Coordination

of Protection
to IEC 60947-4-1

Coordination Tables

1SBC 0097 00 R1001 edition Dec 2001

Home

Fuse

MCCB

MMS

Softstarters UL Comb.

MCB

ABB is providing a large offer of coordination tables needed for any motor
supply feeder for which protection against overload and short circuit are
mandatory in industrial applications.
Choice Guidance
For instance, a table given for 80kA is covering the intermediate short circuit
leveel i.e. 70, 60,...kA at the same voltage. However, you may find some
cheaper solution for lower short circuit levels in the database : the SCPD
upstream is calibrated to give the cheapest solution for the whole
combination starter according to the highest shor circuit level.
General Remarks
- to read before using the coordination tables Please read those remarks
before you start using the coordination. They will give you the general data
and help you use the tables properly.
Following basic functions are achieved :
overload protection, motor control, short circuit protection, isolation.
These functions are applied here for standard starters : direct-on-line
(DOL), reverser, star-delta, softstarters.
Coordination Types
Any table is in conformity with the standard IEC 60947-4-1 which
defines two types of coodinations : - Type 1 : there is not any risk for
the operator and assets, damage to the starter is acceptable, its
replacement for re-starting is generally necessary. - Type 2 : the
single acceptable risk is a light welding of the contactor, that means
the contacts shall be easily separated either by electrical control or
using a tool. After a short circuit, whatever its level, re-starting is
allowed after a few verifications : all the protection device functions
are still operational.

>> Coordination Tables - choose


your type of protection
- Fuses
- MCCBs
- MMS
- MCBs
- Softstarters
- UL Combination Starters

Short Circuit Protection Devices


The starters given in the tables are protected starters or combination
starters i.e. the SCPD (Short Circuit Protection Device) and the starter
are mounted in the same compartment or enclosure. Various SPCDs
are proposed : Moulded-Case Circuit Breaker (MCCB), Manual
Motor Starter (MMS), Switch-Disconnector-Fuse or Switch-Fuse.
Circuit Breakers or fuses coordinated with starters cannot be
determined directly : tests in Power Laboratories shall be carried out
to qualify the coordination type at low fault and high fault currents.
ABB has got a large knowledge about short circuit protection in its
qualified Laboratories in Europe (Low Voltage Agreement Group :
LOVAG). Use of a SCPD not in compliance with the manufacturers'
recommandations (type, settings) may invalidate the coordination.

Home

Fuse

MCCB

MMS

Softstarters UL Comb.

MCB

General Remarks

Motor Current
Tables are based on 4-pole, 3-phase motor currents.
Indicative currents are given.

Magnetic Tripping Current


Magnetic tripping current is everytime
indicated and chosen to withstand the sub
transient current at the starting phase

Ambient Temperature
Tables are given for 40C ambient temperature.
For higher temperature a derating factor must be applied :
Fuses : 0.8 to In when ambient temperature is 70C
MCCBs : 0.8 to In when ambient temperature is 60C
Thermal Overload Relay without derating up to 55C, 0.9 In at 70C

Safety Perimeter
It indicates the minimum distances of any
metallic plates from the components in order
to avoid any breakdown during short circuit.

Starting
Normal starting means up to 5s (cold state) at full speed
(class 10) and up to 2s (warm state)
Long starting or heavy duty means starting time between 5 to 30s
(class 30)
Thermal overload relays DU type and MMS are class 10A
Thermal overload relays SU type are class 30

Reverser Table
A "reverser" (two identical contactors) table
is given by the corresponding "DOL" table

Heavy duty star-delta starters


Heavy duty star-delta starters are star-delta starters for which :
- the motor speed reached at the end of the star period is less than 85% of the nominal one, mainly due to the
incertainty of the load inertia
- the connecting diagram to the motor is not in accordance with the one described in Main catalogue 1SBC0004
99 R1001 (p 8/10)
- the dwelling time (transition between star and delta connection) is longer than 80ms
Note : one only of the above conditions leads to "heavy duty" class.

Home

Fuse

MCCB

MMS

Softstarters UL Comb.

MCB

FUSE
Ue
V

Iq
kA

Coor.
type

Starting
type

SCPD
type

SCPD
curve

Size
kW

400

50

1
2
2

Normal
Normal
Normal

Din Fuse
Din Fuse
Din Fuse

04/02/00
04/02/00

Normal

Din Fuse

HD

Din Fuse

HD

Din Fuse

SD

Din Fuse

SD

Din Fuse

FG4080NS2.1af
FM4080NS2.1af
FG4080NSIN2.1
FM4080NSIN2.1
FG4080HDIN2.1
FM4080HDIN2.1
FG4080HD2.1
FM4080HD2.1af
FM4080SD1.1
FG4080SD1.1
FM4080SD2.1
FG4080SD2.1

29/08/01
29/08/01
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
12/11/01
27/09/00
27/09/00
05/04/00
05/04/00

100

Normal

Din Fuse

415
440

80
80

2
2

Normal
Normal

BS Fuse
Din Fuse

0.37 ... 7.5


0.37 ... 7.5
0.37 ... 355
0.37 ... 290
0.37 ... 250
0.37 ... 290
0.37 ... 200
0.37 ... 200
0.37... 200
0.37 ... 250
4 ... 355
4 ... 355
4 ... 355
4 ... 355
0.37 ... 55
0.37 ... 55
0.37 ... 355
0.37 ... 55
0.37 ... 55

FG4050NS1,1a/b
FG4050NS2.1a/b

gG
gG
gG
aM
gG
aM
gG
aM
gG
aM
aM
gG
aM
gG
gG
aM
gM
gG
aM

FG4000NS1.1
FM4000NS1.1
FGB4180NS2.1
FG4480NS2.1
FM4480NS2.1

04/02/00
04/02/00
04/02/00
04/02/00
04/02/00

500

80

Normal

Din Fuse

Normal

Din Fuse

HD

Din Fuse

HD

Din Fuse

SD

Din Fuse

SD

Din Fuse

1
2
2

Normal
Normal
Normal

Din Fuse
Din Fuse
Din Fuse

Normal

Din Fuse

HD

Din Fuse

HD

Din Fuse

SD

Din Fuse

SD

Din Fuse

gG
aM
gG
aM
gG
aM
gG
aM
aM
gG
gG
aM
gG
gG
gG
aM
gG
aM
gG
aM
gG
aM
aM
gG
gG
aM

0.37 ... 315


0.37 ... 315
0.37 ... 355
0.37 ... 355
0.37 ... 200
0.37 ... 200
0.37 ... 200
0.37 ... 200
4 ... 400
4 ... 355
4 ... 355
4 ... 400
0.37 ... 11
0.37 ...11
1.1 ... 500
1.1 ... 500
0.37 ... 355
0.37 ... 355
0.37 ... 200
0.37 ... 200
0.37 ... 200
0.37 ... 315
4 ... 560
4 ... 400
4 ... 400
4 ... 400

FG5080NS2.1af
FM5080NS2.1af
FG5080NSIN2.1
FM5080NSIN2.1
FG5080HDIN2.1
FM5080HDIN2.1
FG5080HD2.1
FM5080HD2.1
FM5080SD1.1
FG5080SD1.1
FG5080SD2.1
FM5080SD2.1
FG6935NS1.1
FG6935NS2.1
FG6950NS2.1af
FM6950NS2.1af
FG6950NSIN2.1
FM6950NSIN2.1
FG6950HDIN2.1
FM6950HDIN2.1
FG6950HD2.1
FM6950HD2.1
FM6950SD1.1
FG6950SD1.1
FG6950SD2.1
FM6950SD2.1

29/08/01
29/08/01
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
27/09/00
27/09/00
05/04/00
05/04/00
04/02/00
04/02/00
29/08/01
29/08/01
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
27/09/00
27/09/00
05/04/00
05/04/00

80

690

35
50

Table

Last
Update

Glossary
SCPD
HD
NS
SD

Short Circuit Protection Device


Heavy Duty
Normal start
Star Delta

gG
aM

Fuselink for general protection


Fuselink for motor starter protection

IN

INSUM Motor Protection

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : FG4050NS1.1a/b
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 50 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

Fuse
type
gG
[A]
10
10
10
10
20
20
25
25
25
40

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00

B6
B6
B6
B6
B6
B6
B7
B7
B7
A16

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

E16DU2.7
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9

Group

Current
Max.
setting range Current
[A]
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9

Imax [A]
2.7
2.7
2.7
2.7
2.7
6.3
9
9
12
16

FG4050NS1.1b
Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 50kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

Fuse
type
gG
[A]
10
10
10
10
20
20
25
35
40
40

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00

A9
A9
A9
A9
A9
A9
A9
A9
A12
A16

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

E16DU2.7
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9

Group

Current
Max.
setting range Current
[A]
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2,0 - 6.3
2,0 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9

Imax [A]
2.7
2.7
2.7
2.7
2.7
6.3
9
9
12
16

FG4050NS1.1a
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : FG4050NS2.1a/b
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

Fuse
type
gG
[A]
10
10
10
10
20
20
20
20
20
25

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00

B7
B7
B7
B7
B7
B7
B7
B7
B7
A16

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

E16DU2.7
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9

Group

Current
Max.
setting range Current
[A]
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9

Imax [A]
2.7
2.7
2.7
2.7
6.3
6.3
9
9
12
16

FG4050NS2.1b
Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 50kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

Fuse
type
gG
[A]
10
10
10
10
20
20
20
20
20
25

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00

A9
A9
A9
A9
A9
A9
A9
A9
A12
A16

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

E16DU2,7
E16DU2,7
E16DU2,7
E16DU2,7
E16DU6,3
E16DU6,3
E16DU18,9
E16DU18,9
E16DU18,9
E16DU18,9

Group

Current
Max.
setting range Current
[A]
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
2 - 6,3
2 - 6,3
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9

Imax [A]
2.7
2.7
2.7
2.7
2.7
6.3
9
9
12
16

FG4050NS2.1a
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 80 kA - Normal start - up, type : 2
Note : FG4080NS2.1af
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.2
1.5
2
2.6
3.5

2.2
3
4
5.5
7.5

5
6.6
8.5
11.5
15.5
19
22
25
30
32
37
44
50
60
63
72
85
105
135
165
200
240
290
350
420
520
545
610

11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA800D
OESA800D
OESA800D

Fuse
type*
gG
[A]
4
6
6
10
10
10
16
16
25
32
32
40
50
63
63
80
100
100
125
125
160
160
200
200
250
315
400
400
500
630
630
800
800
800

Contactor
Size

Type

OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA2H
OFAA2H
OFAA2H
OFAA3H
OFAA3H
OFAA3H
3
3
3

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A26
A30
A30
A40
A50
A50
A63
A63
A75
A95
A110
A145
A185
A210
A260
AF400
AF400
AF460
AF580
AF580
AF750

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
30
30
10
10
10
10
10
10
10
10
10
10

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E800DU(10)
E800DU(10)
E800DU(10)

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
150 - 500
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800

max [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
16
19
22
25
30
32
40
44
50
60
63
75
90
110
135
175
210
240
290
400
430
580
580
610

FG4080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 80 kA - Normal start - up, type : 2
Note : FM4080NS2.1af
aM
Fuse type aM

Direct-on-line starters with Switch - fuse


400 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.2
1.5
2
2.6
3.5

2.2
3
4
5.5
7.5
11

5
6.6
8.5
11.5
15.5
22
25
30
32
37
40
44
50
60
63
72
75
85
95
105
135
145
165
200
240
280
305
350
400
430
460
520

15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290

Switch-fuse
Type

Fuse*
type
aM

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

[A]
2
2
4
4
6
6
6
10
16
16
20
25
32
32
40
40
50
50
63
63
80
80
100
100
125
160
160
200
200
250
315
315
355
400
500
500
500
630

Contactor
Size

Type

OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A30
A30
A40
A40
A50
A50
A63
A63
A75
A75
A95
A95
A110
A145
A145
A185
A210
A260
A300
A300
AF400
AF400
AF460
AF460
AF580

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA200DU150
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E800DU(10)

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
110 - 150
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
17
22
25
30
32
37
40
45
50
60
63
72
75
85
95
110
135
145
175
200
250
280
305
350
400
430
460
520

FM4080NS2.1af

* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


400 V - 80 kA - Normal start - up, type : 2
Note : FG4080NSIN2.1[INSUM 2]
gG, INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2


400 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5

7.5

11
15
18.5

Switch-fuse

Rated
Current

Ie [A]
1.1
1.5
1.9
2.8
3.5
5.0
6.6
8.6
11.5

15.2

22
28.5
36

22
30

37
45
55
75
90
110
132
160
200
250

42
56

68
83
98
135
158
193
232
282
349
420

Type

Fuse
rating
gG

Contactor
Fuse
Type
and
Size

Type

Safety
clearance

Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2

t6 setting
max
for starter

Max.
Current

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

[A]
4
6
10
10
16
16
20
25

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H

A9
A9
A9
A9
A9
A9
A9
A9

[mm]
15
15
15
15
15
15
15
15

[s]
7
7
7
7
7
7
7
7

Imax [A]
1.3
1.8
3.4
3.4
6.5
6.5
7.5
9

OS32D

32

OFAA 00 H

A12

15

13

OS32D

32

OFAA 00 H

A16

15

15

OS32D

40

OFAA 00 H

A26

20

16.5

OS32D

50

OFAA 00 H

A26

20

19.5

OS32D
OS32D

63
80

OFAA 00 H
OFAA 00 H

A26
A30

20
20

7
7

26
32

OS63D

100

OFAA 00 H

A40

20

37

OS63D

100

OFAA 00 H

A50

20

40

0S125D

125

OFAA 00 H

A50

20

50

OS125D

125

OFAA 00 H

A63

20

58

OESA250D

160

OFAA 1 H

A75

20

66

OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D

160
200
250
315
315
400
400
500
630

OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H

A75
A95
A145
A145
A185
A260
A260
EH370
EH370

20
20
10
10
10
10
10
40
40

5
7
7
7
7
7
7
7
7

75
90
115
145
168
210
235
290
400

OESA630D

630

OFAA 3 H

EH550

40

440

OESA630D

630

OFAA 3 H

EH550

40

480

FG4080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Home

Group

Fuse

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


400 V - 80 kA - Normal start - up, type : 2
Note : FM4080NSIN2.1[INSUM 2]
aM , INSUM2
Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


400 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22

15
18.5
22
30
37
45
55
75

28.5
36
42
56
68
83
98
135

90
110
132

158
193
232

160
200

282
349

250

420

290

520

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D

Fuse
rating
aM

[A]
2
2
4
4
6
10
10
16
16
20
25
32
40
50
63
80
100
125
160
160
200
200
250
315
355
400
500
500
500
630
630

Contactor
Fuse
Type
and
Size

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185
A210
A260
EH370
EH370
EH370
EH550
EH550
EH550
EH550

Safety
clearance

Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2

[mm]
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
40

Group

t6 setting
max
for starter

Max.
Current

[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
5
7
7
7
7
7
7
7
7
5
7
5

Imax [A]
1.7
1.7
3.2
3.2
4.9
7.2
7.2
9
12
16
22
26
30
37
50
65
75
96
125
135
145
162
200
245
275
315
400
415
450
500
520

FM4080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


400 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FG4080HDIN2.1[INSUM 2]
gG , INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2


400 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
1.1
1.5
1.9
2.8
3.5
5.0
6.6
8.6
11.5
15.2
22

15
18.5
22

28,5
36
42

30
37
45
55
75
90
110
132
160
200

56
68
83
98
135
158
193
232
282
349

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

Fuse
rating
gG
[A]
6
10
10
16
16
20
25
32
40
50
63
80
100
125
125
160
200
200
250
315
400
400
500
630
630
630

Contactor
Fuse
Type
and
Size

Type

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A40
A50
A50
A63
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370
EH370

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

[s]
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
21

Imax [A]
1.5
2.7
2.7
5
5
6
7.1
10.5
13
16
22
26.5
32
46
46
51
70
70
92
130
150
175
210
328
328
350

MCU1/ MCU2
[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
10
10
10
10
40
40
40
40

FG4080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


400 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FM4080HDIN2.1[INSUM 2]
aM , INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


400 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
1.1
1.5
1.9
2.8
3.5
5.0
6.6
8.6
11.5
15.2

11
15
18.5
22
30
37
45
55

22
28.5
36
42
56
68
83
98

75
90
110
132
160
200

135
158
193
232
282
349

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D

Fuse
rating
aM
[A]
2
4
4
6
6
10
16
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
355
400
500
630

Contactor
Fuse
Type
and
Size

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM

A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A30
A30
A30
A50
A50
A63
A95
A145
A145
A185
A210
A260
EH370
EH370
EH370
EH550

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

[s]
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28

Imax [A]
1.5
2.6
2.6
4
4
6
11
11
13
18
20
25
31
40
50
60
75
95
110
125
155
190
215
245
320
380

MCU1/ MCU2
[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
40
40
40
40

FM4080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


400 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FG4080HD2.1
gG

Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5

18.5
22

36
42

30
37
45
55
75
90
110
132
160

56
68
83
98
135
158
193
232
290

Type

Fuse
type
gG
[A]
6
10
10
16
16
25
32
40
50
63
80
100
125
125
125
160
200
200
250
315
400
400
500
630
630

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
2
2
2
3
3
3

A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A40
A50
A50
A50
A63
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370

Thermal Overload
Relay

Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
40
40
40

Type

Group

Current
Max.
setting range Current

E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU185
T450SU235
T450SU235
T450SU310

[A]
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
27.5 - 40
35 - 52.5
35 - 52.5
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 -1 40
130 - 185
165 - 235
165 - 235
220 - 310

Imax [A]
1.5
2.7
2.7
4.5
4.5
6.3
9
11
14
18.9
24
30
35
43
43
50
60
68
90
105
140
165
205
235
300

* : trip class of E16DU


(x) : number of primary turns
FG4080HD2.1
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


400 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FM4080HD2.1af
aM

Fuse type aM

Direct-on-line starters with Switch - fuse


400 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22

15

28.5

18.5
22

36
42

30
37
45
55

56
68
83
98

75
90
110
132
160
200
250

135
158
210
250
320
380
470

Type

Fuse
type
aM
[A]
4
4
4
6
10
10
16
20
25
32
40
50
50
63
80
80
100
100
125
160
200
200
250
315
355
400
500
630
800

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
2
2
2
3
3
3

A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A30
A30
A40
A50
A63
A63
A95
A95
A95
A145
A145
A185
A210
A260
A300
AF400
AF400
AF400
AF580

Overload
Relay

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
10
10
40
40

Type

Group

Current
Max.
setting range Current

E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU80(3)
TA450SU80(2)
TA450SU80(2)
TA450SU80(2)
TA450SU105(2)
TA450SU60
TA450SU80
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
TA450SU235
E500 30*
E500 30*
E500 30*
E500 30*

[s]
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
18.3 - 26.7
27.5 - 40
27.5 - 40
27.5 - 40
35 - 52.5
40 - 60
55 - 80
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
165 - 235
150 - 500
150 - 500
150 - 500
150 - 500

Imax [A]
2.7
2.7
2.7
3.7
5.5
5.5
8.5
12
17
18.9
23
26.7
30
35
40
46
55
58
70
88
105
120
140
170
230
260
330
400
500

* : trip class
(x) : number of primary turns
FM4080HD2.1af
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 12/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star delta starters with separate TOR


400 V - 80 kA - Normal start - up, type : 1
Note : FM4080SD1.1
aM
Fuse type aM

Star-Delta starters with Switch - fuse


400 V, 80 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200

Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349

250
290
315
355

430
520
545
610

Switch-fuse
Type

Fuse
rating
aM

Contactor

Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D

[A]
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM

A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145
A185

A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145
A185

A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110
A145

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA110U110
TA200DU135
TA200DU150
TA200DU175

[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175

[A]
10
14
18
24
32
40
50
63
80
95
108
145
188
200
250
315

OESA400D

355

OFAM 2 aM

A210

A210

A185

TA450DU235

165 - 235

355

OESA400D

400

OFAM 2 aM

A210

A210

A185

TA450DU235

165 - 235

400

OESA630D
OESA630D
OESA630D
OESA630D

500
630
630
630

OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A260
AF400
AF400
AF400

A260
AF400
AF400
AF400

A210
A300
A300
A300

TA450DU310
E500DU500
E500DU500
E500DU500

220 - 310
165 - 500
165 - 500
165 - 500

500
630
630
630

FM4080SD1.1

Created 11/04/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 27/09/2000 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Star delta starters with separate TOR


400 V - 80 kA - Normal start - up, type : 1
Note : FG4080SD1.1
gG
Fuse type gG

Star-Delta starters with Switch - fuse


400 V, 80 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160

Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282

200
250
290
315
355

349
430
520
545
610

Switch-fuse
Type

Fuse
rating
gG

Contactor

Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D

[A]
20
25
32
40
50
63
80
100
125
125
160
200
250
250
315

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H

A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145

A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145

A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A110
A110

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA110DU110
TA200DU135
TA200DU150

[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
110 - 150

[A]
10
13
18
24
32
40
50
63
80
90
108
145
188
200
235

OESA400D

315

OFAA 2 H

A185

A185

A145

TA200DU175

130 - 175

285

OESA400D

400

OFAA 2 H

A185

A185

A145

TA200DU175

130 - 175

300

OESA630D
OESA630D
OESA630D
OESA630D
OESA630D

500
500
630
630
630

OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A210
A260
EH370
EH370
EH370

A210
A260
EH370
EH370
EH370

A185
A210
EH260
EH260
EH260

TA450DU235
TA450DU310
T450DU400
T450DU400
T450DU400

165 - 235
220 - 310
285 - 400
285 - 400
285 - 400

400
450
540
610
610

FG4080SD1.1
Created 11/04/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 27/09/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star-delta starters with TOR


400 V - 80 kA - Normal start - up, type : 2
Note : FM4080SD2.1
aM

Fuse type aM

Star-Delta starters with Switch - fuse


400 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200

Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349

250
290
315
355

430
520
545
610

Switch-fuse
Type

Fuse
rating
aM

Contactor

Thermal Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D

[A]
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM

A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A145
A145
A145
A210
A210

A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A145
A145
A145
A210
A210

A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110
A145

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA200DU90
TA200U110
TA200DU135
TA450DU185
TA450DU185

[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
130 - 185
130 - 185

[A]
10
14
18
24
32
40
50
63
80
95
108
145
188
200
250
315

OESA400D

355

OFAM 2 aM

EH370

EH370

A210

T450DU235

165 - 235

355

OESA400D

400

OFAM 2 aM

EH370

EH370

A210

T450DU235

165 - 235

400

OESA630D
OESA630D
OESA630D
OESA630D

500
630
630
630

OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

EH370
EH550
EH550
EH550

EH370
EH550
EH550
EH550

A260
A300
A300
A300

T450DU310
T450DU400
T450DU400
T450DU400

220 - 310
285 - 400
285 - 400
285 - 400

500
630
630
630

FM4080SD2.1

Created 22/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 04/04/2000 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Star delta starters with TOR


400 V - 80 kA - Normal start - up, type : 2
Note : FG4080SD2.1
gG

Fuse type gG

Star-Delta starters with Switch - fuse


400 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160

Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282

200
250
290
315
355

349
430
520
545
610

Switch-fuse
Type

Fuse
rating
gG

Contactor

Thermal Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D

[A]
20
25
32
40
50
63
80
100
125
125
160
200
250
250
315

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H

A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145

A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145

A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA200DU110
TA200DU135
TA200DU175

[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
130 - 175

[A]
10
13
18
24
32
40
50
63
80
90
108
145
188
200
235

OESA400D

315

OFAA 2 H

A185

A185

A145

TA200DU175

130 - 175

285

OESA400D

400

OFAA 2 H

A210

A210

A145

TA450DU185

130 - 185

315

OESA630D
OESA630D
OESA630D
OESA630D
OESA630D

500
500
630
630
630

OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

EH370
EH370
EH370
EH370
EH370

EH370
EH370
EH370
EH370
EH370

A210
A210
A260
A300
A300

TA450DU235
T450DU310
T450DU400
T450DU400
T450DU400

165 - 235
220 - 310
285 - 400
285 - 400
285 - 400

400
450
540
610
610

FG4080SD2.1
Created 22/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 1
Note : FG4000NS1.1
gG

Fuse type gG

Direct-on-line starters with Switch - fuse


400 V, 100 kA, Normal start - up, type 1
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.2
1.5
2
2.6
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55

5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
105

Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OESA00
OESA250D
OESA250D
OESA250D
OESA250D

Fuse
typegG
[A]
6
10
10
16
16
16
25
25
32
40
40
63
80
100
125
160
200
200
250

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A40
A50
A63
A75
A95
A110

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20

Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110

max [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
16
25
30
37
50
63
75
90
110

FG4000NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 1
Note : FM4000NS1.1
aM
Fuse type aM

Direct-on-line starters with Switch - fuse


400 V, 100 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.2
1.5
2
2.6
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55

5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
105

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OESA00
OESA00
OESA00
OESA00

Fuse
type
aM
[A]
4
4
6
6
8
8
8
10
16
20
25
32
40
50
63
100
100
125
160

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A40
A50
A63
A75
A95
A110

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
16
25
30
37
50
63
75
90
110

FM4000NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
415 V - 80 kA - Normal start - up, type : 2
Note : FGB4180NS2.2
BS Fuse
Fuse type BS

Direct-on-line starters with Switch - fuse


415 V, 80 kA, Normal start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current
415

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5

Ie [A]
1.15
1.5
2
2.5
3.5
5
6.5
8.4
11

7.5
11
15
18.5

14
21
28
35

22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

42
55
66
81
96
127
156
188
225
276
339
435
475
530
582

Type

OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA32P3A2
OESA32P3A2
OS63B3
(OESA 63)
OS63B3
OS63B3
OESA100G1
OESA200B3PL1
OESA200B3PL1
OESA 200
OESA200
OESA315
OESA315
OESA400
OESA630
OESA630
OESA630
OESA630
OESA800

Contactor
Safety
clearance

Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current

Fuse typeBS

Size

Type

[A]
NIT4
NIT6
NIT6
NIT16
NIT16
NIT16
NIT20
NIT20
NIT20M25
NIT20M25
NIT20M32
TIA32M50
TIA32M63
TIS63M80

A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A2
A2
A3

A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A30
A50

[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA75DU42

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42

max [A]
1.4
1.8
2.4
3.1
4
5
8.5
8.5
11
14
15.5
25
30
42

TIS63M80
TIS63M100
TC100M125
TC100M160
TC100M200
DEO200M250
DEO200M250
DEO200M315
DEO200M315
ED315M355
ED400M450
630R11/FF630
630R11/FF630
630R11/FF630
800S11/GF800

A3
A3
A4
B1
B1
-

A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
EH370
EH550
EH550
EH550
EH700

20
20
20
20
20
10
10
10
10
10
40
40
40
40
40

TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU175
TA450DU235
TA450DU235
TA450DU310
T450DU400
T900DU500
T900DU500
T900DU650
T900DU650

36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
165 - 235
165 - 235
220 - 310
285 - 400
355 - 500
355 - 500
465 - 650
465 -650

45
63
70
90
100
135
175
210
210
270
370
500
500
550
650

FGB4180NS2.2
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
440 V - 80 kA - Normal start - up, type : 2
Note : FG4480NS2.1
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


440 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75

Ie [A]
1.06
1.25
1.67

1.1
1.5
2.2
3
4
5.5

2.26
3.03
4.31
5.8
7.6
10.3

7.5
11
15
18.5
22

13.5
19.3
26.3
32
37.1

30
37
45
55

50.1
61.9
73.9
90.3

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OESA00
OESA250D
OESA250D
OESA250D

Fuse
type
gG
[A]
4
6
6
6
10
10
16
16
25
32
32
40
50
63
80
100
100
125
160
160
200

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A30
A40
A50
A63
A63
A75
A95
A110

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1.4
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110

[A]
1 - 1.4
1- 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110

Imax [A]
1.4
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
16
25
30
40
42
52
63
70
90
100

FG4480NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
440 V - 80 kA - Normal start - up, type : 2
Note : FM4480NS2.1
aM
Fuse type aM

