Beruflich Dokumente
Kultur Dokumente
POWERCHIP/POWERCORN 50 Special
Installation and assembly instructions
2
POWERCHIP Installation Instructions
Contents Page
1 Introduction..........................................................4
1.1 Safety instructions 4
1.2 Guarantee 4
1.3 Site requirements 4
1.3.1 Boiler room requirements 5
1.3.2 Fuel storeroom requirements 6
1.3.3 Flue requirements 7
4 Plumbing diagrams............................................28
4.1 Plumbing diagrams for Powerchip 20/50 29-35
4.2 Plumbing diagrams for Powerchip 75/100 36-41
4.3 Diagrams for systems supplying multiple
properties 42-44
4.4 Boiler cascade system with sequential boiler control 45
3
POWERCHIP Installation Instructions
1 Introduction
1.2 Guarantee
The manufacturer's guarantee is subject to correct installation
and commissioning of the heating system. Defects and
damage caused by incorrect installation, commissioning or
operation are not covered by the guarantee. To ensure that
the system functions as intended, the manufacturer's
instructions must be followed. Furthermore, only genuine
replacement parts or parts explicitly approved by the
manufacturer may be fitted to the system.
4
POWERCHIP Installation Instructions
5
POWERCHIP Installation Instructions
Fuel auger The drive motor and the necessary electrics must be installed
outside the storeroom.
Damp-proofing The fuel must be protected against rain and contact with water
or damp floors/walls. The storeroom must remain dry all year
round. If there is a risk of temporarily damp walls, fitting a
back-ventilated facing to the walls and lining them with
wooden material may be required.
6
POWERCHIP Installation Instructions
Sub-maximum output
Flue gas Required
Type CO2 Mass flow rate
temp. draught
7
POWERCHIP Installation Instructions
Fig. 1
8
POWERCHIP Installation Instructions
9
POWERCHIP Installation Instructions
8.) Fit the spring arms to the agitator. The agitator rotates
clockwise (Fig. 5). Fit the longest arms opposite one
another. The spring arms (I, Fig. 9) must be 15-20 mm
above the outfeed auger at the point where they pass
over it. Do not tighten the bolts (H, Fig. 9) on the spring
arms. The agitator feet (J, Fig. 9) must be adjusted so
that the longest arm is 3-4 cm clear of the floor at its
lowest point (K, Fig. 9).
9.) Screw the drive unit to the stoker unit using the fixing
screws (L) (M10x100 and M10x140 mm) making sure it
Fig. 5 forms an airtight seal.
Always ensure the drive unit is fitted vertically (at 90‚ to
the floor, see Fig. 6).
10.) Place the agitator centrally in the storeroom so that the
spring arms clear the storeroom walls by a few
centimetres. Firmly secure the agitator to the storeroom
floor using masonry screws and wall plugs.
11.) Using the legs supplied, support the outfeed auger in the
storeroom at the mid-point of the auger and where it
exits the storeroom (Fig. 7) – the legs should not be
more than 120 cm apart.
Position the feet so that they cannot move lengthways.
The legs should rest against the flanges/support
Fig. 6 brackets of the auger. Place sound insulating material
underneath to prevent noise transmission. Adjust the
legs vertically so that the auger is resting firmly on
them. Firmly secure the legs to the storeroom floor
using masonry screws and wall plugs.
12.) Seal the hole in the wall (H, Fig. 9, dimensions H 700 x
W 450 mm) around the outfeed auger with mineral wool
and cover the gap on both sides of the wall with the
cover plates supplied. If necessary, break out the
perforations in the cover plates.
13.) Screw the galvanised mounting brackets supplied to
the boiler base (Fig. 8) using the M8x16 hexagon-head
Fig. 7 bolts and slide the base insert and insulation (N, Fig. 9)
under the boiler base.
14.) If the boiler is to be run on woodchips, a sloping
storeroom floor is not absolutely imperative. If it is to
run on grain or pellets, a sloping storeroom floor must
be constructed.
Use planed timber boards (larch) or blockboard
panels 3 cm thick
Rest the boards/panels on the lip of the outfeed
auger. A supporting substructure as shown in Fig.
11 should be constructed at the rear of the
agitator.
15.) The boarding (V, Fig. 7) over the inspection hatch must
Fig. 8 be provided on site and prevents uncontrolled spillage
of the fuel into the boiler room. A sloping board 3 cm
thick must be fitted at an angle of approx. 20‚, 20 cm
above the outfeed auger, 20 cm from the storeroom
wall and overlapping the inspection hatch opening by at
10
POWERCHIP Installation Instructions
Important → The auger drive unit must form a 100% airtight seal
with the fuel chute. The rubber seal must completely
seal the ball joint. Fix the drive unit securely with the
screws supplied.
