EXHAUST FAN SCHEDULE

DESIGNATION LOCATION AIRFLOW (CFM) DRIVE TYPE EXT. STATIC (in. wg.) MOTOR (RPM) INPUT (WATTS / HP) VOLTAGE/PHASE ACCESSORIES CONTROL TYPE MANUFACTURER MODEL NO. NOTES: CONTROL TYPE: 1. INTERLOCK WITH WALL SWITCH 2. SEE CONTROL SEQUENCE ACCESSORIES: A. FACTORY ROOF CURB B. BACKDRAFT DAMPER C. DISCONNECT SWITCH D. SOLID STATE SPEED CONTROLLER E. ALUMINUM BIRD SCREEN F. DECORATIVE GRILLE EF-1 SHOWROOM ROOF 1200 BELT 1.0 1725 1/3 120/1 A,B,C,E 2 LOREN COOK 120C4B EF-2 TLT ROOM 202 50 DIRECT 0.25 1200 27.2 WATTS 120 / 1 B,D,F 1 LOREN COOK GC-120 EF-3 DETAIL BATH RMS 50 DIRECT 0.25 1200 27.2 WATTS 120/1 B,D,F 1 LOREN COOK GC-120 EXT. STATIC PRESSURE (in. wg) EVAPORATOR FAN HORSEPOWER EVAPORATOR FAN VOLTAGE/PHASE COMPRESSOR QTY. COMPRESSOR VOLTAGE/PHASE CONDENSER FAN HORSEPOWER CONDENSER FAN QTY. CONDENSER VOLTAGE/PHASE MCA (AMPS) MOCP (AMPS) ENTERING AIR TEMPERATURE (DB/WB) AMBIENT TEMPERATURE (DB) GROSS TOTAL COOLING (MBTU/H) GROSS SENSIBLE COOLING (MBTU/H) DESIGNATION AREA SERVED MANUFACTURER MODEL NO. NOMINAL TONS SUPPLY AIR FLOW (CFM) O/A AIRFLOW (CFM)

PACKAGED ROOF TOP UNIT SCHEDULE


RTU-1 SHOWROOM AAON RN-040-3-0-EB09-172 40 14,325 2475 2.5 20 460/3 4 460/3 3/4 4 460/1 130 150 78.5/64 95 450.9 332.39 80 R-410a 10.3 6160 1,2,3,4,5,6,7,8,9,10,12 RTU-2 SHOWROOM AAON RN-018-3-0-EA09-143 18 8000 760 0.75 7 1/2 460/3 2 460/3 3/4 2 460/1 74 80 76.6/62.7 95 202.15 181.38 40 R-410a 11.9 2790 1,2,3,4,5,6,7,8,9,10,12 RTU-3 SHOWROOM AAON RN-016-3-0-EB09-122 16 8000 200 0.75 7 1/2 460/3 2 460/3 3/4 2 460/1 44 50 75.4/61.5 95 193.65 182.59 20 R-410a 12.3 2828 RTU-4 SERVICE BAY AAON RN-040-3-0-EB09-19A 40 9200 9200 0.5 7 1/2 460/3 4 460/3 3/4 4 460/1 166 200 91/78 95 482.56 228.09 120 R-410a 10.3 6895 RTU-5,6,7 SERVICE BAY AAON RN-040-3-0-EB09-17A 40 8400 8400 0.5 7 1/2 460/3 4 460/3 3/4 4 460/1 166 200 91/78 95 482.56 228.09 120

GENERAL NOTES
1. IN THE PREPARATION OF THESE PLANS, THE ENGINEER HAS USED CERTAIN ABBREVIATIONS, CONVENTIONS, AND SYMBOLS, THE MEANING OF WHICH ARE ILLUSTRATED AND EXPLAINED WITHIN THE LEGEND. PLANS ARE DIAGRAMMATIC ONLY. THEY ARE INTENDED TO INDICATE CAPACITY, SIZE, LOCATION, DIRECTION, AND GENERAL ARRANGEMENT, BUT NOT EXACT DETAILS OF CONSTRUCTION. THE FACT THAT ONLY CERTAIN FEATURES OF THE INSTALLATION ARE INDICATED MUST NOT BE TAKEN TO MEAN THAT OTHER FEATURES WILL NOT BE REQUIRED. COORDINATE WITH THE OTHER TRADES TO INSURE THAT EACH TRADE SHALL HAVE SUFFICIENT SPACE TO INSTALL THEIR EQUIPMENT (DUCTWORK, PIPING, ELECTRICAL WORK, ET.) IN GENERAL, ALL PIPING AND DUCTWORK SHALL BE RUN IN THE CEILING SPACE UNLESS NOTED OR INDICATED OTHERWISE. VERIFY ALL DIMENSIONS FROM ARCHITECTURAL PLANS AND FIELD DIMENSIONS. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. ALL RISES AND DROPS IN PIPING AND DUCTWORK MAY NOT NECESSARILY HAVE BEEN SHOWN. CONTRACTOR TO VERIFY. PROVIDE ALL STRUCTURAL MEMBERS, SUPPORT BRACKETS, FLASHING, HARDWARE, ET. REQUIRED TO INSTALL A COMPLETE SYSTEM. DIFFUSERS AND REGISTER LOCATIONS SHALL BE COORDINATED WITH LIGHT FIXTURE AND OTHER CEILING DEVICE LOCATIONS. FIELD VERIFY. MOUNT ALL THERMOSTATS AND/OR SENSORS 4 FEET ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.

ABBREVIATIONS
A AFF AHU BHP BTUH CFM CLG CD CU DB DN DX EA AMPERES

MECHANICAL SYMBOLS LEGEND


CEILING SUPPLY DIFFUSER CEILING RETURN GRILLE

ABOVE FINISHED FLOOR AIR HANDLING UNIT BRAKE HORSEPOWER BRITISH THERMAL UNIT PER HOUR
IN-LINE EXHAUST FAN CEILING EXHAUST GRILLE

2.

CEILING EXHAUST FAN

CUBIC FEET PER MINUTE


WALL

3.

CEILING CONDENSATE DRAIN CONDENSING UNIT

DUCT FD WALL DUCT

DYNAMIC FIRE DAMPER STYLE 'B' FIRE DAMPER STYLE 'CR' FIRE DAMPER FOR ROUND DUCTS

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

4.

DYNAMIC SMOKE DAMPER SD WALL

DRY BULB DOWN


DUCT

5.

COMBINATION DYNAMIC FIRE/SMOKE DAMPER FSD SD DUCT SMOKE DETECTOR RETURN/EXHAUST DUCT TURNING DOWN 1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

6.

DIRECT EXPANSION EXHAUST AIR ENTERING AIR TEMPERATURE EXHAUST FAN

7.

EAT EF EL EXH EQUIP ESP FB FD FLEX FLR OR FL FPI FPM GALV HP KW LBS

8.

RETURN/EXHAUST DUCT TURNING UP

ELEVATION EXHAUST EQUIPMENT EXTERNAL STATIC PRESSURE FILTER BOX FIRE DAMPER FLEXIBLE FLOOR FINS PER INCH FEET PER MINUTE GALVANIZED HORSEPOWER
SIDE WALL RETURN GRILLE SIDE WALL SUPPLY GRILLE RD RADIANT DAMPER (RD) CONNECT TO EXISTING UC SUPPLY DUCT TURNING DOWN SUPPLY DUCT TURNING UP EXISTING DUCT TRANSFER OPENING IN WALL ABOVE CEILING 3/4'' UNDERCUT BELOW DOOR 9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

RADIANT UNIT HEATER SCHEDULE


DESIGNATION AREA SERVED MANUFACTURER MODEL N0. OUTPUT (KW)
ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

AUXILIARY ELECTRIC HEAT (KW) REFRIGERANT

9.
R-410a 10.3 6895

RH-1 SERVICE LANES&DETAIL AREA MARKEL OCH-57-480V-SS 2250 4.7 480/3 11

UNIT E.E.R. (AT A.R.I.) UNIT WEIGHT(LBS.) REMARKS

10.

1,2,3,4,5,6,7,8,9,10,12 1,2,3,4,5,6,7,8,9,10,11,12 1,2,3,4,5,6,7,8,9,10,11,12

AMPS VOLTAGE / PHASE WEIGHT (LBS) NOTES:

REMARKS: 1. PROVIDE WITH 18" HIGH INSULATED ROOF CURB. 2. PROVIDE WITH SINGLE POINT ELECTRICAL CONNECTION KIT. 3. PROVIDE WITH ENTHALPY ECONOMIZER. 4. PROVIDE FACTORY MOUNTED NON-FUSED DISCONNECT. 5. PROVIDE FACTORY MOUNTED AND POWERED 120V WEATHERPROOF GFI SERVICE RECEPTACLE. 6. PROVIDE WITH CONDENSER COIL SALT SPRAY PROTECTION. 7. PROVIDE POWER EXHAUST FAN. 8. PROVIDE 2" SPRING ISOLATORS. 9. PROVIDE MERV 13 FILTERS. 10. PROVIDE WITH MODULATING HOT GAS REHEAT. 11. PROVIDE WITH ENERGY RECOVERY WHEEL. 12. PROVIDE OUTSIDE AIR MONITORING STATION.

