I. Product Introduction
2
1.3 Connect Introduction
USB storage
CTs connect
Voltage connect
Connection spot
3
1.4 Product Specification
:
Series specification:
□-□□
ASENs-91□ □□
(U:
USB storage( :USB Storage)
)
Communication interface(N:
:Ethernet、
、S:
:RS-485 、
:ZigBee)
Z: )
Max current(0:
:150A、
、1:
:300A、
、2:
:600A、
、3:
:50A)
)
Communication RS-485/RJ-45/ZigBee
Electricity One/Three Voltage (V), One/Three Current (I), Power Factor (PF),
Information Power (W.VA.VAR), Power consumption (KWH), Demand
Power Consumption 1W
4
1.5 Product Communication and Storage Specification
Series □-NU
ASENs-91□ □-S
ASENs-91□ □-ZU
ASENs-91□
Data transmit Active transmit Modbus RTU Active transmit
USB Storage ● ●
FTP Download ● ●
One/Three Voltage ● ● ●
One/Three Current ● ● ●
One/Three PF ● ●
Power Factor ● ● ●
Instant Monitoring
KW,KW1,KW2,KW3 ● ● ●
KVA, KVA1,KVA2, KVA3 ● ●
KVAR,KVAR1,KVAR2,KVAR3 ● ●
KWH ● ● ●
KVARH ● ●
Peak/off-Peak KWH ●(Option) ●(Option)
Demand ● ● ●
Frequency ● ●
One/Three Voltage ● ●
One/Three Current ● ●
Power Factor ● ●
Clouding Instant Monitoring
KW ● ●
KVA ● ●
KAVR ● ●
KWH ● ●
Demand ● ●
Daily Power Consumption ● ●
Monthly Power Consumption ● ●
Daily Max Demand ● ●
Monthly Max Demand ● ●
Historic Data Query Recently 2 months Recently 2 months
Receiving Program ● ●
Pulling Program ●
Illustrating Program ● ● ●
Alarm message with SMS ●(Option) ●(Option)
Alarm message with Email ● ●
5
Chapter 2 Meter Installation
、Caution
2.1、
Professional engineer is needed
Turn off the power source before Installation
Personal protective equipment is needed
All electric wires and CTs must be installed to the power meter before
installed to the power panel
Power meter should be setup in a case to keep off the human touch
、Notice
2.2、
Confirm the power type (Single-phase / 2-wire, Single-phase / 3-wire,
3-phase / 3-wire, 3-phase / 4-wire)
Find the measured target(Whole electricity or certain equipment)
Use multi-core electric wire (Diameter above 0.75 mm)
Operating voltage:110 ~ 400 VAC
Maximum voltage measurement:400VAC
Confirm the phase sequence
Maximum current measurement
ASENs-910:150A;
ASENs-911:300A;
ASENs-912:600A;
ASENs-913:50A
、Installation step
2.3、
Step1:Fixed the smart meter
Step2:Adjust the meter type
Single phase / 2-wire
6
1 2 3 4 5 6
1S 1L
N L CT-A
CT connected diagram
R S T N
1S 1L 2S 2L
L2 N L1 CT-A CT-B
7
Three phase / 3-wire (1)
1 3 5
2 4 6
1S 1L 3S 3L
L3 L2 L1 CT-A CT-C
1 2 3 4 5 6
1S 1L 2S 2L 3S 3L
R S T N
1 2 3 4 5 6
1S 1L 2S 2L 3S 3L
R S T N
9
Step3:Installation Example for 3 phase/ 4 wires
Power
Supply
Side
N
R S T
R S T N
Voltage connected Breaker
diagram
CT connected diagram
1 2 3 4 5 6
1S 1L 2S 2L 3S 3L
C
B
A
Current direction Load Side
【Caution!!】
】
1. All electric wires and CTs must be installed to the power meter
before installed to the power panel
2. Never Let the CT contacts become open circuit when there is any
current pass through the CT
3. Confirm the phase sequence (positive phase sequence)
4. Confirm the current direction
10
Total KWH
Indicator
light
Power
consumption
12345678.902
11
、ASENs smart power meter setting steps
2.4、
diagram exposition
ASENs-910 Smart Meter
diagram
1. Use Infrared remote
signal receiver from
remote controller controller to set the smart
meter.
