VXC Evaporative Condensers ................................................................. E2 Benefits ....................................................................................................... E4 Construction Details .................................................................................. E6 Custom Features and Options .................................................................. E8 Accessories ............................................................................................... E10 Engineering Data ..................................................................................... E12 Structural Support .................................................................................. E19 Engineering Specifications ..................................................................... E21
VXC - E 2
VXC
General Description
VXC Evaporative Condensers deliver fully rated thermal performance over a wide range of heat rejection and temperature requirements for various refrigerants. VXC and VXC-C models can be installed indoors and minimize sound levels. VXC-C models are designed to fit in standard dry van containers to minimize ocean freight costs. The Series VX occupies minimum floor space, provides year-round operating reliability and is ideal for sound sensitive applications.
Key Features
Suitable for indoor and outdoor installations Low sound Low ocean freight costs (VXC-C) Single side air inlet Low energy consumption Low installed cost Easy maintenance Reliable year-round operation Long service life Wide capacity range PED 97/23/EC coil design
Baltimore Aircoil
VXC - E 3
Evaporative Condensers
VXC - E 4
Benefits
Wide Capacity Range
Evaporative condenser capacity - The evaporative condensers are available in a broad range of unit capacities, with small capacity increments to permit close matching of unit size to design load. The VX line offers the widest selection of evaporative condensers in the industry to meet virtually every installation and application need.
VXC
Low Sound
Centrifugal Fan - Centrifugal fans have inherently low sound characteristics. Single Side Air Inlet - Particularly sound-sensitive areas can be accommodated by facing the quiet side (back panel) to the sound-sensitive direction.
Baltimore Aircoil
VXC - E 5
Evaporative Condensers
Easy Maintenance
Internal Access - The interior of the unit is easily accessible for adjusting the float valve, cleaning the strainer or flushing the basin.
The water level control is easily reached from the access door.
VXC - E 6
Construction Details
VXC
Upper Section
Lower Section
Baltimore Aircoil
VXC - E 7
Evaporative Condensers
3. Coil
Coil according to European Pressure Equipment Directive 97/23/EC Continuous serpentine, steel tubing Hot-dip galvanized after fabrication (HDGAF) Pneumatically tested at 34 bar standard coil Sloped tubes for free drainage of fluid
4. Drift Eliminators
UV resistant non-corrosive material, impervious to rot, decay and biological attack Three distinct changes in air direction to reduce drift loss significantly Assembled in easy to handle sections, which can be removed for access to the equipment interior
6. Centrifugal Fan(s)
Quiet Operation
8. Access Door
Circular access door
VXC - E 8
VXC
Optional BALTIBOND Corrosion Protection System: The BALTIBOND Corrosion Protection System, a hybrid polymer coating used to extend equipment life, is applied before assembly to all hot-dip galvanized steel components of the unit. Optional Stainless Steel Construction: Steel panels and structural elements are constructed of stainless steel either type 304 or 316. Optional Water-Contact Stainless Steel Cold Water Basin: A cost-effective alternative to an all stainless steel unit. The critical components in the cold water basin and the cold water basin itself are provided in stainless steel. The remaining components are protected with the BALTIBOND Corrosion Protection System.
Note: See section Technical Resources, Material of Construction for more details on the materials described above.
Coil Configurations
Each coil is manufactured according to the European Pressure Equipment Directive (PED) 97/23/EC (For more details, refer to the Evaporative Condenser "Overview" section) BAC condenser coils are standard available at a design pressure of 23 bar, and are pneumatically tested at 34 bar. Standard Serpentine Coil: The standard condensing coil is constructed of continuous lengths of all prime surface steel, hot-dip galvanised after fabrication (HDGAF).
