance is almost unaffected but a high voltage will be developed by the primary current
passing through the magnetizing impedance Thus, secondary circuits associated with CTs
must always he kept in a closed condition or short-circuited in order to prevent these adverse
situations occurring. To illustrate this, an example is given next using typical data for a CT
and a 13.2 kV feeder.

Choice of CT’s Primary rating

The c. t. primary rating is usually chosen to be equal to or greater than the normal full load
current o f the protected circuit. Standard primary ratings are given in B.S. 3938:1973.
Generally speaking, the maximum ratio of CT’s is usually limited to about 3000/1. This is due
to
(I) limitation of size of CT’s and more importantly
(II) the fact that the open circuit volts would be dangerously high for large CT’s Primary
ratings, such as those encountered on large turbo alternators, e.g. 5,000 amperes. It is standard
practice in such applications to use a cascade arrangement of say 5,000/20A together with
20/1A interposing auxiliary CT’s

Instantaneous over current relays

Class P method of specification will a suffice. A secondary accuracy limit current greatly in
excess of the value t o cause relay operation serves no useful purpose and a rated accuracy
limit of 5 will usually be adequate.
When such relays are set to operate at high values of over current, say from 5 to 15 times the
rated current o f the transformer, the accuracy limit factor must be at least as high as the value
of the setting current used in order to ensure fast relay operation.
Rated outputs higher than 15VA and rated accuracy limit factors higher than 10 are not
recommended for general purposes. It is possible, however, to combine a higher rated accuracy
limit factor with a lower rated output and vice versa. But when the product of these two
exceeds 150 the resulting current transformer may be uneconomical, and/or of unduly large
dimensions.
Over current relays with Inverse and Definite Minimum Time
(IDMT) lag characteristic

In general, for both directional and non-directional relays class 10P current transformers
should be used

Earth fault relays with inverse time characteristic

(1) Schemes in which phase fault current stability and accurate time grading are not required.
Class 10P current transformers are generally recommended in which the product of rated
output and rated accuracy limit fact or approaches 150 provided that the earth fault relay is
not set below 20% of the rated current of the associated current transformer and that the
burden of the relay at its setting current does not exceed 4VA.

(2) Schemes in which phase fault stability and/or where time grading is critical.
Class 5P current transformers in which the product of rated output and accuracy
limit factor approaches 150 should be used.

They are in general suitable for ensuring phase fault stability up to 10 times the rated primary
current and for maintaining time grading of the earth f a u l t relays, up to current values of the
order of 10 times the earth fault setting provided t h a t the phase burden effectively imposed
on each current transformer does not exceed 50% of it s rated burden.
The rated accuracy limit factor is not less than 10 the earth fault relay is not set below 30 %
The burden of the relay at its setting does not exceed 4VA
The use of a higher relay setting the use of an earth fault relay having a burden of less than
4VA at its setting The use of current transformers having a product of rated output and rated
accuracy factor in excess of 150.

Class “X” Current Transformer

Protection current transformers specified in terms of complying with Class ' X I


Specification is generally applicable to unit systems where balancing of outputs from each end
of the protected plant is vital.
This balance, or stability during through fault conditions, is essentially of a transient nature and
thus the extent of the unsaturated (or linear) zone is of paramount importance. Hence a
statement of knee point voltage is the parameter of prime importance and it is normal to derive,
from heavy current test results, a formula stating the lowest permissible value of VK if stable
operation is to be guaranteed, e.g.

Vk = K In (RCT + 2RL + R0)

Where
K - Is a constant found by realistic heavy current tests?
In - rated current of C.T. and relay
RCT - secondary winding resistance of the line current transformers
RL - lead burden (route length) in ohms
Ro - any other resistance (or impedance) in circuit

4.Protection Scheme

1 - Feeders Protection Schemes.


2 - Transformers Protection Schemes.
3 - Bus Bar Protection Schemes.
4 - Generators Protection Schemes.

Types and voltage level of Feeders


A – O. H. T. Lines

• 500 KV O. H. T Line
• 400 KV O. H. T Line
• 275 KV O. H. T Line
• 220 KV O. H. T Line
• 132 KV O. H. T Line
• 66 KV O. H. T Line
• 33 KV O. H. T Line
• 22 KV O. H. T Line
• 11 KV O. H. T Line
B – U. G. Cables

• 275 KV U. G. Cable
• 220 KV U. G. Cable
• 132 KV U. G. Cable
• 66 KV U. G. Cable
• 33 KV U. G. Cable
• 11 KV U. G. Cable
500, 400, 275 and 220 KV O.H.T. Lines
Protection Schemes
• Main (A) Protection:
Distance Protection Permissive Over Reach Scheme. (POTT)
• Main (B) Protection:
Distance Protection Permissive Under Reach Scheme. (PUTT)
• Backup Protection:
1. I.D.M.T Directional O/C & E/F Relay.
2. Circuit Breaker Fail to Tripe.
3. Inter Trip.
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip (For Cable Tail )
Drawing : single Line diagram for
protection scheme Click Here
132 and 66 KV O.H.T. Lines
Protection Schemes
• Main Protection:
Distance Protection Permissive Under Reach Scheme. (PUTT)
• Back up Protection:
1. I.D.M.T Directional O/C & E/F Relay.
2. Circuit Breaker Fail To Tripe.
3. Inter Trip.
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip (For Cable Tail)
Drawing : single Line diagram for
protection scheme Click Here
33 and 22 KV O.H.T. Lines
Protection Schemes
• I.D.M.T Direction O/C & EF Relay
• I.D.M.T Non Direction O/C & EF Relay

11 KV O.H.T. Lines
Protection Schemes

• I.D.M.T Direction O/C & EF Relay

275, 220 U.G.C. Line


Protection Scheme
• Main (A) Protection:
Differential Protection (Solkor – R)
• Main (B) Protection:
Distance Protection Permissive Over Reach Scheme. (POTT) With Carrier Signal through
Pilot Cable
• Back up Protection:
1. I.D.M.T Directional O/C & E/F Relay.
2. Circuit Breaker Fail to Tripe
3. Inter Trip.
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip
132, and 66 KV U.G.C. Line
Protection Scheme
• Main Protection:
Differential Protection (Solkor – R)
• Back up Protection:
1. I.D.M.T Directional O/C & E/F Relay.
2. Circuit Breaker Fail to Tripe.
3. Inter Trip (Through Pilot Cable).
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip
33, 22 KV U.G.C. Line
Protection Scheme
• Main Protection:
Differential Protection (Solkor – R)
• Back up Protection:
• I.D.M.T Directional O/C & E/F Relay.
• I.D.M.T Non Directional O/C & E/F Relay.
• Cable Oil Pressure Low Trip.
11 KV U.G.C. Line
Protection Scheme
• Main Protection:
Differential Protection (Solkor – R)
• Back up Protection:
• I.D.M.T Non Directional O/C & E/F Relay.

Transformers Protection Schemes

Some types of power transformers


300 MVA. 3 Winding Power Transformer
275 KV / 132 KV / 33 KV. (Y.Y.Δ).
75 MVA. & 45 MVA. 2 Winding Power Transformer 1
32 KV / 33 KV.
30 MVA 2 Winding Power Transformer
132 KV / 11 KV.
20 MVA & 15 MVA 2 Winding Power Transformer
33 KV / 11 KV.
Drawing : single Line diagram for
protection scheme Click Here
300 MVA 3 Winding Power Transformer
Protection Scheme.
• Main (A&B) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection. (both at 275 kv and 132 kv)
side neutral of the star winding.
• BackupProtection:
1. C.B Fail to trip.
2. I.D.M.T Non Direction O/C & E/F relay on 300 KV side
3. I.D.M.T Direction O/C & E/F relay on 132 KV side
4. Inter Trip (through pilot cable).
5. Buchhols Trip.
6. Tap Changer Buchhols Trip.
7. Oil Temperature Trip.
8. Winding Temperature Trip.
9. Cable oil pressure Low Trip. (for cable tails )
10. SF6 pressure Low Trip.

