Sie sind auf Seite 1von 431

Catalogue Cables and wires

Cables and wires

Catalogue

No 212257

COMPANYs

PROFILE

Elkabel Joint - Stock Company, with headquarters in Bourgas is the first Bulgarian company specialized in the production of cables and conductors. It was established in 1947 on the basis of several small-scale workshops for the production of electrical products. Today, Elkabel is the biggest manufacturer of cables in Bulgaria, which has gone the way of product and scope development and extension in order more fully to response to the high requirements of the market and to the changing needs of different industrial sectors.

KEY DATES OF THE COMPANY HISTORY ARE:


- 1950. The first workshop for the production of conductors was started up. The newly built workshop for the production of flexible cables with rubber insulation started operation. - 1970. Workshop for low voltage power cables with PVC insulation was started. - 1975. A newly built workshop for the production of telecommunication cables after the project of the Italian company De Angeli, started up. During the period 1979-1986 the production of power cables with cross-linked polyethylene insulation started in accordance with the license and equipment bought from Sumitomo Electric including: - two CCV lines cross linking in inert nitrogen media - laboratory equipment for material and end product quality control - know-how for the production of cables - In march 1995 Elkabel was the first company in Bulgaria certified in accordance with ISO 9002 and since 1998 the company has been re-certified by Bureau Veritas Quality International accordingly to the requirements of ISO 9001. - Since 1998 Elkabel is the first privatized company by the sale of shares on the Bulgarian Stock Market. The management is carried out on two levels: A Supervisory Council and A Board of Directors.

Elkabel spread across an area of 190 thousand square meters with built up infrastructure. It is situated in close proximity to the Port of Bourgas, the Duty Free Zone and the Airport. The plant has its own railway line and connection with E 773 Bourgas - Sofia. Elkabel is well-known and respected manufacturer not only in Bulgaria but in the international market as well. Its production is being exported to Germany, UK, France, Belgium, Hungary, Slovakia, Litva, Italy, Macedonia, Albania, Cyprus, Egypt, Nigeria, Russia, Ukraine, Uruguay, USA e.t.c.

types of cables are manufactured in accordance with a license and equipment bought from Sumitomo Electric - Japan. The cores can be copper and aluminium, outer sheaths - PVC or PE. Cables are manufactured with option - with or without armour. 3.Control Cables - with PVC insulation, manufactured to VDE, BS, BDS, IEC and other. 4. Power cables for overhead lines transmission up to 1 kV, manufactured to NFC, VDE, BDS. The changes in the market and customer requirements imposed all types of cables to be manufactured also with an option of waterresistance with longitudinal and cross water resistance, incombustible and halogen-free, with low emission of emitted gasses etc. TELECOMMUNICATION CABLES 1.Low frequency telecommunication cables, PE insulated, for urban telephone networks, copper conductors with D 0.4, 0.5, 0.6 mm, armoured and unarmoured. 2.Low frequency telecommunication cables, PE insulated, jelly filed for guarantee of longitudinal water protection of cables, for urban telephone networks. 3.High frequency telecommunication cables, paper and styroflex insulated, manufactured to BDS and GOST 4.Combined telecommunication cables

THE PRODUCTION STRUCTURE


includes: - production of copper and aluminium cores - production of control and power cables with insulation of PVC, PE and XLPE, armoured and unarmoured - production of power cables for rated voltage up to 110 kV - production of telecommunication cables with paper, styroflex and plastic insulation - production of copper and aluminium bare conductors - laboratory for in-coming and end control of materials and products - accredited testing laboratory

THE PRODUCTION PROGRAM


comprises the following group of cables: POWER CABLES 1.Power cables for rated voltage up to 1 kV, insulated with PVC, manufactured to VDE, BS, BDS, IEC and others. They are used for fixed installation in electrical systems and for transfer and distribution of energy. Cores can be copper and aluminium. Outer sheaths are of PVC or PE depending of the requirements of the standard and client. Cables are manufactured with an option to be with or without armour. 2.Power cables for medium and high voltage with XLPE insulation, for voltage rate 3,6/6, 6/10, 12/20, 20/35 and 64/110 kV. They are manufactured to BDS, IEC, BS, VDE. These

TESTS
Elkabel has a laboratory accredited by the Executive Agency Bulgarian Accreditation Sedvice and RvA - Nitherlands, to carry out independent tests and parameter control of power, telecommunication and rubber cables. It is equipped with up-dated equipment. The latest acquisition is a new high voltage laboratory for long-lasting cable tests.

PRODUCTION CAPACITY
Copper cores - 6,000 tons Aluminium cores - 6,000 tons Power cables - 18,000 tons Telecommunication cables - 1500 tons

ELKABEL

1. POWER CABLES
LOW VOLTAGE POWER CABLES WITH PVC INSULATION . . . . . . . . . . . . . .9 NYM-0; NYM-J . . . . . . . . . . . . . . . . . . . . . .10 NYY-0 NYY-J . . . . . . . . . . . . . . . . . . . . . . .11 NYY-0; NYY-J . . . . . . . . . . . . . . . . . . . . . .12 NAYY-0; NAYY-J . . . . . . . . . . . . . . . . . . . .14 (N)AYY-0; (N)AYY-J . . . . . . . . . . . . . . . . . .16 (N)AY2Y-0; (N)AY2Y-J . . . . . . . . . . . . . . . .18 E-YY-0 E-YY-J . . . . . . . . . . . . . . . . . . . . . .20 E-AY2Y-0 E-AY2Y-J . . . . . . . . . . . . . . . . . .21 AYY-0; AYY-J . . . . . . . . . . . . . . . . . . . . . .22 SZAMKAM . . . . . . . . . . . . . . . . . . . . . . . .23 NYCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 NAYCY . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 NYCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 YBY-0; YBY-J . . . . . . . . . . . . . . . . . . . . . .30 AYBY-0; AYBY-J . . . . . . . . . . . . . . . . . . . .32 PVC/SWA/PVC . . . . . . . . . . . . . . . . . . . . .34 LOW VOLTAGE POWER CABLES WITH XLPE INSULATION . . . . . . . . . . . .35 2XY-0; 2XY-J . . . . . . . . . . . . . . . . . . . . . . .36 2XY-0; 2XY-J . . . . . . . . . . . . . . . . . . . .37 2XYRaY; A2XYRaY . . . . . . . . . . . . . . . . .38 2XYRY-0/J; A2XYRY-0/J . . . . . . . . . . . . . .40 N2XY-0/J . . . . . . . . . . . . . . . . . . . . . . . . . .42 N2XY-0; N2XY-J . . . . . . . . . . . . . . . . . .44 U 1000 R2V; U 1000 AR2V . . . . . . . . . . . . .46 EXVB . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 Cu/XLPE/PVC . . . . . . . . . . . . . . . . . . . . . .51 Cu/XLPE/PVC/SWA/PVC . . . . . . . . . . . . .52 Cu/XLPE/PVC/AWA/PVC . . . . . . . . . . . . .54 POWER CABLES FOR OVERHEAD LINES . . . . . . . . . . . . . . . . . .55 NFA2X //; SH - V . . . . . . . . . . . . . . . . .56 SH - V . . . . . . . . . . . . . . . . . . . . . . . . . .58 Al/R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 SAH-20//SAX; SAHv-20 . . . . . . . . . . . . . . .62

MIDDLE VOLTAGE POWER CABLES . . . . . . . . . . . . . . . . . . .64 2XSY/N2XSY; A2XSY/NA2XSY . . . . . . . . . . . .66 2XS2Y/N2XS2Y; A2XS2Y/NA2XS2Y . . . . . . . .68 2XS2Y-TRIPLEX/N2XS2Y-TRIPLEX; A2XS2Y-TRIPLEX/NA2XS2Y-TRIPLEX . . . . . .70 2XS(F)2Y/N2XS(F)2Y; A2XS(F)2Y/NA2XS(F)2Y . . . . . . . . . . . . . . . . .72 2XS(F)2Y-TRIPLEX /N2XS(F)2Y -TRIPLEX; A2XS(F)2Y-TRIPLEX/NA2XS(F)2Y-TRIPLEX . .74 2XS(FL)2Y/N2XS(FL)2Y; A2XS(FL)2Y/NA2XS(FL)2Y . . . . . . . . . . . . . . .76 2XS(FL)2Y-TRIPLEX/N2XS(FL)2Y-TRIPLEX; A2XS(FL)2Y -TRIPLEX/NA2XS(FL)2Y-TRIPLEX . .78 2XSY/N2XSY; A2XSY/NA2XSY . . . . . . . . . . . . . . . . . . . . .80 2XS2Y/N2XS2Y; A2XS2Y/NA2XS2Y . . . . . . . . . . . . . . . . . . .82 2XS(F)2Y/(N)2XS(F)2Y; A2XS(F)2Y/(N)A2XS(F)2Y . . . . . . . . . . . . . .84 2XS(FL)2Y/(N)2XS(FL)2Y; A2XS(FL)2Y/(N)A2XS(FL)2Y . . . . . . . . . . . .86 2XSY; A2XSY . . . . . . . . . . . . . . . . . . . . . . . . .88 2XS2Y; A2XS2Y . . . . . . . . . . . . . . . . . . . . . . . .90 2XS(F)2Y; A2XS(F)2Y . . . . . . . . . . . . . . . . . . .92 2XS(FL)2Y; A2XS(FL)2Y . . . . . . . . . . . . . . . . .94 2XSY; A2XSY . . . . . . . . . . . . . . . . . . . . . . .96 2XS2Y; A2XS2Y . . . . . . . . . . . . . . . . . . . . .98 2XS(F)2Y; A2XS(F)2Y . . . . . . . . . . . . . . .100 2XS(FL)2Y A2XS(FL)2Y . . . . . . . . . . . . .102 2XSEYBY; A2XSEYBY . . . . . . . . . . . . . . . . . .104 2XSEYB2Y; A2XSEYB2Y . . . . . . . . . . . . . . . .106 2XSE(F)2YB2Y/2XSE(F)2YBY; A2XSE(F)2YB2Y/A2XSE(F)2YBY . . . . . . . . . .108 2XSEYBY; A2XSEYBY . . . . . . . . . . . . . . . . . .110 2XSEYB2Y; A2XSEYB2Y . . . . . . . . . . . . . . . .112 2XSE(F)2YB2Y/2XSE(F)2YBY; A2XSE(F)2YB2Y/A2XSE(F)2YBY . . . . . . . . . .114 A2XS(F)2YT; A2XS2YT . . . . . . . . . . . . . . . . .116 Cu/XLPE/CTS/PVC/AWA/PVC;

ELKABEL

Al/XLPE/CTS/PVC/AWA/PVC . . . . . . . . . . . .118 Cu/XLPE/CTS/PVC/SWA/PVC; Al/XLPE/CTS/PVC/SWA/PVC . . . . . . . . . . . .120 Cu/XLPE/CWS/PE; Al/XLPE/CWS/PE . . . . .122 Cu/XLPE/CWS/PE - TRIPLEX; Al/XLPE/CWS/PE - TRIPLEX . . . . . . . . . . . .124 Cu/XLPE/CWS/PE-wb; Al/XLPE/CWS/PE-wb . . . . . . . . . . . . . . . . . .126 CuwXLPE/CWS/PE-wb AlwXLPE/CWS/PE-wb . . . . . . . . . . . . . . . . . .128 EVAVB; EVAVB-F2 . . . . . . . . . . . . . . . . . . . .130 EXeCWB; EAXeCWB . . . . . . . . . . . . . . . . . .132 EXeCVB; EAXeCVB . . . . . . . . . . . . . . . . . . .134 HIGH VOLTAGE POWER CABLES . . .136 2XS(F)2Y; A2XS(F)2Y . . . . . . . . . . . . . . . .138 A2XSY 150rm/16 ELFILT . . . . . . . . . . . .140 A2XSY 150rm/16 ELFILT . . . . . . . . . . . .141 POWER CABLES, FLAME RETARDANT . . . . . . . . . . . . . .142 NYYfr-0/J . . . . . . . . . . . . . . . . . . . . . . . . .144 NYCY - FR . . . . . . . . . . . . . . . . . . . . . . . .146 FG70R . . . . . . . . . . . . . . . . . . . . . . . . . . .148 2XYRYfr-0/J; A2XYRYfr-0/J . . . . . . . . . . .150 2XYRaY- FR; A2XYRaY-FR . . . . . . . . . . .152 2XSEY- FR; A2XSEY-FR . . . . . . . . . . . . .153 2XSEYBY- FR; A2XSEYBY - FR . . . . . . . .154 2XSYRaY- FR; A2XSYRaY- FR . . . . . . . .155 EVAVB-F2 . . . . . . . . . . . . . . . . . . . . . . . .156 LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT . .158 NHXMH-0; NHXMH-J . . . . . . . . . . . . . . .158 (N)HXH-FE 180 . . . . . . . . . . . . . . . . . . . .160 N2XH-0/J . . . . . . . . . . . . . . . . . . . . . . . . .162 N2XSH; NA2XSH . . . . . . . . . . . . . . . . . . .164 N2XSEH; NA2XSEH . . . . . . . . . . . . . . . . .166 Cu/XLPE/LSF/SWA/LSF . . . . . . . . . . . . .168 Cu/XLPE/LSF/AWA/LSF . . . . . . . . . . . . .170 Cu/XLPE/CTS/LSF/AWA/LSF . . . . . . . . .171 N2XH . . . . . . . . . . . . . . . . . . . . . . . . . . .172

2XBH/2XBH . . . . . . . . . . . . . . . . . . . . . .174 2XSsH/(N)2XSsH; 2XSH/(N)2XSH . . . . .176 Cu/XLPE/CTS/LSF/SWA/LSF . . . . . . . . .177

2. TELEOMMUNICATION CABLES
COMMUNICATION CABLES FOR LONG DISTANCES . . . . . . . . . . . . . . . .178 -PMZ . . . . . . . . . . . . . . . . . . . . . . . . . . .180 -PMZBC . . . . . . . . . . . . . . . . . . . . . . . . .182 COMMUNICATION CABLES FOR LOCAL NETWORKS . . . . . . . . . . . . . . . . . . . . .184 A-2YF(L)2Y . . . . . . . . . . . . . . . . . . . . . . . .184 A-2Y(L)2Y . . . . . . . . . . . . . . . . . . . . . . . . .186 INSTALLATION CABLES FOR TELECOMMUNICATIONS SYSTEMS .188 J-Y(St)Y . . . . . . . . . . . . . . . . . . . . . . . . . .188 FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS . . . . . . . . . . . . . . . . . . . .190 LiYY . . . . . . . . . . . . . . . . . . . . . . . . . . . . .190 LiYCY . . . . . . . . . . . . . . . . . . . . . . . . . . . .194 LiYY-fr . . . . . . . . . . . . . . . . . . . . . . . . . . .198 LiYCY-fr . . . . . . . . . . . . . . . . . . . . . . . . . .204 INSTRUMENTATION AND CONTROL CABLES . . . . . . . . . . . . . . . . . . . . . . . .208 RE-2Y(St)Y . . . . . . . . . . . . . . . . . . . . . . . .208 RD-Y(St)Y . . . . . . . . . . . . . . . . . . . . . . . . .210 RE-2Y(St)Y-fl . . . . . . . . . . . . . . . . . . . . . .212 RE-2Y(St)Y-fl PiMF . . . . . . . . . . . . . . . . . .214 RE-2Y(St)YSWAY-fl . . . . . . . . . . . . . . . . .216 RE-2Y(St)YSWAY-fl - PiMF . . . . . . . . . . .218 RE-2X(St)Y -fr . . . . . . . . . . . . . . . . . . . . . .220 RE-2X(St)Y - fr PiMF . . . . . . . . . . . . . . . .222 PVC/PVC . . . . . . . . . . . . . . . . . . . . . . . . .224 PVC/SWA/PVC . . . . . . . . . . . . . . . . . . . .226 OMMUNICATION AND CONTROL CABLE . . . . . . . . . . . . . . . .228 PVC/PVC/SWA/PVC . . . . . . . . . . . . . . . .228 PVC/PVC/SWA/HDPE . . . . . . . . . . . . . . .234 PVC/OSCR/PVC/SWA/PVC . . . . . . . . . .236

ELKABEL

HALOGEN - FREE COMUNICATION AND CONTROL CABLE . . . . . . . . . . . . . . . . .238 LSZH/LSZH . . . . . . . . . . . . . . . . . . . . . . .238 LSZH/LSZH/SWA/LSZH . . . . . . . . . . . . .242 LSZH/SCR/LSZH/SWA/LSZH . . . . . . .246 JE-HCH ...x2x0.8 BD . . . . . . . . . . . . . . . .248 JE-LiHCH ...x2x0.5mm2 . . . . . . . . . . . . . .249 CONTROL CABLE FOR INDUCED VOLTAGE UP TO 5KV . . . . . . . . . . . . . .250 PE/PE/SWA/PE ...x2x1/0.8 . . . . . . . . . . .250 PE/PE/SWA/PVC . . . . . . . . . . . . . . . . . .254 PE/PJF/PE/SWA/PVC ...x2x1/0.8 . . . . . .258 LOOP FEEDER CABLES PE/SWA/PE . . . . . . . . . . .260 PE/PE . . . . . . . . . . . . . . . . . . . . . . . . . . .260 . . . . . . . . . . . . . . . . . . . . . .261

4. BARE STRANDED CONDUCTORS


MULTIWIRE CONDUCTORS . . . . . . . . .282 Multiwire copper and aluminium conductors class 2 . . . . . . . .282 Multiwire copper conductors class 4 . . .283 Multiwire copper conductors class 5 . . .284 Multiwire copper conductors class 6 . . .285 BARE COPPER CONDUCTORS FOR OVERHEAD LINES . . . . . . . . . . . . . . . .286 Bare copper conductors . . . . . . . . . . . . .286 Bare copper conductors . . . . . . . . . . . . .287 BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES . . . . . . . . . . . . . . . .288 Bare aluminium conductors and aluminum conductors, steel reinforced .288 Bare aluminium stranded conductors . . .289 Bare aluminium conductors, steel reinforced . . . . . . . . . . . . . . . . . . . .290 Bare aluminium conductors . . . . . . . . . .291 Bare aluminium and aluminium steel reinforced stranded conductors . . .292 Bare aluminium conductors and aluminum conductors, steel reinforced . . . . . . . . . .294

3. CONDUCTORS
CONDUCTORS FOR ELECTRIC INSTALLATIONS . . . . . . . . . . . . . . . . . .262 H05V-U/-K . . . . . . . . . . . . . . . . . . . . . . . .264 H07V-U/-R/-K . . . . . . . . . . . . . . . . . . . . . .265 NYIFY . . . . . . . . . . . . . . . . . . . . . . . . . . . .267 CONDUCTORS FOR ELECTRIC APPLIANCES . . . . . . . . . . . .268 H03VV-F; H03VVH2-F . . . . . . . . . . . . . . .268 H05VV-F; H05VVH2-F . . . . . . . . . . . . . . .269 H05RR-F . . . . . . . . . . . . . . . . . . . . . . . . . .270 OIL RESISTANT PVC SHEATED CONDUCTORS . . . . . . . . . . . . . . . . . . .272 H05VV5-F . . . . . . . . . . . . . . . . . . . . . . . . .272 H05VVC4V5-K . . . . . . . . . . . . . . . . . . . . .274 OPVC-JZ-CY . . . . . . . . . . . . . . . . . . . . . .276 OPVC - JZ . . . . . . . . . . . . . . . . . . . . . . . .278 CONDUCTORS FOR ELECTRIC INSTALLATIONS WITH LOW EMISSION OF SMOKE AND CORROSIVE GASES WHEN AFFECTED BY FARE . . . . . . . . .280 H07Z-U/R/K . . . . . . . . . . . . . . . . . . . . . . .280

5. CABLES AND WIRES ACCORDING TO BDS


SVT . . . . . . . . . . . . . . . . . . . . . . . . . . . . .296 SVT-s . . . . . . . . . . . . . . . . . . . . . . . . . . .298 SAVT . . . . . . . . . . . . . . . . . . . . . . . . . . . .300 SVTT . . . . . . . . . . . . . . . . . . . . . . . . . . . .302 SAVTT . . . . . . . . . . . . . . . . . . . . . . . . . . .304 SVBT . . . . . . . . . . . . . . . . . . . . . . . . . . . .306 SAVBT . . . . . . . . . . . . . . . . . . . . . . . . . . .308 SVOBT . . . . . . . . . . . . . . . . . . . . . . . . . . .310 SAPEmT-et 312 SAHEmT- et 313 SHEkT . . . . . . . . . . . . . . . . . . . . . . . . . . .314

ELKABEL

SAHEkT . . . . . . . . . . . . . . . . . . . . . . . . .314 SHEk(vn)P . . . . . . . . . . . . . . . . . . . . . . .316 SAHEk(vn)P . . . . . . . . . . . . . . . . . . . . . .316 SHEk(v)P . . . . . . . . . . . . . . . . . . . . . . . .318 SAHEk(v)P . . . . . . . . . . . . . . . . . . . . . . .318 SvHEk(v)P . . . . . . . . . . . . . . . . . . . . . . . .320 SAvHEk(v)P . . . . . . . . . . . . . . . . . . . . . .320 SHEa(v)P . . . . . . . . . . . . . . . . . . . . . . . .322 SAHEa(v)P . . . . . . . . . . . . . . . . . . . . . . .322 SHEmeT . . . . . . . . . . . . . . . . . . . . . . . . .324 SAHEmeT . . . . . . . . . . . . . . . . . . . . . . . .324 SVBT SAVBT . . . . . . . . . . . . . . . . . . . . .326 SVVn/A . . . . . . . . . . . . . . . . . . . . . . . . . .328 SVVn/A . . . . . . . . . . . . . . . . . . . . . . . . . .330 SVVn/C . . . . . . . . . . . . . . . . . . . . . . . . . .332 SAVVn/ . . . . . . . . . . . . . . . . . . . . . . . . .334 SVBVn/A . . . . . . . . . . . . . . . . . . . . . . . . .336 SVBVn/A . . . . . . . . . . . . . . . . . . . . . . . . .338 SAVBVn/A . . . . . . . . . . . . . . . . . . . . . . . .340 MKG . . . . . . . . . . . . . . . . . . . . . . . . . . . . .342 MKBs . . . . . . . . . . . . . . . . . . . . . . . . . . . .343 MKBP . . . . . . . . . . . . . . . . . . . . . . . . . . . .344 MKEmPBP . . . . . . . . . . . . . . . . . . . . . . . .345 MKKG . . . . . . . . . . . . . . . . . . . . . . . . . . .346 MKKBs . . . . . . . . . . . . . . . . . . . . . . . . . .347 MKKBP . . . . . . . . . . . . . . . . . . . . . . . . . .348 MKKEmPBP . . . . . . . . . . . . . . . . . . . . . . .349 MKKEmPBPj . . . . . . . . . . . . . . . . . . . . . .350 TZG . . . . . . . . . . . . . . . . . . . . . . . . . . . . .352 TZBs . . . . . . . . . . . . . . . . . . . . . . . . . . . .354 TZBP . . . . . . . . . . . . . . . . . . . . . . . . . . . .356 TZEmPBP . . . . . . . . . . . . . . . . . . . . . . . .358 TZEmPBPe . . . . . . . . . . . . . . . . . . . . . . . .360 TPP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .362 TPPP . . . . . . . . . . . . . . . . . . . . . . . . . . . .364 TPPV . . . . . . . . . . . . . . . . . . . . . . . . . . . .366 TPPBP . . . . . . . . . . . . . . . . . . . . . . . . . . .368 TPPBPe . . . . . . . . . . . . . . . . . . . . . . . . . .370 TPJP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .372 TPJPBP . . . . . . . . . . . . . . . . . . . . . . . . . .374

TPJPP . . . . . . . . . . . . . . . . . . . . . . . . . . .376 PPVR . . . . . . . . . . . . . . . . . . . . . . . . . . . .378 PPVAR . . . . . . . . . . . . . . . . . . . . . . . . . .379 PMVSUR . . . . . . . . . . . . . . . . . . . . . . . . .380 PMVS . . . . . . . . . . . . . . . . . . . . . . . . . . . .380 PTPV . . . . . . . . . . . . . . . . . . . . . . . . . . . .381 YV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .382 TSV//V . . . . . . . . . . . . . . . . . . . . . . . . . .384 PVU-1 . . . . . . . . . . . . . . . . . . . . . . . . . . .386 PVU-2 . . . . . . . . . . . . . . . . . . . . . . . . . . .387 PVV-3 . . . . . . . . . . . . . . . . . . . . . . . . . . .388 PVV-MB1 . . . . . . . . . . . . . . . . . . . . . . . . .390 PVOT-2 . . . . . . . . . . . . . . . . . . . . . . . . . . .391 Cu/PVC/PVC . . . . . . . . . . . . . . . . . . . . . .392 PVO . . . . . . . . . . . . . . . . . . . . . . . . . . . . .393 ShKPSS . . . . . . . . . . . . . . . . . . . . . . . . . .394 XYMM K35 . . . . . . . . . . . . . . . . . . . . . . . .395 SPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . .396

TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . .397

ELKABEL

LOW VOLTAGE POWER CABLES WITH PVC INSULATION

ELKABEL

LOW VOLTAGE POWER CABLES WITH PVC INSULATION

NYM-0; NYM-J
LOW VOLTAGE POWER CABLE

Uo/U - 300/500 V VDE 0250 part 204

Cu conductors PVC insulation PVC sheath

Application
NYM is used as power and control cable in static installations for indoor instsllations, on, in and under plaster and in the air where mechanical damage is not anticipated.