Hot Dip Galvanised Coil
Multiple Circuit Coils (Split Coils): In general, multiple circuit coils are required primarily on halocarbon refrigerant systems where it is common practice to maintain individual compressor systems. Also, a circuit can be isolated to provide cooling of a water or glycol loop for compressor jacket cooling. A wide range of multiple circuit arrangements are available. Optional Extended Surface Coil: Coils are available with selected rows finned at 3 to 5 fins per inch for wet/dry applications. The coil is hot-dip galvanised after fabrication (HDGAF). Optional Stainless Steel Coil: Coils are available in Type 304L or 316L stainless steel for specialised applications. Optional High Pressure Coil: Coils are available with a design pressure of 28 bar and pneumatically tested at 40 bar. The Coil is hot-dip galvanised after fabrication (HDGAF). All coils are designed for low pressure drop with sloping tubes for free drainage of fluid.
Baltimore Aircoil
VXC - E 9
Evaporative Condensers
VXC - E 10
Accessories
Ladder, Safety Cage and handrails
In the event the owner requires easy access to the top of the unit, the unit can be furnished with ladders extending from the base of the unit to the top, as well as safety cages, and handrail packages.
VXC
Note: When these access options are employed, the unit must be equipped with steel drift eliminators.
Basin Heaters
Units exposed to below freezing ambient temperatures require protection to prevent freezing of the water in the cold water basin when the unit is idle. Factory-installed heaters, which maintain the water temperature at 4C, are a simple and inexpensive way of providing such protection. The heater package includes the heaters, a thermostat and a low level cut out switch to protect the heaters if the water level is too low. Standard electric heaters are selected for -18C ambient temperature.
Model No. VXC 14-28 36-65 72-97 110-135 150-205 221-454 495-516 562-680 714-908 / 715-804 990-1032
Heater -18C (kW) 1 x 1,5 1 x 1,5 1 x 2,5 1x3 1x4 1x6 2x4 2x5 2x6 4x4
Baltimore Aircoil
VXC - E 11
Model No. VXC 1124-1360 1430-1608 S288-S350 S403-S504 S576-S700 S806-S1010 C220 - C287 C325 - C426
Heater -18C (kW) 4x5 4x6 1x6 2x4 2x6 4x4 1x6
Evaporative Condensers
2x4
Discharge Hoods
Discharge hoods reduce the risk of re-circulation in tight enclosures by increasing discharge air velocity, and can be used to elevate the unit discharge above adjacent walls to comply with layout guidelines.
Desuperheater
Desuperheaters can be used in R-717 systems with reciprocating compressors. They increase the capacity of the standard model and extend the dry operation capacity. They are also effective in reducing the occurrence of visible plumes.
Steel Eliminators
Steel eliminators with Baltibond Corrosion Protection System are available for specific applications.
VXC - E 12
Engineering Data
REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This brochure includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice. Up-to-date engineering data and more can be found at www.BaltimoreAircoil.com.
VXC
1. For VXC 14 through VXC 28: refrigerant in ND 80; 2. For VXC 14 through VXC 28: refrigerant out ND 80: 3. For VXC 36 through VXC 265: refrigerant in ND 100; 4. For VXC 36 through VXC 265: refrigerant out ND 100; 5. Make-up; 6. Overflow; 7. Drain; 8. Access (models 14
Model
