of Protection
to IEC 60947-4-1
Coordination Tables
Home
Fuse
MCCB
MMS
Softstarters UL Comb.
MCB
ABB is providing a large offer of coordination tables needed for any motor
supply feeder for which protection against overload and short circuit are
mandatory in industrial applications.
Choice Guidance
For instance, a table given for 80kA is covering the intermediate short circuit
leveel i.e. 70, 60,...kA at the same voltage. However, you may find some
cheaper solution for lower short circuit levels in the database : the SCPD
upstream is calibrated to give the cheapest solution for the whole
combination starter according to the highest shor circuit level.
General Remarks
- to read before using the coordination tables Please read those remarks
before you start using the coordination. They will give you the general data
and help you use the tables properly.
Following basic functions are achieved :
overload protection, motor control, short circuit protection, isolation.
These functions are applied here for standard starters : direct-on-line
(DOL), reverser, star-delta, softstarters.
Coordination Types
Any table is in conformity with the standard IEC 60947-4-1 which
defines two types of coodinations : - Type 1 : there is not any risk for
the operator and assets, damage to the starter is acceptable, its
replacement for re-starting is generally necessary. - Type 2 : the
single acceptable risk is a light welding of the contactor, that means
the contacts shall be easily separated either by electrical control or
using a tool. After a short circuit, whatever its level, re-starting is
allowed after a few verifications : all the protection device functions
are still operational.
Home
Fuse
MCCB
MMS
Softstarters UL Comb.
MCB
General Remarks
Motor Current
Tables are based on 4-pole, 3-phase motor currents.
Indicative currents are given.
Ambient Temperature
Tables are given for 40C ambient temperature.
For higher temperature a derating factor must be applied :
Fuses : 0.8 to In when ambient temperature is 70C
MCCBs : 0.8 to In when ambient temperature is 60C
Thermal Overload Relay without derating up to 55C, 0.9 In at 70C
Safety Perimeter
It indicates the minimum distances of any
metallic plates from the components in order
to avoid any breakdown during short circuit.
Starting
Normal starting means up to 5s (cold state) at full speed
(class 10) and up to 2s (warm state)
Long starting or heavy duty means starting time between 5 to 30s
(class 30)
Thermal overload relays DU type and MMS are class 10A
Thermal overload relays SU type are class 30
Reverser Table
A "reverser" (two identical contactors) table
is given by the corresponding "DOL" table
Home
Fuse
MCCB
MMS
Softstarters UL Comb.
MCB
FUSE
Ue
V
Iq
kA
Coor.
type
Starting
type
SCPD
type
SCPD
curve
Size
kW
400
50
1
2
2
Normal
Normal
Normal
Din Fuse
Din Fuse
Din Fuse
04/02/00
04/02/00
Normal
Din Fuse
HD
Din Fuse
HD
Din Fuse
SD
Din Fuse
SD
Din Fuse
FG4080NS2.1af
FM4080NS2.1af
FG4080NSIN2.1
FM4080NSIN2.1
FG4080HDIN2.1
FM4080HDIN2.1
FG4080HD2.1
FM4080HD2.1af
FM4080SD1.1
FG4080SD1.1
FM4080SD2.1
FG4080SD2.1
29/08/01
29/08/01
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
12/11/01
27/09/00
27/09/00
05/04/00
05/04/00
100
Normal
Din Fuse
415
440
80
80
2
2
Normal
Normal
BS Fuse
Din Fuse
FG4050NS1,1a/b
FG4050NS2.1a/b
gG
gG
gG
aM
gG
aM
gG
aM
gG
aM
aM
gG
aM
gG
gG
aM
gM
gG
aM
FG4000NS1.1
FM4000NS1.1
FGB4180NS2.1
FG4480NS2.1
FM4480NS2.1
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
500
80
Normal
Din Fuse
Normal
Din Fuse
HD
Din Fuse
HD
Din Fuse
SD
Din Fuse
SD
Din Fuse
1
2
2
Normal
Normal
Normal
Din Fuse
Din Fuse
Din Fuse
Normal
Din Fuse
HD
Din Fuse
HD
Din Fuse
SD
Din Fuse
SD
Din Fuse
gG
aM
gG
aM
gG
aM
gG
aM
aM
gG
gG
aM
gG
gG
gG
aM
gG
aM
gG
aM
gG
aM
aM
gG
gG
aM
FG5080NS2.1af
FM5080NS2.1af
FG5080NSIN2.1
FM5080NSIN2.1
FG5080HDIN2.1
FM5080HDIN2.1
FG5080HD2.1
FM5080HD2.1
FM5080SD1.1
FG5080SD1.1
FG5080SD2.1
FM5080SD2.1
FG6935NS1.1
FG6935NS2.1
FG6950NS2.1af
FM6950NS2.1af
FG6950NSIN2.1
FM6950NSIN2.1
FG6950HDIN2.1
FM6950HDIN2.1
FG6950HD2.1
FM6950HD2.1
FM6950SD1.1
FG6950SD1.1
FG6950SD2.1
FM6950SD2.1
29/08/01
29/08/01
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
27/09/00
27/09/00
05/04/00
05/04/00
04/02/00
04/02/00
29/08/01
29/08/01
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
27/09/00
27/09/00
05/04/00
05/04/00
80
690
35
50
Table
Last
Update
Glossary
SCPD
HD
NS
SD
gG
aM
IN
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : FG4050NS1.1a/b
gG
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
Fuse
type
gG
[A]
10
10
10
10
20
20
25
25
25
40
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
B6
B6
B6
B6
B6
B6
B7
B7
B7
A16
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
E16DU2.7
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9
Group
Current
Max.
setting range Current
[A]
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
Imax [A]
2.7
2.7
2.7
2.7
2.7
6.3
9
9
12
16
FG4050NS1.1b
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
Fuse
type
gG
[A]
10
10
10
10
20
20
25
35
40
40
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
E16DU2.7
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9
Group
Current
Max.
setting range Current
[A]
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2,0 - 6.3
2,0 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
Imax [A]
2.7
2.7
2.7
2.7
2.7
6.3
9
9
12
16
FG4050NS1.1a
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : FG4050NS2.1a/b
gG
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
Fuse
type
gG
[A]
10
10
10
10
20
20
20
20
20
25
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
B7
B7
B7
B7
B7
B7
B7
B7
B7
A16
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
E16DU2.7
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9
Group
Current
Max.
setting range Current
[A]
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
Imax [A]
2.7
2.7
2.7
2.7
6.3
6.3
9
9
12
16
FG4050NS2.1b
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.2
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
Fuse
type
gG
[A]
10
10
10
10
20
20
20
20
20
25
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
E16DU2,7
E16DU2,7
E16DU2,7
E16DU2,7
E16DU6,3
E16DU6,3
E16DU18,9
E16DU18,9
E16DU18,9
E16DU18,9
Group
Current
Max.
setting range Current
[A]
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
0,9 - 2,7
2 - 6,3
2 - 6,3
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
5,7 - 18,9
Imax [A]
2.7
2.7
2.7
2.7
2.7
6.3
9
9
12
16
FG4050NS2.1a
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 80 kA - Normal start - up, type : 2
Note : FG4080NS2.1af
gG
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.2
1.5
2
2.6
3.5
2.2
3
4
5.5
7.5
5
6.6
8.5
11.5
15.5
19
22
25
30
32
37
44
50
60
63
72
85
105
135
165
200
240
290
350
420
520
545
610
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA800D
OESA800D
OESA800D
Fuse
type*
gG
[A]
4
6
6
10
10
10
16
16
25
32
32
40
50
63
63
80
100
100
125
125
160
160
200
200
250
315
400
400
500
630
630
800
800
800
Contactor
Size
Type
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA2H
OFAA2H
OFAA2H
OFAA3H
OFAA3H
OFAA3H
3
3
3
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A26
A30
A30
A40
A50
A50
A63
A63
A75
A95
A110
A145
A185
A210
A260
AF400
AF400
AF460
AF580
AF580
AF750
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
30
30
10
10
10
10
10
10
10
10
10
10
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E800DU(10)
E800DU(10)
E800DU(10)
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
150 - 500
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800
max [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
16
19
22
25
30
32
40
44
50
60
63
75
90
110
135
175
210
240
290
400
430
580
580
610
FG4080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 80 kA - Normal start - up, type : 2
Note : FM4080NS2.1af
aM
Fuse type aM
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.2
1.5
2
2.6
3.5
2.2
3
4
5.5
7.5
11
5
6.6
8.5
11.5
15.5
22
25
30
32
37
40
44
50
60
63
72
75
85
95
105
135
145
165
200
240
280
305
350
400
430
460
520
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
Switch-fuse
Type
Fuse*
type
aM
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
[A]
2
2
4
4
6
6
6
10
16
16
20
25
32
32
40
40
50
50
63
63
80
80
100
100
125
160
160
200
200
250
315
315
355
400
500
500
500
630
Contactor
Size
Type
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A30
A30
A40
A40
A50
A50
A63
A63
A75
A75
A95
A95
A110
A145
A145
A185
A210
A260
A300
A300
AF400
AF400
AF460
AF460
AF580
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA200DU150
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E800DU(10)
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
110 - 150
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
17
22
25
30
32
37
40
45
50
60
63
72
75
85
95
110
135
145
175
200
250
280
305
350
400
430
460
520
FM4080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
Switch-fuse
Rated
Current
Ie [A]
1.1
1.5
1.9
2.8
3.5
5.0
6.6
8.6
11.5
15.2
22
28.5
36
22
30
37
45
55
75
90
110
132
160
200
250
42
56
68
83
98
135
158
193
232
282
349
420
Type
Fuse
rating
gG
Contactor
Fuse
Type
and
Size
Type
Safety
clearance
Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2
t6 setting
max
for starter
Max.
Current
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
[A]
4
6
10
10
16
16
20
25
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
A9
A9
A9
A9
A9
A9
A9
A9
[mm]
15
15
15
15
15
15
15
15
[s]
7
7
7
7
7
7
7
7
Imax [A]
1.3
1.8
3.4
3.4
6.5
6.5
7.5
9
OS32D
32
OFAA 00 H
A12
15
13
OS32D
32
OFAA 00 H
A16
15
15
OS32D
40
OFAA 00 H
A26
20
16.5
OS32D
50
OFAA 00 H
A26
20
19.5
OS32D
OS32D
63
80
OFAA 00 H
OFAA 00 H
A26
A30
20
20
7
7
26
32
OS63D
100
OFAA 00 H
A40
20
37
OS63D
100
OFAA 00 H
A50
20
40
0S125D
125
OFAA 00 H
A50
20
50
OS125D
125
OFAA 00 H
A63
20
58
OESA250D
160
OFAA 1 H
A75
20
66
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
160
200
250
315
315
400
400
500
630
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
A75
A95
A145
A145
A185
A260
A260
EH370
EH370
20
20
10
10
10
10
10
40
40
5
7
7
7
7
7
7
7
7
75
90
115
145
168
210
235
290
400
OESA630D
630
OFAA 3 H
EH550
40
440
OESA630D
630
OFAA 3 H
EH550
40
480
FG4080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Home
Group
Fuse
MCCB
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
15
18.5
22
30
37
45
55
75
28.5
36
42
56
68
83
98
135
90
110
132
158
193
232
160
200
282
349
250
420
290
520
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
Fuse
rating
aM
[A]
2
2
4
4
6
10
10
16
16
20
25
32
40
50
63
80
100
125
160
160
200
200
250
315
355
400
500
500
500
630
630
Contactor
Fuse
Type
and
Size
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185
A210
A260
EH370
EH370
EH370
EH550
EH550
EH550
EH550
Safety
clearance
Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2
[mm]
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
40
Group
t6 setting
max
for starter
Max.
Current
[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
5
7
7
7
7
7
7
7
7
5
7
5
Imax [A]
1.7
1.7
3.2
3.2
4.9
7.2
7.2
9
12
16
22
26
30
37
50
65
75
96
125
135
145
162
200
245
275
315
400
415
450
500
520
FM4080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
1.1
1.5
1.9
2.8
3.5
5.0
6.6
8.6
11.5
15.2
22
15
18.5
22
28,5
36
42
30
37
45
55
75
90
110
132
160
200
56
68
83
98
135
158
193
232
282
349
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
Fuse
rating
gG
[A]
6
10
10
16
16
20
25
32
40
50
63
80
100
125
125
160
200
200
250
315
400
400
500
630
630
630
Contactor
Fuse
Type
and
Size
Type
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A40
A50
A50
A63
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370
EH370
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
[s]
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
21
Imax [A]
1.5
2.7
2.7
5
5
6
7.1
10.5
13
16
22
26.5
32
46
46
51
70
70
92
130
150
175
210
328
328
350
MCU1/ MCU2
[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
10
10
10
10
40
40
40
40
FG4080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
1.1
1.5
1.9
2.8
3.5
5.0
6.6
8.6
11.5
15.2
11
15
18.5
22
30
37
45
55
22
28.5
36
42
56
68
83
98
75
90
110
132
160
200
135
158
193
232
282
349
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
Fuse
rating
aM
[A]
2
4
4
6
6
10
16
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
355
400
500
630
Contactor
Fuse
Type
and
Size
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A30
A30
A30
A50
A50
A63
A95
A145
A145
A185
A210
A260
EH370
EH370
EH370
EH550
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
[s]
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
Imax [A]
1.5
2.6
2.6
4
4
6
11
11
13
18
20
25
31
40
50
60
75
95
110
125
155
190
215
245
320
380
MCU1/ MCU2
[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
40
40
40
40
FM4080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
18.5
22
36
42
30
37
45
55
75
90
110
132
160
56
68
83
98
135
158
193
232
290
Type
Fuse
type
gG
[A]
6
10
10
16
16
25
32
40
50
63
80
100
125
125
125
160
200
200
250
315
400
400
500
630
630
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
2
2
2
3
3
3
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A40
A50
A50
A50
A63
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370
Thermal Overload
Relay
Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
40
40
40
Type
Group
Current
Max.
setting range Current
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU185
T450SU235
T450SU235
T450SU310
[A]
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
27.5 - 40
35 - 52.5
35 - 52.5
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 -1 40
130 - 185
165 - 235
165 - 235
220 - 310
Imax [A]
1.5
2.7
2.7
4.5
4.5
6.3
9
11
14
18.9
24
30
35
43
43
50
60
68
90
105
140
165
205
235
300
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
15
28.5
18.5
22
36
42
30
37
45
55
56
68
83
98
75
90
110
132
160
200
250
135
158
210
250
320
380
470
Type
Fuse
type
aM
[A]
4
4
4
6
10
10
16
20
25
32
40
50
50
63
80
80
100
100
125
160
200
200
250
315
355
400
500
630
800
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
2
2
2
3
3
3
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A30
A30
A40
A50
A63
A63
A95
A95
A95
A145
A145
A185
A210
A260
A300
AF400
AF400
AF400
AF580
Overload
Relay
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
10
10
40
40
Type
Group
Current
Max.
setting range Current
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU80(3)
TA450SU80(2)
TA450SU80(2)
TA450SU80(2)
TA450SU105(2)
TA450SU60
TA450SU80
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
TA450SU235
E500 30*
E500 30*
E500 30*
E500 30*
[s]
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
18.3 - 26.7
27.5 - 40
27.5 - 40
27.5 - 40
35 - 52.5
40 - 60
55 - 80
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
165 - 235
150 - 500
150 - 500
150 - 500
150 - 500
Imax [A]
2.7
2.7
2.7
3.7
5.5
5.5
8.5
12
17
18.9
23
26.7
30
35
40
46
55
58
70
88
105
120
140
170
230
260
330
400
500
* : trip class
(x) : number of primary turns
FM4080HD2.1af
Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 12/11/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
250
290
315
355
430
520
545
610
Switch-fuse
Type
Fuse
rating
aM
Contactor
Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
[A]
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145
A185
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145
A185
A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110
A145
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA110U110
TA200DU135
TA200DU150
TA200DU175
[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
[A]
10
14
18
24
32
40
50
63
80
95
108
145
188
200
250
315
OESA400D
355
OFAM 2 aM
A210
A210
A185
TA450DU235
165 - 235
355
OESA400D
400
OFAM 2 aM
A210
A210
A185
TA450DU235
165 - 235
400
OESA630D
OESA630D
OESA630D
OESA630D
500
630
630
630
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A260
AF400
AF400
AF400
A260
AF400
AF400
AF400
A210
A300
A300
A300
TA450DU310
E500DU500
E500DU500
E500DU500
220 - 310
165 - 500
165 - 500
165 - 500
500
630
630
630
FM4080SD1.1
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
200
250
290
315
355
349
430
520
545
610
Switch-fuse
Type
Fuse
rating
gG
Contactor
Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
[A]
20
25
32
40
50
63
80
100
125
125
160
200
250
250
315
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A95
A110
A145
A145
A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A110
A110
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA110DU110
TA200DU135
TA200DU150
[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
110 - 150
[A]
10
13
18
24
32
40
50
63
80
90
108
145
188
200
235
OESA400D
315
OFAA 2 H
A185
A185
A145
TA200DU175
130 - 175
285
OESA400D
400
OFAA 2 H
A185
A185
A145
TA200DU175
130 - 175
300
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
500
500
630
630
630
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A210
A260
EH370
EH370
EH370
A210
A260
EH370
EH370
EH370
A185
A210
EH260
EH260
EH260
TA450DU235
TA450DU310
T450DU400
T450DU400
T450DU400
165 - 235
220 - 310
285 - 400
285 - 400
285 - 400
400
450
540
610
610
FG4080SD1.1
Created 11/04/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 27/09/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
250
290
315
355
430
520
545
610
Switch-fuse
Type
Fuse
rating
aM
Contactor
Thermal Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
[A]
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A145
A145
A145
A210
A210
A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A145
A145
A145
A210
A210
A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110
A145
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA200DU90
TA200U110
TA200DU135
TA450DU185
TA450DU185
[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
130 - 185
130 - 185
[A]
10
14
18
24
32
40
50
63
80
95
108
145
188
200
250
315
OESA400D
355
OFAM 2 aM
EH370
EH370
A210
T450DU235
165 - 235
355
OESA400D
400
OFAM 2 aM
EH370
EH370
A210
T450DU235
165 - 235
400
OESA630D
OESA630D
OESA630D
OESA630D
500
630
630
630
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
EH370
EH550
EH550
EH550
EH370
EH550
EH550
EH550
A260
A300
A300
A300
T450DU310
T450DU400
T450DU400
T450DU400
220 - 310
285 - 400
285 - 400
285 - 400
500
630
630
630
FM4080SD2.1
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
Ie [A]
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
200
250
290
315
355
349
430
520
545
610
Switch-fuse
Type
Fuse
rating
gG
Contactor
Thermal Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
[A]
20
25
32
40
50
63
80
100
125
125
160
200
250
250
315
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A9
A12
A16
A26
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
A75
A95
A95
A110
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU63
TA110DU90
TA200DU110
TA200DU135
TA200DU175
[A]
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
45 - 63
65 - 90
80 - 110
100 - 135
130 - 175
[A]
10
13
18
24
32
40
50
63
80
90
108
145
188
200
235
OESA400D
315
OFAA 2 H
A185
A185
A145
TA200DU175
130 - 175
285
OESA400D
400
OFAA 2 H
A210
A210
A145
TA450DU185
130 - 185
315
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
500
500
630
630
630
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
EH370
EH370
EH370
EH370
EH370
EH370
EH370
EH370
EH370
EH370
A210
A210
A260
A300
A300
TA450DU235
T450DU310
T450DU400
T450DU400
T450DU400
165 - 235
220 - 310
285 - 400
285 - 400
285 - 400
400
450
540
610
610
FG4080SD2.1
Created 22/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 1
Note : FG4000NS1.1
gG
Fuse type gG
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.2
1.5
2
2.6
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
105
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OESA00
OESA250D
OESA250D
OESA250D
OESA250D
Fuse
typegG
[A]
6
10
10
16
16
16
25
25
32
40
40
63
80
100
125
160
200
200
250
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A40
A50
A63
A75
A95
A110
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
max [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
16
25
30
37
50
63
75
90
110
FG4000NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 1
Note : FM4000NS1.1
aM
Fuse type aM
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.2
1.5
2
2.6
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
105
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OESA00
OESA00
OESA00
OESA00
Fuse
type
aM
[A]
4
4
6
6
8
8
8
10
16
20
25
32
40
50
63
100
100
125
160
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A40
A50
A63
A75
A95
A110
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
12
16
25
30
37
50
63
75
90
110
FM4000NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
415 V - 80 kA - Normal start - up, type : 2
Note : FGB4180NS2.2
BS Fuse
Fuse type BS
Switch-fuse
Rated
Output
Rated
Current
415
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
Ie [A]
1.15
1.5
2
2.5
3.5
5
6.5
8.4
11
7.5
11
15
18.5
14
21
28
35
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
42
55
66
81
96
127
156
188
225
276
339
435
475
530
582
Type
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA20P3A1
OESA32P3A2
OESA32P3A2
OS63B3
(OESA 63)
OS63B3
OS63B3
OESA100G1
OESA200B3PL1
OESA200B3PL1
OESA 200
OESA200
OESA315
OESA315
OESA400
OESA630
OESA630
OESA630
OESA630
OESA800
Contactor
Safety
clearance
Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
Fuse typeBS
Size
Type
[A]
NIT4
NIT6
NIT6
NIT16
NIT16
NIT16
NIT20
NIT20
NIT20M25
NIT20M25
NIT20M32
TIA32M50
TIA32M63
TIS63M80
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A2
A2
A3
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A30
A50
[mm]
15
15
15
15
15
15
15
15
15
15
15
20
20
20
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA75DU42
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
max [A]
1.4
1.8
2.4
3.1
4
5
8.5
8.5
11
14
15.5
25
30
42
TIS63M80
TIS63M100
TC100M125
TC100M160
TC100M200
DEO200M250
DEO200M250
DEO200M315
DEO200M315
ED315M355
ED400M450
630R11/FF630
630R11/FF630
630R11/FF630
800S11/GF800
A3
A3
A4
B1
B1
-
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
EH370
EH550
EH550
EH550
EH700
20
20
20
20
20
10
10
10
10
10
40
40
40
40
40
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU175
TA450DU235
TA450DU235
TA450DU310
T450DU400
T900DU500
T900DU500
T900DU650
T900DU650
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
165 - 235
165 - 235
220 - 310
285 - 400
355 - 500
355 - 500
465 - 650
465 -650
45
63
70
90
100
135
175
210
210
270
370
500
500
550
650
FGB4180NS2.2
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
440 V - 80 kA - Normal start - up, type : 2
Note : FG4480NS2.1
gG
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
Ie [A]
1.06
1.25
1.67
1.1
1.5
2.2
3
4
5.5
2.26
3.03
4.31
5.8
7.6
10.3
7.5
11
15
18.5
22
13.5
19.3
26.3
32
37.1
30
37
45
55
50.1
61.9
73.9
90.3
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OESA00
OESA250D
OESA250D
OESA250D
Fuse
type
gG
[A]
4
6
6
6
10
10
16
16
25
32
32
40
50
63
80
100
100
125
160
160
200
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A30
A40
A50
A63
A63
A75
A95
A110
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
[A]
1 - 1.4
1- 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
Imax [A]
1.4
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
16
25
30
40
42
52
63
70
90
100
FG4480NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
440 V - 80 kA - Normal start - up, type : 2
Note : FM4480NS2.1
aM
Fuse type aM
Rated
Current
Pe [kW]
0.37
0.55
0.75
Ie [A]
1.06
1.25
1.67
1.1
1.5
2.2
3
4
5.5
2.26
3.03
4.31
5.8
7.6
10.3
7.5
11
15
18.5
22
13.5
19.3
26.3
32
37.1
30
37
45
55
50.1
61.9
73.9
90.3
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA00
OESA00
OESA00
Fuse
type
aM
[A]
2
2
4
4
4
6
6
8
10
16
16
20
25
32
50
50
63
63
100
100
125
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A30
A40
A50
A63
A63
A75
A95
A110
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1.4
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
[A]
1 - 1.4
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
Imax [A]
1.4
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
11
16
25
30
40
42
52
63
70
90
100
FM4480NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
Ie [A]
0.85
1.2
1.48
2.1
2.6
3.8
3
4
5.5
5.5
8
9
11
12
14
19
22
25
28
32
33
40
45
52
55
60
65
70
80
100
110
135
160
190
230
280
335
420
430
580
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA800D
OESA800D
Fuse*
type
gG
[A]
4
6
6
10
10
16
16
16
25
25
32
32
32
40
63
63
63
80
80
100
100
125
125
125
125
160
160
200
200
250
315
355
400
500
630
630
800
800
Contactor
Size
Type
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA2H
OFAA2H
OFAA2H
OFAA3H
OFAA3H
OFAA3H
3
3
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A26
A30
A30
A40
A40
A50
A50
A63
A63
A75
A75
A95
A95
A110
A145
A145
A185
A210
A260
AF400
AF400
AF460
AF580
AF580
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
10
10
10
10
10
10
10
10
10
10
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA42DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU150
TA200DU175
TA450DU235
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)**
E800DU(10)
[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
7.5 - 11
10 - 14
10 - 14
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
Imax [A]
1
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
11
12
14
19
22
25
28
32
33
40
45
52
55
60
65
70
80
100
110
135
170
200
240
290
400
430
500
580
FG5080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
** : mounting kit between contactor and relay is not available
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
Ie [A]
0.85
1.2
1.48
2.1
2.6
3.8
3
4
5.5
5.5
8
9
11
12
14
19
22
25
28
32
33
40
45
52
55
63
65
70
80
100
110
125
135
145
160
190
220
240
275
300
335
370
420
430
500
500
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
Fuse*
type
aM
[A]
2
2
4
4
4
4
6
6
10
16
16
16
16
25
32
32
40
40
50
50
63
63
80
80
100
100
125
125
125
160
160
200
200
250
250
315
315
355
400
500
500
500
630
630
Contactor
Size
Type
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A26
A26
A30
A30
A40
A40
A50
A50
A63
A63
A75
A75
A95
A95
A110
A145
A145
A145
A145
A185
A210
A260
A260
A300
AF400
AF400
AF400
AF460
AF460
AF580
AF580
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA42DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150
TA200DU200
TA450DU235
TA450DU235
TA450DU310
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)**
E800DU(10)
[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
7.5 - 11
10 - 14
10 - 14
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
80 - 110
100 - 135
100 - 135
100 - 135
110 - 150
150 - 200
165 - 235
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
Imax [A]
1
1.4
1.8
2.4
3.1
4
5
6.5
8.5
9
11
12
14
19
22
25
28
32
33
40
45
52
55
63
65
70
80
100
110
125
135
145
165
200
220
240
275
300
335
370
420
430
500
500
FM5080NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
** : mounting kit between contactor and relay is not available
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Rated
Current
Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
37
45
55
75
90
110
132
160
200
250
290
315
56
67
82
110
132
158
192
230
279
335
394
440
Switch-fuse
Type
Fuse
rating
gG
Contactor
Fuse
Type
and
Size
Type
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
MCU1/ MCU2
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
[A]
4
6
6
10
10
16
16
20
32
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
A9
A9
A9
A9
A9
A9
A9
A9
A12
[mm]
15
15
15
15
15
15
15
15
15
[s]
7
7
7
7
7
7
7
7
7
Imax [A]
1.3
1.8
1.8
3.4
3.4
6.5
6.5
7.5
12
OS32D
32
OFAA 00 H
A16
15
13
OS32D
40
OFAA 00 H
A26
15
16.5
OS32D
OS32D
OS32D
OS63D
50
63
80
100
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
A26
A30
A40
A50
20
20
20
20
7
7
7
7
19.5
26
33
40
OS125D
125
OFAA 00 H
A50
20
45
OS125D
125
OFAA 00 H
A63
20
55
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
160
200
200
250
315
315
400
400
500
630
630
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A75
A95
A110
A145
A145
A185
A210
A260
EH370
EH370
EH550
20
20
20
10
10
10
10
10
40
40
40
7
7
7
7
7
7
7
7
7
7
7
65
80
88
115
145
168
210
235
290
370
440
OESA630D
630
OFAA 3 H
EH550
40
440
OESA630D
630
OFAA 3 H
EH550
40
480
FG5080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
37
45
55
75
90
56
67
82
110
132
110
132
160
158
192
230
200
250
279
335
290
315
355
394
440
483
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
Fuse
rating
aM
[A]
2
2
2
4
4
6
10
10
16
20
25
32
40
50
63
63
80
100
125
160
160
200
200
250
315
355
400
400
500
500
500
630
Contactor
Fuse
Type
and
Size
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A40
A50
A50
A63
A75
A95
A110
A145
A145
A145
A185
A210
A260
EH370
EH370
EH370
EH550
EH550
EH550
EH550
Safety
clearance
Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2
[mm]
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
40
Group
t6 setting
max
for starter
Max.