2. Don`t cover the signal
receiver on the smart
meter.
Infrared remote controller
Set
1. Use it to read power
Setting shift information.
Down
2. Use it to set the
parameters of smart
Enter
UP meter.
Reset
Setting screen
PCod
PCod 00000
Press to enter the
password scree, the built-in
password is 501, please use
to move setting value,
and use to set the
value. After setting step,
please press ENT into next
setting screen, or press
to leave setting screen.
Electric power type
Conn 3P4w Use to choose
3-phase / 4-wire 3P4W 、
3-phase / 3-wire 3P3W 、
Single-phase / 3-wire 1P3W
or Single-phase / 2-wire
1P2W
Setting the ratio of potential
Ptr 00001
00001 transformer
Use to choose
12
the ratio of potential
transformer. If it without the
use of potential transformer,
please keep the ratio as one.
Setting the ratio of current
Ctr 00010
00010 transformer
Use to set the
value of current transformer.
13
Check power information
diagram exposition
(unit:
Voltage information( :V)
)
rv 1110 v Use to change voltage information
on the screen.
sv 1100 v Ru:Voltage of R-N phase.
Su:Voltage of S-N phase.
tv 1120 v Tu:Voltage of T-N phase.
(unit:
Current information( :A)
)
rA 1234 A Use to change current information
on the screen.
sA 1234 A rA:Current of R phase.
SA:Current of S phase.
tA 1234 A tA:Current of T phase.
:W)
Power information ( unit: )
W 1234 W Use to change power information
on the screen.
q -1234 q W : real power ( Instantaneous power
consumption)
S 1234 s q:reactive power(varactor)
S:apparent power
Power factor information
PF 052
VH WH5 WH4 WH3 WH2 WH1 TRX WH1 : total watt-hour accumulation
Pulse (unit:
:KWH) )
1234567890
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH2: (unit:
:
Pulse )
KWH)
- Doesn`t provide this function.
0000
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH3: (unit:
:
Pulse )
KWH)
- Doesn`t provide this function.
0000
14
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH4: (unit:
:
Pulse )
KWH)
- Doesn`t provide this function.
0000
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH5: (unit:
:
Pulse )
KWH)
- Doesn`t provide this function.
0000
VH WH5 WH4 WH3 WH2 WH1 TRX :Total KVARH(
VH: (unit:
:KVARH)
)
Pulse
12345000
Date
d 11-05-01 - This function only for Ethernet type
device.
Week
sUNDAY - This function only for Ethernet type
device.
-
Time
t 17:55:44 - This function only for Ethernet type
device.
Power frequency
HZ 6000
Power demand
DeMT 00015
Reset
ReseT .... Plug in or off the USB device, please press
the F3 button to reset smart meter.
This smart meter system only uses the USB
device with FAT format.
15
Chapter 3 Controller Installation
RS-485 Port
Ethernet Port
16
3.2 infrastructure description
Connect to DO3、DO4,
AC 220~230V power in
Temperature sensor max current capacity
From 0℃~60℃
<10A(230VAC)
AI1
Ethernet
RS-485 communication Air condition
Controller(
interface link to smart meter Current <2A)
Connect to DO1、DO2,
DI contact signal DI1 DI4
max current capacity
90~240VAC DI2 DI5 <10A(230VAC)
DI3 DI6
DI contact signal 90~240VAC
Communication
Status
17
3.3.2 Digital Input Contact(DI)
The digital input(DI) contact could be input AC signal from 90~240 AC. The DI1 and DI2 are
defined to detect the air condition operation status. The DI3 and DI4 are defined to detect alarm
status. The DI5 is defined to detect the trigger status. While the DI5 channel receives the trigger,
DO3 and DO4 will be close. While the signal are input to the contact, the DI indicator will be
lighting.
Alarm signal
Alarm trigger DI status
signal indicator
Air condition
operation signal
Air condition DO status indicator
operation signal Alarm signal (Lighting means DO break)
18
DO1 In
DO2 In
DO3 In
DO4 In
DO4 out
DO1 out
DO3 out
DO2 out
DI6
DI7
DI8
19
3.4 Controller operation
Function 1: Temperature control
1. While the temperature sensor is higher than the max value set in the device or receive from the
central server, the DO1 and DO2 will be close to turn on the air condition.