Operating Weight (kg) 660 740 830 900 1050 1170 1310 1330 1500 1810 1820 2080 2240 2510 2540 3210 3240 3670 3980 5860 6390 6435
Shipping Weight (kg) 600 670 760 830 920 1030 1160 1180 1330 1490 1500 1730 1800 2050 2080 2640 2670 2950 3255 4250 4770 4815
Heaviest Section Coil (kg) 580* 660* 480 540 920* 1030* 700 700 860 1000 1000 1200 1200 1440 1440 1720 1720 1980 2240 2630 3150 3150
H (mm) 2035 2245 2467 2683 2035 2245 2467 2467 2683 2578 2578 2813 2578 2813 2813 3093 3093 3328 3563 3585 3820 3820
L (mm) 914 914 914 914 1829 1829 1829 1829 1829 2737 2737 2737 3658 3658 3658 3645 3645 3645 3645 3550 3550 3550
W (mm) 1207 1207 1207 1207 1207 1207 1207 1207 1207 1207 1207 1207 1207 1207 1207 1438 1438 1438 1438 2397 2397 2397
Air Flow (m3/s) 2,3 2,2 2,5 2,4 4,6 5,0 4,8 5,3 5,5 5,8 7,5 7,1 10,4 9,9 10,9 13,3 15,8 15,7 16,9 20,8 21,2 22,7
Fan Motor (kW) (1x) 1,5 (1x) 1,5 (1x) 2,2 (1x) 2,2 (1x) 4,0 (1x) 4,0 (1x) 4,0 (1x) 5,5 (1x) 5,5 (1x) 4,0 (1x) 7,5 (1x) 7,5 (1x) 7,5 (1x) 7,5 (1x) 11,0 (1x) 7,5 (1x) 11,0 (1x) 11,0 (1x) 15,0 (1x) 15,0 (1x) 15,0 (1x) 18,5
Water Flow (l/s) 2,2 2,2 2,2 2,2 4,7 4,7 4,7 4,7 4,7 7,1 7,1 7,1 9,5 9,5 9,5 13,9 13,9 13,9 13,9 19,2 19,2 19,2
Pump Motor (kW) (1x) 0,25 (1x) 0,25 (1x) 0,25 (1x) 0,25 (1x) 0,37 (1x) 0,37 (1x) 0,37 (1x) 0,37 (1x) 0,37 (1x) 0,75 (1x) 0,75 (1x) 0,75 (1x) 0,75 (1x) 0,75 (1x) 0,75 (1x) 1,5 (1x) 1,5 (1x) 1,5 (1x) 1,5 (1x) 2,2 (1x) 2,2 (1x) 2,2
VXC 14 VXC 18 VXC 25 VXC 28 VXC 36 VXC 45 VXC 52 VXC 59 VXC 65 VXC 72 VXC 86 VXC 97 VXC 110 VXC 125 VXC 135 VXC 150 VXC 166 VXC 185 VXC 205 VXC 221 VXC 250 VXC 265
Baltimore Aircoil
VXC - E 13
Evaporative Condensers
1. Refrigerant in ND 100; 2. Refrigerant out ND 100; 3. Make-up ND 50; 4. Overflow ND 80; 5. Drain ND 50; 6. Access
Model
Operating Weight (kg) 7600 7630 7705 8320 10225 10285 11270 11320 12500 15120 15220 15400 16655 20555 20755 22570 22770 25035
Shipping Weight (kg) 5525 5555 5630 6180 7170 7230 8125 8175 9260 10880 10980 11100 12355 14415 14615 16420 16550 18505
Heaviest Section (coil) (kg) 3850 3850 3850 4470 4715 4715 5710 5710 6690 3840 3840 3840 4470 5120* 5120* 5710 5710 6690
H (mm) 4248 4248 4248 4483 4013 4013 4248 4248 4483 4248 4248 4248 4483 4013 4013 4248 4248 4483
L (mm) 3550 3550 3550 3550 5385 5385 5385 5385 5385 7226 7226 7226 7226 10903 10903 10903 10903 10903
W (mm) 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397
Air Flow (m3/s) 22,8 24,2 26,7 26,2 36,6 38,9 34,9 37,5 36,6 45,6 48,4 53,4 52,4 73,2 77,8 69,8 75,0 73,2
Fan Motor (kW) (1x) 18,5 (1x) 22,0 (1x) 30,0 (1x) 30,0 (1x) 30,0 (1x) 37,0 (1x) 30,0 (1x) 37,0 (1x) 37,0 (2x) 18,5 (2x) 22,0 (2x) 30,0 (2x) 30,0 (2x) 30,0 (2x) 37,0 (2x) 30,0 (2x) 37,0 (2x) 37,0
Water Flow (l/s) 25,2 25,2 25,2 25,2 38,5 38,5 38,5 38,5 38,5 50,4 50,4 50,4 50,4 77,0 77,0 77,0 77,0 77,0
Pump Motor (kW) (1x) 2,2 (1x) 2,2 (1x) 2,2 (1x) 2,2 (1x) 4 (1x) 4 (1x) 4 (1x) 4 (1x) 4 (2x) 2,2 (2x) 2,2 (2x) 2,2 (2x) 2,2 (2x) 4 (2x) 4 (2x) 4 (2x) 4 (2x) 4
R717 Charge (kg) 164 164 164 196 198 198 246 246 294 328 328 328 392 396 396 492 492 588
VXC S288 VXC S300 VXC S328 VXC S350 VXC S403 VXC S429 VXC S455 VXC S482 VXC S504 VXC S576 VXC S600 VXC S656 VXC S700 VXC S806 VXC S858 VXC S910 VXC S964 VXC S1010
VXC - E 14
VXC
1. Refrigerant in ND 100; 2. Refrigerant out ND 100; 3. Make-up; 4. Overflow ND 80; 5. Drain ND 50; 6. Access; For VXC 357 through VXC 908: make-up ND 50; For VXC 1124 through VXC 1360 Make-up ND 80.
