Underwriters Laboratories (UL) is the independent testing body that has developed the standard UL 1008 which all major transfer switch manufacturers test to. UL lists products which have successfully passed a battery of witnessed tests including the withstand and close into fault tests described herein. Manufacturers that complete these tests are then permitted to label their products with the UL mark.
UL made significant changes in April of 1989 regarding the labeling requirements of transfer switches. Prior to that date there had been concern over coordination with some protective devices. UL clarified the labeling procedure and now allows for three rating categories.
Current limiting fuse Specific class (trip time) of molded case breaker Umbrella or Any Breaker ratings that take into account all types of molded and insulated case circuit breakers; these tests are performed for a duration of 3 cycles on units 225 amps and greater, and for 1.5 cycles on 40-150 amp units (with an optional 3 cycle duration for units up to 150 amps; note the three cycle rating on 150 amp and below units is optional as UL has determined that all breakers in this size clear in less than 1.5 cycles). The Umbrella or Any Breaker rating is therefore the actual UL requirement and definition of the ATS industry 3 cycle (or 1.5 as noted) withstand and closing rating, and should not to be confused with additional, non UL 1008 labeled withstand only tests.
If a transfer switch does not have adequate withstand capabilitysystem failure, fire, injury to personnel or equipment damage may result. A clear understanding of the interrelationship between the protective device, transfer switch and system needs is necessary for a well designed installation. Some basic information on withstand rating terms and calculations follows the enclosed rating charts.
TB-1102 Page 2
UL Letter
Page 3 TB-1102
Test Documents
As fault currents can occur at any level, a transfer switch must be capable of withstanding any fault current up to its maximum rating. This rating is based on the rating of the protective device in front of the unit and must be considered on that basis.
GE tests show results based on various current values and time durations, and include additional high current tests with fuses. By considering this range of values, it is possible to predict performance with different fuse characteristics or specific circuit breaker currenttime curves with a given available short circuit current.
Basic Denitions
a.
RMS Current The Root Mean Square which is the effective value of an alternating current. It is equal to .707 of the peak current for a sine wave. This is the value referred to when people say current.
Interrupting Ratings
Some manufacturers of circuit breaker type automatic transfer switches list interrupting current (IC) ratings in lieu of WCR. These switches will then open on faults instead of withstanding the fault until the external protective device clears. As the transfer switch is then used to open the fault current in place of a protective devicethis may leave the transfer switch with both normal and emergency open which then requires manual resetting of the breakers within the transfer switch enclosure. The circuit breakers may require factory inspection after high current interruption in accordance with common circuit breaker procedures. WCR ratings, as opposed to IC ratings appear to offer a better choice to the system designer as he attempts to coordinate the protection of the entire system. Knowing the maximum amount and duration of fault current a switch will withstand gives the designer the information necessary for complete coordinated system design.
b. c. d. e. f. g. h.
Peak Current The instantaneous maximum value of current the peak current of a sine wave is 1.414 times its RMS value. Symmetrical Current The alternating current which is symmetrical around the zero axis of the sine wave. Asymmetrical Current The alternating current which is not symmetrical around the zero axis. Peak Fault Current The instantaneous maximum current value that occurs after the start of a fault in any phase. Available Peak Current Maximum possible short circuit current that may exist in a system without protective devices. Peak Let Through Current Maximum instantaneous current through the protective device during the total clearing time. Withstand Current Rating The rating that defines the ability of the switch to withstand the thermal and electromagnetic effects of short circuit currents for a set period of time. Withstand and Closing Rating (WCR) UL 1008 test for a transfer switchs ability to close into and withstand a fault current. These are the ratings which will actually appear on the UL label of the product.
i.
NOTE: For diagrams of typical current wave forms, see Figure 1 and Figure 2.
Comparison of Terms
The following values have all been used to describe identical circuit conditions: a. b. c. d. e. Available Short Circuit Current RMS Peak Let Through Current ( cycle) Peak Asymmetrical Current Peak Symmetrical Current Withstand Rating 3 Cycles RMS
120,000 amps 130,000 amps 156,000 amps 140,000 amps 128,000 amps
What do these numbers mean? They mean that a switch was tested at 28,000 amps RMS Sym for 3 cycles; the switch also had a projected peak symmetrical current of 40,000 amps for less than cycle and a peak asymmetrical current of 56,000 amps for less than cycle. The switch has been tested in a system that has an available capacity of 120,000 amps RMS. How should a manufacturer rate a switch? Preferably by submitting test data which is reported as outlined by UL 1008 specifications. This data calls for RMS symmetrical readings based on specific test parameters. Other figures may be misleading.
TB-1102 Page 4
EXAMPLE: 500 kVA transformer 2.5% Impedance 480 Volts, 3 phase 500 x 1000 1.73 (.025) (480) = 24,085 amps
This figure is somewhat lower if a long run of cable introduces a substantial volt drop. Available fault current determine the WCR rating that a transfer must meet.