1. PROVIDE REMOTE MOUNTED TEMPERATURE CONTROL THERMOSTAT, SUMMER FAN SWITCH AND POWER DISCONNECT SWITCH. CONNECT ALL HEATERS TO BUILDING AUTOMATION SYSTEM.

EXHAUST HOOD SCHEDULE


DESIGNATION LOCATION AIRFLOW (CFM) EXT. STATIC (in. wg.) ACCESSORIES MANUFACTURER MODEL NO. NOTES: ACCESSORIES: A. FACTORY ROOF CURB B. BACKDRAFT DAMPER C. ALUMINUM BIRD SCREEN EH-1 DEALER OFFICE REST RM 50 0.15 A,B,C LOREN COOK PR-12

KILOWATT POUNDS MAXIMUM THOUSAND BTU/H MINIMUM OUTSIDE AIR RETURN AIR AND/OR ROOM AIR ROOFTOP UNIT SUPPLY AIR TEMPERATURE TYPICAL UNDERCUT MANUAL VOLUME DAMPER VOLTS WET BULB ROUND
CHWR CHILLED WATER RETURN PIPING CHWS MANUAL VOLUME DAMPER CHILLED WATER SUPPLY PIPING M PIPE TURNING DOWN PIPE TURNING UP R REFRIGERANT PIPING (LINE SET) T THERMOSTAT / TEMPERATURE SENSOR A-12x12 200 CFM AIR DEVICE TYPE AND SIZE AIR FLOW CFM

HEAT PUMP SPLIT SYSTEM SCHEDULE


SYSTEM NUMBER AREA SERVED MANUFACTURER MIN. SYSTEM S.E.E.R @ A.R.I. MIN. SYSTEM H.S.P.F @ A.R.I. AC-1/HP-1 ELEVATOR EQUIP RM MITSUBISHI 17.5 0.63 AC-2/HP-2 IT MITSUBISHI 17.5 0.63 AC-3/HP-3 DETAIL BLDG WAITING RM CARRIER 13.2 --

AIR DISTRIBUTION DEVICE SCHEDULE


A - PRICE MODEL SPD PLAQUE CEILING DIFFUSER B - PRICE MODEL 80 RETURN/EXHAUST EGGCRATE GRILLE C - PRICE MODEL 12"INLET ROUND PLAQUE DIFFUSER-12"/RPD/B12 D - PRICE MODEL 620D SIDEWALL SUPPLY DIFFUSER (W/O.B.D.)

MAX MBH MIN OA RA RTU SA TEMP TYP UC VD V WB

STEVENSON TOYOTA
PRIOR ISSUES: DATE:
1 2

CONDENSATE DRAIN PIPING

INDOOR UNIT No. SUPPLY AIRFLOW (cfm) OUTSIDE AIRFLOW (cfm) EXT. STATIC (in. w.g.)

AC-1 500 0 .01

AC-2 500 0 .01

AC-3 850 120 0.25 1/3

E - PRICE 5'-0" JSP (2.5")1-SLOT 12"INLET SUPPLY DIFFUSER (W/ MANUFACTURER'S ENGINEERED PLENUM) F - PRICE 5'-0" ASP (3.0")1-SLOT 12"INLET SUPPLY DIFFUSER (W/ MANUFACTURER'S ENGINEERED PLENUM) G - PRICE MODEL SPD/3P PLAQUE CEILING DIFFUSER WITH NOMINAL PANEL SIZE 48x24 H - PRICE MODEL LBP 12'-0x6"" WITH CORE 15A RETURN GRILLE NOTE: EACH AIR DEVICE SHALL HAVE A VOLUME DAMPER IN THE DUCT CONNECTED TO THE DEVICE UNLESS NOTED OTHERWISE. IF AIR DEVICE IS LOCATED IN AN INACCESSIBLE CEILING, VOLUME DAMPER SHALL BE INTEGRAL WITH THE AIR DEVICE.

LOUVER SCHEDULE
DESIGNATION LOCATION AIRFLOW (CFM) FUNCTION DIMENSIONS WxH (in.) MAX PRESSURE DROP (in. wg.) FREE AREA (sq. in.) ACCESSORIES MANUFACTURER MODEL NO. NOTES: BLADES ARE TO BE DRAINABLE ACCESSORIES: A. FACTORY PRIMED AND PAINTED B. ALUMINUM BIRD SCREEN L-1 DETAIL AREA WAITING RM 120 INTAKE 12x12 0.05 0.24 A,B RUSKIN ELF6375DXD

EVAP. FAN HP AUX ELEC. HEAT @ 208V (kW) UNIT VOLTS/PHASE/HZ. ENT. AIR TEMP. DB/WB (DEG F) NET TOTAL COOLING (BTU/H) NET TOTAL SENSIBLE COOLING (BTU/H) REV. CYCLE HEATING (BTU/H) @ 47 F MCA/MOCP MODEL No. -208 / 1 / 60 75/62 22,000 13,860 23,200 1.0/(FLA 0.76) MSZ-GA24NA -208 / 1 / 60 75/62 22,000 13,860 23,200 1.0/(FLA 0.76) MSZ-GA24NA

3.8 208 / 1 / 60 76.5/63.5 23,190 18,150 22,470 26/30 FB4CNF030T00

2 POSITION MOTORIZED DAMPER

4-WAY THROW

3-WAY THROW

2-WAY OPPOSITE THROW

2-WAY CORNER THROW

1-WAY THROW

OBD SQFT TAD

OPPOSED BLADE DAMPER SQUARE FEET TRANSFER AIR DUCT


CWR CONDENSING WATER RETURN PIPING CWS CONDENSING WATER SUPPLY PIPING

OUTDOOR UNIT No. REFRIGERANT TYPE AMBIENT TEMP. (DEG. F) UNIT VOLT/PHASE/Hz.

HP-1 R-410A 95 208 / 1 / 60 17/20 MUZ-GA24NA 1,2,3,4,6,7,8,9,10

HP-2 R-410A 95 208 / 1 / 60 17/20 MUZ-GA24NA 1,2,3,4,6,7,8,9,10

HP-3 R-410A 95 208 / 1 / 60 17/25 25HBC324A003 1,2,3,4,5,6,7,8,9,10

GENERAL SYMBOLS
GATE VALVE

CEILING FAN SCHEDULE


DESIGNATION LOCATION DRIVE TYPE FAN SPEED (RPM) INPUT (WATTS/HP) VOLTAGE/PHASE MOCP(AMPS) WEIGHT(LBS) CONTROL TYPE MODEL NO. MANUFACTURER NOTES: CONTROL TYPE: 1. FACTORY PROVIDED WALL MOUNTED LCD, CONNECTED TO BUILDING AUTOMATION SYSTEM CF-1 SERVICE LANES GEARLESS DIRECT 82 630W 120/1 10 230 1 EL12 BIG ASS FANS

MCA/MOCP MODEL No. Remarks Notes:

PLAN OR DETAIL NO. SHEET NUMBER 1 KEYED NOTE TO PLAN

BALL VALVE

CHECK VALVE

1. PROVIDE AHU WITH SINGLE POINT POWER CONNECTION. COORDINATE WITH ELECTRICAL CONTRACTOR. 2. PROVIDE SERVICE DISCONNECT SWITCH FOR AIR HANDLER AND HEAT PUMP: ELETRCIAL CONTRACTOR TO INSTALL. 3. ELECTRONIC PROGRAMMABLE THERMOSTAT 4. TIME DELAY RELAY & TX VALVE 5. AIR HANDLER TO BE INSTALLED WITH HORIZONTAL CONFIGURATION 6. FILTER DRIER 7. COMPRESSOR START ASSIST 8. HIGH & LOW PRESSURE SWITCHES 9. CRANKCASE HEATER 10. SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS FOR MINIMUM CAPACITY LOSS

1 T

REVISION NUMBER

STRAINER

THERMOSTAT / TEMPERATURE SENSOR

STRAINER WITH BLOW DOWN VALVE

SP

STATIC PRESSURE SENSOR


UNION

SD

DUCT SMOKE DETECTOR


NEEDLE VALVE WITH PRESSURE GAUGE

CO

CARBON MONOXIDE SENSOR


THERMOMETER

VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE


UNIT DESIGNATION MANUFACTURER MODEL NUMBER MAX. TERMINAL UNIT AIRFLOW (CFM) MIN. TERMINAL UNIT AIRFLOW (CFM) COIL LEAVING AIR DRY-BULB TEMPERATURE (DEGF) COIL ENTERING AIR DRY-BULB TEMPERATURE (DEGF) COIL HEATING CAPACITY AT MINIMUM AIRFLOW (MBH) COIL HEATING CAPACITY AT MINIMUM AIRFLOW (kW) TERMINAL UNIT INLET DIAMETER (IN.) TERMINAL CONTROL TYPE VOLTAGE/PHASE NOTES:
1. PROVIDE FIELD FURNISHED, FATORY MOUNTED DDC CONTROLLER. 2. PROVIDE FACTORY MOUNTED AND WIRE 120/24V TRANSFORMER. 3. DUCT RUNOUT DIAMETER TO BE EQUIVALENT TO AIR VALVE INLET DIAMETER UNLESS OTHERWISE NOTED ON DRAWINGS. 4. ELECTRIC HEATER WITH MERCURY CONTACTOR ON UNITS INDICATED TO HAVE ELECTRIC HEATING COILS 5. MAX. TERMINAL UNIT PRESSURE DROP NOT TO EXCEED 0.8" W.C. WITH HEATING COIL. 6. MAX. COIL FACE VELOCITY NOT TO EXCEED 800 FPM AT MAX AIRFLOW CONDITIONS.