Cable design
Construction Conductor Accordind to VDE 0250 part 204 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) Insulation PVC type YI1 acc. VDE0207 Core identification according to VDE 0293 Inner sheat elastic or plastic filling compound Sheat PVC type YM1 acc. VDE 0207 Color grey

Technical data
Conductor resistance According to VDE 0295 at 20 C class 1 or 2 (IEC60228) Max. conductor 70 C temperature Max. short circuit temperature 160 C, not more than 5 sec Rated voltage Uo/U 300/500 V Test voltage Bending radius, min. Flame test 3- core 4- core brown, blue, brown black, black, grey grey, or or yellow/green, yellow/gre brown, en, blue black, grey brown AC - 2 kV 50 Hz 6 x D cable VDE 0472 part 804 class B (IEC 332 part 1)

Color coding
Single core - black or yellow/green Double core - blue and brown or yellow-green and black Other constructions according to table

5- core Multiple core blue, brown, black with number mark black, grey, on cores black or or black with number mark yellow/green, on cores and blue, brown, yellow/green core in the black, grey outer cover

Constructive data NYM-o/j 300/500 V


Number of conductors and nominal cross section N x mm2
1 x 1,5 1 x 2,5 1 x 4,0 1 x 6,0 1 x 10,0 1 x 16,0 2 x 1,5 2 x 2,5 2 x 4,0 2 x 6,0 2 x 10,0 2 x 16,0 2 x 25,0 2 x 35,0 3 x 1,5 3 x 2,5 3 x 4,0 3 x 6,0 3 x 10,0 3 x 16,0 3 x 25,0 re re re re re rm re re re re re rm rm rm re re re re re rm rm

Constructive data NYM-o/j 300/500 V


Number of conductors and nominal cross section N x mm2
3 x 35,0 4 x 1,5 4 x 2,5 4 x 4,0 4 x 6,0 4 x 10,0 4 x 16,0 4 x 25,0 4 x 35,0 5 x 1,5 5 x 2,5 5 x 4,0 5 x 6,0 5 x 10,0 5 x 16,0 5 x 25,0 5 x 35,0 7 x 1,5 7 x 2,5 10 x 1,5 12 x 1,5 rm re re re re re rm rm rm re re re re re rm rm rm re re re re

Shape

Outer Cable diameter Cu weight weight approx. approx. approx. mm


5,7 6,4 6,9 7,6 8,7 10,1 9,3 10,5 11,9 12,9 16,2 19,0 22,7 25,8 9,8 11,0 12,5 13,8 16,7 19,9 24,1

Shape

Outer Cable diameter Cu weight weight approx. approx. approx. mm


26,7 10,3 11,9 14,0 15,2 18,2 21,8 26,6 29,3 10,9 12,6 15,2 16,5 19,9 24,3 29,2 32,4 11,8 14,0 14,9 15,3

kg/km
14 23 37 56 94 153 28 46 75 112 188 307 485 673 43 70 112 168 282 460 728

kg/km
50 65 87 110 165 237 140 175 235 297 487 696 1036 1370 145 204 279 364 571 849 1270

kg/km
1010 57 93 149 223 376 614 970 1346 71 116 187 279 470 767 1213 1683 100 163 142 171

kg/km
1656 176 242 352 454 703 1051 1603 2059 207 287 433 541 844 1268 1934 2536 250 366 400 458

Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

10

ELKABEL

NYY-0 NYY-J

Uo/U - 0.6/1 kV VDE 0276 part 627

Cu conductors PVC insulation PVC sheath

LOW VOLTAGE CONTROL CABLE

Application
NYY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical amage is not anticipated.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 627 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0207

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame test According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Inner sheath Sheath Color filling compound or tapes PVC type DMV5 acc. VDE 0207 black

Color coding
black with number mark on cores or black with number mark on cores and yellow/green in the outer cover

15 cable diameter 12 cable diameter VDE 0472 part 804 class B (IEC 332 part 1)

Construction data NYY o/j


Number of wires and nominal cross section N mm2 Shape Outer diameter of cable approx. mm

0.6/1 kV
Cable weight approx. kg/km

Construction data NYY o/j


Number of wires and nominal cross section N mm2 re re re re re re re re re re re re re re re re re Shape Outer diameter of cable approx. mm 19,8 20,7 21,7 22,8 23,9 23,9 26,2 26,8 27,8 29,9 19,3 21,3 23,8 24,5 25,6 26,9 28,2

0.6/1 kV
Cable weight approx. kg/km 662 733 807 916 968 1001 1203 1278 1386 1641 639 766 950 1035 1147 1265 1440

Cu weight kg/km

Cu weight kg/km 279 325 372 441 464 488 557 627 697 859 261 299 373 448 522 597 709

12 x 2,5 7 x 1,5 re 14,7 100 323 14 x 2,5 8 x 1,5 re 16,0 114 385 16 x 2,5 10 x 1,5 re 17,7 142 472 19 x 2,5 12 x 1,5 re 18,2 171 509 20 x 2,5 14 x 1,5 re 19,0 199 559 21 x 2,5 16 x 1,5 re 19,9 227 617 24 x 2,5 19 x 1,5 re 20,8 270 689 27 x 2,5 20 x 1,5 re 21,8 284 729 30 x 2,5 21 x 1,5 re 21,8 299 751 37 x 2,5 24 x 1,5 re 23,9 341 904 7 x 4,0 25 x 1,5 re 24,5 355 968 8 x 4,0 27 x 1,5 re 24,4 384 954 10 x 4,0 30 x 1,5 re 25,3 426 1030 12 x 4,0 37 x 1,5 re 27,0 526 1195 14 x 4,0 7 x 2,5 re 15,8 163 413 16 x 4,0 8 x 2,5 re 17,4 186 493 19 x 4,0 10 x 2,5 re 19,3 232 609 Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

ELKABEL

11

NYY-0; NYY-J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV VDE 0276 part 603

Application
NYY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable design
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0276

Technical data
Conductor resistance at 20 C Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage According to VDE 0295 class 1 or 2 (IEC 60228) 70 C 160 C, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Inner sheath Sheath Color filling compound PVC type DMV5 acc. VDE 0276 black

Bending radius -single core -multi core Temperature of exploitation Flame test

15 x D cable 12 D cable -30 C to +50 C VDE 0472 part 804 class B (IEC 332 part 1)

Color coding
Single core - black or yellow/green Double core - blue and brown or yellow-green and black

3- core

4- core

5- core

Multiple core

blue blue brown brown brown black black with number mark black black grey on cores grey grey black or or or or black with number mark yellow/green yellow/green on cores and yellow/green blue brown yellow/green core in the blue brown black outer cover brown grey black grey

12

ELKABEL

Cu conductors PVC insulation PVC sheath

LOW VOLTAGE POWER CABLE

Constructive data NYY -o/j 0.6/1 kV


Number of conductors and nominal cross section N x mm2 1 x 1,5 1 x 2,5 1 x 4,0 1 x 6,0 1 x 10,0 1 x 16,0 1 x 25,0 1 x 35,0 1 x 50,0 1 x 70,0 1 x 95,0 1 x 120,0 1 x 150,0 1 x 185,0 1 x 240,0 1 x 300,0 1 x 400,0 1 x 500,0 2 x 1,5 2 x 2,5 2 x 4,0 2 x 6,0 2 x 10,0 2 x 16,0 2 x 25,0 2 x 35,0 2 x 50,0 2 x 70,0 2 x 95,0 3 x 1,5 3 x 2,5 3 x 4,0 3 x 6,0 3 x 10,0 3 x 16,0 3 x 25,0 3 x 35,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 re re re re re re rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re rm rm rm rm rm re re re re re re rm rm rm sm sm sm Shape Outer cable diameter approx. mm 7,1 7,5 8,4 8,9 9,7 10,7 12,7 13,9 15,4 17,1 19,4 20,8 22,7 25,0 27,8 30,7 34,1 38,1 12,2 12,9 14,9 15,9 17,5 19,4 23,5 25,7 29,1 32,1 38,0 12,1 12,9 15,0 16,1 18,0 20,1 24,4 26,7 30,4 29,2 33,2 35,4 Copper weight kg/km 14 23 37 56 94 149 243 337 454 656 911 1147 1415 1770 2327 2887 3692 4725 28 46 75 112 188 298 485 673 908 1312 1822 43 70 112 168 282 447 728 1010 1363 1968 2732 3440 Cable weight approx. kg/km 63 76 104 128 183 247 359 462 603 817 1092 1334 1627 2013 2598 3200 4048 5141 192 229 315 382 509 676 1027 1301 1703 2312 3093 201 247 350 435 606 828 1260 1622 2139 2380 3233 3962

Constructive data NYY -o/j 0.6/1 kV


Number of conductors and nominal cross section N x mm2 3 x 150,0 3 x 185,0 3 x 240,0 3 x 300,0 3 x 25,0+16 3 x 35,0+16 3 x 50,0+25 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 3 x 240,0+120 3 x 300,0+150 4 x 1,5 4 x 2,5 4 x 4,0 4 x 6,0 4 x 10,0 4 x 16,0 4 x 25,0 4 x 35,0 4 x 50,0 4 x 70,0 4 x 95,0 4 x 120,0 4 x 150,0 4 x 185,0 4 x 240,0 4 x 300,0 5 x 1,5 5 x 2,5 5 x 4,0 5 x 6,0 5 x 10,0 5 x 16,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 70,0 5 x 95,0 sm sm sm sm sm re sm re sm rm sm rm sm rm sm rm sm rm sm rm sm rm sm rm re re re re re re rm rm sm sm sm sm sm sm sm sm re re re re re re rm rm rm rm rm Shape Outer cable diameter approx. mm 39,2 42,7 48,1 53,5 25,4 27,7 29,2 33,4 37,8 40,8 44,8 49,3 55,3 60,9 12,9 13,8 16,2 17,4 19,5 21,8 27,2 30,1 29,2 33,4 37,8 40,8 44,8 49,3 55,3 60,9 13,7 14,8 17,4 19,0 21,6 24,1 29,9 33,5 38,1 43,3 50,1 Copper weight kg/km 4245 5311 6981 8661 876 1159 1605 2304 3187 4096 4901 6222 8128 10076 57 93 149 223 376 595 970 1346 1817 2624 3643 4587 5660 7082 9308 11548 71 116 187 279 470 744 1213 1683 2271 3280 4554 Cable weight approx. kg/km 4867 6046 7869 9702 1422 1790 2091 2820 3824 4779 5685 7163 9227 11363 232 289 419 525 741 1024 1615 2095 2311 3142 4281 5256 6442 8033 10426 12850 272 341 494 635 911 1262 1964 2593 3435 4638 6318

Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

ELKABEL

13

NAYY-0; NAYY-J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV VDE 0276 part 603

Application
NAYY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0207

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame test According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Inner sheath Sheath Color filling compound PVC type DMV5 acc. VDE 0207 black

15 cable diameter 12 cable diameter VDE 0472 part 804 class B (IEC 332 part 1) 5 - core Multiple core

Color coding
Single core - black or yellow/green Double core -blue and brown or yellow-green and black

3 - core

4 - core blue brown black grey or yellow/ green brown black grey

brown black grey or yellow/green blue brown

blue brown black with number mark black on cores grey or black black with number mark or on cores and yellow/green yellow/green core in the blue outer cover brown black grey

14

ELKABEL

Al conductors PVC insulation PVC sheath

LOW VOLTAGE POWER CABLE

Construction data NAYY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 1x25,0 1 x 35,0 1 x 50,0 1 x 50,0 1 x 70,0 1 x 95,0 1 x 120,0 1 x 150,0 1 x 185,0 1 x 240,0 1 x 300,0 1 x 400,0 1 x 500,0 2 x 25,0 2 x 35,0 2 x 50,0 2 x 35,0 2 x 50,0 2 x 70,0 2 x 95,0 3 x 25,0 3 x 35,0 3 x 50,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 3 x 150,0 3 x 185,0 3 x 240,0 3 x 50,0+25 3 x 50,0+25 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 3 x 240,0+120 3 x 300,0+150 re re re rm rm rm rm rm rm rm rm rm rm re re re rm rm rm rm re re sm sm sm sm sm sm sm sm re+re sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm Shape Outer diameter of cable approx. mm 12,2 13,1 14,5 15,4 17,1 19,3 20,8 22,6 24,9 27,7 30,6 34,0 38,0 22,4 24,3 27,3 25,4 29,1 33,1 37,9 23,7 25,8 30,9 27,8 31,2 35,8 38,0 41,8 45,7 51,1 30,5 31,2 36,0 40,2 43,2 48,0 52,3 58,7 64,3 Al weight kg/km 70 97 131 135 195 270 341 419 526 690 863 1109 1461 140 194 261 199 269 390 539 210 291 404 404 584 809 1023 1257 1579 2071 462 474 684 944 1218 1452 1848 2412 3008 Cable weight approx. kg/km 190 229 288 303 385 499 589 705 862 1083 1325 1657 2172 685 826 1049 880 1155 1447 1905 768 932 1294 994 1250 1675 1964 2365 2913 3693 1310 1158 1537 1971 2346 2839 3470 4399 5321

Construction data NAYY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 4 x 25,0 4 x 35,0 4 x 50,0 4 x 70,0 4 x 95,0 4 x 120,0 4 x 150,0 4 x 185,0 4 x 240,0 4 x 300,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 70,0 5 x 95,0 re re sm sm sm sm sm sm sm sm re re re rm rm rm rm rm Shape Outer diameter of cable approx. mm 25,8 28,2 31,2 36,0 40,2 43,2 48,0 53,7 58,7 64,3 28,1 30,9 35,7 30,4 33,0 38,1 43,3 49,8 Al weight kg/km 281 388 539 779 1079 1364 1676 2105 2762 3452 351 485 653 360 497 673 974 1349 Cable weight approx. kg/km 912 1111 1265 1658 2139 2524 3123 4002 4848 5882 1072 1326 1771 1183 1456 1919 2452 3257

Note Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

ELKABEL

15

LOW VOLTAGE POWER CABLE

(N)AYY-0 (N)AYY-J

Uo/U - 0.6/1 kV
VDE 0276 part 603

Application
(N)AYY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0207

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Sheath Color PVC type DMV5 acc. VDE 0207

Test voltage black Bending radius -single core -multi core Flame test

15 cable diameter 12 cable diameter VDE 0472 part 804 class B (IEC 332 part 1) 4 - core blue brown black grey or yellow/green brown black grey 5 - core blue brown black grey black or yellow/green blue brown black grey

Color coding
Single core - black, or yellow/green Double core - black and blue or yellow-green and black

3 - core brown black grey or yellow/green blue brown

16

ELKABEL

Al conductors PVC insulation PVC sheath

LOW VOLTAGE POWER CABLE

Construction data (N)AYY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 1 x 25,0 1 x 35,0 1 x 50,0 1 x 50,0 1 x 70,0 1 x 95,0 1 x 120,0 1 x 150,0 1 x 185,0 1 x 240,0 1 x 300,0 1 x 400,0 1 x 500,0 2 x 25,0 2 x 35,0 2 x 50,0 2 x 35,0 2 x 50,0 2 x 70,0 2 x 95,0 3 x 25,0 3 x 35,0 3 x 50,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 3 x 150,0 3 x 185,0 re re re rm rm rm rm rm rm rm rm rm rm re re re rm rm rm rm re re re sm sm sm sm sm sm Shape Outer diameter of cable approx. mm 11,5 12,5 13,9 15,1 16,1 18,2 20,0 22,0 24,1 27,1 29,1 33,1 37,1 20,4 22,3 25,3 23,4 26,5 30,0 34,6 21,7 23,6 26,8 25,8 29,2 33,8 36,0 39,8 43,1 Al weight kg/km 70 97 131 135 195 270 341 419 526 690 863 1109 1461 140 194 261 199 269 390 539 210 291 392 404 584 809 1023 1257 1579 Cable weight approx. kg/km 190 229 288 303 385 499 589 705 862 1083 1325 1657 2172 391,5 472,6 594,8 490,8 657,2 961,7 1269,0 587,6 715,8 922,3 913,5 1157,9 1554,2 1835,5 2222,5 2717,4

Construction data (N)AYY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 240,0 3 x 50,0+25 3 x 50,0+25 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 3 x 240,0+120 3 x 300,0+150 4 x 25,0 4 x 35,0 4 x 50,0 4 x 50,0 4 x 70,0 4 x 95,0 4 x 120,0 4 x 150,0 4 x 185,0 4 x 240,0 4 x 300,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 70,0 5 x 95,0 sm re+re sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm re re re sm sm sm sm sm sm sm sm re re re rm rm rm rm rm Shape Outer diameter of cable approx. mm 48,2 28,0 31,2 36,0 40,2 43,2 48,0 52,3 58,7 64,3 23,8 26,2 29,8 29,2 33,6 38,2 41,2 45,2 49,6 55,7 61,3 26,1 28,9 32,8 27,4 30,4 34,6 39,2 45,2 Al weight kg/km 2071 462 474 684 944 1218 1452 1848 2412 3008 281 388 522 539 779 1079 1364 1676 2105 2762 3452 351 485 653 360 497 673 974 1349 Cable weight approx. kg/km 3474,0 986 1068,0 1417,9 1836,2 2162,7 2637,3 3248,3 4124,2 5018,0 609,8 753,5 1032,0 1170,8 1527,4 1991,4 2337,3 2917,5 3776,8 4558,2 5562,8 885,6 1033,8 1376,1 981,0 1194,1 1586,5 1997,9 2672,2

Note Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

ELKABEL

17

LOW VOLTAGE POWER CABLE

(N)AY2Y-0 (N)AY2Y-J

Uo/U - 0.6/1 kV
Similar to VDE 0276 part 603

Application
(N)AY2Y is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0276

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core 3 - core brown black grey or yellow/green light blue brown According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Sheath Color PE type DMP 2 acc. VDE 0276 black

15 cable diameter 12 cable diameter 4 - core light blue brown black grey or yellow/green brown black grey 5 - core light blue brown black grey black or yellow/green light blue brown black grey

Color coding
Single core - black, or yellow/green Double core - light blue and brown or yellow-green and black

18

ELKABEL

Al conductors PVC insulation PE sheath

LOW VOLTAGE POWER CABLE

Construction data (N)AY2Y o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 1 x 25,0 1 x 35,0 1 x 50,0 1 x 50,0 1 x 70,0 1 x 95,0 1 x 120,0 1 x 150,0 1 x 185,0 1 x 240,0 1 x 300,0 1 x 400,0 1 x 500,0 2 x 25,0 2 x 35,0 2 x 50,0 2 x 35,0 2 x 50,0 2 x 70,0 2 x 95,0 3 x 25,0 3 x 35,0 3 x 50,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 3 x 150,0 3 x 185,0 re re re rm rm rm rm rm rm rm rm rm rm re re re rm rm rm rm re re re sm sm sm sm sm sm Shape Outer diameter of cable approx. mm 11,5 12,5 13,9 15,1 16,1 18,2 20,0 22,0 24,1 27,1 29,1 33,1 37,1 20,4 22,3 25,3 23,4 26,5 30,0 34,6 21,7 23,6 26,8 25,8 29,2 33,8 36,0 39,8 43,1 Al weight kg/km 70 97 131 135 195 270 341 419 526 690 863 1109 1461 140 194 261 199 269 390 539 210 291 392 404 584 809 1023 1257 1579 Cable weight approx. kg/km 159 195 249 255 339 447 525 631 780, 986 1233 1531 2019 276 346 451 358 507 781 1045 475 585 763 839 1066 1441 1710 2074 2546

Construction data (N)AY2Y o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 240,0 3 x 50,0+25 3 x 50,0+25 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 3 x 240,0+120 3 x 300,0+150 4 x 25,0 4 x 35,0 4 x 50,0 4 x 50,0 4 x 70,0 4 x 95,0 4 x 120,0 4 x 150,0 4 x 185,0 4 x 240,0 4 x 300,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 70,0 5 x 95,0 sm re+re sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm re re re sm sm sm sm sm sm sm sm re re re rm rm rm rm rm Shape Outer diameter of cable approx. mm 48,2 28,0 31,2 36,0 40,2 43,2 48,0 52,3 58,7 64,3 23,8 26,2 29,8 29,2 33,6 38,2 41,2 45,2 49,6 55,7 61,3 26,1 28,9 32,8 27,4 30,4 34,6 39,2 45,2 Al weight kg/km 2071 462 474 684 944 1218 1452 1848 2412 3008 281 388 522 539 779 1079 1364 1676 2105 2762 3452 351 485 653 360 497 673 974 1349 Cable weight approx. kg/km 3267 940 1003 1337 1738 2050 2509 3096 3939 4801 681 832 1129 1081 1415 1855 2182 2736 3565 4300 5259 750 1009 1352 836 1094 1463 1846 2481

Note Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

ELKABEL

19

E-YY-0 E-YY-J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV
HD 603 S1 part 3A

Cu conductors PVC insulation PVC sheath

Application
E-YY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Construction Conductor Insulation According to HD 603 S1 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV1 acc. HD 603 S1

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core 3 - core brown/black grey or yellow/green light blue/brown According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Sheath Color PVC type DMV 1 acc. HD 603 S1 black

15 cable diameter 12 cable diameter 5 - core


light blue/brown black/grey/ black or yellow/green light blue/brown black/grey

Color coding
Single core - black, or yellow/green Double core - light blue and brown or yellow-green and black

4 - core light blue/brown black/grey or yellow/green brown/black/ grey

Construction data E-YY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 3 x 150,0 3 x 185,0 3 x 240,0 3 x 35,0+16 3 x 50,0+25 re re re re re re sm sm sm sm sm sm sm sm+rm sm+rm Shape Outer diameter of cable approx. mm 11,6 12,4 13,5 14,5 16,2 11,6 25,1 29,2 33,2 35,4 39,2 42,7 48,1 26,0 29,1 Cu weight kg/km 43 70 112 168 282 447 1363 1968 2732 3440 4245 5311 6981 1159 1605 Cable weight approx. kg/km 201 247 350 435 606 828 2139 2380 3233 3962 4867 6046 7869 1790 2091