Current
[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
5
7
7
7
7
7
7
5
7
7
5
7
Imax [A]
1.7
1.7
1.7
3.2
3.2
4.9
7.2
7.2
12
14
22
26
30
38
45
50
63
75
96
125
135
145
162
200
240
275
315
340
415
415
450
500
FM5080NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Rated
Current
Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
37
45
55
75
90
110
132
160
200
56
67
82
110
132
158
192
230
279
Switch-fuse
Type
Fuse
rating
gG
Contactor
Fuse
Type
and
Size
Type
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
MCU1/ MCU2
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
[A]
6
6
10
10
16
16
20
25
32
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
A9
A9
A9
A9
A9
A9
A9
A9
A12
[mm]
15
15
15
15
15
15
15
15
15
[s]
28
28
28
28
28
28
28
28
28
Imax [A]
1.5
1.5
2.7
2.7
5
5
6
7.1
10.5
OS32D
40
OFAA 00 H
A26
20
28
13
OS32D
50
OFAA 00 H
A26
20
28
16
OS32D
OS32D
OS32D
OS125D
63
80
100
125
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
A30
A30
A40
A50
20
20
20
20
28
28
28
28
22
26.5
32
45
OS125D
125
OFAA 00 H
A63
20
28
46
OESA250D
160
OFAA 1 H
A63
20
28
51
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
200
200
250
315
400
400
500
630
630
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370
20
20
10
10
10
10
40
40
40
28
28
28
28
28
28
28
28
28
70
70
92
130
150
175
210
328
328
FG5080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Switch-fuse
Rated
Current
Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
23
29
34
45
56
67
82
110
132
158
192
230
279
335
Type
Fuse
rating
aM
Contactor
Fuse
Type
and
Size
Type
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
MCU1/ MCU2
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
[A]
2
2
4
4
6
6
10
16
16
20
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
[mm]
15
15
15
15
15
15
15
15
15
15
[s]
28
28
28
28
28
28
28
28
28
28
Imax [A]
1.5
1.5
2.6
2.6
4
4
6
11
11
13
OS32D
25
OFAM 00 aM
A26
20
28
18
OS32D
32
OFAM 00 aM
A30
20
28
20
OS32D
OS32D
OS63D
40
50
63
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
A30
A40
A50
20
20
20
28
28
28
25
31
40
OS63D
80
OFAM 00 aM
A50
20
28
45
OS63D
80
OFAM 00 aM
A63
20
28
50
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
100
125
160
200
250
315
355
400
500
630
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
A75
A110
A145
A185
A210
A260
EH370
EH370
EH370
EH550
20
20
10
10
10
10
40
40
40
40
28
28
28
28
28
28
28
28
28
28
60
75
96
125
155
190
215
245
320
380
FM5080HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.88
1.2
1,5
2.2
2.8
4
5.2
6.8
9.1
12.2
17.5
23
29
34
30
37
45
55
75
90
110
132
160
200
45
56
67
82
110
132
158
192
230
279
Switch-fuse
Type
Fuse
type
gG
[A]
4
6
10
10
16
20
25
32
40
50
63
80
100
125
125
160
200
200
250
315
400
400
500
630
630
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
2
2
3
3
3
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A40
A50
A50
A63
A95
A95
A145
A185
A210
A260
EH370
EH370
EH370
Thermal Overload
Relay
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
10
10
10
10
40
40
40
Type
Group
Current
Max.
setting range Current
E16DU1.0 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140
TA450SU185
T450SU185
T450SU235
T450SU235
T450SU310
[s]
0.3 - 1.0
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
27.5 - 40
35 - 52.5
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
185 - 235
185 - 235
220 - 310
Imax [A]
1.0
1.5
2.7
2.7
4.5
5.5
6.3
9
11
14
18.9
24
30
35
43
50
60
68
90
120
170
185
205
235
300
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Ie [A]
0.88
1.2
1.5
2.2
2.8
4
5.2
6,9
9.1
12,2
17,5
23
29
34
45
37
45
55
56
67
82
75
90
110
132
110
132
158
192
160
200
230
279
250
335
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Fuse
type
aM
[A]
2
4
4
4
6
10
10
16
20
25
32
40
50
63
80
100
100
125
160
200
200
250
315
355
400
400
500
630
630
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
2
2
2
2
3
3
3
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A30
A30
A40
A50
A63
A95
A95
A110
A145
A185
A185
A210
A260
EH370
EH370
EH370
EH370
EH550
EH550
Thermal Overload
Relay
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
Type
Group
Current
Max.
setting range Current
E16DU1 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU80(2)
TA450SU(80)2
TA450SU105(2)
TA450SU60
TA450SU80
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
T450SU235
T450SU235
T450SU310
T450SU310
T450SU310
T450SU400
[s]
0.3 - 1
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
27.5 - 40
27.5 - 40
35 - 52.5
40 - 60
55 - 80
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
285 - 400
Imax [A]
1
2.7
2.7
2.7
3.7
5.5
5.5
8,5
12
17
18.9
23
30
35
46
55
58
70
88
105
120
140
170
200
220
240
285
310
350
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
Ie [A]
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
538
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Fuse
rating
aM
[A]
10
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
355
400
500
500
630
Contactor
Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A9
A9
A12
A16
A16
A26
A26
A40
A40
A50
A63
A75
A95
A110
A145
A145
A185
A260
A300
A300
A300
AF400
A9
A9
A12
A16
A16
A26
A26
A40
A40
A50
A63
A75
A95
A110
A145
A145
A185
A260
A300
A300
A300
AF400
A9
A9
A9
A12
A12
A16
A16
A26
A26
A30
A40
A50
A75
A95
A110
A110
A145
A210
A260
A260
A260
A300
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA42DU32
TA42DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU185
TA200DU175
TA450DU235
TA450DU235
TA450DU310
TA450DU310
E500DU500
Group
Current
Max.
setting range Current
[A]
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
165 - 235
220 - 310
220 - 310
165 - 500
[A]
8.6
10
14
18.9
24
32
40
50
63
80
95
115
145
188
200
250
315
355
400
500
500
630
FM5080SD1.1
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
Ie [A]
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
250
290
315
355
335
394
440
483
Switch-fuse
Type
Fuse
rating
gG
Contactor
Thermal Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
[A]
16
20
25
32
40
50
63
80
100
125
125
160
200
250
250
315
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185
A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A185
A9
A9
A9
A12
A12
A16
A16
A26
A26
A30
A40
A50
A75
A95
A110
A110
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32
TA42DU42
TA75DU52
TA75DU63
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU175
[A]
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
[A]
8.6
10
14
18.9
24
32
40
50
63
80
90
110
145
188
200
245
OESA400D
315
OFAA 2 H
A185
A185
A145
TA200DU175
130 - 175
285
OESA400D
400
OFAA 2 H
A210
A210
A185
TA450DU185
130 - 185
315
OESA400D
OESA630D
OESA630D
OESA630D
400
500
500
630
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A210
EH370
EH370
EH370
A210
EH370
EH370
EH370
A185
A210
A260
A300
T450DU235
T450DU235
T450DU310
T450DU310
165 - 235
165 - 235
220 - 310
220 - 310
340
405
450
530
FG5080SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Rated
Current
Pe [kW]
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
Ie [A]
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
538
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS160D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Fuse
rating
aM
[A]
10
10
16
20
25
32
40
50
63
80
100
125
160
200
200
250
315
355
400
500
500
630
Contactor
Thermal Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A210
A210
EH370
EH370
EH370
EH370
EH550
A9
A12
A16
A16
A26
A26
A30
A40
A50
A63
A75
A95
A145
A145
A145
A210
A210
EH370
EH370
EH370
EH370
EH550
A9
A9
A9
A12
A12
A16
A16
A26
A26
A30
A40
A50
A75
A95
A110
A110
A145
A210
A210
A260
A260
A300
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32
TA75DU42
TA75DU52
TA75DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU135
TA450DU185
TA450DU185
TA450DU235
T450DU235
T450DU310
T450DU310
T450DU400
Group
Current
Max.
setting range Current
[A]
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 185
130 - 185
165 - 235
165 - 235
220 - 310
220 - 310
285 - 400
[A]
8.6
10
14
18.9
24
32
40
50
63
80
95
115
145
188
200
250
315
355
400
500
500
630
FM5080SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
690 V - 35 kA - Normal start - up, type : 1
Note : FG6935NS1.1
gG
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
Fuse
type
gG
[A]
6
6
6
6
20
20
20
25
25
32
50
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
E16DU1
E16DU2.7
E16DU2.7
E16DU2.7
E16DU6.3
E16DU6.3
E16DU6.3
E16DU18.9
E16DU18.9
E16DU18.9
E16DU18.9
Group
Current
Max.
setting range Current
[A]
0.3 - 1
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
Imax [A]
1
2.7
2.7
2.7
6.3
6.3
6.3
7
7
9
17
FG6935NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
690 V - 35 kA - Normal start - up, type : 2
Note : FG6935NS2.1
gG
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
Switch-fuse
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
Fuse
type
gG
[A]
4
6
6
6
16
16
20
20
25
32
40
Contactor
Size
Type
00
00
00
00
00
00
00
00
00
00
00
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
Electronic Overload
Relay
Type
E16DU 1
E16DU 2.7
E16DU 2.7
E16DU 2.7
E16DU 6.3
E16DU 6.3
E16DU 6.3
E16DU 18.9
E16DU 18.9
E16DU 18.9
E16DU 18.9
Group
Current
Max.
setting range Current
[s]
0.3 - 1
0.9 - 2.7
0.9 - 2.7
0.9 - 2.7
2 - 6.3
2 - 6.3
2 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
Imax [A]
1
2.7
2.7
2.7
6.3
6.3
6.3
7
9
10
17
FG6935NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
690 V - 50 kA - Normal start - up, type : 2
Note : FG6950NS2.1af
gG
Fuse type gG
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
1.1
1.5
2.2
3
4
Ie [A]
1.5
2
2.9
3.5
4.9
5.5
7.5
11
15
6.7
9
13
17
19
21
25
35
40
43
46
52
63
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
82
95
115
140
170
205
235
245
305
315
370
420
420
470
470
500
500
Type
Contactor
Fuse*
type
gG
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
-
[A]
4
6
6
10
16
16
16
25
32
32
40
50
63
80
100
100
100
125
125
125
200
200
250
315
315
400
400
500
630
630
630
630
630
800
800
800
800
Size
Type
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA00H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA1H
OFAA2H
OFAA2H
OFAA2H
OFAA3H
OFAA3H
OFAA3H
4
4
4
4
4
4
4
4
4
A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A30
A30
A40
A50
A63
A63
A75
A95
A95
A95
A110
A145
A145
A185
A210
A210
A300
AF400
AF400
AF400
AF460
AF580
AF580
AF580
AF580
AF580
AF580
Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
30
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA42DU25
TA42DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA80DU52
TA80DU63
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU175
TA450DU185
TA450DU235
TA450DU235
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)**
E500DU(10)
E500DU(10)**
E500DU(10)
E500DU(10)**
E500DU(10)
[A]
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
130 - 185
165 - 235
165 - 235
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
150 - 500
250 - 800
150 - 500
250 - 800
max [A]
1.8
2.4
3.1
4
5
6.5
7
11
14
17
19
21
25
35
40
43
46
52
63
80
82
100
120
140
170
210
235
270
310
350
400
420
420
480
480
500
500
FG6950NS2.1af
* : tested with ABB fuses. To use such fuses or fuses with similar characteristics
** : mounting kit between contactor and relay is not available
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
690 V - 50 kA - Normal start - up, type : 2
Note : FM6950NS2.1af
aM
Fuse type aM
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
1.1
1.5
2.2
3
4
Ie [A]
1.5
2
2.9
3.5
4.9
5.5
7.5
11
15
6.7
9
13
17
19
21
25
35
40
43
46
52
63
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
82
95
115
140
170
205
220
245
305
315
350
370
420
350
470
470
500
500
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
OESA630D
Fuse*
type
aM
[A]
4
4
4
6
10
10
10
16
20
20
25
25
32
40
50
63
63
63
80
80
100
125
160
200
250
250
315
315
400
400
500
500
630
630
630
630
630
630
Contactor
Size
Type
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM00aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM1aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM2aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
OFAM3aM
A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A30
A30
A40
A50
A63
A63
A75
A95
A95
A95
A110
A145
A145
A185
A210
A210
A260
A300
AF400
AF400
AF400
AF460
AF580
AF580
AF580
AF580
AF580
AF580
Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
30
30
30
30
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Thermal Overload
Group
Relay
Type
Current
Max.
setting range Current
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA42DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA80DU52
TA80DU63
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU150
TA450DU185
TA450DU235
TA450DU235
TA450DU310
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)
E500DU(10)*
E800DU(10)
E500DU(10)*
E800DU(10)
E500DU(10)*
E800DU(10)
[A]
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 185
165 - 235
165 - 235
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
150 - 500
250 - 800
150 - 500
250 - 800
max [A]
1.8
2.4
3.1
4
5
6.5
7
11
14
17
19
21
25
35
40
43
46
52
63
80
82
100
120
150
170
205
220
270
310
320
350
400
430
430
480
480
500
500
FM6950NS2.1af
* : tested with ABB fuses. To use such fuses or fuse with similar characteristics
** : mounting kit between contactor and relay is not available
Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 29/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Switch-fuse
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
15
18.5
22
30
18
21
25
33
37
45
55
75
41
49
60
80
90
110
132
160
200
95
115
139
167
202
250
290
242
301
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
Fuse
rating
gG
[A]
4
4
4
6
10
10
16
16
20
25
32
40
50
63
63
80
100
100
125
160
200
200
250
250
315
315
400
400
500
500
Contactor
Fuse
Type
and
Size
Type
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A30
A30
A30
A40
A50
A63
A75
A95
A95
A110
A145
A145
A145
A185
A210
A210
A260
EH370
EH370
Safety
clearance
Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2
[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
40
40
Group
t6 setting
max
for starter
Max.
Current
[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
5
Imax [A]
1.3
1.3
1.3
1.8
3.4
3.4
6.5
6.5
7.5
9
13
16.5
19.5
21
25
33
40
42
55
65
82
88
115
115
155
168
210
235
290
315
FG6950NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Switch-fuse
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25
30
37
45
55
33
41
49
60
75
90
110
132
160
200
250
80
95
115
139
167
202
242
290
315
355
400
450
301
313
370
405
460
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Fuse
rating
aM
[A]
2
2
2
4
4
4
6
10
10
16
20
25
25
32
40
50
63
63
80
100
125
125
160
200
250
315
315
355
400
400
500
500
630
Contactor
Fuse
Type
and
Size
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A9
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A30
A30
A40
A50
A63
A75
A95
A95
A110
A110
A145
A145
A185
A210
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
Safety
clearance
Thermal Overload
Relay
Type
INSUM 2
MCU1/MCU2
[mm]
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
Group
t6 setting
max
for starter
Max.
Current
[s]
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
Imax [A]
1.7
1.7
1.7
3.2
3.2
3.2
4.9
7
7
13
16
21
21
25
30
38
46
50
63
75
82
96
120
162
200
240
245
275
315
315
370
415
500
FM6950NSIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Switch-fuse
Rated
Current
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
15
18.5
22
30
37
45
55
75
90
110
132
160
200
18
21
25
33
41
49
60
80
95
115
139
167
202
Type
Fuse
rating
gG
Contactor
Fuse
Type
and
Size
Type
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
MCU1/ MCU2
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
[A]
4
4
6
10
10
16
16
20
25
32
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
[mm]
15
15
15
15
15
15
15
15
20
20
[s]
28
28
28
28
28
28
28
28
28
28
Imax [A]
1.2
1.2
1.5
2.7
2.7
5
5
6
7.1
10.5
OS32D
40
OFAA 00 H
A26
20
28
13
OS32D
50
OFAA 00 H
A26
20
28
16
OS32D
OS32D
63
63
OFAA 00 H
OFAA 00 H
A30
A40
20
20
28
28
21
22
OS32D
80
OFAA 00 H
A40
20
28
25
OS32D
80
OFAA 00 H
A50
20
28
26.5
OS63D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
100
125
160
200
250
315
315
400
400
500
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A50
A75
A95
A110
A145
A185
A185
A260
A300
EH370
20
20
20
20
10
10
10
10
10
40
28
28
28
28
28
28
28
28
28
28
33
46
51
70
92
120
130
175
175
210
FG6950HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 28/01/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Contactor
Switch-fuse
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25
30
33
37
45
55
41
49
60
75
90
110
132
80
95
115
139
160
200
250
290
315
355
167
202
242
301
313
370
Type
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Fuse
rating
aM
[A]
2
2
2
4
4
6
6
10
16
16
20
25
32
40
50
63
63
80
80
100
125
160
160
200
250
250
315
355
400
500
500
630
Fuse
Type
and
Size
Type
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
OFAM 3 aM
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A30
A30
A40
A50
A50
A63
A75
A95
A95
A110
A145
A185
A185
A185
A210
A300
EH370
EH370
EH370
EH370
EH550
Thermal Overload
Relay
Safety
clearance
Type
INSUM 2
Group
t6 setting
max
for starter
Max.
Current
[s]
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
Imax [A]
1.5
1.5
1.5
2.6
2.6
4
4
6
11
11
13
18
21
25
31
35
40
46
50
60
75
96
96
120
140
155
190
215
245
320
320
380
MCU1/ MCU2
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
FM6950HDIN2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5.0
6.7
8.8
13
18
21
25
33
41
49
55
75
90
110
60
80
95
115
132
160
200
139
167
202
Switch-fuse
Type
Fuse
rating
gG
[A]
4
4
6
10
10
16
16
25
32
40
50
63
80
100
125
125
160
200
200
250
315
315
400
400
500
500
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
Contactor
Fuse
Type
and
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
2
2
2
3
3
3
3
A9
A9
A9
A9
A9
A9
A9
A26
A26
A26
A26
A30
A50
A63
A95
A95
A95
A110
A110
A145
A185
A185
A210
A260
EH370
EH370
Thermal Overload
Relay
Safety
clearance
[mm]
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
40
40
Type
E16DU1 30*
E16DU1 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
TA450SU185
T450SU235
Group
t6 setting
max
for starter
Max.
Current
[s]
0.3 - 1
0.3 - 1
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
27.5 - 40
35 - 52,5
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
130 - 185
165 - 235
Imax [A]
1
1
1.5
2.7
2.7
4.5
4.5
6.3
9
11
14
18.9
24
30
35
43
50
60
68
90
105
120
140
165
185
205
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Switch-fuse
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8,8
13
18
21
25
30
37
33
41
45
49
55
60
75
90
110
80
95
115
132
160
139
167
200
202
250
290
315
242
301
313
Type
Fuse
rating
aM
[A]
2
2
4
4
4
6
10
10
16
20
25
32
40
50
50
63
80
80
100
125
125
125
160
200
200
250
250
315
355
400
400
500
630
630
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
Contactor
Fuse
Type
and
Size
Type
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
2
2
2
2
3
3
3
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A30
A30
A30
A40
A50
A50
A63
A75
A95
A95
A95
A110
A145
A185
A185
A210
A210
A300
EH370
EH370
EH370
EH370
EH550
EH550
Thermal Overload
Relay
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
20
20
20
20
20
10
10
10
10
10
10
40
40
40
40
40
40
Type
E16DU1 30*
E16DU1 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU2.7 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU6.3 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
E16DU18.9 30*
TA450SU80(3)
TA450SU60(2)
TA450SU60(2)
TA450SU80(2)
TA450SU105(2)
TA450SU105(2)
TA450SU60
TA450SU60
TA450SU80
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
TA450SU185
TA450SU185
T450SU235
T450SU310
T450SU310
T450SU310
T450SU400
Group
t6 setting
max
for starter
Max.