NO2
VAV-14 PRICE SDV5 500 150 85 55 4.9 1.5 8 DDC 277/1 VAV-15 PRICE SDV5 1000 300 85 55 9.8 3.0 10 DDC 277/1 VAV-16 PRICE SDV5 650 221 85 55 6.3 2.0 10 DDC 277/1 VAV-17 PRICE SDV5 500 150 85 55 4.9 1.5 8 DDC 277/1 VAV-18 PRICE SDV5 900 270 85 55 8.8 2.5 10 DDC 277/1 VAV-19 PRICE SDV5 1050 375 85 55 12.2 3.5 12 DDC 277/1 VAV-20 PRICE SDV5 600 180 85 55 5.9

NITROGEN DIOXIDE SENSOR


BUTTERFLY VALVE

VAV-1

VAV-2

VAV-3

VAV-4

VAV-5

VAV-6

VAV-7

VAV-8

VAV-9

VAV-10 PRICE SDV5 500 150 85 55 4.9 1.5 8 DDC 277/1

VAV-11 PRICE SDV5 500 150 85 55 4.9 1.5 8 DDC 277/1

VAV-12 PRICE SDV5 675 221 85 55 6.7 2.0 10 DDC 277/1

VAV-13 PRICE SDV5 300 90 85 55 9.8 2.0 6 DDC 277/1

PRICE PRICE PRICE PRICE PRICE PRICE PRICE PRICE PRICE SDV5 1400 420 85 55 13.7 4.0 12 DDC 277/1 SDV5 700 221 85 55 6.8 2.0 10 DDC 277/1 SDV5 1000 300 85 55 9.8 3.0 10 DDC 277/1 SDV5 1050 375 85 55 12.2 3.5 10 DDC 277/1 SDV5 200 66 85 55 1.9 1.0 6 DDC 277/1 SDV5 500 150 85 55 4.9 1.5 8 DDC 277/1 SDV5 850 255 85 55 8.3 2.5 10 DDC 277/1 SDV5 650 221 85 55 6.3 2.0 10 DDC 277/1 SDV5 800 243 85 55 8.1 2.5 10 DDC 277/1

BALANCING VALVE

NORTH ARROW
FLEX CONNECTION

2325 North Marine Boulevard Jacksonville, NC


5 6 7

M MOTORIZED CONTROL VALVE

TRIPLE DUTY VALVE

2.0 8 DDC 277/1


PUMP EOR: KEITH M. NIX #: 031858 VERTICAL INLINE PUMP (PLAN VIEW)

JANUARY 31, 2011

AUTOMATIC AIR VENT

DRAWN BY:

MECHANICAL SCHEDULES, LEGENDS AND NOTES


GJH KMN

CHECKED BY:

PROJECT NO.:

10048

M0.1
PERMIT SET
c 2009

SF AB AB.5 AA AA.5 AA.9 A B

SG B.1

B.9

C SHC.3

SJ

E.5

SK

F.7

SL

G.8

J.9

K.1

CORRIDOR 117

B 100 CFM B 100 CFM


8 TECH LIBRARY 126

A 100 CFM

6" HR 116 5 CORRIDOR 118 5

8"

A 175 CFM
WOMEN'S RESTROOM 119

12"x8"

A 100 CFM
10"x8"

12"x10"

6"

B 100 CFM

B 100 CFM B 100 CFM

PARTS MANAGER 125 T VAV-5 6"

A 100 CFM

B 100 CFM

STAIR 127

TECH. LOUNGE 128

A 50 CFM B 250 CFM

WOMEN'S LOCKER ROOM 129

A 50 CFM

FIRE RISER ROOM 132

15

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

14
KEYED NOTES:
1 RADIANT HEATER RH-1 CHAIN HUNG WITH BOTTOM AT 14'-0". SEE MO.1 FOR SPECIFICATIONS. SUPPLY DUCT DOWN FROM VAV-19 ABOVE. SEE M2.2 FOR CONTINUATION. 12' CEILING FAN. SEE M0.1 FOR SPECIFICATIONS. SEE M2.2 FOR WORK IN THIS AREA. 12x12 RETURN DUCT SOUND BOOT INTERNALLY LINED. SEE DETAIL ON M3.1 SUPPLY AIR FLEX DUCT DOWN FROM CEILING SPACE ABOVE DISPLAY (RM 158). SEE M2.2 FOR CONTINUATION. 30x12 SUPPLY DUCT DOWN FROM RTU-1. PROVIDE VANED ELBOW AT BASE OF RISER AND FIRE DAMPER AT FLOOR PENETRATION. SEE M2.2 FOR CONTINUATION. 12x10 SUPPLY DUCT DOWN FROM RTU-1. PROVIDE VANED ELBOW AT BASE OF RISER AND FIRE DAMPER AT FLOOR PENETRATION. SEE M2.2 FOR CONTINUATION. 16x10 EXHAUST DUCT UP TO EF-1. PROVIDE FIRE DAMPER AT FLOOR PENETRATION. SEE M2.2 FOR CONTINUATION. REFRIGERANT PIPING UP TO HP-1 AND HP-2. CONDENSATE LINE DOWN FROM AC-2 TO JANITOR CLOSET (RM 138). CONDENSATE DRAIN LINES FROM AC-1 AND AC-2 TO SPILL INDIRECTLY TO MOP SINK. 36"x36" TRANSFER OPENING AT BOTTOM OF CHASE FOR RETURN AIR. PROVIDE FIRE DAMPER AT FLOOR PENETRATION. PROVIDE SQUARE TO ROUND TAKE OFF. RETURN AIR OPENING IN WALL ABOVE CEILING.

A 250 CFM
6"

6"x6"

10"x10"

HR 115

B 100 CFM

A 100 CFM

8"

G 175 CFM

MEN'S RESTROOM 120 6"x6"

10"

6"

8"

VAV-5

6"x6"

6"

6"x6"

A 100 CFM

6" 6"x8" 8"


UP

6"

B 100 CFM

B 100 CFM
12" VAV-17

B 100 CFM B 75 CFM

MEN'S LOCKER ROOM 130

A 175 CFM A 75 CFM B 75 CFM


6"x8" 6"x8"

PARTS OFFICE 14 WHOLESALE 133 6"x6"

13.9

A 75 CFM
6" 14 8"x6"
UP

3 4 5

VAV-12 8"x8" 12"x8" 10"

13 10"x10" 14

B 100 CFM

B 75 CFM
T VAV-12

13.1 13

10"x8" 10"x6" 6"x6"

12"x10" 12"x6"

14 6"x6"

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

A 100 CFM

B 100 CFM
SERVICE ADMIN 114 6" T VAV-19 5

6"

B 50 CFM
12"x10"

8"x8"

JANITOR CLOSET 121

10"x8"

A 500 CFM
14 12"x8"

B 500 CFM T VAV-17


ELECTRICAL ROOM 122

B 200 CFM
8"

CUSTOMER SERVICE 113


ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

8"

16"x12"

A 150 CFM

B 100 CFM

A 200 CFM
CASHIER/WARRANTY 123

PARTS 134

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

12.1 12 11.6 11

11.6 11.5
TRAC 112

9 JANITOR CLOSET 138 9 10

A 100 CFM
6" 2

D 250 CFM
RETAIL 124

D 250 CFM
6"x6" 3/4" CONDENSATE 12"x10"
8" 10"

D 200 CFM

10 VAV-2 10" 14"x10" 30"x16" 14 T VAV-2 7


UP

B AC-1 B 150 CFM 50 CFM


BUSINESS CENTER 135

11

11 12

10"x10"

8" 14"x10" VAV-6

18"x10" 13

3/4" CONDENSATE ELEV. EQUIP. 136

12"x10"

RH-1

VAV-9 T

6"

8"
10"

GENERAL MANAGER 143

B 150 CFM
6" 6"

A 75 CFM

16"x10"

CF-1

SERVICE MANAGER 110 4


UP

MANAGER 141

VAV-6 T

T VAV-8

A B 75 CFM 350 CFM

A 75 CFM

A 75 CFM INTERNET
149
6"

9
5

6.9

RH-1

RH-1

RH-1

RH-1

STAIR 142

VAV-11 T

8"x8" 6" 10" CHILD PLAY AREA 152

B 225 CFM

6"

B 100 CFM A 250 CFM

B 150 CFM

B 100 CFM

6"

A 100 CFM
F&I 153 F&I 154

10"x10"

RH-1 1 1 1 SERVICE LANES 111 RH-1 RH-1 CF-1 3 RH-1 RH-1 1 1

ASM 109 4

6"

B 100 CFM

10"x8"

10"

7 6.3 6

B 300 CFM A 250 CFM

6"

VAV-3 T

8"x8"

A 100 CFM

A 100 CFM
T VAV-1

CAFE 106

NEW VEHICLE DELIVERY 157

5.3 5

5 6"
6"

