ANALOG, ADDRESSABLE FIRE ALARM SYSTEM

AUTOCALL TFX-400 Series


Features n 198 Analog, Addressable Points n Fully Upgradeable n Ideal for Retrofit Applications n System Status Information at a Glance n One Panel Size with Many Features of Larger TFX Panels n Compact Cabinet Fits Between Wall Studs n Cabinet Space for Up To 17 Amp Hours of Battery n Semiflush or Surface Mount Flexibility n Low Cost Options n Remote OCP and Virtual Front Panel n Networking Capability n Graphical User Interface
Description AUTOCALL TFX panels provide flexible operator displays including a backlit LCD and field configurable LED annunciators. The LED annunciators provide quick identification of fire, trouble, and supervisory events by zone, group, or device, while the LCD provides user defined text to describe the event type and its precise location. When used with Grinnells 550 series analog smoke sensors, the AUTOCALL TFX panels provide continuous detector sensitivity monitoring and automatically compensate for environmental influences. Alarm and pre-alarm threshold smoke levels can be defined per device and can be automatically or manually switched between multiple sensitivities based on the time-of-day, dayof-week, or date. Our exclusive CONSYS software configuration tool for site specific user programming easily guides the trained installer through a menu prompted decision process. Up to 1600 discrete contact inputs and voltage outputs in any combination, can be configured into the TFX system. These are typically used for audio evacuation and HVAC control switches, and annunciation LEDs at the main (or remote) control panel. New and existing circuits of conventional 2wire or 4-wire smoke detectors can be completely supervised by the AUTOCALL TFX-400. The conventional circuits are interfaced by using Addressable Detector Monitor Modules (IXA-500DMA ) which can be placed anywhere on an analog, addressable communications loop. The AUTOCALL TFX offers a UL Listed alarm verification feature for use with connected circuits of conventional smoke detection (IXA-500DMA) or any 550 series analog, addressable smoke or heat detector. The AUTOCALL TFX system logs all alarm, trouble and supervisory events into electronic memory with the time and date of occurrence. These events can be displayed on the LCD, or printed. Coincidence alarm grouping (cross-zoning) relates multiple device actuations before confirmation of an alarm occurs. The user can select the number of successive device actuations (2, 3, or 4) required to trigger an output response. The user can define different coded patterns to audible and visual signal circuits. These patterns are typically used to differentiate between alert and evacuate conditions. They can also be used as auxiliary signals, such as tornado warnings. Up to seven (7) remote operator control panels can be connected to a TFX-400 panel. These remote panels can be configured to duplicate the LED and LCD displays, and control switch functions.

TFX-400 Fire Alarm Control Panel

General Information The AUTOCALL TFX-400 is a self-contained, small addressable panel in a single cabinet. The AUTOCALL TFX-400 includes two (2) analog, addressable signaling line circuits that provide 99 points each. The AUTOCALL TFX-400 uses proven technology, used in the TFX-500M and TFX-800M fire alarm and detection systems. The AUTOCALL TFX-400 control is designed to be used with conventional or analog, addressable fire detection devices, in any combination. As a stand alone panel, the AUTOCALL TFX-400 meets the needs of any small-to-mid size building or building complex; networking capability allows the TFX-400 to be used in larger buildings or building complexes.

Full remote operation of any AUTOCALL TFX control panel connected to the optional AUTOCALL TFXnet network is available from the TFX-400. A Virtual Front Panel (VFP) allows the operator to use the LCD and keypad of the TFX-400 as if they were standing at any other AUTOCALL TFX control unit. Once the other control unit is selected, the TFX-400 LCD shows the status of the other control unit and its attached circuits and devices. Operations (such as isolating devices) become much easier with the optional networking capability of the graphical user interface for fire alarm annunciation and control.

Listings & Approvals UL 864 Listed, File S2561 Local Local with Releasing Device Service Auxiliary Remote Station (Protected Premises Unit) Proprietary Protected Premises Unit Central Station (Protected Premises Unit) Fire Alarm Control Unit Proprietary Receiving Unit Central Station Receiving Unit CSFM No. 7165-1493:147, 7170-1493:167

II-282/1198 Page 1 of 8

TFX-400

Initiating Device Circuit Addressable Loop #1 (SLC)

Initiating Device Circuit Line Isolator

System Block Diagram

IXAIXA500CMA 500DMA

(4B/6B) CAA-500LI IXA-RMS 912I 912P 912HP 912H 900D/900DR

Notification Appliance Circuit

Relay Output Circuit

Agent Releasing

Addressable Loop #2 (SLC)

506SDA

OXA504SDA IXA-RMS

GAR-1

OXA-502RM

GARA-1

506SDA/RM

TFXnet (IBN-552/553/554) ISN550I ISN550P IHN135 IHN200 ISN-550DI/DP/R

TFX-500

TFX-400 Remote Bus and DC Power Graphic Annunciator TFX-800 Up to 7 Remote Operator Control Panels