16.) Because of the sprinkler system, the temperature
monitor on the outfeed auger is not required for
storerooms with a capacity of no more than 50 m•. If
the storeroom capacity is larger than 50 m•, the
temperature monitor as well as the sprinkler unit must
be connected to the outfeed channel near to where it
passes through the wall. If 50m• of fuel or more can be
stored, a manually operated fire extinguishing facility
must be installed. It must be protected against freezing
and connected to a pressurised water pipe (DN20
conduit). The discharge point must be located directly
above where the fuel outfeed channel exits the
storeroom. The fire extinguishing facility must be
identified by a sign carrying the inscription "Fuel
storeroom fire extinguisher".
11
POWERCHIP Installation Instructions
Fig. 11 Installation of sloping floor, emergency off switch, air vents, fire
extinguisher, wall opening, safety systems
Fig. 11
12
POWERCHIP Installation Instructions
Fig. 12
Important The overall length of the outfeed auger including agitator must
not exceed 7 m. The wall exit section (WS) must always be
fitted where the auger passes through the wall.
Important Always fit the longest agitator arms opposite one another. The
securing screws (W) on the agitator spring arms must not be
fully tightened. Fit the agitator arms so that they clear the
outfeed auger by approx. 15-20 mm.
13
POWERCHIP Installation Instructions
Wall opening The table of dimensions below details the measurements for
positioning the wall opening. The dimensions refer to the
standard agitator outfeed system specifications, i.e. outfeed
unit + 0.55 m trough and agitator.
Wall opening
Width 450 mm
Height 700 mm
Inspection hatch construction The construction of the inspection hatch and the associated
wall lining should be carried out as described below and will
enable access to the storeroom for the purposes of removing
any objects that may be jammed in the auger before the
enclosed section of the auger trough. The hatch canopy
constructed as per Fig. 7 prevents the stored fuel spilling out
when the inspection hatch is opened.
D
B B 1.) Pack the gap at the sides and below the outfeed auger (A)
C A with mineral wool (B).
Fig. 13 2.) Fit the cover plates supplied (C) on the inside and outside.
3.) Fix the top edge of the lining (D) in the wall flush with the
F E cover plates.
4.) Cut a section of mineral wool (E) to size to fit the hatch
G opening.
5.) Insert the mineral wool (E) between the cover plate (F)
and the inspection hatch rear panel (G) as shown in
Fig. 14 Fig. 14 using the hexagon-head bolts supplied.
6.) Fit the inspection hatch cover (H) and secure with wing
nuts.
H
Fig. 15
14
POWERCHIP Installation Instructions
The hole in the wall for connecting the flue pipe must be lined
with a built-in double-skinned lining tube or fireproof material.
The flue connecting pipe must rise upwards from the boiler to
the flue at an angle of at least 6‚ and be connected with gas-
tight joints. An inspection cover must be provided for cleaning
the flue connecting pipe.
B → Testing point:
distance from boiler
3x flue tube diameter
Flue caps and hoods Must be made of non-combustible materials and must not
reduce the cross-sectional area of the flue, decrease the flue
draught or obstruct the cleaning of the flue. The flue gas
should be able to exit vertically from the flue outlet without
hindrance. The method of fixing must be capable of
withstanding strong gusts of wind.
15
POWERCHIP Installation Instructions
Flue draught The flue draught should not differ by more than +/- 3 pascals
from the figure specified in the flue dimensioning data (see
Section 1.3.3). If the flue draught cannot be reduced to the
required figure, either a larger draught regulator should be
fitted or an additional flue baffle fitted between the flue and the
draught regulator.
Too much flue draught May cause the flue gas temperature to increase and
accelerate combustion as a result. Poor boiler output
adjustability, increased dust discharge and malfunctions can
result.
16
POWERCHIP Installation Instructions
Fig. 17
Powerchip 75/100
E → Drain
Fig. 18
17
POWERCHIP Installation Instructions
Temperature-relief heat exchanger The maximum permissible operating temperature of the boiler
is 110‚C. In order to prevent the maximum allowable
operating temperature being exceeded, connection of a
temperature-relief valve (Fig. 19, Fig. 20) conforming to
Austrian standard ‡NORM 8131 and DIN 4751 and with a
response temperature of 95‚C is required. The supply
pressure must be at least 2 bar but no more than 6 bar.
