Sie sind auf Seite 1von 1

T2G

jim phillips

technical training group

It has been said that we only use 10 percent of our brain. Here is some information to
Short Circuit help you fill the other 90 percent. Brainfiller.comtm

Short Circuit Motor Contribution


Jim Phillips, P.E.
Short Circuit Motor Contribution electric power system must have an adequate short circuit
When a short circuit occurs, all connected running motors act interrupting capability. If an overcurrent device such as a
like generators for a few cycles and produce short circuit fuse or circuit breaker was subjected to a short circuit current
current that is fed back into the power system. The motor beyond its rating, the device could possibly explode leading
contribution can total thousands of amps when all motors are to equipment damage and jeopardizing the safety of
taken into account. personnel. The circuit breaker below has an Ampere
Interrupting Rating (AIC) of 10 kA or 10,000 Amps. This
During a short circuit, the voltage collapses at the point of the means the device’s design was tested in accordance with
fault (short circuit). As the voltage collapses, the motor’s Underwriter Laboratories test procedures and is capable of
field does not instantaneously collapse so there is a rotating being applied at locations where the short circuit current is
magnetic field and motor windings – exactly what it takes to no greater than 10,000 Amps at the device line side
produce electricity. Although the motor’s short circuit current terminals.
only lasts a few electrical cycles, while the field collapses. It
is during the first few electrical cycles that overcurrent
devices must respond and they must either interrupt or
withstand this additional current.
Motor contribution is equal to locked rotor current. i.e. if a
motor has a full load current of 40 Amps and a starting
current (locked rotor current) of 200 Amps, then the motor
can contribute 200 Amps to the short circuit. When there are
many motors on a power system, as there usually are, you
can see the total motor contribution can be significant.

To calculate motor contribution manually, it is easiest to total It is fairly easy to determine a device’s rating from the
all of the motor contribution and add it to the calculated short labeling. However, it is often difficult to determine how much
circuit current. Although this is somewhat simplified and short circuit current would be available at a device if there
therefore not 100 percent accurate, it is the most straight was a fault. Hopefully the past several months of example
forward method. Other considerations would be that motors calculations, formulas and procedures, will help give you a
are distributed throughout the power system and not lumped better understanding of the calculation process. Of course,
at one bus. In that case, you would want to consider what the best method for calculating short circuits is to use as
motor contribution is at each local bus. much detailed data as possible and factor in X/R ratios for
more precise numbers. Due to the complexity of the
In last months example, we calculated a maximum three calculations involved with this level of detail, it is usually
phase short circuit current at the 480 Volt secondary bus of easier to use one of the many available computer programs.
26,845 Amps. Let’s say there are 20 motors with a short The manual methods will get you close, and in most cases
circuit motor contribution of 200 Amps each. That would be will be conservative, which is good for estimating short
a total of 20 X 200 Amps or an additional 4000 Amps of short circuits.
circuit current. If you add this to 26,845 Amps, the total short ________________________________________________
circuit current would be 30,845 Amps. If you were evaluating
equipment rated 30,000 Amps, motor contribution would Legal Stuff - The information contained in this article is
make a difference between an adequate equipment copyrighted material by Technical Training Group. The
application and an inadequate application. information is for general guidance only and neither
Technical Training Group nor Jim Phillips, P.E makes any
NEC® Article 110.9 Short Circuit Interrupting Ratings warranty expressed or implied and assumes no liability what
National Electrical Code® Article 110.9 requires that all so ever for it’s use. Sorry everyone, too many lawyers out
equipment that could interrupt short circuit current in an there.

For more information about T2G Technical Training Group’s Copyright © 2005 T2G Technical Training Group
programs, contact us at 800-874-8883 or www.t2ginc.com You can contact Jim Phillips, P.E. at: jim@jimphillipspe.com

Das könnte Ihnen auch gefallen