FireGraph

RS-232

LX-300 Printer -or- VT520 Video Terminal

II-282/1198 Page 2 of 8

Addressable Manual Stations - IXA-RMS Series Die cast metal construction Low profile, functional design Terminals for field wiring Powered directly by signaling circuit (no additional power required) Programmable for one second alarm reporting Dual action option Break glass option Hex screw or key lock reset option Analog Addressable Smoke Detectors and Heat Detectors 900 Series Detector address in the base is visible from the floor Complete service and maintenance from the floor; no ladders required Low profile appearance Attractive design Interchangeable 4" and 6" bases Designed for fast and easy installation Integral alarm LED Remote alarm LED output Nonpolarized wire connections Optional locking kit Smoke Detector - 912 Series Ionization or photoelectric Analog reporting of measured smoke density Detector service/cleaning messages Pre-alarm and alarm threshold Automatic compensation prevents sensitivity drift Chamber design provides high stability (models 912P and 912HP) Meets NFPA 72 Chapter 7 Annual Sensitivity Testing Requirements Heat Detector - 912H Series Analog reporting of alarm level temperature Two temperature selections

Analog Addressable Duct Smoke Detectors - 900 Series Ionization or photoelectric Integral alarm LED Remote LED output Rugged steel backbox with clear plastic cover Detector address in the base provides easy device identification Analog reporting of measured smoke density Pre-alarm and alarm threshold Automatic compensation prevents sensitivity drift Detector service/cleaning messages Chamber design provides high stability (photoelectronic models) 2 sets of form C alarm relay contacts (10A @ 24VDC/120VAC) Analog Addressable Smoke Detectors and Heat Detectors 550 Series Detector address in the base visible from the floor Complete service and maintenance from the floor - no ladders required Low profile appearance Plug-in interchangeable 2-wire base Tamper resistant locking head Remote LED output Nonpolarized wire connections Smoke Detector - 550 Series Ionization or photoelectric Analog reporting of measured smoke density Detector service/cleaning messages Pre-alarm and alarm threshold Automatic compensation prevents sensitivity drift Interchangeable bases Fine mesh insect screen RFI/EMI immunity Removable cover for field cleaning Heat Detector - 550 Series Analog reporting of alarm level temperature Two temperature selections

Relay Base - IBN-553 Provides a single form C relay contact output for auxiliary control (2A @ 30VDC, 400mA @ 125VAC) Individual and zonal activation Sounder Base - IBN-554 Produces 85db audible signal Modulated sound for increased audibility Individual and zonal activation

Analog Addressable Duct Smoke Detectors 550 Series Ionization or photoelectric Polling/alarm LED Remote LED output Rugged steel backbox with clear plastic cover Xpert address card provides easy device identification Analog reporting of measured smoke density Installation without cover removal Automatic compensation prevents sensitivity drift Detector service/cleaning messages Detector with 2 auxiliary relays available (10A @ 24VDC/120VAC) LED indicates relay operation High EMF/RFI noise immunity

II-282/1198 Page 3 of 8

Addressable Field Modules Contact Monitor Module IXA-500CMA and IXA-501CM Supervises and monitors dry contact devices Normally open and normally closed programmable options (IXA500CMA) IXA-500CMA mounts on standard 2-gang electrical box High EMF/RFI noise immunity Powered directly by signaling circuit (no additional power required) Programmable for normal or fast (polling interrupt) alarm reporting IXA-501CM fits inside standard electrical Box Detector Monitor Module IXA-500DMA Supervises and monitors 2-wire smoke and heat detectors Supervises 24VDC detector power on 2-wire loop Resets detectors on command from control panel Class B (Style B) and Class A (Style D) initiating circuits Contains bicolored LEDs to display alarm fault status High EMF/RFI noise immunity Relay Module - OXA-502RM Provides one form C programmable relay contact (2A @ 24VDC, 0.6A @ 120VAC) Monitored and controlled from a signaling line circuit (addressable loop) Powered by signaling line circuit. No external power LED indicates relay operation High EMF/RFI noise immunity

Notification Appliance Module - OXA-504SDA Provides a Class B (Style Y) or Class A (Style Z) notification appliance circuit Supervises 24VDC appliance power without supervisory relay 2.5 amp output rating Silenceable and non-silenceable operation High EMF/RFI noise immunity Notification Appliance Module - 506SDA Provides a Class B (Style Y) or Class A (Style Z) audio or DC, notification appliance circuit LED annunciation at each device for normal, activated, and trouble conditions Supervises 24VDC appliance power without the need for a supervisory relay 2 A @ 24VDC, 50W @ 25/70VRMS output rating Silenceable and non-silenceable operation High EMF/RFI noise immunity Will not operate into a short circuit fault Plug-in power-limiting option Line Isolator Module CAA-500LI Isolates short circuits on signaling circuit to prevent failure of entire circuit Automatically resets on correction of short circuit Status LED indicates short circuit detection No external power required High EMF/RFI noise immunity Can be configured to meet NFPA Style 7 requirements

