UTOPIA AMF CONTROL GCU 104 VERSION 0.

9
PROGRAM MODE: To change program parameter program mode is used. To active
program mode GCU 104 is in manual mode and generator is in OFF condition.

Then press the HORN key continuously for 2 seconds GCU 104 LCD display show following settings Reset service due Set date / time Fault / data log menu Calibration

HORN

(To enter in set parameters menu) set the course pointer with the help of UP & DOWN arrow key in front of set parameter.

Then press ENTER key

LCD display shows PASSWORD: 0000 (For e.g. password is 1234) To set the password press HORN KEY , the display shows 1000 message on the display Then press up arrow key after that press HORN key tow times, the Module display shows 1200 message on the display.(That means to set the course for particular location press up arrow key & to increment the password value press HORN KEY) LCD display shows PASSWORD: 1234 Then press, ENTER key in set parameter menu there are 30 parameters for key push button setting. LCD display show following message. Parameter no :- 1 Mains low voltage Range:- 90 190 volts (120) To enter in next parameter press ENTER key & to increment the significant value press up arrow key & to decrement the significant value press down arrow key.

10

11

To exit from set parameters menu press TEST key.

TEST

UTOPIA AMF CONTROL GCU 104 VERSION 0.9


PARA. NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 PARAMETER DESCRIPTION Mains low voltage Mains high voltage Engine start delay Mains restoration time LLOP bypass time Stop solenoid time Crank time Crank attempts Crank reset time Engine cooling time Engine warm up time DG low voltage DG high voltage DG max run time DG low frequency DG high frequency Over lode current Load C T ratio Alphanumeric site ID Numeric site ID Engine preheat time Engine periodic start Engine periodic run DG lock time HORN time DG reset time Pull to start Remote stop Set battery voltage Service due RANGE 90 190 volts 250 300 volts 0 300 sec 0 300 sec 0 99 sec 10 99 sec 0 99 sec 1 5 time 1 99 sec 0 300 sec 0 300 sec 180 210 volts 250 285 volts 0 10 hrs 0 disable 43 47 Hz 53 59 Hz 1 100 Amps 10 : 5 to 990 : 5 A to Z 0 to 9 0 300 sec 0 90 days 1 to 60 Minutes 1 to 60 minutes 0 to 15 minutes 0 Infinite time 0 to 10 Hour 0 disable Enable / disable Enable / disable 12 / 24 V dc Enable / disable STANDARD 120 260 10 sec 10 sec 10 sec 10 sec 2 sec 3 time 10 sec 30 sec 5 sec 200 volts 260 volts 4 hrs 47 Hz 53 Hz 30 Amps 60 : 5 UAC 1111 60 sec 0 5 min 1 min 1min 1min Disable Disable 12 V dc Enable