Fig. 19
Powerchip 75/100
Fig. 20
18
POWERCHIP Installation Instructions
Return boost The boiler return temperature must be at least 55‚C and must
be held at the required level by a bypass pump between the
boiler flow and return pipes. If a thermal store is connected,
the boiler return temperature must similarly be at least 55 ‚C,
which must be ensured by a return boost (cross-over valve)
set as shown in the plumbing diagram. If this requirement is
not complied with, there is an increased risk of corrosion and
guarantee entitlement will be lost as a result. Connect the
return boost set precisely as specified in our plumbing
diagrams.
Important → The dimensioning of the return boost pump (set) is designed
for the arrangements shown in GUNTAMATIC plumbing
diagrams. If additional components such as heat meters are
incorporated in the system plumbing, or if the overall thermal
store pipe run (flow and return) is more than 30 m, re-
dimensioning of the boiler charging pump (HP0) may be
necessary.
Expansion vessel The boiler operates in a sealed heating system and must be
provided with an expansion vessel for pressure compensation.
To calculate the expansion volume, the volume of the system
when cold must be known. Please select the expansion vessel
on the basis of the manufacturer's specifications. The
expansion volume of the system is calculated as follows:
Plastic piping If plastic piping for underfloor heating or district heating pipes
are connected, they must be protected against excessive
temperatures by using a limiting thermostat for the circulation
pumps.
Pump selection The choice of pump must be made by the installer or building
technology planner on the basis of the friction data, the pipe
cross-sectional area and the required delivery pressure for the
piping system planned.
19
POWERCHIP Installation Instructions
20
POWERCHIP Installation Instructions
21
POWERCHIP Installation Instructions
Wall controller set MK261 The wall controller set MK261 can be used to control a DHW
cylinder, a pumped heating circuit, 2 mixed heating circuits,
one supplementary function (HWP or EXTERNAL) and a
district heating pipe. If the supplementary and district heating
functions are not used, heating circuit 0 can be operated as a
mixed circuit.
Maximum configuration Max. 3 MK261 wall controller sets per heating system
Temperature Temperature
KVT20 in kΩ PT1000 in kΩ
in ‚C in ‚C
-20‚C 1.383 -10‚C 0.961
-16‚C 1.434 0‚C 1.000
-8‚C 1.537 10‚C 1.039
-4‚C 1.590 20‚C 1.078
0‚C 1.644 30‚C 1.117
10‚C 1.783 40‚C 1.155
20‚C 1.928 50‚C 1.194
30‚C 2.078 60‚C 1.232
40‚C 2.234 70‚C 1.271
50‚C 2.395 80‚C 1.309
60‚C 2.563 100‚C 1.385
70‚C 2.735 125‚C 1.480
80‚C 2.914 150‚C 1.573
22
POWERCHIP Installation Instructions
Important Low-power leads and CAN bus connecting cables must not be
routed along a shared conduit with the mains power!
Sensor 2 x 1mm€
RG 0 RG 3 RG 6
RG 1 CAN - BCE
SH - L H +
RG 4 CAN - BCE
SH - L H +
RG 7 CAN - BCE
SH - L H +
CAN - Bus
CAN - Bus
CAN - Bus CAN - Bus CAN - Bus
SH - L H + SH - L H + SH - L H + SH - L H + SH - L H + SH - L H +
CAN - BCE CAN - BCE CAN - BCE
BCE
DAQ
Key:
TPM → Router module (400VAC)
BCE → Display and control unit
HKR → Heating circuit controller (230V AC)
RG → Analogue room stat
PE N P E 1 0 2 1 0 1 1 00 1 04 1 0 3 N PE N P E 1 0 7 1 0 6 10 5 N 1 1 0 1 0 9 10 8 PE 113 112 111 N N 114 P E N 11 5 P E
TPM 400VAC
CAN - Bus
PE 1 2 6 1 2 5 PE 1 24 1 2 3
12 7
1 30 1 2 9 1 2 8
Important Whenever possible, always wire the CAN bus "in line", i.e.
from the display and control unit to heating circuit controller 0
then from there to heating circuit controller 1, and so on. If
wired in a star pattern, the overall length of the CAN bus must
not exceed 100 metres. Wire the CAN bus +/- and H/L
connections with twisted-pair cable in each case.
23
POWERCHIP Installation Instructions
Mains power supply A three-phase power supply is required (400V, 50Hz, 13A
fuse). The mains power must be connected by means of the
standard non-reversible power socket on the rear panel of the
boiler. It must possible to isolate the system entirely from the
mains without opening the switch panel cover.
Opening switch panel Before the switch panel is opened, the mains lead must be
unplugged from the socket on the rear panel of the boiler. The
system must not be live.