Current
[ s]
0.3 - 1
0.3 - 1
0.8 - 2.7
0.8 - 2.7
0.8 - 2.7
1.9 - 6.3
1.9 - 6.3
1.9 - 6.3
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
5.7 - 18.9
18.3 - 26.7
20 - 30
20 - 30
27.5 - 40
35 - 52.5
35 - 52.5
40 - 60
40 - 60
55 - 80
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
130 - 185
130 - 185
165 - 235
220 - 310
220 - 310
220 - 310
285 - 400
Imax[ A]
1
1
2.7
2.7
2.7
3.7
5.5
5.5
8.5
12
17
18.9
21
25
28
35
43
46
55
60
65
70
88
105
120
140
145
170
185
220
240
285
310
350
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
4
Ie [A]
5
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
450
560
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
445
540
Switch-fuse
Type
Fuse
rating
aM
Contactor
Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
[A]
[A]
OS32D
[A]
6
OFAM 00 aM
A9
A9
A9
TA25DU3.1
2.2 - 3.1
5.3
OS32D
OFAM 00 aM
A9
A9
A9
TA25DU4
2.8 - 4
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
10
10
16
20
25
32
40
50
50
63
80
100
125
160
200
250
250
315
355
400
500
630
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400
AF460
A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400
AF460
A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A145
A145
A185
A185
A300
A300
AF400
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU25
TA75DU32
TA75DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA450DU185
TA450DU185
T450DU235
E500DU500
E500DU500
E500DU500
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 185
130 - 185
165 - 235
165 - 500
165 - 500
165 - 500
8.6
10
14
18.9
24
30
40
43
50
63
80
100
125
155
189
250
250
315
355
400
500
630
FM6950SD1.1
Created 19/05/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 27/09/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
4
Ie [A]
5
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
410
Switch-fuse
Type
Fuse
rating
gG
Contactor
Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
[A]
[A]
OS32D
[A]
10
OFAA 00 H
A9
A9
A9
TA25DU3.1
2.2 - 3.1
5.3
OS32D
10
OFAA 00 H
A9
A9
A9
TA25DU4
2.8 - 4
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
16
20
25
32
40
50
63
63
80
100
125
160
200
200
250
315
315
400
400
500
500
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400
A9
A12
A16
A26
A30
A40
A40
A40
A50
A63
A95
A95
A110
A110
A145
A185
A185
A210
A210
AF400
AF400
A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A110
A145
A185
A185
A300
A300
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA42DU19
TA42DU25
TA42DU25
TA75DU32
TA42DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA200DU175
TA450DU185
TA450DU235
E500DU500
E500DU500
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
130 - 185
165 - 235
165 - 500
165 - 500
8.6
10
14
18.9
24
32
43
43
52
63
85
108
135
145
188
206
285
318
340
405
450
FG6950SD1.1
Created 12/05/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 27/09/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type gG
Rated
Current
Pe [kW]
4
Ie [A]
5
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
410
Switch-fuse
Type
Fuse
rating
gG
Contactor
Thermal Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
[A]
[A]
OS32D
[A]
10
OFAA 00 H
A9
A9
A9
TA25DU3.1
2.2 - 3.1
5.3
OS32D
10
OFAA 00 H
A9
A9
A9
TA25DU4
2.8 - 4
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
OESA630D
OESA630D
16
20
25
32
40
50
63
63
80
100
125
160
200
200
250
315
315
400
400
500
500
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 00 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 1 H
OFAA 2 H
OFAA 2 H
OFAA 2 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
OFAA 3 H
A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A145
A185
A210
A210
EH370
EH370
A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A145
A185
A210
A210
EH370
EH370
A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A110
A145
A185
A185
A210
A260
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA42DU19
TA42DU25
TA42DU25
TA75DU32
TA42DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA200DU175
TA450DU185
TA450DU235
T450DU235
T450DU310
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
130 - 185
165 - 235
165 - 235
220 - 310
8.6
10
14
18.9
24
32
43
43
52
63
85
108
135
145
188
206
285
318
340
405
450
FG6950SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Fuse type aM
Rated
Current
Pe [kW]
4
Ie [A]
5
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
450
560
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
445
540
Switch-fuse
Type
Fuse
rating
aM
Contactor
Thermal Overload
Relay
Fuse
Type
and
Size
K1
Line
K3
Delta
K2
Star
Type
Group
Current
Max.
setting range Current
[A]
[A]
OS32D
[A]
6
OFAM 00 aM
A9
A9
A9
TA25DU3.1
2.2 - 3.1
5.3
OS32D
OFAM 00 aM
A9
A9
A9
TA25DU4
2.8 - 4
OS32D
OS32D
OS32D
OS32D
OS32D
OS32D
OS63D
OS63D
OS63D
OS63D
OS125D
OS125D
OS125D
OESA250D
OESA250D
OESA250D
OESA250D
OESA400D
OESA400D
OESA400D
OESA630D
OESA630D
10
10
16
20
25
32
40
50
50
63
80
100
125
160
200
250
250
315
355
400
500
630
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 00 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 1 aM
OFAM 2 aM
OFAM 2 aM
OFAM 2 aM
OFAM 3 aM
OFAM 3 aM
A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A210
A210
A210
EH370
EH370
EH370
EH550
A12
A16
A26
A26
A26
A30
A40
A40
A50
A63
A95
A95
A110
A145
A145
A210
A210
A210
EH370
EH370
EH370
EH550
A9
A9
A12
A16
A26
A26
A26
A26
A30
A40
A50
A75
A95
A95
A110
A145
A145
A185
A210
A210
A260
A300
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU25
TA75DU32
TA75DU42
TA80DU52
TA80DU63
TA80DU80
TA200DU90
TA200DU110
TA200DU150
TA450DU185
TA450DU185
T450DU235
T450DU235
T450DU310
T450DU400
3.5 - 5
4.5 - 6.5
5 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 185
130 - 185
165 - 235
165 - 235
220 - 310
285 - 400
8.6
10
14
18.9
24
30
40
43
50
63
80
100
125
155
189
250
250
315
355
400
500
630
FM6950SD2.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 04/04/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
MCCB
Ue
V
Iq
kA
Coor.
type
Starting
type
SCPD
type
Overload
mean
kW
Motor
Table
last
update
400
35
2
2
2
2
2
2
2
2
2
2
S-D
DOL/HD
DOL
DOL/HD
S-D
S-D/HD
S-D
DOL
DOL / HD
S-D/HD
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
TOR
TOR
TOR
MP
MP
TOR
INSUM
INSUM
INSUM
MP
MB4035SD2.1af
MB4035HD2.1af
MB4035NS2.1af
MP4035HD2.1af
MP4035SD2.1af
MB4035SDHD2.1af
MB4035SDIN2.1af
MB4035NSIN2.1af
MB4035HDIN2.1af
MP4035SDHD2.1af
24/08/01
24/08/01
11/07/01
11/07/01
24/08/01
30/08/01
31/08/01
14/11/01
14/11/01
30/08/01
50
65
2
2
2
2
2
2
2
2
2
2
2
SD
DOL/HD
DOL
DOL
DOL / HD
S-D
DOL/HD
S-D/HD
S-D
S-D/HD
DOL
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
TOR
MP
TOR
INSUM
INSUM
MP
TOR
TOR
INSUM
MP
TOR
MB4050SD2.1af
MP4050HD2.1af
MB4050NS2.1af
MB4050NSIN2.1af
MB4050HDIN2.1af
MP4050SD2.1af
MB4050HD2.1af
MB4050SDHD2.1af
MB4050SDIN2.1af
MP4050SDHD2.1af
MB4065NS2.1
24/08/01
11/07/01
11/07/01
14/11/01
14/11/01
24/08/01
24/08/01
30/08/01
31/08/01
30/08/01
25/02/00
415
80
DOL
MCCB
TOR
MB4180NS2.1
25/02/00
440
50
2
2
2
2
2
2
2
2
2
2
DOL/HD
DOL
DOL
DOL/HD
S-D
S-D
DOL/HD
S-D/HD
S-D
S-D/HD
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MP
TOR
INSUM
INSUM
TOR
MP
TOR
TOR
INSUM
MP
30 ... 355
0.37 ... 355
0.37 ... 355
0.37 ... 355
5.5 ... 355
45 ... 355
0.37 ... 355
45 ... 355
45 ... 355
45 ... 355
MP4450HD2.1af
MB4450NS2.1af
MB4450NSIN2.1af
MB4450HDIN2.1af
MB4450SD2.1af
MP4450SD2.1af
MB4450HD2.1af
MB4450SDHD2.1af
MB4450SDIN2.1af
MP4450SDHD2.1af
11/07/01
19/09/01
14/11/01
14/11/01
19/09/01
24/08/01
19/09/01
30/08/01
31/08/01
30/08/01
500
50
2
2
2
2
2
2
2
2
2
2
S-D
DOL/HD
DOL
DOL
DOL /HD
S-D
DOL/HD
S-D/HD
S-D
S-D/HD
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
TOR
MP
TOR
INSUM
INSUM
MP
TOR
TOR
INSUM
MP
MB5050SD2.1af
MP5050HD2.1af
MB5050NS2.1af
MB5050NSIN2.1af
MB5050HDIN2.1af
MP5050SD2.1af
MB5050HD2.1af
MB5050SDHD2.1af
MB5050SDIN2.1af
MP5050SDHD2.1af
24/0801
11/07/01
11/07/01
14/11/01
14/11/01
24/08/01
24/08/01
30/08/01
31/08/01
30/08/01
690
50
2
2
2
2
2
2
2
2
2
2
DOL/HD
DOL
DOL/HD
S-D
DOL
DOL/HD
S-D
S-D/HD
S-D
S-D/HD
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
TOR
INSUM
INSUM
TOR
TOR
MP
MP
TOR
INSUM
MP
MB6950HD2.1af
MB6950NSIN2.1af
MB6950HDIN2.1af
MB6950SD2.1af
MB6950NS2.1af
MP6950HD2.1af
MP6950SD2.1af
MB6950SDHD2.1af
MB6950SDIN2.1af
MP6950SDHD2.1af
24/08/01
14/11/01
14/11/01
27/0801
11/07/01
11/07/01
24/08/01
30/08/01
31/08/01
30/08/01
Glossary
SCPD
Home
Fuse
MCCB
MMS
Magnetic only
Softstarters UL Comb.
MCB
HD
NS
SD
Heavy Duty
Normal Start
Star Delta
Prolim
Isomax
MP
MCCB
IN
TOR
Current limiter
SACE isomax S
MCCB + Electronic Motor
Protection
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
STAR-DELTA STARTERS
400 V - 35 kA - Normal start - up, type : 2
Note : MB4035SD2.1af
mccb+AF contactor
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Ie [A]
11.5
15.2
22
28.5
36
42
56
68
68
83
98
135
158
193
132
232
160
282
200
349
250
430
290
520
315
545
355
610
Moulded Case
Circuit-Breaker
Type
Contactors
Thermal Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In125 *
S3N160 In125 *
S3N160 In125 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S4N250 PR211-I
In250
S5N400 PR211-I
In400
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I
In630
S6N630 PR211-I
In630
S6N800 PR211-I
In800
Type
Current
setting
range
[A]
210
260
325
415
540
680
820
1040
900
1050
1250
1700
2000
2500
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145
A9
A9
A9
A 16
A 26
A 26
A 30
A 30
A30
A30
A40
A75
A95
A95
[mm]
10
10
10
10
10
10
10
10
20
20
20
20
20
15
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20
TA25DU14**
TA25DU19**
TA42DU25**
TA75DU32**
TA75DU42**
TA75DU52**
TA75DU63**
TA75DU80**
TA80DU52
TA80DU52
TA80DU63
TA110DU90
TA110DU110
TA200DU135
[A]
10-14
13-19
18-25
22-32
29-42
36-52
45-63
60-80
36 - 52
36 - 52
45 - 63
66 - 90
80 - 110
100 - 135
3000
A145
A145
A110
15
20
TA200DU175
130 - 175
4000
A210
A210
A145
15
15
TA200DU175
130 - 175
4800
A210
A210
A185
15
15
TA450DU235
165 - 235
6300
AF400
AF400
A210
10
15
E500DU500
150 - 500
7560
AF400
AF400
A260
10
15
E500DU500
150 - 500
7560
AF400
AF400
A260
10
15
E500DU500
150 - 500
8000
AF400
AF400
A260
10
15
E500DU500
150 - 500
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DOL STARTERS
400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4035HD2.1af
Isomax+AF+EOL
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.1
1.5
1.9
2.8
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
132
232
160
282
200
349
250
430
Type
Magnetic
tripping
current
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S5N400 PR211-I
In320
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I
Contactor
Type
Thermal Overload
Relay
Safety
clearance
Type
Group
Current
Max.
setting range Current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
TA25DU1.4 **
TA25DU1.8 **
TA25DU2.4 **
TA25DU3.1 **
TA25DU4.0 **
TA25DU5.0**
TA25DU6.5 **
TA25DU8.5 **
TA25DU11 **
TA 450SU60 (4)
TA 450SU60 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60 (1)
TA 450SU80 (1)
TA 450SU80 (1)
TA 450SU105 (1)
TA 450SU140 (1)
TA 450SU185 (1)
TA 450SU185 (1)
TA 450SU235 (1)
[A]
1 -1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 15
13 - 20
20 - 30
23 - 40
23 - 40
40 - 60
55 - 80
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
165 - 235
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
15
20
25
40
40
50
63
80
105
140
185
185
235
3840
A300
15
TA 450SU310 (1)
220 - 310
300
4800
AF 400
10
E 500DU
150 - 500
400
6300
AF 460
10
E 500DU
150 - 500
460
7560
AF 750
10
E 500DU***
150 - 500
500
7560
AF 750
10
E 800DU
250 - 800
630
8000
AF 750
10
E 800DU
250 - 800
750
9600
AF 750
10
E 800DU
250 - 800
750
9600
AF 750
10
E 800DU
250 - 800
750
In630
S6N630 PR211-I
In630
290
520
315
545
355
610
S6N800 PR211-I
In800
S6N800 PR211-I
In800
S6N800 PR211-I
In800
MB4035HD2.1af
* : magnetic only adjustable release.
** : by pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on CT
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.1
1.5
1.9
2.8
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
132
232
160
282
200
349
250
430
Type
Contactor
Magnetic
tripping
current
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 ln5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S5N400 PR211-I
In320
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I
Type
Safety
clearance
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU5.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 -1 4
13 -19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
66 - 90
80 - 110
110 - 150
130 - 175
165 - 235
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210
3840
A260
15
TA450DU310
220 - 310
260
4800
A300
15
TA450DU310
220 - 310
300
6300
AF400
10
E500DU
150 - 500
400
7560
AF580
10
E500DU**
150 - 500
500
7560
AF580
10
E800DU
250 - 800
580
8000
AF580
10
E800DU
250 - 800
580
9600
AF580
10
E800DU
250 - 800
580
9600
AF750
10
E800DU
250 - 800
750
In630
S6N630 PR211-I
In630
290
520
315
545
355
610
S6N800 PR211-I
In800
S6N800 PR211-I
In800
S6N800 PR211-I
In800
MB4035NS2.1af
* Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DIRECT-ON-LINE STARTERS
400 V - 35 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4035HD2-1af
MCCB+PR212MP+AF-cont
Rated
Output
Rated
Current
Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
I1 range
[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Current
setting
PR 212 / MP
release I3 *
Contactor
Type
[A]
600
700
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670
A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF580
AF580
AF750
Group
Safety
Max.
clearance Current
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10
Imax [A]
100
100
100
145
145
185
210
260
320
400
460
580
580
630
MP4035HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** : A300 in case of Normal Start
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610
I1 range
[A]
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
800
960
1280
1600
1920
2240
2560
3780
4410
5040
5040
5670
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactors contactor
A30
A40
A75
A95
A95
A110
A145
A185
A210
A260
A260
A260
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
[mm]
10
10
10
20
20
20
15
15
15
15
15
15
MP4035SD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
45
55
75
90
110
Ie [A]
83
98
135
158
193
132
232
160
282
200
349
250
430
290
520
315
545
355
610
Moulded Case
Circuit-Breaker
Type
Contactors
Thermal Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
[A]
[mm]
[mm]
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I
In250
S5N400 PR211-I
In320
S5N400 PR211-I
In400
S6N630 PR211-I
In630
S6N630 PR211-I
In630
S6N800 PR211-I
In800
S6N800 PR211-I
In800
S6N800 PR211-I
In800
Type
Current
setting
range
[A]
1280
1600
2200
2400
3000
A95
A95
A145
A145
A145
A95
A95
A145
A145
A145
A50
A50
A75
A95
A95
20
20
15
15
15
10
10
10
20
20
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
3840
A210
A210
A145
15
15
TA450SU140
95 - 140
4800
A210
A210
A145
15
15
TA450SU185
130 - 185
6300
AF400
AF400
A185
10
15
E500DU
150 - 500
7560
AF400
AF400
A260
10
15
E500DU
150 - 500
8000
AF400
AF400
A260
10
15
E500DU
150 - 500
9600
AF400
AF400
A260
10
15
E500DU
150 - 500
9600
AF400
AF400
AF400
10
10
E500DU
150 - 500
MB4035SDHD2.1af
* : Magnetic only adjustable release
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610
Moulded Case
Circuit-Breaker
Type
Contactors
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor
S3N160 In125 *
S3N160 In125 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I In250
S4N250 PR211-I In250
S5N400 PR211-I In400
S5N400 PR211-I In400
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N800 PR211-I In800
[A]
1050
1250
1700
2000
2500
3000
4000
4800
6300
7560
7560
8000
A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A30
A40
A75
A95
A95
A110
A145
A185
A210
A260
A260
A260
[mm]
20
20
20
20
15
15
15
15
10
10
10
10
[mm]
10
10
10
10
20
20
15
15
15
15
15
15
MB4035SDIN2.1af
* : Magnetic only adjustable release.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 31/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I In250
S5N400 PR211-I In320
S5N400 PR211-I In400
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N800 PR211-I In800
S6N800 PR211-I In800
S6N800 PR211-I In800
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF750
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
75
95
110
145
175
210
260
300
400
580
580
580
750
MB4035NSIN2.1af
* Magnetic only adjustable release
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3N160 In160 *
S3N160 In160 *
S3N250 In200 *
S3N250 In200 *
S4N250 PR211-I In250
S5N400 PR211-I In320
S5N400 PR211-I In400
S6N630 PR211-I In630
S6N630 PR211-I In630
S6N800 PR211-I In800
S6N800 PR211-I In800
S6N800 PR211-I In800
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF750
AF750
AF750
AF750
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
10
Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
80
110
145
185
200
250
300
400
460
630
750
750
750
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Type
I1 range**
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Pe [kW] Ie [A]
45
55
75
90
110
132
160
200
250
290
315
355
83
98
135
158
193
232
282
349
430
520
545
610
[A]
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactors contactor
A50
A50
A75
A95
A95
A145
A145
A185
A260
A260
A260
AF400
[mm]
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
15
10
MP4035SDHD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
STAR-DELTA STARTERS
400 V - 50 kA - Normal start - up, type : 2
Note : MB4050SD2.1af
mccb+AF contactor
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Ie [A]
11.5
15.2
22
28.5
36
42
56
68
68
83
98
135
158
193
132
232
160
282
200
349
250
430
290
520
315
545
355
610
Moulded Case
Circuit-Breaker
Type
Contactors
Thermal Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S4H250 PR211-I
In250
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6S630 PR211-I
In630
S6S630 PR211-I
In630
S6S630 PR211-I
In630
S6S800 PR211-I
In800
Type
Current
setting
range
[A]
210
260
325
415
540
680
820
1040
900
1050
1250
1700
2000
2500
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A95
A95
A110
A145
A9
A9
A9
A 16
A 26
A 26
A 30
A 30
A30
A30
A40
A75
A95
A95
[mm]
10
10
10
10
10
10
10
10
20
20
20
20
20
15
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20
TA25DU14**
TA25DU19**
TA42DU25**
TA75DU32**
TA75DU42**
TA75DU52**
TA75DU63**
TA75DU80**
TA80DU52
TA80DU52
TA80DU63
TA110DU90
TA110DU110
TA200DU135
[A]
10-14
13-19
18-25
22-32
29-42
36-52
45-63
60-80
36 - 52
36 - 52
45 - 63
66 - 90
80 - 110
100 - 135
3000
A145
A145
A110
15
20
TA200DU175
130 - 175
4000
A210
A210
A145
15
15
TA200DU175
130 - 175
4800
A210
A210
A185
15
15
TA450DU235
165 - 235
6300
AF400
AF400
A210
10
15
E500DU500
150 - 500
7560
AF400
AF400
A260
10
15
E500DU500
150 - 500
7560
AF400
AF400
A260
10
15
E500DU500
150 - 500
8000
AF400
AF400
A260
10
15
E500DU500
150 - 500
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DIRECT-ON-LINE STARTERS
400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4050HD2-1af
MCCB+PR212MP+AF-cont
Rated
Output
Rated
Current
Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
I1 range
Current
setting
PR 212 / MP
release I3 *
[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
[A]
600
700
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670
Contactor
Type
A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF580
AF580
AF580
Group
Safety
Max.
clearance Current
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10
Imax [A]
100
100
100
145
145
185
210
260
320
400
460
460
580
630
MP4050HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** : A300 in case of Normal Start.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
132
232
160
282
200
349
250
430
1.5
1.9
2.8
3.5
Type
Magnetic
tripping
current
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S6S630 PR211-I
In630
S6S630 PR211-I
Contactor
Type
Safety
clearance
Thermal Overload
Relay
Type
Group
Current
setting
range
Max.
Current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
A9
A9
A9
A9
A 16
A26
A 26
A 26
A 30
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A 95
A 110
A 145
A 185
A 210
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210
3840
A 260
15
TA450DU310
220 - 310
260
4800
A 300
15
TA450DU310
220 - 310
300
6300
AF 400
10
E 500DU
150 - 500
400
7560
AF 580
10
E 500DU**
150 - 500
500
7560
AF 580
10
E 800DU
250 - 800
580
8000
AF 580
10
E 800DU
250 - 800
580
9600
AF 580
10
E 800DU
250 - 800
580
9600
AF 750
10
E 800DU
250 - 800
750
In630
S6S630 PR211-I
In630
290
520
315
545
355
610
S6S800 PR211-I
In800
S6S800 PR211-I
In800
S6S800 PR211-I
In800
MB4050NS2.1af
* : Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800
S6S800 PR211-I In800
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF750
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
75
95
110
145
175
210
260
300
400
580
580
580
750
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
1.1
1.5
1.9
2.8
3.5
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800
S6S800 PR211-I In800
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF750
AF750
AF750
AF750
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
10
Imax [A]
1.6
2
2.5
3.2
5
6.5
8.5
11
16
20
25
32
42
50
63
80
110
145
185
200
250
300
400
460
630
750
750
750
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610
I1 range
[A]
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
800
960
1280
1600
1920
2240
2560
3780
4410
5040
5040
5670
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactors contactor
A30
A40
A75
A95
A95
A110
A145
A185
A210
A260
A260
A260
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
[mm]
10
10
10
20
20
20
15
15
15
15
15
15
MP4050SD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DOL STARTERS
400 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4050HD2.1af
Isomax+AF+EOL
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.1
1.5
1.9
2.8
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
290
315
355
520
545
610
Type
Magnetic
tripping
current
Contactor
Type
Thermal Overload
Relay
Safety
clearance
Type
Group
Current
Max.
setting range Current
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
A300
AF 400
AF 460
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
TA25DU1.4 **
TA25DU1.8 **
TA25DU2.4 **
TA25DU3.1 **
TA25DU4 **
TA25DU5**
TA25DU6.5 **
TA25DU8.5 **
TA25DU11 **
TA 450SU60 (4)
TA 450SU60 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60 (1)
TA 450SU80 (1)
TA 450SU80 (1)
TA 450SU105 (1)
TA 450SU140 (1)
TA 450SU185 (1)
TA 450SU185 (1)
TA 450SU235 (1)
TA 450SU310 (1)
E 500DU
E 500DU
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 15
13 - 20
20 - 30
23 - 40
23 - 40
40 - 60
55 - 80
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
165 - 235
220 - 310
150 - 500
150 - 500
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
15
20
25
32
40
50
63
80
105
140
185
185
235
300
400
460
7560
AF 750
10
E 500DU***
150 - 500
500
7560
AF 750
10
E 800DU
250 - 800
630
8000
9600
9600
AF 750
AF 750
AF 750
10
10
10
E 800DU
E 800DU
E 800DU
250 - 800
250 - 800
250 - 800
750
750
750
MB4050HD2.1af
* : Magnetic only adjustable release.
** : by pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on CT
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
45
55
75
90
110
Ie [A]
83
98
135
158
193
132
232
160
282
200
349
250
430
290
520
315
545
355
610
Moulded Case
Circuit-Breaker
Type
Contactors
Thermal Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S6S630 PR211-I
In630
S6S630 PR211-I
In630
S6S800 PR211-I
In800
S6S800 PR211-I
In800
S6S800 PR211-I
In800
Type
Current
setting
range
[A]
1280
1600
2200
2400
3000
A95
A95
A145
A145
A145
A95
A95
A145
A145
A145
A50
A50
A75
A95
A95
[mm]
20
20
15
15
15
[mm]
10
10
10
20
20
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140
[A]
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
3840
A210
A210
A145
15
15
TA450SU140
95 - 140
4800
A210
A210
A145
15
15
TA450SU185
130 - 185
6300
AF400
AF400
A185
10
15
E500DU
150 - 500
7560
AF400
AF400
A260
10
15
E500DU
150 - 500
8000
AF400
AF400
A260
10
15
E500DU
150 - 500
9600
AF400
AF400
A260
10
15
E500DU
150 - 500
9600
AF400
AF400
AF400
10
10
E500DU
150 - 500
MB4050SDHD2.1af
* : Magnetic only adjustable release.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
83
98
135
158
193
232
282
349
430
520
545
610
Moulded Case
Circuit-Breaker
Type
Contactors
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S4H250 PR211-I In250
S5H400 PR211-I In400
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
[A]
1050
1250
1700
2000
2500
3000
4000
4800
6300
7560
7560
8000
A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A95
A95
A95
A110
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A30
A40
A75
A75
A95
A110
A145
A185
A210
A260
A260
A260
[mm]
20
20
20
20
15
15
15
15
10
10
10
10
[mm]
10
10
10
10
20
20
15
15
15
15
15
15
MB4050SDIN2.1af
* : Magnetic only adjustable release.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 31/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Pe
[kW]
Ie [A]
45
55
75
90
110
132
160
200
250
290
315
355
83
98
135
158
193
232
282
349
430
520
545
610
Type
I1 range**
[A]
S4H160 PR212-MP In100
S4H160 PR212-MP In160
S4H160 PR212-MP In160
S4H250 PR212-MP In200
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S5H400 PR212-MP In320
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
S6H800 PR212-MP In630
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
Delta
setting
contactor contactor
PR212 /
type
type
MP
release I3 *
[A]
900
1120
1440
1800
2240
2560
2880
3780
5040
5670
5670
5670
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A50
A50
A75
A95
A95
A145
A145
A185
A260
A260
A260
AF400
[mm]
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
15
10
MP4050SDHD2.1af
* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 65 kA - Normal start - up, type : 2
Note : MB4065NS2.1
MCCB+TOR
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.1
1.5
1.9
2.8
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
132
232
160
282
200
349
250
430
290
520
315
545
355
610
Type
Magnetic
tripping
current
[A]
21
26
33
42
65
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800
S6H800 PR211-I
In800
Contactor
Type
Safety
clearance
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
A9
A9
A9
A9
[mm]
10
10
10
10
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
Imax [A]
1.4
1.8
2.4
3.1
A 16
10
TA25DU4
2.8 - 4
A 16
10
TA25DU5
3.5 - 5
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
A 26
A 26
A 30
A 50
A 50
A 50
A 50
A 50
A 50
A 63
A 75
A 145
A 145
A 145
A 185
A 210
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA200DU110
TA200DU110
TA200DU150
TA200DU175
TA450DU235
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
80 - 110
80 - 110
110 - 150
130 - 175
165 - 235
6.5
8.5
11
14
19
25
32
42
50
63
75
110
110
145
175
210
3840
A 260
15
TA450DU310
220 - 310
260
4800
A 300
15
TA450DU310
220 - 310
300
6300
EH 370
40
T450DU400
285 - 400
400
7560
EH 550
40
T900DU500
355 - 500
500
8000
EH 550
40
T900DU650
465 - 650
550
9600
EH 700
40
T900DU650
465 - 650
650
9600
EH 700
40
T900DU650
465 - 650
650
MB4065NS2.1
* : Magnetic only adjustable release.