Direct-on-line starters with Switch - fuse


440 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75

Ie [A]
1.06
1.25
1.67

1.1
1.5
2.2
3
4
5.5

2.26
3.03
4.31
5.8
7.6
10.3

7.5
11
15
18.5
22

13.5
19.3
26.3
32
37.1

30
37
45
55

50.1
61.9
73.9
90.3

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA00
OESA00
OESA00

Fuse
type
aM
[A]
2
2
4
4
4
6
6
8
10
16
16
20
25
32
50
50
63
63
100
100
125

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A30
A40
A50
A63
A63
A75
A95
A110

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1.4
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110

[A]
1 - 1.4
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110

Imax [A]
1.4
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
11
16
25
30
40
42
52
63
70
90
100

FM4480NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


500 V - 80 kA - Normal start - up, type : 2
Note : FG5080NS2.1af
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


500 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2

Ie [A]
0.85
1.2
1.48
2.1
2.6
3.8

3
4
5.5

5.5
8
9
11
12
14
19
22
25
28
32
33
40
45
52
55
60
65
70
80
100
110
135
160
190
230
280
335
420
430
580

7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA800D
OESA800D

Fuse*
type
gG
[A]
4
6
6
10
10
16
16
16
25
25
32
32
32
40
63
63
63
80
80
100
100
125
125
125
125
160
160
200
200
250
315
355
400
500
630
630
800
800

Contactor
Size

Type

OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA2H
OFAA2H
OFAA2H
OFAA3H
OFAA3H
OFAA3H
3
3

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A26
A30
A30
A40
A40
A50
A50
A63
A63
A75
A75
A95
A95
A110
A145
A145
A185
A210
A260
AF400
AF400
AF460
AF580
AF580

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
10
10
10
10
10
10
10
10
10
10

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA42DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU150
TA200DU175
TA450DU235
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)**
E800DU(10)

[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
7.5 - 11
10 - 14
10 - 14
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800

Imax [A]
1
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
11
12
14
19
22
25
28
32
33
40
45
52
55
60
65
70
80
100
110
135
170
200
240
290
400
430
500
580

FG5080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
** : mounting kit between contactor and relay is not available

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 29/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


500 V - 80 kA - Normal start - up, type : 2
Note : FM5080NS2.1af
aM
Fuse type aM

Direct-on-line starters with Switch - fuse


500 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2

Ie [A]
0.85
1.2
1.48
2.1
2.6
3.8

3
4
5.5

5.5
8
9
11
12
14
19
22
25
28
32
33
40
45
52
55
63
65
70
80
100
110
125
135
145
160
190
220
240
275
300
335
370
420
430
500
500

7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D

Fuse*
type
aM
[A]
2
2
4
4
4
4
6
6
10
16
16
16
16
25
32
32
40
40
50
50
63
63
80
80
100
100
125
125
125
160
160
200
200
250
250
315
315
355
400
500
500
500
630
630

Contactor
Size

Type

OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A26
A30
A30
A40
A40
A50
A50
A63
A63
A75
A75
A95
A95
A110
A145
A145
A145
A145
A185
A210
A260
A260
A300
AF400
AF400
AF400
AF460
AF460
AF580
AF580

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA42DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150
TA200DU200
TA450DU235
TA450DU235
TA450DU310
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)**
E800DU(10)

[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
7.5 - 11
10 - 14
10 - 14
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
80 - 110
100 - 135
100 - 135
100 - 135
110 - 150
150 - 200
165 - 235
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800

Imax [A]
1
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
11
12
14
19
22
25
28
32
33
40
45
52
55
63
65
70
80
100
110
125
135
145
165
200
220
240
275
300
335
370
420
430
500
500

FM5080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
** : mounting kit between contactor and relay is not available
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


500 V - 80 kA - Normal start - up, type : 2
Note : FG5080NSIN2.1[INSUM 2]
gG /INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2


500 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

11
15
18.5
22
30

Rated
Current

Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2

17.5
23
29
34
45

37
45
55
75
90
110
132
160
200
250
290
315

56
67
82
110
132
158
192
230
279
335
394
440

Switch-fuse
Type

Fuse
rating
gG

Contactor
Fuse
Type
and
Size

Type

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

MCU1/ MCU2

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

[A]
4
6
6
10
10
16
16
20
32

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H

A9
A9
A9
A9
A9
A9
A9
A9
A12

[mm]
15
15
15
15
15
15
15
15
15

[s]
7
7
7
7
7
7
7
7
7

Imax [A]
1.3
1.8
1.8
3.4
3.4
6.5
6.5
7.5
12

OS32D

32

OFAA 00 H

A16

15

13

OS32D

40

OFAA 00 H

A26

15

16.5

OS32D
OS32D
OS32D
OS63D

50
63
80
100

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H

A26
A30
A40
A50

20
20
20
20

7
7
7
7

19.5
26
33
40

OS125D

125

OFAA 00 H

A50

20

45

OS125D

125

OFAA 00 H

A63

20

55

OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

160
200
200
250
315
315
400
400
500
630
630

OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A75
A95
A110
A145
A145
A185
A210
A260
EH370
EH370
EH550

20
20
20
10
10
10
10
10
40
40
40

7
7
7
7
7
7
7
7
7
7
7

65
80
88
115
145
168
210
235
290
370
440

OESA630D

630

OFAA 3 H

EH550

40

440

OESA630D

630

OFAA 3 H

EH550

40

480

FG5080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


500 V - 80 kA - Normal start - up, type : 2
Note : FM5080NSIN2.1[INSUM 2]
aM/ INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


500 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45

37
45
55
75
90

56
67
82
110
132

110
132
160

158
192
230

200
250

279
335

290
315
355

394
440
483

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

Fuse
rating
aM

[A]
2
2
2
4
4
6
10
10
16
20
25
32
40
50
63
63
80
100
125
160
160
200
200
250
315
355
400
400
500
500
500
630

Contactor
Fuse
Type
and
Size

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A40
A50
A50
A63
A75
A95
A110
A145
A145
A145
A185
A210
A260
EH370
EH370
EH370
EH550
EH550
EH550
EH550

Safety
clearance

Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2

[mm]
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
40

Group

t6 setting
max
for starter

Max.
Current

[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
5
7
7
7
7
7
7
5
7
7
5
7

Imax [A]
1.7
1.7
1.7
3.2
3.2
4.9
7.2
7.2
12
14
22
26
30
38
45
50
63
75
96
125
135
145
162
200
240
275
315
340
415
415
450
500

FM5080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


500 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FG5080HDIN2.1[INSUM 2]
gG/ INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2


500 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

11
15
18.5
22
30

Rated
Current

Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2

17.5
23
29
34
45

37
45
55
75
90
110
132
160
200

56
67
82
110
132
158
192
230
279

Switch-fuse
Type

Fuse
rating
gG

Contactor
Fuse
Type
and
Size

Type

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

MCU1/ MCU2

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

[A]
6
6
10
10
16
16
20
25
32

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H

A9
A9
A9
A9
A9
A9
A9
A9
A12

[mm]
15
15
15
15
15
15
15
15
15

[s]
28
28
28
28
28
28
28
28
28

Imax [A]
1.5
1.5
2.7
2.7
5
5
6
7.1
10.5

OS32D

40

OFAA 00 H

A26

20

28

13

OS32D

50

OFAA 00 H

A26

20

28

16

OS32D
OS32D
OS32D
OS125D

63
80
100
125

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H

A30
A30
A40
A50

20
20
20
20

28
28
28
28

22
26.5
32
45

OS125D

125

OFAA 00 H

A63

20

28

46

OESA250D

160

OFAA 1 H

A63

20

28

51

OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

200
200
250
315
400
400
500
630
630

OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A95
A95
A145
A185
A210
A260
EH370
EH370
EH370

20
20
10
10
10
10
40
40
40

28
28
28
28
28
28
28
28
28

70
70
92
130
150
175
210
328
328

FG5080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


500 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FM5080HDIN2.1[INSUM 2]
aM /INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


500 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Switch-fuse

Rated
Current

Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5

15
18.5
22
30

37
45
55
75
90
110
132
160
200
250

23
29
34
45

56
67
82
110
132
158
192
230
279
335

Type

Fuse
rating
aM

Contactor
Fuse
Type
and
Size

Type

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

MCU1/ MCU2

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

[A]
2
2
4
4
6
6
10
16
16
20

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM

A9
A9
A9
A9
A9
A9
A9
A12
A12
A16

[mm]
15
15
15
15
15
15
15
15
15
15

[s]
28
28
28
28
28
28
28
28
28
28

Imax [A]
1.5
1.5
2.6
2.6
4
4
6
11
11
13

OS32D

25

OFAM 00 aM

A26

20

28

18

OS32D

32

OFAM 00 aM

A30

20

28

20

OS32D
OS32D
OS63D

40
50
63

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM

A30
A40
A50

20
20
20

28
28
28

25
31
40

OS63D

80

OFAM 00 aM

A50

20

28

45

OS63D

80

OFAM 00 aM

A63

20

28

50

OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D

100
125
160
200
250
315
355
400
500
630

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM

A75
A110
A145
A185
A210
A260
EH370
EH370
EH370
EH550

20
20
10
10
10
10
40
40
40
40

28
28
28
28
28
28
28
28
28
28

60
75
96
125
155
190
215
245
320
380

FM5080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


500 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FG5080HD2.1
gG

Fuse type gG

Direct-on-line starters with Switch - fuse


500 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.88
1.2
1,5
2.2
2.8
4
5.2
6.8
9.1
12.2
17.5
23
29
34

30
37
45
55
75
90
110
132
160
200

45
56
67
82
110
132
158
192
230
279

Switch-fuse
Type

Fuse
type
gG
[A]
4
6
10
10
16
20
25
32
40
50
63
80
100
125
125
160
200
200
250
315
400
400
500
630
630

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
2
2
3
3
3

A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A40
A50
A50
A63
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370

Thermal Overload
Relay

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
10
10
10
10
40
40
40

Type

Group

Current
Max.
setting range Current

E16DU1.0 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140
TA450SU185
T450SU185
T450SU235
T450SU235
T450SU310

[s]
0.3 - 1.0
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
27.5 - 40
35 - 52.5
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
185 - 235
185 - 235
220 - 310

Imax [A]
1.0
1.5
2.7
2.7
4.5
5.5
6.3
9
11
14
18.9
24
30
35
43
50
60
68
90
120
170
185
205
235
300

* : trip class of E16DU


(x) : number of primary turns
FG5080HD2.1
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/04/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


500 V - 80 kA - Long starting (heavy duty) start - up, type : 2
Note : FM5080HD2.1
aM
Fuse type aM

Direct-on-line starters with Switch - fuse


500 V, 80 kA, Long starting (heavy duty) start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30

Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6,9
9.1
12,2
17,5
23
29
34
45

37
45
55

56
67
82

75
90
110
132

110
132
158
192

160
200

230
279

250

335

Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Fuse
type
aM
[A]
2
4
4
4
6
10
10
16
20
25
32
40
50
63
80
100
100
125
160
200
200
250
315
355
400
400
500
630
630

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
2
2
2
2
3
3
3

A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A30
A40
A50
A63
A95
A95
A110
A145
A185
A185
A210
A260
EH370
EH370
EH370
EH370
EH550
EH550

Thermal Overload
Relay

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40

Type

Group

Current
Max.
setting range Current

E16DU1 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU80(2)
TA450SU(80)2
TA450SU105(2)
TA450SU60
TA450SU80
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
T450SU235
T450SU235
T450SU310
T450SU310
T450SU310
T450SU400

[s]
0.3 - 1
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
27.5 - 40
27.5 - 40
35 - 52.5
40 - 60
55 - 80
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
285 - 400

Imax [A]
1
2.7
2.7
2.7
3.7
5.5
5.5
8,5
12
17
18.9
23
30
35
46
55
58
70
88
105
120
140
170
200
220
240
285
310
350

* : trip class of E16DU


(x) : number of primary turns FM5080HD2.1
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star Delta Starters with separate TOR


500 V - 80 kA - Normal start - up, type : 1
Note : FM5080SD1.1
aM
Fuse type aM

Star-Delta starters with Switch - fuse


500 V, 80 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400

Ie [A]
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
538

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Fuse
rating
aM
[A]
10
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
355
400
500
500
630

Contactor

Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A9
A9
A12
A16
A16
A26
A26
A40
A40
A50
A63
A75
A95
A110
A145
A145
A185
A260
A300
A300
A300
AF400

A9
A9
A12
A16
A16
A26
A26
A40
A40
A50
A63
A75
A95
A110
A145
A145
A185
A260
A300
A300
A300
AF400

A9
A9
A9
A12
A12
A16
A16
A26
A26
A30
A40
A50
A75
A95
A110
A110
A145
A210
A260
A260
A260
A300

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA42DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU185
TA200DU175
TA450DU235
TA450DU235
TA450DU310
TA450DU310
E500DU500

Group

Current
Max.
setting range Current

[A]
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
165 - 235
220 - 310
220 - 310
165 - 500

[A]
8.6
10
14
18.9
24
32
40
50
63
80
95
115
145
188
200
250
315
355
400
500
500
630

FM5080SD1.1

Created 02/05/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 27/09/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star-delta starters with TOR


500 V - 80 kA - Normal start - up, type : 2
Note : FG5080SD2.1
gG

Fuse type gG

Star-Delta starters with Switch - fuse


500 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200

Ie [A]
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279

250
290
315
355

335
394
440
483

Switch-fuse
Type

Fuse
rating
gG

Contactor

Thermal Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D

[A]
16
20
25
32
40
50
63
80
100
125
125
160
200
250
250
315

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H

A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185

A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185

A9
A9
A9
A12
A12
A16
A16
A26
A26
A30
A40
A50
A75
A95
A110
A110

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32
TA42DU42
TA75DU52
TA75DU63
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU175

[A]
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175

[A]
8.6
10
14
18.9
24
32
40
50
63
80
90
110
145
188
200
245

OESA400D

315

OFAA 2 H

A185

A185

A145

TA200DU175

130 - 175

285

OESA400D

400

OFAA 2 H

A210

A210

A185

TA450DU185

130 - 185

315

OESA400D
OESA630D
OESA630D
OESA630D

400
500
500
630

OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A210
EH370
EH370
EH370

A210
EH370
EH370
EH370

A185
A210
A260
A300

T450DU235
T450DU235
T450DU310
T450DU310

165 - 235
165 - 235
220 - 310
220 - 310

340
405
450
530

FG5080SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star-delta starters with TOR


500 V - 80 kA - Normal start - up, type : 2
Note : FM5080SD2.1
aM

Fuse type aM

Star-Delta starters with Switch - fuse


500 V, 80 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400

Ie [A]
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
538

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Fuse
rating
aM
[A]
10
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
355
400
500
500
630

Contactor

Thermal Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A210
A210
EH370
EH370
EH370
EH370
EH550

A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A210
A210
EH370
EH370
EH370
EH370
EH550

A9
A9
A9
A12
A12
A16
A16
A26
A26
A30
A40
A50
A75
A95
A110
A110
A145
A210
A210
A260
A260
A300

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32
TA75DU42
TA75DU52
TA75DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU135
TA450DU185
TA450DU185
TA450DU235
T450DU235
T450DU310
T450DU310
T450DU400

Group

Current
Max.
setting range Current

[A]
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 185
130 - 185
165 - 235
165 - 235
220 - 310
220 - 310
285 - 400

[A]
8.6
10
14
18.9
24
32
40
50
63
80
95
115
145
188
200
250
315
355
400
500
500
630

FM5080SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
690 V - 35 kA - Normal start - up, type : 1
Note : FG6935NS1.1
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


690 V, 35 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

Fuse
type
gG
[A]
6
6
6
6
20
20
20
25
25
32
50

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

E16DU1
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9

Group

Current
Max.
setting range Current
[A]
0.3 - 1
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9

Imax [A]
1
2.7
2.7
2.7
6.3
6.3
6.3
7
7
9
17

FG6935NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
690 V - 35 kA - Normal start - up, type : 2
Note : FG6935NS2.1
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


690 V, 35 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13

Switch-fuse
Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

Fuse
type
gG
[A]
4
6
6
6
16
16
20
20
25
32
40

Contactor
Size

Type

00
00
00
00
00
00
00
00
00
00
00

A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15

Electronic Overload
Relay
Type

E16DU 1
E16DU 2.7
E16DU 2.7
E16DU 2.7
E16DU 6.3
E16DU 6.3
E16DU 6.3
E16DU 18.9
E16DU 18.9
E16DU 18.9
E16DU 18.9

Group

Current
Max.
setting range Current
[s]
0.3 - 1
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9

Imax [A]
1
2.7
2.7
2.7
6.3
6.3
6.3
7
9
10
17

FG6935NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
690 V - 50 kA - Normal start - up, type : 2
Note : FG6950NS2.1af
gG
Fuse type gG

Direct-on-line starters with Switch - fuse


690 V, 50 kA, Normal start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
1.1
1.5
2.2
3
4

Ie [A]
1.5
2
2.9
3.5
4.9

5.5
7.5
11
15

6.7
9
13
17
19
21
25
35
40
43
46
52
63

18.5
22
30
37

45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

82
95
115
140
170
205
235
245
305
315
370
420
420
470
470
500
500

Type

Contactor

Fuse*
type
gG

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
-

[A]
4
6
6
10
16
16
16
25
32
32
40
50
63
80
100
100
100
125
125
125
200
200
250
315
315
400
400
500
630
630
630
630
630
800
800
800
800

Size

Type

OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA2H
OFAA2H
OFAA2H
OFAA3H
OFAA3H
OFAA3H
4
4
4
4
4
4
4
4
4

A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A30
A30
A40
A50
A63
A63
A75
A95
A95
A95
A110
A145
A145
A185
A210
A210
A300
AF400
AF400
AF400
AF460
AF580
AF580
AF580
AF580
AF580
AF580

Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
30
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA42DU25
TA42DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA80DU52
TA80DU63
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU175
TA450DU185
TA450DU235
TA450DU235
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)**
E500DU(10)
E500DU(10)**
E500DU(10)
E500DU(10)**
E500DU(10)

[A]
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
130 - 185
165 - 235
165 - 235
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
150 - 500
250 - 800
150 - 500
250 - 800

max [A]
1.8
2.4
3.1
4
5
6.5
7
11
14
17
19
21
25
35
40
43
46
52
63
80
82
100
120
140
170
210
235
270
310
350
400
420
420
480
480
500
500

FG6950NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
** : mounting kit between contactor and relay is not available

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 29/08/2001 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
690 V - 50 kA - Normal start - up, type : 2
Note : FM6950NS2.1af
aM
Fuse type aM

Direct-on-line starters with Switch - fuse


690 V, 50 kA, Normal start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
1.1
1.5
2.2
3
4

Ie [A]
1.5
2
2.9
3.5
4.9

5.5
7.5
11
15

6.7
9
13
17
19
21
25
35
40
43
46
52
63

18.5
22
30
37

45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

82
95
115
140
170
205
220
245
305
315
350
370
420
350
470
470
500
500

Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D

Fuse*
type
aM
[A]
4
4
4
6
10
10
10
16
20
20
25
25
32
40
50
63
63
63
80
80
100
125
160
200
250
250
315
315
400
400
500
500
630
630
630
630
630
630

Contactor
Size

Type

OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM

A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A30
A30
A40
A50
A63
A63
A75
A95
A95
A95
A110
A145
A145
A185
A210
A210
A260
A300
AF400
AF400
AF400
AF460
AF580
AF580
AF580
AF580
AF580
AF580

Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
30
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA42DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA80DU52
TA80DU63
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU150
TA450DU185
TA450DU235
TA450DU235
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)*
E800DU(10)
E500DU(10)*
E800DU(10)
E500DU(10)*
E800DU(10)

[A]
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 185
165 - 235
165 - 235
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
150 - 500
250 - 800
150 - 500
250 - 800

max [A]
1.8
2.4
3.1
4
5
6.5
7
11
14
17
19
21
25
35
40
43
46
52
63
80
82
100
120
150
170
205
220
270
310
320
350
400
430
430
480
480
500
500

FM6950NS2.1af
* : tested with ABB fuses. To use such fuses or fuse with similar characteristics
** : mounting kit between contactor and relay is not available
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


690 V - 50 kA - Normal start - up, type : 2
Note : FG6950NSIN2.1[INSUM2]
gG /INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2


690 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Switch-fuse

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13

15
18.5
22
30

18
21
25
33

37
45
55
75

41
49
60
80

90
110
132
160
200

95
115
139
167
202

250
290

242
301

Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

Fuse
rating
gG

[A]
4
4
4
6
10
10
16
16
20
25
32
40
50
63
63
80
100
100
125
160
200
200
250
250
315
315
400
400
500
500

Contactor
Fuse
Type
and
Size

Type

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A30
A40
A50
A63
A75
A95
A95
A110
A145
A145
A145
A185
A210
A210
A260
EH370
EH370

Safety
clearance

Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2

[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
40
40

Group

t6 setting
max
for starter

Max.
Current

[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
5

Imax [A]
1.3
1.3
1.3
1.8
3.4
3.4
6.5
6.5
7.5
9
13
16.5
19.5
21
25
33
40
42
55
65
82
88
115
115
155
168
210
235
290
315

FG6950NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


690 V - 50 kA - Normal start - up, type : 2
Note : FM6950NSIN2.1[INSUM2]
aM/ INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


690 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Switch-fuse

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25

30
37
45
55

33
41
49
60

75
90
110
132
160
200
250

80
95
115
139
167
202
242

290
315
355
400
450

301
313
370
405
460

Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Fuse
rating
aM
[A]
2
2
2
4
4
4
6
10
10
16
20
25
25
32
40
50
63
63
80
100
125
125
160
200
250
315
315
355
400
400
500
500
630

Contactor
Fuse
Type
and
Size

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A9
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A30
A30
A40
A50
A63
A75
A95
A95
A110
A110
A145
A145
A185
A210
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550

Safety
clearance

Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2

[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40

Group

t6 setting
max
for starter

Max.
Current

[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7

Imax [A]
1.7
1.7
1.7
3.2
3.2
3.2
4.9
7
7
13
16
21
21
25
30
38
46
50
63
75
82
96
120
162
200
240
245
275
315
315
370
415
500

FM6950NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : FG6950HDIN2.1[INSUM2]
gG/ INSUM2
Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Switch-fuse

Rated
Current

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13

15
18.5
22

30
37
45
55
75
90
110
132
160
200

18
21
25

33
41
49
60
80
95
115
139
167
202

Type

Fuse
rating
gG

Contactor
Fuse
Type
and
Size

Type

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

MCU1/ MCU2

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D

[A]
4
4
6
10
10
16
16
20
25
32

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H

A9
A9
A9
A9
A9
A9
A9
A9
A26
A26

[mm]
15
15
15
15
15
15
15
15
20
20

[s]
28
28
28
28
28
28
28
28
28
28

Imax [A]
1.2
1.2
1.5
2.7
2.7
5
5
6
7.1
10.5

OS32D

40

OFAA 00 H

A26

20

28

13

OS32D

50

OFAA 00 H

A26

20

28

16

OS32D
OS32D

63
63

OFAA 00 H
OFAA 00 H

A30
A40

20
20

28
28

21
22

OS32D

80

OFAA 00 H

A40

20

28

25

OS32D

80

OFAA 00 H

A50

20

28

26.5

OS63D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

100
125
160
200
250
315
315
400
400
500

OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A50
A75
A95
A110
A145
A185
A185
A260
A300
EH370

20
20
20
20
10
10
10
10
10
40

28
28
28
28
28
28
28
28
28
28

33
46
51
70
92
120
130
175
175
210

FG6950HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters protected by INSUM 2


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : FM6950HDIN2.1[INSUM2]
aM/ INSUM2
Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Contactor

Switch-fuse

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25

30

33

37
45
55

41
49
60

75
90
110
132

80
95
115
139

160
200
250
290
315
355

167
202
242
301
313
370

Type

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Fuse
rating
aM
[A]
2
2
2
4
4
6
6
10
16
16
20
25
32
40
50
63
63
80
80
100
125
160
160
200
250
250
315
355
400
500
500
630

Fuse
Type
and
Size

Type

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM

A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A30
A30
A40
A50
A50
A63
A75
A95
A95
A110
A145
A185
A185
A185
A210
A300
EH370
EH370
EH370
EH370
EH550

Thermal Overload
Relay

Safety
clearance

Type

INSUM 2

Group

t6 setting
max
for starter

Max.
Current

[s]
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28

Imax [A]
1.5
1.5
1.5
2.6
2.6
4
4
6
11
11
13
18
21
25
31
35
40
46
50
60
75
96
96
120
140
155
190
215
245
320
320
380

MCU1/ MCU2
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40

FM6950HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : FG6950HD2.1
gG

Fuse type gG

Direct-on-line starters with Switch - fuse


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5.0
6.7
8.8
13
18
21
25
33
41
49

55
75
90
110

60
80
95
115

132
160
200

139
167
202

Switch-fuse
Type

Fuse
rating
gG
[A]
4
4
6
10
10
16
16
25
32
40
50
63
80
100
125
125
160
200
200
250
315
315
400
400
500
500

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

Contactor
Fuse
Type
and
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
2
2
2
3
3
3
3

A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A26
A30
A50
A63
A95
A95
A95
A110
A110
A145
A185
A185
A210
A260
EH370
EH370

Thermal Overload
Relay

Safety
clearance

[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
40
40

Type

E16DU1 30*
E16DU1 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
TA450SU185
T450SU235

Group

t6 setting
max
for starter

Max.
Current

[s]
0.3 - 1
0.3 - 1
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
27.5 - 40
35 - 52,5
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
130 - 185
165 - 235

Imax [A]
1
1
1.5
2.7
2.7
4.5
4.5
6.3
9
11
14
18.9
24
30
35
43
50
60
68
90
105
120
140
165
185
205

* : trip class of E16DU


(x) : number of primary turns
FG6950HD2.1
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : FM6950HD2.1
aM
Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Switch-fuse

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8,8
13
18
21
25

30
37

33
41

45

49

55

60

75
90
110

80
95
115

132
160

139
167

200

202

250
290
315

242
301
313

Type

Fuse
rating
aM
[A]
2
2
4
4
4
6
10
10
16
20
25
32
40
50
50
63
80
80
100
125
125
125
160
200
200
250
250
315
355
400
400
500
630
630

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D

Contactor
Fuse
Type
and
Size

Type

00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
2
2
2
2
3
3
3

A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A30
A30
A30
A40
A50
A50
A63
A75
A95
A95
A95
A110
A145
A185
A185
A210
A210
A300
EH370
EH370
EH370
EH370
EH550
EH550

Thermal Overload
Relay

Safety
clearance

[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40

Type

E16DU1 30*
E16DU1 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
TA450SU185
TA450SU185
T450SU235
T450SU310
T450SU310
T450SU310
T450SU400

Group

t6 setting
max
for starter

Max.
Current

[ s]
0.3 - 1
0.3 - 1
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
20 - 30
27.5 - 40
35 - 52.5
35 - 52.5
40 - 60
40 - 60
55 - 80
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
130 - 185
130 - 185
165 - 235
220 - 310
220 - 310
220 - 310
285 - 400

Imax[ A]
1
1
2.7
2.7
2.7
3.7
5.5
5.5
8.5
12
17
18.9
21
25
28
35
43
46
55
60
65
70
88
105
120
140
145
170
185
220
240
285
310
350

* : trip class of E16DU


(x) : number of primary turns
FM6950HD2.1
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star delta starters with separate TOR


690 V - 50 kA - Normal start - up, type : 1
Note : FM6950SD1.1
aM
Fuse type aM

Star-Delta starters with Switch - fuse


690 V, 50 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
4

Ie [A]
5

5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
450
560

6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
445
540

Switch-fuse
Type

Fuse
rating
aM

Contactor

Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

[A]

[A]