2. While the temperature sensor is lower than the min value set in the device or receive from the
central server, the DO1 and DO2 will be open to to turn off the air condition.
20
Chapter 4 Device Setting
There is a web server installed in the device. Users can set the network, temperature,
server IP, USB disk storage ,login ID and password by login the web server.
4.1 Search device
Step 1: search the device in the local lan(the default IP of the device is 192.168.1.10)
ENetUtility.lnk
After linking the device an PC to the local lan, press the and the following
picture will be displayed.
Step 2:
-press the 『Detect』 bottom to detect the device in the local lan. The local lan means
the device and PC in the same subnet. If there are any device to be detected and the
following picture will be display.
Hit: Before logging in the device, the PC IP had be set the same subnet as the device.
-Modify the device IP: Select the device and press the『Set IP』 button and fill the IP.
After filling the IP, press the 『OK』button to finish the setting IP process.
21
- Modify the device mask: Select the device and press the『Set MASK』 button and fill the
mask. After filling the mask, press the 『OK』button to finish the setting mask process.
Step 4:
22
After filling the correct ID and password, the following picture would be displayed.
There are Ethernet information of the device in the picture.
、Set Network
4.2、
Press the 『Network』
』in the left frame and the following picture displayed.
If the DHCP function is enable in the IP router, set the 『DHCP』 enable and press
『save』to storage the setting.
1. If the static IP address would be set in the device, please fill all the information in the
device.
- IP address
- Subnet mask
- Gateway address
- DHCP client set to be 『Disable』
2. If use PPPoE to connect the WAN, please fill all the information.
- Set 『Connection Mode』 to be 『Enable』
- User ID
- Password
- Service Name
23
3. Press『SAVE』button to storage all the parameter and display the picture. Please press
『Reboot』 to run the new parameters.
、Server IP Setting
4.3、
Press the 『Server』and the right frame would show the following picture. The device
connected to the server and waited for the command from the server. The server should be set a
fix IP and the IP and port number would be filled.
24
Server IP Port number
、Device status
4.4、
Press 『data』 button and show all the information, include the meter information and
controller status. There are current, voltage, power, power factor, KWH and power demand in
the smart meter and temperature 1~4 and DI1~DI4 and DO1~DO4 status in the smart sensor.
25
、Download the storage data in the device
4.5、
Step 1: press『Download』in the left frame of the picture.
Step 2: press『Download Data』in the right frame. Fill the ID and password to display all the
storage data in the device.(The default ID: admin,The default password is empty)
Fill the ID
Step 3: after fill the right ID and password. All the historic data is stored by date.
26
All the storage data
files, double click to
download file
Step 4: double click the file to download, select 『save』to download the file to PC.
Click 『save』to
download file from
device to PC
Step 5: Open the download file by any txt editor software, like Excel.
27
、Data storage setting:
4.6、 :
Press the『Storage』in the left frame to set the storage function, include the storage function
enable, data storage interval time and the connect function to the server.
29
Chapter 5 Center Server software
5.1 Demo Central Server Software
Copt the demo central software to PC, and double click the icon , the following picture will
be displayed.