Page 5 TB-1102
F14B/C
260
N/A N/A N/A N/A N/A
50,000
50,000
ZTSCT4
50,000 30,000
F14C
F14B
TB-1102 Page 6
ZTG
ZTGD
ZTX
MX60
Controller >>
80 50,000 65,000
100
F17
30,000
150
200
N/A
F14B
225
N/A
300 50,000 65,000 85,000 ZTS 85,000 ZBTS 85,000 ZBTS 85,000 ZBTS 85,000 ZTS2 65,000 ZTS2 65,000 ZTS2 65,000 ZTS2 65,000 F14 ZTS2 ZTS 50,000 50,000 65,000
F14
N/A
400
50,000
600
800
ZTS2
65,000
ZTS2
1000
1200
ZTS
85,000
ZTS
1600 100,000 ZTS 100,000 ZBTS 100,000 ZBTS 100,000 ZBTS 100,000 ZTS 100,000 ZTS 100,000
2000
2600
ZTS
100,000
ZTS
2600 3000
N/A N/A
3000
4000
4000
UL References:
ZTS E23911, Vol. 4, Sec. 10 (1000-1200A), Sec. 12 (1600-2000A), Sec. 11 (2600-3000A) Sec. 15 (4000A)
Automatic Transfer Switch Coordinated Breaker & Current Limiting Fuse Withstand & Closing Ratings (WCR)
Current Limiting Fuse Specific Coordinated Breaker Rating Any Molded Case Breaker Rating Maximum Maximum Maximum Maximum Maximum Maximum Maximum Maximum Fuse Circuit Amps Circuit Amps Circuit Amps Circuit Amps Circuit Breaker Circuit Amps Circuit Amps at 600 VAC Size, Amps at 600 VAC at 600 VAC at 480 VAC (UL) Size, Amps at 480 VAC (UL) at 480 VAC (UL) (CSA) (CSA) (CSA)
50 100 125 200 300 350 600 750 1,000 1,250 1,500 2,000 2,500 4,000 6,000 50 100 125 200 300 350 600 750 1,000 1,250 1,500 2,000 2,500 4,000 6,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 N/A 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 800 800 800 800 800 800 800 800 1,200 1,600 1,600 2,500 2,500 4,000 5,000 200,000 150,000 5,000 200,000 150,000 4,000 200,000 150,000 2,500 200,000 150,000 2,500 200,000 150,000 1,600 85,000 100,000 100,000 100,000 100,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 65,000 65,000 85,000 85,000 100,000 100,000 100,000 100,000 200,000 150,000 1,600 85,000 200,000 N/A 1,600 65,000 200,000 150,000 800 65,000 200,000 200,000 800 50,000 200,000 200,000 800 50,000 42,000 42,000 50,000 N/A 65,000 65,000 85,000 85,000 85,000 85,000 42,000 42,000 42,000 42,000 42,000 42,000 42,000 50,000 N/A 65,000 65,000 85,000 85,000 85,000 85,000 200,000 200,000 800 50,000 42,000 200,000 200,000 400 30,000 22,000 200,000 200,000 400 30,000 22,000 200,000 200,000 400 30,000 22,000 200,000 200,000 400 30,000 22,000 10,000 10,000 10,000 10,000 35,000 35,000 35,000 50,000 50,000 50,000 50,000 100,000 100,000 100,000 100,000 35,000 35,000 35,000 35,000 35,000 35,000 35,000 50,000 50,000 50,000 50,000 100,000 100,000 100,000 100,000 10,000 10,000 10,000 10,000 35,000 35,000 35,000 42,000 N/A 42,000 42,000 85,000 85,000 85,000 85,000 35,000 35,000 35,000 35,000 35,000 35,000 35,000 42,000 N/A 42,000 42,000 85,000 85,000 85,000 85,000
40
80
100
150
225
260
400
600
800
1,000
1,200
1,600
2,000
3,000
4,000
40
80
100
150
225
260
400
600
800
1,000
1,200
1,600
2,000
3,000
Page 7 TB-1102
4,000
Automatic Transfer Switch Coordinated Breaker & Current Limiting Fuse Withstand & Closing Ratings (WCR)
Current Limiting Fuse Maximum Maximum Maximum Maximum Maximum Maximum Maximum Maximum Fuse Circuit Amps Circuit Amps Circuit Amps Circuit Amps Circuit Breaker Circuit Amps Circuit Amps Size, Amps at 600 VAC at 600 VAC at 600 VAC at 480 VAC (UL) Size, Amps at 480 VAC (UL) at 480 VAC (UL) (CSA) (CSA) (CSA)
125 200 300 350 600 750 1,000 1,250 1,500 2,000 2,500 4,000 4,000 6,000 50 100 125 200 300 350 600 N/A 1,000 1,250 1,500 2,000 2,500 4,000 6,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 N/A 150,000 150,000 150,000 150,000 150,000 150,000 N/A N/A 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 400 800 800 800 800 1,200 1,600 1,600 2,500 2,500 4,000 5,000 200,000 200,000 400 200,000 200,000 400 200,000 200,000 400 200,000 150,000 5,000 200,000 150,000 4,000 100,000 100,000 30,000 30,000 30,000 30,000 30,000 50,000 50,000 50,000 65,000 85,000 85,000 100,000 100,000 100,000 100,000 200,000 N/A N/A N/A 200,000 150,000 2,500 100,000 200,000 150,000 2,500 100,000 200,000 150,000 1,600 