OS32D

[A]
6

OFAM 00 aM

A9

A9

A9

TA25DU3.1

2.2 - 3.1

5.3

OS32D

OFAM 00 aM

A9

A9

A9

TA25DU4

2.8 - 4

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D

10
10
16
20
25
32
40
50
50
63
80
100
125
160
200
250
250
315
355
400
500
630

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM

A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400
AF460

A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400
AF460

A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A145
A145
A185
A185
A300
A300
AF400

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU25
TA75DU32
TA75DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA450DU185
TA450DU185
T450DU235
E500DU500
E500DU500
E500DU500

3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 185
130 - 185
165 - 235
165 - 500
165 - 500
165 - 500

8.6
10
14
18.9
24
30
40
43
50
63
80
100
125
155
189
250
250
315
355
400
500
630

FM6950SD1.1
Created 19/05/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 27/09/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star delta starters with separate TOR


690 V - 50 kA - Normal start - up, type : 1
Note : FG6950SD1.1
gG
Fuse type gG

Star-Delta starters with Switch - fuse


690 V, 50 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
4

Ie [A]
5

5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400

6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
410

Switch-fuse
Type

Fuse
rating
gG

Contactor

Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

[A]

[A]

OS32D

[A]
10

OFAA 00 H

A9

A9

A9

TA25DU3.1

2.2 - 3.1

5.3

OS32D

10

OFAA 00 H

A9

A9

A9

TA25DU4

2.8 - 4

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

16
20
25
32
40
50
63
63
80
100
125
160
200
200
250
315
315
400
400
500
500

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400

A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400

A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A110
A145
A185
A185
A300
A300

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA42DU19
TA42DU25
TA42DU25
TA75DU32
TA42DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA200DU175
TA450DU185
TA450DU235
E500DU500
E500DU500

3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
130 - 185
165 - 235
165 - 500
165 - 500

8.6
10
14
18.9
24
32
43
43
52
63
85
108
135
145
188
206
285
318
340
405
450

FG6950SD1.1
Created 12/05/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 27/09/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star-delta starters with TOR


690 V - 50 kA - Normal start - up, type : 2
Note : FG6950SD2.1
gG

Fuse type gG

Star-Delta starters with Switch - fuse


690 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
4

Ie [A]
5

5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400

6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
410

Switch-fuse
Type

Fuse
rating
gG

Contactor

Thermal Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

[A]

[A]

OS32D

[A]
10

OFAA 00 H

A9

A9

A9

TA25DU3.1

2.2 - 3.1

5.3

OS32D

10

OFAA 00 H

A9

A9

A9

TA25DU4

2.8 - 4

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D

16
20
25
32
40
50
63
63
80
100
125
160
200
200
250
315
315
400
400
500
500

OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H

A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A145
A185
A210
A210
EH370
EH370

A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A145
A185
A210
A210
EH370
EH370

A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A110
A145
A185
A185
A210
A260

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA42DU19
TA42DU25
TA42DU25
TA75DU32
TA42DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA200DU175
TA450DU185
TA450DU235
T450DU235
T450DU310

3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
130 - 185
165 - 235
165 - 235
220 - 310

8.6
10
14
18.9
24
32
43
43
52
63
85
108
135
145
188
206
285
318
340
405
450

FG6950SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star-delta starters with TOR


690 V - 50 kA - Normal start - up, type : 2
Note : FM6950SD2.1
aM

Fuse type aM

Star-Delta starters with Switch - fuse


690 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
4

Ie [A]
5

5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
450
560

6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
445
540

Switch-fuse
Type

Fuse
rating
aM

Contactor

Thermal Overload
Relay

Fuse
Type
and
Size

K1
Line

K3
Delta

K2
Star

Type

Group

Current
Max.
setting range Current

[A]

[A]

OS32D

[A]
6

OFAM 00 aM

A9

A9

A9

TA25DU3.1

2.2 - 3.1

5.3

OS32D

OFAM 00 aM

A9

A9

A9

TA25DU4

2.8 - 4

OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D

10
10
16
20
25
32
40
50
50
63
80
100
125
160
200
250
250
315
355
400
500
630

OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM

A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A210
A210
A210
EH370
EH370
EH370
EH550

A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A210
A210
A210
EH370
EH370
EH370
EH550

A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A145
A145
A185
A210
A210
A260
A300

TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU25
TA75DU32
TA75DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA450DU185
TA450DU185
T450DU235
T450DU235
T450DU310
T450DU400

3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 185
130 - 185
165 - 235
165 - 235
220 - 310
285 - 400

8.6
10
14
18.9
24
30
40
43
50
63
80
100
125
155
189
250
250
315
355
400
500
630

FM6950SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

MCCB
Ue
V

Iq
kA

Coor.
type

Starting
type

SCPD
type

Overload
mean

kW
Motor

Table

last
update

400

35

2
2
2
2
2
2
2
2
2
2

S-D
DOL/HD
DOL
DOL/HD
S-D
S-D/HD
S-D
DOL
DOL / HD
S-D/HD

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

TOR
TOR
TOR
MP
MP
TOR
INSUM
INSUM
INSUM
MP

5.5 ... 355


0.37 ... 355
0.37 ... 355
30 ... 355
45 ... 355
45 ... 355
45 ... 355
0.37 ... 355
0.37 ... 355
45 ... 355

MB4035SD2.1af
MB4035HD2.1af
MB4035NS2.1af
MP4035HD2.1af
MP4035SD2.1af
MB4035SDHD2.1af
MB4035SDIN2.1af
MB4035NSIN2.1af
MB4035HDIN2.1af
MP4035SDHD2.1af

24/08/01
24/08/01
11/07/01
11/07/01
24/08/01
30/08/01
31/08/01
14/11/01
14/11/01
30/08/01

50

65

2
2
2
2
2
2
2
2
2
2
2

SD
DOL/HD
DOL
DOL
DOL / HD
S-D
DOL/HD
S-D/HD
S-D
S-D/HD
DOL

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

TOR
MP
TOR
INSUM
INSUM
MP
TOR
TOR
INSUM
MP
TOR

5.5 ... 355


30 ... 355
0.37 ... 355
0.37 ... 355
0.37 ... 355
45 ... 355
0.37 ... 355
45 ... 355
45 ... 355
45 ... 355
0.37 ... 355

MB4050SD2.1af
MP4050HD2.1af
MB4050NS2.1af
MB4050NSIN2.1af
MB4050HDIN2.1af
MP4050SD2.1af
MB4050HD2.1af
MB4050SDHD2.1af
MB4050SDIN2.1af
MP4050SDHD2.1af
MB4065NS2.1

24/08/01
11/07/01
11/07/01
14/11/01
14/11/01
24/08/01
24/08/01
30/08/01
31/08/01
30/08/01
25/02/00

415

80

DOL

MCCB

TOR

0.37 ... 355

MB4180NS2.1

25/02/00

440

50

2
2
2
2
2
2
2
2
2
2

DOL/HD
DOL
DOL
DOL/HD
S-D
S-D
DOL/HD
S-D/HD
S-D
S-D/HD

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

MP
TOR
INSUM
INSUM
TOR
MP
TOR
TOR
INSUM
MP

30 ... 355
0.37 ... 355
0.37 ... 355
0.37 ... 355
5.5 ... 355
45 ... 355
0.37 ... 355
45 ... 355
45 ... 355
45 ... 355

MP4450HD2.1af
MB4450NS2.1af
MB4450NSIN2.1af
MB4450HDIN2.1af
MB4450SD2.1af
MP4450SD2.1af
MB4450HD2.1af
MB4450SDHD2.1af
MB4450SDIN2.1af
MP4450SDHD2.1af

11/07/01
19/09/01
14/11/01
14/11/01
19/09/01
24/08/01
19/09/01
30/08/01
31/08/01
30/08/01

500

50

2
2
2
2
2
2
2
2
2
2

S-D
DOL/HD
DOL
DOL
DOL /HD
S-D
DOL/HD
S-D/HD
S-D
S-D/HD

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

TOR
MP
TOR
INSUM
INSUM
MP
TOR
TOR
INSUM
MP

5.5 ... 355


30 ... 355
0.37 ... 355
0.37 ... 355
0.37 ... 355
45 ... 355
0.37 ... 355
45 ... 355
45 ... 355
45 ... 355

MB5050SD2.1af
MP5050HD2.1af
MB5050NS2.1af
MB5050NSIN2.1af
MB5050HDIN2.1af
MP5050SD2.1af
MB5050HD2.1af
MB5050SDHD2.1af
MB5050SDIN2.1af
MP5050SDHD2.1af

24/0801
11/07/01
11/07/01
14/11/01
14/11/01
24/08/01
24/08/01
30/08/01
31/08/01
30/08/01

690

50

2
2
2
2
2
2
2
2
2
2

DOL/HD
DOL
DOL/HD
S-D
DOL
DOL/HD
S-D
S-D/HD
S-D
S-D/HD

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

TOR
INSUM
INSUM
TOR
TOR
MP
MP
TOR
INSUM
MP

0.37 ... 500


5.5 ... 500
5.5 ... 500
5.5 ...500
0.37 ... 500
45 ... 500
45 ... 500
45 ... 500
45 ... 355
45 ... 500

MB6950HD2.1af
MB6950NSIN2.1af
MB6950HDIN2.1af
MB6950SD2.1af
MB6950NS2.1af
MP6950HD2.1af
MP6950SD2.1af
MB6950SDHD2.1af
MB6950SDIN2.1af
MP6950SDHD2.1af

24/08/01
14/11/01
14/11/01
27/0801
11/07/01
11/07/01
24/08/01
30/08/01
31/08/01
30/08/01

Glossary
SCPD

Home

Short Circuit Protection Device

Fuse

MCCB

MMS

Magnetic only

Softstarters UL Comb.

MCB

HD
NS
SD

Heavy Duty
Normal Start
Star Delta

Prolim
Isomax
MP

MCCB
IN
TOR

Moulded Case Circuit Breaker


INSUM Motor Protection
Thermal Overload Relay

Current limiter
SACE isomax S
MCCB + Electronic Motor
Protection

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS
400 V - 35 kA - Normal start - up, type : 2
Note : MB4035SD2.1af
mccb+AF contactor

Star-delta starters with MCCB


400V, 35 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

Ie [A]
11.5
15.2
22
28.5
36
42
56
68
68
83
98
135
158
193

132

232

160

282

200

349

250

430

290

520

315

545

355

610

Moulded Case
Circuit-Breaker
Type

Contactors

Thermal Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor

S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In125 *
S3N160 In125 *
S3N160 In125 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S4N250 PR211-I
In250
S5N400 PR211-I
In400
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I
In630
S6N630 PR211-I
In630
S6N800 PR211-I
In800

Type

Current
setting
range

[A]
210
260
325
415
540
680
820
1040
900
1050
1250
1700
2000
2500

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145

A9
A9
A9
A 16
A 26
A 26
A 30
A 30
A30
A30
A40
A75
A95
A95

[mm]
10
10
10
10
10
10
10
10
20
20
20
20
20
15

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20

TA25DU14**
TA25DU19**
TA42DU25**
TA75DU32**
TA75DU42**
TA75DU52**
TA75DU63**
TA75DU80**
TA80DU52
TA80DU52
TA80DU63
TA110DU90
TA110DU110
TA200DU135

[A]
10-14
13-19
18-25
22-32
29-42
36-52
45-63
60-80
36 - 52
36 - 52
45 - 63
66 - 90
80 - 110
100 - 135

3000

A145

A145

A110

15

20

TA200DU175

130 - 175

4000

A210

A210

A145

15

15

TA200DU175

130 - 175

4800

A210

A210

A185

15

15

TA450DU235

165 - 235

6300

AF400

AF400

A210

10

15

E500DU500

150 - 500

7560

AF400

AF400

A260

10

15

E500DU500

150 - 500

7560

AF400

AF400

A260

10

15

E500DU500

150 - 500

8000

AF400

AF400

A260

10

15

E500DU500

150 - 500

* : magnetic only adjustable release


** : TOR to be connected between MCCB and Line/Delta node MB4035SD2.1af
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DOL STARTERS
400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4035HD2.1af
Isomax+AF+EOL

Direct-on-line starters with MCCB


400 V, 35 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case CircuitBreaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.1
1.5
1.9
2.8
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193

132

232

160

282

200

349

250

430

Type

Magnetic
tripping
current

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S5N400 PR211-I
In320
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I

Contactor
Type

Thermal Overload
Relay

Safety
clearance

Type

Group

Current
Max.
setting range Current

[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15

TA25DU1.4 **
TA25DU1.8 **
TA25DU2.4 **
TA25DU3.1 **
TA25DU4.0 **
TA25DU5.0**
TA25DU6.5 **
TA25DU8.5 **
TA25DU11 **
TA 450SU60 (4)
TA 450SU60 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60 (1)
TA 450SU80 (1)
TA 450SU80 (1)
TA 450SU105 (1)
TA 450SU140 (1)
TA 450SU185 (1)
TA 450SU185 (1)
TA 450SU235 (1)

[A]
1 -1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 15
13 - 20
20 - 30
23 - 40
23 - 40
40 - 60
55 - 80
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
165 - 235

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
15
20
25
40
40
50
63
80
105
140
185
185
235

3840

A300

15

TA 450SU310 (1)

220 - 310

300

4800

AF 400

10

E 500DU

150 - 500

400

6300

AF 460

10

E 500DU

150 - 500

460

7560

AF 750

10

E 500DU***

150 - 500

500

7560

AF 750

10

E 800DU

250 - 800

630

8000

AF 750

10

E 800DU

250 - 800

750

9600

AF 750

10

E 800DU

250 - 800

750

9600

AF 750

10

E 800DU

250 - 800

750

In630
S6N630 PR211-I
In630
290

520

315

545

355

610

S6N800 PR211-I
In800
S6N800 PR211-I
In800
S6N800 PR211-I
In800

MB4035HD2.1af
* : magnetic only adjustable release.
** : by pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on CT

Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 24/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS


400 V - 35 kA - Normal start - up, type : 2
Note : MB4035NS2.1af
MCCB+AF-contactor

Direct-on-line starters with MCCB


400V, 35 kA, Normal start - up, type 2
Motor

Moulded Case CircuitBreaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.1
1.5
1.9
2.8
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193

132

232

160

282

200

349

250

430

Type

Contactor

Magnetic
tripping
current

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 ln5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S5N400 PR211-I
In320
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I

Type

Safety
clearance

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 -1 4
13 -19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
66 - 90
80 - 110
110 - 150
130 - 175
165 - 235

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210

3840

A260

15

TA450DU310

220 - 310

260

4800

A300

15

TA450DU310

220 - 310

300

6300

AF400

10

E500DU

150 - 500

400

7560

AF580

10

E500DU**

150 - 500

500

7560

AF580

10

E800DU

250 - 800

580

8000

AF580

10

E800DU

250 - 800

580

9600

AF580

10

E800DU

250 - 800

580

9600

AF750

10

E800DU

250 - 800

750

In630
S6N630 PR211-I
In630
290

520

315

545

355

610

S6N800 PR211-I
In800
S6N800 PR211-I
In800
S6N800 PR211-I
In800

MB4035NS2.1af
* Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT-ON-LINE STARTERS
400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4035HD2-1af
MCCB+PR212MP+AF-cont

Direct-on-line starters with MCCB


400 V, 35 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

I1 range

S4N160 PR212-MP In100


S4N160 PR212-MP In100
S4N160 PR212-MP In100
S4N160 PR212-MP In160
S4N160 PR212-MP In160
S4N250 PR212-MP In200
S5N400 PR212-MP In320
S5N400 PR212-MP In320
S5N400 PR212-MP In320
S6N800 PR212-MP In630
S6N800 PR212-MP In630
S6N800 PR212-MP In630
S6N800 PR212-MP In630
S6N800 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Current
setting
PR 212 / MP
release I3 *

Contactor
Type

[A]

600
700
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670

A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF580
AF580
AF750

Group

Safety
Max.
clearance Current

[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10

Imax [A]
100
100
100
145
145
185
210
260
320
400
460
580
580
630

MP4035HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** : A300 in case of Normal Start

NORMAL and HEAVY-DUTY START


For smaller motor powers, please refer to MMS tables or MCCB / MCB tables
Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


400 V - 35 kA - Normal start - up, type : 2
Note : MP4035SD2.1af
PR212/MP+AF contactor

Star-delta starters with MCCB


400 V, 35 kA, Normal start - up, type 2
Motor
Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610

Moulded Case Circuit-Breaker


Type

I1 range

S4S160 PR212-MP In100


S4S160 PR212-MP In160
S4S160 PR212-/MP In160
S4S250 PR212-MP In200
S5S400 PR212-MP In320
S5S400 PR212-MP In320
S5S400 PR212-MP In320
S6S800 PR212-MP In630
S6S800 PR212-MP In630
S6S800 PR212-MP In630
S6S800 PR212-MP In630
S6S800 PR212-MP In630

[A]
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
800
960
1280
1600
1920
2240
2560
3780
4410
5040
5040
5670

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactors contactor
A30
A40
A75
A95
A95
A110
A145
A185
A210
A260
A260
A260

[mm]
15
15
15
15
15
15
15
10
10
10
10
10

[mm]
10
10
10
20
20
20
15
15
15
15
15
15

MP4035SD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY


400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4035SDHD2.1af
MCCB PR211+AF

Star-delta starters with MCCB


400 V, 35 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110

Ie [A]
83
98
135
158
193

132

232

160

282

200

349

250

430

290

520

315

545

355

610

Moulded Case
Circuit-Breaker
Type

Contactors

Thermal Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
[A]
[mm]
[mm]

S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S5N400 PR211-I
In320
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I
In630
S6N800 PR211-I
In800
S6N800 PR211-I
In800
S6N800 PR211-I
In800

Type

Current
setting
range
[A]

1280
1600
2200
2400
3000

A95
A95
A145
A145
A145

A95
A95
A145
A145
A145

A50
A50
A75
A95
A95

20
20
15
15
15

10
10
10
20
20

TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140

40 - 60
40 - 60
55 - 80
70 - 105
95 - 140

3840

A210

A210

A145

15

15

TA450SU140

95 - 140

4800

A210

A210

A145

15

15

TA450SU185

130 - 185

6300

AF400

AF400

A185

10

15

E500DU

150 - 500

7560

AF400

AF400

A260

10

15

E500DU

150 - 500

8000

AF400

AF400

A260

10

15

E500DU

150 - 500

9600

AF400

AF400

A260

10

15

E500DU

150 - 500

9600

AF400

AF400

AF400

10

10

E500DU

150 - 500

MB4035SDHD2.1af
* : Magnetic only adjustable release
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS + INSUM


400 V - 35 kA - Normal start - up, type : 2
Note : MB4035SDIN2.1af
INSUM PR211+AF

Star-delta starters with MCCB


400 V, 35 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610

Moulded Case
Circuit-Breaker
Type

Contactors

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor

S3N160 In125 *
S3N160 In125 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I In250
S4N250 PR211-I In250
S5N400 PR211-I In400
S5N400 PR211-I In400
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N800 PR211-I In800

[A]
1050
1250
1700
2000
2500
3000
4000
4800
6300
7560
7560
8000

A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A30
A40
A75
A95
A95
A110
A145
A185
A210
A260
A260
A260

[mm]
20
20
20
20
15
15
15
15
10
10
10
10

[mm]
10
10
10
10
20
20
15
15
15
15
15
15

MB4035SDIN2.1af
* : Magnetic only adjustable release.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 31/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS +INSUM


400 V - 35 kA - Normal start - up, type : 2
Note : MB4035NSIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


400 V, 35 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I In250
S5N400 PR211-I In320
S5N400 PR211-I In400
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N800 PR211-I In800
S6N800 PR211-I In800
S6N800 PR211-I In800

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF750

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10

Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
75
95
110
145
175
210
260
300
400
580
580
580
750

MB4035NSIN2.1af
* Magnetic only adjustable release

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4035HDIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


400 V, 35 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I In250
S5N400 PR211-I In320
S5N400 PR211-I In400
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N800 PR211-I In800
S6N800 PR211-I In800
S6N800 PR211-I In800

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF750
AF750
AF750
AF750

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
10

Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
80
110
145
185
200
250
300
400
460
630
750
750
750

* : magnetic only adjustable release. MB4035HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4035SDHD2.1af
MCCB PR212/MP+AF

Star-delta starters with MCCB


400 V, 35 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Type

I1 range**

S4N160 PR212-MP In100


S4N160 PR212-MP In160
S4N160 PR212-MP In160
S4N250 PR212-MP In200
S5N400 PR212-MP In320
S5N400 PR212-MP In320
S5N400 PR212-MP In320
S6N800 PR212-MP In630
S6N800 PR212-MP In630
S6N800 PR212-MP In630
S6N800 PR212-MP In630
S6N800 PR212-/MP In630

50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Pe [kW] Ie [A]
45
55
75
90
110
132
160
200
250
290
315
355

83
98
135
158
193
232
282
349
430
520
545
610

[A]

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactors contactor

A50
A50
A75
A95
A95
A145
A145
A185
A260
A260
A260
AF400

[mm]

[mm]

15
15
15
15
15
15
15
10
10
10
10
10

10
10
10
20
20
15
15
15
15
15
15
10

MP4035SDHD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS
400 V - 50 kA - Normal start - up, type : 2
Note : MB4050SD2.1af
mccb+AF contactor

Star-delta starters with MCCB


400V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

Ie [A]
11.5
15.2
22
28.5
36
42
56
68
68
83
98
135
158
193

132

232

160

282

200

349

250

430

290

520

315

545

355

610

Moulded Case
Circuit-Breaker
Type

Contactors

Thermal Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor

S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S4H250 PR211-I
In250
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6S630 PR211-I
In630
S6S630 PR211-I
In630
S6S630 PR211-I
In630
S6S800 PR211-I
In800

Type

Current
setting
range

[A]
210
260
325
415
540
680
820
1040
900
1050
1250
1700
2000
2500

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145

A9
A9
A9
A 16
A 26
A 26
A 30
A 30
A30
A30
A40
A75
A95
A95

[mm]
10
10
10
10
10
10
10
10
20
20
20
20
20
15

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20

TA25DU14**
TA25DU19**
TA42DU25**
TA75DU32**
TA75DU42**
TA75DU52**
TA75DU63**
TA75DU80**
TA80DU52
TA80DU52
TA80DU63
TA110DU90
TA110DU110
TA200DU135

[A]
10-14
13-19
18-25
22-32
29-42
36-52
45-63
60-80
36 - 52
36 - 52
45 - 63
66 - 90
80 - 110
100 - 135

3000

A145

A145

A110

15

20

TA200DU175

130 - 175

4000

A210

A210

A145

15

15

TA200DU175

130 - 175

4800

A210

A210

A185

15

15

TA450DU235

165 - 235

6300

AF400

AF400

A210

10

15

E500DU500

150 - 500

7560

AF400

AF400

A260

10

15

E500DU500

150 - 500

7560

AF400

AF400

A260

10

15

E500DU500

150 - 500

8000

AF400

AF400

A260

10

15

E500DU500

150 - 500

* : magnetic only adjustable release


** : TOR to be connected between MCCB and Line/Delta node MB4050SD2.1af
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT-ON-LINE STARTERS
400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4050HD2-1af
MCCB+PR212MP+AF-cont

Direct-on-line starters with MCCB


400 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

I1 range

Current
setting
PR 212 / MP
release I3 *

S4H160 PR212-MP In100


S4H160 PR212-MP In100
S4H160 PR212-MP In100
S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

[A]
600
700
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670

Contactor
Type

A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF580
AF580
AF580

Group

Safety
Max.
clearance Current

[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10

Imax [A]
100
100
100
145
145
185
210
260
320
400
460
460
580
630

MP4050HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** : A300 in case of Normal Start.

NORMAL and HEAVY-DUTY START


For smaller motor powers, please refer to MMS tables or MCCB / MCB tables
Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS


400 V - 50 kA - Normal start - up, type : 2
Note : MB4050NS2.1af
MCCB+AF-contactor

Direct-on-line starters with MCCB


400 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case CircuitBreaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193

132

232

160

282

200

349

250

430

1.5
1.9
2.8
3.5

Type

Magnetic
tripping
current

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S6S630 PR211-I
In630
S6S630 PR211-I

Contactor
Type

Safety
clearance

Thermal Overload
Relay
Type

Group

Current
setting
range

Max.
Current

[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000

A9
A9
A9
A9
A 16
A26
A 26
A 26
A 30
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A 95
A 110
A 145
A 185
A 210

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210

3840

A 260

15

TA450DU310

220 - 310

260

4800

A 300

15

TA450DU310

220 - 310

300

6300

AF 400

10

E 500DU

150 - 500

400

7560

AF 580

10

E 500DU**

150 - 500

500

7560

AF 580

10

E 800DU

250 - 800

580

8000

AF 580

10

E 800DU

250 - 800

580

9600

AF 580

10

E 800DU

250 - 800

580

9600

AF 750

10

E 800DU

250 - 800

750

In630
S6S630 PR211-I
In630
290

520

315

545

355

610

S6S800 PR211-I
In800
S6S800 PR211-I
In800
S6S800 PR211-I
In800

MB4050NS2.1af
* : Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


400 V - 50 kA - Normal start - up, type : 2
Note : MB4050NSIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


400 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800
S6S800 PR211-I In800

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF750

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10

Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
75
95
110
145
175
210
260
300
400
580
580
580
750

* Magnetic only adjustable MB4050NSIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4050HDIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


400 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800
S6S800 PR211-I In800

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF750
AF750
AF750
AF750

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
10

Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
80
110
145
185
200
250
300
400
460
630
750
750
750

* : magnetic only adjustable release. MB4050HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


400 V - 50 kA - Normal start - up, type : 2
Note : MP4050SD2.1af
PR212/MP+AF contactor

Star-delta starters with MCCB


400 V, 50 kA, Normal start - up, type 2
Motor
Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610

Moulded Case Circuit-Breaker


Type

I1 range

S4H160 PR212-MP In100


S4H160 PR212-MP In160
S4H160 PR212-/MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630

[A]
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
800
960
1280
1600
1920
2240
2560
3780
4410
5040
5040
5670

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactors contactor
A30
A40
A75
A95
A95
A110
A145
A185
A210
A260
A260
A260

[mm]
15
15
15
15
15
15
15
10
10
10
10
10

[mm]
10
10
10
20
20
20
15
15
15
15
15
15

MP4050SD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DOL STARTERS
400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4050HD2.1af
Isomax+AF+EOL

Direct-on-line starters with MCCB


400 V, 50 kA, long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.1
1.5
1.9
2.8
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250

5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430

290
315
355

520
545
610

Type

Magnetic
tripping
current

Contactor
Type

Thermal Overload
Relay

Safety
clearance

Type

Group

Current
Max.
setting range Current

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630

[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
A300
AF 400
AF 460

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10

TA25DU1.4 **
TA25DU1.8 **
TA25DU2.4 **
TA25DU3.1 **
TA25DU4 **
TA25DU5**
TA25DU6.5 **
TA25DU8.5 **
TA25DU11 **
TA 450SU60 (4)
TA 450SU60 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60 (1)
TA 450SU80 (1)
TA 450SU80 (1)
TA 450SU105 (1)
TA 450SU140 (1)
TA 450SU185 (1)
TA 450SU185 (1)
TA 450SU235 (1)
TA 450SU310 (1)
E 500DU
E 500DU

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 15
13 - 20
20 - 30
23 - 40
23 - 40
40 - 60
55 - 80
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
165 - 235
220 - 310
150 - 500
150 - 500

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
15
20
25
32
40
50
63
80
105
140
185
185
235
300
400
460

S6S630 PR211-I In630

7560

AF 750

10

E 500DU***

150 - 500

500

S6S630 PR211-I In630

7560

AF 750

10

E 800DU

250 - 800

630

S6S800 PR211-I In800


S6S800 PR211-I In800
S6S800 PR211-I In800

8000
9600
9600

AF 750
AF 750
AF 750

10
10
10

E 800DU
E 800DU
E 800DU

250 - 800
250 - 800
250 - 800

750
750
750

MB4050HD2.1af
* : Magnetic only adjustable release.
** : by pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on CT

Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 23/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY


400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4050SDHD2.1af
MCCB PR211+AF

