Figure 5.

Typical wiring for speaker supervision and switching, NFPA Style Y:


WIRES MUST BE SUPERVISED PER NFPA

I56-1169-013

ALL WIRING SHOWN IS SUPERVISED.

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED

TO NEXT DEVICE
SPEAKER SWITCHING CIRCUIT - NFPA STYLE W SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.

)( )+(
CONTROL MODULE

CONNECT MODULES TO LISTED COMPATIBLE CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY NOTIFIER CONTROL PANELS ONLY )( FROM PANEL OR )+( PREVIOUS DEVICE

FCM-1 Supervised Control Module Installation And Maintenance Instructions


Specifications Normal Operating Voltage: Maximum Current Draw: Average Operating Current: mode) Maximum NAC Line Loss: External Supply Voltage: Maximum (NAC): Maximum (Speakers): Drain on External Supply: Max NAC Current Ratings: Temperature Range: Humidity: Dimensions: Accessories: 15 to 32 VDC 6.5 mA (LED on) 375A (LED flashing - in group poll mode) 350A (LED of flashing - in direct poll 485A Max. (LED flashing, NAC shorted) 4 VDC (between Terminals T3 and T4) Regulated 24 VDC 70.7 V RMS, 50 W 1.7 mA Maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply For class B wiring system, the current rating is 3A For class A wiring system, the current rating is 2A 32F to 120F (0C to 49C) 10% to 93% Non-condensing 41/2 H 4 W 11/4 D (Mounts to a 4 square by 21/8 deep box.) SMB500 Electrical Box; CB500 Barrier

47 K EOL RESISTOR ELR-47K

)(

)(
LOOP

8 7 6 5

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4 3 2 10

0 1 2 3 4

)( )+(

AUDIO CIRCUIT DO NOT LOOP WIRE AROUND TERMINALS 3 & 4. BREAK WIRE TO ENSURE SUPERVISION OF CONNECTIONS. )( AUDIO AMPLIFIER, 70.7 Vrms MAX.

ONES

ADDRESS

)+(
SUPERVISION

USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER MUST PROVIDE WIRING SUPERVISION PER NFPA. AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION. ALL TERMINAL WIRING IS POWER LIMITED.

)+(

)+(

MODULE POLARITIES ARE SHOWN IN ALARM

TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES FOR SUPERVISION

C0879-01

Figure 6. Typical fault tolerant wiring for speaker supervision and switching, NFPA Style Z:
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED WIRES MUST BE SUPERVISED PER NFPA

ALL WIRING SHOWN IS SUPERVISED.

Before Installing This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. General Description FCM-1 Supervised Control Modules are intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. This module is used to switch an external power supply, which can be a DC power supply or an audio amplifier (up to 80 VRMS), to notification appliances. It also supervises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The FCM-1 has two pairs of output termination points available for fault-tolerant wiring and a panel-controlled LED indicator. This module can be used to replace a CMX-2 module that has been configured for supervised wiring operation. Compatibility Requirements To ensure proper operation, this module shall be connected to a compatible Notifier system control panels only (list available from Notifier). Mounting The FCM-1 mounts directly to 4 square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8. Surface mounted electrical boxes (SMB500) are available.
C088001

TO NEXT DEVICE

)( )+(
CONTROL MODULE

CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY )( FROM PANEL OR )+( PREVIOUS DEVICE

SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD. 47 K EOL RESISTOR IS INTERNAL AT TERMINALS 8 AND 9

9 8 7 6 5
LOOP

)(

)(

TENS

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 6789 5 4 3 2 10

0 1 2 3 4

)( )+(

ADDRESS

BYPASS CAPACITORS : 100 A2143-20 NONPOLARIZED <10 A LEAKAGE

)+(

)+(

AUDIO CIRCUIT DO NOT LOOP WIRE AROUND TERMINALS 3 & 4. BREAK WIRE TO ENSURE SUPERVISION OF CONNECTIONS. )( AUDIO AMPLIFIER, 70.7 Vrms MAX. USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER )+( MUST PROVIDE WIRING SUPERVISION PER NFPA. SUPERVISION AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
ALL TERMINAL WIRING IS POWER LIMITED.

MODULE POLARITIES ARE SHOWN IN ALARM

TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES FOR SUPERVISION

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
N500-46-00 4

2006 Notifier

I56-1169-013

N500-46-00

I56-1169-013 Notifier, 12 Clintonville Rd., Northford, CT 06472

Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited applications, the CB500 Module Barrier must be used to meet UL requirements for the separation of power-limited and nonpower-limited terminals and wiring. The barrier must be inserted into a 4 4 21/8 junction box, and the control module must be placed into the barrier and attached to the junction box (Figure 2A). The powerlimited wiring must be placed into the isolated quadrant of the module barrier (Figure 2B). 1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. 2. Set the address on the module per job drawings. Note: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1A. 3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. IMPORTANT: When using the FCM-1 for fire fighter telephone applications, remove Jumper (J1) and discard. The Jumper is located on the back under the product label as shown in Figure 1B. The module does not provide ring back when used as a firefighter telephone circuit.
Figure 1A. Removing rotary switch stop: Figure 1B. Jumper location:

Figure 3. Typical notification appliance circuit configuration, NFPA Style Y:

CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY TO NEXT DEVICE )-( )+( CONTROL MODULE

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED )-( )+( FROM PANEL OR PREVIOUS DEVICE

MODULE POLARITIES ARE SHOWN IN ALARM )-( )-( 47K EOL RESISTOR ELR-47K )+( UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1 )+(
LOOP

9 8 7 6 5

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4 3 2 10

0 1 2 3 4

)-( )+(

24 VDC CIRCUIT DO NOT LOOP WIRE ON TERMINALS 3 & 4. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. )-( )+( 24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.

ADDRESS

9 8 7 6 5
LOOP

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4 3 2 10

0 1 2 3 4
BACK OF MODULE LABEL

TO NEXT CONTROL MODULE OR END-OF-LINE-RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO NOTIFIER MANUAL.

C0820-01

ADDRESS

Figure 4. Typical fault tolerant notification appliance circuit configuration, NFPA Style Z:
C0218-00 C0458-00

J1 UNDER LABEL

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

Figure 2A. Module mounting with barrier:

Figure 2B:

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED


)( )+(

CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY


)( )+(

TO NEXT DEVICE

FROM PANEL OR PREVIOUS DEVICE

CONTROL MODULE
MODULE POLARITIES ARE SHOWN IN ALARM
8 9 1 0

9 8 7 6 5
LOOP

LO OP

4 5 6 78 3 9 10 EN 2 S 10 1 11 1 4 5 6 7 8 5 14 13 2 3 9 ON 2 ES 1 0 AD DR ES S

7T

EOL RESISTOR IS INTERNAL AT TERMINALS 8 & 9

)(

)(

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4 3 2 10

0 1 2 3 4

)( )+(

24 VDC CIRCUIT DO NOT LOOP WIRE ON TERMINALS 3 & 4. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
)( )+(

ADDRESS

)+(

)+(

24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.

LO OP

4 5 6 78 3 9 TEN 2 10 S 10 1211 15 4 5 6 7 8 14 13 3 9 ON 2 ES 1 0 AD DR ES S

9 1 0

UL LISTED EOL RELAY SHOWN ENERGIZED 24VDC COIL EOLR-1

ISOLATED QUADRANT

TO NEXT CONTROL MODULE OR END-OF-LINE-RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO NOTIFIER MANUAL.

C0821-01

C0219-00 C0217-00

N500-46-00

I56-1169-013

N500-46-00

I56-1169-013