85,000 200,000 150,000 1,600 85,000 65,000 65,000 85,000 85,000 N/A 85,000 85,000 22,000 22,000 22,000 22,000 22,000 42,000 42,000 N/A 50,000 65,000 65,000 85,000 85,000 85,000 85,000 200,000 150,000 1,600 85,000 65,000 200,000 150,000 800 65,000 50,000 200,000 200,000 800 50,000 42,000 200,000 200,000 800 50,000 42,000 200,000 200,000 800 50,000 42,000 35,000 35,000 35,000 50,000 50,000 50,000 50,000 100,000 100,000 100,000 100,000 100,000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 200,000 200,000 800 50,000 42,000 35,000 200,000 200,000 800 50,000 42,000 35,000 35,000 35,000 35,000 35,000 35,000 42,000 42,000 42,000 42,000 85,000 85,000 N/A 85,000 85,000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
TB-1102 Page 8
100
150
225
260
400
600
800
1,000
1,200
1,600
2,000
2,600
3,000
4,000
ZTG
40
ZTG
80
ZTG
100
ZTG
150
ZTG
225
ZTG
260
ZTG
400
ZTG
600
ZTG
800
ZTG
1,000
ZTG
1,200
ZTG
1,600
ZTG
2,000
ZTG
3,000
ZTG
4,000
Automatic Transfer Switch Coordinated Breaker & Current Limiting Fuse Withstand & Closing Ratings (WCR)
Current Limiting Fuse Specific Coordinated Breaker Rating Any Molded Case Breaker Rating Maximum Maximum Maximum Maximum Maximum Maximum Maximum Circuit Amps Circuit Amps Circuit Amps Maximum Fuse Circuit Amps Circuit Breaker Circuit Amps Circuit Amps at 600 VAC at 600 VAC at 600 VAC Size, Amps at 480 VAC (UL) Size, Amps at 480 VAC (UL) at 480 VAC (UL) (CSA) (CSA) (CSA)
50 100 125 200 300 350 600 N/A 1,000 1,250 1,500 2,000 2,500 4,000 50 100 125 200 300 300 400 500 200,000 200,000 N/A N/A 200,000 N/A 200,000 N/A 200,000 N/A 200,000 N/A 200,000 N/A 400 400 400 400 400 800 800 200,000 N/A 400 200,000 150,000 4,000 200,000 150,000 2,500 200,000 150,000 2,500 200,000 150,000 1,600 85,000 100,000 100,000 100,000 30,000 30,000 30,000 30,000 30,000 30,000 50,000 50,000 Consult Factory 125 200 300 350 600 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 800 800 800 800 800 50,000 50,000 50,000 50,000 50,000 42,000 42,000 42,000 42,000 42,000 35,000 35,000 35,000 35,000 35,000 35,000 35,000 35,000 35,000 35,000 5,000 10,000 10,000 10,000 10,000 200,000 150,000 1,600 85,000 200,000 N/A 1,200 65,000 N/A N/A 800 50,000 200,000 200,000 800 50,000 200,000 200,000 800 50,000 42,000 42,000 N/A N/A 65,000 65,000 85,000 85,000 85,000 N/A N/A N/A N/A N/A N/A N/A N/A 200,000 200,000 800 50,000 42,000 200,000 200,000 800 50,000 42,000 200,000 200,000 800 50,000 42,000 200,000 200,000 800 50,000 42,000 200,000 200,000 800 50,000 42,000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
ZTGD
40
ZTGD
80
ZTGD
100
ZTGD
150
ZTGD
225
ZTGD
260
ZTGD
400
ZTGD
600
ZTGD
800
ZTGD
1,000
ZTGD
1,200
ZTGD
1,600
ZTGD
2,000
ZTGD
3,000
ZTX
40
ZTX
80
ZTX
100
ZTX
150
ZTX
200
ZTX
225
ZTX
300
ZTX
400
40
80
ZTSCT
100
ZTSCT
150
ZTSCT
225
ZTSCT
260
Page 9 TB-1102
ZTSCT
400
Automatic Transfer Switch Coordinated Breaker & Current Limiting Fuse Withstand & Closing Ratings (WCR)
Current Limiting Fuse Maximum Maximum Maximum Maximum Maximum Maximum Maximum Circuit Amps Circuit Amps Maximum Fuse Circuit Amps Circuit Amps Circuit Breaker Circuit Amps Circuit Amps at 600 VAC at 600 VAC Size, Amps at 600 VAC at 480 VAC (UL) Size, Amps at 480 VAC (UL) at 480 VAC (UL) (CSA) (CSA) (CSA)
750 1,000 1,250 1,500 2,000 2,500 4,000 6,000 125 200 300 350 600 750 1,000 1,250 1,500 2,000 2,500 4,000 4,000 6,000 200,000 200,000 150,000 150,000 200,000 N/A 200,000 150,000 200,000 150,000 200,000 150,000 1,600 2,500 2,500 N/A 4,000 5,000 200,000 150,000 1,600 200,000 150,000 1,600 200,000 150,000 800 200,000 200,000 800 200,000 200,000 800 50,000 50,000 65,000 85,000 85,000 85,000 100,000 100,000 N/A 100,000 100,000 200,000 200,000 800 50,000 200,000 200,000 800 50,000 200,000 200,000 800 50,000 200,000 150,000 5,000 100,000 85,000 42,000 42,000 42,000 42,000 42,000 50,000 65,000 65,000 65,000 85,000 85,000 N/A 85,000 85,000 200,000 150,000 4,000 100,000 85,000 200,000 150,000 2,500 100,000 85,000 200,000 150,000 2,500 100,000 85,000 200,000 150,000 1,600 85,000 65,000 200,000 150,000 1,600 85,000 65,000 50,000 50,000 100,000 100,000 100,000 100,000 35,000 35,000 35,000 35,000 35,000 50,000 50,000 50,000 50,000 100,000 100,000 100,000 100,000 100,000 200,000 N/A 1,200 65,000 N/A 50,000 200,000 150,000 800 65,000 50,000 50,000 42,000 N/A 42,000 42,000 85,000 85,000 85,000 85,000 35,000 35,000 35,000 35,000 35,000 42,000 42,000 42,000 42,000 85,000 85,000 N/A 85,000 85,000