Star-delta starters with MCCB


400 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110

Ie [A]
83
98
135
158
193

132

232

160

282

200

349

250

430

290

520

315

545

355

610

Moulded Case
Circuit-Breaker
Type

Contactors

Thermal Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor

S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S6S630 PR211-I
In630
S6S630 PR211-I
In630
S6S800 PR211-I
In800
S6S800 PR211-I
In800
S6S800 PR211-I
In800

Type

Current
setting
range

[A]
1280
1600
2200
2400
3000

A95
A95
A145
A145
A145

A95
A95
A145
A145
A145

A50
A50
A75
A95
A95

[mm]
20
20
15
15
15

[mm]
10
10
10
20
20

TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140

[A]
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140

3840

A210

A210

A145

15

15

TA450SU140

95 - 140

4800

A210

A210

A145

15

15

TA450SU185

130 - 185

6300

AF400

AF400

A185

10

15

E500DU

150 - 500

7560

AF400

AF400

A260

10

15

E500DU

150 - 500

8000

AF400

AF400

A260

10

15

E500DU

150 - 500

9600

AF400

AF400

A260

10

15

E500DU

150 - 500

9600

AF400

AF400

AF400

10

10

E500DU

150 - 500

MB4050SDHD2.1af
* : Magnetic only adjustable release.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS + INSUM


400 V - 50 kA - Normal start - up, type : 2
Note : MB4050SDIN2.1af
INSUM PR211+AF

Star-delta starters with MCCB


400 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610

Moulded Case
Circuit-Breaker
Type

Contactors

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor

S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S4H250 PR211-I In250
S5H400 PR211-I In400
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800

[A]
1050
1250
1700
2000
2500
3000
4000
4800
6300
7560
7560
8000

A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A30
A40
A75
A75
A95
A110
A145
A185
A210
A260
A260
A260

[mm]
20
20
20
20
15
15
15
15
10
10
10
10

[mm]
10
10
10
10
20
20
15
15
15
15
15
15

MB4050SDIN2.1af
* : Magnetic only adjustable release.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 31/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4050SDHD2.1af
MCCB PR212/MP+AF

Star-delta starters with MCCB


400 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Pe
[kW]

Ie [A]

45
55
75
90
110
132
160
200
250
290
315
355

83
98
135
158
193
232
282
349
430
520
545
610

Type

I1 range**

[A]
S4H160 PR212-MP In100
S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630

50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
Delta
setting
contactor contactor
PR212 /
type
type
MP
release I3 *
[A]
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor

A50
A50
A75
A95
A95
A145
A145
A185
A260
A260
A260
AF400

[mm]

[mm]

15
15
15
15
15
15
15
10
10
10
10
10

10
10
10
20
20
15
15
15
15
15
15
10

MP4050SDHD2.1af

* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 65 kA - Normal start - up, type : 2
Note : MB4065NS2.1
MCCB+TOR

Direct-on-line starters with MCCB


400 V, 65 kA, Normal start - up, type 2
Motor

Moulded Case CircuitBreaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.1
1.5
1.9
2.8
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193

132

232

160

282

200

349

250

430

290

520

315

545

355

610

Type

Magnetic
tripping
current
[A]
21
26
33
42
65

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5

S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800
S6H800 PR211-I
In800

Contactor
Type

Safety
clearance

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

A9
A9
A9
A9

[mm]
10
10
10
10

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1

Imax [A]
1.4
1.8
2.4
3.1

A 16

10

TA25DU4

2.8 - 4

A 16

10

TA25DU5

3.5 - 5

84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000

A 26
A 26
A 30
A 50
A 50
A 50
A 50
A 50
A 50
A 63
A 75
A 145
A 145
A 145
A 185
A 210

10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA200DU110
TA200DU110
TA200DU150
TA200DU175
TA450DU235

4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
80 - 110
80 - 110
110 - 150
130 - 175
165 - 235

6.5
8.5
11
14
19
25
32
42
50
63
75
110
110
145
175
210

3840

A 260

15

TA450DU310

220 - 310

260

4800

A 300

15

TA450DU310

220 - 310

300

6300

EH 370

40

T450DU400

285 - 400

400

7560

EH 550

40

T900DU500

355 - 500

500

8000

EH 550

40

T900DU650

465 - 650

550

9600

EH 700

40

T900DU650

465 - 650

650

9600

EH 700

40

T900DU650

465 - 650

650

MB4065NS2.1
* : Magnetic only adjustable release.
Created 14/01/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 25/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line Starters
415 V - 80 kA - Normal start - up, type : 2
Note : MB4180NS2.1
MCCB+TOR

Direct-on-line starters with MCCB


415 V, 80 kA, Normal start - up, type 2
Motor

Moulded Case CircuitBreaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
1.1
1.5
1.9
2.8
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610

Type

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5

S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3L160 In160 *
S3L160 In160 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L800 PR211-I In800
S6L800 PR211-I In800
S6L800 PR211-I In800

Magnetic
tripping
current
[A]
21
26
33
42
65

84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600

Contactor
Type

Safety
clearance

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

A9
A9
A9
A 16

[mm]
10
10
10
10

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1

Imax [A]
1.4
1.8
2.4
3.1

A 26

10

TA25DU4

2.8 - 4

A 26

10

TA25DU5

3.5 - 5

A 26
A 26
A 30
A 50
A 50
A 50
A 50
A 50
A 50
A 63
A 75
A 145
A 145
A 145
A 185
A 210
A 260
A 300
EH 370
EH 550
EH 550
EH 700
EH 700

10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
40
40
40
40
40

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA200DU110
TA200DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
T450DU400
T900DU500
T900DU650
T900DU650
T900DU650

4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
80 - 110
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
285 - 400
355 - 500
465 - 650
465 - 650
465 - 650

6.5
8.5
11
14
19
25
32
42
50
63
75
110
110
145
175
210
260
300
400
500
550
650
650

MB4180NS2.1
* : Magnetic only adjustable release.
Created 24/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 25/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT-ON-LINE STARTERS
440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4450HD2-1af
MCCB+PR212MP+AF-cont

Direct-on-line starters with MCCB


440 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
52
63
75
90
120
147
177
212
260
320
370
436
500
549

Type

I1 range

Current
setting
PR 212 / MP
release I3 *

S4H160 PR212-MP In100


S4H160 PR212-MP In100
S4H160 PR212-MP In100
S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

[A]
600
700
800
960
1280
1600
1920
2240
2880
3780
4410
5040
5040
5670

Contactor
Type

A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF460
AF580
AF580

Group

Safety
Max.
clearance Current

[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10

Imax [A]
100
100
100
145
145
185
210
260
320
400
460
460
580
580

MP4450HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
**: A300 in case of Normal Starter.

NORMAL and HEAVY-DUTY START


For smaller motor powers, please refer to MMS tables or MCCB / MCB tables
Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS


440 V - 50 kA - Normal start - up, type : 2
Note : MB4450NS2.1af
MCCB+AF-contactor

Direct-on-line starters with MCCB


440 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3

Ie [A]
1
1.4
1.7
2.2
3.0
4.4
5.7

4
5.5
7.5

7.8
10.5
13.5

11
15
18,5
22
30
37
45
55
75
90
110

19
26
32
38
52
63
75
90
120
147
177

132

212

160

260

200

320

250

410

290

448

315

500

355

549

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800

Contactor
Type

Safety
clearance

Overload
Relay
Type

Group

Current
Max.
setting range Current

[A]
21
26
33
42
52
65
84
84
145
210
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU175
TA450DU235

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3,5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
165 - 235

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
6.5
11
14
14
16
25
32
42
45
63
70
90
100
135
175
210

3200

A260

15

TA450DU235

165 - 235

235

4000

A300

15

TA450DU310

220 - 310

300

4800

AF 400

10

6300
6300

AF 580
AF 580

10
10

E 500DU
TA450DU400
E 500DU**
E 800DU
TA900DU500

150 - 500
285 - 400
150 - 500
250 - 800
355 - 500

400
400
500
580
500

7560
7560

AF 580
AF 580

10
10

E 500DU**
E 800DU
TA900DU500

150 - 500
250 - 800
355 - 500

500
580
500

8000

AF 580

10

9600

AF 580

10

E 800DU
TA900DU650
E 800DU
TA900DU650

250 - 800
465 - 650
250 - 800
465 - 650

580
580
580
580

MB4450NS2.1af
* Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 19/09/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


440 V - 50 kA - Normal start - up, type : 2
Note : MB4450NSIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


440 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
1
1.4
1.7
2.2
3
4.4
5.7
7.8
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
212
260
320
410
448
500
549

Type

Magnetic
tripping
current
[A]
21
26
33
42
52
65
84
145
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000
3200
4000
4800
6300
7560
8000
9600

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H800 PR211-I In800
S6H800 PR211-I In800

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A63
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF580

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10

Imax [A]
1.6
2
2.5
3.2
4
5
6.5
11
16
16
25
32
42
45
63
70
93
100
145
185
210
240
280
400
580
580
580
580

* : Magnetic only adjustable release MB4450NSIN2.1af


Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4450HDIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM


440 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
1
1.4
1.7
2.2
3
4.4
5.7
7.8
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
212
260
320
410
448
500
549

Type

Magnetic
tripping
current
[A]
21
26
33
42
52
65
84
145
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000
3200
4000
4800
6300
7560
8000
9600

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H800 PR211-I In800
S6H800 PR211-I In800

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A63
A63
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF580
AF750
AF750
AF750

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
10

Imax [A]
1.6
2
2.5
3.2
4
5
6.5
11
16
16
25
32
42
45
63
80
100
125
185
200
240
280
400
400
580
630
750
750

* : Magnetic only adjustable release. MB4450HDIN2.1af


Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS
440 V - 50 kA - Normal start - up, type : 2
Note : MB4450SD2.1af
mccb+AF contactor

Star-delta starters with MCCB


440 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250

Ie [A]
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
212
260
320
410

290

315

355

448

500

549

Moulded Case
Circuit-Breaker
Type

Contactors

Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor

S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 **
S3H160 In125 **
S3H250 In200 **
S3H250 In200 **
S4H250 PR211-I In250
S4H250 PR211-I In250
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630

S6H630 PR211-I In630

S6H630 PR211-I In630

S6H630 PR211-I In630

[A]
210
210
325
415
540
680
820
1040
950
1150
1600
1850
2500
3000
4000
4800
6300

6300

6300

7560

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A145
A145
A145
A145
A210
A210
AF400

AF400

AF400

AF400

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A145
A145
A145
A145
A210
A210
AF400

AF400

AF400

AF400

A 9*
A 9*
A 9*
A 16*
A 16*
A 26*
A 26*
A 30*
A30*
A40*
A75*
A75*
A95
A110
A145
A185
A210

[mm]
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
15
10

A260

A260

A260

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15

10

15

10

15

10

15

Type

[A]
TA25DU14***
10-14
TA25DU14^***
10-14
TA42DU25***
18-25
TA75DU32***
22-32
TA75DU42***
29-42
TA75DU52***
36-52
TA75DU63***
45-63
TA75DU80***
60-80
TA80DU52
36 - 52
TA80DU63
45 - 63
TA80DU80
60 - 80
TA200DU110 80 - 110
TA200DU110 80 - 110
TA200DU135 100 - 135
TA200DU175 130 - 175
TA450DU235 165 - 235
E500DU500

150 - 500

TA450DU310

220 - 310

E500DU500

150 - 500

TA450DU310

220 - 310

E500DU500

150 - 500

TA450DU310

220 - 310

E500DU500

150 - 500

TA450DU400

285 - 400

MB4450SD2.1af
* : Using mounting kits, use Star-contactor size same as Delta-contactor size.
** : Magnetic only adjustable release
** : Connect the OR between the MCCB and the Line-Delta node.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 19/09/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Current
setting
range

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


440 V - 50 kA - Normal start - up, type : 2
Note : MP4450SD2.1af
PR212/MP+AF contactor

Star-delta starters with MCCB


440 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
75
90
120
147
177
212
260
320
410
448
500
549

Type

I1 range

S4H160 PR212-MP In100


S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630

[A]
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
700
960
1120
1440
1600
1920
2560
3780
3780
4410
5040
5040

A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A30
A40
A75
A75
A95
A110
A145
A185
A210
A260
A260
A260

[mm]
15
15
15
15
15
15
15
10
10
10
10
10

[mm]
10
10
10
10
20
20
15
15
15
15
15
15

MP4450SD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DOL STARTERS
440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4450HD2.1af
Isomax+AF+EOL

Direct-on-line starters with MCCB


440 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3

Ie [A]
1
1.4
1.7
2.2
3
4.4
5.7

4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

7.8
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177

132

212

160

260

200

320

250

410

290

448

315

500

355

549

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800

Contactor
Type

Safety
clearance

Overload
Relay
Type

Group

Current
Max.
setting range Current

[A]
21
26
33
42
52
65
84
84
145
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000

A9
A9
A9
A9
A16
A26
A26
A30
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15

TA25DU1.4 **
TA25DU1.8 **
TA25DU2.4 **
TA25DU3.1 **
TA25DU4 **
TA25DU5 **
TA25DU6.5 **
TA25DU8.5 **
TA25DU11 **
TA25DU14 **
TA 450SU60 (4)
TA 450SU80 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60
TA 450SU80
TA 450SU105
TA 450SU105
TA 450SU140
TA 450SU185
TA 450SU235

[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
10 - 15
18 - 27
20 - 30
28 - 40
28 - 40
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
130 - 185
165 - 235

Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
6.5
11
14
15
25
30
40
40
60
80
100
105
140
185
235

3200

A300

15

TA 450SU235

165 - 235

235

4000

AF 400

10

4800

AF 460

10

6300
6300

AF 580
AF 580

10
10

E 500DU
TA450SU310
E 500DU
TA450SU400
E 500DU***
E 800DU
TA900SU500

150 - 500
220 - 310
150 - 500
285 - 400
150 - 500
250 - 800
355 - 500

400
310
400
400
500
580
500

7560
7560

AF 750
AF 750

10
10

E 500DU***
E 800DU
TA900SU500

150 - 500
250 - 800
355 - 500

500
630
500

8000

AF 750

10

9600

AF 750

10

E 800DU
TA900SU650
E 800DU
TA900SU650

250 - 800
465 - 650
250 - 800
465 - 650

750
650
750
650

MB4450HD2.1af
* : Magnetic only adjustable release.
** : by pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on CT
Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 19/09/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY


440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4450SDHD2.1af
MCCB PR211+AF

Star-delta starters with MCCB


440 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110

Ie [A]
75
90
120
147
177

132

212

160

260

200

320

250

410

290

315

355

448

500

549

Moulded Case
Circuit-Breaker
Type

Contactors

Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor

S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6H630 PR211-I
In630

S6H630 PR211-I
In630

S6H800 PR211-I
In800

S6H800 PR211-I
In800

Type

Current
setting
range

[A]
1150
1400
2000
2400
3000

A95
A95
A145
A145
A145

A95
A95
A145
A145
A145

A50**
A50**
A50**
A95
A95

[mm]
20
20
15
15
15

[mm]
10
10
10
10
20

TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140

[A]
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140

3200

A210

A210

A145

15

15

TA450SU140

95 - 140

4000

A210

A210

A145

15

15

TA450SU185

130 - 185

4800

A210

A210

A185

15

15

TA450SU235

165 - 235

6300

AF400

AF400

A260

10

15

E500DU500

150 - 500

TA450SU310

220 - 310

E500DU500

150 - 500

TA450SU310

220 - 310

E500DU500

150 - 500

TA450SU310

220 - 310

E500DU500

150 - 500

TA450SU400

285 - 400

7560

AF400

8000

AF400

9600

AF580

AF400

AF400

AF580

A260

A260

A260

10

10

10

15

15

15

MB4450SDHD2.1af
* : Magnetic only adjustable release.
** : using mounting kits, use star contactor size same as delta contactor size
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/09/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS + INSUM


440 V - 50 kA - Normal start - up, type : 2
Note : MB4450SDIN2.1af
INSUM PR211+AF

Star-delta starters with MCCB


440 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
75
90
120
147
177
212
260
320
410
448
500
549

Moulded Case
Circuit-Breaker
Type

Contactors

Line
Delta
Star
Safety
Safety
Magnetic
contactor
contactor
contactor
clearance
clearance
tripping
type
type
type**
Line-Delta
Star
current
contactor contactor

S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S4H250 PR211-I In250
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H630 PR211-I In630

[A]
950
1150
1600
1850
2500
3000
4000
4800
6300
6300
6300
7560

A95
A95
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A95
A95
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A30
A40
A50
A75
A95
A110
A110
A185
A210
A260
A260
A260

[mm]
20
20
15
15
15
15
15
15
10
10
10
10

[mm]
10
10
10
10
20
20
20
15
15
15
15
15

MB4450SDIN2.1af
* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 31/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4450SDHD2.1af
MCCB PR212/MP+AF

Star-delta starters with MCCB


440 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Type

I1 range**

S4H160 PR212-MP In100


S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630

50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630

Pe [kW] Ie [A]
45
55
75
90
110
132
160
200
250
290
315
355

75
90
120
147
177
212
260
320
410
448
500
549

[A]

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
800
960
1280
1600
1920
2240
2880
3780
4410
5040
5040
5670

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor

A50
A50
A50
A95
A95
A145
A145
A185
A260
A260
A260
A260

[mm]

[mm]

15
15
15
15
15
15
15
10
10
10
10
10

10
10
10
20
20
15
15
15
15
15
15
15

MP4450SDHD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTER
500 V - 50 kA - Normal start - up, type : 2
Note : MB5050SD2.1af
mccb+AF contactor

Star-delta starters with MCCB


500 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483

Moulded Case
Circuit-Breaker
Type

Contactors

Thermal Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type* Line-Delta
Star
contactor contactor

S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In400
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630

[A]
145
210
325
415
540
540
680
800
900
1050
1400
1700
2000
2500
3000
4000
4800
5040
6300
6300

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A145
A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400

A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A145
A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400

A9
A9
A9
A 12
A 16
A 16
A 26
A 30
A30
A30
A50
A75
A95
A95
A110
A145
A185
A210
A210
A260

[mm]
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
10
10
10

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20
20
15
15
15
15
15

Type

TA25DU11**
TA25DU14**
TA42DU19**
TA75DU25**
TA75DU42**
TA75DU42**
TA75DU52**
TA75DU63**
TA80DU52
TA80DU52
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU150
TA200DU175
TA450DU235
E500DU500
E500DU500
E500DU500

MB5050SD2.1af
*: Using mounting kits, use Star-contactor size same as Delta-contactor size.
**: Connect the TOL between the MCCB and the Line-Delta node.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Current
setting
range
[A]
7.5-11
10-14
13-19
18-25
29-42
29-42
36-52
45-63
36 - 52
36 - 52
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
150 - 500
150 - 500
150 - 500

DIRECT-ON-LINE STARTERS
500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP5050HD2-1af
MCCB+PR212MP+AF-cont

Direct-on-line starters with MCCB


500 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
45
56
67
82
110
132
158
192
230
279
335
395
415
451

Type

I1 range

Current
setting
PR 212 / MP
release I3 *

S4L160 PR212-MP In100


S4L160 PR212-MP In100
S4L160 PR212-MP In100
S4L160 PR212-MP In100
S4L160 PR212-MP In160
S4L160 PR212-MP In160
S4L250 PR212-MP In200
S5L400 PR212-MP In320
S5L400 PR212-MP In320
S5L400 PR212-MP In320
S6L800 PR212-MP In630
S6L800 PR212-MP In630
S6L800 PR212-MP In630
S6L800 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630

[A]
600
600
700
800
1280
1440
1800
2240
2560
2880
3780
4410
4410
5040

Contactor
Type

A145
A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF460
AF580

Group

Safety
Max.
clearance Current

[mm]
15
15
15
15
15
15
15
15
15
10
10
10
10
10

Imax [A]
100
100
100
100
145
145
170
210
240
320
400
460
460
580

MP5050HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** : A300 in case of Normal Starter.

NORMAL and HEAVY-DUTY START


For smaller motor powers, please refer to MMS tables or MCCB / MCB tables
Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS


500 V - 50 kA - Normal start - up, type : 2
Note : MB5050NS2.1af
MCCB+AF-contactor

Direct-on-line starters with MCCB


500 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case CircuitBreaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
O.88
1.2
1.5
2.2
2.8

2.2
3
4
5.5
7.5
11
15

4
5.2
6.9
9.1
12.2
17.5
23

18,5
22
30
37
45
55

29
34
45
56
67
82

75
90
110
132
160
200
250
290

110
132
158
192
230
279
335
394

315

355

440

483

Type

Magnetic
tripping
current

Contactor
Type

Safety
clearance

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630

[A]
21
21
26
42
42
42
65
84
110
145
210
325
415
415
540
540
680
800
1050
1250
1250
1700
2050
2400
3000
3840
4800
5040

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A50
A63
A75
A145
A145
A145
A145
A145
A185
A210
A260
A300
AF 400

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
10

TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA75DU25
TA75DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU63
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU150
TA200DU175
TA 450DU235
TA 450DU310
TA 450DU310
E 500DU

[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500

Imax [A]
1
1.4
1.8
2.4
3.1
3.2
5
6.5
8.5
11
14
19
25
32
42
42
52
63
80
90
110
135
145
170
210
240
280
400

S6L630 PR211-I In630

6300

AF 580

10

E 500DU**

150 - 500

500

S6L630 PR211-I In630

6300

AF 580

10

E 800DU

250 - 800

580

S6L630 PR211-I In630

7560

AF 580

10

E 500DU**

150 - 500

500

S6L630 PR211-I In630

7560

AF 580

10

E 800DU

250 - 800

580

S6L630 PR211-I In630

7560

AF 580

10

E 500DU**

150 - 500

500

S6L630 PR211-I In630

7560

AF 580

10

E 800DU

250 - 800

580

MB5050NS2.1af
* : Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


500 V - 50 kA - Normal start - up, type : 2
Note : MB5050NSIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


500 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
O.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483

Type

Magnetic
tripping
current
[A]
21
21
26
42
42
65
84
110
145
210
325
415
540
540
680
800
1050
1250
1700
2050
2400
3000
3840
4800
5040
6300
7560
7560

S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A50
A50
A50
A63
A63
A63
A75
A145
A145
A145
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
10
10
10
10

Imax [A]
1.6
1.6
2
3.2
3.2
5
6.5
8.5
11
16
25
32
42
42
52
63
125
125
145
145
170
210
240
280
400
580
580
580

* : Magnetic only adjustable release MB5050NSIN2.1af


Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB5050HDIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


500 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
O.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483

Type

Magnetic
tripping
current
[A]
21
21
26
42
42
65
84
110
145
210
325
415
540
540
680
800
1050
1250
1700
2050
2400
3000
3840
4800
5040
6300
7560
7560

S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630

Contactor
Type

A9
A9
A16
A26
A26
A26
A26
A30
A30
A50
A50
A50
A63
A63
A63
A75
A145
A145
A145
A185
A210
A260
A300
AF400
AF460
AF750
AF750
AF750

Group

Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
10
10
10
10
10

Imax [A]
1.6
1.6
2
3.2
3.2
5
6.5
8.5
11
16
25
32
42
42
52
63
125
125
145
170
200
240
280
400
460
630
630
630

* : Magnetic only adjustable release. MB5050HDIN2.1af


Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


500 V - 50 kA - Normal start - up, type : 2
Note : MP5050SD2.1af
PR212/MP+AF contactors

Star-delta starters with MCCB


500 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
67
82
110
132
158
192
230
279
335
394
440
483

Type

I1 range

S4L160 PR212-MP In100


S4L160 PR212-MP In100
S4L160 PR212-MP In160
S4L160 PR212-MP In160
S4L250 PR212-MP In200
S5L400 PR212-MP In320
S5L400 PR212-MP In320
S5L400 PR212-MP In320
S6L800 PR212-MP In630
S6L800 PR212-MP In630
S6L800 PR212-MP In630
S6L800 PR212-MP In630

[A]
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
700
800
1120
1280
1600
1920
2240
2560
3780
3780
4410
4410

A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A30
A30
A50
A75
A95
A95
A110
A145
A185
A210
A210
A260

[mm]
15
15
15
15
15
15
15
15
10
10
10
10

[mm]
10
10
10
10
20
20
20
15
15
15
15
15

MP5050SD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DOL STARTERS
500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB5050HD2.1af
Isomax+AF+EOL

Direct-on-line starters with MCCB


500 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5

Ie [A]
O.88
1.2
1.5
2.2
2.8

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290

4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394

315

355

440

483

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

Contactor
Type

Thermal Overload
Relay

Safety
clearance

Type

Group

Current
Max.
setting range Current

S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630

[A]
21
21
26
42
42
42
65
84
110
145
210
325
415
540
540
680
800
1050
1250
1700
2050
2400
3000
3840
4800
5040

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A145
A145
A145
A185
A210
A260
A300
AF 400
AF 460

[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
10
10

TA25DU1.0**
TA25DU1.4**
TA25DU1.8**
TA25DU2.4**
TA25DU3.1**
TA25DU4**
TA25DU5**
TA25DU6.5**
TA25DU8.5**
TA25DU11**
TA 450SU60 (4)
TA 450SU60 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60 (1)
TA 450SU60 (1)
TA 450SU80 (1)
TA 450SU105 (1)
TA 450SU140 (1)
TA 450SU185 (1)
TA 450SU185 (1)
TA 450SU235 (1)
TA 450SU310 (1)
E 500DU
E 500DU

[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 15
13 - 20
20 - 30
27.5 - 40
27.5 - 40
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
165 - 235
220 - 310
150 - 500
150 - 500

Imax [A]
1
1.4
1.8
2.4
3.1
3.2
5
6.5
8.5
11
15
20
30
40
40
52
60
80
105
140
170
185
235
280
400
460

S6L630 PR211-I In630

6300

AF 750

10

E 500DU***

150 - 500

500

S6L630 PR211-I In630

6300

AF 750

10

E 800DU

250 - 800

630

S6L630 PR211-I In630

7560

AF 750

10

E 500DU***

150 - 500

500

S6L630 PR211-I In630

7560

AF 750

10

E 800DU

250 - 800

630

S6L630 PR211-I In630

7560

AF 750

10

E 500DU***

150 - 500

500

S6L630 PR211-I In630

7560

AF 750

10

E 800DU

250 - 800

630

MB5050HD2.1af
* : Magnetic only adjustable release.
** : provide by-pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on the CT
Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY


500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB5050SDHD2.1af
MCCB PR211+AF

Star-delta starters with MCCB


500 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case
Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
67
82
110
132
158
192
230
279
335
394
440
483

Type

Contactors

Thermal Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor

S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630

[A]
1150
1250
1800
2200
2400
3000
3840
4000
5040
6300
6300
7560

A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400

A50
A50
A50
A75
A95
A95
A145
A145
A185
A210
A260
A260

[mm]
15
15
15
15
15
15
15
15
10
10
10
10

[mm]
10
10
10
10
20
20
15
15
15
15
15
15

Type

TA450SU80**
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
E500DU
E500DU
E500DU
E500DU

Current
setting
range
[A]
27.5 - 40
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
150 - 500
150 - 500
150 - 500
150 - 500

MB5050SDHD2.1af
* : Magnetic only adjustable release.
** : 2 cable turns on CT.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP5050SDHD2.1af
MCCB PR212/MP+AF

Star-delta starters with MCCB


500 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355

Ie [A]
67
82
110
132
158
192
230
279
335
394
440
483

Type

I1 range**

S4L160 PR212-MP In100


S4L160 PR212-MP In100
S4L160 PR212-MP In160
S4L160 PR212-MP In160
S4L250 PR212-MP In200
S5L400 PR212-MP In320
S5L400 PR212-MP In320
S5L400 PR212-MP In320
S6L800 PR212-MP In630
S6L800 PR212-MP In630
S6L800 PR212-MP In630
S6L800 PR212-MP In630

[A]
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
700
900
1280
1440
1800
2240
2560
2880
3780
4410
4410
5040

A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400

Delta
contactor
type

A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A50
A50
A50
A75
A95
A95
A145
A145
A185
A210
A260
A260

[mm]
15
15
15
15
15
15
15
15
10
10
10
10

[mm]
10
10
10
10
20
20
15
15
15
15
15
15

MP5050SDHD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DOL STARTERS
690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB6950HD2.1af
Isomax+AF+EOL

Direct-on-line starters with MCCB


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor
Rated Rated
Output Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167

200

202

250

242

290

301

315

313

355

370

400

420

450

470

500

500

Moulded Case
Circuit-Breaker
Type
Magnetic
tripping
current
S2X80 In1
S2X80 In1
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In4
S2X80 In5
S2X80 In6.5
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I
In250
S4X250 PR211-I
In250
S6X400 PR211-I
In320
S6X400 PR211-I
In400
S6X400 PR211-I
In400
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630

Contactor
Type

Safety
clearance

Overload Relay
Type

[A]
13
13
21
26
33
52
65
84
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500

A9
A9
A9
A9
A16
A26
A26
A30
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A185
A210
A210

[mm]
10
10
10
10
10
10
10
10
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15

TA25DU0.63***
TA25DU1***
TA25DU1.4***
TA25DU1.8***
TA25DU2.4***
TA25DU4*** (a)
TA25DU5*** (a)
TA25DU6.5***(a)
TA 450SU60
TA 450SU60
TA 450SU60
TA 450SU60
TA 450SU80
TA 450SU60
TA 450SU80
TA 450SU60
TA 450SU60
TA 450SU80
TA 450SU105
TA 450SU105
TA 450SU140
TA 450SU185
TA 450SU185

3000

A260

15

3840

AF 400

10

4800

AF 400

10

4800

AF 460

10

6300
6300

AF 580
AF 580

10
10

6300
6300

AF 580
AF 580

7560
7560

7560

N of
Current
Max.
primary setting range Current
turns
on CT

7**
5**
4**
3**
3
2
2
1
1
1
1
1
1
1
1

[A]
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6.5
5.7 - 8.6
8 - 12
10 - 15
13 - 20
18 - 27
20 - 30
27.5 - 40
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
130 - 185
130 - 185

Imax [A]
0.63
1
1.4
1.8
2.4
4
5
6.5
8.6
12
15
20
27
30
40
60
60
80
105
105
140
185
185

TA 450SU235

165 - 235

220

E 500DU
TA450SU310
E 500DU
TA450SU310
E 500DU
TA450SU400
E 500DU (X)
E 800DU
TA450SU400

150 - 500
220 - 310
150 - 500
220 - 310
150 - 500
285 - 400
150 - 500
250 - 800
285 - 400

320
310
350
310
400
400
500
500
400

10
10

E 500DU (X)
E 800DU
TA900SU500

1
1

150 - 500
250 - 800
355 - 500

500
500
500

AF 750
AF 750

10
10

E 500DU (X)
E 800DU
TA900SU500

1
1

150 - 500
250 - 800
355 - 500

500
630
500

AF 750

10

E 800DU
TA900SU650

250 - 800
465 - 650

630
650

1
1
1
1

MB6950HD2.1af
* : Magnetic only adjustable release.
** : Cable cross section 4.0 mm2
*** : Use by-pass contactor during motor start-up : A9 < 1.1kW / A16 < 4kW
(X) Mounting kit between Contactor and Relay is not available.
(a) : type 1 coordination, type 2 by the relevant MCB (MO325) table

Home

Fuse

MCCB

Group

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


690 V - 50 kA - Normal start - up, type : 2
Note : MB6950NSIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


690 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

Ie [A]
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500

Type

Magnetic
tripping
current
[A]
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
4800
4800
6300
6300
7560
7560

S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630

Contactor
Type

A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A145
A185
A185
A210
AF400
AF400
AF400
AF580
AF580
AF580
AF750

Group

Safety
Max.
clearance Current
[mm]
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10

Imax [A]
25
25
25
25
50
50
50
100
100
100
120
120
120
170
170
210
320
350
350
500
500
500
630

* : Magnetic only adjustable release.