Undo switch panel securing screw
Lift up front right plastic panel section slightly, pull
forwards at the bottom and unclip at the top.
The circuit boards with the associated connectors and
fuses (see electrical wiring diagram) are located
underneath it in an easily accessible position.
The appropriate cable ducts must be used when
connecting electrical leads.
Boiler cascade system If multiple boilers (max. 4) are operated in a cascade system
(sequential boiler system), all systems must be connected in
line by means of a CAN bus. The CAN bus must be wired
without connecting the + terminal.
Wall controller set MK261 The wall controller set MK261 must be connected to the
power supply at terminal H35 and connected to the boiler or
another wall controller via the CAN bus.
24
POWERCHIP Installation Instructions
External burner request With wall controller set MK261, the supplementary output
(terminal H25) can be used to request heat from an external
boiler. The load on the output must not exceed 230V and
2.0A. With this configuration option, it is not possible to
operate three mixed heating circuits. The district heating pipe
function is available, however.
Connecting 2 DHW cylinders With wall controller set MK261, the supplementary output
(terminal H25) can be used to run an additional DHW cylinder.
With this configuration option, it is not possible to operate
three mixed heating circuits. The district heating pipe function
is available, however.
3 mixed heating circuits With wall controller set MK261, the supplementary output
(terminal H25) and the district heating pipe output (terminal
H26) can be used to control heating circuit 0 using a mixer
valve motor. The associated heating circuit pump is connected
to terminal H33 (HKP 0). With this configuration option, the
district heating pipe and supplementary functions are not
available.
Analogue room stat The room stat should be connected to the MK261 wall
controller set at terminals 1 and 2 (see electrical wiring
diagram).
Digital room controller The room controller must be connected to the boiler or wall
controller set MK 261 via CAN bus.
Emergency off switch According to prTRVB H 118, it must be possible to switch off
the system using an emergency off switch fitted outside the
boiler room near to the boiler room door. The burner must
then shut down but the heating controller and all safety
equipment must remain functional. Connected to the boiler
enabling switch, terminals 22/23 on the boiler circuit board
(see electrical wiring diagram).
Important → Repair work on the system must only be carried out when
the system has been isolated completely from the power
supply.
Automatic ash extraction system This is connected according to the installation and operating
instructions supplied with the automatic ash extraction system.
25
POWERCHIP Installation Instructions
26
POWERCHIP Installation Instructions
The boiler is designed as a Class 3 appliance as defined by the draft standard ‡NORM EN
303-5 (CEN/TC7/WG 1 – Doc. N 36-D) of 15/12/1996 and the agreement of the [Austrian]
Federal States according to Art. 15a BVG, in accordance with the Austrian fire safety
regulations, safety systems, CE and on safety measures for small combustion heating
systems and the combustion heating system approval regulations (LGB.33/1992) of the
Austrian Federal State of Steiermark. The original design type approval certificates (BLT
Wieselburg, IBS Linz) are available for inspection at the manufacturer's offices.
Austria
‡NORM M 7550 Central heating boilers up to 100‚C – Terms,
requirements, tests, standard identification
‡NORM M 7510 Part 1: Guidelines for the inspection of central
heating systems
‡NORM M 7510 Part 2: Guidelines for the inspection of central
heating systems, guide figures
‡NORM B 8130 Safety systems
‡NORM B 8131 Sealed water-circulation heating systems, safety
requirements
‡NORM B 8133 Safety requirements, domestic hot water systems
‡NORM H 5195-1 Assessment and suitability of the heating water
(minimum requirements for the heating water)
prTRVB H 118 Technical regulations, preventative fire safety for
automatic wood-burning systems
HEATING OUTPUT: The heating output is to be selected (set) by the
engineer in accordance with the local heating system regulations so
that the rated heat output does not exceed the heat requirement
determined according to DIN 4701 or ‡NORM M7500.
Germany
DIN 4751-1 / Safety systems for heating systems with flow
temperatures up to 110‚C (120‚C in course of preparation)
DIN 4751-2 / Water-circulation heating systems – sealed heating
systems with thermostatic safety systems and flow temperatures up
to 120‚C – safety systems
DIN 4751-4 / Safety systems for domestic hot water systems with flow
temperatures up to 120‚C; sealed water-circulation heating systems
with static heads over 15 m or rated heat outputs over 350 kW
DIN 1988 Mains water piping systems on building plots, technical
regulations for construction and operation
Switzerland
Swiss Clean Air Regulations (LRV)
Swiss Regulations on Small Combustion Heating Systems
VKF Fire Safety Directive for Heating Systems
SIA 384
United Kingdom
BSEN 303-5
UK Building Regulations 2000 (Parts B, J, L,P)
Other standards and regulations may be applicable in other countries and must be complied
with.