Press the up button and the low fill will display the command message to device
Connection device IP
data=7635
R = ((data÷16383) ×1.2) ÷ 0.005=((7635÷16383)×1.2)÷0.005=111.847
(R −100) (111.847−100)
T= = =30.77℃
0.385 0.385
- Read Controller:
Send Command:
0103000e0005
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01D70B070F1714201D9F00000101
Description of Response Message:
32
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 20):Device Timer(Sec)
21~24 byte(Hex 1D9F):Controller Temperature
25~26 byte(Hex 00):Controller DI status(DI1)
27~28 byte(Hex 00):Controller DI status(DI2)
29~30 byte(Hex 01):Controller DO status(DO1)
31~32 byte(Hex 01):Controller DO status(DO2)
- Read Meter:
Send Command:
01030000000d
Response:
14:24:29 10.0.1.101 SOCKET 1
038E01D70B070F17142000000000000016301620163000000000000000000000003D00
00
Description of Response Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 1F)1F:Device Timer(Sec)
21~24 byte(Hex 0000):Meter Current-R
25~28 byte(Hex 0000):Meter Current-S
33
29~32 byte(Hex 0000):Meter Current-T
33~36 byte(Hex 1630):Meter Voltage-R
37~40 byte(Hex 1620):Meter Voltage-S
41~44 byte(Hex 1630):Meter Voltage-T
45~48 byte(Hex 0000):Meter KW
49~52 byte(Hex 0000):Meter KVA
53~56 byte(Hex 0000):Meter KVAR
57~60 byte(Hex 0000):Meter PF
61~68 byte(Hex 0000003D):Meter KWH_H
69~72 byte(Hex 0000):Meter Power Demand(15 minutes)
- Setting Value:
Send Command:
0110001300020401F40096
Description of Command Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~14 byte(Hex 01100013000204):Command Code
15~18 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
19~ 22byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01A90110001300020401F40096
Description of Response Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
9~22 byte(Hex 01100013000204):Command Code
23~26 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
27~ 30 byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)
34
- Set Timer:
Send Command:
011000190003060B07110D091D
Description of Command Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute 09)
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second 29)
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01D7011000190003060B070F171415
Description of Response Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute=09)
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second=29)
- Reboot:
Send Command:
010655AA00019999
35
- Table of Smart Meter
Factor
Index unit Description
150A
RA A 0.009 Current R
SA A 0.009 Current S
TA A 0.009 Current T
RV V 0.04 Voltage R
SV V 0.04 Voltage S
TV V 0.04 Voltage T
W Kw 0.012 Power KW
VAR Kvar 0.012 KVAR
VA Kva 0.012 KVA
PF % 0.01 PF
DM KW 0.012 Power demand
WH-H KWH 0.012 KWH=
WH-L KWH 0.012 WH-H*65535 + WH- L
36
Chapter 6 Command for Device
The device is set to be the TCP client mode and always connected to TCP server(Central Server).
The device always waits for the command sent from the Central server and response according to
command. The Commands are described as the following.
- Read Controller:
Send Command:
0103000e0005
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01D70B070F1714201D9F00000101
Description of Response Message:
1~8 byte(Hex 038E01D7):Device ID
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 20):Device Timer(Sec)
21~24 byte(Hex 1D9F):Controller Temperature
25~26 byte(Hex 00):Controller DI status(DI1)
27~28 byte(Hex 00):Controller DI status(DI2)
29~30 byte(Hex 01):Controller DO status(DO1)
31~32 byte(Hex 01):Controller DO status(DO2)
- Read Meter:
Send Command:
01030000000d
Response:
14:24:29 10.0.1.101 SOCKET 1
038E01D70B070F17142000000000000016301620163000000000000000000000003D00
00
Description of Response Message:
1~8 byte(Hex 038E01D7):Device ID
37
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 1F)1F:Device Timer(Sec)
21~24 byte(Hex 0000):Meter Current-R
25~28 byte(Hex 0000):Meter Current-S
29~32 byte(Hex 0000):Meter Current-T
33~36 byte(Hex 1630):Meter Voltage-R
37~40 byte(Hex 1620):Meter Voltage-S
41~44 byte(Hex 1630):Meter Voltage-T
45~48 byte(Hex 0000):Meter KW
49~52 byte(Hex 0000):Meter KVA
53~56 byte(Hex 0000):Meter KVAR
57~60 byte(Hex 0000):Meter PF
61~68 byte(Hex 0000003D):Meter KWH_H
69~72 byte(Hex 0000):Meter Power Demand(15 minutes)
- Setting Value:
Send Command:
0110001300020401F40096
Description of Command Message:
1~14 byte(Hex 01100013000204):Command Code
15~18 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
19~ 22byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)
Response:
038E01A90110001300020401F40096
Description of Response Message:
38
1~8 byte(Hex 038E01D7):Device ID
9~22 byte(Hex 01100013000204):Command Code
23~26 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
27~ 30 byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)
- Set Timer:
Send Command:
011000190003060B07110D091D
Description of Command Message:
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute 09)
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second 29)
Response:
038E01D7011000190003060B070F171415
Description of Response Message:
1~8 byte(Hex 038E01D7):Device ID
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute=09)
39
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second=29)
- Reboot:
Send Command:
010655AA00019999