**: From 0.37kW up to 15kW, the cable section must be equal to 4.0 mm2. MB6950NSIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS + INSUM


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB6950HDIN2.1af
MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

Ie [A]
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500

Type

Magnetic
tripping
current
[A]
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
4800
4800
6300
6300
7560
7560

S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630

Contactor
Type

A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A185
A210
A210
A260
AF400
AF400
AF460
AF580
AF580
AF750
AF750

Group

Safety
Max.
clearance Current
[mm]
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10

Imax [A]
25
25
25
25
50
50
50
100
100
100
120
120
170
200
210
220
320
350
400
500
500
630
630

* : Magnetic only adjustable release.


**: From 0.37kW up to 15kW, the cable section must be equal to 4.0 mm2. MB6950HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR DELTA STARTERS


690 V - 50 kA - Normal start - up, type : 2
Note : MB6950SD2.1af
mccb+AF cont

Star-delta starters with MCCB


690 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200

Ie [A]
6.7**
8.8**
13**
18**
21
25
33
41
49
60
80
95
115
139
167
202

250

242

290

301

315

313

355

370

400

420

450

470

500

500

Moulded Case
Circuit-Breaker
Type

Contactors

Overload
Relay

Magnetic
Line
Delta
Star
tripping contactor contactor contactor
current
type
type
type***

S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I
In250
S6X400 PR211-I
In400
S6X400 PR211-I
In400
S6X400 PR211-I
In400
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630

KORC
type

turns
on
CT

[A]
110
140
200
280
320
380
500
620
620
750
1000
1200
1440
1750
2100
2550

A 95
A 95
A 95
A 95
A 145
A 145
A 145
A 145
A145
A145
A145
A145
A145
A145
A145
A185

A 95
A 95
A 95
A 95
A 145
A 145
A 145
A 145
A145
A145
A145
A145
A145
A145
A145
A185

A 26
A 26
A 26
A 26
A 30
A 30
A 30
A 30
A30
A40
A50
A75
A75
A95
A110
A110

4L
185R/4
185R/4
185R/4
185R/4
185R/4
185R/4
185R/4
185R/4
-

n
13
10
7
7
6
6
6
4
-

3200

AF400

AF400

A145

4000

AF400

AF400

A145

4000

AF400

AF400

A185

5040

AF400

AF400

A210

6300

AF460

AF460

A210

6300

AF460

AF460

A260

6300

AF460

AF460

A260

TOL
type

Current
setting
range

TA25DU2.4****
TA25DU2.4****
TA25DU2.4****
TA25DU3.1****
TA25DU3.1****
TA25DU4****
TA25DU5****
TA25DU4****
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA200DU110
TA200DU110
TA200DU135

[A]
6-8.5
7.9-11.1
11.2-15.9
15.2-20.5
17.7-23.9
21.6-30.8
27-38.5
32.4-46.3
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
80 - 110
80 - 110
100 - 135

E500DU500
TA200DU150
E500DU500
TA200DU200
E500DU500
TA200DU200
E500DU500
TA450DU235
E500DU500
TA450DU310
E500DU500
TA450DU310
E500DU500
TA450DU310

150 - 500
110 - 150
150 - 500
150 - 200
150 - 500
150 - 200
150 - 500
165 - 235
150 - 500
220 - 310
150 - 500
220 - 310
150 - 500
220 - 310

MB6950SD2.1af
* : Magnetic only adjustable release.
** : Cable section equal to 4 mm2
***: Using mounting kits, use Star-contactor size same as Delta-contactor size.
****: Connect the TOL between the MCCB and the Line-Delta node.
Created 29/06/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/09/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT ON LINE STARTERS


690 V - 50 kA - Normal start - up, type : 2
Note : MB6950NS2.1af
MCCB+AF-contactor

Direct-on-line starters with MCCB


690 V, 50 kA, Normal start - up, type 2
Motor
Rated Rated
Output Current

Moulded Case CircuitBreaker


Type

Contactor

Magnetic
tripping
current

Type

Safety
clearance

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250

Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242

S2X80 In1
S2X80 In1
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In4
S2X80 In5
S2X80 In6.5
S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320

[A]
13
13
21
26
33
52
65
84
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840

A9
A9
A9
A9
A16
A26
A26
A30
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A145
A185
A185
A210
AF 400

[mm]
10
10
10
10
10
10
10
10
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
10

290

301

S6X400 PR211-I In400

4800

AF 400

10

315

313

S6X400 PR211-I In400

4800

AF 400

10

355

370

S6X630 PR211-I In630


S6X630 PR211-I In630

6300
6300

AF 580
AF 580

10
10

400

420

S6X630 PR211-I In630


S6X630 PR211-I In630

6300
6300

AF 580
AF 580

10
10

450

470

S6X630 PR211-I In630


S6X630 PR211-I In630

7560
7560

AF 580
AF 580

10
10

500

500

S6X630 PR211-I In630

7560

AF 750

10

KORC
(Current
transfo)
Type
N of
primary
turns
on CT

4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L235R/4

13***
10***
7***
7***
6
6
6
4
4
3
2
2
2

Overload
Relay
Type

TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU4 **
TA25DU5 **
TA25DU6.5 **
TA25DU2.4
TA25DU2.4
TA25DU2.4
TA25DU3.1
TA25DU3.1
TA25DU4
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA 450DU185
TA 450DU185
TA 450DU235
E 500DU
TA450DU310
E 500DU
TA450DU310
E 500DU
TA450DU400
E 500DU (X)
E 800DU
TA450DU400
E 500DU (X)
E 800DU
TA900DU500
E 500DU (X)
E 800DU
TA900DU500
E 800DU
TA900DU650

Group

Current
setting
range

Max.
Current

[A]
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1,7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6,5
6 - 8.5
7.9 - 11.1
11.2 - 15.9
15.2 - 20.5
17.7 - 23.9
21.6 - 30.8
27 - 38.5
32.4 - 46.3
40.5 - 57.8
54 - 77.1
64.8 - 92.5
81 - 115.6
103 - 147
130 - 185
130 - 185
165 - 235
150 - 500
220 - 310
150 - 500
220 - 310
150 - 500
285 - 400
150 - 500
250 - 800
285 - 400
150 - 500
250 - 800
355 - 500
150 - 500
250 - 800
355 - 500
250 - 800
465 - 650

Imax [A]
0.63
1
1.4
1.8
2.4
4
5
6.5
8.5
11.1
15.9
20.5
23.9
30.8
38.5
46.3
57.8
77.1
92.5
115.6
120
170
170
210
320
310
350
310
350
400
500
500
400
500
500
500
500
500
500
630
650

MB6950NS2.1af
* : Magnetic only adjustable release.
** : Type 1 coordination, type 2 by the relevant MCB (MO325) table
***: Cable section equal to 4.0 mm2.
(X) Mounting kit between Contactor and Relay is not available.

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 20/09/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

DIRECT-ON-LINE STARTERS
690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP6950HD2-1af
MCCB+PR212MP+AF-cont

Direct-on-line starters with MCCB


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated
Output

Rated
Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500

Type

I1 range

Current
setting
PR 212 / MP
release I3 *

S4X250 PR212-MP In100


S4X250 PR212-MP In100
S4X250 PR212-MP In100
S4X250 PR212-MP In160
S4X250 PR212-MP In160
S4X250 PR212-MP In160
S4X250 PR212-MP In200
S6X400 PR212-MP In320
S6X400 PR212-MP In320
S6X400 PR212-MP In320
S6X630 PR212-MP In400
S6X630 PR212-MP In400
S6X630 PR212-MP In630
S6X630 PR212-MP In630
S6X630 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
200 - 400
200 - 400
315 - 630
315 - 630
315 - 630

[A]
600
600
900
1120
1280
1440
1800
2240
2560
2880
3200
3600
4410
5040
5040

Contactor
Type

Group

Safety
Max.
clearance Current

A145
A145
A145
A145
A145
A185
A185
AF400
AF400
AF400
AF400
AF460
AF580
AF580
AF750

[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10

Imax [A]
100
100
100
120
120
160
170
320
320
320
350
400
500
500
650

MP6950HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
X To be defined by further tests.

NORMAL and HEAVY-DUTY START


For smaller motor powers, please refer to MMS tables or MCCB / MCB tables
Created 07/05/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


690 V - 50 kA - Normal start - up, type : 2
Note : MP6950SD2.1af
PR212/MP+AF contactor

Star-delta starters with MCCB


690V, 50 kA, Normal start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500

Type

I1 range

S4X250 PR212-MP In100


S4X250 PR212-MP In100
S4X250 PR212-MP In100
S4X250 PR212-MP In160
S4X250 PR212-MP In160
S4X250 PR212-MP In160
S4X250 PR212-MP In200
S6X400 PR212-MP In320
S6X400 PR212-MP In320
S6X630 PR212-MP In400
S6X630 PR212-MP In400
S6X630 PR212-MP In630
S6X630 PR212-MP In630
S6X630 PR212-MP In630
S6X630 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
200 - 400
200 - 400
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
600
600
800
960
1120
1280
1600
1920
2240
2800
3200
3780
4410
4410
5040

A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460

Delta
contactor
type

A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460

Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A30
A40
A50
A75
A75
A95
A110
A110
A145
A145
A185
A210
A210
A260
A260

[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10

[mm]
10
10
10
10
10
20
20
20
15
15
15
15
15
15
15

MP6950SD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up
In case of smaller motor powers, please refer to MMS tables.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB6950SDHD2.1af
MCCB PR211+AF

Star-delta starters with MCCB


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case
Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250

290

315

355

400

450

500

Ie [A]
49
60
80
95
115
139
167
202
242

301

313

370

420

470

500

Type

Contactors

Overload
Relay

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor

S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320

S6X400 PR211-I In400

S6X400 PR211-I In400

S6X630 PR211-I In630

S6X630 PR211-I In630

S6X630 PR211-I In630

S6X630 PR211-I In630

[A]
750
1000
1250
1500
1800
2200
2500
3000
3840

A145
A145
A145
A145
A145
A145
A145
A185
AF400

4800

AF400

4800

AF400

6300

AF400

6300

AF460

7560

AF580

7560

AF580

A145
A145
A145
A145
A145
A145
A145
A185
AF400

AF400

AF400

AF400

AF460

AF580

AF580

A30
A40
A50
A75
A75
A95
A110
A145
A145

A185

A185

A210

A260

A260

AF400

[mm]
15
15
15
15
15
15
15
15
10

10

10

10

10

10

10

[mm]
10
10
10
10
10
20
20
15
15

15

15

15

15

15

10

MB6950SDHD2.1af
* : Magnetic only adjustable release.
** : 2 cable turns on CT
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Home

Fuse

MCCB

MMS

Softstarters UL Comb.

MCB

Type

Current
setting
range

TA450SU60**
TA450SU80**
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140

[A]
20 - 30
27.5 - 40
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140

E500DU500

150 - 500

TA450SU185

130 - 185

E500DU500

150 - 500

TA450SU185

130 - 185

E500DU500

150 - 500

TA450SU235

165 - 235

E500DU500

150 - 500

TA450SU235

165 - 235

E500DU500

150 - 500

TA450SU310

220 - 310

E800DU500

250 - 800

TA450SU310

220 - 310

E800DU800

250 - 800

TA450SU310

220 - 310

STAR-DELTA STARTERS + INSUM


690 V - 50 kA - Normal start - up, type : 2
Note : MB6950SDIN2.1af
INSUM PR211+AF

Star-delta starters with MCCB


690 V, 50 kA, Normal start - up, type 2
Motor

Moulded Case
Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500

Type

Contactors

Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor

S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630

[A]
620
750
1000
1200
1440
1750
2100
2550
3200
4000
4000
5040
6300
6300
6300

A145
A145
A145
A145
A145
A145
A145
A185
AF400
AF400
AF400
AF400
AF460
AF460
AF460

A145
A145
A145
A145
A145
A145
A145
A185
AF400
AF400
AF400
AF400
AF460
AF460
AF460

A30
A40
A50
A75
A75
A95
A110
A110
A145
A145
A185
A210
A210
A260
A260

[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10

[mm]
10
10
10
10
10
20
20
20
15
15
15
15
15
15
15

MB6950SDIN2.1af
* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 31/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY


690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP6950SDHD2.1af
MCCB PR212/MP+AF

Star-delta starters with MCCB


690 V, 50 kA, Long starting (heavy duty) start - up, type 2
Motor

Moulded Case Circuit-Breaker

Rated Rated
Output Current

Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500

Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500

Type

I1 range**

S4X250 PR212-MP In100


S4X250 PR212-MP In100
S4X250 PR212-MP In100
S4X250 PR212-MP In160
S4X250 PR212-MP In160
S4X250 PR212-MP In160
S4X250 PR212-MP In200
S6X400 PR212-MP In320
S6X400 PR212-MP In320
S6X630 PR212-MP In400
S6X630 PR212-MP In400
S6X630 PR212-MP In630
S6X630 PR212-MP In630
S6X630 PR212-MP In630
S6X630 PR212-MP In630

[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
200 - 400
200 - 400
315 - 630
315 - 630
315 - 630
315 - 630

Contactors

Current
Line
Delta
Star
Safety
Safety
setting
contactor contactor contactor clearance clearance
PR212 /
type
type
type
Line-Delta
Star
MP
contactor contactor
release I3 *
[A]
600
700
900
1120
1280
1440
1800
2240
2560
3200
3200
3780
4410
5040
5040

A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460

A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460

A30
A40
A50
A75
A75
A95
A110
A145
A145
A185
A185
A210
A260
A260
AF400

[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10

[mm]
10
10
10
10
10
20
20
15
15
15
15
15
15
15
10

MP6950SDHD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
In case of smaller motor powers, please refer to MMS tables
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

MMS
Ue
V

Iq
kA

Coor.
type

Starting
type

SCPD
type

Size
kW

Table

Last
Update

400

16

MMS
MMS
MMS
MMS/DLA
MMS
MMS

0.06 ... 7.5


0.06 ... 7.5
0.37 ... 55
0.37 ... 11
0.12 ... 22
0.12 ... 22

22/11/01
22/11/01

50

Normal
Normal
Normal
Normal
Normal
Normal

MM4016NS1.1
MM4016NS2.1

400

1
2
1
2
1
2

04/02/00
04/02/00
23/10/00
23/10/00

100
25
50
100
25
25

1
2
1
2
1
2
2
2
1
2

SD
SD
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal

MMS
MMS
MMS/DLA
MMS
MMS
MMS
MMS
MMS
MMS
MMS

1.1 ... 55
1.1 ... 55
0.37 ... 11
0.06 ... 55
0.06 ... 18.5
0.06 ... 22
0.06 ... 22
0.06 ... 22
0.12 .. 22
0.12 .. 22

50
100

2
2

Normal
Normal

MMS
MMS

0.06 ... 22
0.06 ... 22

MM4050NS1.1
MM4050NS2.1a
MM4050NS1.1K
MM4050NS2.1K
MM4050SD1.1
MM4050SD2.1
MM4050NS1.1a
MM4050NS2.1
MM4000NS2.1
MM4430NS2.1
MM4450NS2.1
MM4400NS2.1
MM5025NS1.1K
MM5025NS2.1K
MM5050NS2.1
MM5000NS2.1

440

500

04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
25/02/00
25/02/00
04/02/00
04/02/00

Glossary
SCPD
NS
SD
MMS

Short Circuit Protection Device


Normal Start
Star Delta
Manual Motor Starter

Prolim
DLA

Current limiter
MS325 + A-Contactors

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 22/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


400 V - 16 kA - Normal start - up, type : 1
Note : MM4016NS1.1
MS116

Manual Motors Starter MS116


400 V, 16 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

MS116-0.25
MS116-0.4
MS116-0.63
MS116-1
MS116-1
MS116-1.6
MS116-1.6
MS116-2.5
MS116-4
MS116-4
MS116-6.3
MS116-10
MS116-10
MS116-16
MS116-16

3.0
4.8
7.56
12
12
19.2
19.2
30
48
48
75.6
120
120
192
192

A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A12
A16

Safety
clearance
[mm]
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 10
6.3 - 10
10 - 16
10 - 16

Imax [A]
0.25
0.4
0.63
1
1
1.6
1.6
2.5
4
4
6.3
10
10
12
16

MM4016NS1.1
Safety perimeter : 40/10 x 15 x 5 means : 40mm above MS xxx, 10mm below the contactor
15mm in front of each component, 5mm on each side
Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 22/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


400 V - 16 kA - Normal start - up, type : 2
Note : MM4016NS2.1
MS116

Manual Motors Starter MS116


400 V, 16 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

MS116-0.25
MS116-0.4
MS116-0.63
MS116-1
MS116-1
MS116-1.6
MS116-1.6
MS116-2.5
MS116-4
MS116-4
MS116-6.3
MS116-10
MS116-10
MS116-16
MS116-16

3.0
4.8
7.56
12
12
19.2
19.2
30
48
48
75.6
120
120
192
192

A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/BB6
A12/B6
A12/B6
A16
A16
A16
**
**

Safety
clearance
[mm]
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 10
6.3 - 10
10 - 16
10 - 16

Imax [A]
0.25
0.4
0.63
1
1
1.6
1.6
2.5
4
4
6.3
10
10
12
16

MM4016NS2.1
Safety perimeter : 40/10 x 15 x 5 means : 40mm above MS xxx, 10mm below the contactor
15mm in front of each component, 5mm on each side
** : under consideration

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 22/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MM4050NS1.1
MS325/495

Manual Motors Starter MS325


400 V, 50 kA, Normal start - up, type 1
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8,5
11.5
15.5

9
11

18.3
22

15
18.5
22
30
37
45
55

30
37
45
60
72
85
98

Type

Magnetic
tripping
current

Contactor

Overload
Release

Type
<br>

Safety
clearance

Type
<br>

Group

Current
Max.
setting range Current

MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5

[A]r>
18.4
18.4
29
48
48
94.5
135
135
187.5

A9
A9
A9
A9
A9
A9
A9
A9
A12

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5

Imax [A]
1.6
1.6
2.5
4
4
6.3
9
9
12

MS325-16

240

A16

25/5x15x5

12.5 - 16

16

MS450-20

240

A16

50/5x15x10

14 - 20

16

MS325-20

300

A26

25/5x15x5

16 - 20

20

MS325-25

375

A26

25/5x15x5

20 - 25

25

MS450-25

300

A26

50/5x15x10

18 - 25

25

MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100

384
480
540
756
900
1080
1200

A30
A40
A50
A63
A75
A95
A110

50/5x15x10
50/5x15x10
50/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10

22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100

30
40
50
60
72
90
100

MM4050NS1.1
Safety perimeter : 25/5x15x5 means : 25mm above MS325, 5mm below the contactor
15mm in front of each component, 5mm on each side

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : MM4050NS2.1
MS325/DLA

Manual Motors Starter MS325


400 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
22

Manual Motor Starter


Type

Magnetic
tripping
current

MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-25

[A]
18.4
18.4
29
50
50
79
112.5
112.5
156
200
300

Contactor
Type

Safety
clearance

DLA9
DLA9
DLA9
DLA9
DLA12
DLA12
DLA26
DLA26
DLA26
DLA26
DLA26

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25

Imax [A]
1.6
1.6
2.5
4
4
6.3
9
9
12.5
16
25

MM4050NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MM4050NS1.1K
S503K

Manual Motor Starter S503-K


400 V, 50 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.44
0.72
0.83
1.12
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

S503-K 0.58
S503-K 0.8
S503-K 1.1
S503-K 1.5
S503-K 2.1
S503-K 2.1
S503-K 3
S503-K 4.2
S503-K 5.8
S503-K 5.8
S503-K 8
S503-K11
S503-K 15
S503-K 20
S503-K 26
S503-K 32
S503-K 37
S503-K 45

7
10
13
18
25
25
36
50
69
69
96
132
180
240
312
384
444
540

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
0.38 - 0.58
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
1.4 - 2.1
2-3
2.8 - 4.2
3.8 - 5.8
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37
38 - 45

Imax [A]
0.55
0.76
1.05
1.45
2.05
2.05
2.9
4
5.55
5.55
7.65
10.5
14.5
19
24.5
30.5
37
45

MM4050NS1.1K
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/10/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : MM4050NS2.1K
S503K

Manual Motor Starter S503-K


400 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.44
0.72
0.83
1.2
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

S503-K 0.58
S503-K 0.8
S503-K 1.1
S503-K 1.5
S503-K 2.1
S503-K 2.1
S503-K 3
S503-K 4.2
S503-K 5.8
S503-K 5.8
S503-K 8
S503-K11
S503-K 15
S503-K 20
S503-K 26
S503-K 32
S503-K 37
S503-K 45

7
10
13
18
25
25
36
50
69
69
96
132
180
240
312
384
444
540

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A16-30-10
A26-30-10
A26-30-10
A26-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
0.38 - 0.58
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
1.4 - 2.1
2-3
2.8 - 4.2
3.8 - 5.8
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37
38 - 45

Imax [A]
0,55
0,76
1,05
1,45
2,05
2,05
2.9
4
5,55
5.55
7.65
10.5
14.5
19
24.5
30.5
37
45

MM4050NS2.1K
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/10/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star Delta Starters


400 V - 50 kA - Normal start - up, type : 1
Note : MM4050SD1.1
MS325/495

MMS Up-stream

Star-Delta starters with Manual Motor Starter


400 V, 50 kA, Normal start - up, type 1
Motor

Manual Motor
Starter

Rated
Output

Rated
Current

Pe [kW]

Ie [A]

1.1

2.8

1.5

3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55

5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
100

Contactor

Thermal Tripping
Setting Range

Group

Type

Magnetic
tripping
current
Irm (A)

K1
Line

K2
Delta

K3
Star

Type

Current
Max.
setting range starting
time

MS325-4.0

48

A9

A9

A9

[A]
2.5 - 4

(s)
15

MS325-6.3
MS325-9.0
MS325-9.0
MS325-12.5
MS325-16
MS325-25
MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100

94.5
135
135
187.5
240
375
384
480
600
756
900
1080
1200

A9
A9
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63

A9
A9
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63

A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40

4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25
22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100

15
15
15
15
15
15
15
15
30
30
30
30
30

MM4050SD1.1
Created 07/04/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 02/05/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Star - Delta Starters


400 V - 50 kA - Normal start - up, type : 2
Note : MM4050SD2.1
MS325/495

MMS Up-stream

Star-Delta starters with Manual Motor Starter


400 V, 50 kA, Normal start - up, type 2
Motor

Manual Motor
Starter

Rated
Output

Rated
Current

Pe [kW]

Ie [A]

1.1

2.8

1.5

3.5

2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55

5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
100

Contactor

Thermal Tripping
Setting Range

Group

Type

Magnetic
tripping
current
Irm (A)

K1
Line

K2
Delta

K3
Star

Type

Current
Max.
setting range starting
time

MS325-4.0

48

A9

A9

A9

[A]
2.5 - 4

(s)
15

MS325-6.3
MS325-9.0
MS325-9.0
MS325-12.5
MS325-16
MS325-25
MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100

94.5
135
135
187.5
240
375
384
480
600
756
900
1080
1200

A12
A26
A26
A26
A26
A26
A30
A40
A50
A63
A95
A95
A110

A12
A26
A26
A26
A26
A26
A30
A40
A50
A63
A95
A95
A110

A9
A12
A12
A12
A12
A12
A26
A26
A30
A40
A75
A75
A95

4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25
22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100

15
15
15
15
15
15
15
30
30
30
30
30
30

MM4050SD2.1
Created 07/04/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 02/05/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MM4050NS1.1
MS325/DLA

Manual Motors Starter MS325


400 V, 50 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
22

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-25

18.4
18.4
29
50
50
79
112.5
112.5
156
200
300

DLA9
DLA9
DLA9
DLA9
DLA9
DLA9
DLA9
DLA9
DLA12
DLA16
DLA26

Safety
clearance
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25

Imax [A]
1.6
1.6
2.5
4
4
6.3
9
9
12
16
25

MM4050NS1.1
Safety perimeter : 25/5x15x5 means : 25mm above MS325, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : MM4050NS2.1
MS325/495

Manual Motors Starter MS325


400 V, 50 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5

Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5

9
11

18.3
22

15
18.5
22
30
37
45
55

30
37
44
60
72
85
98

Contactor
Safety
clearance

Overload
Release
Type

Group

Type

Magnetic
tripping
current
[A]