75, 45 And 30 MVA- 2 Winding Power Transformer


Protection Scheme.
• Main (A) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection.
(At the neutral of the LV. Winding).
• Backup Protection:
1. Stand-By Earth Fault relay at the neutral of LV. Winding.
2. C.B Fail to trip. (For 132 KV. C.B only)
3. I.D.M.T Non Direction O/C & E/F relay on 132 KV side
4. Inter Trip (through pilot cable).
5. Buchhols Trip.
6. Tap Changer Buchhols Trip.
7. Winding Temperature Trip.
8. Cable oil pressure Low Trip. (For cable tails)

20 & 15 MVA- 33 / 11 KV, 2 Winding Power Transformer


Protection Scheme.
• Main (A) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection.
(At the neutral of the LV. Winding).

• Backup Protection:
1. Stand-By Earth Fault relay at the neutral of LV. Winding.
2. I.D.M.T Non Direction O/C & E/F relay on 33 KV side
3. Inter Trip (through pilot cable).
4. Buchhols Trip.
Bus-Bar Protection Schemes

Bus-Bar Protection Schemes.

• 500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme.
- Differential Protection For each section of bus-bar.
- SF6 Pressure low Trip.

• 66 and 33 KV. Bus-Bar Protection Scheme.


- Differential Protection For each section of bus-bar or Arc protection or Micro switch
protection.
- SF6 Pressure low Trip.

• 22 and 11 KV BUS-Bar Protection Scheme.


- Arc protection or Micro switches protection.

• 500, 400, 275, and 220 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.
- SF6 Pressure Trip.
- Inter Trip (through pilot cable).

• 132 KV BB section & BB couplers protection scheme.


- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.

• 33 KV BB section & BB couplers protection scheme.


- I.D.M.T Non Directional O/C & E/F Relay.

• 11 KV BB section & BB couplers protection scheme.


- I.D.M.T Non Directional O/C & E/F Relay.

Shunt Reactor Protection Scheme.


275 &132 KV. Shunt Reactor Protection Scheme.
• I.D.M.T Non Direction O/C & E/F relay.
• Inter Trip (through pilot cable – SHR connected through cable C.B. “for 132 kV only”).
• Buchhols Trip.
• Oil Temperature Trip.
• Winding Temperature Trip.
• Cable oil pressure Low Trip. (For cable tails)
• SF6 pressure Low Trip.
• C.B Fail to trip. (For 132 KV. C.B only).

33 KV. Shunt Reactor Protection Scheme for both connected


to 33 KV Bus-Bar or to tertiary of 300 MVA Transformer.

• I.D.M.T Non Direction O/C & E/F relay.


• Buchhols Trip.
• Oil Temperature Trip.
• Winding Temperature Trip.
Protection Scheme
1 - Feeders Protection Schemes.
2 - Transformers Protection Schemes.
3 - Bus Bar Protection Schemes.
4 - Generators Protection Schemes.

Types and voltage level of Feeders

A – O. H. T. Lines

• 500 KV O. H. T Line

• 400 KV O. H. T Line

• 275 KV O. H. T Line

• 220 KV O. H. T Line

• 132 KV O. H. T Line

• 66 KV O. H. T Line

• 33 KV O. H. T Line

• 22 KV O. H. T Line

• 11 KV O. H. T Line

B – U. G. Cables

• 275 KV U. G. Cable

• 220 KV U. G. Cable
• 132 KV U. G. Cable

• 66 KV U. G. Cable

• 33 KV U. G. Cable

• 11 KV U. G. Cable

500, 400, 275 and 220 KV O.H.T. Lines


Protection Schemes

• Main (A) Protection:


Distance Protection Permissive Over Reach Scheme. (POTT)

• Main (B) Protection:


Distance Protection Permissive Under Reach Scheme. (PUTT)

• Backup Protection:

1. I.D.M.T Directional O/C & E/F Relay.


2. Circuit Breaker Fail to Tripe.
3. Inter Trip.
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip (For Cable Tail )
Drawing : single Line diagram for
protection scheme Click Here
132 and 66 KV O.H.T. Lines
Protection Schemes

• Main Protection:
Distance Protection Permissive Under Reach Scheme. (PUTT)
• Back up Protection:
1. I.D.M.T Directional O/C & E/F Relay.
2. Circuit Breaker Fail To Tripe.
3. Inter Trip.
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip (For Cable Tail)

Drawing : single Line diagram for


protection scheme Click Here
33 and 22 KV O.H.T. Lines
Protection Schemes

• I.D.M.T Direction O/C & EF Relay

• I.D.M.T Non Direction O/C & EF Relay

11 KV O.H.T. Lines
Protection Schemes
• I.D.M.T Direction O/C & EF Relay

275, 220 U.G.C. Line


Protection Scheme

• Main (A) Protection:


Differential Protection (Solkor – R)

• Main (B) Protection:


Distance Protection Permissive Over Reach Scheme. (POTT) With Carrier Signal through
Pilot Cable

• Back up Protection:

1. I.D.M.T Directional O/C & E/F Relay.


2. Circuit Breaker Fail to Tripe
3. Inter Trip.
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip

132, and 66 KV U.G.C. Line


Protection Scheme

• Main Protection:
Differential Protection (Solkor – R)

• Back up Protection:

1. I.D.M.T Directional O/C & E/F Relay.


2. Circuit Breaker Fail to Tripe.
3. Inter Trip (Through Pilot Cable).
4. SF6 Pressure Low Trip
5. Cable Oil Pressure Low Trip
33, 22 KV U.G.C. Line
Protection Scheme

• Main Protection:
Differential Protection (Solkor – R)

• Back up Protection:

• I.D.M.T Directional O/C & E/F Relay.

• I.D.M.T Non Directional O/C & E/F Relay.

• Cable Oil Pressure Low Trip.

11 KV U.G.C. Line
Protection Scheme

• Main Protection:
Differential Protection (Solkor – R)

• Back up Protection:

• I.D.M.T Non Directional O/C & E/F Relay.


Transformers Protection Schemes
Some types of power transformers

• 300 MVA. 3 Winding Power Transformer


275 KV / 132 KV / 33 KV. (Y.Y.Δ).

• 75 MVA. & 45 MVA. 2 Winding Power Transformer 1


32 KV / 33 KV.

• 30 MVA 2 Winding Power Transformer


132 KV / 11 KV.

• 20 MVA & 15 MVA 2 Winding Power Transformer


33 KV / 11 KV.
Drawing : single Line diagram for
protection scheme Click Here

300 MVA 3 Winding Power Transformer


Protection Scheme.
• Main (A&B) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection. (both at 275 kv and 132 kv)
side neutral of the star winding.
• BackupProtection:
1. C.B Fail to trip.
2. I.D.M.T Non Direction O/C & E/F relay on 300 KV side
3. I.D.M.T Direction O/C & E/F relay on 132 KV side
4. Inter Trip (through pilot cable).
5. Buchhols Trip.
6. Tap Changer Buchhols Trip.
7. Oil Temperature Trip.
8. Winding Temperature Trip.
9. Cable oil pressure Low Trip. (for cable tails )
10. SF6 pressure Low Trip.

75, 45 And 30 MVA- 2 Winding Power Transformer


Protection Scheme.
• Main (A) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection.
(At the neutral of the LV. Winding).
• Backup Protection:
1. Stand-By Earth Fault relay at the neutral of LV. Winding.
2. C.B Fail to trip. (For 132 KV. C.B only)
3. I.D.M.T Non Direction O/C & E/F relay on 132 KV side
4. Inter Trip (through pilot cable).
5. Buchhols Trip.
6. Tap Changer Buchhols Trip.
7. Winding Temperature Trip.
8. Cable oil pressure Low Trip. (For cable tails)

20 & 15 MVA- 33 / 11 KV, 2 Winding Power Transformer


Protection Scheme.
• Main (A) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection.
(At the neutral of the LV. Winding).

• Backup Protection:
1. Stand-By Earth Fault relay at the neutral of LV. Winding.
2. I.D.M.T Non Direction O/C & E/F relay on 33 KV side
3. Inter Trip (through pilot cable).
4. Buchhols Trip.
Bus-Bar Protection Schemes

Bus-Bar Protection Schemes.

• 500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme.
- Differential Protection For each section of bus-bar.
- SF6 Pressure low Trip.

• 66 and 33 KV. Bus-Bar Protection Scheme.


- Differential Protection For each section of bus-bar or Arc protection or Micro switch
protection.
- SF6 Pressure low Trip.