Construction data E-YY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 4 x 6,0 4 x 10,0 4 x 16,0 5 x 1,5 5 x 2,5 5x4 5x6 5 x 10 5 x 16 sm+rm sm+rm sm+rm sm+rm sm+rm re re re re re re re re re Shape Outer diameter of cable approx. mm 33,1 37,6 40,5 45,8 49,8 6,0 17,5 19,7 13,7 14,8 15,7 17,0 19,1 21,6 Cu weight kg/km 2304 3187 4096 4901 6222 223 376 595 71 116 187 279 470 744 Cable weight approx. kg/km 2820 3824 4779 5685 7163 525 741 1024 272 341 494 635 911 1262

Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

20

ELKABEL

E-AY2Y-0 E-AY2Y-J

Uo/U - 0.6/1 kV
HD 603 S1 part 3A

Al conductors PVC insulation PE sheath

LOW VOLTAGE POWER CABLE

Application
E-AY2Y is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV1 acc. HD 603 S1

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core 3 - core brown/black grey or yellow/green blue/brown According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Sheath Color PE type DMP 2 acc. VDE 0276 black

15 cable diameter 12 cable diameter 4 - core blue/brown/ black/grey or yellow/green brown/black/ grey 5 - core blue/brown black/grey/ black or yellow/green blue/brown black/grey

Color coding
Single core - black, or yellow/green Double core - blue and brown or yellow-green and black

Construction data E-AY2Y o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 1 x 25,0 1 x 35,0 1 x 50,0 1 x 50,0 1 x 70,0 1 x 95,0 1 x 120,0 1 x 150,0 1 x 185,0 1 x 240,0 1 x 300,0 1 x 400,0 1 x 500,0 2 x 25,0 2 x 35,0 2 x 50,0 2 x 35,0 2 x 50,0 2 x 70,0 2 x 95,0 re re re rm rm rm rm rm rm rm rm rm rm re re re rm rm rm rm Shape Outer diameter of cable approx. mm 11,5 12,5 13,9 15,1 16,1 18,2 20,0 22,0 24,1 27,1 29,1 33,1 37,1 20,4 22,3 25,3 23,4 26,5 30,0 34,6 Al weight kg/km 70 97 131 135 195 270 341 419 526 690 863 1109 1461 140 194 261 199 269 390 539 Cable weight approx. kg/km 159 195 249 255 339 447 525 631 780, 986 1233 1531 2019 276 346 451 358 507 781 1045

Construction data E-AY2Y o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 25,0 3 x 35,0 3 x 50,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 3 x 150,0 3 x 185,0 3 x 240,0 3 x 50,0+25 3 x 50,0+25 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 3 x 240,0+120 3 x 300,0+150 re re re sm sm sm sm sm sm sm re+re sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm Shape Outer diameter of cable approx. mm 21,7 23,6 26,8 25,8 29,2 33,8 36,0 39,8 43,1 48,2 28,0 31,2 36,0 40,2 43,2 48,0 52,3 58,7 64,3 Al weight kg/km 210 291 392 404 584 809 1023 1257 1579 2071 462 474 684 944 1218 1452 1848 2412 3008 Cable weight approx. kg/km 475 585 763 839 1066 1441 1710 2074 2546 3267 940 1003 1337 1738 2050 2509 3096 3939 4801

Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

ELKABEL

21

LOW VOLTAGE POWER CABLE

AYY-0 AYY-J

Uo/U - 0.6/1 kV
IEC 60502-1

Al conductors PVC insulation PVC sheath

Application
AYY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Construction Conductor Insulation According to IEC 60502-1 solid or multi-strand Al wires class 1 or 2 acc. IEC 60228 PVC type PVC/A acc. to IEC 60502

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame test According to IEC 60228 class 1 or 2 +70 +160, not more than 5 sec 0.6/1 kV 3.5 kV

Core identification single core-black, multiple core according to VDE 0293 Sheath Color PVC type ST1 acc. IEC 60502 black

15 cable diameter 12 cable diameter IEC 332 part 1

Construction data AYY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 4 x 16,0 4 x 25,0 4 x 50,0 4 x 70,0 4 x 95,0 re rm sm sm sm Shape Outer diameter of cable approx. mm 20.3 24.9 28.9 33.2 37.6 Al weight kg/km 180 270 520 760 1060 Cable weight approx. kg/km 460 670 1180 1390 1860

Construction data AYY o/j 0.6/1 kV


Number of wires and nominal cross section N mm2 4 x 120,0 4 x 150,0 4 x 185,0 4 x 240,0 sm sm sm sm Shape Outer diameter of cable approx. mm 40.6 45.4 49.8 55.9 Al weight kg/km 1340 1650 2100 2720 Cable weight approx. kg/km 2210 2710 3320 4110

Note Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502

22

ELKABEL

SZAMKAM

Uo/U - 0.6/1 kV
IEC 60502-1

Al conductors PVC insulation Al tapes screen PVC sheath

LOW VOLTAGE POWER CABLES

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Cable construction
Construction Conductor Insulation Cable core Inner sheath Metal screen Sheath Color re rm sm According to IEC 60502-1 Aluminum wires solid or stranded class 1 or 2, according to IEC 60228 PVC compound Insulated cores are twisted Polymer tapes Al tapes PVC compound black Conductors type circular, solid conductor circular, stranded conductor sector, stranded conductor

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying According to to IEC 60228 70 +160, not more than 5sec 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 10 D cable -5 -30 to +50

Color coding
4 - core - blue, brown, black, grey Temperature range

CONSTRUCTIONAL and ELECTRICAL DATA


Number of ThicBedding Aluminium conductors kness layer and nominal of insulatapes polyester cross section tion tapes N x mm 4x16 re 4x25rm 4x50sm 4x95sm 4x150sm 4x185sm 4x240 sm mm 1.0 1.2 1.4 1.6 1.8 2.0 2.2 mm 0.4 0.4 0.4 0.4 0.6 0.6 0.6 mm 0.4 0.4 0.4 0.4 0.6 0.6 0.6 Thickness of sheath mm 1.8 1.8 2.0 2.3 2.6 2.7 3.0 Outer diameter approx. mm 21.0 24.5 30.0 39.0 47.0 52.0 58.0 Current carrying capacity in air A 63 83 125 190 252 289 339 Current carrying capacity in ground A 76 102 144 215 275 313 364

ELKABEL

23

NYCY
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV
VDE 0276 part 603

Application
NYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0276

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame test According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Inner sheath Concentric conductor Sheath Color tapes and filling compound Cu wires and Cu tapes PVC type DMV5 acc. VDE 0276 black 15 cable diameter 12 cable diameter VDE 0472 part 804 class B (IEC 332 part 1) 4 - core blue brown black grey

Color coding
Single core - black Double core - blue and brown

3 - core brown black grey

24

ELKABEL

Cu conductors PVC insulation Cu concentric conductor PVC sheath Construction data NYCY
Number of wires and nominal cross section N mm2 1 x 1,5 1 x 2,5 1 x 4,0 1 x 6,0 1 x 10 1 x 16 1 x 25 1 x 35 2 x 1,5 2 x 2,5 2 x 4,0, 2 x 6,0 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 3 x 1,5 3 x 2,5 3 x 4,0 3 x 6,0 3 x 10 3 x 16 3 x 25 3 x 25 3 x 35 3 x 35 3 x 50 3 x 35 3 x 35 3 x 50 3 x 50 3 x 70 3 x 70 3 x 95 3 x 95 3 x 120 3 x 120 3 x 150 3 x 150 3 x 185 3 x 240 4 x 1,5 4 x 2,5 4 x 4,0 4 x 6,0 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 re re re re re re rm rm re re re re re re rm rm rm re re re re re re rm rm rm rm rm sm sm sm sm sm sm sm sm sm sm sm sm sm sm re re re re re re rm rm rm sm sm sm sm sm sm sm sm Shape Concentric conductor cross section mm 1,5 2,5 4,0 6,0 10 16 25 35 1,5 2,5 4,0 6,0 10 16 25 35 50 1,5 2,5 4,0 6,0 10 16 16 25 16 35 25 35 16 25 50 35 70 50 95 70 120 70 150 95 120 1,5 2,5 4,0 6,0 10 16 16 16 25 16 25 35 50 70 70 95 120

0.6/1 kV

LOW VOLTAGE POWER CABLES

Outer diameter of cable approx. kg/km 7,9 8,5 9,4 9,9 11,3 12,8 12,9 16,4 13,0 13,7 15,9 17,1 19,1 21,0 25,1 27,8 31,5 13,5 14,3 16,6 17,7 20,0 22,1 27,8 26,6 29,1 29,4 32,7 27,1 26,6 29,6 30,6 33,6 34,1 38,2 39,4 38,3 41,6 44,7 45,8 49,0 54,5 14,3 16,3 17,8 19,0 21,5 23,8 29,0 32,0 36,4 29,8 33,1 38,4 42,6 43,1 50,7 55,3 62,3

Cu weight kg/km 27 47 74 108 182 297 465 654 45 68 110 164 274 435 703 980 1343 56 90 147 243 365 580 855 938 1127 1317 1581 1339 1161 1593 1819 2265 2584 3151 3692 4038 4443 4827 5543 6051 7881 70 136 183 297 457 725 1090 1456 1998 1495 2044 2911 4041 5162 6214 7826 10150

Cable weight approx.

98 122 163 203 286 410 606 807 230 273 375 458 619 841 1276 1642 2193 252 305 425 528 724 999 1440 1524 1813 1987 2415 1644 1627 2174 2260 2932 3097 4004 4336 4925 5124 5890 6352 7329 9399 284 382 494 620 860 1196 1764 2246 3024 2060 2730 3758 5054 6246 7548 9374 12124

Note: Other core configuration and special constructions manufactured upon request.

ELKABEL

25

NAYCY
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV
VDE 0276 part 603

Application
NAYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cable ducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC type DIV4 acc. VDE0276

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U According to VDE 0295 class 1 or 2 (IEC 60228) +70 +160, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Inner sheath Concentric conductor Sheath Color tapes and filling compound Cu wires and Cu tapes

Test voltage PVC type DMV5 acc. VDE 0276 black Bending radius -single core -multi core Flame test

15 cable diameter 12 cable diameter VDE 0472 part 804 class B (IEC 332 part 1) 4 - core blue brown black grey

Color coding
Single core - black Double core - blue and brown

3 - core brown black grey

26

ELKABEL

Al coductors PVC isulation Cu concentric conductor PVC sheath

LOW VOLTAGE POWER CABLES

Construction data NAYCY 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 35,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 3 x 70,0 3 x 70,0 3 x 95,0 3 x 95,0 3 x 120,0 3 x 120,0 3 x 150,0 3 x 150,0 3 x 185,0 re re se se se sm sm sm sm sm sm sm sm sm Shape Concentric Outer diameter conductor of cable cross section approx. mm2 35 50 70 95 120 35 70 50 95 70 120 70 150 95 mm 27,9 31,5 33,1 36,9 40,0 33,1 34,1 37,7 38,7 40,2 40,9 44,2 45,4 48,6 Al weight kg/km 291 392 567 785 993 584 584 809 809 1023 1023 1257 1257 1579 Cu weight kg/km 230 335 456 665 849 236 413 296 580 432 694 432 804 580 Cable weight approx. kg/km 1143 1522 1675 2247 2715 1489 1648 1974 2253 2381 2654 2798 3164 3498

Note Other core configuration and special constructions manufactured upon request.

ELKABEL

27

NYCY
LOW VOLTAGE POWER CABLES

Uo/U 0.6/1 kV VDE 0276 part 627

Application
NYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are also used as control cables for transmission of measured values control and regulation pulses.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation Core Identification Inner sheath Concentric conductor Sheath Color According to VDE 0276 part 627 solid or multi-strand Cu wires class 1or 2 acc. VDE 0295 (lEC 60228) PVC type DIV4 acc. VDE0276 according to VDE 0293 tapes and filling compound of plain round copper wires and one or two transverse counter helix of copper tapes PVC type DMV5 acc. VDE 0276 black

Technical data
Conductor resistance at 20C Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage According to VDE 0295 class 1 or 2 (IEC60228) +70 C

+160 C, not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz ,

Bending radius -single core -multi core

15 cable diameter 12 cable diameter VDE 0472 part 804 class B (lEC 332 part 1)

Color coding
Black with number mark on cores or black with number mark on cores and yellow/green in the outer cover Flame test

28

ELKABEL

Cu conductors PVC insulation Cu concentric conductor PVC sheath

LOW VOLTAGE POWER CABLES

Construction data NYCY


Number of conductors and nominal cross section N mm2 7 x 1,5 8 x 1,5 10 x 1,5 12 x 1,5 14 x 1,5 16 x 1,5 19 x 1,5 20 x 1,5 21 x 1,5 24 x 1,5 27 x 1,5 30 x 1,5 37 x 1,5 7 x 2,5 8 x 2,5 10 x 2,5 12 x 2,5 14 x 2,5 16 x 2,5 19 x 2,5 20 x 2,5 21 x 2,5 24 x 2,5 27 x 2,5 30 x 2,5 37 x 2,5 7 x 4,0 8 x 4,0 10 x 4,0 12 x 4,0 14 x 4,0 16 x 4,0 19 x 4,0 re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re Shape Concentric conductor cross section mm2 2,5 2,5 2,5 2,5 2,5 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 2,5 4,0 4,0 4,0 6,0 6,0 6,0 10 10 10 10 10 10 4,0 6,0 6,0 6,0 6,0 10 10

0.6/1 kV
Copper weight Cable weight approx. kg/km 391 453 540 578 629 699 772 828 850 1000 1052 1129 1355 482 573 687 742 830 905 1016 1114 1146 1355 1433 1542 1801 687 833 1019 1089 1202 1386 1550

Outer diameter approx. mm 16,3 17,6 19,3 19,8 20,6 21,5 22,4 23,4 23,4 25,5 26,0 26,9 29,2 17,4 19,0 20,9 21,4 22,3 23,3 24,4 25,9 25,9 28,5 29,0 30,0 32,2 20,3 22,7 25,2 25,5 26,6 28,5 29,8

kg/km 129 143 171 199 227 286 307 337 351 393 435 477 620 191 224 270 315 377 422 491 560 582 651 719 787 946 298 358 441 497 570 705 799

Note ther core configuration and special constructions manufactured upon request. Cables with same construction may produced according to lEC 60502

ELKABEL

29

YBY-0; YBY-J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV IEC 60502-1

Application
YBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are also used as control cables for transmission of measured values control and regulation pulses.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation According to IEC 60502-1 solid or multi-strand Cu wires class 1 or 2 acc. IEC 60228 PVC acc. to IEC 60502

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame test According to IEC 60228 class 1 or 2 +70 +160, not more than 5 sec 0.6/1 kV AC - 3.5 kV 50 Hz

Core identification single core-black, multiple core according to VDE 0293 Inner sheath Armour Sheath Color tapes and filling compound two steel tapes or two galvanized steel tapes PVC type ST1 acc. IEC 60502 black

15 cable diameter 12 cable diameter IEC 332 part 1

Constructive data YBY-o/j


Number of conductors and nom. cross sec. N mm2 2 x 4,0 2 x 6,0 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 3 x 4,0 3 x 6,0 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 4,0 + 2,5 3 x 6,0 + 4 3 x 10 + 6 3 x 16 + 10 3 x 25 + 16 3 x 35 + 16 Shape re re re re rm rm rm re re re re rm rm rm sm sm sm sm sm sm sm re/re re/re re/re re/re rm/rm rm/rm

0.6/1 kV
Cu weight approx. kg/km 75 112 188 298 485 673 908 112 168 282 447 728 1010 1363 1968 2732 3440 4245 5311 6981 8661 135 205 338 541 881 1163 Cable weight approx. kg/km 466 552 688 878 1277 1577 2016 524 621 804 1048 1541 1942 2498 2909 4085 4860 5910 7201 9184 11182 558 681 883 1170 1721 2108

Outer diameter approx. mm 16,5 17,5 19,1 21,0 25,1 27,3 30,7 17,2 18,3 20,0 22,1 26,6 29,1 32,8 33,0 38,0 40,0 44,2 47,9 53,3 58,7 17,8 19,2 21,0 23,2 27,8 30,1

30

ELKABEL

Cu conductors PVC insulation Armour St. tapes PVC sheath

Constructive data YBY-o/j


Number of conductors and nom. cross sec.
N mm2

0.6/1 kV
Cu weight approx. Cable weight approx.

LOW VOLTAGE POWER CABLE

Shape

Outer diameter approx.

mm

kg/km

kg/km

1605 33,0 sm/rm 3 x 50 + 25 2588 2304 38,2 sm/rm 3 x 70 + 35 3659 3187 42,4 sm/rm 3 x 95 + 50 4753 4096 45,6 sm/rm 3 x 120 + 70 5808 4901 50,2 sm/rm 3x150 + 70 6854 6222 54,5 sm/rm 3 x 185 + 95 8470 8128 60,9 sm/rm 3 x 240 + 120 10699 10076 66,7 sm/rm 3 x 300 + 150 13112 149 18,3 re 4 x 4,0 607 223 19,5 re 4 x 6,0 728 376 21,4 re 4 x 10 960 595 23,8 re 4 x 16 1265 970 29,0 rm 4 x 25 1892 1346 31,9 rm 4 x 35 2399 1817 33,0 sm 4 x 50 2815 2624 38,2 sm 4 x 70 3992 3643 42,4 sm 4 x 95 5226 4587 45,6 sm 4 x 120 6313 5660 50,2 sm 4 x 150 7681 7082 54,5 sm 4 x 185 9366 9308 60,9 sm 4 x 240 12012 11548 66,7 sm 4 x 300 14645 187 19,6 re 5 x 4,0 696 279 21,0 re 5 x 6,0 843 470 23,2 re 5 x 10 1120 744 25,7 re 5 x 16 1495 1213 31,7 rm 5 x 25 2266 1683 34,9 rm 5 x 35 2886 2271 40,1 rm 5 x 50 3990 3280 45,3 rm 5 x 70 5243 100 16,9 re 7 x 1,5 492 114 18,2 re 8 x 1,5 570 142 19,9 re 10 x 1,5 676 171 20,4 re 12 x 1,5 719 199 21,2 re 14 x 1,5 791 227 22,1 re 16 x 1,5 850 270 23,0 re 19 x 1,5 934 284 24,0 re 20 x 1,5 1003 299 24,0 re 21 x 1,5 1015 341 26,1 re 24 x 1,5 1181 384 26,6 re 27 x 1,5 1239 426 27,5 re 30 x 1,5 1326 526 29,4 re 37 x 1,5 1526 163 18,0 re 7 x 2,5 596 186 19,6 re 8 x 2,5 694 232 21,5 re 10 x 2,5 830 279 22,0 re 12 x 2,5 892 325 22,9 re 14 x 2,5 975 372 23,9 re 16 x 2,5 1067 441 25,0 re 19 x 2,5 1183 464 26,1 re 20 x 2,5 1272 488 26,1 re 21 x 2,5 1291 557 28,6 re 24 x 2,5 1518 627 29,2 re 27 x 2,5 1602 697 30,2 re 30 x 2,5 1723 859 32,3 re 37 x 2,5 1998 261 20,9 re 7 x 4,0 824 299 22,9 re 8 x 4,0 970 373 25,4 re 10 x 4,0 1212 391 22,4 re 7 x 6,0 1043 447 19,5 re 8 x 6,0 1229 559 27,4 re 10 x 6,0 1496 Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502

ELKABEL

31

AYBY-0 AYBY-J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV IEC 60502-1

Application
AYBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are also used as control cables for transmission of measured values control and regulation pulses.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation According to IEC 60502-1 solid or multi-strand Al wires class 1 or 2 acc. IEC 60228 PVC acc. to IEC 60502

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame test According to IEC 60228 class 1 or 2 +70 +160, not more than 5 sec 0.6/1 kV AC - 3.5 kV 50 Hz

Core identification single core-black, multiple core according to VDE 0293 Inner sheath Armour Sheath Color tapes and filling compound two steel tapes or two galvanized steel tapes PVC type ST1 acc. IEC 60502 black

15 cable diameter 12 cable diameter IEC 332 part 1

32

ELKABEL

Al conductors PVC insulation Armour St. tapes PVC sheath

LOW VOLTAGE POWER CABLE

Construction data AYBY-o/j 0.6/1 kV


Number of conductors and nominal cross section N mm2 2 x 6,0 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 3 x 6,0 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 3 x 300 3 x 6,0+4 3 x 10+6 3 x 16+10 3 x 25+16 3 x 35+16 3 x 50+25 3 x 70+35 3 x 95+50 3 x 120+70 3 x 150+70 3 x 185+95 3 x 240+120 3 x 300+150 4 x 6,0 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 4 x 300 5 x 6,0 5 x 10 5 x 16 5 x 25 5 x 35 5 x 50 re re re rm rm rm re re re rm rm rm sm sm sm sm sm sm sm re/re re/re re/re rm/rm rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm re re re rm rm sm sm sm sm sm sm sm sm re re re rm rm rm Shape Outer diameter approx. mm 17,5 19,1 21,0 25,1 27,3 30,7 18,3 20,0 22,1 26,6 29,1 32,8 33,0 38,0 40,0 44,2 47,9 53,3 58,7 19,2 21,0 23,2 27,8 30,1 33,0 38,2 42,4 45,6 50,2 54,5 60,9 66,7 19,6 21,5 23,8 29,0 31,9 33,0 38,2 42,4 45,6 50,2 54,5 60,9 66,7 21,0 23,2 25,7 31,7 34,9 40,1 Al weight approx. kg/km 38 56 88 144 199 269 56 83 132 216 298 404 584 809 1023 1257 1579 2071 2589 68 102 160 261 343 476 684 944 1218 1452 1848 2412 3008 75 111 176 288 398 539 779 1079 1364 1676 2106 2762 3452 94 139 220 360 497 673 Cable weight approx. kg/km 473 563 680 955 1129 1412 516 616 751 1058 1270 1593 1599 2264 2572 3081 3666 4535 5433 552 660 811 1135 1334 1536 2125 2629 3083 3628 4329 5364 6430 588 710 869 1247 1503 1595 2246 2798 3262 3909 4654 5814 6980 668 807 1000 1459 1765 2479

Note: Other core configuration and special constructions manufactured upon request.Cables with same construction may produced according to IEC 60502

ELKABEL

33

PVC/SWA/PVC
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV BS 6346

Application
These cables are used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation Core identification Inner sheath Armour Sheath Color According to BS 6346 Cu wires,class 1 or 2 according to BS 6360 (IEC 60228) PVC type TI-1 acc. to BS 7655 according to BS 7655 filling compound galvanized steel wires PVC compound type TM-1 acc. to BS 7655 black

Technical data
Conductor resistance at 20 Operating temperature max. Short circuit temperature Nominal voltage Uo/U: Test voltage Temperature range laying and installing exploitation and storage Bending radius, min. approx. Flame test According to BS 6360 ( IEC 60228) class 1 or 2 70C continuous operation 250C /5 s max./ 0.6/1 kV 3.5 kV -5C to +60C -25C to +70C 6 x D cable IEC 332-1

Construction data PVC/SWA/PVC 0.6/1 kV


Number of wires and nominal cross section N mm2 2 x 1,5 2 x 1,5 2 x 2,5 2 x 2,5 2 x 4,0 2 x 6,0 2 x 10 2 x 16 2 x 25 2 x 35 3 x 1,5 3 x 1,5 3 x 2,5 3 x 2,5 3 x 4,0 re rm re rm rm rm rm rm rm rm re rm re rm rm Shape Outer diameter of cable approx. mm 11,5 12,2 12,9 13,4 14,9 16,2 19,9 21,9 26,3 28,6 12,2 12,6 13,4 13,9 15,5 Cu weight kg/km 20 30 46 48 77 115 194 307 485 673 43 45 70 72 115 Cable weight approx. kg/km 273 290 336 350 451 543 872 1087 1672 2001 311 321 383 397 515