TB-1102 Page 10
600
800
1,000
1,200
1,600
2,000
3,000
4,000
100
150
225
260
400
600
800
1,000
1,200
1,600
2,000
2,600
3,000
4,000
Automatic Transfer Switch Coordinated Breaker & Current Limiting Fuse Withstand & Closing Ratings (WCR)
Current Limiting Fuse Specific Coordinated Breaker Rating Any Molded Case Breaker Rating Maximum Maximum Maximum Maximum Maximum Maximum Maximum Circuit Amps Circuit Amps Maximum Fuse Circuit Amps Circuit Amps Circuit Breaker Circuit Amps Circuit Amps at 600 VAC at 600 VAC Size, Amps at 600 VAC at 480 VAC (UL) Size, Amps at 480 VAC (UL) at 480 VAC (UL) (CSA) (CSA) (CSA) Minimum UL 1008 Ratings (Table 34.1)
100
150
225
ZBTSCT & ZBTECT 750 1,000 1,250 1,500 2,000 2,500 4,000 4,000 6,000 200,000 150,000 5,000 200,000 150,000 4,000 200,000 N/A N/A 200,000 150,000 2,500 200,000 150,000 2,500 200,000 150,000 1,600 85,000 100,000 100,000 N/A 100,000 100,000 200,000 150,000 1,600 85,000 200,000 150,000 1,600 85,000 200,000 150,000 800 65,000 50,000 65,000 65,000 65,000 85,000 85,000 N/A 85,000 85,000
260 50,000 50,000 50,000 50,000 100,000 100,000 100,000 100,000 100,000 42,000 42,000 42,000 42,000 85,000 85,000 N/A 85,000 85,000 12,000 16,000 20,000 24,000 32,000 40,000 52,000 60,000 80,000
400
600
800
1,000
1,200
1,600
2,000
2,600
3,000
4,000
Page 11 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 12
Amp
V-1824
10,000
Siemens
150A 250A 400A 100A 150A 225A 250A 400A 125A 250A 400A
Square D
FDC, HFD HJD, JDC HKD, KD, KDB, KDC, LA Tripac, LCL TB1 SEL, SEP, TEL, THLC1 TFL, THLC2 SFL, SFP SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 CED6, HED4, HED6 CFD6, FD6, FXD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, JD6, JXD6, SCJD6 SHJD6, SJD6 150A FC, FI 250A KC, KH, KI 400A LA, LC, LE, LH, LI, LX, LXI 400
V-1824
10,000
Siemens
150A 250A 400A 100A 150A 225A 250A 400A 125A 250A 400A
Square D
FDC, HFD HJD, JDC HKD, KD, KDB, KDC, LA Tripac, LCL TB1 SEL, SEP, TEL, THLC1 TFL, THLC2 SFL, SFP SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4 CED6 CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, JD6, JXD6, SCJD6, SHJD6, SJD6 150A FI 250A KA, KH, KI 400A LA, LC, LE, LH, LI, LX, LXI
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1870
35,000
Merlin Gerin
Siemens
Square D
250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A
HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 CF250H, CF250L CJ400H, CJ400L, CK400H, CK400N CJ600H CK800H, CK800N CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 KC, KI --LC, LE, LI, LX, LXI ME, MH, MX
Page 13 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 14
Amp
V-1870
35,000
Merlin Gerin
Siemens
Square D
250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A
--KDC, LA Tripac, LCL CLDC, LDC NB Tripac THLC2 SGL4, SGP4, TB4, THLC4 SGL6, SGP6, TB6 SKL8, SKP8, TB8 CF250L CJ400L, CK400H --CK800H CFD6 CJD6, HHJD6, HHJXD6, SCJD6 CLD6, HHLD6, HHLXD6, SCLD6 CMD6, HMD6, HMXD6, SCMD6, SHMD6 KI --LI, LXI --800
V-1287
600
50,000
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1287
600
42,000
V-1929
800
50,000
Page 15 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 16
Amp
50,000
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac CNDC, NDC CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP --CK1000L CM1600 CMD6, SCMD6 CND6, SCND6 CPD6 --NC, NE, NX PCF, PEF, PHF, PXF 1,600
42,000