• 22 and 11 KV BUS-Bar Protection Scheme.


- Arc protection or Micro switches protection.

• 500, 400, 275, and 220 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.
- SF6 Pressure Trip.
- Inter Trip (through pilot cable).

• 132 KV BB section & BB couplers protection scheme.


- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.

• 33 KV BB section & BB couplers protection scheme.


- I.D.M.T Non Directional O/C & E/F Relay.

• 11 KV BB section & BB couplers protection scheme.


- I.D.M.T Non Directional O/C & E/F Relay.

Shunt Reactor Protection Scheme.


275 &132 KV. Shunt Reactor Protection Scheme.
• I.D.M.T Non Direction O/C & E/F relay.
• Inter Trip (through pilot cable – SHR connected through cable C.B. “for 132 kV only”).
• Buchhols Trip.
• Oil Temperature Trip.
• Winding Temperature Trip.
• Cable oil pressure Low Trip. (For cable tails)
• SF6 pressure Low Trip.
• C.B Fail to trip. (For 132 KV. C.B only).

33 KV. Shunt Reactor Protection Scheme for both connected


to 33 KV Bus-Bar or to tertiary of 300 MVA Transformer.

• I.D.M.T Non Direction O/C & E/F relay.


• Buchhols Trip.
• Oil Temperature Trip.
• Winding Temperature Trip.
Over-current and Earth Fault Protection
v Introduction

As the fault impedance is less than load impedance, the fault current is more than load current.
If a short circuit occurs the circuit impedance is reduced to a low value and therefore a fault is
accompanied by large current.

Over-current protection is that protection in which the relay picks up when the magnitude of
current exceeds the pickup level.

The basic element in Over-current protection is an Over-current relay.

The Over-current relays are connected to the system, normally by means of CT's.

Over-current relaying has following types:

1. High speed Over-current protection.

2. Definite time Over-current protection.

3. Inverse minimum time Over-current protection.

4. Directional Over-current protection (of above types).

Over-current protection includes the protection from overloads. This is most widely used
protection. Overloading of a machine or equipment generally) means the machine is taking
more current than its rated current. Hence with overloading, there is an associated temperature
rise. The permissible temperature rise has a limit based on insulation class and material
problems.
Over-current protection of overloads is generally provided by thermal relays.

Over-current protection includes short-circuit protection. Short circuits a be phase faults, earth
faults or winding faults. Short-circuit currents are generally several times (5 to 20) full load
current. Hence fast fault clearance is always desirable on short-circuits.
When a machine is protected by differential protection, the over-current is provided in addition
as a back-up and in some cases to protect the machine from sustained through fault.

Several protective devices are used for over-current protection these include:

1. Fuses

2. Circuit-breakers fitted with overloaded coils or tripped by over-current relays.

3. Series connected trip coils operating switching devices.

4. Over-current relays in conjunction with current transformers.

The primary requirements of over-current protection are:

• The protection should not operate for starting currents, permissible over-current,
and current surges. To achieve this, the time delay is provided (in case of
inverse relays). If time delay cannot be permitted, high-set instantaneous
relaying is used.
• The protection should be coordinated with neighboring over-current protections
so as to discriminate.

v Applications of Over-current Protection

Over-current protection has a wide range of applications. It can be applied where there is an
abrupt difference between fault current within the protected section and that outside the
protected section and these magnitudes are almost constant.

The over-current protection is provided for the following:

v Motor Protection
Over-current protection is the basic type of protection used against overloads and short-circuits
in stator windings of motors. Inverse time and instantaneous phase and ground over-current
relays can be employed for motors above 1200 H.P. For small/medium size motors where cost
of CT's and protective relays is not economically justified, thermal relays and HRC fuses are
employed, thermal relays used for overload protection and HRC fuses for short-circuit
protection.
v Transformer Protection
Transformers are provided with over-current protection against faults, only, when the cost of
differential relaying cannot be justified. However, over-current relays are provided in addition
to differential relays to take care of through faults. Temperature indicators and alarms are
always provided for large transformers.

Small transformers below 500 kVA installed in distribution system are generally protected by
drop-out fuses, as the cost of relays plus circuit-breakers is not generally justified Line
Protection.

The lines (feeders) can be protected by

(1) Instantaneous over-current relays.

(2) Inverse time over-current relays.

(3) Directional over-current relay.

Lines can be protected by impedance or carrier current protection also.

Protection of Utility Equipment

The furnaces, industrial installations commercial, industrial and domestic equipment are all
provided with over-current protection.

v Relays used in Over-current Protection

The choice of relay for over-current protection depends upon the Time / current characteristic
and other features desired. The following relays are used.

1. For instantaneous over-current protection. Attracted armature type, moving iron type,
permanent magnet moving coil type and static.

2. For inverse time characteristic. Electromagnetic induction type, permanent magnet


moving coil type and static.

3. Directional over-current protection. Double actuating quantity induction relay


with directional feature.
4. Static over-current relays.
5. HRC fuses, drop out fuses, etc. are used in low voltage medium voltage
and high voltage distribution systems, generally up to 11 kV.
6. Thermal relays are used widely for over-current protection.

Not: Now Digital Numerical Relay you can used for all types

v Characteristics of relay units for over current protection

There is a wide variety of relay-units. These are classified according to their type and
characteristics. The major characteristic includes:

1. Definite characteristic

2. Inverse characteristic

3. Extremely Inverse
4. Very Inverse

In definite characteristic, the time of operation is almost definite i.e.

I0*T=K

Where:

I = Current in relay coil

T = Relay lime

K = Constant.

In inverse characteristic, time is inversely proportional to current i.e.

I1*T=K

In more inverse characteristic

In*T=K
Where n can be between 2 to 8 the choice depends on discrimination desired.

Instantaneous relays are those which have no intentional time lag sod which operate in less
than 0.1 second, usually less than 0.08 second. As suck they are not instantaneous in real sense.

The relays which are not instantaneous are called Time Delay Relay'. Such relays are provided
with delaying means such as drag magnet, dash poss. bellows, escape mechanisms, back-stop
arrangement, etc.

The operating time of a relay for a particular setting and magnitude actuating quantity can be
known from the characteristics supplied by the manufacturer. The typical characteristics are
shown in (Fig. 1)

An inverse curve is one in which the operating time; becomes less as the magnitude of the
actuating quantity is increased. However for higher magnitudes of actuating quantity the time
is constant. Definite time curve is one in which operating time is little affected by magnitude of
actuating current. However even definite time relay has a characteristic which is slightly
inverse

The characteristic with definite minimum time and of inverse type is also called Inverse
Definite Minimum Time (IDMT) characteristics (Fig.1).
(Fig.1) Inverse Definite Minimum Time (IDMT)
characteristics
Principle of trip circuit
Referring to (Fig. 2) the three current transformers and relay coils connected in star and the star
point is earthed. When short circuit occurs in the protected zone the secondary current of CT's
increases.

These current flows through relay coils and the relay picks-up, the relay contacts close,
thereby the trip circuit is closed and the circuit breaker-operates The over-current protection
scheme with three over-current relays (Fig. 2) responds to phase faults and earth faults
including single-phase to earth fault.
Therefore such schemes are used with solidly earthed systems where phase to phase and phase
to earth faults are likely to occur.

For proper functioning of over-current and earth fault protection, the choice of CT's and
polarity connections should be correct.
Fig.2) Over Current protection with
three phase OC relays

Methods of CT Connections in Over-current Protection of 3-Phase Circuits

v Connection Scheme with Three Over-current Relays

Over-current protection can be achieved by means of three over-current relays or by two over-
current relays (See Table 1).
Table 1

Fig Description Note


1 One OC with one For balanced
CT for over load load only.
protection.
2 Two OC relays
with two CT's for
phase to phase
fault protection.

3 Three OC relays EF current >


with three CT's two time pick-
for phase to up phase
phase fault current
protection.