Model
Operating Weight (kg) 6940 8290 9580 11490 12680 14100 14430 16590 19140 22740 25240 28090
Shipping Weight (kg) 5300 6600 7860 8990 10200 11530 10600 13200 15700 17940 20380 23100
Heaviest Section (coil) (kg) 3940 4730 5510 5810 7010 8200 3940 4730 5510 5810* 7010 8200
H (mm) 4075 4310 4545 4075 4310 4545 4075 4310 4545 4075 4310 4545
L (mm) 3550 3550 3550 5388 5388 5388 7226 7226 7226 10903 10903 10903
W (mm) 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000
Air Flow (m3/s) 34,3 31,6 34,4 51,2 50,0 52,0 68,6 63,2 68,8 102,4 100,1 104,0
Fan Motor (kW) (1x) 22,0 (1x) 22,0 (1x) 30,0 (2x) 18,5 (2x) 18,5 (2x) 22,0 (2x) 22,0 (2x) 22,0 (2x) 30,0 (4x) 18,5 (4x) 18,5 (4x) 22,0
Water Flow (l/s) 30,8 30,8 30,8 46,7 46,7 46,7 61,6 61,6 61,6 93,4 93,4 93,4
Pump Motor (kW) (1x) 4 (1x) 4 (1x) 4 (1x) 4 (1x) 4 (1x) 4 (2x) 4 (2x) 4 (2x) 4 (2x) 4 (2x) 4 (2x) 4
R717 Charge (kg) 180 218 250 250 350 390 360 436 500 500 700 780
VXC 357 VXC 399 VXC 454 VXC 562 VXC 620 VXC 680 VXC 714 VXC 798 VXC 908 VXC 1124 VXC 1240 VXC 1360
Baltimore Aircoil
VXC - E 15
Evaporative Condensers
1. Refrigerant in ND 100; 2. Refrigerant out ND 100; 3. Make-up; 4. Overflow ND 80; 5. Drain ND 50; 6. Access. For VXC 495 through VXC 1032 : Make-up ND50; For VXC 1430 through VXC 1608: Make-up ND 80.
Model
Operating Weight (kg) 12040 13030 17555 17735 19290 24185 26095 35200 35560 38665
Shipping Weight (kg) 8210 9170 11855 12035 13435 16520 18280 23680 23770 26845
Heaviest Section (coil) (kg) 5610 6550 8310 8310 9710 5610 6550 8300 8300 9710
H (mm) 4310 4545 4310 4310 4545 4310 4545 4310 4310 4545
L (mm) 3550 3550 5388 5388 5388 7226 7226 10903 10903 10903
W (mm) 3607 3607 3607 3607 3607 3607 3607 3607 3607 3607
Air Flow (m3/s) 40,0 39,4 56,1 62,3 60,4 80,0 78,8 112,2 124,6 120,8
Fan Motor (kW) (1x) 37,0 (1x) 37,0 (2x) 22,0 (2x) 30,0 (2x) 30,0 (2x) 37,0 (2x) 37,0 (4x) 22,0 (4x) 30,0 (4x) 30,0
Water Flow (l/s) 39,1 39,1 56,8 56,8 56,8 78,2 78,2 113,6 113,6 113,6
Pump Motor (kW) (1x) 4 (1x) 4 (1x) 4 (1x) 4 (1x) 4 (2x) 4 (2x) 4 (2x) 4 (2x) 4 (2x) 4
R717 Charge (kg) 250 298 374 374 450 500 596 748 748 900
VXC 495 VXC 516 VXC 715 VXC 772 VXC 804 VXC 990 VXC 1032 VXC 1430 VXC 1544 VXC 1608
VXC - E 16
VXC
1. Refrigerant in ND 100; 2. Refrigerant out ND 100; 3. Make-up ND 50; 4. Overflow ND 80; 5. Drain ND 50; 6. Access Fan covers are shipped loose.