Construction data PVC/SWA/PVC 0.6/1 kV


Number of wires and nominal cross section N mm2 3 x 6,0 3 x 10 3 x 16 3 x 25 3 x 35 4 x 1,5 4 x 1,5 4 x 2,5 4 x 2,5 4 x 4,0 4 x 6,0 4 x 10 4 x 16 4 x 25 4 x 35 rm rm rm rm rm re rm re rm rm rm rm rm rm rm Shape Outer diameter of cable approx. mm 17,7 20,8 23,0 27,6 30,1 12,9 13,4 14,3 14,9 17,5 18,9 22,4 26,2 29,9 32,6 Cu weight kg/km 173 201 460 728 1010 57 60 93 96 154 230 388 614 970 1346 Cable weight approx. kg/km 732 1006 1288 1970 2410 344 357 434 452 606 846 1184 1721 2346 2901

34

ELKABEL

LOW VOLTAGE POWER CABLES WITH XLPE INSULATION

ELKABEL

2XY-0; 2XY-J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV IEC 60502-1

Cu conductors XLPE insulation PVC sheath

Application
The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable construction
Construction Conductor Insulation Identification of cores Filling Sheath Color According to IEC 60502-1 Cu solid or stranded wires class 1 or 2 according to IEC 60228 XLPE compound color code acc. to VDE 0276-603 filling compound PVC type ST2 black

Technical data
Short circuit temperature Nominal voltage Highest system voltage Test voltage, AC 50 Hz Bending radius single core multicore Temperature of laying Temperature of exploitation Test 250C ( 5 sec.) 0.6/1 kV 1.2 kV 4.0 kV 15 x Dcable 15 x Dcable -5C to 60C -30C to 70C /for PE sheath/ -30 to 70C According to IEC 60502-1

Technical data
Conductor resistance Operating temperature Overload temperature According to IEC 60228 90C 130C/1`00h per year

Construction data 2XY-o/j 0.6/1 kV


Number of conductors and nominal cross section N mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 Thickness of insulation mm 1,0 1,1 1,1 1,2 1,4 1,6 1,7 1,8 2,0 2,2 0,7 0,9 0,9 1,0 1,1 1,1 1,2 1,4 1,6 Thickness off sheath mm 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,9 2,0 1,8 1,8 1,8 1,9 2,1 2,1 2,3 2,4 2,6 Outer diameter approx. min/mm 14,6 16,5 18,5 20,0 21,9 24,1 26,6 29,4 32,9 36,7 20,5 24,3 25,3 28,2 32,8 36,6 39,8 44,0 48,4 max/mm 17 19 20 22 24 27 30 32 37 40 24 31 32 35 40 44 48 58 58 Cu weight kg/km 454 656 911 1147 1415 1770 2827 2887 3692 4725 614 970 1346 1817 2624 3643 4587 5660 7082 Cable weight approx. kg/km 564 779 1032 1275 1561 1925 2488 3058 3887 4937 942 1398 1644 2160 2999 4045 5020 6181 7640

36

ELKABEL

2XY-0; 2XY-J

Al conductors XLPE insulation PVC sheath

Uo/U - 0.6/1 kV IEC 60502-1

LOW VOLTAGE POWER CABLE

Application
The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable construction
Construction Conductor Insulation Identification of cores Filling Sheath Color According to IEC 60502-1 Al solid or stranded wires class 1 or 2 according to IEC 60228 XLPE compound color code acc. to VDE 0276-603 filling compound PVC type ST2 black

Technical data
Conductor resistance Operating temperature Overload temperature Short circuit temperature Nominal voltage Highest system voltage Test voltage, AC 50 Hz Bending radius single core multicore Temperature of laying Temperature of exploitation Test According to IEC 60228 90C 130C/100h per year 250C ( 5 sec.) 0.6/1 kV 1.2 kV 4.0 kV 15 x Dcable 15 x Dcable -5C to 60C -30C to 70C /for PE sheath/ -30 to 70C According to IEC 60502-1

Construction data A2XY-o/j 0.6/1 kV


Number of conductors and nomi- Thickness of insu- Thickness of lation sheath nal cross section mm mm N mm2 1x50rm 1x70rm 1x95rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm 4x16re 4x25re 4x35re 4x50sm 4x70sm 4x95sm 4x120sm 4x150sm 4x185sm 4x240sm 1,0 1,1 1,1 1,2 1,4 1,6 1,7 1,8 2,0 2,2 0,7 0,9 0,9 1,0 1,1 1,1 1,2 1,4 1,6 1,7 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,9 2,0 1,8 1,8 1,8 1,9 2,1 2,1 2,3 2,4 2,6 2,7 Outer diameter approx. min/mm 14,6 16,5 18,5 20,0 21,9 24,1 26,6 29,4 32,9 36,7 20,5 24,3 25,3 28,2 32,8 36,6 39,8 44,0 48,4 62,8 max/mm 17 19 20 22 24 27 30 32 37 40 24 31 32 35 40 44 48 53 58 64 Al weight kg/km 135 195 270 341 419 526 690 863 1109 1461 176 288 398 539 779 1079 1364 1676 2105 2762 Cable weight approx. kg/km 245 318 391 469 565 681 846 1034 1304 1673 546 792 977 1259 1445 1811 2233 2696 3454 4129

ELKABEL

37

LOW VOLTAGE POWER CABLES

2XYRaY A2XYRaY

Uo/U - 0.6/1 kV IEC 60502-1

Application
The power and control cables with cross-linked polyethylene (XLPE) armored with galvanized iron wires are used in electrical installations with nominal voltage Uo/U 0.6/1 kV. These cables are used in industrial installations and urban networks. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial installations, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelters.

Cable construction
Construction Conductor Insulation Inner sheath Armour Sheath According to IEC 60502-1 solid or multi-strand Al or Cu wires class 1 or 2 acc. IEC 60228 XLPE COMPOUND PVC compound Al wires twisted concentrically PVC compound type ST2

Technical data
Conductor resistance at 20 Max. conductor temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage AC - 5 min. Bending radius, min. Temperature of laying Temperature of exploitation According class 1 or 2 IEC 60228 90 continuous operation 130C /100h/per year ./ 250 /5 s max./ 0.6/1 kV 1.2 kV between cores - 3.5 V between core and screen 3.5 V - 15x D cable no less than 0 - 30 to 50

38

ELKABEL

Cu/ Al conductors XLPE insulation PVC sheath Armour Al. Wires PVC sheath

LOW VOLTAGE POWER CABLES

Construction data 2XYRaY , A2XYRaY 0.6/1 kV


Number of conductors Thickness of Thickness of Cable diameter and nominal insulation sheath approx. cross section N mm2 1x25 rm 1x35 rm 1x50 rm 1x70 rm 1x95 rm 1x120 rm 1x150 rm 1x185 rm 1x240 rm 1x300 rm mm 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1,6 1,7 1,8 mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 mm 16.3 17.4 18.7 20.5 22.9 24.5 26.3 28.4 31.2 34.6 2XYRaY Mass of Cu approx kg/km 229 325 458 648 885 1120 1378 1770 2327 2887 Cable weight approx. kg/km 532 657 833 1073 1417 1699 2028 2643 3335 4118 A2XYRaY Mass of Al approx kg/km 68 95 127 190 260 325 405 510 665 830 Cable weight approx. kg/km 370 425 498 611 785 896 1046 1371 1656 2040

ELKABEL

39

LOW VOLTAGE POWER CABLES

2XYRY-0/J A2XYRY-0/J

Uo/U - 0.6/1 kV IEC 60502-1

Application
The power and control cables with cross-linked polyethylene (XLPE) armored with galvanized iron wires are used in electrical installations with nominal voltage Uo/U 0.6/1 kV. These cables are used in industrial installations and urban networks. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial installations, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelters.

Cable construction
Construction Conductor Insulation Inner sheath Armour Sheath According to IEC 60502-1 solid or multi-strand Al or Cu wires class 1 or 2 acc. IEC 60228 XLPE compound PVC compound St wires twisted concentrically PVC compound type ST2

Technical data
Conductor resistance at 20 Max. conductor temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage AC - 5 min. Bending radius, min. Temperature of laying Temperature of exploitation According class 1 or 2 IEC 60228 90 continuous operation 130C /100h/per year ./ 250 /5 s max./ 0.6/1 kV 1.2 kV between cores - 3.5 V between core and screen 3.5 V - 15x D cable no less than 0 - 30 to 50

Color coding
Double core - blue and brown or yellow - green and black

3-core brown black grey or yellow/ green blue brown

4-core blue brown black grey or yellow/ green brown black grey

5-core

Multiple core

blue brown black with black numbered mark or cores grey or black black with number mark or on cores and yellow/green yellow/green core in the blue outer cover brown black grey

40

ELKABEL

Cu/ Al conductors XLPE insulation PVC sheath Armour St. Wires PVC sheath

LOW VOLTAGE POWER CABLES

Construction data 2XYRY-O/J , A2XYRY-O/J 0.6/1 kV


Number of conductors Thickness of Thickness of and nominal insulation sheath cross section N..mm2 2 2.5 rm 2 4 rm 2 10 rm 2 16 rm 2 25 rm 2 50 rm 2 x 95 rm 3 1.5 rm 3 2.5 rm 3 4 rm 3 6 rm 3 10 rm 3 16 rm 3 25 rm 3 35 rm 3 50 rm 3 70 sm 4 2.5 rm 4 4 rm 4 6 rm 4 10 rm 4 16 rm 4 25 rm 4 35 rm 4x50 sm 4x70 sm 4x95 sm 4x120 sm 4x150 sm 4x185 sm 4x240 sm 7 x 1.5 rm 7 x 2.5 rm 12 x 1.5 rm 19 x 2.5 rm mm 0.7 0.7 0.7 0.7 0.9 1.0 1.1 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1,4 1,4 1,6 1,6 1,8 2 2.2 0.7 0.7 0.7 0.7 mm 1.8 1.8 1.8 1.8 1.8 1.9 2.1 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.1 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.1 2,1 2,1 2,2 2,4 2,5 2,6 1.8 1.8 1.8 1.8 Cable diameter approx. mm 14.1 15.2 18.9 20.3 24.9 29.2 38.2 16.5 16.5 17.5 17.8 19.8 21.3 25.4 27.8 30.9 34.6 16.6 17.5 19.1 21.2 23.6. 27.5 30.2 34.4 38.9 43.0 47.5 51.8 56.0 62.3 17.0 18.2 20.4 25.6 2XYRY-O/J Mass of Cu approx. kg/km 46 75 188 298 485 908 1822 43 70 112 168 282 447 728 1010 1363 1968 93 149 223 376 595 970 1346 1817 2624 3643 4587 5660 7082 9308 96 160 165 435 Cable weight approx. kg/km 421 500 863 1050 1584 2376 4058 596 619 713 774 987 1234 1878 2320 2901 3750 933 1060 1248 1576 2278 3059 3701 3535 4701 6017 7626 9144 10976 13861 960 1119 1294 2277 A2XYRY-O/J Mass of Al approx. kg/km 14 23 56 90 140 269 539 13 21 36 51 85 135 210 290 385 585 28 46 68 112 180 270 390 520 760 1060 1340 1650 2100 2720 30 49 51 133 Cable weight approx. kg/km 388 448 729 840 1236 1730 2762 566 570 636 656 788 919 1355 1593 1914 2353 867 956 1091 1309 1859 2352 2736 2225 2818 3408 4346 5094 5945 7207 894 1007 1179 1972

ELKABEL

41

N2XY-0/J
LOW VOLTAGE POWER CABLE

Uo/U - 0.6/1 kV VDE 0276-603

Application
The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable construction
Construction Conductor According to VDE 0276-603/5G Cu solid or stranded wires class 1 or 2 according to HD 383, VDE 0295 XLPE type DIX3 acc. to VDE 0276-603/5G Color code acc. to VDE 0276-603 filling compound PVC type DMV6,acc. to VDE 0276603/sec.1 black

Technical data
Conductor resistance Operating temperature Overload temperature Short circuit temperature Nominal voltage Highest system voltage Test voltage, AC 50 Hz Bending radius single core multicore Temperature of laying Temperature of exploitation Test According to VDE 0295 90C 130C/100h per year 250C ( 5 sec.) 0.6/1 kV 1.2 kV 4.0 kV 15 x Dcable 15 x Dcable -5C to 70C -30C to 70C /for PE sheath/ -30 to 70C According to DIN VDE 0276603 4-core blue brown black grey or yellow/ green black grey 5-core Multiple core

Insulation Identification of cores Filling Sheath Color

Color coding
Single core - black or yellow/green Double core - blue and brown or yellow-green and black

3-core brown black grey or yellow/ green, blue, brown

blue brown black with black number mark on cores grey or black black with number mark or on cores and yellow/green yellow/green core in the blue outer cover brown black grey

42

ELKABEL

Cu conductors XLPE insulation PVC sheath

LOW VOLTAGE POWER CABLE

Construction data N2XY-o/j 0.6/1 kV


Number of conductors and nominal cross section N x mm 116rm 1x25rm 1x35rm 1x50rm 1x70rm 1x95rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm 2x16rm 2x25rm 2x35rm 2x50rm 3x16rm 3x25rm 3x35rm 3x50sm 3x70sm 3x95sm 3x120sm 3x150sm 3x185sm 3x240sm 3x4+2.5re 3x6+4re 3x10+6re 3x16+10re 3x25+16rm 3x35+16rm 3x50+25sm/rm 3x70+35sm/rm 3x95+50sm/rm 3x120+70sm/rm 3x150+70sm/rm 3x185+95sm/rm 3x240+120sm/rm 4x16rm 4x25rm 4x35rm 4x50sm 4x70sm 4x95sm 4x120sm 4x150sm 4x185sm Thickness of insulation Thickness of sheath Outer diameter approx. Cu weight Cable weight approx.

mm 0.7 0.9 0.9 1,0 1,1 1,1 1,2 1,4 1,6 1,7 1,8 2,0 2,2 0,7 0.9 0.9 1.0 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 0.7/0.7 0.7/0.7 0.7/0.7 0.7/0.7 0.9/0.7 0.9/0.7 1.0/0.9 1.1/0.9 1.1/1.0 1.2/1.1 1.4/1.1 1.6/1.1 1.7/1.2 0,7 0,9 0,9 1.0 1,1 1,1 1,2 1,4 1,6

mm 1.8 1.8 1.8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,9 2,0 1,8 1.8 2.0 2.0 1.8 2.0 2.0 2.0 2.0 2.0 2.0 2.2 2.2 2.6 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.2 2.2 2.2 2.6 3.0 1,8 2.0 2.0 2.0 2.0 2,0 2,2 2,2 2,6

mm 11.0 12.5 13.5 15.5 17.0 19.0 21 23.0 27 30 32 37 40 19.5 23 25.5 29.0 20.5 24.5 27.0 24.5 28.0 31.0 34 37.0 42.0 47.5 13.5 15.0 17.0 20.0 27.0 29.5 28.5 33.0 36.5 39.0 44.0 48.5 57.0 22 27 29.5 28.5 33.0 33.0 39 44 49

kg/km 144 228 317 454 656 911 1147 1415 1770 2327 2887 3692 4725 294 466 646 924 441 699 969 1387 1897 2631 3324 4084 5123 6733 135 205 338 541 846 1116 1620 2220 3093 3956 4716 6000 7841 588 932 1292 1850 2530 2530 4433 5446 6831

kg/km 230 340 445 605 800 1065 1275 1610 1925 2483 3058 3887 4937 645 946 1235 1680 805 1220 1575 1765 2350 3145 3915 4820 6045 7885 328 445 611 868 1405 1765 2075 2650 3615 4690 5630 7150 9305 985 1500 1955 2320 3100 3100 5200 6410 8050

ELKABEL

43

LOW VOLTAGE POWER CABLE

N2XY-0 N2XY-J

Uo/U - 0.6/1 kV VDE 0276-603

Application
The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable construction
Construction Conductor Insulation Identification of cores Filling Sheath Color According to VDE 0276-603/5G Al solid or stranded wires class 1 or 2 according to HD 383,VDE 0295 XLPE type DIX3 acc. to VDE 0276-603/5G color code acc. to VDE 0276-603 filling compound

Technical data
Conductor resistance Operating temperature Overload temperature Short circuit temperature Nominal voltage Highest system voltage Test voltage, AC 50 Hz According to VDE 0295 90C 130C/100h per year 250C ( 5 sec.) 0.6/1 kV 1.2 kV 4.0 kV 15 x Dcable 15 x Dcable -5C to 70C -30C to 70C /for PE sheath/ -30 to 70C According to DIN VDE 0276603 4-core blue brown black grey or yellow/ green brown black grey 5-core Multiple core blue brown black with black number mark on cores grey or black black with number mark or on cores and yellow/green yellow/green core in the blue outer cover brown black grey

PVC type DMV6,acc. to VDE 0276-603/sec.1 black

Bending radius single core multicore Temperature of laying Temperature of exploitation Test

Color coding
Single core - black or yellow/green Double core - blue and brown or yellow-green and black

3-core brown black grey or yellow/ green, blue, brown

44

ELKABEL

Al conductors XLPE insulation PVC sheath

LOW VOLTAGE POWER CABLE

Construction data NA2XY-o/j 0.6/1 kV


Number of conductors and nomi- Thickness of insu- Thickness of lation sheath nal cross section N mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 mm 1,0 1,1 1,1 1,2 1,4 1,6 1,7 1,8 2,0 2,2 0,7 0,9 0,9 1,0 1,1 1,1 1,2 1,4 1,6 1,7 0,9 1,0 1,1 1,1 1,2 1,4 1,6 1,7 mm 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,8 1,9 2,0 1,8 1,8 1,8 1,9 2,1 2,1 2,3 2,4 2,6 2,7 1,8 1,9 2,0 2,1 2,2 2,4 2,5 2,7 Outer diameter approx. Al weight Cable weight approx.

min/mm 14,6 16,5 18,5 20,0 21,9 24,1 26,6 29,4 32,9 36,7 20,5 24,3 25,3 28,2 32,8 36,6 39,8 44,0 48,4 62,8 26,5 30,0 33,6 37,4 40,2 43,8 48,8 54,0

max/mm 17 19 20 22 24 27 30 32 37 40 24 31 32 35 40 44 48 53 58 64 30 33 38 41 45 49 54 59

kg/km 135 195 270 341 419 526 690 863 1109 1461 176 288 398 539 779 1079 1364 1676 2105 2762 388 522 756 1046 1324 1626 2042 2679

kg/km 245 318 391 469 565 681 846 1034 1304 1673 546 792 977 1259 1445 1811 2233 2696 3454 4129 977 1259 1446 1812 2233 2696 3285 4233

ELKABEL

45

U 1000 R2V
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV NF C 32-321

Application
These cables are used for distribution and supply of consumers with electrical power with nominal voltage 0.6/1kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts, tunnels and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable construction
Construction Conductor According to NF C 32-321 Cu wires according to NF C 32-321 (IEC 60228): -rm class 1, 1.5 to 16mm2 -rm class 2, 1.5 to 500mm2 -sm class 2, 50 to240mm2 XLPE compound

Technical data
Conductor resistance at 20: Operating temperature Overload temperature Short circuit temperature According to NF C 32-321 90C continuous operation 130C /100h/per year ./ 250C /5 s max./ 0.6/1 kV 1.2 kV -5C to +60C -25C to +70C 10 x D cable

Insulation Inner sheath Sheath Color

tape or extrusion PVC compound black Nominal voltage Uo/U: Highest system voltage Temperature range laying and installing exploitation and storage Bending radius, min. approx.

Color coding
Single core - black or yellow/green Double core - blue and brown or yellow-green and black

3-core brown black grey or yellow/ green, blue, brown

4-core blue brown black grey or yellow/ green brown black grey

5-core Multiple core blue brown black with black number mark on cores grey or black black with number mark or on cores and yellow/green yellow/green core in the blue outer cover brown black grey

46

ELKABEL

Cu conductors

XLPE insulation

PVC sheath

Construction data U 1000 R2V 0.6/1 kV


Number ofconductors and nominal cross section N mm2 110 116 125 135 150 170 195 1120 1150 1185 1240 21.5 22.5 24 26 210 216 225 31.5 32.5 34 36 310 316 rm rm rm rm rm rm rm rm rm rm rm re re re rm rm rm rm re re re rm rm rm Shape Outer Cable cable weight diameter Cu weight approx. approx. mm 9.2 10.5 12.5 13.5 15.0 17.0 19.0 21.0 23.0 25.5 28.5 9.7 10.5 11.5 12.6 14.3 16.0 20.3 10.1 11.0 12.1 13.2 14.9 17.0 kg/km 93 148 229 325 458 648 889 1120 1378 1703 2208 28 46 75 110 182 303 470 42 69 110 165 275 450 kg/km 147 209 300 399 520 738 990 1235 1480 1835 2370 140 173 223 295 410 586 855 160 202 260 352 498 720

Construction data U 1000 R2V 0.6/1 kV


Number ofconductors and nominal cross section N mm2 325 335 350 370 395 3120 3150 3185 3240 3G1.5 3G2.5 3G4 3G6 3G10 3G16 3G25 3x50+35 3x70+50 3x95+50 3x120+70 3x150+70 3x185+70 3x240+95 rm rm rm rm sm sm sm sm sm re re re rm rm rm rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm Shape Outer cable Cable diameter Cu weight weight approx. approx. mm 21.9 23.1 27.0 31.3 35.8 39.6 44.0 49.0 55.6 10.1 11.0 12.1 13.2 14.9 17.0 21.9 29.3 34.2 38.2 42.8 46.9 51.8 58.5 kg/km 700 980 1390 1950 2650 3350 4185 5160 6720 42 69 110 165 275 450 700 1715 2408 3120 4010 4850 5808 7605 kg/km 1065 1393 1830 2570 3460 4304 5280 6612 8588 160 202 260 352 497 720 1065 2150 2982 3830 4917 5848 7068 9241

LOW VOLTAGE POWER CABLES

Construction data U 1000 R2V 0.6/1 kV


Number ofconductors and nominal cross section N mm2 4x1.5 42.5 44 46 410 416 425 4G1.5 4G2.5 4G4 4G6 4G10 4G16 4G25 4G35 4G50 4G70 4G95 4G120 4G150 4G185 4G240 5G1.5 Shape Outer Cable cable weight diameter Cu weight approx. approx. mm 10.8 11.6 13.2 14.3 16.5 18.7 22.6 10.8 11.6 13.2 14.3 16.5 18.7 22.6 25.3 29.7 34.7 39.6 44.0 49.0 55.0 62.1 11.6 kg/km 55 92 146 218 363 582 925 55 92 146 218 363 582 925 1303 1857 2601 3540 4460 5575 6880 8928 69 kg/km 182 236 312 418 605 868 1310 182 236 312 418 605 868 1310 1730 2290 3240 4310 5447 6690 8400 10887 117