27
POWERCHIP Installation Instructions
4 Plumbing diagrams
Diagram no.: PH-01-1 Outside temp. based controller, DHW cylinder ECO305
Diagram no.: PH-01-2 Outside temp. based controller, 2 ECO305 DHW cylinders
Diagram no.: PH-02-1 Outside temp. based controller, thermal store PSB, integrated solar panel
system
Diagram no.: PH-03-1 Outside temp. based controller, DHW cylinder ECO305, thermal store PS
Diagram no.: PH-04-1 Outside temp. based controller, thermal store PSB
Diagram no.: PH-05-1 Outside temp. based controller, DHW cylinder ECO305, district heating
pipe
Diagram no.: PH-06-1 Outside temp. based controller, DHW cylinder ECO305, thermal store
PS, district heating pipe
Diagram no.: PH-07-1 Outside temp. based controller, DHW cylinder ECO305, thermal store PS
Diagram no.: PH-08-1 Outside temp. based controller, thermal store PSB, connected solar
panel system
Diagram no.: PH-09-1 Outside temp. based controller, thermal store PSB
Diagram no.: PH-10-1 Outside temp. based controller, DHW cylinder ECO305
Diagram no.: PH-11-1 Outside temp. based controller, DHW cylinder ECO305, district heating
pipe
Diagram no.: PH-12-1 Outside temp. based controller, DHW cylinder ECO305, thermal store
PS, district heating pipe
Diagram no.: PH-13-1 District heating pipe supply via charging pump (LAP) for max. 3
properties
Diagram no.: PH-14-1 District heating pipe supply via feeder pump (ZUP) for max. 3 properties
Diagram no.: PH-15-1 District heating pipe supply via thermal store pump (PUP) for max. 3
properties
Diagram no.: PH-16-1 Boiler cascade system with sequential boiler control for max. 4 boilers
28
UK Agent:
Plumbing diagram for Powerchip 20/50 TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Setting on HP0 menu: → HP0 mode = Feeder pump Heat from biomass 29
UK Agent:
Plumbing diagram for Powerchip 20/50 TRECO Ltd
Outside-temperature based controller, 2 ECO DHW cylinders Tel. 0845 1309012
1 Wall controller set MK 261 (HKR 0) → 2 DHW cylinders, 1 pumped heating circuit, 2 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Feeder pump Heat from biomass 30
UK Agent:
Plumbing diagram for Powerchip 20/50 TRECO Ltd
Outside-temperature based controller, thermal store PSB, connected solar panel system Tel. 0845 1309012
1 Wall controller set MK 261 (HKR 0) → 1 DHW cylinder in thermal store, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 31
UK Agent:
Plumbing diagram for Powerchip 20/50 TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder, PS thermal store Tel. 0845 1309012
1 Wall controller set MK 261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 32
UK Agent:
Plumbing diagram for Powerchip 20/50 with solid fuel boiler TRECO Ltd
Outside-temperature based controller, thermal store PSB Tel. 0845 1309012
1 Wall controller set MK 261 (HKR 0) → 1 DHW cylinder in thermal store, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 33
UK Agent:
Plumbing diagram for Powerchip 20/50 with district heating pipe TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder Tel. 0845 1309012
1 Wall controller set MK 261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Feeder pump Heat from biomass 34
UK Agent:
Plumbing diagram for Powerchip 20/50 with district heating pipe TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder, PS thermal store Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 35
UK Agent:
Plumbing diagram for Powerchip 75/100 TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder, PS thermal store Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 36
UK Agent:
Plumbing diagram for Powerchip 75/100 TRECO Ltd
Outside-temperature based controller, thermal store PSB, connected solar panel system Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder in thermal store, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
GUNTAMATIC components
Diagram no. PH-08-1 1. Powerchip woodchip system
Electrical connections as per operating and installation instructions 2. Flue draught regulator RE20 with pressure surge
compensator Art. no.: H38-160
3. Outside temp. based wall controller set MK261 Art. no.: S30-030
With wall controller set MK261, the supplementary output (terminal H25) and the district heating
4. Thermal store PSB As price list
pipe output (terminal H26) can be used to control heating circuit 0 using a mixer valve motor. The Order 1 special sleeve, …", for sensor T2 As price list