4 Three OC relays EF setting less


with three CT's than phase
for phase to fault setting
phase fault
protection and
phase to earth
fault.
5 Two OC and one
EF relays for
phase to phase
and phase to
earth fault
protection

v Earth-Fault Protection

When the fault current flows through earth return path, the fault is called Earth Fault. Other
faults which do not involve earth are called phase faults. Since earth faults are relatively
frequent, earth fault protection is necessary in most cases. When separate earth fault protection
is not economical, the phase relays sense the earth fault currents. However such protection
lacks sensitivity. Hence separate earth fault protection is generally provided. Earth fault
protection senses earth fault current. Following are the method of earth fault protection.

v Connections of CT's for Earth-fault Protection

1. Residually connected Earth-fault Relay

Referring to Fig. 3 In absence of earth-fault the vector sum of three line currents is zero. Hence
the vector sum of three secondary currents is also zero.

IR+IY+IB=0
The sum (IR+IY+IB) is called residual current

The earth-fault relay is connected such that the residual current flows through it (Figs.3 and
Fig. 4), in the absence of earth-fault,

Therefore, the residually connected earth-fault relay does not operate. However, in presence of
earth fault the conditions is disturbed and (IR+IY+IB) is no more zero. Hence flows through
the earth-fault relay. If the residual current is above the pick-up value, the earth-fault relay
operates.

In the scheme discussed here the earth-fault at any location near or away from the location of
CT's can cause the residual current flow. Hence the protected

zone is not definite. Such protection is called unrestricted earth-fault protection

(Fig.3) Earth-fault Relay connected in Residual


Circuit.
(Fig.4) Earth fault protection combined with
phase fault protection

2. Earth-fault Relay connected in Neutral to Earth Circuit (Fig. 5).

Another method of connecting an earth-fault relay is illustrated in Fig 5. The relay is connected
to secondary of a CT whose primary is connected in neutral to earth connection. Such protection
can be provided at various voltage levels by connecting earth-fault relay in the neutral-to-earth
connection of that voltage level. The fault current finds the return path through the earth and
then flows through the neutral-to-earth connected. The magnitude of earth fault current is
dependent on type of earthing (resistance, reactance or solid) and location of fault. In this type of
protection,

The zone of protection cannot be accurately defined. The protected area is not restricted to
the transformer/generator winding alone. The relay senses the earth faults
beyond the transformer/generator winding hence such protection is called unrestricted
earth-fault protection. The earth-fault protection by relay in neutral to earth circuit
depends upon the type of neutral Earthing. In case of large generators, voltage transformer
is connected between neutral and earth
(Fig. 5) Earth-fault protection by earth-fault-relay
connected
in neutral-to-earth circuit.

Combined Earth-fault and Phase-fault Protection

It is convenient to incorporate phase-fault relays and earth-fault relay in a combined phase-


fault and earth-fault protection. (Fig. 4) The increase in current of phase causes
corresponding increase in respective secondary currents. The secondary current flows
through respective relay-units Very often only two-phase relays are provided instead of
three, because in case of phase faults current in any at least two phases must increase.
Hence two relay-units are enough.

Earth-fault Protection with Core Balance Current Transformers. (Zero Sequence


CT)
In this type of protection (Fig. 6) a single ring shaped core of magnetic material, encircles
the conductors of all the three phases. A secondary coil is connected to a relay unit. The
cross-section of ring-core is

(Fig.6) Principle of core-balance CT for


earth fault protection
Ample, so that saturation is not a problem. During no-earth-fault condition, the
components of fluxes due to the fields of three conductors are balanced and the secondary
current is negligible. During earth faults, such a balance is disturbed and current is induced
in the secondary. Core-balance protection can be conveniently used for protection of low-
voltage and medium voltage systems. The burden of relays and exciting current are deciding
factors. Very large cross-section of core is necessary for sensitivity less than 10 A. This form
of protection is likely to be more popular with static relays due to the fewer burdens of the
latter. Instantaneous relay unit is generally used with core balance schemes.

Theory of Core Balance CT

. Let Ia, Ib and I c , be the three line currents and Φa, Φb and Φc be corresponding
components of magnetic flux in the core. Assuming linearity, we get resultant flux Φ as,

Φ=k (Ia + Ib + I c )

where k is a constant Φ = K * Ia. Referring to theory of symmetrical components

(Ia + Ib + I c )= 3 I c= I n
Where, Io is zero sequence current and In, is current in neutral to ground circuit. During
normal condition, when earth fault is absent,

(Ia + Ib + Ic) = 0

Hence Φr = 0 and relay does not operate


During earth fault the earth fault current flows through return neutral path.
For example for single line ground fault,

If = 3Iao = In

Hence the zero-sequence component of I o produces the resultant flux Φr in the core.
Hence core balance current transformer is also called as zero sequence current
transformers (ZSCT).

Application for Core Balance CT's with Cable Termination Joints

The termination of a three core cable into three separate lines or bus-bars is through cable
terminal box. Ref. (Fig. 7), the Core Balance Protection is used along with the cable box and
should be installed before making the cable joint.

The induced current flowing through cable sheath of normal healthy cable needs particular
attention with respect to the core balance protection.

The sheath currents (Ish) flow through the sheath to the cover of cable-box and then to earth
through the earthing connection between cable-box. For eliminating the error due to sheath
current (Ish) the earthing lead between the cable-box and the earth should be taken through
the core of the core balance protection.
Thereby the error due to sheath currents is eliminated. The cable box should be insulated
from earth.
1. Cable terminal box
2. Sheath of 3 core cable connection to (1)
3. Insulator support for 1
4. Earthing connection passing through 5
5. Core balance CT

Fig (7) Mounting of Core Balance CT


with Cable Terminal Box

Frame-leakage Protection

The metal-clad switchgear can be provided with frame leakage protection. The switchgear is
lightly y insulated from the earth. The metal-frame-work or enclosure of the switchgear is
earthed with a primary of a CT in between (Fig. 8).

The concrete foundation of the switchgear and the cable-boxes and other conduits are slightly
insulated from earth, the resistance to earth being about 12 ohms. In the event of an earth
fault within the switchgear, the earth-fault current finds the' path through the neutral
connection. While doing so, it is sensed by the earth fault relay.
(Fig.
8) Principle of frame-leakage protection
of metal-clad-switchgear

Circulating current differential protection also responds to earth-faults within its protected
zone.

Earth-fault protection can be achieved by following methods:

1. Residually connected relay.


2. Relay connected in neutral-to-ground circuit.
3. Core-balance-scheme.
4. Frame leakage method.
5. Distance relays arranged for detecting earth faults on lines.
6. Circulating current differential protection.

Directional Over-current Protection

The over-current protection can be given directional feature by adding directional


element in the protection system. Directional over-current protection responds to over-
currents for a particular direction flow. If power flow is in the opposite direction, the
directional over-current protection remains un-operative.

Directional over-current protection comprises over-current relay and power directional


relay- in a single relay casing. The power directional relay does not measure the power but
is arranged to respond to the direction of power flow.

Directional operation of relay is used where the selectivity can be achieved by directional
relaying. The directional relay recognizes the direction in which fault occurs, relative to
the location of the relay. It is set such that it actuates for faults occurring in one direction
only. It does not act for faults occurring in the other direction. Consider a feeder AC (Fig.
9) passing through sub-section B. The circuit breaker CB3 is provided with a directional
(Fig.
9) Principle of directional protection
Relay `R' which will trip the breaker CB3 if fault power flow in direction C alone.
Therefore for faults in feeder AB, the circuit breaker CB3 does not trip unnecessarily.
However for faults in feeder BC the circuit-breaker CB3 trips
Because it's protective relaying is set with a directional feature to act in
direction AC
Another interesting example of directional protection is that of reverse power protection
of generator (Fig. 10). If the prime mover fails, the generator continues to run as a motor
and takes power from bus-bars.

(Fig.
10) Reverse powers protection against motoring
action of a generator
Directional power protection operates in accordance with the direction of power flow.
Reverse power protection operates when the power direction is reversed in relation to the
normal working direction. Reverse power relay is different in construction than
directional over-current relay.
In directional over-current relay, the directional element does not measure the
magnitude of power. It senses only direction of power flow. However, in Reverse Power
Relays, the directional element measures magnitude and direction of power flow.

Relay connections of Single Phase Directional Over-current Relay :

The current coils in the directional over-current relay are normally connected to a
secondary of line CT. The voltage coil of directional element is connected to a line VT,
having phase to phase output (of 110 V). There are four common methods of connecting
the relay depending upon phase angle between current in the current coil and voltage
applied to the voltage coil.
Fig.11 Numerical Over
current, and Overload
Protection Relay

3-Phase Directional over current relays

When fault current can flow in both directions through the relay location, it is
necessary to make the response of the relay directional by the introduction of
directional control elements. These are basically power measuring devices in which
the system voltage is used as a reference for establishing the relative direction or
phase of the fault current.