Created 14/01/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 25/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line Starters
415 V - 80 kA - Normal start - up, type : 2
Note : MB4180NS2.1
MCCB+TOR
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
1.1
1.5
1.9
2.8
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
5
6.6
8.6
11.5
15.2
22
28.5
36
42
56
68
83
98
135
158
193
232
282
349
430
520
545
610
Type
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3L160 In160 *
S3L160 In160 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L800 PR211-I In800
S6L800 PR211-I In800
S6L800 PR211-I In800
Magnetic
tripping
current
[A]
21
26
33
42
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
8000
9600
9600
Contactor
Type
Safety
clearance
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
A9
A9
A9
A 16
[mm]
10
10
10
10
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
Imax [A]
1.4
1.8
2.4
3.1
A 26
10
TA25DU4
2.8 - 4
A 26
10
TA25DU5
3.5 - 5
A 26
A 26
A 30
A 50
A 50
A 50
A 50
A 50
A 50
A 63
A 75
A 145
A 145
A 145
A 185
A 210
A 260
A 300
EH 370
EH 550
EH 550
EH 700
EH 700
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
40
40
40
40
40
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA200DU110
TA200DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
T450DU400
T900DU500
T900DU650
T900DU650
T900DU650
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
80 - 110
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
285 - 400
355 - 500
465 - 650
465 - 650
465 - 650
6.5
8.5
11
14
19
25
32
42
50
63
75
110
110
145
175
210
260
300
400
500
550
650
650
MB4180NS2.1
* : Magnetic only adjustable release.
Created 24/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 25/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DIRECT-ON-LINE STARTERS
440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP4450HD2-1af
MCCB+PR212MP+AF-cont
Rated
Output
Rated
Current
Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
52
63
75
90
120
147
177
212
260
320
370
436
500
549
Type
I1 range
Current
setting
PR 212 / MP
release I3 *
[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
[A]
600
700
800
960
1280
1600
1920
2240
2880
3780
4410
5040
5040
5670
Contactor
Type
A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF460
AF580
AF580
Group
Safety
Max.
clearance Current
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10
Imax [A]
100
100
100
145
145
185
210
260
320
400
460
460
580
580
MP4450HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
**: A300 in case of Normal Starter.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
Ie [A]
1
1.4
1.7
2.2
3.0
4.4
5.7
4
5.5
7.5
7.8
10.5
13.5
11
15
18,5
22
30
37
45
55
75
90
110
19
26
32
38
52
63
75
90
120
147
177
132
212
160
260
200
320
250
410
290
448
315
500
355
549
Magnetic
tripping
current
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800
Contactor
Type
Safety
clearance
Overload
Relay
Type
Group
Current
Max.
setting range Current
[A]
21
26
33
42
52
65
84
84
145
210
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA42DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU175
TA450DU235
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3,5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
130 - 175
165 - 235
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
6.5
11
14
14
16
25
32
42
45
63
70
90
100
135
175
210
3200
A260
15
TA450DU235
165 - 235
235
4000
A300
15
TA450DU310
220 - 310
300
4800
AF 400
10
6300
6300
AF 580
AF 580
10
10
E 500DU
TA450DU400
E 500DU**
E 800DU
TA900DU500
150 - 500
285 - 400
150 - 500
250 - 800
355 - 500
400
400
500
580
500
7560
7560
AF 580
AF 580
10
10
E 500DU**
E 800DU
TA900DU500
150 - 500
250 - 800
355 - 500
500
580
500
8000
AF 580
10
9600
AF 580
10
E 800DU
TA900DU650
E 800DU
TA900DU650
250 - 800
465 - 650
250 - 800
465 - 650
580
580
580
580
MB4450NS2.1af
* Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 19/09/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
1
1.4
1.7
2.2
3
4.4
5.7
7.8
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
212
260
320
410
448
500
549
Type
Magnetic
tripping
current
[A]
21
26
33
42
52
65
84
145
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000
3200
4000
4800
6300
7560
8000
9600
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H800 PR211-I In800
S6H800 PR211-I In800
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A63
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF580
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
Imax [A]
1.6
2
2.5
3.2
4
5
6.5
11
16
16
25
32
42
45
63
70
93
100
145
185
210
240
280
400
580
580
580
580
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
1
1.4
1.7
2.2
3
4.4
5.7
7.8
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
212
260
320
410
448
500
549
Type
Magnetic
tripping
current
[A]
21
26
33
42
52
65
84
145
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000
3200
4000
4800
6300
7560
8000
9600
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H800 PR211-I In800
S6H800 PR211-I In800
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A30
A50
A50
A63
A63
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF580
AF750
AF750
AF750
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
10
10
10
10
10
10
Imax [A]
1.6
2
2.5
3.2
4
5
6.5
11
16
16
25
32
42
45
63
80
100
125
185
200
240
280
400
400
580
630
750
750
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
STAR-DELTA STARTERS
440 V - 50 kA - Normal start - up, type : 2
Note : MB4450SD2.1af
mccb+AF contactor
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
Ie [A]
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
212
260
320
410
290
315
355
448
500
549
Moulded Case
Circuit-Breaker
Type
Contactors
Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 **
S3H160 In125 **
S3H250 In200 **
S3H250 In200 **
S4H250 PR211-I In250
S4H250 PR211-I In250
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
[A]
210
210
325
415
540
680
820
1040
950
1150
1600
1850
2500
3000
4000
4800
6300
6300
6300
7560
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A95
A95
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A 9*
A 9*
A 9*
A 16*
A 16*
A 26*
A 26*
A 30*
A30*
A40*
A75*
A75*
A95
A110
A145
A185
A210
[mm]
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
15
10
A260
A260
A260
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
10
15
10
15
10
15
Type
[A]
TA25DU14***
10-14
TA25DU14^***
10-14
TA42DU25***
18-25
TA75DU32***
22-32
TA75DU42***
29-42
TA75DU52***
36-52
TA75DU63***
45-63
TA75DU80***
60-80
TA80DU52
36 - 52
TA80DU63
45 - 63
TA80DU80
60 - 80
TA200DU110 80 - 110
TA200DU110 80 - 110
TA200DU135 100 - 135
TA200DU175 130 - 175
TA450DU235 165 - 235
E500DU500
150 - 500
TA450DU310
220 - 310
E500DU500
150 - 500
TA450DU310
220 - 310
E500DU500
150 - 500
TA450DU310
220 - 310
E500DU500
150 - 500
TA450DU400
285 - 400
MB4450SD2.1af
* : Using mounting kits, use Star-contactor size same as Delta-contactor size.
** : Magnetic only adjustable release
** : Connect the OR between the MCCB and the Line-Delta node.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 19/09/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Current
setting
range
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
75
90
120
147
177
212
260
320
410
448
500
549
Type
I1 range
[A]
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
700
960
1120
1440
1600
1920
2560
3780
3780
4410
5040
5040
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A30
A40
A75
A75
A95
A110
A145
A185
A210
A260
A260
A260
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
[mm]
10
10
10
10
20
20
15
15
15
15
15
15
MP4450SD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DOL STARTERS
440 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB4450HD2.1af
Isomax+AF+EOL
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
Ie [A]
1
1.4
1.7
2.2
3
4.4
5.7
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
7.8
10.5
13.5
19
26
32
38
52
63
75
90
120
147
177
132
212
160
260
200
320
250
410
290
448
315
500
355
549
Magnetic
tripping
current
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In4
S2X80 In5
S2X80 In6.5
S2X80 In6.5
S2X80 In11
S2X80 In16
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800
Contactor
Type
Safety
clearance
Overload
Relay
Type
Group
Current
Max.
setting range Current
[A]
21
26
33
42
52
65
84
84
145
210
210
325
415
540
680
820
1040
1150
1400
1920
2300
3000
A9
A9
A9
A9
A16
A26
A26
A30
A30
A30
A30
A30
A50
A50
A50
A63
A95
A110
A145
A185
A210
A260
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
15
15
15
15
TA25DU1.4 **
TA25DU1.8 **
TA25DU2.4 **
TA25DU3.1 **
TA25DU4 **
TA25DU5 **
TA25DU6.5 **
TA25DU8.5 **
TA25DU11 **
TA25DU14 **
TA 450SU60 (4)
TA 450SU80 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60
TA 450SU80
TA 450SU105
TA 450SU105
TA 450SU140
TA 450SU185
TA 450SU235
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
10 - 15
18 - 27
20 - 30
28 - 40
28 - 40
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
130 - 185
165 - 235
Imax [A]
1.4
1.8
2.4
3.1
4
5
6.5
6.5
11
14
15
25
30
40
40
60
80
100
105
140
185
235
3200
A300
15
TA 450SU235
165 - 235
235
4000
AF 400
10
4800
AF 460
10
6300
6300
AF 580
AF 580
10
10
E 500DU
TA450SU310
E 500DU
TA450SU400
E 500DU***
E 800DU
TA900SU500
150 - 500
220 - 310
150 - 500
285 - 400
150 - 500
250 - 800
355 - 500
400
310
400
400
500
580
500
7560
7560
AF 750
AF 750
10
10
E 500DU***
E 800DU
TA900SU500
150 - 500
250 - 800
355 - 500
500
630
500
8000
AF 750
10
9600
AF 750
10
E 800DU
TA900SU650
E 800DU
TA900SU650
250 - 800
465 - 650
250 - 800
465 - 650
750
650
750
650
MB4450HD2.1af
* : Magnetic only adjustable release.
** : by pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on CT
Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 19/09/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
45
55
75
90
110
Ie [A]
75
90
120
147
177
132
212
160
260
200
320
250
410
290
315
355
448
500
549
Moulded Case
Circuit-Breaker
Type
Contactors
Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I
In250
S5H400 PR211-I
In320
S5H400 PR211-I
In400
S5H400 PR211-I
In400
S6H630 PR211-I
In630
S6H630 PR211-I
In630
S6H800 PR211-I
In800
S6H800 PR211-I
In800
Type
Current
setting
range
[A]
1150
1400
2000
2400
3000
A95
A95
A145
A145
A145
A95
A95
A145
A145
A145
A50**
A50**
A50**
A95
A95
[mm]
20
20
15
15
15
[mm]
10
10
10
10
20
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU140
[A]
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
3200
A210
A210
A145
15
15
TA450SU140
95 - 140
4000
A210
A210
A145
15
15
TA450SU185
130 - 185
4800
A210
A210
A185
15
15
TA450SU235
165 - 235
6300
AF400
AF400
A260
10
15
E500DU500
150 - 500
TA450SU310
220 - 310
E500DU500
150 - 500
TA450SU310
220 - 310
E500DU500
150 - 500
TA450SU310
220 - 310
E500DU500
150 - 500
TA450SU400
285 - 400
7560
AF400
8000
AF400
9600
AF580
AF400
AF400
AF580
A260
A260
A260
10
10
10
15
15
15
MB4450SDHD2.1af
* : Magnetic only adjustable release.
** : using mounting kits, use star contactor size same as delta contactor size
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/09/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
75
90
120
147
177
212
260
320
410
448
500
549
Moulded Case
Circuit-Breaker
Type
Contactors
Line
Delta
Star
Safety
Safety
Magnetic
contactor
contactor
contactor
clearance
clearance
tripping
type
type
type**
Line-Delta
Star
current
contactor contactor
S3H160 In125 *
S3H160 In125 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S4H250 PR211-I In250
S5H400 PR211-I In400
S5H400 PR211-I In400
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H630 PR211-I In630
S6H630 PR211-I In630
[A]
950
1150
1600
1850
2500
3000
4000
4800
6300
6300
6300
7560
A95
A95
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A95
A95
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A30
A40
A50
A75
A95
A110
A110
A185
A210
A260
A260
A260
[mm]
20
20
15
15
15
15
15
15
10
10
10
10
[mm]
10
10
10
10
20
20
20
15
15
15
15
15
MB4450SDIN2.1af
* : Magnetic only adjustable release.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Type
I1 range**
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
315 - 630
Pe [kW] Ie [A]
45
55
75
90
110
132
160
200
250
290
315
355
75
90
120
147
177
212
260
320
410
448
500
549
[A]
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
800
960
1280
1600
1920
2240
2880
3780
4410
5040
5040
5670
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A50
A50
A50
A95
A95
A145
A145
A185
A260
A260
A260
A260
[mm]
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
20
20
15
15
15
15
15
15
15
MP4450SDHD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
STAR-DELTA STARTER
500 V - 50 kA - Normal start - up, type : 2
Note : MB5050SD2.1af
mccb+AF contactor
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
Moulded Case
Circuit-Breaker
Type
Contactors
Thermal Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type* Line-Delta
Star
contactor contactor
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In400
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
[A]
145
210
325
415
540
540
680
800
900
1050
1400
1700
2000
2500
3000
4000
4800
5040
6300
6300
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A145
A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
A 30
A 30
A 30
A 50
A 50
A 50
A 63
A 75
A145
A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
A9
A9
A9
A 12
A 16
A 16
A 26
A 30
A30
A30
A50
A75
A95
A95
A110
A145
A185
A210
A210
A260
[mm]
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
10
10
10
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
20
20
20
15
15
15
15
15
Type
TA25DU11**
TA25DU14**
TA42DU19**
TA75DU25**
TA75DU42**
TA75DU42**
TA75DU52**
TA75DU63**
TA80DU52
TA80DU52
TA80DU80
TA110DU90
TA200DU110
TA200DU135
TA200DU150
TA200DU175
TA450DU235
E500DU500
E500DU500
E500DU500
MB5050SD2.1af
*: Using mounting kits, use Star-contactor size same as Delta-contactor size.
**: Connect the TOL between the MCCB and the Line-Delta node.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Current
setting
range
[A]
7.5-11
10-14
13-19
18-25
29-42
29-42
36-52
45-63
36 - 52
36 - 52
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
150 - 500
150 - 500
150 - 500
DIRECT-ON-LINE STARTERS
500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP5050HD2-1af
MCCB+PR212MP+AF-cont
Rated
Output
Rated
Current
Pe [kW]
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
45
56
67
82
110
132
158
192
230
279
335
395
415
451
Type
I1 range
Current
setting
PR 212 / MP
release I3 *
[A]
50 - 100
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
[A]
600
600
700
800
1280
1440
1800
2240
2560
2880
3780
4410
4410
5040
Contactor
Type
A145
A145
A145
A145
A145
A145
A185
A210
A260
AF400**
AF400
AF460
AF460
AF580
Group
Safety
Max.
clearance Current
[mm]
15
15
15
15
15
15
15
15
15
10
10
10
10
10
Imax [A]
100
100
100
100
145
145
170
210
240
320
400
460
460
580
MP5050HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
** : A300 in case of Normal Starter.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
O.88
1.2
1.5
2.2
2.8
2.2
3
4
5.5
7.5
11
15
4
5.2
6.9
9.1
12.2
17.5
23
18,5
22
30
37
45
55
29
34
45
56
67
82
75
90
110
132
160
200
250
290
110
132
158
192
230
279
335
394
315
355
440
483
Type
Magnetic
tripping
current
Contactor
Type
Safety
clearance
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
[A]
21
21
26
42
42
42
65
84
110
145
210
325
415
415
540
540
680
800
1050
1250
1250
1700
2050
2400
3000
3840
4800
5040
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A50
A63
A75
A145
A145
A145
A145
A145
A185
A210
A260
A300
AF 400
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
10
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA75DU25
TA75DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU63
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU150
TA200DU175
TA 450DU235
TA 450DU310
TA 450DU310
E 500DU
[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
Imax [A]
1
1.4
1.8
2.4
3.1
3.2
5
6.5
8.5
11
14
19
25
32
42
42
52
63
80
90
110
135
145
170
210
240
280
400
6300
AF 580
10
E 500DU**
150 - 500
500
6300
AF 580
10
E 800DU
250 - 800
580
7560
AF 580
10
E 500DU**
150 - 500
500
7560
AF 580
10
E 800DU
250 - 800
580
7560
AF 580
10
E 500DU**
150 - 500
500
7560
AF 580
10
E 800DU
250 - 800
580
MB5050NS2.1af
* : Magnetic only adjustable release.
** Mounting kit between Contactor and Relay is not available
Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 10/07/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
O.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
Type
Magnetic
tripping
current
[A]
21
21
26
42
42
65
84
110
145
210
325
415
540
540
680
800
1050
1250
1700
2050
2400
3000
3840
4800
5040
6300
7560
7560
S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A50
A50
A50
A63
A63
A63
A75
A145
A145
A145
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
10
10
10
10
Imax [A]
1.6
1.6
2
3.2
3.2
5
6.5
8.5
11
16
25
32
42
42
52
63
125
125
145
145
170
210
240
280
400
580
580
580
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
O.88
1.2
1.5
2.2
2.8
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
440
483
Type
Magnetic
tripping
current
[A]
21
21
26
42
42
65
84
110
145
210
325
415
540
540
680
800
1050
1250
1700
2050
2400
3000
3840
4800
5040
6300
7560
7560
S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
Contactor
Type
A9
A9
A16
A26
A26
A26
A26
A30
A30
A50
A50
A50
A63
A63
A63
A75
A145
A145
A145
A185
A210
A260
A300
AF400
AF460
AF750
AF750
AF750
Group
Safety
Max.
clearance Current
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
10
10
10
10
10
Imax [A]
1.6
1.6
2
3.2
3.2
5
6.5
8.5
11
16
25
32
42
42
52
63
125
125
145
170
200
240
280
400
460
630
630
630
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
67
82
110
132
158
192
230
279
335
394
440
483
Type
I1 range
[A]
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
700
800
1120
1280
1600
1920
2240
2560
3780
3780
4410
4410
A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A30
A30
A50
A75
A95
A95
A110
A145
A185
A210
A210
A260
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
[mm]
10
10
10
10
20
20
20
15
15
15
15
15
MP5050SD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DOL STARTERS
500 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB5050HD2.1af
Isomax+AF+EOL
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
Ie [A]
O.88
1.2
1.5
2.2
2.8
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
4
5.2
6.9
9.1
12.2
17.5
23
29
34
45
56
67
82
110
132
158
192
230
279
335
394
315
355
440
483
Magnetic
tripping
current
Contactor
Type
Thermal Overload
Relay
Safety
clearance
Type
Group
Current
Max.
setting range Current
S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
[A]
21
21
26
42
42
42
65
84
110
145
210
325
415
540
540
680
800
1050
1250
1700
2050
2400
3000
3840
4800
5040
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A145
A145
A145
A185
A210
A260
A300
AF 400
AF 460
[mm]
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
10
10
TA25DU1.0**
TA25DU1.4**
TA25DU1.8**
TA25DU2.4**
TA25DU3.1**
TA25DU4**
TA25DU5**
TA25DU6.5**
TA25DU8.5**
TA25DU11**
TA 450SU60 (4)
TA 450SU60 (3)
TA 450SU60 (2)
TA 450SU80 (2)
TA 450SU80 (2)
TA 450SU60 (1)
TA 450SU60 (1)
TA 450SU80 (1)
TA 450SU105 (1)
TA 450SU140 (1)
TA 450SU185 (1)
TA 450SU185 (1)
TA 450SU235 (1)
TA 450SU310 (1)
E 500DU
E 500DU
[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 15
13 - 20
20 - 30
27.5 - 40
27.5 - 40
40 - 60
40 - 60
55 - 80
70 - 105
95 - 140
130 - 185
130 - 185
165 - 235
220 - 310
150 - 500
150 - 500
Imax [A]
1
1.4
1.8
2.4
3.1
3.2
5
6.5
8.5
11
15
20
30
40
40
52
60
80
105
140
170
185
235
280
400
460
6300
AF 750
10
E 500DU***
150 - 500
500
6300
AF 750
10
E 800DU
250 - 800
630
7560
AF 750
10
E 500DU***
150 - 500
500
7560
AF 750
10
E 800DU
250 - 800
630
7560
AF 750
10
E 500DU***
150 - 500
500
7560
AF 750
10
E 800DU
250 - 800
630
MB5050HD2.1af
* : Magnetic only adjustable release.
** : provide by-pass contactor on the TOR during starting, same size as the line contactor
*** Mounting kit between Contactor and Relay is not available.
(x) : number of primary turns on the CT
Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Moulded Case
Circuit-Breaker
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
67
82
110
132
158
192
230
279
335
394
440
483
Type
Contactors
Thermal Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
[A]
1150
1250
1800
2200
2400
3000
3840
4000
5040
6300
6300
7560
A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A145
A145
A145
A145
A145
A145
A210
A210
AF400
AF400
AF400
AF400
A50
A50
A50
A75
A95
A95
A145
A145
A185
A210
A260
A260
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
[mm]
10
10
10
10
20
20
15
15
15
15
15
15
Type
TA450SU80**
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
TA450SU140
TA450SU185
E500DU
E500DU
E500DU
E500DU
Current
setting
range
[A]
27.5 - 40
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
95 - 140
130 - 185
150 - 500
150 - 500
150 - 500
150 - 500
MB5050SDHD2.1af
* : Magnetic only adjustable release.
** : 2 cable turns on CT.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
Ie [A]
67
82
110
132
158
192
230
279
335
394
440
483
Type
I1 range**
[A]
50 - 100
50 - 100
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
700
900
1280
1440
1800
2240
2560
2880
3780
4410
4410
5040
A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
Delta
contactor
type
A145
A145
A145
A145
A145
A210
A210
A210
AF400
AF400
AF400
AF400
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A50
A50
A50
A75
A95
A95
A145
A145
A185
A210
A260
A260
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
[mm]
10
10
10
10
20
20
15
15
15
15
15
15
MP5050SDHD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DOL STARTERS
690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MB6950HD2.1af
Isomax+AF+EOL
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
200
202
250
242
290
301
315
313
355
370
400
420
450
470
500
500
Moulded Case
Circuit-Breaker
Type
Magnetic
tripping
current
S2X80 In1
S2X80 In1
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In4
S2X80 In5
S2X80 In6.5
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I
In250
S4X250 PR211-I
In250
S6X400 PR211-I
In320
S6X400 PR211-I
In400
S6X400 PR211-I
In400
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
Contactor
Type
Safety
clearance
Overload Relay
Type
[A]
13
13
21
26
33
52
65
84
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
A9
A9
A9
A9
A16
A26
A26
A30
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A185
A210
A210
[mm]
10
10
10
10
10
10
10
10
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
TA25DU0.63***
TA25DU1***
TA25DU1.4***
TA25DU1.8***
TA25DU2.4***
TA25DU4*** (a)
TA25DU5*** (a)
TA25DU6.5***(a)
TA 450SU60
TA 450SU60
TA 450SU60
TA 450SU60
TA 450SU80
TA 450SU60
TA 450SU80
TA 450SU60
TA 450SU60
TA 450SU80
TA 450SU105
TA 450SU105
TA 450SU140
TA 450SU185
TA 450SU185
3000
A260
15
3840
AF 400
10
4800
AF 400
10
4800
AF 460
10
6300
6300
AF 580
AF 580
10
10
6300
6300
AF 580
AF 580
7560
7560
7560
N of
Current
Max.
primary setting range Current
turns
on CT
7**
5**
4**
3**
3
2
2
1
1
1
1
1
1
1
1
[A]
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6.5
5.7 - 8.6
8 - 12
10 - 15
13 - 20
18 - 27
20 - 30
27.5 - 40
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
130 - 185
130 - 185
Imax [A]
0.63
1
1.4
1.8
2.4
4
5
6.5
8.6
12
15
20
27
30
40
60
60
80
105
105
140
185
185
TA 450SU235
165 - 235
220
E 500DU
TA450SU310
E 500DU
TA450SU310
E 500DU
TA450SU400
E 500DU (X)
E 800DU
TA450SU400
150 - 500
220 - 310
150 - 500
220 - 310
150 - 500
285 - 400
150 - 500
250 - 800
285 - 400
320
310
350
310
400
400
500
500
400
10
10
E 500DU (X)
E 800DU
TA900SU500
1
1
150 - 500
250 - 800
355 - 500
500
500
500
AF 750
AF 750
10
10
E 500DU (X)
E 800DU
TA900SU500
1
1
150 - 500
250 - 800
355 - 500
500
630
500
AF 750
10
E 800DU
TA900SU650
250 - 800
465 - 650
630
650
1
1
1
1
MB6950HD2.1af
* : Magnetic only adjustable release.
** : Cable cross section 4.0 mm2
*** : Use by-pass contactor during motor start-up : A9 < 1.1kW / A16 < 4kW
(X) Mounting kit between Contactor and Relay is not available.
