JOB NO: CUSTMOR NAME ADDRESS AHU TAG NO: CONDITIONED AREA TOTAL WALL HEIGHT CEILING HEIGHT (FC) EXPOSURE GLASS AREA -SQ.FT WALL AREA- SQ.FT ** PARTITION AREA SKY GLASS AREA NO OF AIR CHANGES NO. OF PEOPLE CFM/PERSON EXHAUST AIR QTY. LIGHTING LOAD EQUIPMENT LOAD MISCELLANEOUS-SENS MISCELLANEOUS-LATE EXPOSED FLOOR ROOF GAIN CEILING GAIN SH PER PERSON LH PER PERSON BYPASS FACTOR CONDITIONED AREA CEILING HEIGHT (FC) VOLUME BYPASS FACTOR PEOPLE - BASIS EXHAUST AIR CHANGE BASIS TOTAL VENTILATION CFM NORTH WALL NORTH EAST WALL EAST WALL SOUTH EAST WALL SOUTH WALL SOUTH WEST WALL WEST WALL NORTH WEST WALL NORTH GLASS NORTH EAST GLASS EAST GLASS SOUTH EAST GLASS SOUTH GLASS SOUTH WEST GLASS WEST GLASS NORTH WEST GLASS SKY GLASS ALL GLASS PARTITION WALL FLOOR CEILING ROOF VENTILATION PEOPLE LIGHTS EQUIPMENT MISCELLANEOUS

4/20/2012

INPUT DATA
RENIASSENCE-II SHESADRIPURAM Guest Room 06 -3rd TO 21st Floor 325 11.8 10 N 316 320 SQ.FT FT. FT. N-E E 108 58 SQ.FT SQ.FT PER HOUR ** WALL AREA FIGURES ARE FOR THE HEIGHT OF WALL UP TO FALSE CEILING AND BALANCE HEIGHT WILL BE TO S-E S S-W W 85 N-W DATE: TIME OF PEAK MONTH OF PEAK 1600 HRS MAY OUTSIDE DESIGN CONDITIONS DB - OF RH - % WB - F TH - BTU/LB GRAINS/LB FACTORS WALL 0.33 GLASS 0.56 ALL GLASS 1.13 PARTITION 0.42 CEILING 0.31 FLOOR 0.32 ROOF 0.12 SKY GLASS 0.56
O

LATITUDE ALTITUDE

19.03.09 12.58 Deg N 3000 FT INSIDE DESIGN CONDITIONS

96 45 78 41.6 115

DB - OF RH - % WB - F TH - BTU/LB GRAINS/LB
O

68 55 62 28 56

3 20 2 1.0 CFM WATT/SQ.FT KW BTU/HR BTU/HR SQ.FT SQ.FT SQ.FT BTU/HR BTU/HR

ADP/SHR VALUES FOR INSIDE DESIGN DB 68 RH 55 SHR ADP 1 56.25 0.93 55.5 0.83 53.45 0.77 51.76

245 105 0.1

HEAT LOAD ESTIMATE


325 SQ.FT 10 FT. 3250 CU.FT 0.1 3 x x OUTSIDE INSIDE 20 3250 x 0.0166 = = = 60 DIFFERENCE DB 96 68 28 %RH 45 55 WB 78 62 16 TH 41.6 28 13.6 GR/LB 115 56 59

60 316 58 x x x x x x x x x x x x x x 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.56 0.56 0.56 0.56 0.56 0.56 x x x x x x x x x x x x x x 17 23 31 31 29 27 25 19 35 11.23 11.23 11.23 11.23 70.9 159 145.5 110 28 23 23 23 48 0.108 1 3.41 3410 1 12.5 0.067 1 1 5 = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = 1773 593 RETURN AIR GAIN FOR WALLS = ((WALL GAIN) x (HEIGHT ABOVE CEILING)) (CEILING HEIGHT (FC))

RETURN AIR GAIN **** 701 BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM SPACE LOAD AND ADDED TO RETURN AIR GAIN

85

108

679

SENSIBLE HEAT RATIO (ESHF) APPARATUS DEW POINT DEHUMIDIFIED CFM TOTAL SPACE HEAT VENTILATION HEAT RETURN AIR GAIN **** REFRIGERATION SUB TOTAL SAFETY (PUMP GAIN ETC.,) 5% REFRIGERATION TOTAL REFRIGERATION LOAD F CFM BTU/HR BTU/HR BTU/HR BTU/HR BTU/HR BTU/HR TR
O

= = = = = = = = = =

0.97 53.45 1336 19477 3305 552 23334 1167 24501 2.04

x 0.56 x x 0.56 x x 0.56 x 108 x 1.13 x 320 x 0.42 x x 0.32 x x 0.31 x x 0.12 x 60 x 28 x 3 x 245 x 650 x 1 x 1 x 1 x x 1 x SPACE SENSIBLE SUB TOTAL DUCT HEAT GAIN+FAN MOTOR+SAFETY PERCENTAGE TOTAL SPACE SENSIBLE HEAT VENTILATION 60 x 59 x PEOPLE 3 x 105 x MISCELLANEOUS x 1 x SPACE LATENT SUB TOTAL SAFETY PERCENTAGE TOTAL SPACE LATENT HEAT TOTAL SPACE SENSIBLE HEAT TOTAL SPACE HEAT

3417 3091

181 735 2217 3410 16798 2100 18898 237 315 552 28 580 18898 19477

\\vboxsrv\conversion_tmp\scratch24450\70112485.xls.ms_office

HEATLOAD ESTIMATE