Although power measuring devices in principle, they are not arranged to respond to
the actual system power for a number of reasons:

1. The power system, apart from loads, is reactive so that the fault power factor
is usually low. A relay

V a , Vb and Vc. Normal system


voltages
V b 1 and V c 1 Voltages at fault
location on faulted phases
V b 2 and V c 2 Voltages remote from
fault location

Fig.12 Phase voltages for a B-C


fault

Responding purely to the active component would not develop a high torque and
might be much slower and less decisive than it could be.
1. The system voltage must collapse at the point of short circuit. When the
fault is single-phase, it is the particular voltage across the short-circuited
points which are reduced. So a B—C phase fault will cause the B and C phase
voltage vectors to move together, the locus of their ends being the original line
be for a homogeneous system, as shown in (Fig.12)
At the point of fault the vectors will coincide, leaving zero voltage across the fault, but
the fault voltage to earth will be half the initial phase to neutral voltage. At other
points in the system the vector displacement will be less, but relays located at such
points will receive voltages which are unbalanced in their value and phase position.

The effect of the large unbalance in currents and voltages is to make the torques
developed by the different phase elements vary widely and even differ in sign if the
quantities applied to the relay are not chosen carefully. To this end, each phase of the
relay is polarized with a voltage which will not be reduced excessively except by close
three-phase faults, and which will remain in a satisfactory relationship to the current
under all conditions.

Relay connections

This is the arrangement whereby suitable current and voltage quantities are applied
to the relay. The various connections are dependent on the phase angle, at unity
system power factor, by which the current and voltage applied to the relay are
displaced.

Relay maximum torque


The maximum torque angle (MTA) is defined as the angle by which the current
applied to the relay must be displaced from the voltage applied to the relay to
produce maximum torque.
Although the relay element may be inherently wattmetric, its characteristic can be
varied by the addition of phase shifting components to give maximum torque at the
required phase angle.
A number of different connections have been used and these are discussed below.
Examination of the suitability of each arrangement involves determining the limiting
conditions of the voltage and current applied to each phase element of the relay, for
all fault conditions, taking into account the possible range of source and line
impedances.

30° relay connection (0° MTA)


The A phase relay is supplied with current la and voltage V ac. In this case, the flux
due to the voltage coil lags the applied Vac voltage by 90°, so the maximum torque
occurs when the current lags the system phase to neutral voltage by 30°. For unity
power factor and 0.5 lagging power factor the maximum torque available is 0.866 of
maximum. Also, the potential coil voltage lags the current in the current coil by 30°
and gives a tripping zone from 60° leading to 120° lagging currents, as shown in (Fig.
13a).

The most satisfactory maximum torque angle for this connection, that ensures
correct operation when used for the protection of plain feeders, is 0°, and it can be
shown that a directional element having this connection and 0° MTA will provide
correct discrimination for all types of faults, when applied to plain feeders

If applied to transformer feeders, however, there is a danger that at least one of the
three phase relays will operate for faults in the reverse direction; for this reason a
directional element having this connection should never be used to protect
transformer feeders.
This connection has been used widely in the past, and it is satisfactory under all
conditions for plain feeders provided that three phase elements are employed. When
only two phase elements and an earth fault element are used there is a probability of
failure to operate for one condition. An inter-phase short circuit causes two elements
to be energized but for low power factors one will receive inputs which, although
correct, will produce only a poor torque. In particular a B—C fault will strongly
energize the B element with lb current and Vba voltage, but the C element will
receive Ic and the collapsed Vcb voltage, which quantities have a large relative phase
displacement, as shown in (Fig. 13b). This is satisfactory provided that three phase
elements are used, but in the case of a two phase and one earth fault element relay,
with the B phase element omitted, operation will depend upon the C element, which
may fail to operate if the fault is close to the relaying point.
A phase element connected l a Va c
B phase element connected l b Vba
C phase element connected Ic Vcb
(a) Characteristic and inputs
for phase A element

(b) B-C Fault with voltage


distortion

(Fig. 13) Vector diagrams for the 30°


connection

60° No. 1 connection (0° MTA)


The A phase relay is supplied with lab current and Vac voltage. In this case, the flux
due to the voltage coil lags the applied voltage to the relay by 90°, so maximum
torque is produced when the current lags the system phase to neutral voltage by 60°.
This connection, which uses Vac voltage with delta current produced by adding phase
A and phase B currents at unity power factor, gives a current leading the voltage Vac
by 60°, and provides a correct directional tripping zone over a current range of 30°
leading to 150° lagging. The torque at unity power factor is 0.5 of maximum torque
and at zero power factor lagging 0.866; see (Fig.14).
It has been proved that the most suitable maximum torque angle for this relay
connection, that is, one which ensures correct directional discrimination with the
minimum risk of mal-operation when applied to either plain or transformer feeders,
is 0°.
When used for the protection of plain feeders there is a slight possibility of the
element associated with the A phase mal-operating for a reversed B—C fault.

A phase element connected lab Va c


B phase element connected I bc V b a
C phase element connected Ica Vcb

(Fig.14) Vector diagram for the 60°


No. 1 connection
(phase A element)
However, although the directional element may mal-operation, it is unlikely that the
over current element which the directional element controls will receive sufficient
current to cause it to operate. For this reason the connection may be safely
recommended for the protection of plain feeders.
When applied to transformer feeders there is a possibility of one of the directional
elements mal-operation for an earth fault on the star side of a delta/star transformer,
remote from the relay end. For mal-operation to occur, the source impedance would
have to be relatively small and have a very low angle at the same time that the arc
resistance of the fault was high. The possibility of mal-operation with this connection
is very remote, for two reasons: first, in most systems the source impedance may be
safely assumed to be largely reactive, and secondly, if the arc resistance is high
enough to cause mal-operation of the directional element it is unlikely that the over
current element associated with the mal-operation directional element will see
sufficient current to operate.
The connection, however, does suffer from the disadvantage that it is necessary to
connect the current transformers in delta, which usually precludes their being used
for any other protective function. For this reason, and also because it offers no
advantage over the 90° connection, it is rarely used.

60° No. 2 connection (0° MTA)


The A phase relay is supplied with current la and voltage In this case, the flux of the
voltage coil lags the applied voltage by 90° so the maximum torque is produced when
the current lags the system phase to neutral voltage by 60°. This connection gives

A phase element connected Ia —Vc


B phase element connected Ib — Va
C phase element connected Ic —Vb

(Fig.15) Vector diagram for the 60° No. 2


connection
(phase A element).
a correct directional tripping zone over the current range of 30° leading to 150°
lagging. The relay torque at unity power factor is 0.5 of the relay maximum torque and
at zero power factor lagging 0.866; see (Fig.15).
The most suitable maximum torque angle for a directional element using this
connection is 0°. However, even if this maximum torque angle is used, there is a risk of
incorrect operation for all types of faults with the exception of three-phase faults. For
this reason, the 60° No. 2 connection is now never recommended.

A phase element connected Ia Vbc


B phase element connected Ib Vca
C phase element connected Ic Vab
(Fig.16) Vector diagram for the 90°- 30°
connection
(Phase A element)

90° relay quadrature connection


This is the standard connection for the type CDD relay; depending on the angle by
which the applied voltage is shifted to produce the relay maximum torque angle, two
types are available.

90°- 30° characteristic (30° MTA)


The A phase relay is supplied with la current and Vbc voltage displaced by 30° in an
anti-clockwise direction. In this case, the flux due to the voltage coil lags the applied
voltage Vbc by 60°, and the relay maximum torque is produced when the current lags
the system phase to neutral voltage by 60°. This connection gives a correct directional
tripping zone over the current range of 30° leading to 150° lagging; see (Fig.16). The
relay torque at unity power factor is 0.5 of the relay maximum torque and at zero
power factor lagging 0.866. A relay designed .for quadrature connection and having a
maximum torque angle of 30° is recommended when the relay is used for the
protection of plain feeders with the zero sequence source behind the relaying point.
90°- 45° characteristic (45° MTA)
The A phase relay is supplied with current la and voltage Vbc displaced by 45° in an
anti-clockwise direction. In this case, the flux due to the voltage coil lags the applied
voltage Vbc by 45°, and the relay maximum torque is produced when the current lags
the system phase to neutral voltage by 45°. This connection gives a correct directional
tripping zone over the current range of 45° leading to 135° lagging.