Construction data U 1000 R2V 0.6/1 kV


Number ofconductors and nominal cross section N mm2 5G2.5 5G4 5G6 5G10 5G16 5G25 7G1.5 8G1.5 10G1.5 12G1.5 14G1.5 19G1.5 24G1.5 30G1.5 37G1.5 7G2.5 8G2.5 10G2.5 12G2.5 14G2.5 19G2.5 24G2.5 30G2.5 37G2.5 Shape Outer Cable cable weight diameter Cu weight approx. approx. mm 12.7 14.3 15.4 18.2 20.4 25.3 12.5 13.7 15.4 16.0 16.5 18.7 21.5 22.5 24.8 13.7 14.9 17.0 17.6 18.7 20.9 24.2 25.3 27.5 kg/km 114 182 275 455 745 1165 96 110 140 165 195 260 330 410 506 160 182 228 275 320 435 546 685 845 kg/km 274 360 497 725 1060 1585 230 260 316 357 403 511 630 748 890 312 350 428 487 545 701 860 1045 1247

re re re rm rm rm rm re re re rm rm rm rm rm rm rm sm sm sm sm re

re re rm rm rm rm re re re re re re re re re re re re re re re re re re

ELKABEL

47

U 1000 AR2V
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV NF C 32-321

Application
These cables are used for distribution and supply of consumers with electrical power with nominal voltage 0.6/1kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts, tunnels and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable construction
Construction Conductor According to NF C 32-321 Aluminum wires acc. NF C 32-321 - single core circular class 2, 2.5 to 35mm2 - stranded class 2 round and - sector, 35 to240mm2 XLPE compound - up to 6 cores - PVC filling - 7 cores and more - polyester tape PVC compound black

Technical data
Conductor resistance at 20: Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Temperature range laying and installing exploitation and storage Bending radius, min. approx. 3-core brown black grey or yellow/ green blue brown 4-core blue brown black grey or yellow/ green brown black grey According to NF C 32-321 90C continuous operation 130C /100h/per year ./ 250C /5 s max./ 0.6/1 kV 1.2 kV -5C to +60C -25C to +70C 10 x D cable

Insulation Filling Sheath Color

Color coding
Single core - black or yellow/green Double core - blue and brown or yellow-green and black

5-core Multiple core blue brown black with black number mark on cores grey or black black with number mark or on cores and yellow/green yellow/green core in the blue outer cover brown black grey

48

ELKABEL

Al conductors

XLPE insulation

PVC sheath

LOW VOLTAGE POWER CABLES

Construction data U 1000 R2V 0.6/1 kV


Number of conductors and nominal cross section N mm2 110 116 125 135 150 170 195 1120 1150 1185 1240 22.5 24 26 210 216 225 32.5 34 36 310 316 re re re re rm rm rm rm rm rm rm re re re re re re re re re re re Shape Outer cable diameter Al weight approx. mm 9.2 10.5 12.5 13.5 15.0 17.0 19.0 21.0 23.0 25.5 28.5 10.5 11.5 12.6 14.3 16.0 20.3 11.0 12.1 13.2 14.9 17.0 kg/km 28 45 68 95 127 190 260 325 405 510 665 14 23 34 56 90 137 21 36 51 85 135 Cable weight approx. kg/km 82 106 139 170 192 283 361 440 507 642 827 141 173 220 284 373 522 154 186 238 308 405

Construction data U 1000 R2V 0.6/1 kV


Number of conductors and nominal cross section N mm2 325 335 350 370 395 3120 3150 3185 3240 3G2.5 3G4 3G6 3G10 3G16 3G25 3x50+35 3x70+50 3x95+50 3x120+70 3x150+70 3x185+70 3x240+95 re re rm sm sm sm sm sm sm re re re re re re rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm Shape Outer cable diameter Al weight approx. mm 21.9 23.1 27.0 31.3 35.8 39.6 44.0 49.0 55.6 11.0 12.1 13.2 14.9 17.0 21.9 29.3 34.2 38.2 42.8 46.9 51.8 58.5 kg/km 210 290 385 585 810 1020 1255 1560 2035 21 36 51 85 135 210 480 680 910 1180 1405 1750 2295 Cable weight approx. kg/km 575 703 825 1205 1620 1975 2350 3012 3903 154 186 238 308 405 575 915 1254 1620 2087 2403 3010 3931

Construction data U 1000 R2V 0.6/1 kV


Number of conductors and nominal cross section N mm2 42.5 44 46 410 416 425 4G2.5 4G4 4G6 4G10 4G16 4G25 4G35 4G50 4G70 4G95 4G120 4G150 Shape Outer cable diameter Al weight approx. mm 11.6 13.2 14.3 16.5 18.7 22.6 11.6 13.2 14.3 16.5 18.7 22.6 25.3 29.7 34.7 39.6 44.0 49.0 kg/km 28 46 68 112 180 270 28 46 68 112 180 270 390 520 760 1060 1340 1650 Cable weight approx. kg/km 144 166 268 354 466 655 144 166 268 354 466 655 817 953 1400 1830 2327 2765

Construction data U 1000 R2V 0.6/1 kV


Number of conductors and nominal cross section N mm2 4G185 4G240 5G2.5 5G4 5G6 5G10 5G16 5G25 7G2.5 8G2.5 10G2.5 12G2.5 14G2.5 19G2.5 24G2.5 30G2.5 37G2.5 Shape Outer cable diameter Al weight approx. mm 55.0 62.1 12.7 14.3 15.4 18.2 20.4 25.3 13.7 14.9 17.0 17.6 18.7 20.9 24.2 25.3 27.5 kg/km 2100 2720 35 58 85 140 225 345 49 56 70 84 98 133 168 210 260 Cable weight approx. kg/km 3620 4680 195 236 307 410 540 765 201 224 270 296 323 400 482 570 662

re re re re re re re re re re re re re rm sm sm sm sm

sm sm re re re re re re re re re re re re re re re

ELKABEL

49

EXVB
Cu conductors

Uo/U - 0.6/1 kV NBN C 33-322 / NBN C 30-004

XLPE insulation

PVC filling

PVC sheath

LOW VOLTAGE POWER CABLES

Application
These cables are used for distribution and supply of consumers with electrical power with nominal voltage 0.6/1kV and frequency 50 Hz in industrial installations and urban networks They are suitable for fixed indoor assembly in cable ducts, tunnels and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable design
Construction Conductor According to NBN C 33-322 Cu according to NBN C 33-322 (IEC 60228): -rm class 1 1.5 to 16mm2 -rm class 2 1.5 to 500mm2 XLPE compound

Technical data
Conductor resistance at 20: Operating temperature Overload temperature Short circuit temperature IEC 60228 90C continuous operation 130C /100h/per year ./ 250C /5 s max./ 0.6/1 kV 1.2 kV -5C to +60C -25C to +70C 12 x D cable

Insulation Inner sheath Sheath Color

tape or extrusion PVC compound black

Nominal voltage Uo/U: Highest system voltage Temperature range laying and installing exploitation and storage Bending radius, min. approx. Construction 4

Color coding

Core color Blue / brown / black / black

Construction data EXVB 0.6/1 kV


Number of conductors and nominal cross section N mm2 410 416 425 re rm rm Shape Cable diameter approx. mm 18.5 21.0 25.5 Cu weight kg/km 363 592 925 Cable weight approx. kg/km 695 1002 1445

50

ELKABEL

Cu/XLPE/PVC
Cu conductors

Uo/U - 0.6/1 kV IEC 60502-1 and BS 7889/97

XLPE insulation

PVC sheath

LOW VOLTAGE POWER CABLES

Application
These cables are used for distribution and supply of consumers with electrical power with nominal voltage 0.6/1kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts, tunnels and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.

Cable design
Construction Conductor Insulation Sheath Color According to IEC60502/BS 7889/97 Cu wires,class 2 according to BS 6360 IEC 60228 XLPE, black PVC compound black


Conductor resistance at 20: Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Temperature range laying and installing exploitation and storage Bending radius, min. approx. According to NF C 32-321 90C continuous operation 130C /100h/per year ./ 250C /5 s max./ 0.6/1 kV 1.2 kV -5C to +60C -25C to +70C 10 x D cable

Construction data Cu/XLPE/PVC 0.6/1 kV


Number of conductors and nominal cross section N mm2 1x6 110 116 125 135 150 170 195 rm rm rm rm rm rm rm rm Shape Outer Cable cable weight diameter Cu weight approx. approx. mm 7.3 8.2 8.9 10.5 11.6 13.6 15.6 17.5 kg/km 55 93 148 229 325 458 648 885 kg/km 92 135 191 285 376 540 750 1010

Construction data Cu/XLPE/PVC 0.6/1 kV


Number of conductors and nominal cross section N mm2 1120 1150 1185 1240 1x300 1x400 1x500 1x630 rm rm rm rm rm rm rm rm Shape Outer Cable cable weight diameter Cu weight approx. approx. mm 19.2 21.3 23.4 26.3 29.0 32.7 36.6 41.3 kg/km 1120 1378 1703 2208 2765 3680 4600 5890 kg/km 1250 1530 1900 2470 3080 3890 4970 6370

ELKABEL

51

Cu/XLPE/PVC/SWA/PVC

Uo/U - 0.6/1 kV BS 5467-1997

LOW VOLTAGE POWER CABLES

Application
The power and control cables with cross-linked polyethylene (XLPE) armored with galvanized steel wires are used in electrical installations with nominal voltage Uo/U 0.6/1 kV. These cables are used in industrial installations and urban networks. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial installations, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelters.

Cable construction
Construction Conductor Insulation Colors According to BS 5467-97 u wires stranded according to BS 6360 ( IEC 60228 ) class 2 XLPE compound type GP 8 specified in BS 7655 2-cores - brown; blue 3-cores - brown; black; grey 4-cores - brown; black; grey; blue 5-cores - brown; black; grey; green /yellow; blue Control - black with white numbers or white with black numbers polymer compound galvanized steel wires , applied helically PVC compound according to type 9 specified in BS 7655 black

Technical data
Conductor resistance at 20 Operating temperature max. Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage According to BS 6360 (IEC228) class 2 90 continuous operation 130C /100h/per year ./ 250 /5 s max./ 0.6/1 kV 1.2 kV between cores - 3.5 V between core and screen 3.5 V - 6x D cable - 8 D cable no less than 0

Inner sheath Armour Sheath Color

Test voltage AC - 5 min Bending radius, min. - circular cores - sector Temperature of laying Temperature of exploitation

- 30 to 50 Cu cores - 50*n*S core

Force of strain in laying N -n-number of cores max. and -S-nominal cross section of cores in mm

52

ELKABEL

Cu conductors

XLPE insulation PVC sheath PVC sheath

Armour

LOW VOLTAGE POWER CABLES

Construction data
Number of conductors and nominal cross section N mm2 Thickness of insulation mm

Cu/XLPE/PVC/SWA/PVC 0.6/1 kV
Thickness of Cable diameter oversheath approx. mm mm Mass of Cu approx. kg/km Cable weight approx. kg/km

Nominal steel armour wire diameter mm

2x1.5 rm 2x2.5 rm 2x4.0 rm 2x6.0 rm 2x10 rm 2x16 rm 2x25 rm 2x35 rm 3x1.5 rm 3x2.5 rm 3x4.0 rm 3x6.0 rm 3x10 rm 3x16 rm 3x25 rm 3x35 rm 4x1.5 rm 4x2.5 rm 4x4.0 rm 4x6.0 rm 4x10 rm 4x16 rm 4x25 rm 4x35 rm 4x35 sm 4x50 sm 4x70 sm 4x95 sm 4x120sm 4x150 sm 4x185 sm 5x1.5 rm 5x2.5 rm 5x4.0 rm 5x6.0 rm 5x10 rm 5x16 rm 5x25 rm 5x35 rm 7x1.5rm 12x1.5 rm 19x1.5 rm 27x1.5 rm 37x1.5 rm 7x2.5 rm 12x2.5 rm 19x2.5 rm 27x2.5 rm 37x2.5 rm 7x4.0 rm 12x4.0 rm 19x4.0 rm 27x4.0 rm 37x4.0 rm

0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

0.9 0.9 0.9 0.9 0.9 1.25 1.25 1.6 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 0.9 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 0.9 0.9 0.9 1.25 1.25 1.60 1.60 1.60 0.9 1.25 1.25 1.6 1.6 0.9 1.25 1.6 1.6 1.6 1.25 1.6 1.6 1.6 2.0

1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.3 1.4 1.4 1.4 1.5 1.6 1.7 1.8 1.3 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.9 2.1 2.2 2.4 2.6 2.6 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 1.4 1.5 1.6 1.7 1.7 1.4 1.6 1.7 1.8 1.8 1.5 1.6 1.7 1.9 2.0

12.1 12.9 14.7 15.9 18.0 21.9 26.7 29.2 12.8 14.1 15.8 18.0 21.2 23.1 28.2 30.8 13.3 15.0 16.4 18.7 21.1 23..4 28.9 33.7 28.6 32 37.7 41.7 47.1 51.4 56.6 14.3 16.3 19.0 20.9 25.8 28.4 33.5 36.6 15.2 18.5 21.1 26.7 29.0 17.1 22.4 26.6 30.7 33.8 19.7 25.7 29.3 34.4. 39.2

28 46 75 110 182 303 470 652 42 69 110 165 275 450 700 980 55 92 146 218 363 592 925 1303 1303 1857 2601 3540 4460 5575 6880 69 114 182 275 455 745 1165 1640 96 165 260 373 506 160 525 590 621 845 258 442 700 994 1362

272 337 407 491 655 955 1263 1732 301 379 457 558 863 1267 1956 2118 331 426 525 754 1005 1326 2037 2529 2332 2965 4199 5368 6899 8227 9943 383 487 622 873 1180 1752 2450 3044 434 737 946 1385 1659 564 960 1440 1854 2253 808 1403 1854 2430 3316

ELKABEL

53

Cu/XLPE/PVC/AWA/PVC

Uo/U - 0.6/1 kV BS 5467-1997

LOW VOLTAGE POWER CABLES

Cu conductors

XLPE insulation PVC sheath PVC sheath

Armour Al wires

Application
The single-core power cables with insulation of cross-linked polyethylene (XLPE) type LSOH are flame retardant, with low halogen free smoke emission and corrosion at fire conditions and are suitable for use in electrical installations for nominal voltage Uo/U 0.6/1 kV. Cables are designed with sheath, which does not contain halogen materials, flame retardant, free smoke emission and corrosion, and non-magnetic armor of l wires. They are suitable for use in distribution networks, electrical power stations and substations. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial sites, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Insulation Inner sheath Armour Sheath Color According to BS 5467-97 u stranded wires according to BS 6360 (IEC 60228) class 2 XLPE compound, black and red PVC compound non-magnetic l wires, laid concentrically PVCcompound type 9 black

Technical data
Conductor resistance at 20 Operating temperature max. Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage AC - 5 min Bending radius, min. Temperature of laying Temperature of exploitation According to BS 6360 (IEC 60228) class 2 90 continuous operation 130 /100h/per year ./ 250 /5 s max./ 0.6/1 kV 1.2 kV Between core and screen 3.5kV 6x D cable no less than 0 - 30 to 50

Cu cores- 50*n*Score Force of strain in laying N n-number of cores and max. S-nominal cross-section of cores in mm

Construction data Cu/XLPE/PVC/AWA/PVC


Number of conductors and nominal cross section N mm2 Thickness of insulation mm Diameter of Al Thickness of Cable diameter wires in armor sheath approx. mm mm mm Mass of Cu approx kg/km Cable weight approx. kg/km

1x150rm 1x185 rm 1x240 rm 1x300 rm 1x400 rm 1x500 rm

1.4 1.6 1.7 1.8 2.0 2.2

1.6 1.6 1.6 1.6 2.0 2.0

1.7 1.8 1.8 1.9 2.0 2.1

26.3 28.7 31.4 34.1 38.9 42.8

1378 1703 2208 2765 3680 4600

1724 2113 2696 3305 4286 5381

54

ELKABEL

POWER CABLES FOR OVERHEAD LINES

ELKABEL

LOW VOLTAGE POWER CABLES FOR OVERHEAD LINES - SELF-SUPPORTING TYPE

NFA2X // SH - V

Uo/U - 0.6/1 kV VDE 0276-626/4F // FN KI 02.003

Application
The power cables with XLPE insulation for overhead lines - self-supporting type are designed for transfer, distribution and supply with electrical power in networks low voltage Uo/U 0.6/1 kV. In constructions for distribution networks these cable permit suspension on fasades and trees. They allow crossing of forest areas without cutting and maintenance of openings in the wood. The suspension and support of the whole bundle is carried out by the phase ( basic ) insulated current-conductive.

Cable construction
Construction Conductor -phase (main) According to VDE 0276-626/4F FN KI 02.003-96 Al stranded compacted or Non-compacted according to VDE 0276-626 Al stranded compacted or Non-compacted according to VDE 0276-626 XLPE with min. 2% carbon black content type TIX-2 constructions twisted into a bundle include: - phase (main) insulated cores() - one, two, or three additional reduced insulated cores for lighting ( R ) black for NFA2X - to VDE 0276-626 for SAH-VO - to FN KI 02 003

Technical data
Operating temperature Short-circuit temperature Nominal voltage 80 130 Uo/U 0.6/1 kV

-additional for lighting

Highest system voltage AC, not more than Test voltage C -5 min DC - 15 min Bending radius, min. Temperature of laying

1.2 kV

Insulation Cable lay up (cable constructions)

4 kV 10 kV 18xD cable no less than - 10 recommended 15 50 - 0.641/ 70-0.443 / 95 - 0.320/ 50 - 8.45 N 70 -11.32 N 95 - 15.68 kN

Conductor resistance at 16 - 1.91 / 25 - 1.20 / 20C 35 - 0.868/ 16 - 2.84 kN 25 -4.17 kN 35 - 5.78 kN

Color Marking

Breaking strengh min.

56

ELKABEL

Al conductors XLPE insulation

LOW VOLTAGE POWER CABLES FOR OVERHEAD LINES - SELF-SUPPORTING TYPE

Construction data NFA2X / SAH-VO 0.6/1 kV


Number of conductors and nominal cross section N mm2 1x16 1x25 1x35 1x50 1x70 1x95 2x16 2x25 2x35 2x50 4x16 4x25 4x35 4x50 4x70 4x95 4x25+1x16 4x25+2x16 4x35+1x16 4x35+2x16 4x35+1x25 4x35+2x25 4x50+1x16 4x50+2x16 4x50+1x25 4x50+2x25 4x50+1x35 4x50+2x35 4x70+1x16 4x70+2x16 4x70+1x25 4x70+2x25 4x70+1x35 4x70+2x35 4x95+1x16 4x95+2x16 4x95+1x25 4x95+2x25 4x95+1x35 4x95+2x35 Diameter of bundle approx. Mass approx. Mass of l cores approx. kg/km 44 67 97 137 187 267 91 139 196 281 181 278 397 562 764 1091 323 368 442 487 453 536 607 652 631 700 661 760 810 855 834 903 854 963 1136 1181 1160 1230 1190 1289 Cable weight approx. kg/km 74 103 133 185 242 333 152 210 272 277 303 421 543 753 986 1358 496 572 619 695 645 754 829 905 858 964 889 1025 1061 1137 1091 1196 1121 1257 1434 1510 1463 1569 1494 1630 Allowed current in power Allowed current supply netat short-circuit works A 81 107 132 162 205 245 81 107 132 162 81 107 132 162 205 243 107 107 132 132 132 132 162 162 162 162 162 162 205 205 205 205 205 205 245 245 245 245 245 245 kA 0,8 1,3 1,9 2,7 3,8 5,2 0,8 1,3 1,9 2,7 0,8 1,3 1,9 2,7 3,8 5,2 1,3 1,3 1,9 1,9 1,9 1,9 2,7 2,7 2,7 2,7 2,7 2,7 3,8 3,8 3,8 3,8 3,8 3,8 5,2 5,2 5,2 5,2 5,2 5,2

mm 9,0 10,0 11,0 12,5 14,0 16,0 18,0 20,0 22,0 25,0 19,0 20,0 25,0 28,0 32,0 44,0 25,0 28,0 28,0 31,0 29,0 32,0 30,0 34,0 31,0 35,0 32,0 36,0 35,0 38,0 36,0 38,0 36,0 40,0 41,0 44,0 42,0 45,0 42,0 46,0

ELKABEL

57

SH - V
LOW VOLTAGE POWER CABLES FOR OVERHEAD LINES WITH SUPPORTING NEUTRAL

Uo/U - 0.6/1 kV FN KI 02.003

Application
The power cables with XLPE insulation for overhead lines - self-supporting type are designed for transfer, distribution and supply with electrical power in networks low voltage Uo/U 0.6/1 kV. In constructions for distribution networks these cable permit suspension on fasades and trees. They allow crossing of forest areas without cutting and maintenance of openings in the wood. The suspension and support of the whole bundle is carried out by a supporting insulated neutral wire of aluminium steel conductor or of aluminium alloy.

Cable construction
Construction Conductor -phase(main) According to FN KI 02.003-96 Al stranded compacted or Non-compacted according to FN KI 02.003 steel reinforced Al stranded conductor or Al alloy conductor to FN KI 02.003 Al stranded compacted or noncompacted according to FN KI 02 003 XLPE with min. 2% carbon black constructions twisted into a bundle - phase (main) insulated cores() - neutral supporting insulated core ( N ) - one, two, or three additional reduced insulated cores for lighting ( R ) black to FN KI 02.003

Technical data
Operating temperature Short-circuit temperature Nominal voltage DC Highest system voltage AC, not more than Test voltage C -5 min DC - 15 min Bending radius, min. Temperature of laying 80 130 Uo/U 0.6/1 kV 0.9 kV

- neutral (supporting) N -additional for lighting R

1.2 kV 4 kV 10 kV - 18xD cable no less than - 10 recommended 15 16 - 1.91 / 50 - 0.641/ 25 - 1.20 / 70 - 0.443/ 35 - 0.868/ 95 - 0.320/ (Al/St) 71.5 - 0.470/ 15.5 N

Insulation Cable lay up include:

Color Marking

Conductor resistance at 20C

Supported neutral breaking strength min.

58

ELKABEL

Al conductors XLPE insulation

Construction data SAH-VO 0.6/1 kV


Mass approx. Construction, number and cross section Diameter of bundle approx. Mass of l cores approx. kg/km 499 544 589 588 633 679 712 757 802 864 909 954 Cable weight approx. kg/km 675 751 827 767 843 919 925 1000 1076 1099 1175 1250 Allowed current in power Allowed cursupply net- rent at shortcircuit works A 107 107 107 132 132 132 162 162 162 205 205 205 kA 1,3 1,3 1,3 1,9 1,9 1,9 2,7 2,7 2,7 3,8 3,8 3,8

LOW VOLTAGE POWER CABLES FOR OVERHEAD LINES WITH SUPPORTING NEUTRAL

N mm2 3x25rm+71,5ASt/rm 3x25rm+71,5ASt+1x16rm 3x25rm+71,5ASt+2x16rm 3x35rm+71,5ASt 3x35rm+71,5ASt+1x16rm 3x35rm+71,5ASt+2x16rm 3x50rm+71,5ASt 3x50rm+71,5ASt+1x16rm 3x50rm+71,5ASt+2x16rm 3x70rm+71,5ASt 3x70rm+71,5ASt+1x16rm 3x70rm+71,5ASt+2x16rm

mm 27 27 27 31 31 31 34 34 34 40 40 40

ELKABEL

59

Al/R
LOW VOLTAGE POWER CABLES FOR OVERHEAD LINES WITH SUPPORTING NEUTRAL

Uo/U - 0.6/1 kV NF C 33-209

Application
The power cables with cross-linked polyethylene (XLPE) insulation for overhead lines are designed for electrical installations with alternating power networks with nominal voltage Uo/U 0.6/1 kV or in direct power networks with maximum voltage according to land 0.9 V. The cables with supporting (bearing) zero conductors are used for building networks in city and urban areas and the self-supporting type cables are for building distribution networks in these areas. Cables for overhead installations may be used in different types of installations: on free hanging facades; between posts; on fixed facades; trees and poles. Interception of forest areas without the need of clearance and maintenance of openings is allowed. -Cables with supporting zero conductor, the whole bundle is suspended and carried by the supporting conductor, which is made of aluminum compound. - Self-supporting construction, suspension and carrying of the whole bundle is done by the phase insulated conductors. Bundles can include one or two additional conductors for public lighting and control pair.