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac --CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP ----MC16H1, MP16H1, MP16H2 CMD6, SCMD6 CND6, SCND6 CPD6, HPD6, HRD6 --NC, NE, NX PCF, PEF, PHF, PXF
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1291
1,600 2,000
100,000 100,000
V-1291
1,600 2,000
85,000
V-1291
2,600 3,000
100,000 100,000
V-1291
85,000
4,000
100,000 100,000
V-1825
4,000
85,000
Page 17 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 18
Amp
V-2002
35,000
General Electric
Merlin Gerin
Siemens
Square D
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
----JHB ----FDC, HFD HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac THLC1, SEL, SEP SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TJL, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 --CF250H, CF250L CJ400L, CJ400H, CK400H, CK400N CJ600H CK800H, CK800N --CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 --KC, KI LC, LE, LI, LX, LXI LC, LE, LI, LX, LXI ME, MH, MX
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-2002
35,000
General Electric
Merlin Gerin
Siemens
Square D
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
----JHB, MHB ----FDC JDC HKD, KDC, LA Tripac, LCL CLDC, LDC NB Tripac THLC1 THLC2 SGL4, SGP4, TB4, THLC4 SGL6, SGP6, TB6 SKL8, SKP8, TB8 --CF250L CJ400L, CK400H, CK400L, CK400N, CK400NN --CK800H --CFD6 CJD6, HHJD6, HHJXD6, HJD6, HLD6, SCJD6 CLD6, HHLD6, HHLXD6, SCLD6 CMD6, HMD6, HMXD6, SCMD6, SHMD6 --KI LC, LE, LI, LX, LXI LI, LXI ---
Page 19 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 20
Amp
V-1287
600
50,000
V-1287
600
42,000
V-1929
800
50,000
600A 800A 600A 800A 600A 800A 600A 800A 800A 1,200A 800A 1,200A 800A 1,200A 800A 1,200A 800A 1,200A
CLDC, LDC DSL206, NB Tripac TB6, SGL6, SGP6 TB8, THC, THP, SKP8 CLD6, SCLD6 CMD6, HMD6, SCMD6, SHMD6 LI, LXI NC, NE, NX CHMDL, HMDL, NB Tripac CHND, CNDC, HND, NDC TB8, TC, THC, THP, TKL85, TP, SKL8, SKP8 TKL12S, SKL12, SKP12 CMD6, HMD6, SCMD6, SHMD6 CND6, HND6, SCND6, SHND6 --CK1000L ME, MH, MX NC, NE, NX
1,200
200,000
1,200
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1288 V-1288A
50,000
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac CNDC, NDC CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP --CK1000L CM1600 CMD6, SCMD6 CND6, SCND6 CPD6 --NC, NE, NX PCF, PEF, PHF, PXF
V-1288 V-1288A
42,000
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac --CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP ----MC16H1, MP16H1, MP16H2 CMD6, SCMD6 CND6, SCND6 CPD6, HPD6, HRD6 --NC, NE, NX PCF, PEF, PHF, PXF
Page 21 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 22
Amp
V-1291
1,600 2,000
100,000 100,000
V-1291
1,600 2,000
85,000
V-1291
2,600 3,000
100,000 100,000
V-1291
2,600 3,000
85,000
V-1825
100,000 100,000
V-1825
4,000
85,000
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1824
N/A
Siemens
150A 250A 400A 100A 150A 225A 250A 400A 125A 250A 400A
Square D
FDC, HFD HJD, JDC HKD, KD, KDB, KDC, LA Tripac, LCL TB1 SEL, SEP, TEL, THLC1 TFL, THLC2 SFL, SFP SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 CED6, HED4, HED6 CFD6, FD6, FXD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, JD6, JXD6, SCJD6 SHJD6, SJD6 150A FC, FI 250A KC, KH, KI 400A LA, LC, LE, LH, LI, LX, LXI
V-1824
N/A
Siemens
150A 250A 400A 100A 150A 225A 250A 400A 125A 250A 400A
Page 23 TB-1102
Square D
FDC, HFD HJD, JDC HKD, KD, KDB, KDC, LA Tripac, LCL TB1 SEL, SEP, TEL, THLC1 TFL, THLC2 SFL, SFP SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4 CED6 CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, JD6, JXD6, SCJD6, SHJD6, SJD6 150A FI 250A KA, KH, KI 400A LA, LC, LE, LH, LI, LX, LXI
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 24
Amp
V-1870
260 400
N/A
General Electric
Merlin Gerin
Siemens
Square D
V-1870
260 400
N/A
42,000 Cutler-Hammer
N/A
200,000
600
General Electric
Merlin Gerin
250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A
HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 CF250H, CF250L CJ400H, CJ400L, CK400H, CK400N CJ600H CK800H, CK800N CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 KC, KI --LC, LE, LI, LX, LXI ME, MH, MX --KDC, LA Tripac, LCL CLDC, LDC NB Tripac THLC2 SGL4, SGP4, TB4, THLC4 SGL6, SGP6, TB6 SKL8, SKP8, TB8 CF250L CJ400L, CK400H --CK800H
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
Square D
CFD6 CJD6, HHJD6, HHJXD6, SCJD6 CLD6, HHLD6, HHLXD6, SCLD6 CMD6, HMD6, HMXD6, SCMD6, SHMD6 KI --LI, LXI --N/A N/A N/A N/A
V-2021
600
N/A
General Electric
Merlin Gerin
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
----JHB ----FDC, HFD HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac SEL, SEP, THLC1 SFP, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TJL, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKL8, SKH8, SKP8, TB8 --CF250H, CF250L CJ400H, CJ400L, CK400H, CK400N CJ600H CK800H, CK800N
Page 25 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 26
Amp
Square D
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
--CFD6, HFD6 CJD6, HJD6, HHJD6, HHJXD6, SCJD6, SHJD6 CLD6, HLD6, HHLD6, HHLXD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 --KI, KC LC, LE, LI, LX, LXI LC, LE, LI, LX, LXI ME, MH, MX N/A 200,000 L 1,200
V-1929
800
N/A
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1288 V-1288A
N/A
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac CNDC, NDC CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP --CK1000L CM1600 CMD6, SCMD6 CND6, SCND6 CPD6 --NC, NE, NX PCF, PEF, PHF, PXF
V-1288
N/A
V-1288A
Merlin Gerin
Siemens
Page 27 TB-1102
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac --CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP ----MC16H1, MP16H1, MP16H2 CMD6, SCMD6 CND6, SCND6 CPD6, HPD6, HRD6 --NC, NE, NX PCF, PEF, PHF, PXF
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 28
Amp
V-1291
1,600 2,000
N/A
V-1291
1,600 2,000
N/A
V-1291
2,600 3,000
N/A
V-1291
2,600 3,000
N/A
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-2002
35,000
General Electric
Merlin Gerin
Siemens
Square D
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
----JHB ----FDC, HFD HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac THLC1, SEL, SEP SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TJL, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 --CF250H, CF250L CJ400L, CJ400H, CK400H, CK400N CJ600H CK800H, CK800N --CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 --KC, KI LC, LE, LI, LX, LXI LC, LE, LI, LX, LXI ME, MH, MX
Page 29 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 30
Amp
V-2002
35,000
General Electric
Merlin Gerin
Siemens
Square D
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
----JHB, MHB ----FDC JDC HKD, KDC, LA Tripac, LCL CLDC, LDC NB Tripac THLC1 THLC2 SGL4, SGP4, TB4, THLC4 SGL6, SGP6, TB6 SKL8, SKP8, TB8 --CF250L CJ400L, CK400H, CK400L, CK400N, CK400NN --CK800H --CFD6 CJD6, HHJD6, HHJXD6, HJD6, HLD6, SCJD6 CLD6, HHLD6, HHLXD6, SCLD6 CMD6, HMD6, HMXD6, SCMD6, SHMD6 --KI LC, LE, LI, LX, LXI LI, LXI ---
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-2021
600
N/A
Cutler-Hammer
General Electric
Merlin Gerin
Siemens
Square D
150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
----JHB ----FDC, HFD HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac SEL, SEP, THLC1 SFP, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TJL, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKL8, SKH8, SKP8, TB8 --CF250H, CF250L CJ400H, CJ400L, CK400H, CK400N CJ600H CK800H, CK800N --CFD6, HFD6 CJD6, HJD6, HHJD6, HHJXD6, SCJD6, SHJD6 CLD6, HLD6, HHLD6, HHLXD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 --KC, KI LC, LE, LI, LX, LXI LC, LE, LI, LX, LXI ME, MH, MX
Page 31 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 32
Amp
V-1929
800
N/A
V-1288
N/A
V-1288A
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac CNDC, NDC CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP --CK1000L CM1600 CMD6, SCMD6 CND6, SCND6 CPD6 --NC, NE, NX PCF, PEF, PHF, PXF