The relay torque at unity power factor is 0.707 of the maximum torque and the same at
zero power factor lagging; see (Fig.17).

A phase element connected Ia ,Vbc


B phase element connected Ih Vca
C phase element connected Ic Vab
(Fig.17) Vector diagram for the 90°-
45° connection
(Phase A element)

This connection is recommended for the protection of transformer feeders or feeders


which have a zero sequence source in front of the relay. The 90°- 45° connection is
essential in the case of parallel trans-formers or transformer feeders, in order to ensure
correct relay operation for faults beyond the star/ delta transformer. This connection
should also be used whenever single-phase directional relays are applied to a circuit

Theoretically, three fault conditions can cause mal-operation of the directional


element: a phase-phase ground fault on a plain feeder, a phase-ground fault on a
transformer feeder with the zero sequence source in front of the relay and a phase-
phase fault on a power transformer with the relay looking into the delta winding of the
transformer.

It should be remembered, however, that the conditions assumed above to establish the
maximum angular displacement between the current and voltage quantities at the
relay, are such that, in practice, the magnitude of the current input to the relay would
be insufficient to cause the over current element to operate. It can be shown
analytically that the possibility of mal-operation with the 90°- 45° connection is, for all
practical purposes, non-existent.

Parallel feeders

If non-directional relays are applied to parallel feeders, any faults that might occur on
any one line will, regardless of the relay settings used, isolate both lines and completely
disconnect the power supply. With this type of system configuration it is necessary to
apply directional relays at the receiving end and to grade them with the non-
directional relays at the sending end, to ensure correct discriminative operation of the
relays during line. faults. This is done by setting the directional relays R'1 and R'2 as
shown in (Fig.18) with their directional elements looking into the protected line, and
giving them lower time and current settings than relays R1 and R2. The usual practice
is to set relays R'1 and R'2 to 50% of the normal full load of the protected circuit and
0.1 TMS, but care must be taken to ensure that their continuous thermal rating of twice
rated current is not exceeded.

Ring mains

Directional relays are more commonly applied to ring mains. In the case of a ring main
fed at one point only, the relays at the supply end and at the mid-point substation,
where the setting of both relays are identical, can be made non-directional, provided
that in the latter case the relays are located on the same feeder, that is, one at each end
of the feeder.

It is interesting to note that when the number of feeders round the ring is an even
number, the two relays with the same operating time are at the same substation and will
have to be directional, whereas when the number of feeders is an odd number, the two
relays with the same operating time are at different substations and therefore do not
need to be directional.

It may also be noted that, at inter-mediate substations, whenever the operating times of
the relays at each substation are different, the difference between their operating times
is never less than the grading margin, so the relay with the longer operating time can be
non-directional.

Grading of ring mains

The usual procedure for grading relays in an inter-connected system is to open the ring
at the supply point and to grade the relays first clockwise and then anti-clockwise; that
is, the relays looking in a clock-wise direction round the ring are arranged to operate in
the sequence 1—2—3—4—5—6 and the relays looking in the anti-clockwise direction are
arranged to operate in the sequence 1'—2'—3'—4'—5'—6', as shown in (Fig.19)

(Fig.19) Grading of ring mains

The arrows associated with the relaying points indicate the direction of current flow
that will cause the relays to operate.
A double-headed arrow is used to indicate a non-directional relay, such as those at the
supply point where the power can flow only in one direction, and a single-headed
arrow a directional relay, such as those at intermediate substations around the ring
where the power can flow in either direction. The directional relays are set in
accordance with the invariable rule, applicable to all forms of directional protection
that the current in the system must flow from the substation bus-bars into the
protected line in order that the relays may operate.
Disconnection of the faulty line is carried out according to time and fault current
direction. As in any parallel system, the fault current has two parallel paths and
divides itself in the inverse ratio of their impedances.

Thus, at each substation in the ring, one set of relays will be made inoperative because
of the direction of current flow, and the other set operative. It will also be found that
the operating times of the relays that are inoperative are faster than those of the
operative relays, with the exception of the mid-point substation, where the operating
times of relays 3 and 3' happen to be the same.

The relays which are operative are graded downwards towards the fault and the last to
be affected by the fault operates first. This applies to both paths to the fault.
Consequently, the faulty line is the only one to be disconnected from the ring and the
power supply is maintained to all the substations.

When two or more power sources feed into a ring main, time graded over current
protection is difficult to apply and full discrimination may not be possible. With two
sources of supply, two solutions are possible. The first is to open the ring at one of the
supply points, whichever is more convenient, by means of a suitable high set
instantaneous over-current relay and then to proceed to grade the ring as in the case of
a single infeed, the second to treat the section of the ring between the two supply points
as a continuous bus separate from the ring and to protect it with a unit system of
protection, such as pilot wire relays, and then proceed to grade the ring as in the case
of a single infeed.

Directional Earth-Fault Protection

In the directional over-current protection the current coil of relay is actuated from
secondary current of line CT. whereas the current coil of directional earth fault relay is
actuated by residual current.

In directional over-current relay, the voltage coil is actuated by secondary of line VT. In
directional earth fault relay, the voltage coil is actuated by the residual voltage.
Directional earth fault relays sense the direction in which earth fault occurs with respect
to the relay location and it operates for fault in a particular direction. The directional
earth fault relay (single phase unit) has two coils. The polarizing quantity is obtained
either from residual current
I RS = (Ia + Ib + Ic)

or residual voltage VRs = V a + V b + V c

Where V a , V b and Vc are phase voltages.

Referring to (Fig. 11) the directional earth-fault relay has two coils. One to the coils is
connected in residual current circuits (Ref. Fig. 5). This coil gets current during earth-
faults. The other coil gets residual voltage,

V RS= V a + V b + V c

Where V a , V b a n d V c are secondary voltages of the potential transformer

('Three phase five limb potential transformer or three separate single phase potential
transformers connected as shown in Fig. 20). The coil connected in potential-transformer
secondary circuit gives a polarizing field.

The residual current I RS i.e. the out of balance current is given to the current coil and the
residual voltage VRs is given to the voltage coil of the relay. The torque is proportional to
T = I RS * V RS * cos (Φ - α)
Φ = angle between I RS and VRs
α = angle of maximum torque.

Summary
Over-current protection responds to increase in current above the pick-up value over-
currents are caused by overloads and short-circuits.
The over-current relays are connected the secondary of current transformer. The
characteristic of over-current relays include inverse time characteristic, definite time
characteristic.
Earth fault protection responds to single line to ground faults and double line to ground
faults. The current coil of earth-fault relay is connected either in neutral to ground circuit
or in residually connected secondary CT circuit.
Core balance CTs are used for earth-fault protection.
Frame leakage protection can be used for metal clad switchgear.
Directional over-current relay and Directional Earth fault relay responds to fault in which
power flow is in the set direction from the CT and PT locations. Such directional relays
are used when power can flow from both directions to the fault point.
Co-ordination
Correct current relay application requires knowledge of the fault current that can flow
in each part of the network. Since large scale tests are normally impracticable, system
analysis must be used. It is generally sufficient to use machine transient reactance X'd
and to work on the instantaneous symmetrical currents. The data required for a relay
setting study are:
1. A one-line diagram of the power system involved, showing the type and
rating of the protective devices and their associated current
transformers.
2. The impedances in ohms, per cent or per unit, of all power
transformers, rotating machines and feeder circuits.
3. The maximum and minimum values of short circuit currents that are
expected to flow through each protective device.
4. The starting current requirements of motors and the starting and
stalling times of induction motors.
5. The maximum peak load current through protective devices.
6. Decrement curves showing the rate of decay of the fault current
supplied by the generators.
7. Performance curves of the current transformers.
8. The relay settings are first determined so as to give the shortest
operating times at maximum fault levels and then checked to see if
operation will also be satisfactory at the minimum fault current
expected. It is always advisable to plot the curves of relays and other
protective devices, such as fuses, that are to operate in series, on a
common scale. It is usually more convenient to use a scale corresponding
to the current expected at the lowest voltage base or to use the
predominant voltage base. The alternatives are a common MVA base or
a separate current scale for each system voltage.
9. The basic rules for correct relay co-ordination can generally be stated as
follows:
10. Whenever possible, use relays with the same operating characteristic in
series with each other.
11. Make sure that the relay farthest from the source has current settings equal
to or less than the relays behind it, that is, that the primary current required
operating the relay in front is always equal to or less than the primary current
required operating the relay behind it.