Cable construction
Construction Conductor phase(main) - neutral (supporting) N -additional for lighting R Insulation According to NF C 33-209 Al stranded compacted or Non-compacted according to NF C 33-209 AL stranded according to NF C 33-209 Al stranded compacted or noncompacted according to NF C 33209 XLPE with min. 2% carbon black con tent Constructions twisted into a bundle include: - phase (main) insulated cores() - neutral supporting insulated core ( N ) - one, two, or three additional reduced insulated cores for lighting ( R ) black raised with paint: - phase ( ) - with numbers 1;2;3 - supporting 0 core( N ) ELKABEL NF C 33-209 additional cores for lighting ( R ) - EP1 and EP2

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage DC According to NF C 33-209 90 continuous operation 130 /100h/per year ./ 250 /5 s max./ Uo/U 0.6/1 kV 0.9 kV 1.2 kV 4 kV 10 kV between cores - 3.5 V between core and armor - 3.5 V - 18x D cable no less than - 10 recommended 15 16 -1.91/ 25 -1.20/ 70-0.443/ 95-0.320/

Highest system voltage AC, not more than Test voltage: C -15 min DC - 15 min Bending radius, min. Temperature of laying Resistance at 20:

Color Marking:

35 - 0.868/ 120-0.253/ 50 - 0.641/ 150-0.206/ 54.6Alm-0.63/;70Alm-.5/ Supported neutral breaking strength min. 95Alm - 0.343/ 54.6 - 16.6N 70 - 20.50kN 95 - 27.50N

60

ELKABEL

Al conductors XLPE insulation

LOW VOLTAGE POWER CABLES FOR OVERHEAD LINES WITH SUPPORTING NEUTRAL

Construction data Al/R 0.6/1 kV


Number of conductors Thickness of insu- Diameter and nominal cross of bundle lation M/N/R section approx. N mm2 2x16 2x25 4x16 4x25 3x25+54.6Alm 3x25+54.6Alm+Kx16 3x35+54.6Alm 3x35+54.6Alm+Kx16 3x50+54.6Alm 3x50+54.6Alm+Kx16 3x50+54.6Alm+Kx25 3x70+54.6Alm 3x70+54.6Alm+Kx16 3x70+54.6Alm+Kx25 3x70+70Alm 3x70+70Alm+Kx16 3x70+70Alm+Kx25 3x95+54.6Alm 3x95+54.6Alm+Kx16 3x95+54.6Alm+Kx25 3x95+70Alm 3x95+70Alm+Kx16 3x95+70Alm+Kx25 3x120+70Alm 3x120+70Alm+Kx16 3x120+70Alm+Kx25 3x120+95Alm 3x120+95Alm+Kx16 3x120+95Alm+Kx25 3x150+70Alm 3x150+70Alm+Kx16 3x150+70Alm+Kx25 mm 1.2 1.4 1.2 1.4 1.4/1.6 1.4/1.6/1.2 1.6/1.6 1.6/1.6/1.4 1.6/1.6 1.6/1.6/1.2 1.6/1.6/1.4 1.8/1.6 1.8/1.6/1.2 1.8/1.6/1.4 1.8/1.5 1.8/1.5/1.2 1.8/1.5/1.4 1.8/1.6/ 1.8/1.6/1.2 1.8/1.6/1.4 1.8/1.5 1.8/1.5/1.2 1.8/1.5/1.4 1.8/1.5 1.8/1.5/1.2 1.8/1.5/1.4 1.8/1.6 1.8/1.6/1.2 1.8/1.6/1.4 1.7/1.5/ 1.7/1.5/1.2 1.7/1.5/1.4 mm 15 18 18 22 30 30 33 33 36 36 36 37 40 40 41 41 41 44 44 44 44 44 44 46 46 46 47 47 47 48 48 48 Allowed current in power supply networks 112 112 / 83 138 138 / 83 168 168 / 93 168 / 111 213 213 / 83 213 / 111 213 213 / 83 213 / 111 258 258 / 83 258 / 111 258 258 / 83 258 / 111 300 300 / 83 300 /111 300 300 / 83 300 / 111 344 344 / 83 344 / 111 Allowed current in distribution networks A walls/air/facades 72 / 93 / 83 95 / 122 / 111 63 / 83 / 75 83 / 111 / 99 -

l/R
Mass of l cores approx. kg/km 91 142 183 285 369 460 455 546 583 674 725 754 845 896 798 889 940 967 1059 1110 1011 1102 1154 1225 4828 1368 1296 1387 1439 1482 1573 1624 Cable weight approx. kg/km 125 165 260 395 505 635 615 745 725 860 925 950 1080 1150 984 1115 1185 1195 1325 1355 1355 1615 1485 1445 1575 1610 1535 1660 1735 1670 1795 1870

Note: 1. "" - is the number of conductors for public electricity and can accept values of 0; 1; 2 or 3. 2. Mass of core and cable are shown in =2

ELKABEL

61

SAH-20//SAX SAHv-20
CONDUCTORS WITH XLPE INSULATION FOR OVERHEAD LINES TO 20 KV

Uo/U - 12/20 kV FN KI 02.004/06 / / SFS 5791/94

Application
Conductors with XLPE insulation for overhead lines, are designed for transfer and distribution of electrical power in overhead electrical networks with nominal voltage to Uo/U/Um 12/20/24 kV and frequency 50 Hz. The main characteristics of overhead lines with XLPE insulation overhead conductors are low susceptibility to operational failures when conductors strike against each other or when a tree is temporarily leaning on the line. Also the space in the terrain required for the line is narrower, specially in casse of parallel lines.

Cable construction
Construction Conductor According to FN KI 02.004 and SFS 5791/94 Al alloy conductor stranded com pacted -steel reinforced Al stranded com pacted or stranded type AC XLPE with min. 2% carbon black Longitudinal water blocking( ), may be provided by agreement between the manufacturer and the purchaser Black SAH-20 - to FN I 02 004 SAHv-20 -to FN I 02 004 with longitudinal water blocking S - SFS 5791 /94

Technical data
Operating temperature Short-circuit temperature Nominal voltage 50Hz 90 in operation 250 max. 5sec. to Uo/U 12/20 kV (6/10kV)

Insulation Additional element

Highest system voltage Um not more than

24 kV

Color Marking

Test voltage

4kV / 5 min

Bending radius, min. Temperature of laying

10xD cable no less than - 20 recommended 15

62

ELKABEL

Al conductors XLPE insulation

CONDUCTORS WITH XLPE INSULATION FOR OVERHEAD LINES TO 20 KV

Construction and electrical data


Nominal crossNumber of Nominal Nominal Approximate section of a strands in a diameter of thickness overall a of conductor conductor conductor covering diameter mm2 35Alm 50Alm 70Alm 95Alm 120 Alm 150 Alm 35/rm 50/rm 70/rm 95/rm 120/rm 150/rm *35/rm *50/rm *70/rm *95/rm N 7 7 7 7 19 19 7 7 7 7 19 19 7 7 7 7 mm 7.00.20 8.00.20 9.70.25 11.30.3 12.80.3 14.20.3 7.00.20 8.00.20 9.70.25 11.30.3 12.80.3 14.20.3 8.4 9.6 11.4 13.5 mm 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 mm 11.6 12.6 14.3 15.9 17.4 18.8 11.6 12.6 14.3 15.9 17.4 18.8 13.0 14.2 16.0 18.1 Mass of cable approx. ResistanBreaking Short ce at tem- Current load circuit perature carrying min. current 20 capacity for 1 s m N 11.2 14.2 20.6 27.9 35.2 43.4 11.2 14.2 20.6 27.9 35.2 43.4 13.38 17.01 23.59 32.98 / 0.986 0.720 0.493 0.363 0.288 0.236 0.986 0.720 0.493 0.363 0.288 0.236 0.778 0.595 0.422 0.301 A 195 245 300 370 425 495 195 245 300 370 425 495 195 245 300 370 kA 3.2 4.35 6.85 8.908. 11.70 14.50 3.2 4.35 6.85 8.908. 11.70 14.50 3.2 4.35 6.85 8.908.

kg/km 160 200 270 350 425 510 205 250 340 450 470 590 245 305 405 545

NOTE: * Conductors type AC according to BDS 1133

ELKABEL

63

MIDDLE VOLTAGE POWER CABLES

ELKABEL

MIDDLE VOLTAGE POWER CABLES

ELKABEL

2XSY/N2XSY Uo/U - 6/10 kV, 12/20 kV, 18/30kV A 2 X S Y / N A 2 X S Y EC 60502-2 / DIN VDE 0276-620
MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Inner semiconductive layer Insulation Outer semiconductive layer

Metal screen

max. 5 pC 15x D cable no less than - 20

Separating layer Sheath

PVC compound type ST2 according to IEC 60502 type DMV 6 according to VDE 0276 red

Temperature of exploitation Tests

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620 Al cores - 30*n*S core Cu cores - 50*n*S core n- number of cores and -S-cross-section of conductors in mm

Color

Force of strain in laying N max. where:

66

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PVC sheath

Construction data 2XSY/N2XSY, A2XSY/NA2XSY 6/10; 12/20; 18/30 kV


Number of conNominal ThicThicductors and crosskness of kness of section of nominal cross insulation sheath section screen N mm2 mm mm mm2 Cable diameter approx. 2XSY, N2XSY Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km A2XSY, NA2XSY Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

min mm

max mm

6/10 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 12/20 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 18/30 kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8 8 8 8 8 8 8 8 8 8

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

23 24 26 27 29 30 32 34 30 32 34 36 40 43 27 28 30 31 33 34 36 39 34 36 39 41 44 47 33 35 36 38 39 41 43 46 49 52

28 29 31 32 34 35 37 39 35 37 39 41 45 48 32 33 35 36 38 39 41 44 39 41 44 46 49 52 38 40 41 43 44 46 48 51 54 57

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

935 1076 1312 1599 1859 2155 2536 3126 2239 2620 3210 3800 4736 5795 1116 1264 1512 1809 1995 2385 2777 3466 2469 2861 3466 4071 5025 6127 1508 1768 2078 2358 2758 3163 3786 4428 5425 6555

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

712 775 878 996 1101 1219 1366 1587 1302 1450 1671 1896 2307 2657 893 964 1078 1206 1237 1448 1607 1927 1532 1691 1927 2168 2596 2988 1208 1334 1475 1600 1822 1993 2246 2524 2996 3417

ELKABEL

67

- 6/10 kV, 12/20 kV, 18/30kV 2 X S 2 Y / N 2 X S 2 Y Uo/U 60502-2 / DIN VDE 0276-620 IEC A2XS2Y/NA2XS2Y

MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PE compound type ST7 according to IEC 60502 type DMP 2 according to VDE 0276 black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Metal screen

Separating layer Sheath

max. 5 pC 15x D cable no less than - 20

Color

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

68

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data 2XS2Y/N2XS2Y, A2XS2Y/NA2XS2Y 6/10; 12/20; 18/30 kV


Number of conThicThicknes Nominal ductors and crosskness of s of nominal cross insulation sheath section of section screen N mm2 mm mm mm2 Cable diameter approx. 2XS2Y, N2XS2Y Mass of Cu approx. kg/km Mass of cable approx. kg/km A2XS2Y, NA2XS2Y Mass of Al approx. kg/km Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

min mm

max mm

6/10 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 12/20kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 18/30 kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8 8 8 8 8 8 8 8 8 8

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

23 24 26 27 29 30 32 34 30 32 34 36 40 43 27 28 30 31 33 34 36 39 34 36 39 41 44 47 33 35 36 38 39 41 43 46 49 52

28 29 31 32 34 35 37 39 35 37 39 41 45 48 32 33 35 36 38 39 41 44 39 41 44 46 49 52 38 40 41 43 44 46 48 51 54 57

a 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

858 995 1225 1506 1761 2052 2427 3008 2136 2511 3092 3674 4598 5647 1023 1167 1409 1701 1881 2266 2652 3333 2350 2736 3333 3930 4872 5956 1394 1648 1952 2226 2622 3020 3635 4262 5242 6352

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

635 694 791 903 1003 1115 1257 1469 1199 1341 1553 1770 2169 2508 800 867 975 1098 1124 1329 1482 1793 1413 1566 1793 2026 2443 2818 1093 1214 1349 1469 1685 1850 2095 2359 2813 3213

ELKABEL

69

2XS2Y- TRIPLEX / N2XS2Y- TRIPLEX A2XS2Y- TRIPLEX / NA2XS2Y- TRIPLEX

Uo/U-6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES

Application
The three single-core cables with insulation of cross-linked polyethylene (XLPE) factory bindled in TRIPLEX, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PE compound type ST7 according to IEC 60502 type DMP2 according to VDE 0276 three single-core cables factory bindled in TRIPLEX black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Metal screen

max. 5 pC 15x D cable no less than - 20

Separating layer Sheath

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Factory bundled in TRIPLEX Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

70

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data
2XS2Y- TRIPLEX / N2XS2Y- TRIPLEX, A2XS2Y- TRIPLEX / NA2XS2Y- TRIPLEX 6/10; 12/20; 18/30 kV Nominal Number of conducThicThiccrosstors and nominal kness of kness of section of cross section insulation sheath screen N mm2 mm mm mm2 Cable diameter approx.
2XS2Y- TRIPLEX N2XS2Y- TRIPLE A2XS2Y- TRIPLEX NA2XS2Y- TRIPLEX

MIDDLE VOLTAGE POWER CABLES

min mm

max mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6/10 kV 3x(1x35rm /16) 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150rm /16) 3x(1x185rm /16) 3x(1x240rm /16) 3x(1x150 rm /25) 3x(1x185rm /25) 3x(1x240rm /25) 3x(1x300rm /25) 12/20 kV 3x(1x35rm /16) 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150rm /16) 3x(1x185rm /16) 3x(1x240rm /16) 3x(1x150 rm /25) 3x(1x185rm /25) 3x(1x240rm /25) 18/30 kV 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150 rm /25) 3x(1x185rm /25)

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 16 16 16 16 16 16* 16* 16* 25 25 25 16 16 16 16 25 25

49.6 51.8 56.2 58.3 62.6 64.8 69.1 73.4 64.8 69.1 73.4 77.8 58.3 60.5 64.8 67.0 71.3 73.4 77.8 84.2 73.4 77.8 84.2 71.3 75.6 77.8 82.1 84.2 88.6

60.5 62.6 67.0 69.1 73.4 75.6 79.9 84.2 75.6 79.9 84.2 88.6 69.1 71.3 75.6 77.8 82.1 84.2 88.6 95.0 84.2 88.6 95.0 82.1 86.4 88.6 92.9 95.0 99.4

1479 1812 2379 3099 3765 4521 5526 7095 4788 5790 7362 8940 1479 1812 2379 3099 3765 4521 5526 7095 4788 5790 7362 1812 2379 3099 3765 4788 5790

2574 2985 3675 4518 5283 6156 7281 9024 6408 7533 9276 11022 3069 3501 4227 5103 5643 6798 7956 9999 7050 8208 9999 4182 4944 5856 6678 7866 9060

282 381 549 762 963 1182 1485 1947 1182 1485 1947 2436 282 381 549 762 963 1182 1485 1947 1182 1485 1947 381 549 762 963 1182 1485

528 528 528 528 528 528 528 528 795 795 795 795 528 528 528 528 528 528 528 528 795 795 795 528 528 528 528 795 795

1905 2082 2373 2709 3009 3345 3771 4407 3597 4023 4659 5310 2400 2601 2925 3294 3372 3987 4446 5379 4239 4698 5379 3279 3642 4047 4407 5055 5550

ELKABEL

71

2XS(F)2Y/ N2XS(F)2Y A2XS(F)2Y/ NA2XS(F)2Y

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen According to IEC 60502-2 DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulating tape -II option - water absorbing powder and a layer of plastic tape PE compound type ST7 according to IEC 60502 type DMP 2 according to VDE 0276 Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV max. 5 pC 15x D cable no less than - 20 -30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Water resisting element

Sheath

Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

72

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data 2XS(F)2Y/N2XS(F)2Y, A2XS(F)2Y/NA2XS(F)2Y 6/10; 12/20; 18/30 kV


2XS(F)2Y, N2XS(F)2Y Number of conNominal Cable diameter ThicThicductors and approx. kness of kness of cross secnominal cross insulation sheath tion of section screen max min N mm2 mm mm mm2 mm mm Mass of Cu approx. kg/km Mass of cable approx. kg/km A2XS(F)2Y, NA2XS(F)2Y Mass of Al approx. kg/km Mass of Cu approx. Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

kg/km

6/10 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 12/20 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 18/30 kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8 8 8 8 8 8 8 8 8 8

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

23 24 26 27 29 30 32 34 30 32 34 36 40 43 27 28 30 31 33 34 36 39 34 36 39 41 44 47 33 35 36 38 39 41 43 46 49 52

28 29 31 32 34 35 37 39 35 37 39 41 45 48 32 33 35 36 38 39 41 44 39 41 44 46 49 52 38 40 41 43 44 46 48 51 54 57

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

906 1043 1279 1564 1822 2116 2495 3081 2200 2579 3165 3752 4683 5738 1081 1228 1473 1768 1952 2340 2730 3416 2424 2814 3416 4018 4966 6073 1465 1722 2030 2308 2707 3109 3728 4361 5347 6482

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

683 745 846 961 1064 1180 1325 1542 1264 1409 1626 1849 2254 2599 858 927 1039 1165 1194 1403 1560 1876 1487 1644 1876 2114 2537 2919 1164 1289 1427 1550 1770 1939 2189 2458 2918 3343

ELKABEL

73

2XS(F)2Y-TRIPLEX / N2XS(F)2Y -TRIPLEX A2XS(F)2Y-TRIPLEX / NA2XS(F)2Y-TRIPLEX

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES

Application
The three single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements, factory bindled in TRIPLEX, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors According to IEC 60502-2 DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulating tape -II option - water absorbing powder and a layer of plastic tape PE compound type ST7 according to IEC 60502 type DMP 2 according to VDE 0276 Black three single-core cables factory bindled in TRIPLEX

Technical data
Conductor resistance at According to IEC60228 class 2 20C and VDE 0295 class 2 Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10; 12/20; 18/30 kV 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV 6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV max. 5 pC / 2 pC 15x D cable no less than - 20

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element

Sheath

Temperature of exploitation -30 to 50 Tests according to IEC 60502-2 or DIN VDE 0276-620 Force of strain in laying N Al cores - 30*n*S core Cu cores - 50*n*S core max. N is number of cores and S is cross section of cores in Tests - water penetration in mm the region of metallic IEC 60502-2 annex F screen where:

Color Factory bundled in TRIPLEX

74

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

MIDDLE VOLTAGE POWER CABLES

Construction data 2XS(F)2Y- TRIPLEX / N2XS(F)2Y- TRIPLEX, A2XS(F)2Y- TRIPLEX / NA2XS(F)2Y- TRIPLEX Uo/U 6/10; 12/20; 18/30 kV
2XS(F)2Y- TRIPLEX N2XS(F)2Y- TRIPLEX A2XS(F)2Y- TRIPLEX NA2XS(F)2Y- TRIPLEX

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6/10 kV 3x(1x35rm /16) 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150rm /16) 3x(1x185rm /16) 3x(1x240rm /16) 3x(1x150 rm /25) 3x(1x185rm /25) 3x(1x240rm /25) 3x(1x300rm /25) 12/20 kV 3x(1x35rm /16) 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150rm /16) 3x(1x185rm /16) 3x(1x240rm /16) 3x(1x150 rm /25) 3x(1x185rm /25) 3x(1x240rm /25) 18/30 kV 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150 rm /25) 3x(1x185rm /25)

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 16 16 16 16 16 16* 16* 16* 25 25 25 16 16 16 16 25 25

49.7 51.8 56.2 58.3 62.6 64.8 69.1 73.4 64.8 69.1 73.4 77.8 58.3 60.5 64.8 66.9 71.3 73.4 77.8 84.2 73.4 77.8 84.2 71.3 75.6 77.8 82.1 84.3 88.6

60.5 62.6 67.0 69.2 73.4 75.6 79.9 84.3 75.6 79.9 84.2 88.6 69.2 71.3 75.6 77.8 82.2 84.3 88.6 95.1 84.3 88.6 95.1 82.1 86.4 88.6 92.9 95.1 99.4

1479 1812 2379 3099 3765 4521 5526 7095 4788 5790 7362 8940 1479 1812 2379 3099 3765 4521 5526 7095 4788 5790 7362 1812 2379 3099 3765 4788 5790

2718 3129 3837 4692 5466 6348 7485 9243 6600 7737 9495 11256 3243 3684 4419 5304 5856 7020 8190 10248 7272 8442 10248 4395 5166 6090 6924 8121 9327

282 381 549 762 963 1182 1485 1947 1182 1485 1947 2436 282 381 549 762 963 1182 1485 1947 1182 1485 1947 381 549 762 963 1182 1485

528 528 528 528 528 528 528 528 795 795 795 795 528 528 528 528 528 528 528 528 795 795 795 528 528 528 528 795 795

2049 2235 2538 2883 3192 3540 3975 4626 3792 4227 4878 5547 2574 2781 3117 3495 3582 4209 4680 5628 4461 4932 5628 3492 3867 4281 4650 5310 5817

ELKABEL

75

2XS(FL)2Y / N2XS(FL)2Y A2XS(FL)2Y / NA2XS(FL)2Y

Uo/U - 6/10 kV, 12/20, 18/30kV, IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors According to IEC 60502-2 DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. - water absorbing powder Al foil with copolymer protection from moisture ingress layer type ST7 according to IEC 60502-2 type DMP 2 according to VDE 0276 Black

Technical data
Conductor resistance at According to IEC60228 class 2 20C and VDE 0295 class 2 Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10; 12/20; 18/30 kV 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV 6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV max. 5 pC / 2 pC 15x D cable no less than - 20

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element Radial Sheath PE compound Color

-30 to 50 Temperature of exploitation according to IEC 60502-2 or Tests DIN VDE 0276620 Force of strain in laying N Al cores - 30*n*S core Cu cores - 50*n*S core max. N is number of cores and S is cross section of cores in Tests - water penetration in mm the region of metallic screen IEC 60502-2 annex F where:

76

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Al foil PE sheath

Construction data 2XS(FL)2Y / N2XS(FL)2Y, A2XS(FL)2Y / NA2XS(FL)2Y 6/10; 12/20; 18/30 kV


2XS(FL)2Y, N2XS(FL)2Y A2XS(FL)2Y, NA2XS(FL)2Y

MIDDLE VOLTAGE POWER CABLES

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N x mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6/10 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 12/20 kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 18/30 kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8 8 8 8 8 8 8 8 8 8

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

23 24 26 27 29 30 32 34 30 32 34 36 40 43 27 28 30 31 33 34 36 39 34 36 39 41 44 47 33 35 36 38 39 41 43 46 49 52

28 29 31 32 34 35 37 39 35 37 39 41 45 48 32 33 35 36 38 39 41 44 39 41 44 46 49 52 38 40 41 43 44 46 48 51 54 57

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

906 1043 1279 1564 1822 2116 2495 3081 2200 2579 3165 3752 4683 5738 1081 1228 1473 1768 1952 2340 2730 3416 2424 2814 3416 4018 4966 6073 1465 1722 2030 2308 2707 3109 3728 4361 5347 6482

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

683 745 846 961 1064 1180 1325 1542 1264 1409 1626 1849 2254 2599 858 927 1039 1165 1194 1403 1560 1876 1487 1644 1876 2114 2537 2919 1164 1289 1427 1550 1770 1939 2189 2458 2918 3343