Type

Current
Max.
setting range Current

MS325-0.25
MS325-0.4
MS325-0.63
MS325-1
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5

2.44
3.9
6.14
11.5
11.5
18.4
18.4
28.7
48
48
94.5
135
135
187.5

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5

Imax [A]
0.25
0.4
0.63
1
1
1.6
1.6
2.5
4
4
6.3
9
9
12.5

MS325-16

240

A26

25/5x15x5

12.5 - 16

16

MS450-20

240

A26

50/5x15x10

14 - 20

16

MS325-20

300

A26

25/5x15x5

16 - 20

20

MS325-25

375

A30

25/5x15x5

20 - 25

25

MS450-25

300

A30

50/5x15x10

18 - 25

25

MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100

384
480
600
756
900
1080
1200

A30
A40
A50
A63
A95
A95
A110

50/5x15x10
50/5x15x10
50/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10

22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100

30
40
50
63
75
90
100

MM4050NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters with current limiter


400 V - 100 kA - Normal start - up, type : 2
Note : MM4000NS2.1
MS325/450

MS 325 & MS 450

Direct-on-line starters with Current limiter


400 V, 100 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15

Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
18.3
22
30

18.5

Type

Protection

Contactor

Magnetic
tripping
current

Limiter
type
Prolim

Type

MS325-0.25
MS325-0.40
MS325-0.63
MS325-1
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-20
MS325-25

[A]
2.44
3.9
6.14
11.5
11.5
18.4
18.4
28.75
48
48
94.5
135
135
187.5
240
300
375

PLM 36-A
PLM 36-A
PLM 36-A
PLM 63-A

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A26
A30

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

MS450-32

384

PLM 63-A

A30

50/5x15x10

S 503 K32

416

PLM 63-A

A30

20

S 503 K37

481

PLM 63-A

A50

20

37

Safety
clearance

Overload
Release
Type

Group

Current
Max.
setting range Current
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
16 - 20
20 - 25

Imax [A]
0.25
0.40
0.63
1
1
1.6
1.6
2.5
4
4
6.3
9
9
12.5
16
20
25

22 - 32

30

23 - 32

30.5

29 - 37

37

MM4000NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 17/08/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line Starters


440 V - 25 kA - Normal start - up, type : 2
Note : MM4430NS2.1
MS325/450

Direct-on-line starters
440 V, 25 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5

Ie [A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31
5.8
7.6
10.3

7.5
9
11
12.5
15

13.5
15.8
19.3
21.9
26.3

Protection

Contactor
Safety
clearance

Overload
Release
Type

Group

Type

Magnetic
tripping
current
[A]

Limiter
type
Prolim

Type

Current
Max.
setting range Current

MS325-0.25
MS325-0.4
MS325-0.4
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-2.5
MS325-4
MS325-6.3
MS325-6.3
MS325-9
MS325-12.5

2.44
3.9
3.9
6.14
11.5
18.4
18.4
28.75
28.75
48
94.5
94.5
135
187.5

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A26
A26

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
0.16 - 0.25
0.25 - 0.4
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
1.6 - 2.5
2.5 - 4
4 - 6.3
4 - 6.3
6.3 - 9
9 - 12.5

Imax [A]
0.25
0.4
0.4
1
1
1.6
1.6
2.5
2.5
4
6.3
6.3
9
12.5

MS325-16
MS325-16
MS325-20
MS325-25

240
240
300
375

A26
A26
A26
A30

25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

12.5 - 16
12.5 - 16
16 - 20
20 - 25

16
16
20
25

S 503K 32

416

A30

35

23 - 32

30.5

MS450-32

384

A30

50/5x15x10

22 - 32

30

S 503K 37
S 503K 37

481
481

A50
A50

35
35

29 - 37
29 - 37

37
37

18.5
22

32
37

MM4430NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line Starters


440 V - 50 kA - Normal start - up, type : 2
Note : MM4450NS2.1
MS325/450

Direct-on-line starters
440 V, 50 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2,2
3
4
5.5

Ie [A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31
5.8
7.6
10.3

7.5
9
11
12.5
15

13.5
15.8
19.3
21.9
26.3

Type

Protection

Contactor
Safety
clearance

Overload
Release
Type

Group

Magnetic
tripping
current

Limiter
type
Prolim

Type

Current
Max.
setting range Current

MS325-0,25
MS325-0.4
MS325-0.4
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-2.5
MS325-4
MS325-6.3
MS325-6.3
MS325-9
MS325-12.5

[A]
2.44
3.9
3.9
6.14
11.5
18.4
18.4
28.75
28.75
48
94.5
94.5
135
187.5

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A26
A26

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
0.16 - 0.25
0.25 - 0.4
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
1.6 - 2.5
2.5 - 4
4 - 6.3
4 - 6.3
6.3 - 9
9 - 12.5

Imax [A]
0.25
0.4
0.4
1
1
1.6
1.6
2.5
2.5
4
6.3
6.3
9
12.5

MS325-16
MS325-16
MS325-20
MS325-25

240
240
300
375

PLM 36-A
PLM 36-A
PLM 36-A
PLM 36-A
PLM 63-A

A26
A26
A26
A30

25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

12.5 - 16
12.5 - 16
16 - 20
20 - 25

16
16
20
25

S 503K 32

416

PLM 63-A

A30

35

23 - 32

30.5

MS450-32

384

PLM 63-A

A30

50/5x15x10

22 - 32

30

18.5

32

S 503K 37

481

PLM 63-A

A50

35

29 - 37

37

22

37

S 503K 37

481

PLM 63-A

A50

35

29 - 37

37

MM4450NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters with current limiter


440 V - 100 kA - Normal start - up, type : 2
Note : MM4400NS2.1
MS325

Direct-on-line starters with current limiter


440 V, 100 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2

Ie [A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31

5.8

7.5

11.3

Type

MS325-0.25
MS325-0.4
MS325-0.4
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-2.5
MS325-4

2.44
3.9
3.9
6.14
11.5
18.4
18.4
28.75
28.75
50

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
0.16 - 0,25
0.25 - 0.4
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
1.6 - 2.5
2.5 - 4

Imax [A]
0.25
0.4
0.4
1
1
1.6
1.6
2.5
2.5
4

MS325-6.3

78.7

PLM 36-A

A26

25/5x15x5

4 - 6.3

6.3

MS325-6.3

78.7

MO325-6.3

A26

25/5x15x5

4 - 6.3

6.3

MS325-6.3

78.7

PLM 36-A

A26

25/5x15x5

4 - 6.3

6.3

MS325-6.3

78.7

MO325-6.3

A26

25/5x15x5

4 - 6.3

6.3

MS325-9

135

PLM 36-A

A26

25/5x15x5

6.3 - 9

MS325-9

135

MO325-9

A26

25/5x15x5

6.3 - 9

MS325-12.5

187.5

PLM 36-A

A26

25/5x15x5

9 - 12.5

12.5

MS325-12.5

187.5

MO325-12.5

A26

25/5x15x5

9 - 12.5

12.5

MS325-16

240

PLM 36-A

A26

25/5x15x5

12.5 - 16

16

MS325-16

240

MO325-16

A26

25/5x15x5

12.5 - 16

16

MS325-16

240

PLM 36-A

A26

25/5x15x5

12.5 - 16

16

MS325-16

240

MO325-16

A26

25/5x15x5

12.5 - 16

16

MS325-20

300

PLM 36-A

A26

25/5x15x5

16 - 20

20

MS325-20

300

MO325-20

A26

25/5x15x5

16 - 20

20

12.5

MS325-25

375

PLM 63-A

A26

25/5x15x5

20 - 25

25

MS325-25

375

MO325-25

A26

25/5x15x5

20 - 25

25

19.3

21.9

Home

Fuse

MCCB

MMS

Softstarters UL Comb.

Type

Group

Limiter
type
Prolim

13.5

Safety
clearance

Overload
Release

Magnetic
tripping
current
[A]

15.8

11

Contactor

Type

7.6

5.5

Protection

MCB

Current
Max.
setting range Current

15

26.3

18.5
22

32
37

S 503K 32

416

PLM 63-A

A30

35

23 - 32

30

MS450-32

384

PLM 63-A

A30

50/5x15x10

22 - 32

30

S 503K 37
S 503K 37

481
481

PLM 63-A
PLM 63-A

A50
A50

35
35

29 - 37
29 - 37

37
37

MM4400NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 30/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
500 V - 25 kA - Normal start - up, type : 1
Note : MM5025NS1.1K
S503K

Manual Motor Starter S503-K


500 V, 25 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33

Manual Motor Starter

Contactor

Type

Current setting
Magnetic release

Type

S503-K0.42
S503-K0.8
S503-K0.8
S503-K1.1
S503-K1.5
S503-K2.1
S503-K3
S503-K3
S503-K4.2
S503-K5.8
S503-K8
S503-K11
S503-K15
S503-K20
S503-K26
S503-K32
S503-K37

5
10
10
13
18
25
36
36
50
69
96
132
180
240
312
384
444

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00

Overload
Release

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35

Type
-

Group

Current
Max.
setting range Current
[A]
0.28 - 0.42
0.53 - 0.8
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
2-3
2-3
2.8 - 4.2
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37

Imax [A]
0.42
0.77
0.77
1.05
1.45
2.05
2.9
2.9
4
5,55
7.65
10.5
14.5
19
24.5
30.5
37

MM5025NS1.1K

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 05/04/2000 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
500 V - 25 kA - Normal start - up, type : 2
Note : MM5025NS2.1K
S503K

Manual Motor Starter S503-K


500 V, 25 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33

Manual Motor Starter

Contactor

Type

Current setting
Magnetic release

Type

S503-K 0.42
S503-K 0.80
S503-K 0.80
S503-K 1.10
S503-K 1.50
S503-K 2.10
S503-K 3.00
S503-K 3.00
S503-K 4.20
S503-K 5.80
S503-K 8.00
S503-K 11.0
S503-K 15.0
S503-K 20.0
S503-K 26.0
S503-K 32.0
S503-K 37.0

5
10
10
13
18
25
36
36
50
69
96
132
180
240
312
384
444

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A26-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00

Overload
Release

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35

Type
-

Group

Current
Max.
setting range Current
[A]
0.28 - 0.42
0.53 - 0.8
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
2-3
2-3
2.8 - 4.2
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37

Imax [A]
0.42
0.77
0.77
1.05
1.45
2.05
2.9
2.9
4
5.55
7.65
10.5
14.5
19
24.5
30.5
37

MM5025NS2.1K

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 05/04/2000 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line Starters
500 V - 50 kA - Normal start - up, type : 2
Note : MM5050NS2.1
MS325/450

Direct-on-line starters
500 V, 50 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
18.5

Ie [A]
0.16
0.24
0.33
0.46
0.59
0.85
1.2
1.48
2.1
2.6
3.8
5.1
6.5
8.9
11.9
13.9
16.7
22.5
28.5

22

Type

Protection

Contactor

Type

Group

Magnetic
tripping
current

Limiter
type
Prolim

Type

MS325-0.25
MS325-0.25
MS325-0.4
MS325-0.63
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-20
MS325-25

[A]
2.44
2.44
3.9
6.14
6.14
11.5
18.4
18.4
28.75
48
48
94.5
135
135
187.5
240
300
375

PLM 36-B
PLM 36-B
PLM 36-B
PLM 36-B
PLM 36-B
PLM 63-B
PLM 63-B

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A26
A26
A30

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
0.16 - 0.25
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.40 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4.0 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
16 - 20
20 - 25

Imax [A]
0.25
0.25
0.4
0.63
0.63
1.6
1.6
1.6
2.5
4
4
6.3
9
9
12.5
16
20
25

S 503K 32

416

PLM 63-B

A30

35

23 - 32

30.5

MS450-32

384

PLM 63-B

A30

50/5x15x10

22 - 32

30

S 503K 37

481

PLM 63-B

A50

35

29 - 37

37

33

Safety
clearance

Overload
Release

Current
Max.
setting range Current

MM5050NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters with current limiter


500 V - 100 kA - Normal start - up, type : 2
Note : MM5000NS2.1
MS325

Direct-on-line starters with current limiter


500 V, 100 kA, Normal start - up, type 2
Motor

Manual Motor Starter

Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5

Ie [A]
0.16
0.24
0.33
0.46
0.59
0.85
1.2
1.48
2.1
2.6

2.2

Type

5.1

7.5

11.9

MS325-0.25
MS325-0.25
MS325-0.4
MS325-0.63
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5

[A]
2.44
2.44
3.9
6.14
6.14
11.5
18.4
18.4
28.75

A9
A9
A9
A9
A9
A9
A9
A9
A9

[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5

[A]
0.16 - 0.25
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5

Imax [A]
0,25
0.25
0.40
0.63
0.63
1.6
1.6
1.6
2.5

MS325-4

50

PLM 36-B

A12

25/5x15x5

2.5 - 4

4.0

MS325-4

50

MO325-4

A12

25/5x15x5

2.5 - 4

4.0

MS325-4

50

PLM 36-B

A12

25/5x15x5

2.5 - 4

4.0

MS325-4

50

MO325-4

A12

25/5x15x5

2.5 - 4

4.0

MS325-6.3

78.7

PLM 36-B

A26

25/5x15x5

4 - 6.3

6.3

MS325-6.3

78.7

MO325-6.3

A26

25/5x15x5

4 - 6.3

6.3

MS325-9

135

PLM 36-B

A26

25/5x15x5

6.3 - 9

9.0

MS325-9

135

MO325-9

A26

25/5x15x5

6.3 - 9

9.0

MS325-9

135

PLM 36-B

A26

25/5x15x5

6.3 - 9

9.0

MS325-9

135

MO325-9

A26

25/5x15x5

6.3 - 9

9.0

MS325-12.5

187.5

PLM 36-B

A26

25/5x15x5

9 - 12.5

12.5

MS325-12.5

187.5

MO325-12.5

A26

25/5x15x5

9 - 12.5

12.5

MS325-16

240

PLM 36-B

A26

25/5x15x5

12.5 - 16

16

MS325-16

240

MO325-16

A26

25/5x15x5

12.5 - 16

16

MS325-20

300

PLM 36-B

A26

25/5x15x5

16 - 20

20

MS325-20

300

MO325-20

A26

25/5x15x5

16 - 20

20

13.9

11

16.7

Home

Fuse

MCCB

MMS

Softstarters UL Comb.

Type

Group

Type

8.9

Safety
clearance

Overload
Release

Limiter
type
Prolim

6.5

5.5

Contactor

Magnetic
tripping
current

3.8

Protection

MCB

Current
Max.
setting range Current

15

18.5

22.5

28.5

22

33

MS325-25

375

PLM 63-B

A26

25/5x15x5

20 - 25

25

MS325-25

375

MO325-25

A26

25/5x15x5

20 - 25

25

S 503K 32

416

PLM 63-B

A30

35

23 - 32

30,5

MS450-32

384

PLM 63-B

A30

50/5x15x10

22 - 32

30

S 503K 37

481

PLM 63-B

A50

35

29 - 37

37

MM5000NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 30/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS
Ue
V

Iq
kA

Coor.
type

Starting
type

SCPD
type

Size
kW

400

50

400

65

415

65

440
500

50
50
65

1
1
2

690

50

Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal

MMS
MMS
MCCB
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
MCCB
MCCB
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
MCCB

0.06 ... 50
15 ... 50
0.37 ... 400
1.5 ... 160
1.5 ... 55
30 ... 450
25 ... 400
7.5 ... 132
7.5 ... 110
1.5 ... 75
1.5 .... 55
30 ... 500
30 ... 400
7.5 ... 132
8 ... 110
0.37 ... 400
0.37 ... 355
2.2 ... 90
2.2 .. 75
45 ... 550
45 ... 500
11 ... 160
11 ... 160
0.25 ... 600

Table
MMPS4050LIN40-1
MMPD4050LIN40-1
MBPS4050LIN40-1
PSS4065LINE40
PSS4065LINE50
PSD4065LINE40
PSD4065LINE50
PSS4065DELTA40
PSS4065DELTA50
PSS4165LINE40
PSS4165LINE50
PSD4165LINE40
PSD4165LINE50
PSS4165DELTA40
PSS4165DELTA50
MBPS4450LIN40-1
MBPS5050LIN40-1
PSS5065LINE40
PSS5065LINE50
PSD5065LINE40
PSD5065LINE50
PSS5065DELTA40
PSS5065DELTA50
MBPS6950LIN40-1

Last
Update
13/11/01
13/11/01
13/11/01
14/11/01
20/11/00
14/11/01
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
13/11/01
13/11/01
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
13/11/01

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH MMS


400 V - 50 kA - Normal start - up, type : 1
Note : MMPS4050LIN40-1
SoftMMS

SOFTSTARTERS PS S 03 ... 105


400 V, 50 kA (up to 40C) IEC 947-4-2, type 1, AC-53a,b
Starter and MMS in line
Softstarter
Manual Motor Starter

Motor
Rated
Output

Max
current

[kW]

1.5
2.5
4

[A]
0.16
0.25
0.4
0.63
1
1.6
2.5
3.5
6.3
9

5.5

10
12

7.5

16

17

12.5

18
25

0.06

0.55

15
18,5
22
25
30
37
45
51

26
27
30
32
37
44
45
50
55
60
72
75
85
96
100

Type

Type

PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500

MS225-0.16
MS225-0.25
MS225-0.4
MS225-0.63
MS225-1
MS225-1.6
MS225-2.5
MS225-4
MS225-6.3
MS225-9
MS325-10
MS325-10
MS325-12.5
MS325-12.5
MS325-16
MS325-16
MS325-20
MS325-20
MS325-20
MS325-25
MS325-25
MS450-32
MS450-32
MS450-32
MS450-40
MS450-40
MS450-50
MS450-50
MS450-50
MS495-63
MS495-63
MS495-75
MS495-75
MS495-90
MS495-100
MS495-100

Current setting
range
[A]
0.1 - 0.16
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1.6 - 2.5
2.5 - 4
4 - 6.3
6.3 - 9
6 - 10
6 10
9 12.5
9 - 12.5
12.5 - 16
12.5 - 16
16 20
16 - 20
16 20
18 25
18 - 25
22 32
22 32
22 32
28 - 40
28 - 40
40 - 50
40 - 50
40 - 50
45 - 63
45 - 63
57 - 75
57 - 75
70 - 90
80-100
80-100

Line
By-pass
contactor contactor
Type

Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A12
A16
A16
A16
A16
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A63
A63
A75
A75
A95
A95
A110

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A9
A9
A9
Integrated
A9
Integrated
A9
Integrated
A9
A9
Integrated
A12
A12
A16
A26
A26
A26
A26
A30
A30
A40
A50
A50
A50
A50
A50

MMPS4050LIN40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH MMS


400 V - 50 kA - Normal start - up, type : 1
Note : MMPD4050LINE40-1
SoftPSDMMS

SOFTSTARTERS PS D 75 ... 110


400 V, 50 kA (up to 40C) IEC 947-4-2, type 1, AC-53a,b
Starter and MMS in line
Softstarter
Manual Motor Starter

Motor
Rated
Output

Max
current

[kW]
15

[A]
30
32
37
40
45
50
60
65
72
75
85
90
96
100

18.5
20
22
25
30
37
45

51

Type

Type

PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110

MS450-40
MS450-40
MS450-40
MS450-40
MS450-45
MS450-50
MS495-63
MS495-75
MS495-75
MS495-75
MS495-100
MS495-100
MS495-100
MS495-100

Current setting
range
[A]
28 - 40
28 - 40
28 - 40
28 - 40
36 - 45
36 - 50
45 - 63
57 - 75
57 - 75
57 - 75
70 - 90
70 - 90
80 - 100
80 - 100

Line
By-pass
contactor contactor
Type

Type

A30
A30
A40
A50
A50
A50
A63
A63
A75
A75
A95
A95
A95
A110

A16
A26
A26
A26
A26
A40
A40
A50
A50
A50
A50
A50
A50
A50

MMPD4050LINE40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH MCCB


400 V - 50 kA - Normal start - up, type : 1
Note : MBPS4050LIN40-1
SoftMCCB

SOFTSTARTERS PS S 03 ... PS D840


400 V, 50 kA (up to 40C) IEC 947-4-2, type 1, AC-53b
Starter and MCCB in line
Softstarter
Moulded Case
Overload
Circuit-Breaker
Relay

Motor
Rated
Output

Max
current

[kW]
0.37
0.55

[A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210
260
300
400
500
580
580
750

1.1
1.5
2.2
4
5
6.5
9
12.5
15
20
25
40
45
55
75
90
140
160
200
257
315
400

Type

Type

PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 25-400B
PS S 25-400B
PS S 25-400B
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 300/515-500
PS S 300/515-500
PS D 470
PS D 570
PS D 720
PS D 720
PS D 840

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800

Magnetic
tripping
current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
7560
9600
9600

Type

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
E 500DU
E 500DU**
E 800DU
E 800DU
E 800DU

Line
By-pass
contactor contactor

Setting
range
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800

Type

Type

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF750

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A26
A26
A30
A50
A50
A50
A63
A95
A145
A145
A185
A210
A260
A300
AF400
AF400
AF580

* magnetic only adjustable release


** mounting kit between contactor and relay is not available
MBPS4050LIN40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


400 V - 65 kA - Normal start - up, type : 2
Note : PSS4065LINE40
PSS40/40

SOFTSTARTERS PS S 03 ... 142


400 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]
1.5
2.2
2.5
4
5
5.5
8

Max
current
[A]
3.5
5
6.5
8.5
11
12
17

12,5

18
25

15
18,5
22
25
30
37
40
45
51
55
59
75
80
90

100
132
140
147
160

Type

PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 250/430-500
PS S 250/430-500
PS S 300/515-500
PS S 300/515-500
PS S 300/515-500

26
27
30
37
44
45
50
55
60
65
72
75
85
96
100
105
110
115
125
142
145
160
175
185
210
250
260
275
300

Rated
current
[A]
16
20
25
32
40
40
50
50
50
80
50
80
80
80
125
160
160
160
200
200
250
250
250
250
315
315
315
315
450
450
450
500
500
500
630
630
700
700
700
700

Bussmann
ref.

Type

Type

170M1359
170M1360
170M1361
170M1362
170M1363
170M1363
170M1364
170M1364
170M1364
170M1366
170M1364
170M1366
170M1366
170M1366
170M1368
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80

TA25DU4.0
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU150
TA200DU175
TA200DU175
TA200DU175
TA200DU200
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310

Setting
range
[A]
2.8 - 4.0
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
110 - 150
130 - 175
130 - 175
130 - 175
150 - 200
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310

Type

Type

A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A30
A30
A40
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A110
A110
A110
A145
A145
A145
A145
A185
A185
A185
A210
A260
A260
A300
A300

Built-in
Built-in
Built-in
Built-in
Built-in
Built-in
A9
Built-in
A9
A9
Built-in
A12
A12
A16
A26
A26
A26
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
A110
A145
A145
A145
A145
A185
A185
A210

PSS4065LINE40
Created 13/10/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


400 V - 65 kA - Normal start - up, type : 2
Note : PSS4065LINE50
PSS40/50

SOFTSTARTERS PS S 03 ... 142


400 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]
1.5
5.5

Max
current
[A]
3.5
9
12

7.5

11
12.5

15

18.5
22
25
30
37

45

55

Type

PS S 03-400B
PS S 18/30-500
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

15,5
16
17
22
25
26
27
30
32
34
37
40
44
46
50
55
60
65
72
75
78
85
95
96
110
110
130

Rated
current
[A]
16
50
50
40
50
50
50
80
80
50
80
80
125
125
125
160
160
160
160
200
200
250
250
315
315
315
400
400
400
450
450
450

Bussmann
ref.

Type

Type

170M1359
170M1364
170M1364
170M1363
170M1364
170M1364
170M1364
170M1366
170M1366
170M1364
170M1366
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU4.0
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU32
TA42DU32
TA42DU42
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135

Setting
range
[A]
2.8 - 4.0
7.5 - 11
10 - 14
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
22 - 32
22 - 32
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135

Type

Type

A9
A9
A12
A12
A16
A16
A16
A26
A26
A26
A26
A30
A30
A30
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A95
A110
A110
A145

Built-in
A9
A9
Built-in
A9
A9
Built-in
A9
A12
Built-in
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A63
A75
A75
A95
A95

PSS4065LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


400 V - 65 kA - Normal start - up, type : 2
Note : PSD4065LINE40
PSD40/40

SOFTSTARTERS PS D 75 ... 840

Motor
Rated
Output
[kW]
30
37
45
51
55
59
75
90
110
132
140
147
160
180
200
250
257
295
315
355
400
450

Max
current
[A]
60
65
75
96
100
110
115
125
145
175
185
210
250
260
275
300
305
350
370
400
460
470
500
570
580
600
700
720
750
800

400 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b


Starter and fuses in line
Softstarter Semi-conductor Switch Fuse
Overload
fuses
Relay
Type

PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 175
PS D 210
PS D 210
PS D 250
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840

Rated
current
[A]
200
250
250
315
315
315
400
400
400
450
500
500
630
700
700
700
900
900
900
1250
1250
1250
1500
1500
1800
1800
1800
1800
1800
1800

Bussmann
ref.

Type

Type

170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3021
170M3021
170M4016
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
1)
1)

TA75DU63
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU150
TA200DU175
TA200DU200
TA200DU200
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
E500DU
E500DU
E500DU
E500DU
E500DU
E800DU
E800DU
E800DU
E800DU
E800DU
E800DU
E800DU
E800DU
T900DU850

Setting
range
[A]
45 - 63
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
110 - 150
130 - 175
150 - 200
150 - 200
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
610 - 850

Line
By-pass
contactorcontactor
Type

Type

A63
A63
A75
A95
A110
A110
A145
A145
A145
A185
A185
A210
A260
A260
A300
A300
AF400
AF400
AF400
AF400
AF460
AF580
AF580
AF580
AF580
AF750
AF750
AF750
AF750
IOR1000

A40
A50
A50
A50
A50
A63
A63
A75
A95
A145
A145
A145
A145
A185
A185
A210
A210
A210
A260
A260
A300
A300
A300
AF400
AF400
AF400
AF460
AF580
AF580
AF580

1) Use Bussmann fuseholder 170H 3004


PSD4065LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


400 V - 65 kA - Normal start - up, type : 2
Note : PSD4065LINE50
PSD40/50

SOFTSTARTERS PS D 75 ... 840


400 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]
25
30

37
45

55

75

90

110
132

160

200

250

315
355

400

Max
current
[A]
50
55
60
65
69
72
75
85
95
96
101
105
110
133
135
140
145
161
170
185
193
205
230
245
250
260
276
295
300
305
340
350
370
400
432
460
470
524
550
580
636
650
662
700
710
720

Type

PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
PS D 840

Rated
current
[A]
250
250
250
250
250
315
315
315
315
315
315
400
400
400
450
450
450
450
500
500
500
630
630
700
700
700
700
900
900
900
900
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
1800
1800
1800

Bussmann
ref.

Type

Type

170M1371
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80

TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA80DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU150
TA200DU150
TA200DU150
TA200DU150
TA200DU175
TA200DU175
TA200DU200
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU400
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
T900DU850

Setting
range
[A]
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 80
65 - 80
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
110 - 150
110 - 150
110 - 150
110 - 150
130 - 175
130 - 175
150 - 200
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 500
285 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
610 - 850

Type

Type

A50
A53
A63
A63
A75
A75
A75
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
A185
A185
A185
A210
A210
A260
A260
A260
A260
A300
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
EH700
EH800
EH800

A30
A30
A40
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
A95
A110
A110
A145
A145
A145
A145
A185
A185
A210
A210
A210
A260
A260
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700

PSD4065LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


400 V - 65 kA - Normal start - up, type : 2
Note : PSS4065DELTA40
PSS40/40DEL

SOFTSTARTERS PS S 18 ... 142


400 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter inside delta and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor
inside
inside
delta
delta

Motor

Rated
Output
[kW]
7.5
11
15
18.5

22
25

30

37

45

55

75

90

110
132

Max
current
[A]
15
20
22
29
30
37
40
43
44
46
50
51
55
60
63
64
72
76
77
85
86
94
103
105
112
124
129
140
147
165
170
173
181
189
198
205
215
245

Type

PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

Rated
current
[A]
50
50
50
50
50
80
80
80
80
80
80
80
125
125
125
125
160
160
160
160
200
200
200
200
250
250
315
315
315
400
400
400
400
450
450
450
450
450

Bussmann
ref.