Model
Operating Weight (kg) 5940 6415 6440 7450 8730 8735 9430 9470 10260
Shipping Weight (kg) 4250 4770 4795 5315 6135 6145 6945 7030 7830
Heaviest Section (coil) (kg) 2630 3150 3150 3665 3885 3885 4685 4685 5485
H (mm) 3585 3820 3820 4055 3585 3585 3820 3820 4055
L (mm) 3550 3550 3550 3550 5385 5385 5385 5385 5385
W (mm) 2245 2245 2245 2245 2245 2245 2245 2245 2245
Air Flow (m3/s) 20,6 20,1 21,7 22,5 31,5 33,5 32,2 35,5 34,7
Fan Motor (kW) (1x) 15,0 (1x) 15,0 (1x) 18,5 (1x) 22,0 (1x) 18,5 (1x) 22,0 (1x) 22,0 (1x) 30,0 (1x) 30,0
Water Flow (l/s) 19,2 19,2 19,2 19,2 29,0 29,0 29,0 29,0 29,0
Pump Motor (kW) (1x) 2,2 (1x) 2,2 (1x) 2,2 (1x) 2,2 (1x) 4 (1x) 4 (1x) 4 (1x) 4 (1x) 4
R717 Charge (kg) 118 146 146 154 156 156 196 196 234
VXC C220 VXC C250 VXC C265 VXC C287 VXC C325 VXC C340 VXC C380 VXC C408 VXC C426
General Notes
1. Standard refrigerant connection sizes are ND 100 BSP MPT inlet and outlet (for models VXC 14 through 28 refrigerant connection sizes are ND 80 BSP MPT), consult your local BAC representative for size and location. Other connection sizes are available on special order. Refrigerant connections are standard bevelled for welding. 2. Make up, overflow, suction, drain connections and access door can be provided on side opposite to that shown; consult your BAC Balticare representative. 3. Unit height is indicative, for precise value refer to certified print. 4. Shipping/operating weights indicated are for units without accessories such as sound attenuators, discharge hoods, etc. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted. 5. The drawings for units with only one spray pump show the standard right hand arrangement, which has the air inlet side on the right when facing the connection end. Left hand arrangement can be furnished by special order. 6. Coil, overflow, make-up and spray water connections are always located on the same end of the unit. For double pump units an additional set of coil connections and an additional overflow connection will be installed on the other end of the unit. 7. On models VXC 14 through VXC 135 access doors are located at the opposite of the air inlet side, ensure sufficient space for entry when positioning these units. 8. For indoor applications of evaporative condensers, the room may be used as a plenum with ductwork attached to the discharge only. If inlet ductwork is required, an enclosed fan section must be specified; consult your BAC representative for details. 9. Fan kW is at 0 Pa ESP. To operate against external static pressure up to 125 Pa, increase each fan motor one size. 10.Refrigerant charge listed is R 717 operating charge. To determine operating charge of R22 refrigerants, multiply by: 1,93. For R134A, multiply by: 1,98. 11.For dry operation, standard motors must be increased one size to avoid motor overloading. Extended surface coils are available to vastly increase dry capacity without motor size increase. Consult your local BAC Balticare representative for selection and pricing. 12.Models VXC 357-454, VXC 562-380, VXC 495-516 and VXC 715-804 have only 1 coil casing section and one or two fan motors. Fan cycling results in only on-off operation. On these units all fans need to operate simultaneously. 13.Models VXC 714-907, VXC 1124-1360, VXC 990-1032 and VXC 1430-1608 have 2 coil casing sections and one or two fan motors per coil casing section. Fan cycling results in only on-off operation. On these units all fans need to operate simultaneously per coil casing section.