A 100 CFM

4.6

ASM 108 4 1 1 1 1

B 100 CFM

F&I 155

4.7

B 100 CFM

F&I 156

4.2 4.15
A 100 CFM

4.1

RH-1

RH-1

1 RH-1

RH-1

RH-1

B 300 CFM
5 ASM 107

3.8
1 1

CF-1 3 1 1

LOUNGE 105

T RTU-3

4
A 300 CFM B 300 CFM

T RTU-2

4 6

DISPLAY 158

3.4

RH-1

RH-1

RH-1

RH-1

VAV-4 T

1 RH-1

SALES MANAGER 159

4 SCION DISPLAY 104

3 2.9

PRIOR ISSUES:

VESTIBULE 102

3.2

2325 North Marine Boulevard Jacksonville, NC


5 6 7

ELEVATOR 137 BROCHURES 139 8"

A 100 CFM

6"

A 150 CFM

8" SALES 145 SALES 146 SALES 147

VAV-3

9.2 9.1

B 300 CFM

A 75 CFM

STEVENSON TOYOTA
1 2 3 4

A 150 CFM

8"

10"x10"

8"

A 50 CFM

6"

10"x8"

VAV-11

VAV-8

10"

B 50 CFM

B 50 CFM

A 50 CFM
6" STORAGE 140

28"x10"

A 200 CFM

A 250 CFM

BULLPEN 144

A 200 CFM

13

12

A 50 CFM
SALES 148

30"x12"

STAIR 151

B 50 CFM
SPARE KEYS 150

13 14

10

EOR: KEITH M. NIX #: 031858

DATE:

JANUARY 31, 2011

1st FLOOR HVAC PLAN SHOWROOM


DRAWN BY: CHECKED BY: PQ KMN

PROJECT NO.:

10048

1 M2.0

1st FLOOR HVAC PLAN - SHOWROOM


SCALE: 1/8" = 1'-0"

M2.0
PERMIT SET
c 2009

PLAN

TRUE

B.9 C SA SB SC SD SE SF SG

C.3 SH

E SJ

E.5

F SK

F.7

G SL

G.8

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802 3 1 1 1 T RTU-4 T RTU-5 CO NO2 7
AIR

25 24
A 750 CFM
RH-1 CO NO2 7

RH-1 RH-1
OIL OIL OIL AIR AIR

B 1550 CFM

OIL B OIL AIR 1550 CFM AIR

OIL OIL AIR AIR

B 1550 CFM

OIL B OIL AIR 1550 CFM AIR

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

1 RH-1

A 800 CFM

A 1400 CFM
18" 16"

A 1400 CFM

16"

16"

A 1400 CFM

14" RH-1 RH-1


161A

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

20"x18"

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

22"x18"

163

161

23

SD 5
160H

SD 5 16" 16"
44"x20"

16"
44"x20"

16" RTU-5 6

RTU-4 6

A 1400 CFM A 1400 CFM

A 1400 CFM

A 1400 CFM

160D

STEVENSON TOYOTA
PRIOR ISSUES: DATE:
1 2

21

20"x18"

20"x18"

KEYED NOTES:
1 RADIANT HEATER RH-1 CHAIN HUNG WITH BOTTOM AT 14'-0". SEE M0.1 FOR SPECIFICATIONS. IN-FLOOR AUTOMOBILE EXHAUST EVAC SYSTEM BY SERVICE EQUIPMENT VENDOR. TYP OF 32. (2)AUTOMOBILE EXHAUST EVAC BLOWERS BY SERVICE EQUIPMENT VENDOR. APPROX 5400 CFM TOTAL EXHAUSTED. NOT USED. 60"x18" LINED RETURN DUCT UP TO RTU ABOVE. LINED SUPPLY DUCT DOWN FROM RTU-1. RISER TO MATCH UNIT'S DISCHARGE DIMENSIONS INTO 64"x20" SUPPLY PLENUM. SEAL AIR TIGHT ALL SEAMS AT ROOF PENETRATION AND PLENUM INLET. REMOTE SENSORS TO BE COLUMN OR WALL MOUNTED AS FOLLOWS: CO SENSOR TO BE MOUNTED BETWEEN 4'-0" AND 6'-0" AFF NO2 SENSOR TO BE MOUNTED BETWEEN 1"-0" AND 1'-6" BELOW CEILING. CO/NO2 DETECTION SYSTEM ALARM PANEL.

20

2 16" 16"

A 1400 CFM A 1400 CFM

16"

16"

A 1400 CFM
AIR AIR OIL OIL AIR AIR OIL OIL AIR AIR OIL OIL

A 1400 CFM
AIR AIR OIL OIL

4 5 6

B 1550 CFM

B 1550 CFM
7 CO NO2 7 CO NO2

B 1550 CFM

B 1550 CFM

19

OIL OIL AIR AIR

OIL OIL AIR AIR

OIL OIL AIR AIR

OIL OIL AIR AIR

B 1550 CFM

B 1550 CFM

B 1550 CFM

B 1550 CFM A 1400 CFM


16" 16"

16"

16"

A 1400 CFM A 1400 CFM

A 1400 CFM
20"x18"

18
20"x18"
160C

160B

17
SD 5 16"
44"x20"

SD 5 16" RTU-6 6 16"


44"x20"

16" RTU-7 6

160G

A 1400 CFM

A 1400 CFM

A 1400 CFM

A 1400 CFM

16

20"x18"

20"x18"

2325 North Marine Boulevard Jacksonville, NC


5 6 7

16"

16"

16"

16"

CO NO2

A 1400 CFM
AIR AIR OIL OIL

A 1400 CFM
AIR AIR OIL OIL

A 1400 CFM
AIR AIR OIL OIL AIR AIR OIL OIL

A 1400 CFM

AA

AA.5

AA.9 A

AIR OIL OIL

B .1

J.9

K K.1
EOR: KEITH M. NIX #: 031858

7 CO NO2

B 1550 CFM

B 1550 CFM

B 1550 CFM

B 1550 CFM

JANUARY 31, 2011

15
160A

T RTU-6

T RTU-7

131

14

1st FLOOR HVAC PLAN SERVICE


DRAWN BY: CHECKED BY: PQ KMN

PROJECT NO.:
1 M2.1

10048

1st FLOOR HVAC PLAN-SERVICE


SCALE: 1/8" = 1'-0"

PLAN

TRUE

M2.1
PERMIT SET
c 2009

SF AB AB.5 AA AA.5 AA.9 A

SG B .1

B.9 SHC.3 C

SJ

E.5

SK

F.7

SL

G.8 H I J J.9 K K.1

15

OFFICE 220

OFFICE 221

OFFICE 222

? ?
12"x10"

14

14 13.9

A 150 CFM
OFFICE 219

A 100 CFM

A 100 CFM B 100 CFM


8"x8" 14"x12"

A 100 CFM B 100 CFM


10"x10"

A 100 CFM B 100 CFM


10"x10" 12"x10" 22"x12"

A 100 CFM

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

VAV-20

18"x10"

6"

VAV-16 10" 28"x12"


10" 72"x24"
DN

8"

A 150 CFM
8"

34"x12" 15

A 150 CFM
PARTS 226 4
DN

8"

B 150 CFM T VAV-16

6"

B 100 CFM

6"

6"

6"

12"x10"

8"

6"

B 100 CFM

10"x10"

8"x10"

8"

10"

SP

B 250 CFM

GENERAL OFFICE 218

B 250 CFM

B 100 CFM A 250 CFM


BREAK ROOM 217

54"x12"

13.1 13

VAV-15

VAV-18

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

8"

14"x12"

10"
10" 14"x12"

14"x12"

10"

64"x20"

T VAV-20

10"x10"

8"

B 250 CFM B 250 CFM

A 250 CFM
T VAV-18

10"x8"

A 350 CFM B 250 CFM


ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

A 350 CFM

A 300 CFM

AC-2

64"x12"

I.T. 225

A 150 CFM
SD

A 150 CFM

11.5
11

VAV-19 14"x12" 12"


10"

3/4" CONDENSATE

15 32"x18" 15
44"x20"

19 16"x12" T VAV-15 SHOWER ROOM 216

B 75 CFM

6"

B 100 CFM
6"

32"x18"

10"x8" 8"x8"
6" 8" 24"x12"

A 250 CFM A 175 CFM

30"x12"

MEN'S RESTROOM 214

B 250 CFM

18 13 15

64"x12"

58"x12"

12.1 12 11.6 11

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

A 250 CFM
8"

10

VAV-9
12"x12"

10"x6"

8"