(a) : type 1 coordination, type 2 by the relevant MCB (MO325) table
Home
Fuse
MCCB
Group
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
Magnetic
tripping
current
[A]
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
4800
4800
6300
6300
7560
7560
S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
Contactor
Type
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A145
A185
A185
A210
AF400
AF400
AF400
AF580
AF580
AF580
AF750
Group
Safety
Max.
clearance Current
[mm]
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
Imax [A]
25
25
25
25
50
50
50
100
100
100
120
120
120
170
170
210
320
350
350
500
500
500
630
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
Magnetic
tripping
current
[A]
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
4800
4800
6300
6300
7560
7560
S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
Contactor
Type
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A185
A210
A210
A260
AF400
AF400
AF460
AF580
AF580
AF750
AF750
Group
Safety
Max.
clearance Current
[mm]
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
Imax [A]
25
25
25
25
50
50
50
100
100
100
120
120
170
200
210
220
320
350
400
500
500
630
630
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
Ie [A]
6.7**
8.8**
13**
18**
21
25
33
41
49
60
80
95
115
139
167
202
250
242
290
301
315
313
355
370
400
420
450
470
500
500
Moulded Case
Circuit-Breaker
Type
Contactors
Overload
Relay
Magnetic
Line
Delta
Star
tripping contactor contactor contactor
current
type
type
type***
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I
In250
S6X400 PR211-I
In400
S6X400 PR211-I
In400
S6X400 PR211-I
In400
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
S6X630 PR211-I
In630
KORC
type
turns
on
CT
[A]
110
140
200
280
320
380
500
620
620
750
1000
1200
1440
1750
2100
2550
A 95
A 95
A 95
A 95
A 145
A 145
A 145
A 145
A145
A145
A145
A145
A145
A145
A145
A185
A 95
A 95
A 95
A 95
A 145
A 145
A 145
A 145
A145
A145
A145
A145
A145
A145
A145
A185
A 26
A 26
A 26
A 26
A 30
A 30
A 30
A 30
A30
A40
A50
A75
A75
A95
A110
A110
4L
185R/4
185R/4
185R/4
185R/4
185R/4
185R/4
185R/4
185R/4
-
n
13
10
7
7
6
6
6
4
-
3200
AF400
AF400
A145
4000
AF400
AF400
A145
4000
AF400
AF400
A185
5040
AF400
AF400
A210
6300
AF460
AF460
A210
6300
AF460
AF460
A260
6300
AF460
AF460
A260
TOL
type
Current
setting
range
TA25DU2.4****
TA25DU2.4****
TA25DU2.4****
TA25DU3.1****
TA25DU3.1****
TA25DU4****
TA25DU5****
TA25DU4****
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA200DU110
TA200DU110
TA200DU135
[A]
6-8.5
7.9-11.1
11.2-15.9
15.2-20.5
17.7-23.9
21.6-30.8
27-38.5
32.4-46.3
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
80 - 110
80 - 110
100 - 135
E500DU500
TA200DU150
E500DU500
TA200DU200
E500DU500
TA200DU200
E500DU500
TA450DU235
E500DU500
TA450DU310
E500DU500
TA450DU310
E500DU500
TA450DU310
150 - 500
110 - 150
150 - 500
150 - 200
150 - 500
150 - 200
150 - 500
165 - 235
150 - 500
220 - 310
150 - 500
220 - 310
150 - 500
220 - 310
MB6950SD2.1af
* : Magnetic only adjustable release.
** : Cable section equal to 4 mm2
***: Using mounting kits, use Star-contactor size same as Delta-contactor size.
****: Connect the TOL between the MCCB and the Line-Delta node.
Created 29/06/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/09/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Contactor
Magnetic
tripping
current
Type
Safety
clearance
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
Ie [A]
0.6
0.9
1.1
1.6
2
2.9
3.8
5
6.7
8.8
13
18
21
25
33
41
49
60
80
95
115
139
167
202
242
S2X80 In1
S2X80 In1
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In4
S2X80 In5
S2X80 In6.5
S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
[A]
13
13
21
26
33
52
65
84
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
A9
A9
A9
A9
A16
A26
A26
A30
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A145
A185
A185
A210
AF 400
[mm]
10
10
10
10
10
10
10
10
20
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
10
290
301
4800
AF 400
10
315
313
4800
AF 400
10
355
370
6300
6300
AF 580
AF 580
10
10
400
420
6300
6300
AF 580
AF 580
10
10
450
470
7560
7560
AF 580
AF 580
10
10
500
500
7560
AF 750
10
KORC
(Current
transfo)
Type
N of
primary
turns
on CT
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L235R/4
13***
10***
7***
7***
6
6
6
4
4
3
2
2
2
Overload
Relay
Type
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU4 **
TA25DU5 **
TA25DU6.5 **
TA25DU2.4
TA25DU2.4
TA25DU2.4
TA25DU3.1
TA25DU3.1
TA25DU4
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA 450DU185
TA 450DU185
TA 450DU235
E 500DU
TA450DU310
E 500DU
TA450DU310
E 500DU
TA450DU400
E 500DU (X)
E 800DU
TA450DU400
E 500DU (X)
E 800DU
TA900DU500
E 500DU (X)
E 800DU
TA900DU500
E 800DU
TA900DU650
Group
Current
setting
range
Max.
Current
[A]
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1,7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6,5
6 - 8.5
7.9 - 11.1
11.2 - 15.9
15.2 - 20.5
17.7 - 23.9
21.6 - 30.8
27 - 38.5
32.4 - 46.3
40.5 - 57.8
54 - 77.1
64.8 - 92.5
81 - 115.6
103 - 147
130 - 185
130 - 185
165 - 235
150 - 500
220 - 310
150 - 500
220 - 310
150 - 500
285 - 400
150 - 500
250 - 800
285 - 400
150 - 500
250 - 800
355 - 500
150 - 500
250 - 800
355 - 500
250 - 800
465 - 650
Imax [A]
0.63
1
1.4
1.8
2.4
4
5
6.5
8.5
11.1
15.9
20.5
23.9
30.8
38.5
46.3
57.8
77.1
92.5
115.6
120
170
170
210
320
310
350
310
350
400
500
500
400
500
500
500
500
500
500
630
650
MB6950NS2.1af
* : Magnetic only adjustable release.
** : Type 1 coordination, type 2 by the relevant MCB (MO325) table
***: Cable section equal to 4.0 mm2.
(X) Mounting kit between Contactor and Relay is not available.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
DIRECT-ON-LINE STARTERS
690 V - 50 kA - Long starting (heavy duty) start - up, type : 2
Note : MP6950HD2-1af
MCCB+PR212MP+AF-cont
Rated
Output
Rated
Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
I1 range
Current
setting
PR 212 / MP
release I3 *
[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
160 - 320
200 - 400
200 - 400
315 - 630
315 - 630
315 - 630
[A]
600
600
900
1120
1280
1440
1800
2240
2560
2880
3200
3600
4410
5040
5040
Contactor
Type
Group
Safety
Max.
clearance Current
A145
A145
A145
A145
A145
A185
A185
AF400
AF400
AF400
AF400
AF460
AF580
AF580
AF750
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
Imax [A]
100
100
100
120
120
160
170
320
320
320
350
400
500
500
650
MP6950HD2-1af
* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes when
the motor is starting-up.
X To be defined by further tests.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
I1 range
[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
200 - 400
200 - 400
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
setting
contactor
PR212 /
type
MP
release I3 *
[A]
600
600
800
960
1120
1280
1600
1920
2240
2800
3200
3780
4410
4410
5040
A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460
Delta
contactor
type
A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460
Star
Safety
Safety
contactor clearance clearance
type
Line-Delta
Star
contactor contactor
A30
A40
A50
A75
A75
A95
A110
A110
A145
A145
A185
A210
A210
A260
A260
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
[mm]
10
10
10
10
10
20
20
20
15
15
15
15
15
15
15
MP6950SD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up
In case of smaller motor powers, please refer to MMS tables.
Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 24/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Moulded Case
Circuit-Breaker
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
Contactors
Overload
Relay
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type Line-Delta
Star
contactor contactor
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
[A]
750
1000
1250
1500
1800
2200
2500
3000
3840
A145
A145
A145
A145
A145
A145
A145
A185
AF400
4800
AF400
4800
AF400
6300
AF400
6300
AF460
7560
AF580
7560
AF580
A145
A145
A145
A145
A145
A145
A145
A185
AF400
AF400
AF400
AF400
AF460
AF580
AF580
A30
A40
A50
A75
A75
A95
A110
A145
A145
A185
A185
A210
A260
A260
AF400
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
[mm]
10
10
10
10
10
20
20
15
15
15
15
15
15
15
10
MB6950SDHD2.1af
* : Magnetic only adjustable release.
** : 2 cable turns on CT
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Home
Fuse
MCCB
MMS
Softstarters UL Comb.
MCB
Type
Current
setting
range
TA450SU60**
TA450SU80**
TA450SU60
TA450SU60
TA450SU80
TA450SU105
TA450SU105
TA450SU140
[A]
20 - 30
27.5 - 40
40 - 60
40 - 60
55 - 80
70 - 105
70 - 105
95 - 140
E500DU500
150 - 500
TA450SU185
130 - 185
E500DU500
150 - 500
TA450SU185
130 - 185
E500DU500
150 - 500
TA450SU235
165 - 235
E500DU500
150 - 500
TA450SU235
165 - 235
E500DU500
150 - 500
TA450SU310
220 - 310
E800DU500
250 - 800
TA450SU310
220 - 310
E800DU800
250 - 800
TA450SU310
220 - 310
Moulded Case
Circuit-Breaker
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
Contactors
Magnetic
Line
Delta
Star
Safety
Safety
tripping contactor contactor contactor clearance clearance
current
type
type
type** Line-Delta
Star
contactor contactor
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
[A]
620
750
1000
1200
1440
1750
2100
2550
3200
4000
4000
5040
6300
6300
6300
A145
A145
A145
A145
A145
A145
A145
A185
AF400
AF400
AF400
AF400
AF460
AF460
AF460
A145
A145
A145
A145
A145
A145
A145
A185
AF400
AF400
AF400
AF400
AF460
AF460
AF460
A30
A40
A50
A75
A75
A95
A110
A110
A145
A145
A185
A210
A210
A260
A260
[mm]
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
[mm]
10
10
10
10
10
20
20
20
15
15
15
15
15
15
15
MB6950SDIN2.1af
* : Magnetic only adjustable release.
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated Rated
Output Current
Pe [kW]
45
55
75
90
110
132
160
200
250
290
315
355
400
450
500
Ie [A]
49
60
80
95
115
139
167
202
242
301
313
370
420
470
500
Type
I1 range**
[A]
50 - 100
50 - 100
50 - 100
80 - 160
80 - 160
80 - 160
100 - 200
160 - 320
160 - 320
200 - 400
200 - 400
315 - 630
315 - 630
315 - 630
315 - 630
Contactors
Current
Line
Delta
Star
Safety
Safety
setting
contactor contactor contactor clearance clearance
PR212 /
type
type
type
Line-Delta
Star
MP
contactor contactor
release I3 *
[A]
600
700
900
1120
1280
1440
1800
2240
2560
3200
3200
3780
4410
5040
5040
A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460
A145
A145
A145
A145
A145
A145
A145
AF400
AF400
AF400
AF400
AF400
AF460
AF460
AF460
A30
A40
A50
A75
A75
A95
A110
A145
A145
A185
A185
A210
A260
A260
AF400
[mm]
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
[mm]
10
10
10
10
10
20
20
15
15
15
15
15
15
15
10
MP6950SDHD2.1af
* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the
motor is starting-up.
** The protection against overload (L function) of the MP release, must be set with class 30 starting class.
In case of smaller motor powers, please refer to MMS tables
Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 30/08/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
MMS
Ue
V
Iq
kA
Coor.
type
Starting
type
SCPD
type
Size
kW
Table
Last
Update
400
16
MMS
MMS
MMS
MMS/DLA
MMS
MMS
22/11/01
22/11/01
50
Normal
Normal
Normal
Normal
Normal
Normal
MM4016NS1.1
MM4016NS2.1
400
1
2
1
2
1
2
04/02/00
04/02/00
23/10/00
23/10/00
100
25
50
100
25
25
1
2
1
2
1
2
2
2
1
2
SD
SD
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
MMS
MMS
MMS/DLA
MMS
MMS
MMS
MMS
MMS
MMS
MMS
1.1 ... 55
1.1 ... 55
0.37 ... 11
0.06 ... 55
0.06 ... 18.5
0.06 ... 22
0.06 ... 22
0.06 ... 22
0.12 .. 22
0.12 .. 22
50
100
2
2
Normal
Normal
MMS
MMS
0.06 ... 22
0.06 ... 22
MM4050NS1.1
MM4050NS2.1a
MM4050NS1.1K
MM4050NS2.1K
MM4050SD1.1
MM4050SD2.1
MM4050NS1.1a
MM4050NS2.1
MM4000NS2.1
MM4430NS2.1
MM4450NS2.1
MM4400NS2.1
MM5025NS1.1K
MM5025NS2.1K
MM5050NS2.1
MM5000NS2.1
440
500
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
25/02/00
25/02/00
04/02/00
04/02/00
Glossary
SCPD
NS
SD
MMS
Prolim
DLA
Current limiter
MS325 + A-Contactors
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
Contactor
Type
Magnetic
tripping
current
[A]
Type
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1
MS116-1
MS116-1.6
MS116-1.6
MS116-2.5
MS116-4
MS116-4
MS116-6.3
MS116-10
MS116-10
MS116-16
MS116-16
3.0
4.8
7.56
12
12
19.2
19.2
30
48
48
75.6
120
120
192
192
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A12
A16
Safety
clearance
[mm]
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 10
6.3 - 10
10 - 16
10 - 16
Imax [A]
0.25
0.4
0.63
1
1
1.6
1.6
2.5
4
4
6.3
10
10
12
16
MM4016NS1.1
Safety perimeter : 40/10 x 15 x 5 means : 40mm above MS xxx, 10mm below the contactor
15mm in front of each component, 5mm on each side
Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 22/11/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
Contactor
Type
Magnetic
tripping
current
[A]
Type
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1
MS116-1
MS116-1.6
MS116-1.6
MS116-2.5
MS116-4
MS116-4
MS116-6.3
MS116-10
MS116-10
MS116-16
MS116-16
3.0
4.8
7.56
12
12
19.2
19.2
30
48
48
75.6
120
120
192
192
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/B6
A9/BB6
A12/B6
A12/B6
A16
A16
A16
**
**
Safety
clearance
[mm]
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
40/10
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 10
6.3 - 10
10 - 16
10 - 16
Imax [A]
0.25
0.4
0.63
1
1
1.6
1.6
2.5
4
4
6.3
10
10
12
16
MM4016NS2.1
Safety perimeter : 40/10 x 15 x 5 means : 40mm above MS xxx, 10mm below the contactor
15mm in front of each component, 5mm on each side
** : under consideration
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MM4050NS1.1
MS325/495
Rated
Output
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8,5
11.5
15.5
9
11
18.3
22
15
18.5
22
30
37
45
55
30
37
45
60
72
85
98
Type
Magnetic
tripping
current
Contactor
Overload
Release
Type
<br>
Safety
clearance
Type
<br>
Group
Current
Max.
setting range Current
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
[A]r>
18.4
18.4
29
48
48
94.5
135
135
187.5
A9
A9
A9
A9
A9
A9
A9
A9
A12
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
Imax [A]
1.6
1.6
2.5
4
4
6.3
9
9
12
MS325-16
240
A16
25/5x15x5
12.5 - 16
16
MS450-20
240
A16
50/5x15x10
14 - 20
16
MS325-20
300
A26
25/5x15x5
16 - 20
20
MS325-25
375
A26
25/5x15x5
20 - 25
25
MS450-25
300
A26
50/5x15x10
18 - 25
25
MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100
384
480
540
756
900
1080
1200
A30
A40
A50
A63
A75
A95
A110
50/5x15x10
50/5x15x10
50/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10
22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100
30
40
50
60
72
90
100
MM4050NS1.1
Safety perimeter : 25/5x15x5 means : 25mm above MS325, 5mm below the contactor
15mm in front of each component, 5mm on each side
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : MM4050NS2.1
MS325/DLA
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
22
Magnetic
tripping
current
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-25
[A]
18.4
18.4
29
50
50
79
112.5
112.5
156
200
300
Contactor
Type
Safety
clearance
DLA9
DLA9
DLA9
DLA9
DLA12
DLA12
DLA26
DLA26
DLA26
DLA26
DLA26
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25
Imax [A]
1.6
1.6
2.5
4
4
6.3
9
9
12.5
16
25
MM4050NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MM4050NS1.1K
S503K
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.44
0.72
0.83
1.12
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44
Contactor
Type
Magnetic
tripping
current
[A]
Type
S503-K 0.58
S503-K 0.8
S503-K 1.1
S503-K 1.5
S503-K 2.1
S503-K 2.1
S503-K 3
S503-K 4.2
S503-K 5.8
S503-K 5.8
S503-K 8
S503-K11
S503-K 15
S503-K 20
S503-K 26
S503-K 32
S503-K 37
S503-K 45
7
10
13
18
25
25
36
50
69
69
96
132
180
240
312
384
444
540
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
0.38 - 0.58
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
1.4 - 2.1
2-3
2.8 - 4.2
3.8 - 5.8
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37
38 - 45
Imax [A]
0.55
0.76
1.05
1.45
2.05
2.05
2.9
4
5.55
5.55
7.65
10.5
14.5
19
24.5
30.5
37
45
MM4050NS1.1K
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/10/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : MM4050NS2.1K
S503K
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.44
0.72
0.83
1.2
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44
Contactor
Type
Magnetic
tripping
current
[A]
Type
S503-K 0.58
S503-K 0.8
S503-K 1.1
S503-K 1.5
S503-K 2.1
S503-K 2.1
S503-K 3
S503-K 4.2
S503-K 5.8
S503-K 5.8
S503-K 8
S503-K11
S503-K 15
S503-K 20
S503-K 26
S503-K 32
S503-K 37
S503-K 45
7
10
13
18
25
25
36
50
69
69
96
132
180
240
312
384
444
540
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A16-30-10
A26-30-10
A26-30-10
A26-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
0.38 - 0.58
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
1.4 - 2.1
2-3
2.8 - 4.2
3.8 - 5.8
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37
38 - 45
Imax [A]
0,55
0,76
1,05
1,45
2,05
2,05
2.9
4
5,55
5.55
7.65
10.5
14.5
19
24.5
30.5
37
45
MM4050NS2.1K
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 23/10/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
MMS Up-stream
Manual Motor
Starter
Rated
Output
Rated
Current
Pe [kW]
Ie [A]
1.1
2.8
1.5
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
100
Contactor
Thermal Tripping
Setting Range
Group
Type
Magnetic
tripping
current
Irm (A)
K1
Line
K2
Delta
K3
Star
Type
Current
Max.
setting range starting
time
MS325-4.0
48
A9
A9
A9
[A]
2.5 - 4
(s)
15
MS325-6.3
MS325-9.0
MS325-9.0
MS325-12.5
MS325-16
MS325-25
MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100
94.5
135
135
187.5
240
375
384
480
600
756
900
1080
1200
A9
A9
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A9
A9
A9
A9
A9
A12
A16
A26
A26
A40
A40
A50
A63
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A30
A40
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25
22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100
15
15
15
15
15
15
15
15
30
30
30
30
30
MM4050SD1.1
Created 07/04/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 02/05/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
MMS Up-stream
Manual Motor
Starter
Rated
Output
Rated
Current
Pe [kW]
Ie [A]
1.1
2.8
1.5
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
5
6.6
8.5
11.5
15.5
22
30
37
44
60
72
85
100
Contactor
Thermal Tripping
Setting Range
Group
Type
Magnetic
tripping
current
Irm (A)
K1
Line
K2
Delta
K3
Star
Type
Current
Max.
setting range starting
time
MS325-4.0
48
A9
A9
A9
[A]
2.5 - 4
(s)
15
MS325-6.3
MS325-9.0
MS325-9.0
MS325-12.5
MS325-16
MS325-25
MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100
94.5
135
135
187.5
240
375
384
480
600
756
900
1080
1200
A12
A26
A26
A26
A26
A26
A30
A40
A50
A63
A95
A95
A110
A12
A26
A26
A26
A26
A26
A30
A40
A50
A63
A95
A95
A110
A9
A12
A12
A12
A12
A12
A26
A26
A30
A40
A75
A75
A95
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25
22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100
15
15
15
15
15
15
15
30
30
30
30
30
30
MM4050SD2.1
Created 07/04/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 02/05/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MM4050NS1.1
MS325/DLA
Rated
Current
Pe [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
22
Contactor
Type
Magnetic
tripping
current
[A]
Type
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-25
18.4
18.4
29
50
50
79
112.5
112.5
156
200
300
DLA9
DLA9
DLA9
DLA9
DLA9
DLA9
DLA9
DLA9
DLA12
DLA16
DLA26
Safety
clearance
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
20 - 25
Imax [A]
1.6
1.6
2.5
4
4
6.3
9
9
12
16
25
MM4050NS1.1
Safety perimeter : 25/5x15x5 means : 25mm above MS325, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 2
Note : MM4050NS2.1
MS325/495
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
9
11
18.3
22
15
18.5
22
30
37
45
55
30
37
44
60
72
85
98
Contactor
Safety
clearance
Overload
Release
Type
Group
Type
Magnetic
tripping
current
[A]
Type
Current
Max.
setting range Current
MS325-0.25
MS325-0.4
MS325-0.63
MS325-1
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
2.44
3.9
6.14
11.5
11.5
18.4
18.4
28.7
48
48
94.5
135
135
187.5
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
Imax [A]
0.25
0.4
0.63
1
1
1.6
1.6
2.5
4
4
6.3
9
9
12.5
MS325-16
240
A26
25/5x15x5
12.5 - 16
16
MS450-20
240
A26
50/5x15x10
14 - 20
16
MS325-20
300
A26
25/5x15x5
16 - 20
20
MS325-25
375
A30
25/5x15x5
20 - 25
25
MS450-25
300
A30
50/5x15x10
18 - 25
25
MS450-32
MS450-40
MS450-50
MS495-63
MS495-75
MS495-90
MS495-100
384
480
600
756
900
1080
1200
A30
A40
A50
A63
A95
A95
A110
50/5x15x10
50/5x15x10
50/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10
70/5x15x10
22 - 32
28 - 40
40 - 50
45 - 63
57 - 75
70 - 90
80 - 100
30
40
50
63
75
90
100
MM4050NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
Ie [A]
0.22
0.33
0.42
0.72
0.83
1.2
1.5
2
2.6
3.5
5
6.6
8.5
11.5
15.5
18.3
22
30
18.5
Type
Protection
Contactor
Magnetic
tripping
current
Limiter
type
Prolim
Type
MS325-0.25
MS325-0.40
MS325-0.63
MS325-1
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-20
MS325-25
[A]
2.44
3.9
6.14
11.5
11.5
18.4
18.4
28.75
48
48
94.5
135
135
187.5
240
300
375
PLM 36-A
PLM 36-A
PLM 36-A
PLM 63-A
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A26
A30
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
MS450-32
384
PLM 63-A
A30
50/5x15x10
S 503 K32
416
PLM 63-A
A30
20
S 503 K37
481
PLM 63-A
A50
20
37
Safety
clearance
Overload
Release
Type
Group
Current
Max.
setting range Current
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
16 - 20
20 - 25
Imax [A]
0.25
0.40
0.63
1
1
1.6
1.6
2.5
4
4
6.3
9
9
12.5
16
20
25
22 - 32
30
23 - 32
30.5
29 - 37
37
MM4000NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 17/08/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
440 V, 25 kA, Normal start - up, type 2
Motor
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
Ie [A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31
5.8
7.6
10.3
7.5
9
11
12.5
15
13.5
15.8
19.3
21.9
26.3
Protection
Contactor
Safety
clearance
Overload
Release
Type
Group
Type
Magnetic
tripping
current
[A]
Limiter
type
Prolim
Type
Current
Max.
setting range Current
MS325-0.25
MS325-0.4
MS325-0.4
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-2.5
MS325-4
MS325-6.3
MS325-6.3
MS325-9
MS325-12.5
2.44
3.9
3.9
6.14
11.5
18.4
18.4
28.75
28.75
48
94.5
94.5
135
187.5
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A26
A26
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
0.16 - 0.25
0.25 - 0.4
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
1.6 - 2.5
2.5 - 4
4 - 6.3
4 - 6.3
6.3 - 9
9 - 12.5
Imax [A]
0.25
0.4
0.4
1
1
1.6
1.6
2.5
2.5
4
6.3
6.3
9
12.5
MS325-16
MS325-16
MS325-20
MS325-25
240
240
300
375
A26
A26
A26
A30
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
12.5 - 16
12.5 - 16
16 - 20
20 - 25
16
16
20
25
S 503K 32
416
A30
35
23 - 32
30.5
MS450-32
384
A30
50/5x15x10
22 - 32
30
S 503K 37
S 503K 37
481
481
A50
A50
35
35
29 - 37
29 - 37
37
37
18.5
22
32
37
MM4430NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
440 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2,2
3
4
5.5
Ie [A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31
5.8
7.6
10.3
7.5
9
11
12.5
15
13.5
15.8
19.3
21.9
26.3
Type
Protection
Contactor
Safety
clearance
Overload
Release
Type
Group
Magnetic
tripping
current
Limiter
type
Prolim
Type
Current
Max.
setting range Current
MS325-0,25
MS325-0.4
MS325-0.4
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-2.5
MS325-4
MS325-6.3
MS325-6.3
MS325-9
MS325-12.5
[A]
2.44
3.9
3.9
6.14
11.5
18.4
18.4
28.75
28.75
48
94.5
94.5
135
187.5
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A26
A26
A26
A26
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
0.16 - 0.25
0.25 - 0.4
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
1.6 - 2.5
2.5 - 4
4 - 6.3
4 - 6.3
6.3 - 9
9 - 12.5
Imax [A]
0.25
0.4
0.4
1
1
1.6
1.6
2.5
2.5
4
6.3
6.3
9
12.5
MS325-16
MS325-16
MS325-20
MS325-25
240
240
300
375
PLM 36-A
PLM 36-A
PLM 36-A
PLM 36-A
PLM 63-A
A26
A26
A26
A30
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
12.5 - 16
12.5 - 16
16 - 20
20 - 25
16
16
20
25
S 503K 32
416
PLM 63-A
A30
35
23 - 32
30.5
MS450-32
384
PLM 63-A
A30
50/5x15x10
22 - 32
30
18.5
32
S 503K 37
481
PLM 63-A
A50
35
29 - 37
37
22
37
S 503K 37
481
PLM 63-A
A50
35
29 - 37
37
MM4450NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
Ie [A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31
5.8
7.5
11.3
Type
MS325-0.25
MS325-0.4
MS325-0.4
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-2.5
MS325-4
2.44
3.9
3.9
6.14
11.5
18.4
18.4
28.75
28.75
50
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
0.16 - 0,25
0.25 - 0.4
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
1.6 - 2.5
2.5 - 4
Imax [A]
0.25
0.4
0.4
1
1
1.6
1.6
2.5
2.5
4
MS325-6.3
78.7
PLM 36-A
A26
25/5x15x5
4 - 6.3
6.3
MS325-6.3
78.7
MO325-6.3
A26
25/5x15x5
4 - 6.3
6.3
MS325-6.3
78.7
PLM 36-A
A26
25/5x15x5
4 - 6.3
6.3
MS325-6.3
78.7
MO325-6.3
A26
25/5x15x5
4 - 6.3
6.3
MS325-9
135
PLM 36-A
A26
25/5x15x5
6.3 - 9
MS325-9
135
MO325-9
A26
25/5x15x5
6.3 - 9
MS325-12.5
187.5
PLM 36-A
A26
25/5x15x5
9 - 12.5
12.5
MS325-12.5
187.5
MO325-12.5
A26
25/5x15x5
9 - 12.5
12.5
MS325-16
240
PLM 36-A
A26
25/5x15x5
12.5 - 16
16
MS325-16
240
MO325-16
A26
25/5x15x5
12.5 - 16
16
MS325-16
240
PLM 36-A
A26
25/5x15x5
12.5 - 16
16
MS325-16
240
MO325-16
A26
25/5x15x5
12.5 - 16
16
MS325-20
300
PLM 36-A
A26
25/5x15x5
16 - 20
20
MS325-20
300
MO325-20
A26
25/5x15x5
16 - 20
20
12.5
MS325-25
375
PLM 63-A
A26
25/5x15x5
20 - 25
25
MS325-25
375
MO325-25
A26
25/5x15x5
20 - 25
25
19.3
21.9
Home
Fuse
MCCB
MMS
Softstarters UL Comb.
