DELTA AND WYE CIRCUIT EQUATIONS

Typical 3-Phase Wiring Diagrams and Equations

For Both Wye and Delta (Balanced Loads) Wye and Delta Equivalent
VP = Phase Voltage WDELTA = 3 WWYE
VL = Line Voltage Open3-Phase Circuit Formulas:
IP = Phase Current 2
Open Delta Watts = /3 WDELTA
IL = Line Current 1
Open Wye Watts = /2 WWYE
R = R1 = R2 = R3 = Resistance of each branch 2
W = Wattage Open 4-wire Wye Watts = /3 WWYE

3-Phase Wye
(Balanced Load) 3-Phase Open Wye
(No Neutral)

IP = I L IPO = I LO
VP = VL/1.73 VPO = VL/2
2 2 1
WWYE = VL /R = 3 (VP ) /R WOWYE = /2 ( VL /R)
WWYE = 1.73VLIL WOWYE = 2 (VPO2/R)
WOWYE = VLILO

3-Phase Delta 3-Phase Open Delta


(Balanced Load)

VP = VL
IP = I L/1.73
IPO1 = I PO3 = I LO2
VP = VL
2
ILO3 = 1.73 I PO1
WDELTA = 3(VL )/R 2
WODELTA = 2(VL /R )
WDELTA = 1.73VLIL

1 จาก 2 19/4/2554 15:59


Delta and Wye circuit equations and Connections http://www.generatorjoe.net/html/gendelta.html

Copyright © 1999-2010 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved.

This is a new pop-up window on top of your browser window.

CLICK TO CLOSE WINDOW

2 จาก 2 19/4/2554 15:59