KEYED NOTES:
1 2 3 42"x20" LINED SUPPLY DUCT DOWN FROM RTU ABOVE WITH VANED ELBOW AT BASE OF RISER. 50"x20" LINED RETURN DUCT UP TO RTU ABOVE. LINED SUPPLY DUCT DOWN FROM RTU-1. RISER TO MATCH UNIT'S DISCHARGE DIMENSIONS INTO 64"x20" SUPPLY PLENUM. SEAL AIR TIGHT ALL SEAMS AT ROOF PENETRATION AND PLENUM INLET. 90"x24" LINED RETURN DUCT UP TO RTU-1. REFRIGERANT LINES FROM AC-2&3 TO HP-2&3 ON ROOF. ALL HORIZONTAL RUNS ROUTED IN CEILING SPACE AS SHOWN. SEE M2.3 FOR CONTINUATION. F/500 CFM. DIFFUSER TO BE COORDINATED WITH ARCHITECTURAL CEILING FEATURE SO MOUNTING APPEARS FLUSH WITH GRID. SEE DEVICE SCHEDULE FOR SPECIFICATIONS ON M0.1 VAV BOX AND DUCT RUN TO BE ROUTED BETWEEN JOIST. BOX TO BE SITUATED SUCH THAT CONTROLS AND SERVICE CLEARANCE ARE UNOBSTRUCTED. MOUNT LINEAR DIFFUSER FLUSH WITH CEILING TILE AS SHOWN. SEE DEVICE SCHEDULE FOR SPECIFICATIONS ON M0.1 6" DUCT UP TO ROOF VENTILATOR EH-1. 30x12 DOWN TO 1st FLOOR. PROVIDE FIRE DAMPER AT FLOOR PENETRATION AND VANED ELBOW AT BASE OF RISER. 14x12 DOWN TO SERVE 1st FLOOR VAV BOXES IN CEILING SPACE AS SHOWN. PROVIDE VANED ELBOW AT BASE OF RISER. RETURN AIR PATH THROUGH OPEN SLOTS IN ARCHITECTURAL CEILING SYSTEM. 16x10 EXHAUST DUCT UP TO EF-1 AND DOWN TO FIRST FLOOR CEILING SPACE. PROVIDE FIRE DAMPER AT FLOOR PENETRATION. SEE M2.3 AND M2.0 FOR CONTINUATION. 12x10 SUPPLY DUCT DOWN TO FIRST FLOOR CEILING SPACE. PROVIDE FIRE DAMPER AT FLOOR PENETRATION. SEE M2.0 FOR CONTINUATION. RETURN AIR OPENING IN WALL ABOVE CEILING. SUPPLY AIR FLEX DUCT IN CEILING SPACE ABOVE 'NEW CAR DELIVERY' (RM 157) TO DIFFUSER IN DISPLAY (RM 158). SEE M2.0 FOR CONTINUATION. PRICE MODEL LBP TO MATCH OTHER RETURN GRILLES IN GRID WITH CUSTOM LENGTH TO COLUMN. CONDENSATE LINE TO MECHANICAL CHASE AND DOWN TO JANITOR CLOSET (RM 138). SEE M2.0 FOR CONTINUATION. SUPPLY AIR DUCT DOWN TO CEILING SPACE ABOVE TRAC (RM 112). SEE M2.0 FOR CONTINUATION. 8" 8" 8"

6"x6"

6"

5
DN

12"x10"

6.9

B 100 CFM

10"x8"

A 100 CFM

VAV-13 T SERVING AREA 209

B 300 CFM

8" VAV-13 8" OFFICE 204

10"

WAITING AREA 211

T VAV-14

VAV-10 T

8"

6"

B 200 CFM

H 700 CFM

G 350 CFM

7
10"

6.3 6

A 200 CFM
12"x8"

8" CONFERENCE ROOM 208

8"

10"

10"

10"

10"

12"

6 12"

10"

10"

10"

C 500 CFM
12

C 500 CFM

17

22"x10"

18"x10"

10"

10"

A 150 CFM

B 200 CFM

17

G 350 CFM
10"

14"x10"

B 200 CFM

D 250 CFM

D 250 CFM

D 250 CFM

D 250 CFM

A 150 CFM

A 200 CFM A 50 CFM

5.3
G 350 CFM

6" 12

9 6"

EF-2 28"x8" STORAGE 203 VAV-1


10"

10

B 200 CFM
2

12"

4.6

SD 1

TLT. ROOM 202

12"

6 M3.1

4.7

A 200 CFM

14"

42"x20"

14"

12"
12"

20"x20"

12 13

4.1
16" 6

16" 12"

B 200 CFM

DEALER OFFICE 201

8"

12"

C 500 CFM

12"

11

C 500 CFM

10" 12" 14" 8"

A 200 CFM

C 500 CFM

H 700 CFM

4.2
G 350 CFM

4.15 4

14"
12"

14" 12"
12" 42"x20"

T VAV-7 12" 16"

14

24"x20"

3.8

12"

A 200 CFM

B 200 CFM

16"

16

15 16

14"

16"

C 500 CFM C 500 CFM C 500 CFM

12"

16"

C 500 CFM

VAV-4

14"x12"

10"

C 500 CFM

1
16" 10"

3.4
17

C 500 CFM
SD
12" 12" 12"

18

16"

12"

16"

B 350 CFM

19

E E 625 CFM 625 CFM

E 625 CFM

E 625 CFM B 350 CFM


16"
12" 12"

A 350 CFM

A 350 CFM

3.2 3
PRIOR ISSUES:

16"

2.9
12" 12" 12" 12"

8
12" 12"

12"

12"

16"

16"

16"

E E 625 CFM 625 CFM


8

E E 625 CFM 625 CFM

E E 650 CFM 650 CFM

E E 650 CFM 650 CFM

E E 625 CFM 650 CFM

2325 North Marine Boulevard Jacksonville, NC


5 6 7

B 100 CFM

B 500 CFM

A 250 CFM

A 250 CFM

22"x10"

VAV-7

6"

A 200 CFM

B 200 CFM

12

B 500 CFM

STEVENSON TOYOTA
2 3 4

CORRIDOR 213

6"x6"

TRAINING ROOM 210

8"

ELEVATOR 215

A 75 CFM
6"x6"

WOMEN'S RESTROOM 212 10"x10"

8"

A 50 CFM

STAIR 206
DN

6"x6"

A 100 CFM
10"x6"

10"x10" 8" VAV-10 10"

FD

STORAGE 207 22"x10"

10"x10" VAV-14

10
18"x12"

A 100 CFM
OFFICE A ADMIN. 200 CFM 205

10"

9.2 9

9.1

2
EOR: KEITH M. NIX #: 031858

DATE:

JANUARY 31, 2011

2nd FLOOR HVAC PLAN SHOWROOM


DRAWN BY: CHECKED BY: PQ KMN

PROJECT NO.:

10048

1 M2.2

2nd FLOOR HVAC PLAN - SHOWROOM


SCALE: 1/8" = 1'-0"

M2.2
PERMIT SET
c 2009

PLAN

TRUE

SF

SG

B.9 SHC.3 C

SJ

E.5

SK

F.7

SL

G.8

AB

AB.5

AA

AA.5

AA.9 A

B .1

J.9

K K.1

15

14 13.9

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

13.1 13
1 P-17 P-18 RTU-1 1 1/2" CONDENSATE

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com EF-1

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

11.5
1

KEYED NOTES:
TERMINATE CONDENSATE DRAIN LINE INTO ROOF DRAIN WITH 90DEGREE SCREENED ELBOW.

12.1 12 11.6 11

10

8.6

HP-2

HP-1

STEVENSON TOYOTA
2 3 4

9.2 9

9.1

6.9 6.7

7 6.3 6

P-18 P-17 1
1 1/4" CONDENSATE

P-18 1 P-17 EH-1

5.3 5

4.6

4.7
RTU-2
1 1/4" CONDENSATE

4.2 4.15 4

4.1

3.8

3.4

RTU-3

3.2 3 2.9

PRIOR ISSUES:

2325 North Marine Boulevard Jacksonville, NC


5 6 7

2
EOR: KEITH M. NIX #: 031858

DATE:

JANUARY 31, 2011

ROOF HVAC PLAN SHOWROOM


DRAWN BY: CHECKED BY: PQ KMN

PROJECT NO.:

10048

1 M2.3

ROOF HVAC PLAN - SHOWROOM


SCALE: 1/8" = 1'-0"

M2.3
PERMIT SET
c 2009

PLAN

TRUE

SA SB

SC

SD

SE

SF

SG

B.9 SHC.3 C

SJ

E.5

SK

F.7

SL

G.8

25 24
10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

23

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com RTU-4 1 RTU-5

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

1 1/4" CONDENSATE

1 1/4" CONDENSATE

KEYED NOTES:
1 TERMINATE CONDENSATE DRAIN LINE INTO GUTTER WITH 90DEGREE SCREENED ELBOW.