Type
Group
Limiter
type
Prolim
13.5
Safety
clearance
Overload
Release
Magnetic
tripping
current
[A]
15.8
11
Contactor
Type
7.6
5.5
Protection
MCB
Current
Max.
setting range Current
15
26.3
18.5
22
32
37
S 503K 32
416
PLM 63-A
A30
35
23 - 32
30
MS450-32
384
PLM 63-A
A30
50/5x15x10
22 - 32
30
S 503K 37
S 503K 37
481
481
PLM 63-A
PLM 63-A
A50
A50
35
35
29 - 37
29 - 37
37
37
MM4400NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 30/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
500 V - 25 kA - Normal start - up, type : 1
Note : MM5025NS1.1K
S503K
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33
Contactor
Type
Current setting
Magnetic release
Type
S503-K0.42
S503-K0.8
S503-K0.8
S503-K1.1
S503-K1.5
S503-K2.1
S503-K3
S503-K3
S503-K4.2
S503-K5.8
S503-K8
S503-K11
S503-K15
S503-K20
S503-K26
S503-K32
S503-K37
5
10
10
13
18
25
36
36
50
69
96
132
180
240
312
384
444
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00
Overload
Release
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
Type
-
Group
Current
Max.
setting range Current
[A]
0.28 - 0.42
0.53 - 0.8
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
2-3
2-3
2.8 - 4.2
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37
Imax [A]
0.42
0.77
0.77
1.05
1.45
2.05
2.9
2.9
4
5,55
7.65
10.5
14.5
19
24.5
30.5
37
MM5025NS1.1K
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
500 V - 25 kA - Normal start - up, type : 2
Note : MM5025NS2.1K
S503K
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33
Contactor
Type
Current setting
Magnetic release
Type
S503-K 0.42
S503-K 0.80
S503-K 0.80
S503-K 1.10
S503-K 1.50
S503-K 2.10
S503-K 3.00
S503-K 3.00
S503-K 4.20
S503-K 5.80
S503-K 8.00
S503-K 11.0
S503-K 15.0
S503-K 20.0
S503-K 26.0
S503-K 32.0
S503-K 37.0
5
10
10
13
18
25
36
36
50
69
96
132
180
240
312
384
444
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A26-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00
Overload
Release
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
Type
-
Group
Current
Max.
setting range Current
[A]
0.28 - 0.42
0.53 - 0.8
0.53 - 0.8
0.73 - 1.1
1 - 1.5
1.4 - 2.1
2-3
2-3
2.8 - 4.2
3.8 - 5.8
5.3 - 8
7.3 - 11
10 - 15
14 - 20
18 - 26
23 - 32
29 - 37
Imax [A]
0.42
0.77
0.77
1.05
1.45
2.05
2.9
2.9
4
5.55
7.65
10.5
14.5
19
24.5
30.5
37
MM5025NS2.1K
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Direct-on-line Starters
500 V - 50 kA - Normal start - up, type : 2
Note : MM5050NS2.1
MS325/450
Direct-on-line starters
500 V, 50 kA, Normal start - up, type 2
Motor
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
18.5
Ie [A]
0.16
0.24
0.33
0.46
0.59
0.85
1.2
1.48
2.1
2.6
3.8
5.1
6.5
8.9
11.9
13.9
16.7
22.5
28.5
22
Type
Protection
Contactor
Type
Group
Magnetic
tripping
current
Limiter
type
Prolim
Type
MS325-0.25
MS325-0.25
MS325-0.4
MS325-0.63
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
MS325-4
MS325-4
MS325-6.3
MS325-9
MS325-9
MS325-12.5
MS325-16
MS325-20
MS325-25
[A]
2.44
2.44
3.9
6.14
6.14
11.5
18.4
18.4
28.75
48
48
94.5
135
135
187.5
240
300
375
PLM 36-B
PLM 36-B
PLM 36-B
PLM 36-B
PLM 36-B
PLM 63-B
PLM 63-B
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A26
A26
A30
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
0.16 - 0.25
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.40 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
2.5 - 4
2.5 - 4
4.0 - 6.3
6.3 - 9
6.3 - 9
9 - 12.5
12.5 - 16
16 - 20
20 - 25
Imax [A]
0.25
0.25
0.4
0.63
0.63
1.6
1.6
1.6
2.5
4
4
6.3
9
9
12.5
16
20
25
S 503K 32
416
PLM 63-B
A30
35
23 - 32
30.5
MS450-32
384
PLM 63-B
A30
50/5x15x10
22 - 32
30
S 503K 37
481
PLM 63-B
A50
35
29 - 37
37
33
Safety
clearance
Overload
Release
Current
Max.
setting range Current
MM5050NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Output
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
Ie [A]
0.16
0.24
0.33
0.46
0.59
0.85
1.2
1.48
2.1
2.6
2.2
Type
5.1
7.5
11.9
MS325-0.25
MS325-0.25
MS325-0.4
MS325-0.63
MS325-0.63
MS325-1
MS325-1.6
MS325-1.6
MS325-2.5
[A]
2.44
2.44
3.9
6.14
6.14
11.5
18.4
18.4
28.75
A9
A9
A9
A9
A9
A9
A9
A9
A9
[mm]
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
25/5x15x5
[A]
0.16 - 0.25
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.6
1 - 1.6
1.6 - 2.5
Imax [A]
0,25
0.25
0.40
0.63
0.63
1.6
1.6
1.6
2.5
MS325-4
50
PLM 36-B
A12
25/5x15x5
2.5 - 4
4.0
MS325-4
50
MO325-4
A12
25/5x15x5
2.5 - 4
4.0
MS325-4
50
PLM 36-B
A12
25/5x15x5
2.5 - 4
4.0
MS325-4
50
MO325-4
A12
25/5x15x5
2.5 - 4
4.0
MS325-6.3
78.7
PLM 36-B
A26
25/5x15x5
4 - 6.3
6.3
MS325-6.3
78.7
MO325-6.3
A26
25/5x15x5
4 - 6.3
6.3
MS325-9
135
PLM 36-B
A26
25/5x15x5
6.3 - 9
9.0
MS325-9
135
MO325-9
A26
25/5x15x5
6.3 - 9
9.0
MS325-9
135
PLM 36-B
A26
25/5x15x5
6.3 - 9
9.0
MS325-9
135
MO325-9
A26
25/5x15x5
6.3 - 9
9.0
MS325-12.5
187.5
PLM 36-B
A26
25/5x15x5
9 - 12.5
12.5
MS325-12.5
187.5
MO325-12.5
A26
25/5x15x5
9 - 12.5
12.5
MS325-16
240
PLM 36-B
A26
25/5x15x5
12.5 - 16
16
MS325-16
240
MO325-16
A26
25/5x15x5
12.5 - 16
16
MS325-20
300
PLM 36-B
A26
25/5x15x5
16 - 20
20
MS325-20
300
MO325-20
A26
25/5x15x5
16 - 20
20
13.9
11
16.7
Home
Fuse
MCCB
MMS
Softstarters UL Comb.
Type
Group
Type
8.9
Safety
clearance
Overload
Release
Limiter
type
Prolim
6.5
5.5
Contactor
Magnetic
tripping
current
3.8
Protection
MCB
Current
Max.
setting range Current
15
18.5
22.5
28.5
22
33
MS325-25
375
PLM 63-B
A26
25/5x15x5
20 - 25
25
MS325-25
375
MO325-25
A26
25/5x15x5
20 - 25
25
S 503K 32
416
PLM 63-B
A30
35
23 - 32
30,5
MS450-32
384
PLM 63-B
A30
50/5x15x10
22 - 32
30
S 503K 37
481
PLM 63-B
A50
35
29 - 37
37
MM5000NS2.1
Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor
15mm in front of each component, 5mm on each side
Created 30/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
SOFTSTARTERS
Ue
V
Iq
kA
Coor.
type
Starting
type
SCPD
type
Size
kW
400
50
400
65
415
65
440
500
50
50
65
1
1
2
690
50
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
MMS
MMS
MCCB
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
MCCB
MCCB
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
MCCB
0.06 ... 50
15 ... 50
0.37 ... 400
1.5 ... 160
1.5 ... 55
30 ... 450
25 ... 400
7.5 ... 132
7.5 ... 110
1.5 ... 75
1.5 .... 55
30 ... 500
30 ... 400
7.5 ... 132
8 ... 110
0.37 ... 400
0.37 ... 355
2.2 ... 90
2.2 .. 75
45 ... 550
45 ... 500
11 ... 160
11 ... 160
0.25 ... 600
Table
MMPS4050LIN40-1
MMPD4050LIN40-1
MBPS4050LIN40-1
PSS4065LINE40
PSS4065LINE50
PSD4065LINE40
PSD4065LINE50
PSS4065DELTA40
PSS4065DELTA50
PSS4165LINE40
PSS4165LINE50
PSD4165LINE40
PSD4165LINE50
PSS4165DELTA40
PSS4165DELTA50
MBPS4450LIN40-1
MBPS5050LIN40-1
PSS5065LINE40
PSS5065LINE50
PSD5065LINE40
PSD5065LINE50
PSS5065DELTA40
PSS5065DELTA50
MBPS6950LIN40-1
Last
Update
13/11/01
13/11/01
13/11/01
14/11/01
20/11/00
14/11/01
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
13/11/01
13/11/01
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
20/11/00
13/11/01
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
Max
current
[kW]
1.5
2.5
4
[A]
0.16
0.25
0.4
0.63
1
1.6
2.5
3.5
6.3
9
5.5
10
12
7.5
16
17
12.5
18
25
0.06
0.55
15
18,5
22
25
30
37
45
51
26
27
30
32
37
44
45
50
55
60
72
75
85
96
100
Type
Type
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
MS225-0.16
MS225-0.25
MS225-0.4
MS225-0.63
MS225-1
MS225-1.6
MS225-2.5
MS225-4
MS225-6.3
MS225-9
MS325-10
MS325-10
MS325-12.5
MS325-12.5
MS325-16
MS325-16
MS325-20
MS325-20
MS325-20
MS325-25
MS325-25
MS450-32
MS450-32
MS450-32
MS450-40
MS450-40
MS450-50
MS450-50
MS450-50
MS495-63
MS495-63
MS495-75
MS495-75
MS495-90
MS495-100
MS495-100
Current setting
range
[A]
0.1 - 0.16
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 1.6
1.6 - 2.5
2.5 - 4
4 - 6.3
6.3 - 9
6 - 10
6 10
9 12.5
9 - 12.5
12.5 - 16
12.5 - 16
16 20
16 - 20
16 20
18 25
18 - 25
22 32
22 32
22 32
28 - 40
28 - 40
40 - 50
40 - 50
40 - 50
45 - 63
45 - 63
57 - 75
57 - 75
70 - 90
80-100
80-100
Line
By-pass
contactor contactor
Type
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A12
A16
A16
A16
A16
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A63
A63
A75
A75
A95
A95
A110
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A9
A9
A9
Integrated
A9
Integrated
A9
Integrated
A9
A9
Integrated
A12
A12
A16
A26
A26
A26
A26
A30
A30
A40
A50
A50
A50
A50
A50
MMPS4050LIN40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
Max
current
[kW]
15
[A]
30
32
37
40
45
50
60
65
72
75
85
90
96
100
18.5
20
22
25
30
37
45
51
Type
Type
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
MS450-40
MS450-40
MS450-40
MS450-40
MS450-45
MS450-50
MS495-63
MS495-75
MS495-75
MS495-75
MS495-100
MS495-100
MS495-100
MS495-100
Current setting
range
[A]
28 - 40
28 - 40
28 - 40
28 - 40
36 - 45
36 - 50
45 - 63
57 - 75
57 - 75
57 - 75
70 - 90
70 - 90
80 - 100
80 - 100
Line
By-pass
contactor contactor
Type
Type
A30
A30
A40
A50
A50
A50
A63
A63
A75
A75
A95
A95
A95
A110
A16
A26
A26
A26
A26
A40
A40
A50
A50
A50
A50
A50
A50
A50
MMPD4050LINE40-1
Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 13/11/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
Max
current
[kW]
0.37
0.55
[A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210
260
300
400
500
580
580
750
1.1
1.5
2.2
4
5
6.5
9
12.5
15
20
25
40
45
55
75
90
140
160
200
257
315
400
Type
Type
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 25-400B
PS S 25-400B
PS S 25-400B
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 300/515-500
PS S 300/515-500
PS D 470
PS D 570
PS D 720
PS D 720
PS D 840
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800
Magnetic
tripping
current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
7560
9600
9600
Type
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
E 500DU
E 500DU**
E 800DU
E 800DU
E 800DU
Line
By-pass
contactor contactor
Setting
range
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800
Type
Type
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
AF750
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A26
A26
A30
A50
A50
A50
A63
A95
A145
A145
A185
A210
A260
A300
AF400
AF400
AF580
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
1.5
2.2
2.5
4
5
5.5
8
Max
current
[A]
3.5
5
6.5
8.5
11
12
17
12,5
18
25
15
18,5
22
25
30
37
40
45
51
55
59
75
80
90
100
132
140
147
160
Type
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 250/430-500
PS S 250/430-500
PS S 300/515-500
PS S 300/515-500
PS S 300/515-500
26
27
30
37
44
45
50
55
60
65
72
75
85
96
100
105
110
115
125
142
145
160
175
185
210
250
260
275
300
Rated
current
[A]
16
20
25
32
40
40
50
50
50
80
50
80
80
80
125
160
160
160
200
200
250
250
250
250
315
315
315
315
450
450
450
500
500
500
630
630
700
700
700
700
Bussmann
ref.
Type
Type
170M1359
170M1360
170M1361
170M1362
170M1363
170M1363
170M1364
170M1364
170M1364
170M1366
170M1364
170M1366
170M1366
170M1366
170M1368
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
TA25DU4.0
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU150
TA200DU175
TA200DU175
TA200DU175
TA200DU200
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
Setting
range
[A]
2.8 - 4.0
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
110 - 150
130 - 175
130 - 175
130 - 175
150 - 200
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
Type
Type
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A30
A30
A40
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A110
A110
A110
A145
A145
A145
A145
A185
A185
A185
A210
A260
A260
A300
A300
Built-in
Built-in
Built-in
Built-in
Built-in
Built-in
A9
Built-in
A9
A9
Built-in
A12
A12
A16
A26
A26
A26
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
A110
A145
A145
A145
A145
A185
A185
A210
PSS4065LINE40
Created 13/10/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 14/11/2001 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
1.5
5.5
Max
current
[A]
3.5
9
12
7.5
11
12.5
15
18.5
22
25
30
37
45
55
Type
PS S 03-400B
PS S 18/30-500
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
15,5
16
17
22
25
26
27
30
32
34
37
40
44
46
50
55
60
65
72
75
78
85
95
96
110
110
130
Rated
current
[A]
16
50
50
40
50
50
50
80
80
50
80
80
125
125
125
160
160
160
160
200
200
250
250
315
315
315
400
400
400
450
450
450
Bussmann
ref.
Type
Type
170M1359
170M1364
170M1364
170M1363
170M1364
170M1364
170M1364
170M1366
170M1366
170M1364
170M1366
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU4.0
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU32
TA42DU32
TA42DU42
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
Setting
range
[A]
2.8 - 4.0
7.5 - 11
10 - 14
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
22 - 32
22 - 32
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
Type
Type
A9
A9
A12
A12
A16
A16
A16
A26
A26
A26
A26
A30
A30
A30
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A95
A110
A110
A145
Built-in
A9
A9
Built-in
A9
A9
Built-in
A9
A12
Built-in
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A63
A75
A75
A95
A95
PSS4065LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
30
37
45
51
55
59
75
90
110
132
140
147
160
180
200
250
257
295
315
355
400
450
Max
current
[A]
60
65
75
96
100
110
115
125
145
175
185
210
250
260
275
300
305
350
370
400
460
470
500
570
580
600
700
720
750
800
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 175
PS D 210
PS D 210
PS D 250
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
Rated
current
[A]
200
250
250
315
315
315
400
400
400
450
500
500
630
700
700
700
900
900
900
1250
1250
1250
1500
1500
1800
1800
1800
1800
1800
1800
Bussmann
ref.
Type
Type
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3021
170M3021
170M4016
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
1)
1)
TA75DU63
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU150
TA200DU175
TA200DU200
TA200DU200
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
E500DU
E500DU
E500DU
E500DU
E500DU
E800DU
E800DU
E800DU
E800DU
E800DU
E800DU
E800DU
E800DU
T900DU850
Setting
range
[A]
45 - 63
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
110 - 150
130 - 175
150 - 200
150 - 200
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
150 - 500
150 - 500
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
250 - 800
610 - 850
Line
By-pass
contactorcontactor
Type
Type
A63
A63
A75
A95
A110
A110
A145
A145
A145
A185
A185
A210
A260
A260
A300
A300
AF400
AF400
AF400
AF400
AF460
AF580
AF580
AF580
AF580
AF750
AF750
AF750
AF750
IOR1000
A40
A50
A50
A50
A50
A63
A63
A75
A95
A145
A145
A145
A145
A185
A185
A210
A210
A210
A260
A260
A300
A300
A300
AF400
AF400
AF400
AF460
AF580
AF580
AF580
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
25
30
37
45
55
75
90
110
132
160
200
250
315
355
400
Max
current
[A]
50
55
60
65
69
72
75
85
95
96
101
105
110
133
135
140
145
161
170
185
193
205
230
245
250
260
276
295
300
305
340
350
370
400
432
460
470
524
550
580
636
650
662
700
710
720
Type
PS D 75
PS D 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
PS D 840
Rated
current
[A]
250
250
250
250
250
315
315
315
315
315
315
400
400
400
450
450
450
450
500
500
500
630
630
700
700
700
700
900
900
900
900
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
1800
1800
1800
Bussmann
ref.
Type
Type
170M1371
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA80DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU150
TA200DU150
TA200DU150
TA200DU150
TA200DU175
TA200DU175
TA200DU200
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU400
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
T900DU850
Setting
range
[A]
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
65 - 80
65 - 80
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
110 - 150
110 - 150
110 - 150
110 - 150
130 - 175
130 - 175
150 - 200
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 500
285 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
610 - 850
Type
Type
A50
A53
A63
A63
A75
A75
A75
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
A185
A185
A185
A210
A210
A260
A260
A260
A260
A300
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
EH700
EH800
EH800
A30
A30
A40
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
A95
A110
A110
A145
A145
A145
A145
A185
A185
A210
A210
A210
A260
A260
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
PSD4065LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
7.5
11
15
18.5
22
25
30
37
45
55
75
90
110
132
Max
current
[A]
15
20
22
29
30
37
40
43
44
46
50
51
55
60
63
64
72
76
77
85
86
94
103
105
112
124
129
140
147
165
170
173
181
189
198
205
215
245
Type
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
Rated
current
[A]
50
50
50
50
50
80
80
80
80
80
80
80
125
125
125
125
160
160
160
160
200
200
200
200
250
250
315
315
315
400
400
400
400
450
450
450
450
450
Bussmann
ref.
Type
Type
170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150
Setting
range
[A]
7.5 - 11
10 - 14
10 - 14
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
110 - 150
Type
Type
A9
A12
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A40
A50
A50
A50
A50
A50
A63
A63
A63
A63
A75
A75
A95
A95
A95
A110
A110
A110
A110
A145
A145
A145
A145
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
PSS4065DELTA40
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
7.5
11
15
18.5
25
30
37
45
55
75
90
110
Max
current
[A]
15
20
22
29
30
37
43
44
46
47
50
55
60
63
68
70
72
78
85
86
94
103
105
112
114
129
135
140
146
163
165
166
170
181
189
205
225
Type
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
Rated
current
[A]
50
50
50
80
80
80
80
80
80
80
125
125
160
160
160
160
160
160
200
200
200
250
250
250
250
315
315
400
400
400
400
400
450
450
450
450
450
Bussmann
ref.
Type
Type
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
Setting
range
[A]
7.5 - 11
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
Type
Type
A9
A12
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A63
A75
A75
A95
A95
A95
A95
A95
A95
A110
A110
A110
A145
A145
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A63
A75
A75
A75
A75
A95
A95
A95
PSS4065DELTA50
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
Max
current
[A]
3.5
12
7.5
Type
PS S 03-400B
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 25-400B
PS S 18/30-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
14
17
18
11
15
18.5
22
25
30
37
45
55
75
21
26
27
28
30
32
35
37
40
44
45
47
50
55
60
65
66
72
75
80
85
96
100
105
110
115
125
135
142
Rated
current
[A]
16
40
40
50
50
50
50
50
80
80
80
80
80
125
125
125
160
160
160
160
160
200
200
250
250
250
315
315
315
400
400
400
450
450
450
450
450
Bussmann
ref.
Type
Type
170M1359
170M1364
170M1363
170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU4.0
TA25DU14
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU32
TA42DU42
TA42DU42
TA42DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150
Setting
range
[A]
2.8 - 4.0
10 - 14
10 - 14
10 - 14
13 - 19
13 - 19
13 - 19
13 - 19
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
22 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
110 - 150
Type
Type
A9
A12
A12
A16
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
Built-in
A9
Built-in
A9
A9
Built-in
A9
Built-in
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
PSS4165LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
Max
current
[A]
3.5
9
12
7.5
11
12.5
15
18.5
22
25
30
37
45
55
Type
PS S 03-400B
PS S 18/30-500
PS S 18/30-500
PS S 12-400B
PS S 18/30-500
PS S 18/30-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 25-400B
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
14
16
17
21
22
23
25
26
27
28
30
32
34
35
37
40
45
47
50
55
60
65
66
72
78
80
85
95
96
105
110
130
Rated
current
[A]
16
50
50
40
50
50
50
80
80
80
80
50
80
80
125
125
125
125
160
160
160
160
200
200
200
250
250
315
315
315
400
400
400
400
450
450
450
Bussmann
ref.
Type
Type
170M1359
170M1364
170M1364
170M1363
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1364
170M1366
170M1366
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU4.0
TA25DU11
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU32
TA42DU42
TA75DU42
TA75DU42
TA42DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
Setting
range
[A]
2.8 - 4.0
7.5 - 11
10 - 14
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
22 - 32
29 - 42
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
Type
Type
A9
A9
A12
A12
A16
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A95
A95
A110
A110
A145
Built-in
A9
A9
Built-in
A9
A9
Built-in
A9
A9
A12
A12
Built-in
A16
A16
A26
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A75
A75
A95
A95
PSS4165LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
37
45
55
75
90
110
132
160
200
250
315
400
450
500
Max
current
[A]
60
65
66
72
80
96
100
110
115
125
135
145
160
165
175
185
200
210
242
250
260
275
285
300
340
350
370
400
425
450
470
535
550
570
650
700
720
740
800
830
840
Type
PSD 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS S 145
PS S 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
PS D 840
PS D 840
Rated
current
[A]
250
250
250
250
315
315
315
315
400
400
400
400
450
450
450
500
500
500
630
630
700
700
700
700
900
900
900
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
1800
1800
Bussmann
ref.
Type
Type
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU150
TA200DU150
TA200DU175
TA200DU200
TA200DU200
TA200DU200
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU400
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
T900DU850
T900DU850
T900DU850
T900DU850
Setting
range
[A]
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
100 - 135
100 - 135
110 - 150
110 - 150
130 - 175
150 - 200
150 - 200
150 - 200
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
610 - 850
610 - 850
610 - 850
610 - 850
Type
Type
A63
A63
A75
A75
A95
A95
A110
A110
A145
A145
A145
A145
A185
A185
A185
A185
A210
A210
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH800
IOR1000
IOR1000
IOR1000
IOR1000
A40
A50
A50
A50
A50
A50
A50
A63
A63
A75
A95
A95
A110
A145
A145
A145
A145
A145
A185
A185
A185
A210
A210
A210
A260
A260
A260
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
PSD4165LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
37
45
55
75
90
110
132
160
200
250
315
355
Max
current
[A]
60
65
66
72
80
96
105
110
133
135
145
161
165
185
193
200
230
242
250
260
276
280
300
340
350
400
425
432
470
524
535
550
580
650
662
700
720
Type
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
Rated
current
[A]
250
250
250
315
315
315
400
400
400
450
450
450
500
500
500
630
630
700
700
700
700
900
900
900
1250
1250
1250
1250
1500
1500
1800
1800
1800
1800
1800
1800
1800
Bussmann
ref.
