Sie sind auf Seite 1von 3

66 KV CANANOOR FEEDER

(ANNUAL RELAY TEST)


DATE OF TEST:
LC. NO:

DATE OF LAST TEST:

1) Over Current and Earth Fault Relay:


Name Plate Detail:
Make: GEC ALSTHOM
Type: CDD
SL.No: 67 A - 9712 4150 003
67C - 9712 4150 004
67N - 9712 4158 002
Settings:-
Current TLS
O/L E/L O/L E/L
Available: ( 0.5, 0.75, 1 , 1.25, 1.5, 1.75, 2) ( 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8 ) 0 -1 0-1

Adopted:- 1 0.4 0.05 0.05

O/L E/L
Obtained Obtained
Applied Expected Applied Expected
67A 67C 67N
Pick up 1A Pick up 0.4 A
2A 0.501 Sec 0.8 A 0.501 Sec
Current = 9, 10
4A 0.249 Sec 1.6 A 0.249 Sec Contact = 3, 4
8A 0.169 Sec 3.2 A 0.165 Sec
10 A 0.149 Sec 4A 0.149 Sec

2) Breaker Testing:-
Make:-
(a) Open / Close Time Intervel:-

+ ve - M 1
RØ YØ BØ
Close - T 1
Close
Open - U 1
Open
Instrument Used:- single pole Timer, Make: PLA, SL.No:423, T & P of AE / GRT / MSG

(b) Contact Resistance:-


Not Measured due to non avaliblity of Kit

( C )Trip Coil Current & Dip in Voltage:-


Trip Coil Current: (+) (-)
M1 & U1

Dip in Voltage: (+) (-)


U1 & U2
52 a Opening Time:-
( 3 ) CT Secondary IR Value:-
(1) Protection ( C74 ) =

( 2 ) Metering ( D72 ) =

Megger Used: Make: Ricken, modle: Lm 500, SL.No: 0409, T & P of AE / GRT / MSG

( 4 )Protection Trip Checking:-

Checked manually by actuating 67A Relay and found the breaker tripped with annoncation .
and 86B , 67X relay indication

AEE / P&C / MSG AE / GTR / MSG

Das könnte Ihnen auch gefallen