21

20

STEVENSON TOYOTA
PRIOR ISSUES: DATE:
1 2

19

18

17

RTU-6

RTU-7

1 1/4" CONDENSATE

1 1/4" CONDENSATE

16

2325 North Marine Boulevard Jacksonville, NC


5 6 7

AA

AA.5

AA.9 A

B .1

J.9

K K.1

15

14 13.9

EOR: KEITH M. NIX #: 031858

JANUARY 31, 2011

ROOF HVAC PLAN SERVICE


1 M2.4

ROOF HVAC PLAN - SERVICE


SCALE: 1/8" = 1'-0"

DRAWN BY: CHECKED BY:

PQ KMN

PLAN

TRUE

PROJECT NO.:

10048

M2.4
PERMIT SET
c 2009

MECHANICAL SUBCONTRACTOR SHALL PROVIDE ITEMS NOTED BELOW ROOFTOP UNIT GASKET AND SILICONE SEALING

GENERAL CONTRACTOR SHALL PROVIDE THE ITEMS NOTED BELOW

SEE DETAIL A-A

COUNTER FLASHING STRIP 1" RIGID INSULATION PRESSURE-TREATED WOOD NAILER STRIP CURB HEIGHT = 14" FACTORY CURB: NRCA APPROVED, 18 GAGE, SQUARE WITHIN 1/8" ON DIAGONAL MEASUREMENT, WITH A MINIMUM OF 8" ABOVE TOP OF ROOF PERFORATED CAST IRON MANHOLE LID AND FRAME GROUT GRADE 1/2'' THREADED RODS UP TO STRUCTURE ABOVE (TYPICAL OF 4) SPRING-TYPE VIBRATION ISOLATOR (TYPICAL OF 4) DUCT SMOKE DETECTOR (WHERE SUPPLY AIR FLOW EXCEEDS 2000 CFM) FLEXIBLE DUCT CONNECTOR (TYPICAL AT BOTH ENDS) DO NOT BLOCK ACCESS TO CIRCUIT BREAKER OR CONTROL PANEL GASKET & SEALANT 2-#10 TEK SCREWS @ 24" PT 2x WOOD NAILER ROOFING & FLASHING, SEE ARCH ROOF MEMBRANE RETURN DUCT 24" DIAMETER X 4'-0" LONG REINFORCED CONCRETE PIPE COIL SECTION FAN SECTION SUPPLY DUCT 1/2'' DIA. EXPANSION BOLT 24'' O.C. CONCRETE PAD BY OTHERS CONDENSATE DRAIN LINE WITH 6" DEEP P-TRAP FULL SIZE OF UNIT CONNECTION. 4'' STEEL CHANNEL (TYPICAL OF 2) FLOAT SWITCH WIRED TO SHUT DOWN UNIT UPON ACTIVATION BY WATER IN AUXILIARY PAN. 1'' THICK NEOPRENE PAD (TYPICAL OF 4) AUXILIARY DRAIN PAN UNDER FULL WIDTH AND LENGTH OF UNIT. DETAIL A-A NOTES: 1. 2. NOTE: DUCT SMOKE DETECTORS SHALL BE WIRED TO SHUT DOWN UNIT UPON DETECTION OF SMOKE AND SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM. MECHANICAL SUBCONTRACTOR SHALL FURNISH ROOF OPENING SIZES & LOCATIONS, FOR STRUCTURAL SUPPORT FRAMING BY GENERAL CONTRACTOR. THIS CURB DETAIL WILL ALLOW THE UNIT TO SLOPE WITH THE SLOPE OF THE ROOF PITCH. THIS DETAIL CAN ONLY BE USED: (A) IF THE CONDENSATE DRAIN PAN OUTLET IS ON THE LOW SIDE OF THE UNIT, OR (B) IF THE CONDENSATE DRAIN PAN IS NOT AFFECTED BY SLOPE. THIS DETAIL CAN NOT BE USED IF THE CONDENSATE DRAIN CONNECTION IS ON THE HIGH SIDE OF THE UNIT. COORDINATE THIS DETAIL WITH ARCHITECTURAL APPLICATIONS FOR THE ROOF. 9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com CURB SET DIRECTLY ON CONCRETE 3" CANT STRIP ROOF MEMBRANE

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

CONCRETE PAD BY OTHERS

MECH UNIT BASE 12 GA ANGLE W/ 1~8" LEGS 0'-6" LG @ 24" (2 MIN PER SIDE) W/ 2-#10 TEK SCREWS EACH LEG

FILTER ACCESS

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

CONDENSATE PIPING

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

24"

3.

FILL WITH GRAVEL

1 M3.0

DRYWELL DETAIL
SCALE: NTS

2 M3.0

HORIZONTAL AIR HANDLING UNIT DETAIL


SCALE: NTS

3 M3.0

ROOFTOP UNIT CURB DETAIL


SCALE: NTS

STEVENSON TOYOTA
PRIOR ISSUES: DATE:
1 2

CONDENSATE DRAIN SEE DETAIL SINGLE POINT ELECTRICAL POWER ENTRY IN BOTTOM OF UNIT.

MOTOR: INTERNALLY PROTECTED. SEE SCHEDULE FOR BELT OR DIRECT DRIVE REQUIREMENTS. PROVIDE VARIABLE SPEED CONTROL FOR DIRECT DRIVE FANS CONDUIT CHASE THRU CURB CAP TO MOTOR COMPARTMENT. WIRING BY DIVISION 16. FLASHING HANGER SUPPORTS: 1" X 22 GA, DO NOT SUPPORT FROM CEILING. INSULATION
12"

FACTORY MOUNTED DISCONNECT SWITCH. REMOVABLE MOTOR WEATHER COVER: ALUMINUM

FACTORY INSTALLED NON-FUSED DISCONNECT SWITCH FACTORY-INSTALLED AND POWERED 120/1 VOLT CONVENIENCE OUTLET.

SEE NOTE 1

GALVANIZED, INSULATED PREFAB CURB WITH BUILT-IN CANT.

INTAKE HOOD WITH WASHABLE FILTERS

PLAN VIEW

SEE NOTE 2 INTEGRAL BACKDRAFT DAMPER ROOF DECK P.T. BLOCKING AS REQUIRED. FAN GRAVITY BACK DRAFT DAMPER TRANSITION DUCT TO FULL SIZE OF DAMPER SUPPLIED WITH ROOF VENTILATOR; SEAL AIR TIGHT. DUCT WHERE APPLICABLE FACTORY CURB; SEE DETAIL NOTES: VARIABLE SPEED CONTROLLER MARK WITH THE "AS BALANCED POSITION" (DIRECT DRIVE UNITS). DISCONNECT SWITCH: FURNISHED BY MECHANICAL CONTRACTOR OR FAN MANUFACTURER. CEILING 1. 2. 3. 4. SECURE CURB CAP TO WOOD NAILING STRIP WITH 1/4" STAINLESS STEEL LAG BOLTS NOT OVER 12" ON CENTER. SECURE ROOF CURB, DUCT WORK AND DAMPER TO ROOF WITH EXPANSION BOLTS (CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF). SIZE OF DUCT THROUGH ROOF SHALL NOT BE LARGER THAN CURB SUPPLIED WITH ROOF VENTILATOR. RUN ELECTRIC LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE. DUCT SMOKE DETECTOR RETURN AIR SUPPLY AIR SIDE VIEW

NOTE: DUCT SMOKE DETECTOR SHALL BE WIRED TO SHUT DOWN UNIT UPON DETECTION OF SMOKE AND SHALL NOTIFY THE BUILDING FIRE ALARM SYSTEM.

ROOF

4 M3.0

CEILING MOUNTED FAN DETAIL


SCALE: NTS

5 M3.0

CENTRIFUGAL ROOF EXHAUST FAN DETAIL


SCALE: NTS

6 M3.0

ROOFTOP UNIT DETAIL


SCALE: NTS FIRE-RATED STRUCTURE

CEILING SPACE EXTERIOR WALL PROVIDE CLOSURE SPRING AND LATCHES FOR HORIZONTAL INSTALLATION HEAT PUMP SECURE PIPING TO WALL WITH MECHANICAL FASTENERS AND BRACKETS. 20 GA. STEEL BLADES WITH INTERLOCKING JOINTS ROUND OR RECTANGULAR DUCT BREAK-AWAY CONNECTION BLADE AND LINK CINCH 22 GA. STEEL MOUNTING COLLAR FINISHED WALL FLOOR GRADE ACCESS PANEL RATED STRUCTURE ROUND OR RECTANGULAR DUCT FUSIBLE LINK (165F) PROVIDE CLOSURE SPRING AND LATCHES FOR HORIZONTAL INSTALLATION PROVIDE COLLAR WHERE DUCTS PASS THRU WALL

20 GA. STEEL BLADES WITH INTERLOCKING JOINTS

2325 North Marine Boulevard Jacksonville, NC


5 6 7

6" MIN. OR AS OTHERWISE NOTED.

EOR: KEITH M. NIX #: 031858 22 GA. STEEL MOUNTING COLLAR

JANUARY 31, 2011

SLOPE LINES, DOWN, TOWARD OUTSIDE SEAL WATER TIGHT. 4" THK. CONC. PAD 3/8'' x 3" EXPANSION BOLT (TYP OF 4) ROUTE REFRIGERANT LINES UP ALONG INTERIOR OF BUILDING.

FOOTING COLLAR

1 1/2'' x 1 1/2'' x 1/8'' STEEL ANGLE FASTENED TO COLLAR ONLY WITH #10 SCREWS

BREAK-AWAY CONNECTION 1 1/2'' x 1 1/2'' x 1/8'' STEEL ANGLE FASTENED TO COLLAR ONLY WITH #10 SCREWS (TYP.)

MECHANICAL DETAILS
DRAWN BY: GJH PQ

FUSIBLE LINK (165F) BLADE AND LINK CINCH ACCESS PANEL

7 M3.0

CONDENSING UNIT DETAIL


SCALE: NTS

8 M3.0

UL-555 DYNAMIC FIRE DAMPER DETAIL


SCALE: NTS

9 M3.0

UL-555 DYNAMIC FIRE DAMPER DETAIL


SCALE: NTS

CHECKED BY:

PROJECT NO.:

10048

M3.0
PERMIT SET
c 2009

HANGER STRAPS: 1"x 22 GAUGE, SUPPORTED FROM STRUCTURE ABOVE, (3) SHEET METAL SCREWS BELOW.