Type
Type
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU150
TA200DU150
TA200DU150
TA200DU150
TA200DU200
TA200DU200
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
Setting
range
[A]
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
110 - 150
110 - 150
110 - 150
110 - 150
150 - 200
150 - 200
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
Type
Type
A63
A63
A75
A75
A95
A95
A110
A110
A145
A145
A145
A185
A185
A185
A210
A210
A260
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
EH800
A40
A50
A50
A50
A50
A75
A75
A95
A95
A95
A110
A145
A145
A145
A145
A145
A185
A210
A210
A210
A260
A260
A260
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
PSD4165LINE50
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
15
18.5
22
25
30
37
45
55
75
90
100
110
132
Max
current
[A]
15
20
28
29
35
40
43
46
47
51
55
63
64
66
76
77
80
85
86
94
96
103
105
112
124
135
147
165
173
181
189
198
200
215
242
245
Type
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
Rated
current
[A]
50
50
50
80
80
80
125
125
125
125
125
125
125
160
160
160
160
160
160
200
200
200
250
250
250
315
315
400
400
400
450
450
450
450
450
450
Bussmann
ref.
170M364
170M1364
170M1364
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
170M3020
Type
Type
OS 160RD0380
TA25DU11
OS 160RD0380
TA25DU14
OS 160RD0380
TA25DU19
OS 160RD0380
TA25DU19
OS 160RD0380
TA25DU25
OS 160RD0380
TA25DU25
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA25DU32
OS 160RD0380
TA42DU32
OS 160RD0380
TA75DU32
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU52
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU63
OS 160RD0380
TA75DU80
OS 160RD0380
TA75DU80
OS 160RD0380
TA110DU90
OS 160RD0380
TA110DU90
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA110DU110
OESA 250R03D80 TA200DU135
OESA 250R03D80 TA200DU135
OESA 250R03D80 TA200DU135
OESA 250R03D80 TA200DU1505
OESA 250R03D80 TA200DU1505
Setting
range
[A]
7.5 - 11
10 - 14
13 - 19
13 - 19
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
100 - 150
100 - 150
Type
Type
A9
A12
A16
A16
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A63
A63
A75
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
A145
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
PSS4165DELTA40
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
8
11
15
18.5
22
30
37
45
55
75
90
100
110
Max
current
[A]
15
20
21
28
29
35
37
40
43
44
46
47
55
63
66
68
70
78
80
86
94
96
103
112
114
124
135
146
163
165
166
181
189
200
225
Type
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
Rated
current
[A]
50
50
50
50
80
80
80
80
80
80
80
80
80
125
125
160
160
160
200
200
200
250
250
250
250
315
315
400
400
400
400
450
450
450
450
Bussmann
ref.
Type
Type
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU11
TA25DU14
TA25DU19
TA25DU19
TA25DU19
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
Setting
range
[A]
7.5 - 11
10 - 14
13 - 19
13 - 19
13 - 19
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
Type
Type
A9
A12
A16
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A63
A75
A75
A95
A95
A95
A95
A95
A110
A110
A145
A145
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
A95
PSS4165DELTA50
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
Max
current
[kW]
0.37
0.55
[A]
1.4
1.8
2.4
3.1
4
5
6.5
8.5
11
14
19
25
32
42
50
63
75
90
110
145
175
210
260
300
400
500
580
750
1.1
1.5
2.2
4
5
6.5
9
12.5
15
20
25
40
45
55
75
90
140
160
200
257
315
400
Type
Type
PS S 03-400B
PS S 03-400B
PS S 03-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 12-400B
PS S 25-400B
PS S 25-400B
PS S 25-400B
PS S 37/64-500
PS S 44/76-500
PS S 50/85-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 300/515-500
PS S 300/515-500
PS D 470
PS D 570
PS D 720
PS D 840
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In3.2
S2X80 In5
S2X80 ln5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In20
S2X80 In25
S2X80 In32
S2X80 In42
S2X80 In52
S2X80 In63
S2X80 In80
S3H160 In160 *
S3H160 In160 *
S3H250 In200 *
S3H250 In200 *
S4H250 PR211-I In250
S5H400 PR211-I In320
S5H400 PR211-I In400
S6S630 PR211-I In630
S6S630 PR211-I In630
S6S800 PR211-I In800
S6S800 PR211-I In800
Magnetic
tripping
current
[A]
21
26
33
42
65
65
84
110
145
210
260
325
415
540
680
820
1040
1250
1500
2150
2400
3000
3840
4800
6300
7560
9600
9600
Type
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA75DU32
TA75DU42
TA75DU52
TA75DU63
TA75DU80
TA110DU90
TA110DU110
TA200DU150
TA200DU175
TA450DU235
TA450DU310
TA450DU310
E 500DU
E 500DU**
E 800DU
E 800DU
Line
By-pass
contactor contactor
Setting
range
[A]
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13 - 19
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
250 - 800
250 - 800
Type
Type
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF750
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A26
A26
A30
A50
A50
A50
A63
A95
A145
A145
A185
A210
A260
A300
AF400
AF580
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
Max
current
[kW]
0.37
[A]
1
1.4
1.8
2.4
3.1
3.2
5
6.5
8.5
11
14
19
25
32
42
42
52
63
80
90
110
135
145
170
210
240
280
400
500
500
580
1.1
1.5
4
5
6.5
9
12.5
20
40
55
75
90
100
147
160
200
355
355
Type
Type
PS S 03-480B
PS S 03-480B
PS S 03-480B
PS S 03-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 12-480B
PS S 25-480B
PS S 25-480B
PS S 25-480B
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 72/124-500
PS S 72/124-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 175/300-500
PS S 175/300-500
PS S 250/430-500
PS S 250/430-500
PS S 300/515-500
PS D 470
PS D 570
PS D 570
PS D 720
S2X80 In1.6
S2X80 In1.6
S2X80 In2
S2X80 In3.2
S2X80 In3.2
S2X80 In3.2
S2X80 In5
S2X80 In6.5
S2X80 In8.5
S2X80 In11
S2X80 In16
S2X80 In25
S2X80 In32
S2X80 In32
S2X80 In42
S2X80 In42
S2X80 In52
S2X80 In63
S3L160 In125 *
S3L160 In125 *
S3L160 In125 *
S3L250 In200 *
S3L250 In200 *
S3L250 In200 *
S4L250 PR211-I In250
S5L400 PR211-I In320
S5L400 PR211-I In400
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
S6L630 PR211-I In630
Magnetic
tripping
current
[A]
21
21
26
42
42
42
65
84
110
145
210
325
415
415
540
540
680
800
1050
1250
1250
1700
2050
2400
3000
3840
4800
5040
7560
7560
7560
Type
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA75DU25
TA75DU32
TA75DU42
TA75DU42
TA75DU52
TA75DU63
TA80DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU150
TA200DU175
TA 450DU235
TA 450DU310
TA 450DU310
E 500DU
E 500DU**
E 500DU**
E 800DU
Line
By-pass
contactor contactor
Setting
range
[A]
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13 - 19
18 - 25
22 - 32
29 - 42
29 - 42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
150 - 500
250 - 800
Type
Type
A9
A9
A9
A9
A16
A26
A26
A26
A30
A30
A30
A30
A50
A50
A50
A50
A63
A75
A145
A145
A145
A145
A145
A185
A210
A260
A300
AF400
AF580
AF580
AF580
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
A26
A26
A26
A30
A50
A50
A50
A63
A95
A95
A145
A146
A147
A210
A260
A300
A300
AF400
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
5.5
7.5
Max
current
[A]
3.5
9
12
Type
PS S 03-480B
PS S 12-480B
PS S 18/30-500
PS S 12-480B
PS S 18/30-500
PS S 25-480B
PS S 18/30-500
PS S 18/30-500
PS S 25-480B
PS S 30/52-500
PS S 25-480B
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60105-500
PS S 60105-500
PS S 60105-500
PS S 72124-500
PS S 72124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
14
11
15
18.5
22
25
30
37
45
55
75
90
17
18
22
23
25
26
27
28
30
33
37
38
44
45
50
54
55
60
65
72
79
80
85
100
105
106
115
125
128
142
Rated
current
[A]
16
40
40
40
50
50
50
50
50
80
50
80
80
80
80
125
125
160
160
160
160
200
200
200
250
250
315
315
315
400
400
400
450
450
450
450
Bussmann
ref.
Type
Type
170M1359
170M1363
170M1364
170M1363
170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1364
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU4.0
TA25DU14
TA25DU14
TA25DU14
TA25DU14
TA25DU14
TA25DU19
TA25DU19
TA25DU25
TA25DU32
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU90
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU150
TA200DU150
Setting
range
[A]
2.8 - 4.0
10 - 14
10 - 14
10 - 14
10 - 14
10 - 14
13 - 19
13 - 19
18 - 25
24 - 32
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
65 - 90
80 - 110
100 - 135
100 - 135
100 - 135
100 - 135
110 - 150
110 - 150
Type
Type
A9
A9
A12
A12
A16
A16
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A95
A95
A95
A110
A110
A145
A145
A145
A145
A145
A145
Built-in
Built-in
A9
Built-in
A9
Built-in
A9
A9
Built-in
A9
Built-in
A12
A12
A16
A16
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
PSS5065LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
2.2
5.5
7.5
Max
current
[A]
3.5
9
12
14
Type
PS S 03-480B
PS S 12-480B
PS S 12-480B
PS S 18/30-500
PS S 25-480B
PS S 18/30-500
PS S 30/52-500
PS S 25-480B
PS S 30/52-500
PS S 30/52-500
PS S 25-480B
PS S 30/52-500
PS S 37/52-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
16
22
15
18.5
22
25
30
37
45
55
75
23
25
27
28
33
34
38
40
44
45
46
54
55
65
66
78
79
80
85
95
96
100
105
106
130
Rated
current
[A]
16
40
40
50
50
50
80
50
80
80
50
80
80
125
125
160
160
160
160
160
200
200
250
250
315
400
400
400
400
400
450
450
450
450
Bussmann
ref.
Type
Type
170M1359
170M1363
170M1363
170M1364
170M1364
170M1364
170M1366
170M1364
170M1366
170M1366
170M1364
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1371
170M1371
170M1372
170M3019
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU4.0
TA25DU11
TA25DU14
TA25DU14
TA25DU14
TA25DU19
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA80DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU150
Setting
range
[A]
2.8 - 4.0
7.5 - 11
10 - 14
10 - 14
10 - 14
13 - 19
18 - 25
18 - 25
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
110 - 150
Type
Type
A9
A9
A12
A16
A16
A26
A26
A26
A30
A30
A30
A30
A30
A40
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
A95
A95
A110
A110
A110
A110
A145
A145
A145
Built-in
Built-in
Built-in
A9
Built-in
A9
A9
Built-in
A12
A12
Built-in
A16
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A50
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
PSS5065LINE50
Created 16/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
45
55
75
90
110
132
160
200
250
315
400
500
Max
current
[A]
65
75
79
80
100
106
110
128
145
156
160
170
175
186
210
220
240
250
275
278
280
300
350
353
370
400
445
450
470
538
550
570
680
700
720
800
840
Type
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 175
PS D 175
PS D 175
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 250
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
Rated
current
[A]
250
250
315
315
315
315
315
450
450
450
450
450
450
500
500
630
630
630
700
700
700
700
900
900
900
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
Bussmann
ref.
Type
Type
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M1372
170M3020
170M3020
170M3020
170M3020
170M3020
170M3020
170M3021
170M3021
170M4016
170M4016
170M4016
170M4017
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU175
TA200DU175
TA200DU175
TA200DU175
TA200DU175
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU310
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU810
T900DU810
T900DU810
T900DU850
T900DU850
Setting
range
[A]
60 - 80
80 - 110
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
130 - 175
130 - 175
130 - 175
130 - 175
130 - 175
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
610 - 810
610 - 810
610 - 810
610 - 850
610 - 850
Type
Type
A75
A95
A95
A95
A110
A145
A145
A145
A145
A185
A185
A185
A210
A210
A210
A260
A260
A300
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH800
IOR1000
IOR1000
A50
A50
A50
A50
A50
A63
A63
A95
A95
A110
A110
A145
A145
A145
A145
A145
A185
A185
A210
A210
A210
A210
A210
A260
A260
A260
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
PSD5065LINE40
Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
45
55
75
90
110
132
160
200
250
315
400
450
500
Max
current
[A]
55
60
65
69
79
80
85
95
100
101
105
106
128
133
135
145
156
161
170
186
193
210
220
230
240
250
276
278
280
300
340
350
353
370
400
432
445
470
524
538
550
608
650
662
680
700
720
Type
PS D 75
PS D 75
PS D 75
PS D 75
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 110
PS D 145
PS D 145
PS D 145
PS D 145
PS D 175
PS D 175
PS D 175
PS D 175
PS D 210
PS D 210
PS D 210
PS D 250
PS D 250
PS D 250
PS D 300
PS D 300
PS D 300
PS D 370
PS D 370
PS D 370
PS D 370
PS D 470
PS D 470
PS D 470
PS D 470
PS D 470
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
PS D 720
PS D 720
PS D 720
PS D 840
PS D 840
PS D 840
Rated
current
[A]
250
250
250
250
315
315
315
315
315
315
400
400
400
400
450
450
450
450
500
500
500
630
630
630
700
700
700
900
900
900
900
1250
1250
1250
1250
1250
1500
1500
1500
1800
1800
1800
1800
1800
1800
1800
1800
Bussmann
ref.
Type
Type
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3021
170M3021
170M3021
170M4016
170M4016
170M4016
170M4017
170M4017
170M4017
170M5015
170M5015
170M5015
170M5015
170M5018
170M5018
170M5018
170M5018
170M5018
170M6018
170M6018
170M6018
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
170M6020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 400R03D80
OESA 630R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
OESA 800R03D80
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU150
TA200DU150
TA200DU175
TA200DU175
TA200DU200
TA450DU235
TA450DU235
TA450DU235
TA450DU235
TA450DU235
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
TA450DU310
T450DU400
T450DU400
T450DU400
T450DU400
T900DU500
T900DU500
T900DU500
T900DU500
T900DU650
T900DU650
T900DU650
T900DU650
T900DU650
T900DU850
T900DU850
T900DU850
T900DU850
Setting
range
[A]
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
60 - 80
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
100 - 135
100 - 135
110 - 150
110 - 150
130 - 175
130 - 175
150 - 200
165 - 235
165 - 235
165 - 235
165 - 235
165 - 235
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
220 - 310
285 - 400
285 - 400
285 - 400
285 - 400
355 - 500
355 - 500
355 - 500
355 - 500
465 - 650
465 - 650
465 - 650
465 - 650
465 - 650
610 - 850
610 - 850
610 - 850
610 - 850
Type
Type
A63
A75
A75
A95
A95
A95
A110
A110
A110
A145
A145
A145
A145
A145
A145
A145
A185
A185
A185
A210
A210
A210
A260
A260
A260
A300
A300
A300
A300
EH370
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
EH700
EH800
A30
A40
A50
A50
A50
A50
A50
A63
A75
A75
A75
A95
A95
A95
A95
A110
A145
A145
A145
A145
A145
A185
A185
A185
A210
A210
A260
A260
A260
A260
A260
A300
A300
A300
EH370
EH370
EH370
EH370
EH550
EH550
EH550
EH550
EH550
EH700
EH700
EH700
EH700
PSD5065LINE50
Created 16/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
11
18.5
22
25
30
37
45
55
75
90
110
132
160
Max
current
[A]
15
17
20
24
28
33
37
38
43
44
46
48
51
54
56
64
65
76
77
79
85
94
103
105
106
112
124
128
137
147
156
172
173
181
186
198
215
220
245
Type
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
Rated
current
[A]
50
50
50
50
50
80
80
80
80
80
80
80
80
125
125
125
160
160
160
160
160
200
200
200
250
250
250
315
315
315
400
400
400
400
450
450
450
450
450
Bussmann
ref.
Type
Type
170M1364
170M1364
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1372
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU11
TA25DU14
TA25DU14
TA25DU14
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA80DU80
TA80DU80
TA110DU90
TA110DU90
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU135
TA200DU150
Setting
range
[A]
7.5 - 11
10 - 14
10 - 14
10 - 14
18 - 25
18 - 25
18 - 25
18 - 25
18 - 25
24 - 32
24 - 32
24 - 32
24 - 32
24 - 32
29 - 42
29 - 42
29 - 42
36 - 52
36 - 52
36 - 52
36 - 52
45 - 63
45 - 63
45 - 63
45 - 63
60 - 80
60 - 80
60 - 80
65 - 90
65 - 90
80 - 110
80 - 110
80 - 110
100 - 135
100 - 135
100 - 135
100 - 135
100 - 135
110 - 150
Type
Type
A9
A12
A12
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A40
A50
A50
A50
A50
A63
A63
A63
A75
A75
A75
A75
A95
A95
A95
A110
A110
A110
A110
A145
A145
A145
A145
A145
A145
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A40
A50
A50
A50
A50
A50
A50
A50
A50
A50
A50
A63
A63
A63
A75
A95
A95
PSS5065DELTA40
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
[kW]
11
15
18.5
22
25
30
37
45
55
75
90
110
132
160
Max
current
[A]
15
17
20
23
24
28
33
37
38
43
44
46
48
54
56
58
65
68
70
77
78
79
94
96
103
106
112
114
128
135
137
146
156
163
166
172
181
186
220
225
Type
PS S 18/30-500
PS S 18/30-500
PS S 18/30-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 30/52-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 37/64-500
PS S 44/76-500
PS S 44/76-500
PS S 44/76-500
PS S 50/85-500
PS S 50/85-500
PS S 60/105-500
PS S 60/105-500
PS S 60/105-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 72/124-500
PS S 85/147-500
PS S 85/147-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 105/181-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
PS S 142/245-500
Rated
current
[A]
50
50
50
80
80
80
80
80
125
125
125
125
125
125
125
125
160
160
160
160
160
200
200
200
250
250
250
250
315
315
400
400
400
400
400
450
450
450
450
450
Bussmann
ref.
Type
Type
170M1364
170M1364
170M1364
170M1366
170M1366
170M1366
170M1366
170M1366
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1368
170M1369
170M1369
170M1369
170M1369
170M1369
170M1370
170M1370
170M1370
170M1371
170M1371
170M1371
170M1371
170M1372
170M1372
170M3019
170M3019
170M3019
170M3019
170M3019
170M3020
170M3020
170M3020
170M3020
170M3020
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OS 160RD0380
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
OESA 250R03D80
TA25DU11
TA25DU11
TA25DU14
TA25DU14
TA25DU14
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU25
TA25DU32
TA25DU32
TA25DU32
TA25DU32
TA42DU42
TA42DU42
TA75DU42
TA75DU42
TA75DU42
TA75DU52
TA75DU52
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU63
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA110DU110
TA200DU135
TA200DU135
TA200DU135
TA200DU150
Setting
range
[A]
7.5-11
7.5-11
10-14
10-14
10-14
18-25
18-25
18-25
18-25
18-25
24-32
24-32
24-32
24-32
29-42
29-42
29-42
29-42
29-42
36-52
36-52
45-63
45-63
45-63
45-63
45-63
60-80
60-80
60-80
60-80
60-80
80-110
80-110
80-110
80-110
80-110
100-135
100-135
100-135
110-150
Type
Type
A9
A12
A12
A16
A16
A26
A26
A26
A26
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A63
A63
A75
A75
A75
A75
A95
A95
A95
A95
A110
A110
A110
A110
A110
A145
A145
A145
A145
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A16
A26
A26
A26
A26
A26
A26
A30
A30
A30
A30
A30
A40
A40
A50
A50
A50
A50
A50
A50
A50
A63
A63
A75
A75
A75
A95
A95
A95
PSS5065DELTA50
Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 20/11/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
Rated
Output
Max
current
[kW]
[A]
0.63
1
1.4
1.8
2.4
4
5
6.5
8.5
11.1
15.9
20.5
23.9
30.8
38.5
46.3
57.8
77.1
92.5
115.6
120
170
170
210
310
310
320
350
400
500
500
500
500
500
500
630
650
0.55
1.5
4
6.5
9
12.5
20
25
40
51
100
160
200
475
600
Type
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 18/30-690
PS S 30/52-690
PS S 30/52-691
PS S 37/64-690
PS S 44/76-690
PS S 50/85-690
PS S 60/105-690
PS S 85/147-690
PS S 105/181-690
PS S 142/245-690
PS S 142/245-690
PS S 175/300-690
PS S 175/300-690
PS S 250/430-690
PS D 370
PS D 370
PS D 370
PS D 370
PS D 470
PS D 570
PS D 570
PS D 570
PS D 570
PS D 570
PS D 570
PS D 720
PS D 720
S2X80 In1
S2X80 In1
S2X80 In1.6
S2X80 In2
S2X80 In2.5
S2X80 In4
S2X80 In5
S2X80 In6.5
S3X125 In25*
S3X125 In25 *
S3X125 In25 *
S3X125 In25 *
S3X125 In50 *
S3X125 In50 *
S3X125 In50 *
S3X125 In100 *
S3X125 In100 *
S3X125 In100 *
S3X125 In125 *
S3X125 In125 *
S3X200 In200 *
S3X200 In200 *
S4X250 PR211-I In250
S4X250 PR211-I In250
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X400 PR211-I In320
S6X400 PR211-I In400
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
S6X630 PR211-I In630
Magnetic
tripping
current
[A]
13
13
21
26
33
52
65
84
110
140
200
280
320
380
500
620
740
920
1250
1450
1750
2100
2500
3000
3840
4800
3840
4800
6300
6300
7560
6300
7560
6300
7560
7560
7560
Type
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU4
TA25DU5
TA25DU6.5
TA25DU2.4
TA25DU2.4
TA25DU2.4
TA25DU3.1
TA25DU3.1
TA25DU4
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA25DU4
TA25DU5
TA25DU5
TA 450DU185
TA 450DU185
TA 450DU235
TA450DU310
TA450DU310
E 500DU
E 500DU
TA450DU400
TA900DU500
TA900DU500
E 800DU
E 800DU
E 500DU **
E 500DU **
E 800DU
TA900DU650
Setting
range
[A]
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1,7 - 2.4
2.8 - 4
3.5 - 5
4.5 - 6,5
6 - 8.5
7.9 - 11.1
11.2 - 15.9
15.2 - 20.5
17.7 - 23.9
21.6 - 30.8
27 - 38.5
32.4 - 46.3
40.5 - 57.8
54 - 77.1
64.8 - 92.5
81 - 115.6
103 - 147
130 - 185
130 - 185
165 - 235
220 - 310
220 - 310
150 - 500
150 - 500
285 - 400
355 - 500
355 - 500
250 - 800
250 - 800
150 - 500
150 - 500
250 - 800
465 - 650
Type
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L185R/4
4L235R/4
Primary
turns
on CT
13***
10***
7***
7***
6
6
6
4
4
3
2
2
2
Line
By-pass
contactorcontactor
Type
Type
A9
A9
A9
A9
A16
A26
A26
A30
A95
A95
A95
A95
A145
A145
A145
A145
A145
A145
A145
A145
A145
A185
A185
A210
AF400
AF400
AF400
AF400
AF580
AF580
AF580
AF580
AF580
AF580
AF580
AF750
AF750
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A26
A26
A30
A40
A50
A50
A75
A75
A145
A145
A145
A210
A210
A210
A210
A260
A300
A300
A300
A300
A300
A300
AF460
AF460
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Iq
kA
Coor.
type
Starting
type
SCPD
type
hp
Table
Last
Update
240
480
200
200
35
85
1
1
1
1
DOL
DOL
DOL
DOL
J Fuse
J Fuse
MCCB
MCCB
2 ... 100
5 ... 200
5 ... 25
25 ... 200
08-11-00
08-11-00
08-11-00
08-11-00
600
200
DOL
J Fuse
FUL2400NS1.1
FUL4800NS1.1
MB4835NS1.1
MB4885NS1.1
FUL6000NS1.1
08-11-00
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
[hp]
type
Amp/Type
type
type
[in.]
2
3
5
10
OESA-CF30J6S
OESA-CF30J6S
OESA-CF30J6S
30J
30J
30J
A9
A12
A16
TA25DU14
TA25DU14
TA25DU19
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
OESA-CF30J6S
30J
A26
TA25DU32
14 x 12 x 8
OEAS-F60J6A
60J
A26
TA25DU32
14 x 12 x 8
OEAS-F60J6A
OESA-F100JT6A
OESA-F100JT6A
OES200JT6A
OES200JT6A
OES200JT6A
OES200JT6A
OES200JT6A
60J
100J
100J
200J
200J
200J
200J
200J
A30
A40
A50
A63
A75
A95
A110
A145
TA25DU32
TA42DU42
TA75DU63
TA75DU80
TA75DU80
TA110DU110
TA110DU110
TA200DU135
14 x 12 x 8
20 x 16 x 8
20 x 16 x 8
20 x 16 x 8
20 x 16 x 8
24 x 20 x 10
24 x 20 x 10
24 x 20 x 10
OES400JT6
250J
A185
TA200DU150
24 x 20 x 10
OES400JT6
300J
A185
TA200DU175
24 x 20 x 10
OES400JT6
OES400JT6
OES600JT6
350J
400J
600J
A210
A260
A300
TA450DU200
TA450DU235
TA450DU310
30 x 30 x 10
30 x 30 x 10
30 x 30 x 10
10
10
20
25
30
30
40
50
60
75
100
100
FUL2400NS1.1
ULFuse
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
[hp]
type
Amp/Type
type
type
[in.]
