Presented by
Bob Omidvar
Dry bulb 15C Relative humidity 60% Wet bulb temperature 7.2C Atmospheric pressure 1 bar (sea level)
Most of the gas turbine installations are not in ISO standard locations, they are in the real world
Water Tank
Exhaust Gas
Fuel
Combustion Turbine
Evaporative Cooler
Applications: Areas where RH and wet bulb temperature is rather low
Advantage
# # # #
Disadvantage
#
Lowest capital cost Lowest O&M cost Can operate on raw water Quick delivery and installation time Operates as an air washer and cleans the inlet air
Exhaust Gas
Fuel
Combustion Turbine
Fog Systems
Fogging System Demin. Water Consumption Inlet air 36C DB, 25C WB Chilled air temp 25.5C DB 25C WB, 96%RH
t/h
Fogging System
Applications: Areas where RH and wet bulb temperature is rather low
Advantage
# # #
Disadvantage
#
Low capital cost Low O&M cost Can increase gas turbine performance better than evaporative cooling Quick delivery and installation time
Combustion Air Air Filter Condensate Drip Pan Ammonia Liquid Line
Exhaust Gas
Fuel
Combustion Turbine
Advantage
#
Disadvantage
# # #
Can increase gas turbine performance better than evaporative cooling, and fog system
High initial capital cost High O&M cost Longer delivery and installation time Expertise is needed to operate and maintain the plant
Combustion Air Mechanical Chiller Air Filter Air Cooling Coil Condensate Drip Pan
Exhaust Gas
Fuel
Combustion Turbine
Advantage
#
Disadvantage
# # # #
Can increase gas turbine performance better than evaporative cooling, and fog system Not very sensitive to ambient air wet bulb temperature
# # #
High initial capital cost High O&M cost Long delivery and installation time Expertise is needed to operate and maintain the plant Requires extra chilled water cooling circuit Higher parasitic load than direct type Higher energy input compared to direct type chiller
Inlet Air Cooling With Ice Storage, Chilled Water Storage System Schematic
Combustion Air Mechanical Chiller/ Ice Maker Ice Storage Tank Air Filter Air Cooling Coil Condensate Drip Pan
Exhaust Gas
Fuel
Combustion Turbine
Mech. Chiller
Combustion Air Air Filter Air Cooling Coil Condensate Drip Pan
Exhaust Gas
Fuel
Combustion Turbine
Advantage
#
Disadvantage
# # #
Can increase gas turbine performance better than evaporative cooling, and fog system Not very sensitive to ambient air wet bulb temperature Can utilise low night time tariff to produce and store ice for peak hours operation
High initial capital cost High O&M cost Longer delivery and installation time Higher expertise is needed to operate and maintain the plant
Chiller Electrical Load MW 36C DB, 25C WB, 10C Chilled Air Temp
6
Combustion Air Absorption Chiller Air Filter Return Condensate LP Steam Air Cooling Coil Condensate Drip Pan
Exhaust Gas
Fuel
Flow Diagram
Pressure approx. 60 Torr 60 mm Hg 80 mbar 8 kPa Condenser tc 45C 37C Tower Water Out
Generator
Heat Medium In
70 C
95 C
to 4C 6C Chilled Water
Evaporator
12C
Absorber 32,5C 27C ta 35C Chilled Water Tower Water Concentrated Solution (LiBr) Diluted Solution (LiBr) Steam or Hot Water Refrigerant (Water) 50C Picture courtesy of York International Tower Water In
70C
Absorption Chiller Steam Consumption 36C DB, 25C WB, 10C Chilled Air Temp
80 70
60 50 40 30 20 10 0
25
50
75
100
125
150
175
200
225
250
275
Advantage
#
Disadvantage
# # #
Can increase gas turbine performance better than evaporative cooling, and fog system Not very sensitive to ambient air wet bulb temperature Low electrical parasitic load
High initial capital cost High O&M cost Longer delivery and installation time High expertise is needed to operate and maintain the plant In case of a steam operated chiller, cannot be applied in an open cycle gas turbine plant
Advantage
#
Disadvantage
# # #
Can increase gas turbine performance better than evaporative cooling, and fog system Not very sensitive to ambient air wet bulb temperature Low electrical parasitic load Requires less steam per unit of refrigeration than single stage chiller
High initial capital cost High O&M cost Longer delivery and installation time High expertise is needed to operate and maintain the plant In case of a steam operated chiller, cannot be applied in an open cycle gas turbine plant
# #
Condensate Formation on the Chilled Water Coil t/h Based on 36C DB, 25C WB, 10C Chilled Inlet Air Temperature
Condensate Formation t/h
20 15 10 5 0
25
35
45
55
65
75
85
95
105 115 125 135 145 155 165 175 185 195 205 215 225 235 245 255 265
15.3%
6% 7.69%
O&M Costs
# # # # # # # # # # # # # #
Make up water Water treatment (if applicable) Make up water Demineralised water treatment Injection pump power consumption Steam Cooling tower chemical treatment Chiller maintenance Electric power consumption Steam Cooling tower chemical treatment and make up water Chiller maintenance Electric power consumption Electric power consumption Cooling tower chemical treatment and make up water Chiller maintenance
# #
0.470
590 CO2 Emission kg/MWh 580 570 560 550 540 530 520 0 5 10 15 20 25 30 35 40 45 Ambient Temperature deg C
0.43
10
15
20
25
30
35
40
45
550
Check the generator capacity in order not to overload the generator Quality of raw water for the evaporative cooler When using an existing demineralised water treatment plant, be careful about the capacity and quality of available demineralised water With an existing heat recovery steam generator, inlet air cooling will change the behaviour of the existing HRSG, leading to a drop in steam production at high pressure and increase in intermediate and low pressure steam
! !