PRINCIPLES OF TIME/CURRENT GRADING


Among the various possible methods used to achieve correct relay co-ordination are
those using either time or over current or a combination of both time and over-current.
The common aim of all three methods is to give correct discrimination. That is to say,
each one must select and isolate only the faulty section of the power system network,
leaving the rest of the system undisturbed.
1. Discrimination by time
In this method an appropriate time interval is given by each of the relays controlling
the circuit breakers in a power system to ensure that the breaker nearest to the fault
opens first. A simple radial distribution system is shown in (Fig. 21) to illustrate the
principle.

Circuit breaker protection is provided at B, C, D and E, that is, at the infeed end of
each section of the power system. Each protection unit comprises a definite time delay
over current relay in which the operation of the current sensitive element simply
initiates the time delay element. Provided the setting of the current element is below
the fault current value this element plays no part in the achievement of discrimination.
For this reason, the relay is sometimes described as an 'independent definite time delay
relay' since its operating time is for practical purposes independent of the level of over
current.

It is the time delay element, therefore, which provides the means of discrimination. The
relay at B is set at the shortest time delay permissible to allow a fuse to blow for a
fault on the secondary side of trans-former A. Typically, a time delay of 0.25s is
adequate.

If a fault occurs at F, the relay at B will operate in 0.25s, and the subsequent operation
of the circuit breaker at B will clear the fault before the relays at C, D and E have time
to operate. The main disadvantage of this method of discrimination is that the longest
fault clearance time occurs for faults in the section closest to the power source, where
the fault level (MVA) is highest.

1. Discrimination by current

Discrimination by current relies on the fact that the fault current varies with the
position of the fault, because of the difference in impedance values between the source
and the fault. Hence, typically, the relays controlling the various circuit breakers are
set to operate at suitably tapered values such that only the relay nearest to the fault
trips its breaker. (Fig. 22) illustrates the method.

For a fault at F1, the system short circuit current is given by:

I = 6350 /(Zs + ZL1) A

Where Zs = source impedance = 112 / 250 = 0.485 ohms

ZL1= cable impedance between C and B = 0.24 ohms


Hence I=6350/0.725 = 8800 A

So a relay controlling the circuit breaker at C and set to operate at a fault current of
8800 A would in simple theory protect the whole of the cable section between C and
B. However, there are two important practical points which affect this method of co-
ordination.

1. It is not practical to distinguish between a fault at Fl and a fault at F 2,


since the distance between these points can be only a few meters,
corresponding to a change in fault current of approximately 0.1%.
2. In practice, there would be variations in the source fault level, typically
from 250 MVA to 130 MVA. At this lower fault level the fault current
would not exceed 6800 A even for a cable fault close to C, so a relay set
at 8800 A would not protect any of the cable section concerned.

Discrimination by current is therefore not a practical proposition for correct


grading between the circuit breakers at C and B. However, the problem changes
appreciably when there is significant impedance between the two circuit breakers
concerned. This can be seen by considering the grading required between the circuit
breakers at B and A in (Fig. 22).
Assuming a fault at F4, the short-circuit current is given by:

I = 6350 /(Zs + ZL1 + ZL2 +ZT) A

Where
ZS = source impedance
=112 / 250 = 0.485 ohms

ZL1 = cable impedance between C and B 0.24 ohms


ZL2 = cable impedance between B and 4 MVA
transformer 0.04 ohms
ZT = transformer impedance
=0.07(112/4) =2.12 ohms
Hence I = 6350/ 2.885 = 2200 A

For this reason, a relay controlling the circuit breaker at B and set to operate at a
current of 2200 A plus a safety margin would not operate for a fault at F4 and would
thus discriminate with the relay at A. Assuming a safety margin of 20% to allow for
relay errors and a further 10% for variations in the system impedance values, it is
reasonable to choose a relay setting of 1.3 x 2200, that is, 2860 A for the relay at B.
Now, assuming a fault at F3, that is, at the end of the 11 kV cable feeding the 4 MVA
transformers, the short-circuit current is given by:
I = 6350 /(Zs + ZL1 + ZL2 +ZT)
I = 6350 /(0.485 + 0.24 + 0.04)=8300 Amp.
Alternatively, assuming a source fault level of 130 MVA:
I = 6350 /(0.93 + 0.24 + 0.004)=5250 Amp.

In other words, for either value of source level, the relay at B would operate
correctly for faults anywhere on the 11 kV cable feeding the transformer.
Discrimination by both time and current
3 Discrimination by both time and current

Each of the two methods described so far has a fundamental disadvantage. In the
case of discrimination by time alone, the disadvantage is due to the fact that the more
severe faults are cleared in the longest operating time. Discrimination by current can
only be applied where there is appreciable impedance between the two circuit breakers
concerned.

It is because of the limitations imposed by the independent use of either time or


current co-ordination that the inverse time over current relay characteristic has evolved.
With this characteristic, the time of operation is inversely proportional to the fault
current level and the actual characteristic is a function of both 'time' and 'current'
settings.
The advantage of this method of relay

Co-ordination may be best illustrated by the system shown in (Fig.23) which is


identical to that shown in (Fig.21) except that typical system parameters have been
added.

In order to carry out a system analysis, before a relay co-ordination study of the
system shown in (Fig. 23), it is necessary to refer all the system impedances to a common
base and thus, using 10 MVA as the reference base, we have:

4MVA transformer percentage impedance on 10MVA base=7X (10/4) =17.5%

11 kV cable between B and A percentage impedance on10 MVA base

= (0.04 X 100 X 10) / 112= 0.33%

11 kV cable between C and B percentage impedance on 10 MVA base

= (0.24 X 100 X10) /112 =1.98 %

30 MVA transformer percentage impedance on 10 MVA base

=22.5 X 10 / 30 =7.5 %

132 kV overhead line percentage impedance on10 MVA base

= (6.2x100x10)/ 1322 =0.36%


132 kV source percentage impedance on 10 MVA base

= (100 x 10) /3500 =0.29%

The graph in (Fig.23) illustrates the use of 'discrimination curves', which are an
important aid to satisfactory protection co-ordination. In this example, a voltage base of
3.3kV has been chosen and the first curve plotted is that of the 200 A fuse, which is
assumed to protect the largest outgoing 3.3kV circuit. Once the operating characteristic
of the highest rated 3.3kV fuse has been plotted, the grading of the over current relays at
the various sub-stations of the radial system is carried out as follows:

Substation B

CT ratio 250/5A Relay over current characteristic assumed to be extremely inverse,


as for the type CDG 14 relay. This relay must discriminate with the 200A fuse at fault
levels up to:

(10 x 100) / (17.5+0.33+1.98+7.5+0.36+0.29) = 35.7 MVA

That is, 6260 A at 3.3kV or 1880 A at 11 kV. The operating characteristics of the
CDG 14 relay show that at a plug setting of 100%, that is, 250 A and 4.76 MVA at 11 kV,
and at a time multiplier setting of 0.2, suitable discrimination with the 200 A fuse is
achieved.

Substation C

CT ratio 500/5A Relay over current characteristic assumed to be extremely inverse,


as for the type CDG 14 relay. This relay must discriminate with the relay in substation
B at fault levels up to:

(10 X 100) / (1.98 +7.5 +0.36 +0.29) = 98.7MVA

That is, 17,280 A at 3.3kV or 5180 A at 11 kV. The operating characteristics of the
CDG 14 relay show that at a plug setting of 100%, that is, 500 A and 9.52 MVA at 11 kV,
and at a time multiplier setting of 0.7, suitable discrimination with the relay at substation
B is achieved.
(Fig.23) Time and current grading

Substation D

CT ratio 150/1A Relay over current characteristic assumed to be extremely inverse,


as for the type CDG 14 relay. This relay must discriminate with the relay in substation C
at fault levels up to

(10 X 100) / (7.5 + 0.36 + 0.29) = 123 MVA

That is, 21,500 A at 3.3kV or 538 A at 132 kV. The operating characteristics of the
CDG 14 relay show that at a plug setting of 100%, that is, 150 A and 34.2 MVA at 132 kV
and at a time multiplier setting of 0.25, suitable discrimination with the relay at
substation C is achieved.