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1288 V-1288A
N/A
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac --CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP ----MC16H1, MP16H1, MP16H2 CMD6, SCMD6 CND6, SCND6 CPD6, HPD6, HRD6 --NC, NE, NX PCF, PEF, PHF, PXF Any
V-1291
N/A
V-1291
N/A
V-1291
N/A
V-1291
2,600 3,000
N/A
Page 33 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 34
Amp
V-1824
N/A
Siemens
150A 250A 400A 100A 150A 225A 250A 400A 125A 250A 400A
Square D
FDC, HFD HJD, JDC HKD, KD, KDB, KDC, LA Tripac, LCL TB1 SEL, SEP, TEL, THLC1 TFL, THLC2 SFL, SFP SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 CED6, HED4, HED6 CFD6, FD6, FXD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, JD6, JXD6, SCJD6 SHJD6, SJD6 150A FC, FI 250A KC, KH, KI 400A LA, LC, LE, LH, LI, LX, LXI
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1870
300 400
N/A
General Electric
Merlin Gerin
Siemens
Square D
250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A
HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 CF250H, CF250L CJ400H, CJ400L, CK400H, CK400N CJ600H CK800H, CK800N CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 KC, KI --LC, LE, LI, LX, LXI ME, MH, MX
Page 35 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 36
Amp
V-2002
35,000
General Electric
Merlin Gerin
Siemens
Square D
400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
JHB ----FDC, HFD HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac THLC1, SEL, SEP SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TJL, TLB4 SGL6, SGP6, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 --CF250H, CF250L CJ400L, CJ400H, CK400H, CK400N CJ600H CK800H, CK800N --CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 --KC, KI LC, LE, LI, LX, LXI LC, LE, LI, LX, LXI ME, MH, MX
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-2002
35,000
General Electric
Merlin Gerin
Siemens
Square D
400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A 150A 250A 400A 600A 800A
JHB, MHB ----FDC JDC HKD, KDC, LA Tripac, LCL CLDC, LDC NB Tripac THLC1 THLC2 SGL4, SGP4, TB4, THLC4 SGL6, SGP6, TB6 SKL8, SKP8, TB8 --CF250L CJ400L, CK400H, CK400L, CK400N, CK400NN --CK800H --CFD6 CJD6, HHJD6, HHJXD6, HJD6, HLD6, SCJD6 CLD6, HHLD6, HHLXD6, SCLD6 CMD6, HMD6, HMXD6, SCMD6, SHMD6 --KI LC, LE, LI, LX, LXI LI, LXI ---
Page 37 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 38
Amp
V-1287
600
50,000
V-1287
600
42,000
V-1929
800
50,000
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-1288 V-1288A
50,000
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac CNDC, NDC CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP --CK1000L CM1600 CMD6, SCMD6 CND6, SCND6 CPD6 --NC, NE, NX PCF, PEF, PHF, PXF
V-1288 V-1288A
42,000
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac --CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP ----MC16H1, MP16H1, MP16H2 CMD6, SCMD6 CND6, SCND6 CPD6, HPD6, HRD6 --NC, NE, NX PCF, PEF, PHF, PXF
Page 39 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 40
Amp
V-1291
1,600 2,000
100,000 100,000
V-1291
1,600 2,000
85,000
V-1291
2,600 3,000
100,000 100,000
V-1291
2,600 3,000
85,000
V-1825
100,000 100,000
V-1825
4,000
85,000
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
V-2044
35,000
Merlin Gerin
Siemens
Square D
250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A
For ZBTSCT series, consult factory HJD, JDC CHKD, HKD, KDC, LA Tripac, LCL CHLD, CLDC, HLD, LDC NB Tripac SFL, SFP, TFL, THLC2 SGL4, SGP4, TB4, THLC4, TLB4 SGL6, SGP6, SGPA, TB6, TJL1S-6S, TJL4V, TKL4V SKH8, SKL8, SKP8, TB8 CF250H, CF250L CJ400H, CJ400L, CK400H, CK400N CJ600H CK800H, CK800N CFD6, HFD6 CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6 CLD6, HHLD6, HHLXD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 KC, KI --LC, LE, LI, LX, LXI ME, MH, MX
