Sie sind auf Seite 1von 14

CHEMIN-IIM (XVI E)

SYMBOLS & STANDARDS


1) INSTRUMENT ABBREVIATIONS PRESSURE

P PI PG PCV PT PIT PIC PDT PRV PSV PS PSH PSL PSHH PSLL PDS PDSH PDSL PA

: : : : : : : : : : : : : : : : : : :

PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE

INDICATOR GAUGE CONTROL VALVE TRANSMITTER INDICATING TRANSMITTER INDICATING CONTROLLER DIFFERENTIAL TRANSMITTER REDUCING VALVE SAFETY VALVE SWITCH SWITCH HIGH SWITCH LOW SWITCH HIGH HIGH SWITCH LOW LOW DIFFERENTIAL SWITCH DIFFERENTIAL SWITCH HIGH DIFFERENTIAL SWITCH LOW ALARM

TEMPERATURE

T TI TW TM TE RTD T/C TT TIC TRC TCV TS TSH TSL TA

: : : : : : : : : : : : : : :

TEMPERATURE TEMPERATURE INDICATOR THERMOWELL THERMOMETER TEMPERATURE ELEMENT RESISTANCE TEMPERATURE DETECTOR THERMOCOUPLE TEMPERATURE TRANSMITTER TEMPERATURE INDICATING CONTROLLER TEMPERATURE RECORDER CONTROLLER TEMPERATURE CONTROL VALVE TEMPERATURE SWITCH TEMPERATURE SWITCH HIGH TEMPERATURE SWITCH LOW TEMPERATURE ALARM

FLOW

F FI FG FE FIT FCV FIC FS FY FA FR FRC

: : : : : : : : : : : :

FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW

INDICATOR GLASS / FLOW GAUGE ELEMENT INDICATING TRANSMITTER CONTROL VALVE INDICATING CONTROLLER SWITCH CONVERTER ALARM RECORDER RECORDING CONTROLLER
Page 1 of 14

LEVEL

CHEMIN-IIM (XVI E)

L LI LG LIT LCV LDT LIC LRC LS LSH LSL LA RLT

: : : : : : : : : : : : :

LEVEL LEVEL INDICATOR LEVEL GAUGE LEVEL INDICATING TRANSMITTER LEVEL CONTROL VALVE LEVEL DISPLACER TRANSMITTER LEVEL INDICATING CONTROLLER LEVEL RECORDING CONTROLLER LEVEL SWITCH LEVEL SWITCH HIGH LEVEL SWITCH LOW LEVEL ALARM RADAR LEVEL TRANSMITTER

GENERAL

DCS : SCADA : PLC : HART : HHT : SFC : ESD : AOV : MOV : SV : XVE : XVT : AE : JB : ILD : P&ID : IIS : TDR : SP : NC : NO : MCC : IAS : IGS : ACFO : AOFC : FFA : P/I P to I : I/P I to P : PB : PID : E/H : BOV : A/M : ZS : HS :

DISTRIBUTED CONTROL SYSTEM SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM PROGRAMMABLE LOGIC CONTROLLER HIGHWAY ADDRESSABLE REMOTE TRANSDUCER HAND HELD TERMINAL SMART FIELD CONFIGURATOR EMERGENCY SHUT DOWN AIR OPERATED VALVE MOTOR OPERATED VALVE SOLENOID VALVE VIBRATION PROXIMITOR VIBRATION TRANSMITTER ANALYZER JUNCTION BOX INSTRUMENT LOOP DIAGRAM PIPING AND INSTRUMENT DIAGRAM INSTRUMENT INSTALLATION SCHEDULE TIME DELAY RELAY SET POINT NORMALLY CLOSED NORMALLY OPEN MOTOR CONTROL CENTRE INSTRUMENT AIR SUPPLY INSTRUMENT GAS SUPPLY AIR TO CLOSE FAIL OPEN AIR TO OPEN FAIL CLOSE FLAME FAILURE ALARM PNEUMATIC TO CURRENT CONVERTER CURRENT TO PNEUMATIC CONVERTER PUSH BUTTON PROPORTIONAL, INTEGRAL AND DERIVATIVE ELECTRO HYDRAULIC ACTUATOR BLOW DOWN VALVE AUTO / MANUAL 2 POSITION SWITCH POSITION SWITCH HAND SWITCH

Page 2 of 14

CHEMIN-IIM (XVI E) 2) INSTRUMENT LINE SYMBOLS


2.1) INSTRUMENT SUPPLY or CONNECTION TO PROCESS 2.2) PNEUMATIC SIGNAL ___________________ ___________________

2.3) ELECTRICAL SIGNAL (ANALOG SIGNAL) (mA DC (OR) VDC) -----------------------3.4) ELECTROMAGNETIC or SONIC SIGNAL 3.5) HYDRAULIC SIGNAL 2.6) CAPILLARY TUBE (FILLED SYSTEM) ___________________ ___________________ ___________________