heating circuit pump is connected to output HKP 0 (terminal H33) and flow temperature sensor 0 Order thermal store lower heat exchanger flange As price list
to terminal H21/H22. With this configuration option, the district heating pipe and supplementary 5. Mixer valve positioner motor SM70 Art. no.: S50-501
6. Room stat RFF25 Art. no.: S70-006
functions are not available. 7. GSM module Art. no.: S15-002
8. Recommendation for 30m 1…" thermal store piping (flow and return)
Grundfos UPS 32-100 or Wilo S30/10 Not supplied
in conjunction with thermostatic valve, 55C‚ 2" Art. no.: H39-204
Alternatively: RA100 EnergieA Art. no.: H39-010
9. Fault indicator lamp Important: follow wiring diagram! Not supplied
10. Ridged pipe heat exchanger As price list
11. 2 Thermal store sensors Art. no.: S70-003
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 37
UK Agent:
Plumbing diagram for Powerchip 75/100 TRECO Ltd
Outside-temperature based controller, thermal store PSB Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder in thermal store, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 38
UK Agent:
Plumbing diagram for Powerchip 75/100 TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Feeder pump Heat from biomass 39
UK Agent:
Plumbing diagram for Powerchip 75/100 with district heating pipe TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder Tel. 0845 1309012
1 Wall controller set MK 261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Feeder pump Heat from biomass 40
UK Agent:
Plumbing diagram for Powerchip 75/100 with district heating pipe TRECO Ltd
Outside-temperature based controller, ECO DHW cylinder, PS thermal store Tel. 0845 1309012
1 Wall controller set MK261 (HKR 0) → 1 DHW cylinder, 3 mixed heating circuits info@treco.co.uk
www.treco.co.uk
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump HP0 sensor = HCC 0 Heat from biomass 41
Plumbing diagram for district heating pipe supply via charging pump (LAP) for max. 3 UK Agent:
properties TRECO Ltd
POWERCHIP, POWERCORN or BIOCOM 75/100 kW boiler Tel. 0845 1309012
For each property, one wall controller set MK261 → max. 1 thermal store, 1 pump circuit, 2 mixed circuits and 2 DHW cylinders info@treco.co.uk
per property www.treco.co.uk
compensator Art. no.: H38-160
3. Outside temp. based wall controller set MK261 Art. no.: S30-030
4. DHW cylinder ECO305 Art. no.: 048-500
5. Thermal store PSB As price list
6. Room stat RFF25 Art. no.: S70-006
7. GSM module Art. no.: S15-002
8. Recommendation: Grundfos UPS 32-100
or Wilo Top-S30/10 Not supplied
in conjunction with thermostatic valve, 55C‚ 2" Art. no.: H39-204
Alternatively: RA100 EnergieA Art. no.: H39-010
9. Dimension charging pumps according to length of piping run
11. Mixer valve positioner motor SM70 Art. no.: S50-501
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump Heat from biomass 42
Plumbing diagram for district heating pipe supply via feeder pump (ZUP) for max. 3 properties UK Agent:
POWERCHIP, POWERCORN or BIOCOM 75/100 kW boiler TRECO Ltd
For each property, one wall controller set MK261 → max. 1 pump circuit, 2 mixed heating circuits and 2 DHW cylinders per Tel. 0845 1309012
property info@treco.co.uk
www.treco.co.uk
1. Powerchip, Powercorn or Biocom 75/100 kW
2. Flue draught regulator RE20 with pressure surge
3. Outside temp. based wall controller set MK261 Art. no.: S30-030
4. DHW cylinder ECO305 Art. no.: 048-500
Settings on HP0 parameters menu: → HP0 mode = Thermal store pump Heat from biomass 43
Plumbing diagram for district heating pipe supply via thermal store pump (PUP) for max. 3
UK Agent:
properties TRECO Ltd
POWERCHIP, POWERCORN or BIOCOM 75/100 kW boiler Tel. 0845 1309012
For each property, one wall controller set MK261 → max. 1 thermal store, 1 pump circuit, 2 mixed circuits and 2 DHW cylinders info@treco.co.uk
per property www.treco.co.uk
GUNTAMATIC components
1. Powerchip, Powercorn or Biocom 75/100 kW
3. Outside temp. based wall controller set MK261 Art. no.: S30-030
Setting on HP0 parameters menu: → HP0 mode = Feeder pump Heat from biomass 44
UK Agent:
Plumbing diagram for boiler cascade system with sequential boiler control TRECO Ltd
POWERCHIP, POWERCORN or BIOCOM boiler Tel. 0845 1309012
For maximum of 4 boilers info@treco.co.uk
www.treco.co.uk
Important: The CAN bus must be wired without connecting the + terminal.