ELKABEL

77

2XS(FL)2Y- TRIPLEX / N2XS(FL)2Y- TRIPLEX A2XS(FL)2Y - TRIPLEX / NA2XS(FL)2Y- TRIPLEX

Uo/U - 6/10 kV, 12/20, 18/30kV, IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES

Application
The three single-core cables with insulation of cross-linked polyethylene (XLPE) factory bindled in TRIPLEX, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors According to IEC 60502-2 DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. - water absorbing powder Al foil with copolymer moisture ingress layer PE compound type ST7 according to IEC 60502-2 type DMP 2 according to VDE 0276 Black three single-core cables factory bindled in TRIPLEX

Technical data
Conductor resistance at According to IEC60228 class 2 20C and VDE 0295 class 2 Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10; 12/20; 18/30 kV 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV 6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV max. 5 pC / 2 pC 15x D cable no less than - 20

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element Radial protection from Sheath

-30 to 50 Temperature of exploitation according to IEC 60502-2 or Tests DIN VDE 0276620 Force of strain in laying N Al cores - 30*n*S core Cu cores - 50*n*S core max. where: Tests - water penetration in the region of metallic screen N is number of cores and S is cross section of cores in mm IEC 60502-2 annex F

Color Factory bundled in TRIPLEX

78

ELKABEL

Cu or Al conductors XLPE insulation Cu screen Al foil PE sheath

Construction data 2XS(FL)2Y- TRIPLEX / N2XS(FL)2Y- TRIPLEX, A2XS(FL)2Y- TRIPLEX / NA2XS(FL)2Y- TRIPLEX Uo/U 6/10; 12/20; 18/30 kV
2XS(FL)2Y- TRIPLEX N2XS(FL)2Y- TRIPLEX A2XS(FL)2Y- TRIPLEX NA2XS(FL)2Y- TRIPLEX

MIDDLE VOLTAGE POWER CABLES

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6/10 kV 3x(1x35rm /16) 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150rm /16) 3x(1x185rm /16) 3x(1x240rm /16) 3x(1x150 rm /25) 3x(1x185rm /25) 3x(1x240rm /25) 3x(1x300rm /25) 12/20 kV 3x(1x35rm /16) 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150rm /16) 3x(1x185rm /16) 3x(1x240rm /16) 3x(1x150 rm /25) 3x(1x185rm /25) 3x(1x240rm /25) 18/30 kV 3x(1x50rm /16) 3x(1x70rm /16) 3x(1x95rm /16) 3x(1x120rm /16) 3x(1x150 rm /25) 3x(1x185rm /25)

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0 8,0

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5

16 16 16 16 16 16* 16* 16* 25 25 25 25 16 16 16 16 16 16* 16* 16* 25 25 25 16 16 16 16 25 25

49.7 51.8 56.2 58.3 62.6 64.8 69.1 73.4 64.8 69.1 73.4 77.8 58.3 60.5 64.8 66.9 71.3 73.4 77.8 84.2 73.4 77.8 84.2 71.3 75.6 77.8 82.1 84.3 88.6

60.5 62.6 67.0 69.2 73.4 75.6 79.9 84.3 75.6 79.9 84.2 88.6 69.2 71.3 75.6 77.8 82.2 84.3 88.6 95.1 84.3 88.6 95.1 82.1 86.4 88.6 92.9 95.1 99.4

1479 1812 2379 3099 3765 4521 5526 7095 4788 5790 7362 8940 1479 1812 2379 3099 3765 4521 5526 7095 4788 5790 7362 1812 2379 3099 3765 4788 5790

2718 3129 3837 4692 5466 6348 7485 9243 6600 7737 9495 11256 3243 3684 4419 5304 5856 7020 8190 10248 7272 8442 10248 4395 5166 6090 6924 8121 9327

282 381 549 762 963 1182 1485 1947 1182 1485 1947 2436 282 381 549 762 963 1182 1485 1947 1182 1485 1947 381 549 762 963 1182 1485

528 528 528 528 528 528 528 528 795 795 795 795 528 528 528 528 528 528 528 528 795 795 795 528 528 528 528 795 795

2049 2235 2538 2883 3192 3540 3975 4626 3792 4227 4878 5547 2574 2781 3117 3495 3582 4209 4680 5628 4461 4932 5628 3492 3867 4281 4650 5310 5817

ELKABEL

79

2XSY/ N2XSY A2XSY/ NA2XSY

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase Three insulated and screenesd phases are twisted with fillings and tape support PVC compound PVC compound type ST2 according to IEC 60502 type DMV 6 according to VDE 0276 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV max. 5 pC 15x D cable no less than - 20 -30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Inner semiconductive layer Insulation Outer semiconductive layer

Metal screen

Cable assembly

Inner sheatth Sheath

Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

80

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PVC sheath

Construction data 2XSEY/N2XSEY, A2XSEY/NA2XSEY 6/10; 12/20; 18/30 kV 2XSEY, N2XSEY


Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N x mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES - THREE CORE

A2XSY, NA2XSEY
Mass of Al approx. kg/km . kg/km

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 12/20kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 18/30 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8 8 8 8 8

2,5 2,5 2,7 2,8 2,9 3,0 3,2 3,4 3,5 2,8 2,9 3,0 3,1 3,2 3,4 3,5 3,7 3,3 3,4 3,5 3,7 3,8

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 25

46,4 48,8 53,0 57,1 60,3 64,2 68,5 74,3 79,6 56,7 59,3 63,3 67,4 70,6 74,7 78,8 84,5 71,7 75,8 79,8 83,3 87,1

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 1363 1968 2732 3440 4245

2907 3408 4279 5308 6195 7383 8741 10817 12906 3793 4345 5248 6331 7275 8566 9968 12155 5624 6610 7791 8819 10185

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 404 584 809 1023 1257

2231 2497 2965 3481 3899 4545 5195 6153 7138 3117 3434 3934 4504 4979 5728 6422 7491 4713 5296 5964 6523 7347

ELKABEL

81

2XS2Y / N2XS2Y A2XS2Y / NA2XS2Y

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase Three insulated and screenesd phases are twisted with fillings and tape support PVC compound PE compound type ST7 according to IEC 60502 type DMP 2 according to VDE 0276 Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Inner semiconductive layer Insulation Outer semiconductive layer

Metal screen

Cable assembly

max. 5 pC 15x D cable no less than - 20

Inner sheatth Sheath

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

82

ELKABEL

Cu / Al conductors XLPE insulation Cu screen P sheath

Construction data 2XSE2Y / N2XSE2Y, A2XSE2Y / NA2XSE2Y 6/10; 12/20; 18/30 kV 2XSE2Y, N2XSE2Y A2XS2Y, NA2XSE2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES - THREE CORE

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 3x300 rm /25 12/20kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 18/30 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0

2,5 2,5 2,7 2,8 2,9 3,0 3,2 3,4 3,5 2,8 2,9 3,0 3,1 3,2 3,4 3,5 3,7 3,3 3,4 3,5 3,7 3,8

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 25

46,4 48,8 53,0 57,1 60,3 64,2 68,5 74,3 79,6 56,7 59,3 63,3 67,4 70,6 74,7 78,8 84,5 71,7 75,8 79,8 83,3 87,1

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 1363 1968 2732 3440 4245

2849 3348 4208 5229 6108 7287 8632 10690 12766 3714 4259 5153 6226 7162 8439 9830 11998 5505 6480 7651 8665 10019

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 404 584 809 1023 1257

2174 2437 2894 3402 3812 4449 5086 6027 6999 3038 3349 3839 4399 4866 5601 6284 7334 4596 5167 5824 6369 7181

ELKABEL

83

2XS(F)2Y/ (N)2XS(F)2Y A2XS(F)2Y/ (N)A2XS(F)2Y

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Layer of semi-conductive water absorbing tapes - discret Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Layer of semi-conductive water absorbing tapes Three insulated and screened phases with longitudinal waterblocking element are twisted in three core cable Filling and inner sheath-PE - LDPE PE compound - HDPE Black

Water resisting element Cable assembly

max. 5 pC 15x D cable no less than - 20

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Inner sheatth Sheath Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

84

ELKABEL

Cu / Al conductors XLPE insulation Cu screen with WB element PE sheath

Construction data 2XSE(F)2Y / (N)2XSE(F)2Y, A2XSE(F)2Y / (N)A2XSE(F)2Y 6/10; 12/20; 18/30 kV


2XSE(F)2Y, (N)2XSE(F)2Y A2XS(F)2Y, (N)A2XSE(F)2Y

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of cable approx. kg/km

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 12/20kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 18/30 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0

2,5 2,6 2,7 2,9 3.0 3,1 3,2 3,4 2,8 2,9 3,0 3,1 3,2 3,4 3,5 3,7 3,3 3,4 3,5 3,7 3,8

16 16 16 16 16 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 25

48.5 51.0 55.5 59.0 62.5 65.5 70.5 75.5 58.0 60.0 64.5 68.5 71.5 75.0 79.0 85.0 72.0 76.0 80.0 83,5 87,0

1010 1360 1965 2730 3440 4245 5310 6980 1010 1360 1965 2730 3440 4245 5310 6980 1360 1965 2730 3440 4245

2715 3215 4095 5125 6045 7110 8740 10555 3160 3677 4550 5570 6475 7500 9150 10950 5124 6100 7120 8110 9185

295 405 585 805 1020 1255 1575 2070 295 405 585 805 1020 1255 1575 2070 405 585 805 1020 1255

2005 2260 2715 3220 3625 4445 5195 6065 2445 2750 3170 3650 4060 4550 5100 6020 3710 4295 5160 6120 7100

ELKABEL

85

2XS(FL)2Y/ (N)2XS(FL)2Y A2XS(FL)2Y/ (N)A2XS(FL)2Y

Uo/U - 6/10 kV, 12/20 kV IEC 60502-2 / DIN VDE 0276-620

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal and radial water-blocking elements, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to IEC 60502 and DIN VDE 0276-620 u and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes - discret Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Layer of semi-conductive water absorbing tapes Three insulated and screened phases with longitudinal waterblocking element are twisted in three core cable Filling - filiers with water-blocking element Layer of semi-conductive water absorbing tapes

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element Cable assembly

max. 5 pC 15x D cable no less than - 20 -30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Inner sheath Radial protection from moisture ingress Sheath Color

Al foil with copolymer layer PE compound - HDPE Black

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

86

ELKABEL

Cu or Al conductors XLPE insulation Cu screen with WB element Al foil PE sheath


Construction data 2XSE(FL)2Y / (N)2XSE(FL)2Y, A2XSE(FL)2Y / (N)A2XSE(FL)2Y 6/10; 12/20kV
2XSE(FL)2Y, (N)2XSE(FL)2Y
A2XS(FL)2Y, (N)A2XSE(FL)2Y

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Number of conductors Thickness Thickness Nominal Cable diameter approx. and nominal cross sec- of insulaof cross section tion sheath tion of screen N mm2 mm mm mm2 mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of cable approx. kg/km

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 12/20kV 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5

2,6 2,7 2,8 2,9 3.0 3,2 3,3 3,4 3,0 3,2 3,3 3,4 3,5 3,7

16 16 16 16 16 25 25 25 16 16 16 25 25 25

49.4 52.0 56.5 59.8 63.1 67.6 70.2 75.5 64.5 68.3 71,6 74,8 78,8 84.3

1010 1363 1968 2730 3440 4245 5310 6980 1965 2730 3440 4245 5310 6980

2997 3508 4379 5210 6050 7508 8300 10363 4270 5280 6395 7190 8540 10600

298 404 584 805 1020 1255 1575 2070 585 810 1020 1255 1575 2070

2321 2597 3065 3285 3630 4070 4555 5453 2890 3365 3985 4195 4810 5670

ELKABEL

87

2XSY A2XSY
MIDDLE VOLTAGE POWER CABLES

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer According to IEC 60502 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PVC compound type ST2 according to IEC 60502 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV max. 5 pC 15x D cable no less than - 20 -30 to 50

Metal screen

Separating layer Sheath Color

according to IEC 60502-2 or Tests DIN VDE 0276-620 Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

88

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PVC sheath

Construction data 2XSY, A2XSY 3.6/6; 8.7/15; 20/35 kV


Number of con- Thickness Thickness Nominal Cable crossductors and nom- of insulaof section of diameter inal cross section tion sheath approx. screen N mm2 mm mm mm2 mm 2XSY Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. A2XSY Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

kg/km

3,6/6 kV 1x35rm /16 1x50rm /16 1x70rm /16 1x95rm /16 1x120rm /16 1x150rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 8,7/15 kV 1x35rm /16 1x50rm /16 1x70rm /16 1x95rm /16 1x120rm /16 1x150rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 20/35 kV 1x50rm /16 1x70rm /16 1x95rm /16 1x120rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,5 2,5 2,6 2,8 3,0 3,2 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8

1,8 1,8 1,8 1,8 1,8 1,9 1,9 2,0 1,9 1,9 2,0 2,1 2,2 2,4 1,8 1,8 1,8 1,9 2,0 2,0 2,1 2,2 2,0 2,1 2,2 2,2 2,3 2,5 2,1 2,1 2,2 2,3 2,3 2,4 2,5 2,5 2,6 2,8

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

21,0 22,1 23,8 25,5 26,9 28,6 30,3 33,1 28,6 30,3 33,1 36,0 39,9 43,9 25,0 26,1 27,8 29,7 31,3 32,8 34,7 37,3 32,8 34,7 37,3 39,6 43,06 46,66 35,3 37,0 38,9 40,5 42,0 43,9 46,5 48,8 52,3 55,9

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

804 939 1166 1443 1696 1996 2368 2969 2080 2452 3053 3670 4635 5750 942 1083 1320 1619 1894 2192 2590 3199 2276 2674 3283 3877 4836 5943 1516 1776 2103 2401 2803 3229 3874 4501 5503 6662

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

581 638 732 840 938 1059 1198 1430 1143 1282 1514 1766 2206 2611 719 782 886 1016 1136 1255 1419 1660 1339 1503 1743 1973 2407 2803 1215 1342 1500 1643 1867 2058 2335 2597 3074 3523

ELKABEL

89

2XS2Y A2XS2Y
MIDDLE VOLTAGE POWER CABLES

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer According to IEC 60502 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PE compound type ST7 according to IEC 60502 black

Technical data
Conductor resistance at According to BDS904 20C (IEC60228) class 2 Operating temperature 90 continuous operation Overload temperature 130 /100h per year max./ Short circuit temperature 250 /5 s max./ 6/10;12/20 kV Nominal voltage Uo/U: Highest system voltage 6/10; 12/20 kV Uo/U, no more than 12kV; 24kV kV Test voltage Uo/U 6/10; 12/20 kV AC () - 5 min 15kV; 30kV kV DC (=) - 15 min 48kV; 96kV kV Level of partial discharge at 2*Uo max. 5 pC Bending radius, min 15x D cable Temperature of laying Temperature of exploitation no less than - 20

Metal screen

Separating layer Sheath Color

-30 to 50 according to IEC 60502-2 or Tests DIN VDE 0276-620 Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

90

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data 2XS2Y, A2XS2Y 3.6/6; 7.5/15; 20/35 kV


2XS2Y Nominal Cable Number of ThicThicdiameconductors and kness of kness of crosster Mass of Mass of nominal cross insulation sheath section of Cu cable screen approx. section approx. approx. A2XS2Y

MIDDLE VOLTAGE POWER CABLES

Mass of Al approx. kg/km

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

N mm2

mm

mm

mm2

mm

kg/km

kg/km

3,6/6 kV 1x35rm /16 1x50rm /16 1x70rm /16 1x95rm /16 1x120rm /16 1x150rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 8,7/15kV 1x35rm /16 1x50rm /16 1x70rm /16 1x95rm /16 1x120rm /16 1x150rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 20/35 kV 1x50rm /16 1x70rm /16 1x95rm /16 1x120rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,5 2,5 2,6 2,8 3,0 3,2 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8

1,8 1,8 1,8 1,8 1,8 1,9 1,9 2,0 1,9 1,9 2,0 2,1 2,2 2,4 1,8 1,8 1,8 1,9 2,0 2,0 2,1 2,2 2,0 2,1 2,2 2,2 2,3 2,5 2,1 2,1 2,2 2,3 2,3 2,4 2,5 2,5 2,6 2,8

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

21,0 22,1 23,8 25,5 26,9 28,6 30,3 33,1 28,6 30,3 33,1 36,0 39,9 43,9 25,0 26,1 27,8 29,7 31,3 32,8 34,7 37,3 32,8 34,7 37,3 39,6 43,1 46,7 35,3 37,0 38,9 40,5 42,0 43,9 46,5 48,8 52,3 55,9

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

754 886 1108 1381 1630 1922 2290 2879 2006 2374 2963 3567 4517 5609 881 1019 1251 1543 1809 2103 2491 3088 2187 2575 3172 3760 4703 5787 1416 1671 1987 2276 2673 3087 3719 4337 5321 6453

94 127 183 254 321 394 495 649 394 495 694 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

531 586 674 778 872 985 1120 1340 1069 1203 1424 1664 2088 2470 658 718 818 940 1052 1166 1321 1549 1250 1405 1633 1856 2274 2649 1115 1237 1384 1518 1737 1917 2180 2433 2892 3315

ELKABEL

91

2XS(F)2Y A2XS(F)2Y
MIDDLE VOLTAGE POWER CABLES

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen According to IEC 60502-2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulat ing tape -II option - water absorbing powder and a layer of plastic tape PE compound type ST7 according to IEC 60502 Black

Technical data
Conductor resistance at According to BDS904 20C (IEC60228) class 2 Operating temperature 90 continuous operation Overload temperature 130 /100h per year max./ Short circuit temperature 250 /5 s max./ Nominal voltage Uo/U: 6/10;12/20 kV Highest system voltage 6/10; 12/20 kV Uo/U, no more than 12kV; 24kV kV Test voltage Uo/U 6/10; 12/20 kV AC () - 5 min 15kV; 30kV kV DC (=) - 15 min 48kV; 96kV kV Level of partial discharge at 2*Uo max. 5 pC Bending radius, min 15x D cable Temperature of laying Temperature of exploitation no less than - 20

Water resisting element

Sheath Color

-30 to 50 according to IEC 60502-2 or Tests DIN VDE 0276-620 Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

92

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data2XS(F)2Y, A2XS(F)2Y 3.6/6; 8.7/15; 20/35 kV


Cable Nominal Number of con- Thickness Thickness cross sec- diameter ductors and nom- of insulaof approx. tion of inal cross section tion sheath screen N mm2 mm mm mm2 mm 2XS(F)2Y Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km A2XS(F)2Y Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

3,6/6 kV 1x35 rm /16 1x50 rm /16 1x70 rm /16 1x95 rm /16 1x120 rm /16 1x150 rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 8,7/15kV 1x35 rm /16 1x50 rm /16 1x70 rm /16 1x95 rm /16 1x120 rm /16 1x150 rm /16 1x185rm /16 1240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 20/35 kV 1x50 rm /16 1x70 rm /16 1x95 rm /16 1x120 rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,5 2,5 2,6 2,8 3,0 3,2 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8

1,8 1,8 1,8 1,8 1,8 1,9 1,9 2,0 1,9 1,9 2,0 2,1 2,2 2,4 1,8 1,8 1,8 1,9 2,0 2,0 2,1 2,2 2,0 2,1 2,2 2,2 2,3 2,5 2,1 2,1 2,2 2,3 2,3 2,4 2,5 2,5 2,6 2,8

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

22,2 23,3 25,0 26,7 28,3 29,8 31,7 34,5 29,8 31,7 34,5 37,4 41,3 45,1 26,2 27,3 29,2 30,9 32,5 34,2 35,9 38,5 34,2 35,9 38,5 41,0 44,5 47,9 36,5 38,4 40,1 41,7 43,4 45,1 47,7 50,2 53,7 57,1

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

796 930 1156 1432 1693 1980 2361 2958 2064 2445 3041 3653 4610 5699 931 1072 1317 1603 1873 2180 2563 3165 2264 2647 3249 3854 4804 5883 1488 1758 2068 2359 2773 3178 3815 4453 5445 6569

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

572 629 722 829 935 1044 1191 1418 1128 1275 1502 1749 2181 2560 708 771 883 1000 1116 1244 1392 1626 1328 1476 1710 1950 2375 2744 1188 1325 1465 1602 1836 2008 2276 2550 3016 3430

ELKABEL

93

2XS(FL)2Y A2XS(FL)2Y
MIDDLE VOLTAGE POWER CABLES

Uo/U - 3.6/6 kV, 8.7/15, 20/35 kV IEC 60502-2

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 8.7/15; 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen According to IEC 60502-2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. - water absorbing powder

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying According to IEC60228 class 2 and VDE 0295 class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10; 12/20; 18/30 kV 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV 6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV max. 5 pC / 2 pC 15x D cable no less than - 20

Water resisting element Radial protection from moisture ingress

Al foil with copolymer layer

-30 to 50 Temperature of exploitation according to IEC 60502-2 or Tests DIN VDE 0276620 Force of strain in laying N Al cores - 30*n*S core Cu cores - 50*n*S core max. N is number of cores and S is cross section of cores in Tests - water penetration in mm the region of metallic screen IEC 60502-2 annex F where:

Sheath

PE compound type ST7 according to IEC 60502-2 Black

Color

94

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Al foil PE sheath Construction data 2XS(FL)2Y, A2XS(FL)2Y 3.6/6; 8.7/15; 20/35 kV
2XS(FL)2Y Nominal Number of con- Thickness Thickness cross sec- Cable ductors and nom- of insulaof diameter tion of inal cross section tion sheath approx. screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km A2XS(FL)2Y Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

3,6/6 kV 1x35 rm /16 1x50 rm /16 1x70 rm /16 1x95 rm /16 1x120 rm /16 1x150 rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 8,7/15kV 1x35 rm /16 1x50 rm /16 1x70 rm /16 1x95 rm /16 1x120 rm /16 1x150 rm /16 1x185rm /16 1x240rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35 20/35 kV 1x50 rm /16 1x70 rm /16 1x95 rm /16 1x120 rm /16 1x150rm /25 1x185rm /25 1x240rm /25 1x300rm /25 1x400rm /35 1x500rm /35

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,5 2,5 2,6 2,8 3,0 3,2 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8 8,8

1,8 1,8 1,8 1,8 1,8 1,9 1,9 2,0 1,9 1,9 2,0 2,1 2,2 2,4 1,8 1,8 1,8 1,9 2,0 2,0 2,1 2,2 2,0 2,1 2,2 2,2 2,3 2,5 2,1 2,1 2,2 2,3 2,3 2,4 2,5 2,5 2,6 2,8

16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35

22,2 23,3 25,0 26,7 28,3 29,8 31,7 34,5 29,8 31,7 34,5 37,4 41,3 45,1 26,2 27,3 29,2 30,9 32,5 34,2 35,9 38,5 34,2 35,9 38,5 41,0 44,5 47,9 36,5 38,4 40,1 41,7 43,4 45,1 47,7 50,2 53,7 57,1

493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1507 1842 2365 1596 1930 2454 2980 3836 4807 604 793 1033 1255 1596 1930 2454 2980 3836 4807

796 930 1156 1432 1693 1980 2361 2958 2064 2445 3041 3653 4610 5699 931 1072 1317 1603 1873 2180 2563 3165 2264 2647 3249 3854 4804 5883 1488 1758 2068 2359 2773 3178 3815 4453 5445 6569

94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 394 495 649 812 1043 1374 127 183 254 321 394 495 649 812 1043 1374

176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363

572 629 722 829 935 1044 1191 1418 1128 1275 1502 1749 2181 2560 708 771 883 1000 1116 1244 1392 1626 1328 1476 1710 1950 2375 2744 1188 1325 1465 1602 1836 2008 2276 2550 3016 3430