Baltimore Aircoil
VXC - E 17
Sound Attenuation
XA + XB Sound Attenuation
Evaporative Condensers
1. Access Door; L1= Intake Attenuator Length; L2= Discharge Attenuator Length; W= Unit Width; H.= Unit Height (see Engineering Data).
XC Sound Attenuation
1. Access Door; L1= Intake Attenuator Length; L2= Discharge Attenuator Length; W= Unit Width; H.= Unit Height (see Engineering Data).
VXC - E 18
VXC
# Access doors
(2)
Dimensions (mm) W2 XA, XB XC 2352 2352 2352 2352 2583 3542 3542 3542 3542 3542 4145 4145 4145 4145 4752 4752 4752 4752 H1 W1 L1 L2 XA 902 1816 2731 3645 3645 3645 3645 5480 110 175 230 300 380 500 500 660 Intake XB XC Solid Bottom 30 50 70 100 120 190 190 300 380 600 230 350 460 700 280 420 560 840
Weights (kg) Discharge XA 130 175 280 360 440 530 660 XB XC XA Total XB 310 490 720 890 XC N.A. N.A. N.A. N.A.
14 - 28 36 - 65 72 - 97
4(1) 4(1) 4 4 4 4 4 4 7 7 4 4 7 7 4 4 7 7
150 N.A. 270 220 N.A. 400 350 N.A. 580 420 N.A. 760
N.A. 1090 1030 1800 N.A. 1090 1030 2710 N.A. 1090 1030 3635 3728 1600 1420 3635 4687 2070 1955 3525 4687 2070 2365 3525 4687 2070 2365 5365 4687 2070 2365 7050
VXC
110 - 135 150 - 205 221 - 265 S288 - S350 S403 - S504 S576 - S700 S806 S1010 357 - 454 562 - 680 714 - 908 1124 - 1360 495 - 516 715 - 804 990 - 1032 1430 - 1608
520 1070 940 1120 2270 650 1330 1220 1470 2940 800 1640 1350 1620 3250
830 1090 2240 1790 2250 4510 1320 1600 3280 2700 3240 6500 1660 2180 4480 3580 4500 9020 710 880 1820 1500 1820 3670
4687 2070 2365 10730 10998 1320 1720 3940 5290 2560 2965 3525 5290 2560 2965 5365 5290 2560 2965 7050 3645 5480 560 730 710 1620 980 2240
900 1210 2490 1980 2540 5080 1420 1760 3640 3000 3640 7340 1800 2420 4980 3960 5080 10160 810 1030 2130 1650 2020 4030 1020 1410 2920 2170 2810 5580 1620 2060 4260 3300 4040 8060 2040 2820 5840 4340 5620 11160
5290 2560 2965 10730 10994 1460 1960 4480 5897 2560 3575 3525 5897 2560 3575 5365 5897 2560 3575 7050 3645 5480 560 730 710 1620 980 2240
(1)
VXC 14, VXC 18, VXC-36 and VXC-45 + Attenuator are shipped in 3 pieces
(2) Intake Attenuator: Access opening is 775 mm high, 405 mm wide and is located at each end of the unit. Discharge Attenuator : Access opening is 405 mm high, 1170 mm wide and is located at blank off side of the unit (VXC14-28 has 650 mm width)
Baltimore Aircoil
VXC - E 19
Structural Support
REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This brochure includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice. Up-to-date engineering data and more can be found at www.BaltimoreAircoil.com.
The recommended support arrangement for units consists of parallel I-beams running the full length of the unit, spaced as shown in the following drawing. Besides providing adequate support, the steel also serves to raise the unit above any solid foundation to ensure access to the bottom of the unit. To support units in an alternate steel support arrangement, consult your BAC Balticare Representative.