Page 41 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 42
Amp
V-2044
35,000
Merlin Gerin
Siemens
Square D
250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A 250A 400A 600A 800A
For ZBTSCT series, consult factory --KDC, LA Tripac, LCL CLDC, LDC NB Tripac THLC2 SGL4, SGP4, TB4, THLC4 SGL6, SGP6, TB6 SKL8, SKP8, TB8 CF250L CJ400L, CK400H --CK800H CFD6 CJD6, HHJD6, HHJXD6, SCJD6 CLD6, HHLD6, HHLXD6, SCLD6 CMD6, HMD6, HMXD6, SCMD6, SHMD6 KI --LI, LXI --800
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 600A, 480V
65,000 Cutler-Hammer General Electric Siemens Square D 600A 800A 600A 800A 600A 800A 600A 800A CHDC, CLDC, HLD, LDC CHMDL, HMDL, DSL206, NB Tripac TB6, TJL, SGL6, SGP6 TB8, TC, THC, THP, TP, SKL8, SKP8 CLD6, HLD6, SCLD6, SHLD6 CMD6, HMD6, SCMD6, SHMD6 LC, LE, LI, LX, LXI ME, MH, MX, NC, NE, NX 200,000 L 200,000 J 200,000 RK5 200,000 RK1 750 750 750 750
V-1287
600
50,000
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 600A, 600V
50,000 Cutler-Hammer General Electric Siemens Square D 600A 800A 600A 800A 600A 800A 600A 800A CLDC, LDC DSL206, NB Tripac TB6, SGL6, SGP6 TB8, THC, THP, SKP8 CLD6, SCLD6 CMD6, HMD6, SCMD6, SHMD6 LI, LXI NC, NE, NX 800 150,000 L 150,000 J 150,000 RK5 150,000 RK1 750 750 750 750
V-1287
600
42,000
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 800-1200A, 480V
85,000 Cutler-Hammer 1,600 200,000 L 3,000
V-1288
50,000
V-1288A
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A
NB Tripac CNDC, NDC CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP --CK1000L CM1600 CMD6, SCMD6 CND6, SCND6 CPD6 --NC, NE, NX PCF, PEF, PHF, PXF
Page 43 TB-1102
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
TB-1102 Page 44
Amp
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 800-1200A, 600V
65,000 Cutler-Hammer 1,600 150,000 L 3,000
V-1288
42,000
V-1288A
Merlin Gerin
Siemens
Square D
800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A 800A 1,200A 1,600A Any 4,000
NB Tripac --CRDC, PB Tripac, PC, PCC, RDC SKP8, TB8, THC, THP SKP12 THC, THP, TRP ----MC16H1, MP16H1, MP16H2 CMD6, SCMD6 CND6, SCND6 CPD6, HPD6, HRD6 --NC, NE, NX PCF, PEF, PHF, PXF
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 1600-2000A, 480V
200,000 L 2,500
V-1291
100,000 100,000
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 1600-2000A, 600V
4,000 150,000 L 2,500
V-1291
1,600 2,000
85,000
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 2600-3000A, 480V
Any 4,000 200,000 L 4,000
V-1291
100,000 100,000
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 2600-3000A, 600V
Any 4,000 150,000 L 4,000
V-1291
2,600 3,000
85,000
Automatic Transfer Switch Coordinated Breaker Withstand & Closing Ratings (WCR)
Maximum Coordinated Breaker Rating Max MCCB Breaker Ampere Size Current Limiting Fuse Rating Fuse Class
Drawing reference
Amp
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 4000A, 480V
Any Any 5,000 5,000 200,000 200,000 L L 6,000 6,000
V-1825
4,000
100,000 100,000
ZBTS & ZBTE, ZBTSD & ZBTED, ZBTSCT & ZBTECT series, 4000A, 600V
85,000
V-1825
4,000
85,000
Page 45 TB-1102
Product Overview
When you purchase emergency power equipment, reliability and quality are a necessity. GE is committed to providing the highest level of quality demanded by the industry. Our complete product line will allow you to specify a total power management system while maintaining overall compatibility and the most comprehensive warranty in the industry.
Commitment to our customer has been GEs driving force for more than 100 years in the power control industry. This same sense of purpose and responsibility will continue as we address future power control challenges.
GE Energy Digital Energy 830 W 40th Street, Chicago, IL 60609 USA 800 637 1738 www.gepowerquality.com
TB-1102 (8/10)
Information subject to change without notice. Please verify all details with GE. 2010 General Electric Company All Rights Reserved