NO.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20 20 21 22 23

Standard Isolation Turbine/Generator Open and LOTO breaker, MOT6417 Turbine fan A Open and LOTO breaker, MOT6418 Turbine fan B Open and LOTO breaker, MOT6413 Generator fan A Open and LOTO breaker, MOT6416 Generator fan B Open and LOTO breaker, MOT6415 Hydraulic Starter Open and LOTO breaker, MOT6435 Turbine L.O. Separator Open and LOTO breaker, MOT-6031 Generator Jacking Oil Pump Open and LOTO breaker, MOT-6899 Gear Box Turning Motor Open and LOTO breaker, MOT-6075A Generator Lube Oil Pump A Open and LOTO breaker, MOT-6075B Generator Lube Oil Pump B Open and LOTO breaker, MOT-6085A Generator Air/Oil Separator Open and LOTO breaker, Generator Emergency Lube Oil Pump ( DC ) Open and LOTO breaker, MOT -6241 Liquid fuel Boost Pump Open and LOTO breaker, MOT -6242A Water Inj. HP Liquid Pump Open and LOTO breaker, MOT -62059 Water Inj. LP Gas Pump Open and LOTO breaker, MOT -62226 Sprint Water Pump Open and LOTO breaker, Main Generator Open and Tag Out breaker, Igniter on Live Panel Shut and LOTO , CO2 Isolation valve Shut and LOTO , Fuel Gas Isolation valve Open and Tag Out the vent valves at the last chance filter (each filter) Shut and LOTO, Fuel Gas Oil Supply Isolation valve Shut and LOTO, Fuel Gas Oil Return Isolation valve

LOTO POSITION POSITION PERSON REQUIRED BEFORE AFTER APPLYING

Shut and LOTO, Instrument air valve Shut and LOTO, DM water valve Open and LOTO breaker, Generator winding heater

NO.

Turbine /Generator Fans

LOTO REQUIRED

POSITION BEFORE

POSITION AFTER

PERSON APPLYING

1 2

Generator Fan A Stop the Fan A from the control room console Open and LOTO breaker, MOT6413 Generator fan A Generator Fan B Stop the Fan A from the control room console Open and LOTO breaker, MOT6416 Generator fan B Turbine Fan A Stop the Fan A from the control room console Open and LOTO breaker, MOT6417 Turbine fan A Turbine Fan B Stop the Fan B from the control room console Open and LOTO breaker, MOT6418 Turbine fan B

1 2

1 2

1 2

In row no:7, Stop the Fan B from the control room console

NO. 1 2 3

Turbine /Generator Packages Ispection and Cleaning Turbine Open and LOTO breaker, MOT6413 Generator fan A Open and LOTO breaker, MOT6416 Generator fan B Close the CO2 valve and LOTO the valve

LOTO POSITION POSITION PERSON REQUIRED BEFORE AFTER APPLYING

1 2 3

Generator Open and LOTO breaker, MOT6417 Turbine fan A Open and LOTO breaker, MOT6418 Turbine fan B Close the CO2 valve and LOTO the valve

Open and LOTO breaker, MOT6415 Hydraulic Starter Shut and LOTO , Fuel Gas Isolation valve

Shut and LOTO, Fuel Gas Oil Supply Isolation valve Shut and LOTO, Fuel Gas Oil Return Isolation valve

NO. 1 2 5 8 9 10 11

Turbine Packages Work on Gas System / or HOT WORK Open and LOTO breaker, MOT6417 Turbine fan A Open and LOTO breaker, MOT6418 Turbine fan B Close the CO2 valve and LOTO the valve Shut and Tag Out, Fuel Gas Supply Isolation valve Open and Tag Out the vent valve at the last chance filter (each filter) Shut and Tag Out, Fuel Gas Oil Supply Isolation valve Shut and Tag Out, Fuel Gas Oil Return Isolation valve

LOTO POSITION POSITION PERSON REQUIRED BEFORE AFTER APPLYING

NO.
1 2 3 4 5 6 7 8

Turbine Packages Work on G/O System or HOT WORK Open and LOTO breaker, MOT6417 Turbine fan A Open and LOTO breaker, MOT6418 Turbine fan B
Close the CO2 valve and LOTO the valve Shut and Tag Out, Fuel Gas Supply Isolation valve Open and Tag Out the vent valves at the last chance filter (each filter) Shut and Tag Out, Fuel Gas Oil Supply Isolation valve Shut and Tag Out, Fuel Gas Oil Return Isolation valve

LOTO POSITION POSITION PERSON REQUIRED BEFORE AFTER APPLYING

Drain the Gas Oil system inside the package

NO.