Evaporative Condensers
Model
A Unit Length (mm) 914 1829 2737 3658 3645 3550 3550 5385 7226
B Unit width (mm) 1207 1207 1207 1207 1438 2397 2397 2397 2397
C D Center dis. Center dis. Length Width (mm) (mm) 750 1664 2572 3492 3492 3238 3238 5074 6914 1153 1153 1153 1153 1378 2397 2327 2327 2327
G (mm) -
Mounting holes 4 4 4 4 4 4 4 8 8
VXC 14-28 VXC 36-65 VXC 72-97 VXC 110-135 VXC 150-205 VXC 221-265 VXC S288-S350 VXC S403-S504 VXC S576-S700
VXC - E 20
Model
A Unit Length (mm) 10903 3550 5388 7226 10903 3550 5388 7226 10903 3550 5385
B Unit width (mm) 2397 3000 3000 3000 3000 3607 3607 3607 3607 2245 2245
C D Center dis. Center dis. Length Width (mm) (mm) 10586 3238 5074 6914 10586 3238 5074 6914 10586 3238 5074 2327 2934 2934 2934 2934 3537 3537 3537 3537 2175 2175
Mounting holes 16 4 8 8 16 4 8 8 16 4 8
VXC S806-S1010 VXC 357-454 VXC 562-680 VXC 714-908 VXC 1124-1360
VXC
VXC 495-516 VXC 715-804 VXC 990-1032 VXC 1430-1608 VXC C220-C287 VXC C325-C426
1. Outline of Unit; 2. Mounting Holes 22 mm; 3. Outline of attenuator (optional XA or XB);4. Support Channel attached to optional XA or XB attenuator; 5.+3. Outline of Attenuator (optional XC); 6.+4. Support Channels attached to optional XC attenuator; 7. Unit; 8. Sound Attenuator; 9. Air Intake.
Notes:
1. The recommended support arrangement for VX units consists of parallel I-beams extending the full length of the unit. Supports and anchor bolts are to be designed and furnished by others. 2. All supporting beams are to be flush and level at top and must be oriented relative to gage line as shown. 3. Recommended design loads for each unit support beam should be 70% of the total unit operating weight applied as a uniform load to each of the unit beams. The support beam(s) for the optional intake attenuator(s) needs to carry attenuator only, uniform load of 250 kg/m. Beams should be designed in accordance with standard structural practice. For the maximum allowable deflection of beams under the unit refer to above table. 4. All mounting holes have a diameter of 22 mm at the locations shown. 5. If vibration isolators are used, a rail or channel must be provided between the unit (and optional attenuator) and the isolators to provide continuous unit support. Additionally the support beams must be designed to accommodate the overall length and mounting hole location of the isolators that may differ from those of the unit. Refer to vibration isolator drawings for these data.
Baltimore Aircoil
VXC - E 21
Engineering Specifications
General
A. General: Furnish and install, _____ factory assembled evaporative condenser(s) of counterflow blow-through design, with single side entry, conforming in all aspects to the specifications and schedule as shown on the plans. B. Capacity: The evaporative condenser(s) shall be warranted by the manufacturer to have condensing capacity of _____ kW heat rejection, operating with ____ refrigerant and ___C condensing temperature and ___C entering wet-bulb temperature. C. Warranty: The manufacturers standard equipment warranty shall be for a period of one year from the date of startup or eighteen months from the date of shipment, whichever ends first. D. Quality Assurance: The manufacture shall have Management System certified by an accredited registrar as complying with the requirements of ISO-9001:2000 to ensure consistent quality of products and services.
Evaporative Condensers
Products
1.0 Evaporative Condenser Materials and Components
General: All steel panels and structural elements shall be constructed from heavy-gauge, Z600 hot-dip galvanized steel, with cut edges given a protective coating of zinc-rich compound.
VXC
5.0 Sound
5.1 Sound Level: To maintain the quality of the local environment, the maximum sound pressure levels (dB) measured 15 m from the condenser operating at full fan speed shall not exceed the sound levels detailed below.
63
125
250
500
1000
2000
4000
8000
dB(A)
Baltimore Aircoil