FLEXIBLE DUCT: INSULATED, MAXIMUM 8'-0" DO NOT SAG OR KINK ROUND SELF-SEALING DUCT EQUAL TO SPIROSAFE; WRAP WITH 2" DUCT INSULATION; SEAL INSULATION WITH GLASS FABRIC/MASTIC

WRAP INSULATION: OVERLAP 4" MINIMUM, STAPLE & TAPE FOR VAPOR SEAL

WIRE SUPPORTS TO PREVENT SAGS AND KINKS IN FLEX

SIZES SHOWN ARE NET INSIDE FREE AREA DIMENSIONS

TAPE AND MASTIC OUTER JACKET (TYPICAL)

LINED SHEET METAL DUCT FOR SOUND ATTENUATION. SEE DRAWING FOR DUCT SIZE NO TURNING VANES

SECURE INSULATION WITH STICK-PINS AT 18" O.C. AND ADHESIVE ON BOTTOM, FOR DUCTS 24" AND LARGER CONICAL SPIN-IN FITTING WITH VOLUME DAMPER EQUAL TO CROWN PRODUCTS MODEL 3200-DS (SEE SPECS FOR OTHER OPTIONS)

MINIMUM RADIUS EQUAL TO THE FLEX DUCT DIAMETER

BAND CLAMP AND THREE SHEET METAL SCREWS THROUGH HELIX OF FLEXIBLE DUCT LINER (TYPICAL)

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

MAXIMUM VERTICAL DUCT RUN

SUPPORT FROM STRUCTURE (TYP.)

LOCATE REMOTE ALARM AND TEST STATION IN CEILING BELOW UNIT. PHOTOELECTRIC TYPE HEAD, RIGIDLY MOUNTED TO SIDE OF DUCT IN ACCESSIBLE LOCATION. SAMPLING TUBE TO TRANSVERSE ENTIRE WIDTH OF DUCT WITH INLET HOLES FACING UPSTREAM.

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

DUCT FABRICATION NOTES: 1. 2. 3. 4. 5. 6. 7. AIR FLOW 8. 9.


" 12

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

10. 11. 12.

DETECTOR SHALL BE SUITABLE FOR APPLICATION INTENDED, INCLUDING TEMPERATURE RANGE, HUMIDITY RANGE, ALTITUDE AND AIR VELOCITY.

24 "

6-10 EQUIVALENT DUCT DIAMETERS FROM INLETS AND BENDS, OR MINIMUM AS RECOMMENDED BY MANUFACTURER.

13.

DUCTS SHALL BE FABRICATED & INSTALLED PER THE LATEST EDITION OF SMACNA DUCT CONSTRUCTION STANDARDS. ALTERNATE INTERPRETATIONS OF SMACNA DUCT MATERIAL, HANGERS AND REINFORCEMENTS ARE SUBJECT TO ENGINEER APPROVAL, AND REQUIRE SEPARATE SUBMITTAL OF THE ALTERNATES. FLEXIBLE DUCT CONNECTORS SHALL BE PROVIDED WHERE SHOWN ON THE PLAN. SUPPLY AIR DROPS FROM ROOF TOP UNITS SHALL TRANSITION FROM THE UNIT OPENING SIZE TO SQUARE NECK ELBOWS, WITH SIZES AS SHOWN ON THE PLAN. IF TWO SUPPLY AIR DUCT RUNS ARE THE UNIT, THEN TWO AT SEPARATE DROPS & ELBOWS SHALL BE PROVIDED. RETURN AIR DROPS FROM THE ROOF TOP UNITS SHALL BE FULL SIZE OF THE UNIT OPENING. ELBOWS SHALL BE SQUARE NECK (SAME IN OUT DIMENSION) WITH 2" DOUBLE THICKNESS TURNING VANES. OFFSETS SHALL NOT REDUCE THE FREE AREA, AND SHALL NOT EXCEED 30. A RADIUS HEEL SHALL BE PROVIDED ON 30 OFFSETS. SMALLER OFFSETS SHALL BE MITERED AT BOTH THEHEEL & THROAT. TRANSITIONS SHALL NOT EXCEED 1:3 RATIO (4" TRANSITION PER FOOT SINGLE SIDED TRANSITION,AND 8" PER FOOT DOUBLE SIDED TRANSITION). INSULATION SHALL BE NFPA 90 APPROVED, WITH MINIMUM R-VALUE OF 4.2. WRAP INSULATIONSHALL BE 2" THICK WITH ALUMINUM FOIL FACING. LINER SHALL BE 1" THICK, 1-1/2 PCF DENSITY. RECTANGULAR BRANCH CONNECTIONS SHALL BE 45 ENTRY TYPE PER SMACNA FIGURE 2-6. ROUND DUCT CONNECTIONS SHALL BE WITH "CROWN PRODUCTS COMPANY" 3200-DS FITTINGS, DAMPER AND HANDLE. SPRAY PAINT LOCATIONS OF HANDLES. FLEXIBLE DUCT SHALL INCLUDE AN INNER POLYETHYLENE LINER, A SPRING HELIX, 1-1/4" BLANKET INSULATION (R6.0), A FOIL OUTER VAPOR BARRIER, AND BE UL-181 APPROVED. SEAL ALL SUPPLY, RETURN & OUTSIDE AIR DUCT JOINTS WITH DUCT SEALER; SEAL ALL INSULATION JOISTS WITH GLASS FABRIC AND MASTIC.

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

1" DUCT LINER

1 M3.1

DUCT MOUNTED SMOKE DETECTOR DETAIL.


SCALE: NTS

2 M3.1

RETURN SOUND BOOT DETAIL


SCALE: 1/4" = 1'-0"

3 M3.1

CONCEALED DUCTWORK INSTALLATION DETAIL - SHEET METAL

STEVENSON TOYOTA
TRAPEZE HANGARS STRAP OR ANGLE ROD UNLESS FOOT OF STRAP IS PLACED UNDER A BOTTOM DUCT REINFORCEMENT RECTANGULAR OR FLAT OVAL DUCT 1" MIN. SIZE BOLT(S) FOR LOAD HANGAR WITH LOAD RATED FASTENER FASTENERS STRAP ROD

SCALE: NTS

SLOPE TOP OF COVER FOR WATER RUN-OFF.

COORDINATE TOP OF COVER WITH POINT OF ENTRY AND TRUSS LAYOUT. CAULK AT WALL CONTACT WITH PAINTABLE SEALANT.

HANGER STRAPS: 1"x 22 GAUGE, SUPPORTED FROM STRUCTURE ABOVE, (3) SHEET METAL SCREWS BELOW.

WIRE SUPPORTS TO PREVENT SAGS AND KINKS IN FLEX

WRAP INSULATION: OVERLAP 4" MINIMUM, STAPLE & TAPE FOR VAPOR SEAL

FIELD VERIFY

ANCHOR FLANGES TO EXTERIOR 1" MINIMUM. EMBED WITH 1/8" STAINLESS STEEL ANCHOR BOLTS, 1 FOOT SPACING ON CENTER, ALL SIDES.

ROUND SELF-SEALING DUCT EQUAL TO SPIROSAFE; WRAP WITH 2" DUCT INSULATION; SEAL INSULATION WITH GLASS FABRIC/MASTIC

FLEXIBLE DUCT: INSULATED, MAXIMUM 8'-0'' DO NOT SAG OR KINK

18 GAUGE GALVANNEAL STEEL COVER

SIZES SHOWN ARE NET INSIDE FREE AREA DIMENSIONS

TAPE AND MASTIC OUTER JACKET (TYPICAL)

GALVANIZED SHOP FABRICATED INSULATED PLENUM

PRIME AND PAINT WITH OWNER/ ARCHITECT SELECTED COLOR.

SUPPLY DUCT WRAP INSULATION

BOTTOM OF COVER TO STOP 6" ABOVE FINISHED GRADE.

BREAK ALL CORNERS, REMOVE SHARP EDGES AND BURRS, (TYPICAL) CONICAL SPIN-IN FITTING WITH VOLUME DAMPER EQUAL TO CROWN PRODUCTS MODEL 3200-DS (SEE SPECS FOR OTHER OPTIONS) CEILING BAND CLAMP AND THREE SHEET METAL SCREWS THROUGH HELIX OF FLEXIBLE DUCT LINER (TYPICAL) LINEAR DIFFUSER

SEAL OPENING WITH SPRAY FOAM REFRIGERANT LINES TO CONDENSING UNIT

STRAP HANGARS 4 M3.1

EXTERIOR PIPE COVER DIAGRAM


SCALE: NTS

5 M3.1

LINEAR DIFFUSER RUN OUT DETAIL


SCALE: NTS

HANGER STRAPS 60'' MAX.

T.O. SR PARAPET 26' - 6" T.O. SD PARAPET 24' - 6" T.O. SD ROOF DECK 22' - 10" T.O. SR ROOF DECK 24' - 9"

SCREWS MAY BE OMITTED IF HANGAR LOOPS UNDER DUCT

12"x12" 12" VAV-1

10"x22"

B.O. STEEL 16' - 0" T.O. NC ROOF DECK 14' - 11 1/2" 10"

CONSTRUCT GALVANIZED SHEET METAL HOOD. HOOD SEAMS SHALL BE SLODERED . PROVIDE HOOD FOR PIPING EXITING ON OPPOSITE SIDES WHERE SHOWN ON ROOF PLAN.

TWO PIECE PIPE CLAMP INSULATED REFRIGERANT PIPE 24'' DIA. MAX.