5
7.5
10
20
OESA-CF30J6S
OESA-CF30J6S
OESA-CF30J6S
30J
30J
30J
A9
A12
A16
TA25DU14
TA25DU14
TA25DU19
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
OESA-CF30J6S
30J
A26
TA25DU32
14 x 12 x 8
OEAS-F60J6A
60J
A26
TA25DU32
14 x 12 x 8
OEAS-F60J6A
OESA-F100JT6A
OESA-F100JT6A
60J
100J
100J
A30
A40
A50
TA25DU32
TA42DU42
TA75DU63
14 x 12 x 8
20 x 16 x 8
20 x 16 x 8
OES200JT6A
200J
A63
TA75DU80
20 x 16 x 8
OES200JT6A
200J
A75
TA75DU80
20 x 16 x 8
OES200JT6A
OES200JT6A
OES200JT6A
200J
200J
200J
A95
A110
A145
TA110DU110
TA110DU110
TA200DU135
24 x 20 x 10
24 x 20 x 10
24 x 20 x 10
OES400JT6
250J
A185
TA200DU150
24 x 20 x 10
OES400JT6
300J
A185
TA200DU175
24 x 20 x 10
OES400JT6
OES400JT6
OES600JT6
350J
400J
600J
A210
A260
A300
TA450DU200
TA450DU235
TA450DU310
30 x 30 x 10
30 x 30 x 10
30 x 30 x 10
25
30
40
60
60
75
100
125
150
200
200
FUL4800NS1.1
ULFuse
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
UL STARTERS
480 V - 35 kA - start - up, type :
Under Construction :No
On Internet :No
Note : MB4835NS1.1
type
type
type
[in.]
5
7.5
10
20
25
S3L010MW
S3L050MW
S3L050MW
S3L100MW
S3L150MW
A9
A12
A16
A26
A30
TA25DU14
TA25DU14
TA25DU19
TA25DU32
TA42DU32
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
UL STARTERS
480 V - 85 kA - start - up, type :
Under Construction :No
On Internet :No
Note : MB4885NS1.1
type
type
type
[in.]
25
30
40
60
S3L150MW
S3L150MW
S3L150MW
S3L250MW
A30**
A40**
A50
TA42DU42
TA42DU42
TA75DU63
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
A63
TA75DU80
14 x 12 x 8
A75
TA75DU80
14 x 12 x 8
A110
A145**
TA110DU110
TA200DU135
20 x 16 x 8
24 x 20 x 10
A185
TA200DU150
24 x 20 x 10
A185
TA200DU175
24 x 20 x 10
A210
TA450DU200
30 x 30 x 10
A260
TA450DU235
30 x 30 x 10
A260
TA450DU310
30 x 30 x 10
A300
TA450DU310
30 x 30 x 10
75
100
125
150
200
200
S3L250MW
S4N250MW
S4N250MW
S4N250MW
S5N400MW
S5N400MW
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Motor
[hp]
type
Amp/Type
type
type
[in.]
7.5
10
15
25
OESA-CF30J6S
OESA-CF30J6S
OESA-CF30J6S
30J
30J
30J
A9
A12
A16
TA25DU14
TA25DU14
TA25DU19
14 x 12 x 8
14 x 12 x 8
14 x 12 x 8
OESA-CF30J6S
30J
A26
TA25DU32
14 x 12 x 8
OEAS-F60J6A
60J
A26
TA25DU32
14 x 12 x 8
OEAS-F60J6A
OESA-F100JT6A
OESA-F100JT6A
60J
100J
100J
A30
A40
A50
TA25DU32
TA42DU42
TA75DU63
14 x 12 x 8
20 x 16 x 8
20 x 16 x 8
OES200JT6A
200J
A63
TA75DU80
20 x 16 x 8
OES200JT6A
200J
A75
TA75DU80
20 x 16 x 8
OES200JT6A
OES200JT6A
OES200JT6A
200J
200J
200J
A95
A110
A145
TA110DU110
TA110DU110
TA200DU135
24 x 20 x 10
24 x 20 x 10
24 x 20 x 10
OES400JT6
250J
A185
TA200DU150
24 x 20 x 10
OES400JT6
300J
A185
TA200DU175
24 x 20 x 10
OES400JT6
OES400JT6
OES600JT6
350J
400J
600J
A210
A260
A300
TA450DU200
TA450DU235
TA450DU310
30 x 30 x 10
30 x 30 x 10
30 x 30 x 10
30
40
50
75
75
100
125
150
200
250
300
FUL6000NS1.1
UL Fuse
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
MCB
Ue
V
Iq
kA
Coor.
type
Starting
type
SCPD
type
Overload
mean
Size
kW
400
10
1
2
Normal
Normal
MCB
MCB
TOR
TOR
0.06 ... 22
0.06 ... 22
MC4010NS1.1
MC4010NS2.1
04/02/00
04/02/00
16
1
2
Normal
Normal
MCB
MCB
TOR
TOR
0.06 ... 15
0.06 ... 15
04/02/00
04/02/00
35
1
2
Normal
Normal
MCB
MCB
TOR
TOR
0.06 ... 11
0.06 ... 11
HD
MCB
EOR
0.06 ... 9
1
2
1
2
1
2
Normal
Normal
Normal
Normal
Normal
Normal
MCB
MCB
MCB
MCB
MCB
MCB
TOR
TOR
TOR
TOR
TOR
TOR
0.12 ... 30
0.12 ... 30
0.06 ... 11
0.06 ... 11
0.12 ... 37
0.12 ... 37
MC4016NS1.1
MC4016NS2.1
MC4035NS1.1
MC4035NS2.1
MC4035HD2.1
MC4050NS1.1
MC4050NS2.1
1
2
1
2
Normal
Normal
Normal
Normal
MCB
MCB
MCB
MCB
TOR
TOR
TOR
TOR
0.25 ... 15
0.25 ... 15
0.18 ... 11
0.18 ... 11
MC4000NS1.1
MC4000NS2.1
MC5025NS1.1
MC5025NS2.1
MC5000NS1.1
MC5000NS2.1
MC6900NS1.1
MC6900NS2.1
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
50
100
500
25
100
690
100
Table
Last
Update
04/02/00
04/02/00
04/02/00
04/02/00
04/02/00
Glossary
SCPD
HD
NS
SD
MCB
Prolim
TOR
EOR
Current limiter
Thermal Overload Relay
Electronic Overload Relay
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 10 kA - Normal start - up, type : 1
Note : MC4010NS1.1
S273
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Ie [A]
0.22
0.34
0.44
0.6
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
28.5
37
44
Magnetic
tripping
current
S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40
S 283-K50
S283-K63
[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
560
700
882
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A26
A40
A40
A50
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA42DU32
TA42DU42
TA75DU52
[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
35 - 52
Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
30
40
50
MC4010NS1.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-On-Line Starters
400 V - 10 kA - Normal start - up, type : 2
Note : MC4010NS2.1
S273
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
Ie [A]
0.22
0.34
0.44
0.6
0.83
1.12
1.45
1.9
2.6
3.5
2.2
3
4
5.5
7.5
11
15
18.5
22
4.8
6.5
8.5
11.5
15
22
28.5
37
44
Miniature Circuit-Breaker
Type
Magnetic
tripping
current
S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40
S 283-K50
S283-K63
[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
560
700
882
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A26
A30
A30
A40
A50
A50
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
Imax [A]
0.25
0.4
0.63
0,63
1
1.35
1.75
2.35
2.95
TA25DU4
2.8 - 4
3.75
TA25DU5
3,5 - 5
4.75
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA42DU32
TA42DU42
TA75DU52
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
35 - 52
6.25
8
10.5
13.5
18.5
24.5
30.5
38.5
50
MC40101NS2.1
Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 16 kA - Normal start - up, type : 1
Note : MC4016NS1.1
S273
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
28.5
Magnetic
tripping
current
S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40
[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
560
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A40
A40
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32
[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10-14
13-19
18-25
24-32
Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
30
MC4016NS1.1
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-On-Line Starters
400 V - 16 kA - Normal start - up, type : 2
Note : MC4016NS2.1
S273
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5
2.2
3
4
5.5
7.5
11
15
4.8
6.5
8.5
11.5
15
22
28.5
Miniature Circuit-Breaker
Type
Magnetic
tripping
current
S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
S 283-K40
[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
560
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
A26
A30
A30
A30
A40
A40
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.40
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
Imax [A]
0.25
0.4
0.63
0,63
1
1.35
1.75
2.35
2.95
TA25DU4
2.8 - 4
3.75
TA25DU5
3,5 - 5
4.75
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
TA42DU32
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
6.25
8
10.5
13.5
18.5
24.5
30
MC4016NS2.1
Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 35 kA - Normal start - up, type : 1
Note : MC4035NS1.1
S273
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7,5
11
Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
Magnetic
tripping
current
S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A40
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
MC4035NS1.1
Created 26/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-On-Line Starters
400 V - 35 kA - Normal start - up, type : 2
Note : MC4035NS2.1
S273
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
Ie [A]
0.22
0.34
0.44
0.60
0.83
1.12
1.45
1.9
2.6
3.5
2.2
3
4
5.5
7,5
11
4.8
6.5
8.5
11.5
15
22
Miniature Circuit-Breaker
Type
Magnetic
tripping
current
S 273-K1
S 273-K1
S 273-K1
S 273-K1.6
S 273-K1.6
S 273-K2
S 273-K3
S 273-K3
S 273-K4
S 273-K6
S 273-K8
S 283-K10
S 283-K13
S 283-K16
S 283-K20
S 283-K32
[A]
12
12
12
19.2
19.2
24
36
36
48
72
96
140
182
224
280
448
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A16
A26
A26
A26
A26
A30
A30
A30
A40
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU0.63
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
[A]
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.4 - 0.63
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
Imax [A]
0.25
0.4
0.63
0,63
1
1.35
1.75
2.35
2.95
TA25DU4
2.8 - 4
3.75
TA25DU5
3,5 - 5
4.75
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA42DU25
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
6.25
8
10.5
13.5
18.5
24
MC4035NS2.1
Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7,5
9
Ie [A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
18.3
Magnetic
tripping
current
MO325-0.25
MO325-0.4
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-4
MO325-4
MO325-6.3
MO325-9
MO325-16
MO325-20
MO325-25
S503X-AG0074-32
[A]
2.44
3.9
6.14
11.5
11.5
16
16
27.5
40
40
67.7
112.5
200
250
312.5
352
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A30
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
Overload relay
Type
E16DU0.32 (10)
E16DU1.0 (10)
E16DU1.0 (10)
E16DU1.0 (10)
E16DU1.0 (10)
E16DU2.7 (20)
E16DU2.7 (20)
E16DU2.7 (20)
E16DU6.3 (20)
E16DU6.3 (20)
E16DU6.3 (20)
E16DU18.9 (20)
E16DU18.9 (20)
E16DU18.9 (20)
E16DU18.9 (20)
E16DU18.9 (20)
Group
starter
AB16
AB16
AB16
AB16
AB16
Imax [A]
0.25
0.4
0.63
0.95
0.95
1.45
1.45
2.2
3.5
3.5
5.4
7.3
10.5
13
16
18.9
MC4035HD2.1
Created 19/08/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Tmax
start.
(s)
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
Direct-on-line starters
400 V - 50 kA - Normal start - up, type : 1
Note : MC4050NS1.1KM
S503KM
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Ie [A]
0.44
0.72
0.83
1.2
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44
60
Contactor
Type
Magnetic
tripping
current
[A]
Type
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 2.5
S503-KM 2.5
S503-KM 4.0
S503-KM 6.0
S503-KM 6.0
S503-KM 6.0
S503-KM 9.0
S503-KM 20
S503-KM 20
S503-KM 20
S503-KM 32
S503-KM 32
S503-KM 52
S503-KM 63
S503-KM 75
16
16
16
16
25
25
45
55
55
55
100
200
200
200
400
400
580
800
840
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00
A63-30-00
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35
Thermal Overload
Relay
Type
TA25DU0.63
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
Group
Current
Max.
setting range Current
[A]
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
Imax [A]
0.63
1
1
1.4
1.8
2.4
3.1
4
5
6
8.5
9
12
16
25
32
40
50
63
MC4050NS1.1KM
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
4
5.5
7.5
11
15
18.5
22
30
Ie [A]
0.44
0.72
0.83
1.2
1.5
2
2.6
3.5
4.4
5
6.6
8.5
11.5
15.5
22
30
37
44
60
Contactor
Type
Magnetic
tripping
current
[A]
Type
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM2.5
S503-KM2.5
S503-KM4
S503-KM6
S503-KM6
S503-KM6
S503-KM9
S503-KM20
S503-KM20
S503-KM20
S503-KM32
S503-KM32
S503-KM52
S503-KM63
S503-KM75
16
16
16
16
25
25
45
55
55
55
100
200
200
200
400
400
580
800
840
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A16-30-10
A26-30-10
A26-30-10
A26-30-10
A26-30-10
A30-30-10
A40-30-00
A50-30-00
A63-30-00
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35
Thermal Overload
Relay
Type
TA25DU0.63
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA42DU42
TA75DU52
TA75DU63
Group
Current
Max.
setting range Current
[A]
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
Imax [A]
0.5
0.8
1
1.4
1.4
2.2
3.1
4
5
6.5
8.5
11
14
19
25
32
42
52
63
MC4050NS2.1KM
Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 18/02/2000 by Jean-Paul Guitton
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 1
Note : MC4000NS1.1
MO325
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
Magnetic
tripping
current
MO325-0.25
MO325-0.4
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4.0
MO325-6.3
MO325-9.0
MO325-12.5
MO325-16
MO325-20
MO325-25
[A]
2.44
3.9
6.14
11.5
11.5
16
16
27.5
27.5
40
67.7
112.5
156
200
250
312.5
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A16
A26
A26
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4.0
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
Imax [A]
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
MC4000NS1.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
400 V - 100 kA - Normal start - up, type : 2
Note : MC4000NS2.1
MO325
Rated
Current
Pe [kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
Ie [A]
0.22
0.34
0.44
0.72
0.83
1.12
1.45
1.9
2.6
3.5
4.8
6.5
8.5
11.5
15
22
Magnetic
tripping
current
MO325-0.25
MO325-0.4
MO325-0.63
MO325-1.0
MO325-1.0
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4.0
MO325-6.3
MO325-9.0
MO325-12.5
MO325-16
MO325-20
MO325-25
[A]
2.44
3.9
6.14
11.5
11.5
16
16
27.5
27.5
40
67.7
112.5
156
200
250
312.5
Contactor
Type
A9
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
A26
A26
A26
A26
A26
Safety
clearance
[mm]
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Thermal Overload
Relay
Type
Group
Current
Max.
setting range Current
TA25DU0.25
TA25DU0.4
TA25DU0.63
TA25DU1.0
TA25DU1.0
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
[A]
0.16 - 0.25
0.25 - 0.4
0.40 - 0.63
0.63 - 1
0.63 - 1
1.0 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
Imax [A
0.25
0.4
0.63
1
1
1.35
1.75
2.35
2.75
3.75
6.25
8
10.5
13.5
18.5
24
MC4000NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 01/02/2000 by Jean-Michel Eymery
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33
44
54
Contactor
Type
Current setting
Magnetic release
Type
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 1.6
S503-KM 2.5
S503-KM 2.5
S503-KM 4
S503-KM 6
S503-KM 9
S503-KM 9
S503-KM 20
S503-KM 20
S503-KM 20
S503-KM 32
S503KM 32
S503-KM 52
S503-KM 63
S503-KM 75
16
16
16
16
16
25
25
45
55
100
100
200
200
200
400
400
580
800
840
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00
A63-30-00
A95-30-00
Thermal Overload
Relay
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35
35
35
Type
Group
Current
Max.
setting range Current
TA 25DU0.4
TA 25DU0.93
TA 25DU1
TA 25DU1
TA 25DU1.4
TA 25DU1.8
TA 25DU2.4
TA 25DU3.1
TA 25DU4
TA 25DU6.5
TA 25DU8.5
TA 25DU11
TA 25DU14
TA 25DU19
TA 25DU25
TA 25DU32
TA 75DU42
TA 75DU52
TA 80DU63
[A]
0.25 - 0.4
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
Imax [A]
0.4
0.63
1
1
1.35
1.75
2.3
2.95
4
6.25
8.1
10.5
13.5
18.5
24.5
30.5
39
48.5
63
MC5025NS1.1
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
Ie [A]
0.35
0.58
0.68
0.9
1.2
1.5
2.1
2.7
3.8
5.1
6.5
8.9
11.9
17
22.5
28.5
33
44
54
Contactor
Type
Current setting
Magnetic release
Type
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM1.6
S503-KM2.5
S503-KM2.5
S503-KM4
S503-KM6
S503-KM9
S503-KM9
S503-KM20
S503-KM20
S503-KM20
S503-KM32
S503KM32
S503-KM52
S503-KM63
S503-KM75
16
16
16
16
16
25
25
45
55
100
100
200
200
200
400
400
580
800
840
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A9-30-10
A12-30-10
A12-30-10
A16-30-10
A16-30-10
A16-30-10
A16-30-10
A26-30-10
A30-30-10
A40-30-10
A50-30-00
A63-30-00
A95-30-00
Thermal Overload
Relay
Safety
clearance
[mm]
20
20
20
20
20
20
20
20
20
35
35
35
35
35
35
35
35
35
35
Type
TA25DU0.4
TA25DU0.93
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
TA25DU3.1
TA25DU4
TA25DU6.5
TA25DU8.5
TA25DU11
TA25DU14
TA25DU19
TA25DU25
TA25DU32
TA75DU42
TA75DU52
TA80DU63
Group
Current
Max.
setting range Current
[A]
0.25 - 0.4
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4
4.5 - 6.5
6 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
29 - 42
36 - 52
45 - 63
Imax [A]
0.4
0.63
1
1
1.35
1.75
2.3
2.95
4
6.25
8.1
10.5
13.5
18.5
24.5
30.5
39
48.5
63
MC5025NS2.1
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
500 V - 100 kA - Normal start - up, type : 1
Note : MC5000NS1.1
MO325
Circuit-Breaker
and Current Limitor
Rated
Output
Rated
Current
Pe [kW]
0.25
0.37
0.55
0.75
1.1
1.5
Ie [A]
0.66
0.88
1.2
1.5
2.1
2.8
2.2
2.5
3
4
5.5
7.5
11
15
3.8
4.3
5.2
6.9
9.1
12.2
17.5
22.8
Contactor
Type
Safety
clearance
Type
Limiter
type
PROLIM
Magnetic
tripping
current
Type
Current
Max
setting range Current
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
[A]
11.5
11.5
16
16
27.5
A9
A9
A9
A9
A9
[mm]
15
15
15
15
15
TA25DU1
TA25DU1
TA25DU1.4
TA25DU1.8
TA25DU2.4
[A]
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
MO325-4
40
A9
15
TA25DU3.1
2.2 - 3.1
Imax [A]
1
1
1.35
1.75
2.3
2.95
MO325-4
40
A9
15
TA25DU4
2.8 - 4
3.75
MO325-4
MO325-6.3
MO325-6.3
MO325-9
MO325-12.5
40
67.7
67.7
112.5
156
A9
A9
A12
A12
A16
15
15
15
15
15
TA25DU5
TA25DU5
TA25DU6.5
TA25DU8.5
TA25DU11
3.5 - 5
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
4.2
4.75
6.25
8
10.5
MO325-12.5
156
A26
15
TA25DU14
10 - 14
12.5
MO325-16
PLM 36-B*
200
A26
15
TA25DU14
10 - 14
13.5
MO325-20
MO325-25
PLM 36-B
PLM 36-B
250
312.5
A26
A26
15
15
TA25DU19
TA25DU25
13 - 19
18 - 25
18.5
23
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
500 V - 100 kA - Normal start - up, type : 2
Note : MC5000NS2.1
MO325
Circuit-Breaker
and Current Limitor
Rated
Output
Rated
Current
Pe [kW]
0.25
0.37
0.55
0.75
1.1
1.5
Ie [A]
0.66
0.88
1.2
1.5
2.1
2.8
2.2
2.5
3
4
5.5
7.5
11
15
3.8
4.3
5.2
6.9
9.1
12.2
17.5
22.8
Contactor
Type
Safety
clearance
Type
Limiter
type
PROLIM
Magnetic
tripping
current
Type
Current
Max
setting range Current
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
[A]
11.5
11.5
16
16
27.5
A9
A9
A9
A9
A12
[mm]
15
15
15
15
15
TA 25DU1
TA 25DU1
TA 25DU1.4
TA 25DU1.8
TA 25DU2.4
[A]
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
MO325-4
40
A12
15
TA 25DU3.1
2.2 - 3.1
Imax [A]
1
1
1.35
1.75
2.3
2.95
MO325-4
40
A16
15
TA 25DU4
2.8 - 4
3.75
MO325-4
MO325-6.3
MO325-6.3
MO325-9
MO325-12.5
40
67.7
67.7
112.5
156
A26
A26
A26
A26
A26
15
15
15
15
15
TA 25DU5
TA 25DU5
TA 25DU6.5
TA 25DU8.5
TA 25DU11
3.5 - 5
3.5 - 5
4.5 - 6.5
6 - 8.5
7.5 - 11
4.2
4.75
6.25
8
10.5
MO325-12.5
156
A26
15
TA 25DU14
10 - 14
12.5
MO325-16
PLM 36-B*
200
A26
15
TA 25DU14
10 - 14
13.5
MO325-20
MO325-25
PLM 36-B
PLM 36-B
250
312.5
A26
A26
15
15
TA 25DU19
TA 25DU25
13 - 19
18 - 25
18.5
23
Home
Fuse
MCCB
Coordination Table
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
690 V - 100 kA - Normal start - up, type : 1
Note : MC6900NS1.1
MO325
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
Ie [A]
0.26
0.42
0.48
0.65
0.84
1.1
1.5
1.99
2.54
2.77
3.74
4
5.5
7.5
11
4.97
6.41
8.54
12.4
Circuit Breaker
and Current Limiter
Contactor
Type
Safety
clearance
Type
Limiter
type
PROLIM
Magnetic
tripping
current
Type
Current
Max
setting range Current
MO325-0.40
MO325-0.63
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4
[A]
3.9
6.14
6.14
11.5
11.5
18.4
18.4
28.75
28.75
50
A9
A9
A9
A9
A9
A9
A9
A9
A9
A9
[mm]
15
15
15
15
15
15
15
15
15
15
TA 25DU0.40
TA 25DU0.63
TA 25DU0.63
TA 25DU1
TA 25DU1
TA 25DU1.4
TA25DU1.8
TA 25DU2.4
TA 25DU3.1
TA 25DU3.1
[A]
0.25 - 0.40
0.4 - 0.63
0.4 - 0.63
0.63 - 1
0.63 - 1
1.0 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.3 - 3.1
Imax [A]
0.40
0.63
0.63
1
1
1.35
1.75
2.35
2.6
3
MO325-4
50
A9
15
TA 25DU4
2.8 - 4.0
3.75
MO325-4
50
A9
15
TA 25DU5
3.5 - 5.0
4.5
MO325-6.3
MO325-6.3
PLM 20-C
78.75
78.75
A9
A9
15
15
TA 25DU6.5
TA 25DU8.5
4.5 - 6.5
6 - 8.5
6.25
6.7
MO325-9
PLM 20-C
135
A12
15
TA 25DU11
7.5 - 11
MO325-12.5
PLM 20-C
187.5
A16
15
TA25DU11
7.5 - 11
10
MO325-12.5
PLM 20-C
187.5
A26
15
TA 25DU14
10 - 14
13.5
MC6900NS1.1
Home
Fuse
Coordination Table
MCCB
MMS
Softstarters UL Comb.
MCB
Direct-on-line starters
690 V - 100 kA - Normal start - up, type : 2
Note : MC6900NS2.1
MO325
Circuit Breaker
and Current Limiter
Rated
Output
Rated
Current
Pe [kW]
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
1.85
2.2
3
Ie [A]
0.26
0.42
0.48
0.65
0.84
1.1
1.5
1.99
2.54
2.77
3.74
4
5.5
7.5
11
4.97
6.41
8.54
12.4
Contactor
Type
Safety
clearance
Type
Limiter
type
PROLIM
Magnetic
tripping
current
Type
Current
Max
setting range Current
MO325-0.40
MO325-0.63
MO325-0.63
MO325-1
MO325-1
MO325-1.6
MO325-1.6
MO325-2.5
MO325-2.5
MO325-4
[A]
3.9
6.14
6.14
11.5
11.5
18.75
18.75
28.75
28.75
50
A9
A9
A9
A9
A9
A9
A9
A9
A12
A12
[mm]
15
15
15
15
15
15
15
15
15
15
TA 25DU0.40
TA 25DU0.63
TA 25DU0.63
TA 25DU1
TA 25DU1
TA 25DU1.4
TA25DU1.8
TA 25DU2.4
TA 25DU3.1
TA 25DU3.1
[A]
0.25 - 0.40
0.4 - 0.63
0.4 - 0.63
0.63 - 1
0.63 - 1
1 - 1.4
1.3 - 1.8
1.7 - 2.4
2.3 - 3.1
2.3 - 3.1
Imax [A]
0.40
0.63
0.63
1
1
1.35
1.75
2.35
2.6
3
MO325-4
50
A12
15
TA 25DU4
2.8 - 4
3.75
MO325-4
50
A26
15
TA 25DU5
3.5 - 5
4.75
MO325-6.3
MO325-6.3
PLM 20-C
78.75
78.75
A26
A26
15
15
TA 25DU6.5
TA 25DU8.5
4.5 - 6.5
6 - 8.5
6.25
8.0
MO325-9
PLM 20-C
135
A26
15
TA 25DU11
7.5 - 11
MO325-12.5
PLM 20-C
187.5
A26
15
TA25DU11
7.5 - 11
10.5
MO325-12.5
PLM 20-C
187.5
A26
15
TA 25DU14
10 - 14
13.5
MC6900NS2.1
Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB
Latest changed 06/07/2001 by Jean-Paul Guitton