Type

Type

170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150

Setting
range
[A]
7.5 - 11
10 - 14
10 - 14
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
110 - 150

Type

Type

A9
A12
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A40
A50
A50
A50
A50
A50
A63
A63
A63
A63
A75
A75
A95
A95
A95
A110
A110
A110
A110
A145
A145
A145
A145

A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95

PSS4065DELTA40
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


400 V - 65 kA - Normal start - up, type : 2
Note : PSS4065DELTA50
PSS40/50DEL

SOFTSTARTERS PS S 18 ... 142


400 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter inside delta and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor
inside
inside
delta
delta

Motor

Rated
Output
[kW]
7.5
11
15
18.5

25
30

37
45

55

75

90

110

Max
current
[A]
15
20
22
29
30
37
43
44
46
47
50
55
60
63
68
70
72
78
85
86
94
103
105
112
114
129
135
140
146
163
165
166
170
181
189
205
225

Type

PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

Rated
current
[A]
50
50
50
80
80
80
80
80
80
80
125
125
160
160
160
160
160
160
200
200
200
250
250
250
250
315
315
400
400
400
400
400
450
450
450
450
450

Bussmann
ref.

Type

Type

170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135

Setting
range
[A]
7.5 - 11
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135

Type

Type

A9
A12
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A63
A75
A75
A95
A95
A95
A95
A95
A95
A110
A110
A110
A145
A145

A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A63
A75
A75
A75
A75
A95
A95
A95

PSS4065DELTA50
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


415 V - 65 kA - Normal start - up, type : 2
Note : PSS4165LINE40
PSS41/40

SOFTSTARTERS PS S 03 ... 142


415 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]

Max
current
[A]
3.5
12

7.5

Type

PS S 03-400B
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

14
17
18

11

15

18.5
22

25
30

37

45
55

75

21
26
27
28
30
32
35
37
40
44
45
47
50
55
60
65
66
72
75
80
85
96
100
105
110
115
125
135
142

Rated
current
[A]
16
40
40
50
50
50
50
50
80
80
80
80
80
125
125
125
160
160
160
160
160
200
200
250
250
250
315
315
315
400
400
400
450
450
450
450
450

Bussmann
ref.

Type

Type

170M1359
170M1364
170M1363
170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU4.0
TA25DU14
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU32
TA42DU42
TA42DU42
TA42DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150

Setting
range
[A]
2.8 - 4.0
10 - 14
10 - 14
10 - 14
13 - 19
13 - 19
13 - 19
13 - 19
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
22 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
110 - 150

Type

Type

A9
A12
A12
A16
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145

Built-in
A9
Built-in
A9
A9
Built-in
A9
Built-in
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95

PSS4165LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


415 V - 65 kA - Normal start - up, type : 2
Note : PSS4165LINE50
PSS41/50

SOFTSTARTERS PS S 03 ... 142


415 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]

Max
current
[A]
3.5
9
12

7.5

11
12.5

15

18.5
22
25
30

37

45

55

Type

PS S 03-400B
PS S 18/30-500
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

14
16
17
21
22
23
25
26
27
28
30
32
34
35
37
40
45
47
50
55
60
65
66
72
78
80
85
95
96
105
110
130

Rated
current
[A]
16
50
50
40
50
50
50
80
80
80
80
50
80
80
125
125
125
125
160
160
160
160
200
200
200
250
250
315
315
315
400
400
400
400
450
450
450

Bussmann
ref.

Type

Type

170M1359
170M1364
170M1364
170M1363
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1364
170M1366
170M1366
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU4.0
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU32
TA42DU42
TA75DU42
TA75DU42
TA42DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135

Setting
range
[A]
2.8 - 4.0
7.5 - 11
10 - 14
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
22 - 32
29 - 42
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135

Type

Type

A9
A9
A12
A12
A16
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A95
A95
A110
A110
A145

Built-in
A9
A9
Built-in
A9
A9
Built-in
A9
A9
A12
A12
Built-in
A16
A16
A26
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A75
A75
A95
A95

PSS4165LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


415 V - 65 kA - Normal start - up, type : 2
Note : PSD4165LINE40
PSD41/40

SOFTSTARTERS PS D 75 ... 840


415 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]

37
45
55

75

90

110
132

160
200

250

315

400

450
500

Max
current
[A]
60
65
66
72
80
96
100
110
115
125
135
145
160
165
175
185
200
210
242
250
260
275
285
300
340
350
370
400
425
450
470
535
550
570
650
700
720
740
800
830
840

Type

PSD 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS S 145
PS S 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
PS D 840
PS D 840

Rated
current
[A]
250
250
250
250
315
315
315
315
400
400
400
400
450
450
450
500
500
500
630
630
700
700
700
700
900
900
900
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
1800
1800

Bussmann
ref.

Type

Type

170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80

TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU150
TA200DU150
TA200DU175
TA200DU200
TA200DU200
TA200DU200
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU400
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
T900DU850
T900DU850
T900DU850
T900DU850

Setting
range
[A]
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
100 - 135
100 - 135
110 - 150
110 - 150
130 - 175
150 - 200
150 - 200
150 - 200
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
610 - 850
610 - 850
610 - 850
610 - 850

Type

Type

A63
A63
A75
A75
A95
A95
A110
A110
A145
A145
A145
A145
A185
A185
A185
A185
A210
A210
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH800
IOR1000
IOR1000
IOR1000
IOR1000

A40
A50
A50
A50
A50
A50
A50
A63
A63
A75
A95
A95
A110
A145
A145
A145
A145
A145
A185
A185
A185
A210
A210
A210
A260
A260
A260
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700

PSD4165LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


415 V - 65 kA - Normal start - up, type : 2
Note : PSD4165LINE50
PSD41/50

SOFTSTARTERS PS D 75 ... 840


415 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]

37
45
55

75

90

110
132

160
200

250

315
355

Max
current
[A]
60
65
66
72
80
96
105
110
133
135
145
161
165
185
193
200
230
242
250
260
276
280
300
340
350
400
425
432
470
524
535
550
580
650
662
700
720

Type

PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840

Rated
current
[A]
250
250
250
315
315
315
400
400
400
450
450
450
500
500
500
630
630
700
700
700
700
900
900
900
1250
1250
1250
1250
1500
1500
1800
1800
1800
1800
1800
1800
1800

Bussmann
ref.

Type

Type

170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80

TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU150
TA200DU150
TA200DU150
TA200DU150
TA200DU200
TA200DU200
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850

Setting
range
[A]
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
110 - 150
110 - 150
110 - 150
110 - 150
150 - 200
150 - 200
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850

Type

Type

A63
A63
A75
A75
A95
A95
A110
A110
A145
A145
A145
A185
A185
A185
A210
A210
A260
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
EH800

A40
A50
A50
A50
A50
A75
A75
A95
A95
A95
A110
A145
A145
A145
A145
A145
A185
A210
A210
A210
A260
A260
A260
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700

PSD4165LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


415 V - 65 kA - Normal start - up, type : 2
Note : PSS4165DELTA40
PSS41/40DEL

SOFTSTARTERS PS S 18 ... 142


415 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter inside delta and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor
inside
inside
delta
delta

Motor

Rated
Output
[kW]

15
18.5
22

25
30

37

45

55

75
90
100

110
132

Max
current
[A]
15
20
28
29
35
40
43
46
47
51
55
63
64
66
76
77
80
85
86
94
96
103
105
112
124
135
147
165
173
181
189
198
200
215
242
245

Type

PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

Rated
current
[A]
50
50
50
80
80
80
125
125
125
125
125
125
125
160
160
160
160
160
160
200
200
200
250
250
250
315
315
400
400
400
450
450
450
450
450
450

Bussmann
ref.
170M364
170M1364
170M1364
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
170M3020

Type

Type

OS 160RD0380
TA25DU11
OS 160RD0380
TA25DU14
OS 160RD0380
TA25DU19
OS 160RD0380
TA25DU19
OS 160RD0380
TA25DU25
OS 160RD0380
TA25DU25
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA42DU32
OS 160RD0380
TA75DU32
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU80
OS 160RD0380
TA75DU80
OS 160RD0380
TA110DU90
OS 160RD0380
TA110DU90
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA200DU135
OESA 250R03D80 TA200DU135
OESA 250R03D80 TA200DU135
OESA 250R03D80 TA200DU1505
OESA 250R03D80 TA200DU1505

Setting
range
[A]
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
100 - 150
100 - 150

Type

Type

A9
A12
A16
A16
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A63
A63
A75
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
A145

A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95

PSS4165DELTA40
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


415 V - 65 kA - Normal start - up, type : 2
Note : PSS4165DELTA50
PSS41/50DEL

SOFTSTARTERS PS S 18 ... 142


415 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter inside delta and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor
inside
inside
delta
delta

Motor

Rated
Output
[kW]
8
11
15
18.5
22

30
37

45

55

75

90
100
110

Max
current
[A]
15
20
21
28
29
35
37
40
43
44
46
47
55
63
66
68
70
78
80
86
94
96
103
112
114
124
135
146
163
165
166
181
189
200
225

Type

PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

Rated
current
[A]
50
50
50
50
80
80
80
80
80
80
80
80
80
125
125
160
160
160
200
200
200
250
250
250
250
315
315
400
400
400
400
450
450
450
450

Bussmann
ref.

Type

Type

170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135

Setting
range
[A]
7.5 - 11
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135

Type

Type

A9
A12
A16
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A63
A75
A75
A95
A95
A95
A95
A95
A110
A110
A145
A145

A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
A95

PSS4165DELTA50
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH MCCB


440 V - 50 kA - Normal start - up, type : 1
Note : MBPS4450LIN40-1
SoftMCCB

SOFTSTARTERS PS S 03 ... PS D840


440 V, 50 kA (up to 40C) IEC 947-4-2, type 1, AC-53b
Starter and MCCB in line
Softstarter
Moulded Case
Overload
Circuit-Breaker
Relay

Motor
Rated
Output

Max
current

[kW]
0.37
0.55

[A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210
260
300
400
500
580
750

1.1
1.5
2.2
4
5
6.5
9
12.5
15
20
25
40
45
55
75
90
140
160
200
257
315
400

Type

Type

PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 25-400B
PS S 25-400B
PS S 25-400B
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 300/515-500
PS S 300/515-500
PS D 470
PS D 570
PS D 720
PS D 840

S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800

Magnetic
tripping
current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
9600
9600

Type

TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
E 500DU
E 500DU**
E 800DU
E 800DU

Line
By-pass
contactor contactor

Setting
range
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
250 - 800
250 - 800

Type

Type

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF750

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A26
A26
A30
A50
A50
A50
A63
A95
A145
A145
A185
A210
A260
A300
AF400
AF580

* magnetic only adjustable release


** mounting kit between contactor and relay is not available
MBPS4450LIN40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH MCCB


500 V - 50 kA - Normal start - up, type : 1
Note : MBPS5050LIN40-1
SoftMCCB

SOFTSTARTERS PS S 03 ... PS D840


500 V, 50 kA (up to 40C) IEC 947-4-2, type 1, AC-53b
Starter and MCCB in line
Softstarter
Moulded Case
Overload
Circuit-Breaker
Relay

Motor
Rated
Output

Max
current

[kW]
0.37

[A]
1
1.4
1.8
2.4
3.1
3.2
5
6.5
8.5
11
14
19
25
32
42
42
52
63
80
90
110
135
145
170
210
240
280
400
500
500
580

1.1
1.5

4
5
6.5
9
12.5
20

40
55
75
90
100
147
160
200
355
355

Type

Type

PS S 03-480B
PS S 03-480B
PS S 03-480B
PS S 03-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 25-480B
PS S 25-480B
PS S 25-480B
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 72/124-500
PS S 72/124-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 250/430-500
PS S 300/515-500
PS D 470
PS D 570
PS D 570
PS D 720

S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630

Magnetic
tripping
current
[A]
21
21
26
42
42
42
65
84
110
145
210
325
415
415
540
540
680
800
1050
1250
1250
1700
2050
2400
3000
3840
4800
5040
7560
7560
7560

Type

TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA75DU25
TA75DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU63
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU150
TA200DU175
TA 450DU235
TA 450DU310
TA 450DU310
E 500DU
E 500DU**
E 500DU**
E 800DU

Line
By-pass
contactor contactor

Setting
range
[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
250 - 800

Type

Type

A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A50
A63
A75
A145
A145
A145
A145
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580

Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A26
A26
A26
A30
A50
A50
A50
A63
A95
A95
A145
A146
A147
A210
A260
A300
A300
AF400

* magnetic only adjustable release


** mounting kit between contactor and relay is not available
MBPS5050LIN40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


500 V - 65 kA - Normal start - up, type : 2
Note : PSS5065LINE40
PSS50/40

SOFTSTARTERS PS S 03 ... 142


500 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]
5.5
7.5

Max
current
[A]
3.5
9
12

Type

PS S 03-480B
PS S 12-480B
PS S 18/30-500
PS S 12-480B
PS S 18/30-500
PS S 25-480B
PS S 18/30-500
PS S 18/30-500
PS S 25-480B
PS S 30/52-500
PS S 25-480B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60105-500
PS S 60105-500
PS S 60105-500
PS S 72124-500
PS S 72124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

14
11
15

18.5
22
25
30

37

45
55

75

90

17
18
22
23
25
26
27
28
30
33
37
38
44
45
50
54
55
60
65
72
79
80
85
100
105
106
115
125
128
142

Rated
current
[A]
16
40
40
40
50
50
50
50
50
80
50
80
80
80
80
125
125
160
160
160
160
200
200
200
250
250
315
315
315
400
400
400
450
450
450
450

Bussmann
ref.

Type

Type

170M1359
170M1363
170M1364
170M1363
170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1364
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU4.0
TA25DU14
TA25DU14
TA25DU14
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU150
TA200DU150

Setting
range
[A]
2.8 - 4.0
10 - 14
10 - 14
10 - 14
10 - 14
10 - 14
13 - 19
13 - 19
18 - 25
24 - 32
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
100 - 135
100 - 135
100 - 135
100 - 135
110 - 150
110 - 150

Type

Type

A9
A9
A12
A12
A16
A16
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A110
A110
A145
A145
A145
A145
A145
A145

Built-in
Built-in
A9
Built-in
A9
Built-in
A9
A9
Built-in
A9
Built-in
A12
A12
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95

PSS5065LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


500 V - 65 kA - Normal start - up, type : 2
Note : PSS5065LINE50
PSS50/50

SOFTSTARTERS PS S 03 ... 142


500 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]
2.2
5.5
7.5

Max
current
[A]
3.5
9
12
14

Type

PS S 03-480B
PS S 12-480B
PS S 12-480B
PS S 18/30-500
PS S 25-480B
PS S 18/30-500
PS S 30/52-500
PS S 25-480B
PS S 30/52-500
PS S 30/52-500
PS S 25-480B
PS S 30/52-500
PS S 37/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

16
22
15

18.5
22
25
30

37
45

55

75

23
25
27
28
33
34
38
40
44
45
46
54
55
65
66
78
79
80
85
95
96
100
105
106
130

Rated
current
[A]
16
40
40
50
50
50
80
50
80
80
50
80
80
125
125
160
160
160
160
160
200
200
250
250
315
400
400
400
400
400
450
450
450
450

Bussmann
ref.

Type

Type

170M1359
170M1363
170M1363
170M1364
170M1364
170M1364
170M1366
170M1364
170M1366
170M1366
170M1364
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1372
170M3019
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU4.0
TA25DU11
TA25DU14
TA25DU14
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU150

Setting
range
[A]
2.8 - 4.0
7.5 - 11
10 - 14
10 - 14
10 - 14
13 - 19
18 - 25
18 - 25
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
110 - 150

Type

Type

A9
A9
A12
A16
A16
A26
A26
A26
A30
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
A95
A95
A110
A110
A110
A110
A145
A145
A145

Built-in
Built-in
Built-in
A9
Built-in
A9
A9
Built-in
A12
A12
Built-in
A16
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A50
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95

PSS5065LINE50
Created 16/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


500 V - 65 kA - Normal start - up, type : 2
Note : PSD5065LINE40
PSD50/40

SOFTSTARTERS PS D 75 ... 840


500 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]
45
55

75
90
110

132
160

200

250

315

400

500

Max
current
[A]
65
75
79
80
100
106
110
128
145
156
160
170
175
186
210
220
240
250
275
278
280
300
350
353
370
400
445
450
470
538
550
570
680
700
720
800
840

Type

PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 175
PS D 175
PS D 175
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 250
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840

Rated
current
[A]
250
250
315
315
315
315
315
450
450
450
450
450
450
500
500
630
630
630
700
700
700
700
900
900
900
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800

Bussmann
ref.

Type

Type

170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M1372
170M3020
170M3020
170M3020
170M3020
170M3020
170M3020
170M3021
170M3021
170M4016
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80

TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU175
TA200DU175
TA200DU175
TA200DU175
TA200DU175
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU310
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU810
T900DU810
T900DU810
T900DU850
T900DU850

Setting
range
[A]
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
130 - 175
130 - 175
130 - 175
130 - 175
130 - 175
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
610 - 810
610 - 810
610 - 810
610 - 850
610 - 850

Type

Type

A75
A95
A95
A95
A110
A145
A145
A145
A145
A185
A185
A185
A210
A210
A210
A260
A260
A300
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH800
IOR1000
IOR1000

A50
A50
A50
A50
A50
A63
A63
A95
A95
A110
A110
A145
A145
A145
A145
A145
A185
A185
A210
A210
A210
A210
A210
A260
A260
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700

PSD5065LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


500 V - 65 kA - Normal start - up, type : 2
Note : PSD5065LINE50
PSD50/50

SOFTSTARTERS PS D 75 ... 840


500 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor

Motor
Rated
Output
[kW]

45
55

75
90

110

132

160

200

250

315

400
450

500

Max
current
[A]
55
60
65
69
79
80
85
95
100
101
105
106
128
133
135
145
156
161
170
186
193
210
220
230
240
250
276
278
280
300
340
350
353
370
400
432
445
470
524
538
550
608
650
662
680
700
720

Type

PS D 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
PS D 840

Rated
current
[A]
250
250
250
250
315
315
315
315
315
315
400
400
400
400
450
450
450
450
500
500
500
630
630
630
700
700
700
900
900
900
900
1250
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
1800
1800
1800

Bussmann
ref.

Type

Type

170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4016
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80

TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU150
TA200DU150
TA200DU175
TA200DU175
TA200DU200
TA450DU235
TA450DU235
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU400
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
T900DU850

Setting
range
[A]
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
100 - 135
100 - 135
110 - 150
110 - 150
130 - 175
130 - 175
150 - 200
165 - 235
165 - 235
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
610 - 850

Type

Type

A63
A75
A75
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
A145
A145
A145
A185
A185
A185
A210
A210
A210
A260
A260
A260
A300
A300
A300
A300
EH370
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
EH700
EH800

A30
A40
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
A95
A95
A110
A145
A145
A145
A145
A145
A185
A185
A185
A210
A210
A260
A260
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700

PSD5065LINE50
Created 16/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


500 V - 65 kA - Normal start - up, type : 2
Note : PSS5065DELTA40
PSS50/40DEL

SOFTSTARTERS PS S 18 ... 142


500 V, 65 kA (up to 40C) IEC 947-4-2, type 2, AC-53a,b
Starter inside delta and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor
inside
inside
delta
delta

Motor

Rated
Output
[kW]
11

18.5
22
25
30

37

45

55

75

90

110

132

160

Max
current
[A]
15
17
20
24
28
33
37
38
43
44
46
48
51
54
56
64
65
76
77
79
85
94
103
105
106
112
124
128
137
147
156
172
173
181
186
198
215
220
245

Type

PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

Rated
current
[A]
50
50
50
50
50
80
80
80
80
80
80
80
80
125
125
125
160
160
160
160
160
200
200
200
250
250
250
315
315
315
400
400
400
400
450
450
450
450
450

Bussmann
ref.

Type

Type

170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU11
TA25DU14
TA25DU14
TA25DU14
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA80DU80
TA80DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU150

Setting
range
[A]
7.5 - 11
10 - 14
10 - 14
10 - 14
18 - 25
18 - 25
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
100 - 135
100 - 135
110 - 150

Type

Type

A9
A12
A12
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A75
A75
A95
A95
A95
A110
A110
A110
A110
A145
A145
A145
A145
A145
A145

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95

PSS5065DELTA40
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH FUSES


500 V - 65 kA - Normal start - up, type : 2
Note : PSS5065DELTA50
PSS50/50DEL

SOFTSTARTERS PS S 18 ... 142


500 V, 65 kA (up to 50C) IEC 947-4-2, type 2, AC-53a,b
Starter inside delta and fuses in line
Softstarter Semi-conductor Switch Fuse Thermal Overload
Line
By-pass
fuses
Relay
contactorcontactor
inside
inside
delta
delta

Motor

Rated
Output
[kW]
11
15
18.5
22
25
30

37

45

55

75

90

110

132
160

Max
current
[A]
15
17
20
23
24
28
33
37
38
43
44
46
48
54
56
58
65
68
70
77
78
79
94
96
103
106
112
114
128
135
137
146
156
163
166
172
181
186
220
225

Type

PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500

Rated
current
[A]
50
50
50
80
80
80
80
80
125
125
125
125
125
125
125
125
160
160
160
160
160
200
200
200
250
250
250
250
315
315
400
400
400
400
400
450
450
450
450
450

Bussmann
ref.

Type

Type

170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020

OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80

TA25DU11
TA25DU11
TA25DU14
TA25DU14
TA25DU14
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA75DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150

Setting
range
[A]
7.5-11
7.5-11
10-14
10-14
10-14
18-25
18-25
18-25
18-25
18-25
24-32
24-32
24-32
24-32
29-42
29-42
29-42
29-42
29-42
36-52
36-52
45-63
45-63
45-63
45-63
45-63
60-80
60-80
60-80
60-80
60-80
80-110
80-110
80-110
80-110
80-110
100-135
100-135
100-135
110-150

Type

Type

A9
A12
A12
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A63
A63
A75
A75
A75
A75
A95
A95
A95
A95
A110
A110
A110
A110
A110
A145
A145
A145
A145

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A50
A63
A63
A75
A75
A75
A95
A95
A95

PSS5065DELTA50
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

SOFTSTARTERS WITH MCCB


690 V - 50 kA - Normal start - up, type : 1
Note : MBPS6950LIN40-1
SoftMCCB

SOFTSTARTERS PS S 03 ... PS D840

Motor

Rated
Output

Max
current

[kW]

[A]
0.63
1
1.4
1.8
2.4
4
5
6.5
8.5
11.1
15.9
20.5
23.9
30.8
38.5
46.3
57.8
77.1
92.5
115.6
120
170
170
210
310
310
320
350
400
500
500
500
500
500
500
630
650

0.55
1.5

4
6.5
9
12.5
20
25
40
51

100

160
200

475

600

690 V, 50 kA (up to 40C) IEC 947-4-2, type 1, AC-53b


Starter and MCCB in line
Softstarter
Moulded Case
Overload
KORC
Circuit-Breaker
Relay
Current
Transformer
Type

Type

PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 30/52-690
PS S 30/52-691
PS S 37/64-690
PS S 44/76-690
PS S 50/85-690
PS S 60/105-690
PS S 85/147-690
PS S 105/181-690
PS S 142/245-690
PS S 142/245-690
PS S 175/300-690
PS S 175/300-690
PS S 250/430-690
PS D 370
PS D 370
PS D 370
PS D 370
PS D 470
PS D 570
PS D 570
PS D 570
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720

S2X80 In1
S2X80 In1
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In4
S2X80 In5
S2X80 In6.5
S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630

Magnetic
tripping
current
[A]
13
13
21
26
33
52
65
84
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
4800
3840
4800
6300
6300
7560
6300
7560
6300
7560
7560
7560

Type

TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU4
TA25DU5
TA25DU6.5
TA25DU2.4
TA25DU2.4
TA25DU2.4
TA25DU3.1
TA25DU3.1
TA25DU4
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA 450DU185
TA 450DU185
TA 450DU235
TA450DU310
TA450DU310
E 500DU
E 500DU
TA450DU400
TA900DU500
TA900DU500
E 800DU
E 800DU
E 500DU **
E 500DU **
E 800DU
TA900DU650

Setting
range
[A]
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1,7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6,5
6 - 8.5
7.9 - 11.1
11.2 - 15.9
15.2 - 20.5
17.7 - 23.9
21.6 - 30.8
27 - 38.5
32.4 - 46.3
40.5 - 57.8
54 - 77.1
64.8 - 92.5
81 - 115.6
103 - 147
130 - 185
130 - 185
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
285 - 400
355 - 500
355 - 500
250 - 800
250 - 800
150 - 500
150 - 500
250 - 800
465 - 650

Type

4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L235R/4

Primary
turns
on CT

13***
10***
7***
7***
6
6
6
4
4
3
2
2
2

Line
By-pass
contactorcontactor

Type

Type

A9
A9
A9
A9
A16
A26
A26
A30
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A145
A185
A185
A210
AF400
AF400
AF400
AF400
AF580
AF580
AF580
AF580
AF580
AF580
AF580
AF750
AF750

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A30
A40
A50
A50
A75
A75
A145
A145
A145
A210
A210
A210
A210
A260
A300
A300
A300
A300
A300
A300
AF460
AF460

* magnetic only adjustable release


** mounting kit between contactor and relay is not available
MBPS6950LIN40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

UL Combination Starters acc. to UL 508


Ue
V

Iq
kA

Coor.
type

Starting
type

SCPD
type

hp

Table

Last
Update

240
480

200
200
35
85

1
1
1
1

DOL
DOL
DOL
DOL

J Fuse
J Fuse
MCCB
MCCB

2 ... 100
5 ... 200
5 ... 25
25 ... 200

08-11-00
08-11-00
08-11-00
08-11-00

600

200

DOL

J Fuse

7.5 ... 300

FUL2400NS1.1
FUL4800NS1.1
MB4835NS1.1
MB4885NS1.1
FUL6000NS1.1

08-11-00

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


240 V - 200 kA - start - up, type :
Under Construction :No
On Internet :No
Note : FUL2400NS1.1

Motor

COMBINATION MOTOR CONTROLLERS - TYPE A - Normal start-up


J FUSES - 240V / 200kA
Disconnecting
Fuse
Contactor
Thermal Overload
Minimum
mean
Protection
enclosure

[hp]

type

Amp/Type

type

type

[in.]

2
3
5
10

OESA-CF30J6S
OESA-CF30J6S
OESA-CF30J6S

30J
30J
30J

A9
A12
A16

TA25DU14
TA25DU14
TA25DU19

14 x 12 x 8
14 x 12 x 8
14 x 12 x 8

OESA-CF30J6S

30J

A26

TA25DU32

14 x 12 x 8

OEAS-F60J6A

60J

A26

TA25DU32

14 x 12 x 8

OEAS-F60J6A
OESA-F100JT6A
OESA-F100JT6A
OES200JT6A
OES200JT6A
OES200JT6A
OES200JT6A
OES200JT6A

60J
100J
100J
200J
200J
200J
200J
200J

A30
A40
A50
A63
A75
A95
A110
A145

TA25DU32
TA42DU42
TA75DU63
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA200DU135

14 x 12 x 8
20 x 16 x 8
20 x 16 x 8
20 x 16 x 8
20 x 16 x 8
24 x 20 x 10
24 x 20 x 10
24 x 20 x 10

OES400JT6

250J

A185

TA200DU150

24 x 20 x 10

OES400JT6

300J

A185

TA200DU175

24 x 20 x 10

OES400JT6
OES400JT6
OES600JT6

350J
400J
600J

A210
A260
A300

TA450DU200
TA450DU235
TA450DU310

30 x 30 x 10
30 x 30 x 10
30 x 30 x 10

10
10
20
25
30
30
40
50
60

75
100
100

FUL2400NS1.1
ULFuse

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 08/11/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


480 V - 200 kA - start - up, type :
Under Construction :No
On Internet :No
Note : FUL4800NS1.1

Motor

COMBINATION MOTOR CONTROLLERS - TYPE A - Normal start-up


J FUSES - 480V / 200kA
Disconnecting
Fuse
Contactor
Thermal Overload
Minimum
mean
Protection
enclosure

[hp]

type

Amp/Type

type

type

[in.]