PRIOR ISSUES:

22"x10"

B.O. BEAMFRAMING CEILING BEYOND H.P. RAKED WALL 1/8" 3/4" T.O. STEEL TUBE T.O. 22' - 114x6 B.O. HSS012x8 HSS 12x8 21' - 5" 21' - 6" 3" T.O. WALL SHEATHING SERVICE FACE OF @FRAMING ACM CLG.T.O. WALL SOFFIT PANEL 20' 1/4" T.O. STEEL20' -H.S.O. @ 20' 3/4" 2 - 4" 1 - 2" 19' - 7 3/4"

2325 North Marine Boulevard Jacksonville, NC


5 6 7

T.O. 2ND FLOOR SLAB 12' - 0" 8"x28" FILL VOID WITH EXPANDING FOAM PITCH

1-5/8", 16 GAUGE GALVANIZED CHANNELS BACK TO BACK. 36'' DIA. MAX. BAND OF SAME SIZE AS HANGER STRAP 2" PIPE SUPPORT COLUMN

SECURE WIRE

B.O. CONC. BEAM 8' - 8"

10'' DIA. MAX.

EOR: KEITH M. NIX #: 031858

ROOF DECK

INSULATION HANGER RODS, WIRES OR STRAPS 4" X 4" X 1/4" THICK STEEL PLATE ANCHORED TO ROOF DECK. ANCHORS SHALL NOT PENETRATE THE ROOF DECK MORE THAN 3/4" DEEP. NUTS ANGLES ALTERNATE LOCATION

DATE:

JANUARY 31, 2011

MECHANICAL DETAILS
DRAWN BY: CHECKED BY: GJH PQ

T.O. SERV. BAY FL. 0' - 0"

RIC MB RC C INV EL OUT24"


6 M3.1

GROUND FLR 0' - 0"

GENERAL NOTES: 1. 2. DETAILS BASED ON SMACNA 1995, FIG. 4-4. DUCT REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES. DO NOT EXCEED SMACNA, CH. 4, ALLOWABLE LOADLIMITS. HANGERS MUST NOT DEFORM DUCT SHAPE.

NOTES: 1. 2. FLASH AROUND PIPING SUPPORT COLUMN. PIPING SHALL BE SLOPED TOWARD THE CONDENSING UNIT. BAND, ONE-HALF ROUND, MAY BE USED IF DUCT SHAPE IS MAINTAINED.

PROJECT NO.:

10048

3. 4.

NEW CAR DELIVERY HVAC SECTION


SCALE: 1/4" = 1'-0"

7 M3.1

REFRIGERANT PIPING ROOF CAP DIAGRAM


SCALE: NTS

8 M3.1

DUCTWORK SUPPORT DETAILS


SCALE: NTS

M3.1
PERMIT SET
c 2009

PIPE CLAMP, "UNISTRUT" #P2600 WITH CUSHION BETWEEN PIPE & CLAMP. SIZE TO MATCH PIPING.

REFRIGERANT PIPING 10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 PRIMER PLUG NOTES: 1. 2. ALL REFRIGERANT PIPING SHALL BE HARD COPPER, TYPE "L" WITH LONG RADIUS ELBOWS. TRAPS SHALL BE SINGLE PIECE, WROUGHT COPPER. PITCH DOWN TOWARD DRAIN. Y 1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com CLEAN OUT www.kasperarch.com FL License No.: AA26000802

SUPPORT CHANNEL, " UNISTRUT" 1" WIDTH SERIES

DRAIN PAN (FURNISHED WITH AHU).

3. INSULATE SUCTION LINE WITH 3/4" ARMAFLEX INSULATION FULL LENGTH. DO NOT SPLIT DURING INSULATION BUTT JOINTS WITH ARMAFLEX SEALANT, AND APPLY ARMAFLEX PRESERVATIVE ON ALL INSULATION ABOVE THE ROOF LINE. WHERE REFRIGERANT OR CONDENSATE PIPING RUNS THROUGH RETURN AIR PLENUM, INSULATION SHALL BE FIRE RATED ARMAFLEX "AP" 25/50. 4. ROUTING OF ALL REFRIGERANT PIPING SHALL BE PLUMB AND SHALL RUN TRUE WITH THE BUILDING LINES. HORIZONTAL RUNS OF SUCTION LINES OVER 25' SHALL BE PITCHED "ONE - HALF" BUBBLE TOWARD THE COMPRESSOR, FOR OIL RETURN.

5. SUPPORT OF ALL PIPING AT COMPRESSORS, CONDENSERS, AND AIR HANDLING UNITS SHALL BE AS SHOWN ABOVE. SUPPORT OF PIPING IN BETWEEN THE UNITS SHALL BE WITH STRAP MATERIAL, USINGARMAFLEX INSULATION AS SADDLES. NO METAL-TO - METAL CONTACT. 6. 7. 8. BRAZE REFRIGERANT PIPING WITH FLOW OF DRY NITROGEN DURING BRAZING. SOLDER SHALL BE 15% SILVER "SIL-FOS" OR EQUAL. CHANGE FILTER - DRIER CORES AFTER 30 DAYS OF OPERATION. UNIT TYPE DRAW THRU BLOW THRU Y P + 1" 1" MIN. X 1/2 * (Y) 1'' + P 9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

WHERE P = STATIC PRESSURE IN PAN

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

1 M3.2

REFRIGERANT PIPING DETAIL


SCALE: NTS

2 M3.2

CONDENSATE DRAIN TRAP DIAGRAM


SCALE: NTS

STEVENSON TOYOTA
PRIOR ISSUES: DATE:
1 2

2325 North Marine Boulevard Jacksonville, NC


5 6 7

EOR: KEITH M. NIX #: 031858

JANUARY 31, 2011

MECHANICAL DETAILS
DRAWN BY: CHECKED BY: GJH PQ

PROJECT NO.:

10048

M3.2
PERMIT SET
c 2009

10175 Fortune Parkway, Suite 701 Jacksonville, FL 32256 p 904.683.9201 f 904.683.9702 www.kasperarch.com FL License No.: AA26000802

1610 East Morehead Suite 200 Charlotte, NC 28207 p 704.365.3160 f 704.365.3101 www.amkingconstruction.com

9133 RG Skinner Parkway Jacksonville, FL 32256 p 904.483.5200 p 904.636.6770 www.mcveighmangum.com

ALL REPORTS, SPECIFICATIONS, COMPUTER FILES, FIELD DATA AND OTHER DOCUMENTATION PREPARED BY KASPER ARCHITECTURE & DEVELOPMENT, INC. (KAD) AS INSTRUMENTS OF SERVICE SHALL REMAIN THE PROPERTY OF KAD. KAD SHALL RETAIN ALL COMMON LAW, STATUATORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. THIS DRAWING SHALL NEVER BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF KAD

DD DA DB DC DE

DG DF DH DJ DK DL

STEVENSON TOYOTA
PRIOR ISSUES: DATE:
1 2

AIR COMPRESSOR 308


4"

HP-3

D4
W

5 4 D

D3
1 1

LAUNDRY 307 1 1 1

KEYED NOTES:
RADIANT HEATER CHAIN HUNG FROM SUSPENDED UTILITY FRAME. SEE M0-1 FOR SPECIFICATIONS. 6x6 EXHAUST DISCHARGE TO WALL CAP WITH INSECT SCREEN. MATCH EXTERIOR COLOR AND FINISH. 6x6 OUTSIDE AIR DUCT TO WALL LOUVER L-1. PROVIDE DUCT MOUNTED MOTORIZED DAMPER INTERLOCKED WITH AHU-3. (BALANCE TO 120 CFM) REFRIGERANT LINES FROM HP-3 TO AC-3. PIPES TO BE RAN IN BETWEEN JOISTS IN CEILING SPACE. 4"DRYER VENT THRU WALL WITH BACKDRAFT DAMPER, AND WALL CAP WITH INSECT SCREEN. MATCH CAP TO EXTERIOR COLOR AND FINSIH. CONDENSATE FROM AC-3 TO BE RAN HORIZONTALLY IN CEILING SPACE AS SHOWN WITH A MINIMUM 1/8" PITCH FOR GRAVITY DRAINAGE. CONDENSATE TO SPILL TO DRYWELL. SEE DRYWELL DETAIL ON M3.2

D2

DETAIL AREA 306

5 1 1

ELECTRICAL ROOM 303

D1.7
1 1 1 1 1 OFFICE 302

TLT. ROOM 304


6"

B 240 CFM
6"

6"x6" 2

B 90 CFM
8"x10"

6"

A 100 CFM

EF-3 EF-3 TLT. ROOM 305

A 250 CFM
10"

6 3/4" CONDENSATE 3

6"x6"

B 400 CFM
1 1 1 1 1

10"x10"

14"x12" AC-3 14"x12"

L-1 120 CFM

A 10" 10" 250 CFM

A 250 CFM

WAITING 301

D1

2325 North Marine Boulevard Jacksonville, NC


5 6 7

1 MD1.0

1st FLOOR HVAC PLAN - DETAIL BLDG


SCALE: 1/8" = 1'-0"

PLAN

TRUE

EOR: KEITH M. NIX #: 031858

JANUARY 31, 2011

DETAIL BLDG HVAC PLANS


DRAWN BY: CHECKED BY: PQ KMN

PROJECT NO.:

10048

MD1.0
PERMIT SET
c 2009