Note: Only one boiler can be controlled/queried remotely via the GSM
module. However, faults are forwarded to the GSM module via
the CAN bus.
Heating circuit
installation:
Diagram PH-13-1
with charging pump (LAP)
and thermal store
Diagram PH-14-1
with feeder pump (ZUP) and
without thermal store
Set output HP0 to thermal store pump for each system Heat from biomass 45
POWERCHIP Installation Instructions
5 Electrical wiring diagram (only use flexible cable and core sleeving for wiring)
5.1 Control panel and 400V router module
Key:
BCE = Display and control unit
GSM = Remote control via mobile phone
STB = Safety temperature limiter
Power I/0 = Mains power switch (system On/Off)
TPM 400V = 400V router module circuit board
Netz 400V 13A = 400V 13A power supply connection
Netz 230V = Boiler circuit board power supply
CAN-BUS = Cable connection betw. BCE and wall controller set MK261 or room controller RS100
SY-BUS = Cable connection betw. BCE and boiler circuit board
HKR = Outside-temperature based heating circuit controller
RS100 = Digital room controller
G1 = Drive motor, 400V (stoker drive motor)
A1 = Drive motor, 400V (fuel auger A1)
A2 = Drive motor, 400V (feeder auger A2)
TKS3 = Overfill cover monitor, feeder auger A2
SY-Bus
Netz 230V
BCE
(Bedien- u. Kontrolleinheit)
GSM
Power I/0
GSM STB
KP - I/O
CAN-Bus (HKR, RS100)
Netz 400V 13A
Netz 230V
S ic h e r h ei ts k ette
(400V)
(400V)
(400V)
G1
A1
A2
PE
PE
L1
L2
L3
N
1 18 1 1 7 1 1 6
R e la is
R e la is
P E 1 22 12 1 1 2 0 1 19
P E 1 2 6 1 2 5 P E 1 2 4 1 23
TPM 400V
(Transportmodul 400V)
12 7
1 3 1 13 0 1 2 9 1 28
F1 6 F1 5 F 13 F 11
F 18 F1 7
CAN MODULE
address
Default setting: TKS 3
F 14 F 12 F 10 Position "0" (230V)
PE 134
N
135
DIP switch
Default setting:
Both "OFF"
O FF
ON
1 5 4 153 1 5 2 151 1 5 0 1 4 9 1 4 8 147 146 1 4 5 1 4 4 143 1 4 2 141 140 139 1 3 8 1 3 7 136
46
POWERCHIP Installation Instructions
5.2 Boiler circuit board (only use flexible cable and core sleeving for wiring)
Netz 230V = Boiler circuit board power supply Power supply for electronics upline
F2 T 0.63A
Lambda = Flue gas monitor of mains transformer
BSK = Fire safety flap
F3 T 10A STB, ZG, REI, HP0
SMA = Fault indicator output
Hall 1 = Grate cleaner motor monitor
F4 T 2A STB, KFR, TKS1
FZ = Fill level switch (fire box monitor)
RGT = Non-replaceable flue gas temperature sensor F5 T 4A Line fuse: SG
T1 = Boiler temperature sensor input
T2 = Thermal store sensor input F6 T 4A Line fuse: not used
T3 = Thermal store top sensor input
STF = Stoker sensor input (stoker temperature monitor)
TKS1 = Door switch (firebox door and ash box monitor)
TKS2 = Cover switch (overfill cover monitor, feeder auger A1)
BÅ = If unused jumper is standard
KFR = Boiler enabling switch (emergency off)
HP0 = Programmable output: thermal store pump or feeder pump
REI = Drive motor for stepped grate and grate cleaning
SG = Flue draught fan
ZG = Ignition fan
NF = Mains filter
Hall A1
(green)
(black)
(24V)
(red)
BSK
Lambda
SY-Bus
PE
L1
Stecker
RGT
M
T1
24V=
FZ
SMA
Netz 230V
(yellow/green)
1 (black) VCC
+ (green)
1 (black)
2 (white)
+ (black)
2 (black)
- (white)
3 (6-pol)
1 (6-pol)
(white)
(white)
- (grey)
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 39 40 4 1 4 2 4 3 4 4 4 5 4 6 4 7 4 8 4 9 50