Agent Releasing Kits 506SDA/RM Provides a Class B (Style Y) releasing circuit LED annunciation at each device for normal, activated, and trouble conditions 2 Amp output rating High EMF/RFI noise immunity Power-limited Addressable Agent Releasing Stations Agent Releasing Station - GAR-1 Series Releasing station constructed of die-cast metal Low profile, functional design Dual action Agent Releasing Station - GARA-1 Series Same features as GAR-1 series Abort switch System activated indication System normal indication

II-282/1198 Page 4 of 8

Remote Operator Control Panel Option Up to seven remote annunciators per TFX-400 Red fire alarm LEDs Yellow supervisory LED Yellow fault LED Yellow isolate LED Green power-on LED Enable key switch Panel silence button and yellow LED Alarm silence button and yellow LED System reset button and yellow LED Drill button and red LED Three programmable yellow LEDs Lamp test Internal buzzer Seven optional sockets accept red, yellow or green LEDs for special requirements Optional Operator Display Module 80 character (40 programmable) alphanumeric display Numeric touch-pad No/delete button Scroll up button Scroll down button Yes/enter button Quit button Fast access button Optional 16-Indicator Module Red zone alarm LEDs Yellow zone trouble LEDs

Remote Reporting Options Digital Alarm Communicator Transmitter SK5128 4 reporting channels Dual phone line monitor with line seizure Field configurable to transmit in one of eight different formats Used with SRA-550 supplemental relay assembly City Box Transmitter - CEB-500 NFPA 72 Auxiliary Protective Signaling Systems Reverse Polarity Transmitter - CVB-500 NFPA 72 Remote Station Protective Signaling Systems AUTOCALL TFXnet Option Grinnells AUTOCALL TFXnet is a fault resilient and flexible peer-to-peer communications network. Up to 62 AUTOCALL TFX series fire panels connect to a single AUTOCALL TFXnet network; supports up to 61,380 analog, addressable points. The TLI-530 module operates as the interface between a TFX panel and the TFXnet Network. One TLI-530 is required per TFX and is installed onto the TFX main processor board. Panels maintain full stand-alone functionality Communications True peer-to-peer communications; no host or master controller Node failure does not affect remainder of network Groups of nodes isolated due to circuit faults continue to communicate within the group Supported communication media - combinations of fiber optic, twisted/shielded pair and dedicated telephone line cabling Supported topologies - combinations of star, bus, and ring connections Token-passing, non-collision (deterministic) communications protocol with patented half-bit communications delay Plug-in module connects equipment anywhere on the network

TFX Panel Operation Each panel can be configured to respond to events from all or any subset of other panels Up to 3 panels can be configured to provide full system annunciation, control and logging; configuring two panels as identical receiving units provides hot backup of central monitoring equipment Virtual Front Panel (VFP) feature allows operator interrogation and control of any panel from any other panel All TFX-500 and TFX-800 features and capabilities are retained TFX panels can be configured with integrated single and multiple channel voice and audio evacuation equipment when required. FireGraph Option FireGraph PC based graphical user interface connects directly to the network PC based multiuser head end system provides security integration and virtually unlimited expansion; supports multiple 62 panel networks Printer Option Hard-copy text printing of alarm and trouble events Convenient, versatile paper handling High speed printing Quiet operation Simple control panel Compact design Video Display Option Displays system status and events 25, 42, or 53 data lines 14" flat-profile, antiglare screen Selectable page size - 24, 25, 36, 42, 48, 50, and 72 Tilt and swivel adjustments Self test

II-282/1198 Page 5 of 8

Specifications AUTOCALL TFX-400 is intended for use within a building interior, free from exposure to moisture, condensation and excessive dust. Temperature Range: 32F (0C) to 122F (49C) Relative Humidity: 85% (noncondensing) Battery Space Available in Cabinet: 7 1/4"H x 14" W x 4 7/8" D Analog, Addressable Signaling Lines Loop Styles: NFPA 72 Style 4 and 6. Line isolators optional for short circuit isolation. Maximum Addresses per Loop: 99 Maximum Loops per System: Two (2) Voltage: 26VDC, 300mA Supervisory Current: 20mA per loop (plus load) Alarm Current: 24mA per loop (plus load) Resistance: Maximum 75 Ohms Capacitance: Maximum 0.5 microfarad (mutual) Inductance: Maximum 1.5 millihenry (total) Maximum Continuous Distance: 6500 feet

See Installation Instructions (Publication Number 19700427) for additional information.]

