2 Correction curves
The Contractor shall submit the following correction curves:
Change of Plant power output and heat rate with
• ambient air temperature;
• ambient air pressure;
• ambient air humidity;
• generator power factor;
• grid frequency;
• fuel analysis
• gas turbine air inlet pressure drop (for information only);
• gas turbine exhaust pressure drop (for information only);
• non recoverable performance degradation curves (power output and heat rate) due to aging
(expected values for 25 years of operation).
The correction curves will be used to transpose the results of the Performance Tests conducted
at Site conditions ("As-run") to the design conditions ("corrected as-run"), as to allow to compare
"corrected as-run" Test results to Performance Guarantees.
4 Performance Tests
4.1 Scope
The purpose of the Tests on Completion is not only to check whether or not the plant
meets the Performance Guarantee but also to provide a full mass, heat and energy
balance for the whole Plant.
This balance will serve as a reference to evaluate the evolution of the Plant performance
over its life.
Exhibit_B_Attachment_06_Tests_on_Completion.doc Page 3 of 15