5
7.5
10
20

OESA-CF30J6S
OESA-CF30J6S
OESA-CF30J6S

30J
30J
30J

A9
A12
A16

TA25DU14
TA25DU14
TA25DU19

14 x 12 x 8
14 x 12 x 8
14 x 12 x 8

OESA-CF30J6S

30J

A26

TA25DU32

14 x 12 x 8

OEAS-F60J6A

60J

A26

TA25DU32

14 x 12 x 8

OEAS-F60J6A
OESA-F100JT6A
OESA-F100JT6A

60J
100J
100J

A30
A40
A50

TA25DU32
TA42DU42
TA75DU63

14 x 12 x 8
20 x 16 x 8
20 x 16 x 8

OES200JT6A

200J

A63

TA75DU80

20 x 16 x 8

OES200JT6A

200J

A75

TA75DU80

20 x 16 x 8

OES200JT6A
OES200JT6A
OES200JT6A

200J
200J
200J

A95
A110
A145

TA110DU110
TA110DU110
TA200DU135

24 x 20 x 10
24 x 20 x 10
24 x 20 x 10

OES400JT6

250J

A185

TA200DU150

24 x 20 x 10

OES400JT6

300J

A185

TA200DU175

24 x 20 x 10

OES400JT6
OES400JT6
OES600JT6

350J
400J
600J

A210
A260
A300

TA450DU200
TA450DU235
TA450DU310

30 x 30 x 10
30 x 30 x 10
30 x 30 x 10

25
30
40
60

60
75
100
125

150
200
200

FUL4800NS1.1
ULFuse

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 23/10/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

UL STARTERS
480 V - 35 kA - start - up, type :
Under Construction :No
On Internet :No
Note : MB4835NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE C* - Normal start-up


MCCB - 480V / 35kA
Contactor
Thermal Overload
Minimum
Motor
Disconnecting
mean
Protection
enclosure
[hp]

type

type

type

[in.]

5
7.5
10
20
25

S3L010MW
S3L050MW
S3L050MW
S3L100MW
S3L150MW

A9
A12
A16
A26
A30

TA25DU14
TA25DU14
TA25DU19
TA25DU32
TA42DU32

14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8

* : UL listed Moulded Case Circuit Breaker


MB4835NS1.1
UL/MCCB

Created 06/12/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 06/12/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

UL STARTERS
480 V - 85 kA - start - up, type :
Under Construction :No
On Internet :No
Note : MB4885NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE C* - Normal start-up


MCCB - 480V / 85kA
Contactor
Thermal Overload
Minimum
Motor
Disconnecting
mean
Protection
enclosure
[hp]

type

type

type

[in.]

25
30
40
60

S3L150MW
S3L150MW
S3L150MW
S3L250MW

A30**
A40**
A50

TA42DU42
TA42DU42
TA75DU63

14 x 12 x 8
14 x 12 x 8
14 x 12 x 8

A63

TA75DU80

14 x 12 x 8

A75

TA75DU80

14 x 12 x 8

A110
A145**

TA110DU110
TA200DU135

20 x 16 x 8
24 x 20 x 10

A185

TA200DU150

24 x 20 x 10

A185

TA200DU175

24 x 20 x 10

A210

TA450DU200

30 x 30 x 10

A260

TA450DU235

30 x 30 x 10

A260

TA450DU310

30 x 30 x 10

A300

TA450DU310

30 x 30 x 10

75
100
125

150
200

200

S3L250MW
S4N250MW
S4N250MW

S4N250MW
S5N400MW

S5N400MW

* : UL listed Moulded Case Circuit Breaker


** : 65kA limitation
MB4885NS1.1
UL/MCCB

Created 06/12/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 06/12/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct on line starters


600 V - 200 kA - start - up, type :
Under Construction :No
On Internet :No
Note : FUL6000NS1.1

Motor

COMBINATION MOTOR CONTROLLERS - TYPE A - Normal start-up


J FUSES - 600V / 200kA
Disconnecting
Fuse
Contactor
Thermal Overload
Minimum
mean
Protection
enclosure

[hp]

type

Amp/Type

type

type

[in.]

7.5
10
15
25

OESA-CF30J6S
OESA-CF30J6S
OESA-CF30J6S

30J
30J
30J

A9
A12
A16

TA25DU14
TA25DU14
TA25DU19

14 x 12 x 8
14 x 12 x 8
14 x 12 x 8

OESA-CF30J6S

30J

A26

TA25DU32

14 x 12 x 8

OEAS-F60J6A

60J

A26

TA25DU32

14 x 12 x 8

OEAS-F60J6A
OESA-F100JT6A
OESA-F100JT6A

60J
100J
100J

A30
A40
A50

TA25DU32
TA42DU42
TA75DU63

14 x 12 x 8
20 x 16 x 8
20 x 16 x 8

OES200JT6A

200J

A63

TA75DU80

20 x 16 x 8

OES200JT6A

200J

A75

TA75DU80

20 x 16 x 8

OES200JT6A
OES200JT6A
OES200JT6A

200J
200J
200J

A95
A110
A145

TA110DU110
TA110DU110
TA200DU135

24 x 20 x 10
24 x 20 x 10
24 x 20 x 10

OES400JT6

250J

A185

TA200DU150

24 x 20 x 10

OES400JT6

300J

A185

TA200DU175

24 x 20 x 10

OES400JT6
OES400JT6
OES600JT6

350J
400J
600J

A210
A260
A300

TA450DU200
TA450DU235
TA450DU310

30 x 30 x 10
30 x 30 x 10
30 x 30 x 10

30
40
50
75

75
100
125
150

200
250
300

FUL6000NS1.1
UL Fuse

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 23/10/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

MCB
Ue
V

Iq
kA

Coor.
type

Starting
type

SCPD
type

Overload
mean

Size
kW

400

10

1
2

Normal
Normal

MCB
MCB

TOR
TOR

0.06 ... 22
0.06 ... 22

MC4010NS1.1
MC4010NS2.1

04/02/00
04/02/00

16

1
2

Normal
Normal

MCB
MCB

TOR
TOR

0.06 ... 15
0.06 ... 15

04/02/00
04/02/00

35

1
2

Normal
Normal

MCB
MCB

TOR
TOR

0.06 ... 11
0.06 ... 11

HD

MCB

EOR

0.06 ... 9

1
2
1
2
1
2

Normal
Normal
Normal
Normal
Normal
Normal

MCB
MCB
MCB
MCB
MCB
MCB

TOR
TOR
TOR
TOR
TOR
TOR

0.12 ... 30
0.12 ... 30
0.06 ... 11
0.06 ... 11
0.12 ... 37
0.12 ... 37

MC4016NS1.1
MC4016NS2.1
MC4035NS1.1
MC4035NS2.1
MC4035HD2.1
MC4050NS1.1
MC4050NS2.1

1
2
1
2

Normal
Normal
Normal
Normal

MCB
MCB
MCB
MCB

TOR
TOR
TOR
TOR

0.25 ... 15
0.25 ... 15
0.18 ... 11
0.18 ... 11

MC4000NS1.1
MC4000NS2.1
MC5025NS1.1
MC5025NS2.1
MC5000NS1.1
MC5000NS2.1
MC6900NS1.1
MC6900NS2.1

04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00

50
100
500

25
100

690

100

Table

Last
Update

04/02/00
04/02/00
04/02/00
04/02/00
04/02/00

Glossary
SCPD
HD
NS
SD
MCB

Short Circuit Protection Device


Heavy Duty
Normal Start
Star Delta
Miniature Circuit Breaker

Prolim
TOR
EOR

Current limiter
Thermal Overload Relay
Electronic Overload Relay

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 14/11/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 10 kA - Normal start - up, type : 1
Note : MC4010NS1.1
S273

Direct-on-line starters with S 273-K circuit-breaker


400V, 10 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22

Ie [A]
0.22
0.34
0.44
0.6
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
28.5
37
44

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40
S 283-K50
S283-K63

[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
560
700
882

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A26
A40
A40
A50

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA42DU32
TA42DU42
TA75DU52

[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
35 - 52

Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
30
40
50

MC4010NS1.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-On-Line Starters
400 V - 10 kA - Normal start - up, type : 2
Note : MC4010NS2.1
S273

Direct-on-line starters with S 273/S283-K circuit-breaker


400V, 10 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5

Ie [A]
0.22
0.34
0.44
0.6
0.83
1.12
1.45
1.9
2.6
3.5

2.2
3
4
5.5
7.5
11
15
18.5
22

4.8
6.5
8.5
11.5
15
22
28.5
37
44

Miniature Circuit-Breaker
Type

Magnetic
tripping
current

S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6

S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40
S 283-K50
S283-K63

[A]
12
12
12
19.2
19.2
24
36
36
48
72

96
140
182
224
280
448
560
700
882

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A16

A26
A26
A26
A26
A30
A30
A40
A50
A50

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1

[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1

Imax [A]
0.25
0.4
0.63
0,63
1
1.35
1.75
2.35
2.95

TA25DU4

2.8 - 4

3.75

TA25DU5

3,5 - 5

4.75

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA42DU32
TA42DU42
TA75DU52

4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
35 - 52

6.25
8
10.5
13.5
18.5
24.5
30.5
38.5
50

MC40101NS2.1
Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 16 kA - Normal start - up, type : 1
Note : MC4016NS1.1
S273

Direct-on-line starters with S 273-K circuit-breaker


400 V, 16 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15

Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
28.5

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40

[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
560

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A40
A40

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32

[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13-19
18-25
24-32

Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
30

MC4016NS1.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-On-Line Starters
400 V - 16 kA - Normal start - up, type : 2
Note : MC4016NS2.1
S273

Direct-on-line starters with S 273/S283-K circuit-breaker


400 V, 16 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5

Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5

2.2
3
4
5.5
7.5
11
15

4.8
6.5
8.5
11.5
15
22
28.5

Miniature Circuit-Breaker
Type

Magnetic
tripping
current

S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6

S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40

[A]
12
12
12
19.2
19.2
24
36
36
48
72

96
140
182
224
280
448
560

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A12
A16
A26

A26
A26
A30
A30
A30
A40
A40

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1

[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1

Imax [A]
0.25
0.4
0.63
0,63
1
1.35
1.75
2.35
2.95

TA25DU4

2.8 - 4

3.75

TA25DU5

3,5 - 5

4.75

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32

4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32

6.25
8
10.5
13.5
18.5
24.5
30

MC4016NS2.1
Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 35 kA - Normal start - up, type : 1
Note : MC4035NS1.1
S273

Direct-on-line starters with S 273-K circuit-breaker


400 V, 35 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7,5
11

Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32

[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A40

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25

[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25

Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24

MC4035NS1.1
Created 26/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-On-Line Starters
400 V - 35 kA - Normal start - up, type : 2
Note : MC4035NS2.1
S273

Direct-on-line starters with S 273/S283-K circuit-breaker


400 V, 35 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5

Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5

2.2
3
4
5.5
7,5
11

4.8
6.5
8.5
11.5
15
22

Miniature Circuit-Breaker
Type

Magnetic
tripping
current

S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6

S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32

[A]
12
12
12
19.2
19.2
24
36
36
48
72

96
140
182
224
280
448

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A16
A26
A26

A26
A26
A30
A30
A30
A40

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15

15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1

[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1

Imax [A]
0.25
0.4
0.63
0,63
1
1.35
1.75
2.35
2.95

TA25DU4

2.8 - 4

3.75

TA25DU5

3,5 - 5

4.75

TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25

4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25

6.25
8
10.5
13.5
18.5
24

MC4035NS2.1
Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters, heavy duty class 20


400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MC4035HD2.1
MO325

Direct-on-line starters with MO 325 circuit-breaker, class 20 heavy-duty


400 V, 35 kA, long starting (heavy duty), type2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7,5
9

Ie [A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
18.3

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

MO325-0.25
MO325-0.4
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-4
MO325-4
MO325-6.3
MO325-9
MO325-16
MO325-20
MO325-25
S503X-AG0074-32

[A]
2.44
3.9
6.14
11.5
11.5
16
16
27.5
40
40
67.7
112.5
200
250
312.5
352

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A30

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10

Overload relay
Type

E16DU0.32 (10)
E16DU1.0 (10)
E16DU1.0 (10)
E16DU1.0 (10)
E16DU1.0 (10)
E16DU2.7 (20)
E16DU2.7 (20)
E16DU2.7 (20)
E16DU6.3 (20)
E16DU6.3 (20)
E16DU6.3 (20)
E16DU18.9 (20)
E16DU18.9 (20)
E16DU18.9 (20)
E16DU18.9 (20)
E16DU18.9 (20)

Group
starter

Current Separate Max.


setting range mounting Current
[A]
0.1 - 0.32
0.3 - 1
0.3 - 1
0.3 - 1
0.3 - 1
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9

AB16
AB16
AB16
AB16
AB16

Imax [A]
0.25
0.4
0.63
0.95
0.95
1.45
1.45
2.2
3.5
3.5
5.4
7.3
10.5
13
16
18.9

MC4035HD2.1
Created 19/08/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Tmax
start.
(s)
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MC4050NS1.1KM
S503KM

Miniature Circuit Breaker S503-KM


400 V, 50 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22
30

Ie [A]
0.44
0.72
0.83
1.2
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44
60

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 2.5
S503-KM 2.5
S503-KM 4.0
S503-KM 6.0
S503-KM 6.0
S503-KM 6.0
S503-KM 9.0
S503-KM 20
S503-KM 20
S503-KM 20
S503-KM 32
S503-KM 32
S503-KM 52
S503-KM 63
S503-KM 75

16
16
16
16
25
25
45
55
55
55
100
200
200
200
400
400
580
800
840

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00
A63-30-00

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35

Thermal Overload
Relay
Type

TA25DU0.63
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63

Group

Current
Max.
setting range Current
[A]
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63

Imax [A]
0.63
1
1
1.4
1.8
2.4
3.1
4
5
6
8.5
9
12
16
25
32
40
50
63

MC4050NS1.1KM
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on line starters


400 V - 50 kA - Normal start - up, type : 2
Note : MC4050NS2.1KM
S503KM

Miniature Circuit Breaker S503-KM


400 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22
30

Ie [A]
0.44
0.72
0.83
1.2
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44
60

Manual Motor Starter

Contactor

Type

Magnetic
tripping
current
[A]

Type

S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM2.5
S503-KM2.5
S503-KM4
S503-KM6
S503-KM6
S503-KM6
S503-KM9
S503-KM20
S503-KM20
S503-KM20
S503-KM32
S503-KM32
S503-KM52
S503-KM63
S503-KM75

16
16
16
16
25
25
45
55
55
55
100
200
200
200
400
400
580
800
840

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A16-30-10
A26-30-10
A26-30-10
A26-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00
A63-30-00

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35

Thermal Overload
Relay
Type

TA25DU0.63
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63

Group

Current
Max.
setting range Current
[A]
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63

Imax [A]
0.5
0.8
1
1.4
1.4
2.2
3.1
4
5
6.5
8.5
11
14
19
25
32
42
52
63

MC4050NS2.1KM
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 1
Note : MC4000NS1.1
MO325

Direct-on-line starters with MO 325 circuit-breaker


400 V, 100 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

MO325-0.25
MO325-0.4
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4.0
MO325-6.3
MO325-9.0
MO325-12.5
MO325-16
MO325-20
MO325-25

[A]
2.44
3.9
6.14
11.5
11.5
16
16
27.5
27.5
40
67.7
112.5
156
200
250
312.5

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25

[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25

Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24

MC4000NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 2
Note : MC4000NS2.1
MO325

Direct-on-line starters with MO 325 circuit-breaker


400 V, 100 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11

Ie [A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22

Moulded Case CircuitBreaker


Type

Magnetic
tripping
current

MO325-0.25
MO325-0.4
MO325-0.63
MO325-1.0
MO325-1.0
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4.0
MO325-6.3
MO325-9.0
MO325-12.5
MO325-16
MO325-20
MO325-25

[A]
2.44
3.9
6.14
11.5
11.5
16
16
27.5
27.5
40
67.7
112.5
156
200
250
312.5

Contactor
Type

A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A26

Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

Thermal Overload
Relay
Type

Group

Current
Max.
setting range Current

TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU1.0
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25

[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1.0 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25

Imax [A
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24

MC4000NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

500 V - 25 kA - Normal start - up, type : 1


Note : MC5025NS1.1
S503KM

Miniature Circuit Breaker S503-KM


500 V, 25 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37

Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33
44
54

Manual Motor Starter

Contactor

Type

Current setting
Magnetic release

Type

S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 2.5
S503-KM 2.5
S503-KM 4
S503-KM 6
S503-KM 9
S503-KM 9
S503-KM 20
S503-KM 20
S503-KM 20
S503-KM 32
S503KM 32
S503-KM 52
S503-KM 63
S503-KM 75

16
16
16
16
16
25
25
45
55
100
100
200
200
200
400
400
580
800
840

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00
A63-30-00
A95-30-00

Thermal Overload
Relay

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35
35
35

Type

Group

Current
Max.
setting range Current

TA 25DU0.4
TA 25DU0.93
TA 25DU1
TA 25DU1
TA 25DU1.4
TA 25DU1.8
TA 25DU2.4
TA 25DU3.1
TA 25DU4
TA 25DU6.5
TA 25DU8.5
TA 25DU11
TA 25DU14
TA 25DU19
TA 25DU25
TA 25DU32
TA 75DU42
TA 75DU52
TA 80DU63

[A]
0.25 - 0.4
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63

Imax [A]
0.4
0.63
1
1
1.35
1.75
2.3
2.95
4
6.25
8.1
10.5
13.5
18.5
24.5
30.5
39
48.5
63

MC5025NS1.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

500 V - 25 kA - Normal start - up, type : 2


Note : MC5025NS2.1
S503KM

Miniature Circuit Breaker S503-KM


500 V, 25 kA, Normal start - up, type 2
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37

Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33
44
54

Manual Motor Starter

Contactor

Type

Current setting
Magnetic release

Type

S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM2.5
S503-KM2.5
S503-KM4
S503-KM6
S503-KM9
S503-KM9
S503-KM20
S503-KM20
S503-KM20
S503-KM32
S503KM32
S503-KM52
S503-KM63
S503-KM75

16
16
16
16
16
25
25
45
55
100
100
200
200
200
400
400
580
800
840

A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A16-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00
A63-30-00
A95-30-00

Thermal Overload
Relay

Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35
35
35

Type
TA25DU0.4
TA25DU0.93
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA75DU42
TA75DU52
TA80DU63

Group

Current
Max.
setting range Current
[A]
0.25 - 0.4
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63

Imax [A]
0.4
0.63
1
1
1.35
1.75
2.3
2.95
4
6.25
8.1
10.5
13.5
18.5
24.5
30.5
39
48.5
63

MC5025NS2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 01/02/2000 by Jean-Michel Eymery

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
500 V - 100 kA - Normal start - up, type : 1
Note : MC5000NS1.1
MO325

MO 325 circuit-breaker with Prolim current limiter


500 V, 100 kA, Normal start - up, type1
Motor

Circuit-Breaker
and Current Limitor

Rated
Output

Rated
Current

Pe [kW]
0.25
0.37
0.55
0.75
1.1
1.5

Ie [A]
0.66
0.88
1.2
1.5
2.1
2.8

2.2
2.5
3
4
5.5
7.5

11
15

3.8
4.3
5.2
6.9
9.1
12.2

17.5
22.8

Contactor
Type

Safety
clearance

Thermal Overload Relay Group

Type

Limiter
type
PROLIM

Magnetic
tripping
current

Type

Current
Max
setting range Current

MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5

[A]
11.5
11.5
16
16
27.5

A9
A9
A9
A9
A9

[mm]
15
15
15
15
15

TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4

[A]
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4

MO325-4

40

A9

15

TA25DU3.1

2.2 - 3.1

Imax [A]
1
1
1.35
1.75
2.3
2.95

MO325-4

40

A9

15

TA25DU4

2.8 - 4

3.75

MO325-4
MO325-6.3
MO325-6.3
MO325-9
MO325-12.5

40
67.7
67.7
112.5
156

A9
A9
A12
A12
A16

15
15
15
15
15

TA25DU5
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11

3.5 - 5
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11

4.2
4.75
6.25
8
10.5

MO325-12.5

156

A26

15

TA25DU14

10 - 14

12.5

MO325-16

PLM 36-B*

200

A26

15

TA25DU14

10 - 14

13.5

MO325-20
MO325-25

PLM 36-B
PLM 36-B

250
312.5

A26
A26

15
15

TA25DU19
TA25DU25

13 - 19
18 - 25

18.5
23

* : PLM 36-B only needed for Iq > 100 kA


MC5000NS1.1
Created 30/04/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 03/02/2000 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
500 V - 100 kA - Normal start - up, type : 2
Note : MC5000NS2.1
MO325

MO 325 circuit-breaker with Prolim current limiter


500V, 100 kA, Normal start - up, type 2
Motor

Circuit-Breaker
and Current Limitor

Rated
Output

Rated
Current

Pe [kW]
0.25
0.37
0.55
0.75
1.1
1.5

Ie [A]
0.66
0.88
1.2
1.5
2.1
2.8

2.2
2.5
3
4
5.5
7.5

11
15

3.8
4.3
5.2
6.9
9.1
12.2

17.5
22.8

Contactor
Type

Safety
clearance

Thermal Overload Relay Group

Type

Limiter
type
PROLIM

Magnetic
tripping
current

Type

Current
Max
setting range Current

MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5

[A]
11.5
11.5
16
16
27.5

A9
A9
A9
A9
A12

[mm]
15
15
15
15
15

TA 25DU1
TA 25DU1
TA 25DU1.4
TA 25DU1.8
TA 25DU2.4

[A]
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4

MO325-4

40

A12

15

TA 25DU3.1

2.2 - 3.1

Imax [A]
1
1
1.35
1.75
2.3
2.95

MO325-4

40

A16

15

TA 25DU4

2.8 - 4

3.75

MO325-4
MO325-6.3
MO325-6.3
MO325-9
MO325-12.5

40
67.7
67.7
112.5
156

A26
A26
A26
A26
A26

15
15
15
15
15

TA 25DU5
TA 25DU5
TA 25DU6.5
TA 25DU8.5
TA 25DU11

3.5 - 5
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11

4.2
4.75
6.25
8
10.5

MO325-12.5

156

A26

15

TA 25DU14

10 - 14

12.5

MO325-16

PLM 36-B*

200

A26

15

TA 25DU14

10 - 14

13.5

MO325-20
MO325-25

PLM 36-B
PLM 36-B

250
312.5

A26
A26

15
15

TA 25DU19
TA 25DU25

13 - 19
18 - 25

18.5
23

* : PLM 36-B only needed for Iq > 100 kA MC5000NS2.1


Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 25/02/2000 by Jean-Michel Eymery

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
690 V - 100 kA - Normal start - up, type : 1
Note : MC6900NS1.1
MO325

MO 325 circuit-breaker with Prolim current limiter


690 V, 100 kA, Normal start - up, type 1
Motor
Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3

Ie [A]
0.26
0.42
0.48
0.65
0.84
1.1
1.5
1.99
2.54
2.77
3.74

4
5.5
7.5

11

4.97
6.41
8.54

12.4

Circuit Breaker
and Current Limiter

Contactor
Type

Safety
clearance

Thermal Overload Relay Group

Type

Limiter
type
PROLIM

Magnetic
tripping
current

Type

Current
Max
setting range Current

MO325-0.40
MO325-0.63
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4

[A]
3.9
6.14
6.14
11.5
11.5
18.4
18.4
28.75
28.75
50

A9
A9
A9
A9
A9
A9
A9
A9
A9
A9

[mm]
15
15
15
15
15
15
15
15
15
15

TA 25DU0.40
TA 25DU0.63
TA 25DU0.63
TA 25DU1
TA 25DU1
TA 25DU1.4
TA25DU1.8
TA 25DU2.4
TA 25DU3.1
TA 25DU3.1

[A]
0.25 - 0.40
0.4 - 0.63
0.4 - 0.63
0.63 - 1
0.63 - 1
1.0 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.3 - 3.1

Imax [A]
0.40
0.63
0.63
1
1
1.35
1.75
2.35
2.6
3

MO325-4

50

A9

15

TA 25DU4

2.8 - 4.0

3.75

MO325-4

50

A9

15

TA 25DU5

3.5 - 5.0

4.5

MO325-6.3
MO325-6.3

PLM 20-C

78.75
78.75

A9
A9

15
15

TA 25DU6.5
TA 25DU8.5

4.5 - 6.5
6 - 8.5

6.25
6.7

MO325-9

PLM 20-C

135

A12

15

TA 25DU11

7.5 - 11

MO325-12.5

PLM 20-C

187.5

A16

15

TA25DU11

7.5 - 11

10

MO325-12.5

PLM 20-C

187.5

A26

15

TA 25DU14

10 - 14

13.5

MC6900NS1.1

Created 30/04/99 by Jean-Paul Guitton/FRCTL/ABB


Latest changed 27/09/2000 by Jean-Paul Guitton

Home

Fuse

Coordination Table

MCCB

MMS

Softstarters UL Comb.

MCB

Direct-on-line starters
690 V - 100 kA - Normal start - up, type : 2
Note : MC6900NS2.1
MO325

MO 325 circuit-breaker with Prolim current limiter


690 V, 100 kA, Normal start - up, type 2
Motor

Circuit Breaker
and Current Limiter

Rated
Output

Rated
Current

Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3

Ie [A]
0.26
0.42
0.48
0.65
0.84
1.1
1.5
1.99
2.54
2.77
3.74

4
5.5
7.5

11

4.97
6.41
8.54

12.4

Contactor
Type

Safety
clearance

Thermal Overload Relay Group

Type

Limiter
type
PROLIM

Magnetic
tripping
current

Type

Current
Max
setting range Current

MO325-0.40
MO325-0.63
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4

[A]
3.9
6.14
6.14
11.5
11.5
18.75
18.75
28.75
28.75
50

A9
A9
A9
A9
A9
A9
A9
A9
A12
A12

[mm]
15
15
15
15
15
15
15
15
15
15

TA 25DU0.40
TA 25DU0.63
TA 25DU0.63
TA 25DU1
TA 25DU1
TA 25DU1.4
TA25DU1.8
TA 25DU2.4
TA 25DU3.1
TA 25DU3.1

[A]
0.25 - 0.40
0.4 - 0.63
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.3 - 3.1

Imax [A]
0.40
0.63
0.63
1
1
1.35
1.75
2.35
2.6
3

MO325-4

50

A12

15

TA 25DU4

2.8 - 4

3.75

MO325-4

50

A26

15

TA 25DU5

3.5 - 5

4.75

MO325-6.3
MO325-6.3

PLM 20-C

78.75
78.75

A26
A26

15
15

TA 25DU6.5
TA 25DU8.5

4.5 - 6.5
6 - 8.5

6.25
8.0

MO325-9

PLM 20-C

135

A26

15

TA 25DU11

7.5 - 11

MO325-12.5

PLM 20-C

187.5

A26

15

TA25DU11

7.5 - 11

10.5

MO325-12.5

PLM 20-C

187.5

A26

15

TA 25DU14

10 - 14

13.5

MC6900NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 06/07/2001 by Jean-Paul Guitton

Home

Fuse

MCCB

Coordination Table

MMS

Softstarters UL Comb.

MCB

Das könnte Ihnen auch gefallen