Substation E

CT ratio 500/1 A Relay over current characteristic assumed to be extremely inverse,


as for the type CDG 14 relay. This relay must discriminate with the relay

in substation D at fault levels up to:

(10 x 100) / (0.36+0.29) = 1540 MVA

That is, 270,000 A at 3.3kV or 6750 A at 132 kV. The operating characteristics of the
CDG 14 relay show that at a plug setting of 100%, that is, 500 A and 114 MVA at 132 kV,
and at a time multiplier setting of 0.9, suitable discrimination with the relay at sub-
station D is achieved.

A comparison between the relay operating times shown in (Fig. 21) and the times
obtained from the discrimination curves of (Fig. 23) at the maximum fault level reveals
significant differences. These differences can be summarized as follows:

Relay Fault Time from Time from


level Fig.12 Fig.14
(MVA) (seconds) (seconds)
B 98.7 0.25 0.07
C 123 0.65 0.33
D 1540 1.05 0.07
E 3500 1.45 0.25

These figures show that for faults close to the relaying points the inverse time
characteristic can achieve appreciable reductions in fault clearance times.

Even for faults at the remote ends of the protected sections, reductions in fault
clearance times are still obtained, as shown by the following table:

Relay Fault level Time from Fig.14


(MVA) (seconds)
B 35.7 0.17
C 98.7 0.42
D 123 0.86
E 1540 0.39

To finalize the co-ordination study it is instructive to assess the average operating


time for each extremely inverse over current relay at its maximum and minimum fault
levels, and to compare these with the operating time shown in (Fig.21) for the definite
time over current relay.

Relay Fault level Time from Average


(Max./Min Fig.14 time
MVA) (seconds) (seconds)
(Max./ Min)
B 98.7/35.7 0.07/0.17 0.12
C 123/98.7 0.33/0.42 0.375
D 1540/123 0.07/0.86 0.465
E 3500/1540 0.25/0.39 0.32

This comparison clearly shows that when there is a large variation in fault level all
along the system network the overall performance of the inverse time over current relay
is far superior to that of the definite over current relay.

4 GRADING MARGIN
The time interval between the operations of two adjacent relays depends upon a
number of factors:

1. The fault current interrupting time of the circuit breaker.


2. The overshoot time of the relay.
3. Errors.
4. Final margin on completion of operation.

A. Circuit breaker interrupting time

The circuit breaker interrupting the fault must have completely interrupted the
current before the discriminating relay ceases to be energized.

B. Overshoot

When the relay is de-energized, operation may continue for a little longer until any
stored energy has been dissipated. For example, an induction disc relay will have stored
kinetic energy in the motion of the disc; static relay circuits may have energy stored in
capacitors. Relay design is directed to minimizing and absorbing these energies, but some
allowance is usually necessary.

The overshoot time is not the actual time during which some forward operation takes
place, but the time which would have been required by the relay if still energized to
achieve the same amount of operational advance.

C. Errors

All measuring devices such as relays and current transformers are subject to some
degree of error. The operating time characteristic of either or both relays involved in the
grading may have a positive or negative error, as may the current transformers, which
can have phase and ratio errors due to the exciting current required to magnetize their
core. This does not, however, apply to independent definite time delay over current
relays.

Relay grading and setting is carried out assuming the accuracy of the calibration
curves published by manufacturers, but since some error is to be expected, some
tolerance must be allowed.
D. Final margin

After the above allowances have been made, the discriminating relay must just fail to
complete its operation. Some extra allowance, or safety margin, is required to ensure that
a satisfactory contact gap (or equivalent) remains.

E. Recommended time

The total amount to be allowed to cover the above items depends on the operating
speed of the circuit breakers and the relay performance. At one time 0.5s was a normal
grading margin. With faster modern circuit breakers and lower relay overshoot times
0.4s is reasonable, while under the best possible conditions 0.35s may be feasible.

In some instances, however, rather than using a fixed grading margin, it is better to
adopt a fixed time value, to allow for the operating time of the circuit breaker and relay
overshoot, and to add to it a variable time value that takes into account the relay errors,
the CT errors and the safety margin.

A value of 0.25s is chosen for the fixed time value, made up of 0.1 s for the fault
current interrupting time of the circuit breaker, 0.05s for the relay over-shoot time and
0.1 s for the safety margin. Considering next the variable time values required, it is first
assumed that each inverse time over current relay complies with Error Class E7.5
defined as normal British practice in BS 142:1966.

The normal limits of error for an E7.5 relay are ±7.5% but allowance should also be
made for the effects of temperature, frequency, and departure from reference setting. A
practical approximation is to assume a total effective error of 2 x 7.5, that is, 15%, this to
apply to the relay nearest to the fault, which shall be considered to be slow.

To this total effective error for the relay a further 10% should be added for the
overall current transformer error. Hence, for the time interval t' required between
inverse time over current relays it is proposed to adopt the equation:

t' = 0.25t + 0.25 seconds


Where t = nominal operating time of relay nearer to the fault.

As far as the independent definite time delay over-current relays are concerned, it is
assumed that these comply with Error Class El 0, defined as normal British practice in
BS 142:1966. The normal limits of error for an El 0 relay are ± 10%, but allowance
should also be made for the effects of temperature, voltage, frequency and departure
from reference setting. A practical approximation is to assume a total effective error of 2
x 10, that is, 20%, this to apply to the relay, nearest to the fault, which shall be considered
to be slow. However, unlike the inverse time over current relay, it is not necessary to add
a further error for the current transformers. Hence, for the time interval t' required
between independent definite time delay over current relays, it is proposed to adopt the
equation:

t' = 0.2t + 0.25 seconds

Where t = nominal operating time of relay nearest to the fault.

v STANDARD I.D.M.T. OVER CURRENT RELAY (TYPE CDG 11)

Limits of accuracy have been considered by various national committees and (Fig.24)
shows a typical example of the limits set by the British Standards Institution specification
BS 142:1966 for the standard inverse definite minimum time over current relay.

The discriminating curves shown in (Fig.25) illustrate the application of such a relay
to a sectioned radial feeder; it will be seen that with the assumed relay settings and the
tolerances allowed in BS 142:1966 the permissible grading margin between the over
current relays at each section breaker is approximately 0.5s. With the increase in system
fault current it is desirable to shorten the clearance time for faults near the power source,
in order to minimize damage. It is therefore necessary to reduce the time errors, which
are in this situation disproportionately large when compared with the clearance time of
modern circuit breakers; this can only be achieved by improving the limits of accuracy,
pick-up and overshoot
(Fig. 24) Typical limits of accuracy set by BS
142: 1966 for an inverse
Definite Minimum Time over current relay

NORMAL BRITISH PRACTICE


ACCURACY CLASS E7.5%
TIME/CURRENT CHARACTERISTIC
ALLOWABLE LIMIT
At 2 times setting 222E
At 5 times setting 1.13E
At 10 times setting 1.01E
At 20 times setting 1.00E

NOTE: The allowance error in operating time should not be less than 100ms

All this must be obtained without detriment to the general performance of the relay;
in other words, there must be no reduction in the operating torque or weakening of the
damper magnets or contact pressures, and the construction must remain simple with the
minimum number of moving parts. While these requirements present considerable
difficulties in manufacture, owing to variations in materials and practical tolerances, the
progress made in the GEC Measurements relays has made it possible to discriminate
more closely by reducing the margin between both the current and the time setting of the
relays on adjacent breakers.
(Fig.25) application of an IDMT over current
relay to a sectioned
Radial feeder

These relays will thus enable the time setting of the relay nearest the power source to
be reduced, or, alternatively, make it possible to increase the number
of breakers in series without increasing the time setting of the relays
at the power source.

Web address: http://www.sayedsaad.com/

Das könnte Ihnen auch gefallen