Main Processor Wiring Diagram

Power Supply Wiring Diagram

II-282/1198 Page 6 of 8

SEMIFLUSH MOUNTING WALL LINE

1.50"
2.00"

SURFACE MOUNTING WALL LINE

3/4" AND 1" CONDUIT KNOCKOUTS TOP AND BOTTOM (TYPICAL) 14.25"

2.00"

1.50" 14.75"

19.875"

20.25"

5.25" 5.13"

Cabinet Dimensions Ordering Information Part No. Model Description Fire alarm control panel 976422 TFX-400 Addressable Manual Stations Addressable pull station 976277 IXA-RMS Addressable manual station, single action, keylock reset 976407 IXA-RMS-KL Smoke, Duct, and Heat Detectors Ionization smoke detector head, amalog, addressable 515462 912I Photoelectronic smoke detector head, analog, addressable 515463 912P High performance photoelectronic smoke detector head, analog, addressable 515464 912HP Heat detector head, analog, addressable with programmable setting (135F fixed 515461 912H temperature/rate-of-rise or 200F fixed temperature) 515467 4B 4" base, low profile w/remote LED output 515468 6B 6" base, low profile w/remote LED output 515472 900K Detector address key, unprogrammed, package of 10 515476 600/900LK Detector head locking kit, package of 100 515465 900D Duct detector housing, analog, addressable, less detector head 515466 900DR Duct detector housing, analog, addressable, with relay, less detector head Analog ionization smoke detector head, low profile 920095 ISN-550I Analog photoelectric smoke detector head; low profile 920096 ISN-550P Analog heat detector head, 135 degree F, low profile 920097 IHN-135 Analog heat detector head, 200 degree F; low profile 920098 IHN-200 6" low profile addressable base with remote LED output 920192 IBN-552 6" addressable relay base with remote LED output 920194 IBN-553 6" addressable sounder base with remote LED output 920195 IBN-554 Duct housing with analog ionization smoke detector head 920102 ISN-550DI Duct housing w/analog photoelectric smoke detector head 920103 ISN-550DP Duct housing w/analog photoelectric head and auxiliary relays 920353 ISN-550DPR Duct housing w/analog ionization head and auxiliary relays 920354 ISN-550DIR

II-282/1198 Page 7 of 8

ANALOG, ADDRESSABLE FIRE ALARM SYSTEM


AUTOCALL TFX-400 Series

Ordering Information (continued) Part No. Model Description Addressable Field Modules Addressable power supply monitor module 976122 500PSM 976092 IXA-500CMA Contact monitor module, mounted to 2-gang plate 976081 IXA-501CM Mini contact monitor module 976093 IXA-500DMA Addressable detector monitor module mtd to 4" sq. cover 976258 OXA-502RM Addressable relay module mounted to 2-gang plate Notification appliance module kit mounted to 2-gang 976378 506SDA plate 976216 OXA-504SDA Notification appliance module mounted to 2-gang plate 976026 CAA-500LI Line isolator module mounted to 2-gang plate Agent Releasing Kits 976413 505SDA/RM Agent releasing kit - panel mount 976414 506SDA/RM Agent releasing kit - remote mount Agent Releasing Stations Agent releasing station with abort 976376 GARA-1 Agent releasing station 976381 GAR-1 Remote Operator Control Panel 976401* Remote OCP with fire control and blank module Remote OCP with fire control and operator display 976402* module Remote OCP with fire control and 16-indicator module 976403* 976404 Backbox, semiflush mounting 976416 Backbox, surface mounting Remote Reporting Options 910688 SK5128 Digital alarm communicator transmitter 976080 SRA-550 Supplemental relay assembly 976030 CVB-500 Reverse polarity transmitter 976031 CEB-500 City box transmitter Network Option 976165 TLI-530 TFXnet - Networking board. (1) required per TFX panel. Interface between TFX panel and TFXnet Accessory Devices 976264 LX-300 Printer, 9-pin dot matrix 976263 VT520 Video terminal
Please reference both the model and part numbers when ordering. * Add S suffix to part number for socketed LED option.

This literature does not cover all the variations in the equipment described, nor does it provide for every possible contingency to be met in connection with installation, operation and maintenance. All specifications and listings are subject to change without notice. If you need more information on this product, or have a question, contact Grinnell Fire Protection Systems Company, Westlake, Ohio 44145. 1998 Grinnell Fire Protection Systems Company, a Division of the Grinnell Corporation. AUTOCALL is a registered trademark of the Grinnell Corporation.

835 Sharon Drive, Westlake, Ohio 44145 Phone: (440) 899-5445; FAX (440) 871-2301 http://www.grinnellfire.com A tyco INTERNATIONAL LTD. COMPANY