GLO System

LOTO REQUIRED

POSITION BEFORE

POSITION AFTER

PERSON APPLYING

1 2 3 4 5 6 7 8 9 10
11

12 13 14 15

Open and LOTO breaker, MOT6413 Generator fan A Open and LOTO breaker, MOT6416 Generator fan B Open and LOTO breaker, MOT6415 Hydraulic Starter Open and LOTO breaker, MOT-6031 Generator Jacking Oil Pump Open and LOTO breaker, MOT-6899 Gear Box Turning Motor Open and LOTO breaker, MOT-6075A Generator Lube Oil Pump A Open and LOTO breaker, MOT-6075B Generator Lube Oil Pump B Open and LOTO breaker, MOT-6085A Generator Air/Oil Separator Open and LOTO breaker, HE 6067A Generator Lube Oil Heater A Open and LOTO breaker, HE 6067B Generator Lube Oil Heater B Open and LOTO breaker, Generator Emergency Lube Oil Pump ( DC ) Close and Tag Out the Generator Lube Oil Pump A discharge valve Close and Tag Out the Generator Lube Oil Pump B discharge valve Close and Tag Out the DC Generator Lube Oil Pump discharge valve Close and LOTO the CO2 valve

NO.

GLO System

LOTO REQUIRED

POSITION BEFORE

POSITION AFTER

PERSON APPLYING

1 2 3 4 5 6 7 8
9 10 11

12 13 14 15

Open and LOTO breaker, MOT6413 Generator fan A Open and LOTO breaker, MOT6416 Generator fan B Open and LOTO breaker, MOT6415 Hydraulic Starter Open and LOTO breaker, MOT-6031 Generator Jacking Oil Pump Open and LOTO breaker, MOT-6899 Gear Box Turning Motor Open and LOTO breaker, MOT-6075A Generator Lube Oil Pump A Open and LOTO breaker, MOT-6075B Generator Lube Oil Pump B Open and LOTO breaker, MOT-6085A Generator Air/Oil Separator Open and LOTO breaker, Generator Emergency Lube Oil Pump ( DC ) Open and LOTO breaker, HE 64050 Generator Space Heater Open and LOTO main Generator Breaker Close and Tag Out the Generator Lube Oil Pump A discharge valve Close and Tag Out the Generator Lube Oil Pump B discharge valve Close and Tag Out the DC Generator Lube Oil Pump discharge valve Close and LOTO the CO2 valve

NO. 1 2 3 4 5 6 7 8

TLO System Open and LOTO breaker, MOT6417 Turbine fan A Open and LOTO breaker, MOT6418 Turbine fan B Open and LOTO breaker, MOT6435 Turbine L.O. Separator Open and LOTO breaker, MOT6415 Hydraulic Starter Open and LOTO breaker, HE 6104 Turbine L.O. Heater
Close and Tag Out Turbine oil supply valve (from the Turbine oil tank )

LOTO POSITION POSITION PERSON REQUIRED BEFORE AFTER APPLYING

Close the CO2 valve and LOTO the valve Drain the Turbine Oil system inside the package

NO.
1 2 3 4 5 6

Hydraulic Starter Open and LOTO breaker, MOT6417 Turbine fan A Open and LOTO breaker, MOT6418 Turbine fan B Open and LOTO breaker, MOT6415 Hydraulic Starter Open and LOTO breaker, HE 1610 Hydr. Starter Heater
Close and Tag Out Hydraulic oil supply valve (from the Hyd. oil tank) Close the CO2 valve and LOTO the valve

LOTO POSITION POSITION PERSON REQUIRED BEFORE AFTER APPLYING