IGS ALARM & SAFETY DEVICE TEST RECORD

DATE: 27th June 2006


Abnormal Normal Alarm Alarm
Description Safety Devices Result
State Point Set point Display
Electric Source Fail Energized Failure ER CR System Trip
Control Air Pressure Low 7 kg/cm2 4.2 kg/cm2 ER CR System Stop
Scrubber Water Level High N.W.L. 250 mm ER CR System Trip
Scrubber C.W. Flow Low 280 T/H 240 T/H ER CR System Stop
Scrubber Seal W. Flow Low 3.2 T/H 1.6 T/H ER CR WH alarm only
Scrubber C.W. P/p Motor Trip RUN Overlaod ER CR System Stop
Deck Seal Water Level Low N.W.L. 50 mm ER CR WH alarm only
Deck Seal Water Flow Low 4.8 T/H 2.4 T/H ER CR WH System Stop
No.1 Seal Water Pump Trip RUN Overlaod ER WH alarm only
No.2 Seal Water Pump Trip RUN Overlaod ER WH alarm only
IG Fan Outlet Temp. High 5 ~ 60 'C 65 'C ER CR System Stop
IG Deck Main Press High 1150 mmAq ER CR WH alarm only
200 ~ 1400
IG Deck Main Press Low 200 mmAq ER CR WH alarm only
mmAq
IG Deck Main Press Low-Low 100 mmAq ER CR WH alarm only
No.1 IG Fan Motor Trip RUN Overlaod ER CR System Stop
No.2 IG Fan Motor Trip RUN Overlaod ER CR System Stop
IG Oxygen Content High Below 5 % 5% ER CR alarm only
IG Oxygen Content High-High Below 5 % 8% ER CR IG V/v Shut
Emergency Stop Switch Press Energized Failure ER CR WH System Trip

[Safety Devices Description]


A. System Trip Scrubber C.W. P/p "Stop" Inert Gas
IG Fan "Stop" - Fan Outlet Valve "Shut" Trip :
Uptake Valve "Shut" - Air Seal Valve "Open", C.O.P. Stop
Main Control V/v "Shut" - Vent V/v "Open", Purge Control V/v "Open" Interlock
B. System Stop IG Fan "Stop" - Fan Outlet Valve "Shut" I.G.S. Trip:
Uptake Valve "Shut" - Air Seal Valve "Open", C.O.P. Stop
Main Control V/v "Shut" - Vent V/v "Open", Purge Control V/v "Open" Interlock
C. IG Valve Shut Purge Control V/v "Open", Main Control V/v "Shut" - Vent V/v "Open"
"Oxygen content H/High purge switch is fitted in CCR IGS Sub control panel."

[Reference]
1. I.G.S. Capacity 20,250 m3/Hr
2. I.G. Fan Capacity 20,250 m3/Hr x 2 sets > C.O.P. 5400 m3/Hr x 3 sets = 16,200 m3/Hr
3. P/V Breaker Sealing range = (+) 1950 mmAq ~ (-) 700 mmAq
Sealing liquid = Ethylene glycol 25% + Fresh Water 75% (S.G.= 1.042 @ 20'C)

[Remark]
Tested by Elect.Engineer Chief Engineer