MODIFICATION MADE DURING RELIABILITY TEST

ANTIFOAM DOSING FLOW HIGH - WARNING IS GIVEN A TIME DELAY OF 10 SECONDS


CONTINOUS DOSING FLOW LOW LOW ACTIVE AND ANY TWO OF THE THREE DOSING PUMPS RUNNING CONTINOUSLY FOR M
CONTINOUS DOSING FLOW LOW ACTIVE AND ANY TWO OF THE THREE DOSING PUMPS RUNNING CONTINOUSLY FOR MORE
SHOCK DOSING FLOW LOW ACTIVE AND ANY TWO OF THE THREE DOSING PUMPS RUNNING CONTINOUSLY FOR MORE THAN
SHOCK DOSING FLOW LOW LOW ACTIVE AND ANY TWO OF THE THREE DOSING PUMPS RUNNING CONTINOUSLY FOR MORE

WARNING ACTIVE AT 0.3 PPM


CEP DISCH PRESS HIGH ALARM CHANGED FROM 26 barg-->26.5 barg

Offset is given 20 mm
CLNG WTR DWN STRM PRESS HIGH WARNING CHANGED FROM 2.0barg-->2.2barg

DRN SEP LSL ALARM-->WARNING


DRN SEP LSH ALARM-->WARNING
SEAWATER MAKEUP FLOW LOW WARNING CHANGED FROM 7600-->6000m3/h
ANTIFOAM DOSING FLOW IS GIVEN A SMOOTHENING TIME OF 5 SECONDS
ANTISCALE DOSING FLOW IS GIVEN A SMOOTHENING TIME OF 5 SECONDS
SODIUM SULPHATE DOSING FLOW IS GIVEN A SMOOTHENING TIME OF 5 SECONDS
LASTSTAGE DISTILLATE LEVEL 1 o 2 WARNING LEVEL CHANGED 800-950 mm

Set point of Desuper Heater Control Valve is rearranged such that if [ TBT<102 => SP = 105 & TBT>102 => SP = 119]

GP#1 PRIMING TANK 1 LSL ALARM --> WARNING


GP#1 PRIMING TANK 2 LSL ALARM --> WARNING
GP#2 PRIMING TANK 1 LSL ALARM --> WARNING
GP#2 PRIMING TANK 2 LSL ALARM --> WARNING
COND WATER FLOW LOW [<165 m3/h] ACTIVE & CONDENSATE MIN FLOW VALVE CLOSED FOR MORE THAN 30 SEC , THEN, TH
COND WTR TO DS/HTR FLOW HIGH WARNING--> STATUS

ABSORBER FLOW LOW CHANGED 370-->200 mm

ANTIFOAM DOSING FLOW WARNING A TIMEDELAY OF 60 SECONDS


ANTIFOAM DOSING FLOW WARNING A TIMEDELAY OF 60 SECONDS
DEGAS LS LL ALARM --> WARNING
DEGAS LS LL ALARM --> WARNING
BRINE BLOW DOWN FLOW LOW WARNING IS GIVEN A DELAY OF 30 SEC

IF THE DEVIATION (>10) OF DESUPERHEATERCONTROL VALVE REMAINS MORE THAN 30 SECONDS THEN WARNING IS ACTIVE

IF CEP 1 & 2 CLOSED FOR MORE THAN 10 SECONDS (TIME DELAY) THEN PROTECTION CLOSE IS GIVEN TO BH LEVEL CONTROL

IF DIP1&2 CLOSED MORE THAN 1 MINUTE (TIME DELAY) THEN PROTECTION CLOSE IS GIVEN TO DIST WTR LEVEL CONTROL VA
ING CONTINOUSLY FOR MORE THAN 30 SECONDS --> WARNING ACTIVE
ONTINOUSLY FOR MORE THAN 30 SECONDS --> ALARM ACTIVE
NOUSLY FOR MORE THAN 30 SECONDS --> WARNING ACTIVE
CONTINOUSLY FOR MORE THAN 30 SECONDS --> ALARM ACTIVE

02 => SP = 119]

E THAN 30 SEC , THEN, THE FLOW LOW WARNING WILL BE ACTIVE

THEN WARNING IS ACTIVE

N TO BH LEVEL CONTROL VALVE

WTR LEVEL CONTROL VALVE