2.7) PULSE TRAIN 2.8) INTERNAL SYSTEM LINK (SOFTWARE or DATA LINK)

_ _ _ _ _ _ _

-----------------------------------------------------------------------------------------------------------------

3) TYPES OF SUPPLY
3.1) 3.2) 3.3) 3.4) 3.5) 3.6) 3.7) AS ES GS HS NS SS WS AIR SUPPLY ELECTRICAL SUPPLY GAS SUPPLY HYDRAULIC SUPPLY NITROGEN SUPPLY STEAM SUPPLY WATER SUPPLY IA PA INSTRUMENT AIR PLANT AIR

Options

The ES or AS symbol is to be used only for Field Devices requiring supply. For panel mounted instruments power supplies are not shown on flow sheet.

ES 24 V DC

IAS 130 kPa

Page 3 of 14

CHEMIN-IIM (XVI E) 4) GENERAL INSTRUMENT SYMBOLS

Page 4 of 14

CHEMIN-IIM (XVI E)

Page 5 of 14

CHEMIN-IIM (XVI E) 5) IDENTIFICATION LETTERS TABLE 1 FIRST LETTER (4)


MEASURED / INITIATING VARIABLE MODIFIER

SUCCEEDING LETTER (3)


READOUT / PASSIVE FUNCTION
ALARM USERS CHOICE (1) USERS CHOICE (1) CONTROL (13) USERS CHOICE (1)

OUTPUT FUNCTION

MODIFIER

A B C D E F G H I J K L M N O P Q R S T U V

ANALYSIS (5, 19) BURNER, COMBUSTION USERS CHOICE (1) USERS CHOICE (1) VOLTAGE FLOW RATE USERS CHOICE (1) HAND CURRENT (ELECTRICAL) POWER TIME, TIME SCHEDULE LEVEL USERS CHOICE (1) MOMENTARY (4) SCAN (7) TIME, RATE OF CHANGE (4, 21) RATIO (FRACTION) (4) DIFFERENTIAL (4)

SENSOR (PRIMARY ELEMENT)

GLASS, VIEWING DEVICE (9) HIGH (7,15,16) INDICATE (10)

CONTROL STATION (22) LIGHT (11) LOW (7, 15, 16) MIDDLE, INTERMEDIATE (7, 15) USERS CHOICE (1) ORIFICE, RESTRICTION POINT (TEST) CONNECTION USERS CHOICE (1) USERS CHOICE (1)

USERS CHOICE (1) USERS CHOICE (1) PRESSURE, VACUUM QUANTITY RADIATION SPEED, FREQUENCY TEMPERATURE MULTIVARIABLE (6) VIBRATION, MECHANICAL ANALYSIS (19) SAFETY (8) INTEGRATE, TOTALIZE (4)

RECORD (17) SWITCH (13) TRANSMIT (18)


MULTIFUNCTION (12) MULTIFUNCTION (12) MULTIFUNCTION (12)

VALVE, DAMPER, LOUVER (13) WELL X AXIS Y AXIS Z AXIS UNCLASSIFIED (2) UNCLASSIFIED (2) RELAY, COMPUTE, CONVERT(13,14,18) DRIVER, ACTUATOR, UNCLASSIFIED FINAL CONTROL ELEMENT UNCLASSIFIED (2)

W WEIGHT, FORCE X Y Z
UNCLASSIFIED (2) EVENT, STATE / PRESENCE (20) POSITION, DIMENSION

NOTE: Numbers in parentheses refer to specific explanatory notes.

Page 6 of 14

CHEMIN-IIM (XVI E) 6) TYPICAL LETTER COMBINATIONS TABLE 2

Page 7 of 14

CHEMIN-IIM (XVI E) 7) FUNCTIONAL BLOCKS FUNCTIONAL DESIGNATIONS


THE FUNCTION DESIGNATIONS ASSOCIATED WITH CONTROLLERS, COMPUTING DEVICES, CONVERTERS AND RELAYS MAY BE USED INDIVIDUALLY OR IN COMBINATION (ALSO SEE TABLE 1, NOTE 14). THE USE OF A BOX AVOIDS CONFUSION BY SETTING OFF THE SYMBOL FROM OTHER MARKINGS ON A DIAGRAM AND PERMITS THE FUNCTION TO BE USED AS A STAND ALONE BLOCK ON CONCEPTUAL DESIGNS.

TABLE -3

Page 8 of 14

CHEMIN-IIM (XVI E)

Page 9 of 14

CHEMIN-IIM (XVI E)

Page 10 of 14

CHEMIN-IIM (XVI E)

Page 11 of 14

CHEMIN-IIM (XVI E)

Page 12 of 14

CHEMIN-IIM (XVI E)

Page 13 of 14

CHEMIN-IIM (XVI E)
8. APPLICATION EXERCISE