LINE NF
MKR
BCE
L 5 1 5 2 5 3 5 4 5 5 5 6 5 7 5 8 5 9 6 0 6 1 6 2 6 3 6 4 6 5 66 39 40 41 42 43 44 45 46 47 48 49 50
LOAD
31 32 33 34 35 36 37 38
37 38
STF
BCE - TPM 400V
1 PE N 2 3 PE N
1 PE N 2 3 PE N
ZG
35 36
M
1~
(230V)
33 34
T3
SG
1~
M
(230V)
31 32
T2
KP - I/O
4 PE N
4 PE N
L
28 29 30
28 29 30
PE
B‰
N
Kesselplatine - I/O
24 PE 25 26 PE 27
24 PE 25 26 PE 27
TKS 1
(230V)
5 PE N
5 PE N
TKS 2
(230V)
6 7 8 PE 9
6 7 8 PE 9
10 PE N 11 12 16 17 18 19
13 PE N 14 PE N 15 PE N 20 PE N 21 PE N 22 PE 23
13 PE N 14 PE N 15 PE N 20 PE N 21 PE N 22 PE 23
10 PE N 11 12 16 17 18 19
B‰
1~
1~
M
M
(230V)
(230V)
(230V)
KFR
HP0
REI
47
POWERCHIP Installation Instructions
5.3 Wall controller set MK261 (only use flexible cable and core sleeving for wiring)
Key:
CAN-BUS = Cable connection betw. BCE, wall controller set MK261 and room controller RS100
Netz 230V = Wall controller power supply
HKR 0 (1, 2) = Wall controller set MK261 Fuse assignment for wall controller
BCE = Display and control unit
F1 T 0.63A Power supply for electronics
RS100 = Digital room controller
RG 0 (1, 2) = Analogue room stat input HKP 0, HKP 1, HKP 2, MI 0, MI
F2 T 6.30A
AF = Outside sensor input 1, MI 2, SLP 0, FL 0, ZU 0
VF 0 (1, 2) = Flow temperature sensor input
SF = Cylinder sensor input Function of LEDs
ZSF = Supplementary cylinder sensor input
Controller on, CAN bus cable correctly connected:
T2 = Thermal store sensor input
T3 = Thermal store top sensor input LED → H5 (green) should light up
SMA = Fault indicator output LED → H6, H7 (orange) should flash
FFR = District heating pipe enabling switch Mains power and fuse F1 are OK
BÅ = If unused jumper is standard
SLP 0 (1, 2) = Cylinder charging pump output LED → H1, H4 (green) should light up
LED → H2, H3 (green) should flash
HKP 0 (1, 2) = Heating circuit pump output
MI 0 (1, 2) = Mixer valve motor output
FL 0 (1, 2) = Output for district heating pipe pump
ZU 0 (1, 2) = Output usable for ext. burner or DHW cylinder (see Section 2.14 Electrical connections)
FL+ZU = Programmable as third mixed heating circuit on wall controller (see Section 2.14 Electrical
connections)
us
(9,2V= 20 mA)
-B00)
AN(RS1
SMA
C
CAN-Bus CAN-Bus
(BCE) (HKR)
H39 H38
Terminal assignment on RFF25
Connect contacts 1 and 2
SH - L H + SH - L H +
1 CAN - BCE
H1 H2
RG 0 (3, 6) 2
1
H3 H4
RG 1 (4, 7) 2 ON
RG 2 (5, 8) 2 1 2
both DIP switches "ON"
OFF
H 7 H8
AF
H9 H10
VF 2 (5, 8)
B‰
H11 H12
VF 1 (4, 7)
H 13 H 14
H36 PE H37
SF 0 (1, 2) Caution:
Change to S2 setting only FFR
effective after switching mains (230V)
H15 H16
T2
HKR 0 (1, 2)
H19 H 20
T3
(WandgerŠt Set MK261)
H21 H 22
VF 0 (3, 6)
H25 PE N H26 PE N
PE
N
AUF
ZU
ZU
AUF
Netz
(230V)
ZU
AUF
1~
1~
1~
1~
1~
1~
1~
1~
M
M
M
(230V)
(230V)
SLP 0 (1,2)
(230V)
ZU 0 (1, 2)
(230V)
(230V)
(230V)
(230V)
(230V)
FL 0 (1, 2)
MI 2 (5, 8)
HKP 0 (3, 6)
HKP 2 (5, 8)
HKP 1 (4, 7)
MI 1 (4, 7)
1~
M
(230V)
MI 0 (3, 6)
48
POWERCHIP Installation Instructions
6 Technical data
6.1 Powerchip 20/30 and 40/50
49
POWERCHIP Installation Instructions
50
POWERCHIP Installation Instructions
51
POWERCHIP Installation Instructions
6 Millennium Place
Tiverton Business Park
Tiverton
Devon
EX16 6SB
Tel: 0845 1309012
info@treco.co.uk
www.treco.co.uk
52