ELKABEL

95

2XSY A2XSY
MIDDLE VOLTAGE POWER CABLES - THREE CORE

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer According to IEC 60502 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase Three insulated and screenesd phases are twisted with fillings and tape support PVC compound PVC compound type ST2 according to IEC 60502 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Metal screen

Cable assembly

Inner sheath Sheath Color

max. 5 pC 15x D cable no less than - 20

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

96

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PVC sheath


Construction data 2XSEY, A2XSEY 3.6/6; 8.7/15; 20/35 kV 2XSEY
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N x mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES - THREE CORE

A2XSEY
Mass of Al approx. kg/km Mass of cable approx. kg/km

3,6/6 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 8,7/15 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 20/35 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,8 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8

2,5 2,5 2,5 2,7 2,8 2,9 3,0 3,2 3,4 2,6 2,7 2,8 3,0 3,1 3,2 3,4 3,5 3,7 3,4 3,5 3,7 3,8 3,9

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 25 16 16 16 16 25

46,2 48,8 53,0 57,1 60,3 64,2 68,5 74,3 79,6 56,5 59,3 63,3 67,2 70,6 74,7 78,6 84,3 79,6 75,6 79,6 83,7 87,1 91,0

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 8661 1363 1968 2732 3440 4245

2609 3079 3904 4914 5784 6943 8268 10332 12497 3365 3883 4760 5844 6751 7978 9386 11502 13631 6077 7083 8284 9343 10724

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 2589 404 584 809 1023 1257

1933 2168 2590 3087 3488 4105 4722 5668 6729 2689 2972 3446 4017 4456 5140 5840 6838 7863 5166 5769 6456 7054 7885

ELKABEL

97

2XS2Y A2XS2Y
MIDDLE VOLTAGE POWER CABLES - THREE CORE

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer According to IEC 60502 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase Three insulated and screenesd phases are twisted with fillings and tape support PVC compound P compound type ST7 according to IEC 60502 Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Metal screen

Cable assembly

Inner sheath Sheath Color

max. 5 pC 15x D cable no less than - 20

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

98

ELKABEL

Cu / Al conductors XLPE insulation Cu screen P sheath


Construction data 2XSE2Y, A2XSE2Y 3.6/6; 8.7/15; 20/35 kV 2XSE2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES - THREE CORE

A2XSE2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

3,6/6 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 3x300 rm /25 8,7/15 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 3x300 rm /25 20/35 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,8 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8

2,5 2,5 2,5 2,7 2,8 2,9 3,0 3,2 3,4 2,6 2,7 2,8 3,0 3,1 3,2 3,4 3,5 3,7 3,4 3,5 3,7 3,8 3,9

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 25 16 16 16 16 25

46,2 48,8 53,0 57,1 60,3 64,2 68,5 74,3 79,6 56,5 59,3 63,3 67,2 70,6 74,7 78,6 84,3 79,6 75,6 79,6 83,7 87,1 91,0

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 8661 1363 1968 2732 3440 4245

2552 3019 3838 4837 5699 6849 8165 10213 12361 3289 3803 4672 5743 6642 7858 9252 11354 13464 5948 6943 8129 9177 10546

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 2589 404 584 809 1023 1257

1876 2108 2524 3010 3404 4012 4619 5549 6593 2613 2892 3358 3916 4347 5020 5706 6690 7697 5038 5629 6301 6888 7708

ELKABEL

99

2XS(F)2Y A2XS(F)2Y
MIDDLE VOLTAGE POWER CABLES - THREE CORE

Uo/U - 3.6/6 kV, 8.7/15kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen According to IEC 60502 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes - discret Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Layer of semi-conductive water absorbing tapes Three insulated and screened phases with longitudinal waterblocking element are twisted in three core cable Filling and inner sheath-PE - LDPE PE compound - HDPE Black Tests

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Water resisting element Cable assembly

max. 5 pC 15x D cable no less than - 20

Inner sheath Sheath Color

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

100

ELKABEL

Cu / Al conductors XLPE insulation Cu screen with WB element PE sheath

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Construction data 2XSE(F)2Y, A2XSE(F)2Y 3.6/6; 8.7/15kV 2XSE(F)2Y


Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

A2XSE(F)2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

3,6/6 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 8,7/15 kV 3x120rm / 50 3x240 rm /50

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 4.5 4.5

2,5 2,5 2,6 2,7 2,8 2,9 3,1 3,3 3.1 3,6

16 16 16 16 16 25 25 25 50 50

44.2 46.9 51.0 54.9 68.2 61.4 65.3 71.8 69 82.5

1010 1360 1965 2730 3440 4245 5310 6980 3440 6980

2440 2950 3780 4785 5685 6725 8035 10165 6400 10765

295 405 585 805 1020 1255 1575 2070 1020 2070

1730 1970 2400 2865 3265 3740 4305 5255 3983 5850

ELKABEL

101

2XS(FL)2Y A2XS(FL)2Y
MIDDLE VOLTAGE POWER CABLES - THREE CORE

Uo/U - 20/35 kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal and radial water-blocking elements, are designed for transfer and distribution of electrical power with nominal voltage Uo/U20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen According to IEC 60502 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound

Technical data
Conductor resistance at 20C Operating temperature Overload temperature According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 20/35 kV 20/35 kV 42 kV 20/35 kV 70 kV 224 kV

semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes - discret Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Layer of semi-conductive water absorbing tapes Three insulated and screened phases with longitudinal waterblocking element are twisted in three core cable Filling - filiers with water-blocking element Layer of semi-conductive water absorbing tapes Short circuit temperature Nominal voltage Uo/U: Highest system voltage Um, no more than Test voltage Uo/U AC ( ) - 5 min DC ( ) - 15 min

Water resisting element Cable assembly

Inner sheath

Radial protection from Al foil with copolymer layer moisture ingress Sheath Color PE compound - HDPE Black

Level of partial discharge at 2*Uo Bending radius, min Temperature of laying

max. 5 pC 15x D cable no less than -5

Temperature of exploitation Tests Force of strain in laying N max. where:

-30 to 500 according to IEC 60502 Al cores - 30*n*S core Cu cores - 50*n*S core n- number of cores andS-cross-section in mm

102

ELKABEL

Cu or Al conductors XLPE insulation Cu screen with WB element Al foil PE sheath


Construction data 2XSE(FL)2Y, A2XSE(FL)2Y 20/35 kV 2XSE(FL)2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES - THREE CORE

A2XSE(FL)2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

20/35 kV 3x70 rm /25 3x95 rm /25 3x120 rm /25 3x150rm /25 3x185 rm /35 3x185 rm /50 3x240 rm /25

8.8 8.8 8.8 8.8 8.8 8.8 8.8

3.5 3.7 3.8 3.9 4.0 4.0 4.2

25 25 25 25 35 50 25

49.7 83.6 87.2 90.1 94.0 94.0 79,6

1965 2730 3440 4245 5310 5310 6980

5665 6730 7530 8775 10195 10334 12285

585 810 1025 1255 1575 1575 2070

4285 4810 5295 5785 6465 6595 7375

ELKABEL

103

2XSEYBY A2XSEYBY
MIDDLE VOLTAGE POWER CABLES-THREE CORE

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen over each phase Metal screen Cable assembly according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound -I option - Cu tapes laid with over lap over each phase -II option - Cu wires laid concen trically Three insulated and screened phases are twisted with fillings and tape support PVC compound two steel tapes or two steel galvanized tapes PVC compound type ST2 according to IEC 60502 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Inner sheatth Armour Sheath Color

max. 5 pC 15x D cable no less than - 20

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

104

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Armour st. tapes PVC sheath


Construction data 2XSEYBY, A2XSEYBY 6.10; 12/20; 18/30 kV 2XSEYBY
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N x mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES-THREE CORE

A2XSEYBY
Mass of Al approx. . kg/km Mass of cable approx. kg/km

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 12/20 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 18/30 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 8,0 8,0 8,0 8,0 8,0

2,5 2,6 2,7 2,9 3,0 3,1 3,2 3,4 3,7 2,9 2,9 3,1 3,2 3,3 3,4 3,6 3,8 3,3 3,5 3,7 3,8 3,9

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 25

48,4 51,0 55,0 59,3 62,5 66,4 70,5 76,3 83,2 58,7 61,3 65,5 69,4 72,8 76,7 82,0 87,7 73,7 78,0 83,4 86,7 90,5

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 1363 1968 2732 3440 4245

3639 4203 5117 6239 7178 8433 9831 12001 15023 4717 5286 6281 7433 8430 9756 12065 14364 6765 7852 9914 10996 12462

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 404 584 809 1023 1257

2963 3292 3803 4412 4882 5595 6285 7337 9255 4041 4376 4967 5606 6134 6918 8519 9700 5854 6538 8086 8701 9623

ELKABEL

105

2XSEYB2Y A2XSEYB2Y
MIDDLE VOLTAGE POWER CABLES-THREE CORE

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U U 6/10kV; 12/20kV 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen over each phase Metal screen Cable assembly according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound -I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concen trically Three insulated and screened phases are twisted with fillings and tape support PVC compound two steel tapes or two steel galvanized tapes PE compound type ST7 according to IEC 60502 Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Inner sheatth Armour Sheath Color

max. 5 pC 15x D cable no less than - 20

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

106

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Armour st. tapes PE sheath


Construction data 2XSEYB2Y, A2XSEYB2Y 6/10; 12/20; 18/30 kV 2XSEYB2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES-THREE CORE

A2XSEYB2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 12/20 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25 3x240 rm /25 18/30 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120 rm /16 3x150rm /25 3x185 rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0 8.0

2,5 2,6 2,7 2,9 3,0 3,1 3,2 3,4 3,7 2.8 2.9 3.0 3,2 3,3 3,4 3,5 3,7 3.2 3.3 3.4 3,6 3,7 3,8 4.0

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 16 25 25

48,4 51,0 55,0 59,3 62,5 66,4 70,5 76,3 83,2 57.2 60.0 64.0 68.0 71.5 75.0 80.0 85.5 69.5 72.5 76.1 80.2 83.5 87.0 92.3

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 1010 1363 1968 2732 3440 4245 5311

3579 4137 5043 6153 7085 8330 9718 11871 14868 4149 4733 5668 6792 7800 8916 11123 13404 5583 6220 7226 8424 9497 10672 13075

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 298 404 584 809 1023 1257 1579

2903 3226 3729 4327 4782 5492 6172 7207 9101 3437 3773 4284 4869 5384 5928 7391 8494 4871 5261 5842 6501 7080 7684 9343

ELKABEL

107

2XSE(F)2YB2Y / 2XSE(F)2YBY A2XSE(F)2YB2Y/ A2XSE(F)2YBY

Uo/U - 6/10, 12/20 kV IEC 60502-2

MIDDLE VOLTAGE POWER CABLES-THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements ,are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 12/20kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen over each phase according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes - discret Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Layer of semi-conductive water absorbing tapes Three insulated and screened phases with longitudinal waterblocking element are twisted in three core cable Filling and inner sheath-PE - LDPE two steel tapes or two steel galvanized tapes For type 2Y- PE compound HDPE For type Y- PVC compound type ST2 according to IEC 60502 For type 2Y - black For type Y - red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Water resisting element Cable assembly

max. 5 pC 15x D cable no less than - 20

Inner sheatth / bedding / Armour Sheath

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

108

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Armour St. tapes PE orPVC sheat


Construction data 2XSE(F)2YB2Y, A2XSE(F)2YB2Y 6/10; 12/20kV 2XSE(F)2YB2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES-THREE CORE

A2XSE(F)2YB2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 3x240rm /25 12/20 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 3x240rm /25 6/10 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 3x240rm /25 12/20 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 3x240rm /25

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

2.7 2.7 2,9 2,9 3,1 3,2 3,4 3,6 2.9 3.0 3.1 3.3 3.4 3.5 3,6 3,8 2.7 2.7 2,9 2,9 3,1 3,2 3,4 3,6 2.9 3.0 3.1 3.3 3.4 3.5 3,6 3,8

16 16 16 16 25 25 25 25 16 16 16 16 25 25 25 25 16 16 16 16 25 25 25 25 16 16 16 16 25 25 25 25

53.0 55.5 59.5 62.5 67.0 70.5 74.5 80.0 61.0 63.5 67.0 71.0 75.0 78.0 82.0 87.5 53.0 55.5 59.5 62.5 67.0 70.5 74.5 80.0 61.0 63.5 67.0 71.0 75.0 78.0 82.0 87.5

1010 1360 1965 2730 3440 4245 5310 6980 1010 1360 1965 2730 3440 4245 5310 6980 1010 1360 1965 2730 3440 4245 5310 6980 1010 1360 1965 2730 3440 4245 5310 6980

3635 4190 5090 6100 7215 8330 9780 11995 4430 5040 5975 7125 8190 9330 10805 13070 3850 4425 5355 6380 7540 8685 10160 12435 4710 5330 6300 7480 8580 9750 11260 13575

295 405 585 805 1020 1255 1575 2070 295 405 585 805 1020 1255 1575 2070 295 405 585 805 1020 1255 1575 2070 295 405 585 805 1020 1255 1575 2070

2920 3240 3710 4175 4800 5340 6040 7085 3720 4085 4595 5195 5770 6340 7070 8160 3135 3470 3975 4455 5120 5690 6425 7525 3995 4375 4920 5555 6160 6760 7525 8670

ELKABEL

109

2XSEYBY A2XSEYBY
MIDDLE VOLTAGE POWER CABLES-THREE CORE

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen over each phase Metal screen Cable assembly according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound -I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concen trically Three insulated and screened phases are twisted with fillings and tape support PVC compound two steel tapes or two steel galvanized tapes PVC compound type ST2 according to IEC 60502 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV max. 5 pC 15x D cable no less than - 20 -30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Inner sheatth Armour Sheath Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

110

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Armour st. tapes PVC sheath


Construction data 2XSEYBY, A2XSEYBY 3.6/6; 8.7/15; 20/35 kV 2XSEYBY
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N x mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES-THREE CORE

A2XSEYBY
Mass of Al approx. kg/km Mass of cable approx. kg/km

3,6/6 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 8,7/15 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 20/35 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,8 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8

2,5 2,5 2,6 2,7 2,8 3,0 3,1 3,3 3,5 2,7 2,8 2,9 3,1 3,2 3,3 3,4 3,7 3,5 3,6 3,8 3,9 4,0

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 25

44,3 46,7 50,8 54,8 58,3 62,1 66,2 72,4 78,8 54,0 56,5 60,6 64,9 68,1 72,0 76,0 83,2 77,8 81,8 87,1 90,5 94,4

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 1363 1968 2732 3440 4245

3270 3782 4696 5749 6716 7920 9314 11481 13751 4210 4767 5714 6867 7827 9121 10562 13620 7316 8388 10471 11626 13106

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 404 584 809 1023 1257

2594 2871 3382 39218 4420 5081 5768 6817 7983 3534 3856 4400 5040 5532 6283 7016 8956 6405 7073 8644 9331 10268

ELKABEL

111

2XSEYB2Y A2XSEYB2Y
MIDDLE VOLTAGE POWER CABLES-THREE CORE

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen over each phase Metal screen Cable assembly according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound -I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concen trically Three insulated and screened phases are twisted with fillings and tape support PVC compound two steel tapes or two steel galvanized tapes PE compound type ST7 according to IEC 60502 Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV max. 5 pC 15x D cable no less than - 20 -30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Inner sheatth Armour Sheath Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

112

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Armour st. tapes PE sheath


Construction data 2SEYB2Y, A2XSEYB2Y 3.6/6; 8.7/15; 20/35 kV 2XSEYB2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES-THREE CORE

A2XSEYB2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

3,6/6 kV 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 3x300rm /25 8,7/15 Kv 3x35 rm /16 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25 3x185rm /25 3x240rm /25 20/30 kV 3x50 rm /16 3x70 rm /16 3x95 rm /16 3x120rm /16 3x150rm /25

2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,6 2,8 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 8,8 8,8 8,8 8,8 8,8

2,5 2,5 2,6 2,7 2,8 3,0 3,1 3,3 3,5 2,7 2,8 2,9 3,1 3,2 3,3 3,4 3,7 3,5 3,6 3,8 3,9 4,0

16 16 16 16 16 25 25 25 25 16 16 16 16 16 25 25 25 16 16 16 16 25

44,3 46,7 50,8 54,8 58,3 62,1 66,2 72,4 78,8 54,0 56,5 60,6 64,9 68,1 72,0 76,0 83,2 77,8 81,8 87,1 90,5 94,4

1010 1363 1968 2732 3440 4245 5311 6981 8661 1010 1363 1968 2732 3440 4245 5311 6981 1363 1968 2732 3440 4245

3215 3724 4630 5675 6635 7827 9211 11361 13612 4137 4688 5626 6766 7718 9002 10432 13465 7179 8240 10304 11448 12916

298 404 584 809 1023 1257 1579 2071 2589 298 404 584 809 1023 1257 1579 2071 404 584 809 1023 1257

2539 2813 3316 3854 4338 4987 5665 6697 7845 3461 3777 4312 4939 5423 6164 6886 8802 6268 6925 8478 9153 10078

ELKABEL

113

2XSE(F)2YB2Y/ 2XSE(F)2YBY A2XSE(F)2YB2Y/ A2XSE(F)2YBY

Uo/U - 3.6/6, 8.7/15 kV IEC 60502-2

MIDDLE VOLTAGE POWER CABLES-THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements ,are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 8.7/15 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes - discret

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV

Metal screen over Cu wires concentrically laid and each phase contact of Cu tape with thickness one of 0.1mm Water resisting element Cable assembly Layer of semi-conductive water absorbing tapes Three insulated and screened phases with longitudinal waterblocking element are twisted in three core cable Filling and inner sheath-PE - LDPE two steel tapes or two steel galvanized tapes For type 2Y- PE compound HDPE For type Y- PVC compound type ST2 according to IEC 60502 For type 2Y - black For type Y - red

max. 5 pC 15x D cable no less than - 20

Inner sheatth / bedding / Armour Sheath

-30 to 50 according to IEC 60502-2 or DIN VDE 0276-620

Color

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

114

ELKABEL

Cu / Al conductors XLPE insulation Cu screen Armour St. tapes PE orPVC sheat


Construction data 2XSE(F)2YB2Y, A2XSE(F)2YB2Y 3.6/6; 8.7/15kV 2XSE(F)2YB2Y
Nominal Number of conductors Thickness Thickness cross sec- Cable diameter approx. and nominal cross sec- of insulaof tion of tion tion sheath screen N mm2 mm mm mm2 mm Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES-THREE CORE

A2XSE(F)2YB2Y
Mass of Al approx. kg/km Mass of cable approx. kg/km

3.6/6 kV 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 8.7/15 kV 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 3.6/6 kV 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25 8.7/15 kV 3x70 rm /16 3x95 rm /16 3x120rm /25 3x150rm /25 3x185rm /25

2.5 2.5 2.5 2.5 2.5 4.5 4.5 4.5 4.5 4.5 2.5 2.5 2.5 2.5 2.5 4.5 4.5 4.5 4.5 4.5

2.7 2.9 3.0 3.1 3.2 3.0 3.0 3.3 3.4 3,5 2.7 2.9 3.0 3.1 3.2 3.0 3.0 3.3 3.4 3,5

16 16 25 25 25 16 16 25 25 25 16 16 25 25 25 16 16 25 25 25

55.0 58.5 62.5 66.0 70.0 65.0 67.5 72.5 75.5 79.5 55.0 58.5 62.5 66.0 70.0 65.0 67.5 72.5 75.5 79.5

1965 2730 3440 4245 5310 1965 2730 3440 4245 5310 1965 2730 3440 4245 5310 1965 2730 3440 4245 5310

4690 5705 6770 7865 9280 5615 6610 7750 8915 10385 4920 5965 7055 8175 9630 5920 6220 8120 9310 10820

585 805 1020 1255 1575 585 805 1020 1255 1575 585 805 1020 1255 1575 585 805 1020 1255 1575

3310 3780 4350 4875 5545 4235 4680 5335 5925 6650 3540 4040 4640 5190 5895 4540 4990 5700 6320 7085

ELKABEL

115

A2XS(F)2YT A2XS2YT
MIDDLE VOLTAGE POWER CABLES FOR OVERHEAD LINES

Uo/U - 12/20 kV IEC 60502-2

Application
The cables are designed for transfer and distribution of electrical power wite nominal voltage Uo/U 12/20 kV and frequency 50 Hz in urban and district electrical networks. The cables can be installed in air hanger on supporting element included in the bundle of three phases. They are recommended in: - regions where is not allowed cutting of trees for openings of overhead lines; - in boggy terrains where digging of a ditch is difficult and expensive; - in coastal and highly polluted industrial areas in atmosphere as well as in ground; - in stony wooden areas; -in all cases when laying of cables in the ground and construction of overhead lines is hampered and effective overhead cabling can be proved.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Waterresisting element Metal screen According to IEC 60502-2 Al stranded compacted, according to IEC 60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insu lating tape -II option - water absorbing powder and a layer of plastic tape PE compound type ST7 according to IEC 60502 black St rope with insulation Constructions twisted into a bundle include: - 3-phase and supporting insulated St rope

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min According to IEC60228 class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 12/20 kV 12/20kV 24kV 12/20kV 42kV 134kV

Waterresisting element

Sheath Color Supporting insulated Strope Cable lay up TRIPLEX

Level of partial discharge at 2*Uo Bending radius, min Temperature of laying

max. 5 pC 15x D cable no less than - 20

Temperature of exploitation Tests

-30 to 50 according to IEC 60502-2

116

ELKABEL

Al conductors XLPE insulation Cu screen PE sheath Supporting St rope

MIDDLE VOLTAGE POWER CABLES-THREE CORE

Construction data
Number of conductors and nominal cross section N x mm2

A2XS2YT, A2XS(F)2YT 12/20 kV


Mass of Al approx. kg/km Mass of cable approx. kg/km

Nominal Thickness of Thickness of cross section Diameter of bundle insulation sheath of screen approx. 2 mm mm mm mm

3(150rm/16)+50St 3(170rm/16)+50St 3(1120rm/16)+50St

5.5 5,5 5,5

2.5 2,5 2,5

16 16 16

63 69 76

390 570 990

3282 3624 4025

* Water blocking element is aveilable in cables type A2XS(F)2YT

ELKABEL

117

Cu/XLPE/CTS/PVC/AWA/PVC Al/XLPE/CTS/PVC/AWA/PVC

Uo/U - 6.35/11 kV; 8.7/15 kV;12.7/22 kV; 19/33 kV BS 6622

MIDDLE VOLTAGE POWER CABLES

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements ,are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 8.7/15 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to BS 6622 u or Al stranded compacted, according to BS 6360 (IEC60228 class 2 ) semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Cu tapes laid with overlap PVC compound - type 9 l wires laid concentrically PVC compound - type 9 to BS 6755-4.2 black or red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at : According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6.35/11;8.7/15; 12.7/22; 19/33 kV 12kV ; 17.5kV; 24 kV; 36 kV

Inner semiconductive layer Insulation Outer semiconductive layer Metal screen Separating layer Armour Sheath Color

25.5 V;

35kV; 76kV

51kV;

12.5 kV; 17.5kV; 25.5kV; 38kV 10pC 15x D cable 12x D cable no less than 0 - 30 to 50

Bending radius, min Bending radius adjacent to joints or terminations, min Temperature of laying Ambient temperatures

Force of strain in laying N Al cores - 30*n*S core Cu cores - 50*n*S core max. n-number of cores and S-cross section of cores in mm

118

ELKABEL

Cu or Al cores XLPE insulation Cu screen PVC sheath Armour Al wires PVC sheath
Construction data Cu/XLPE/CTS/PVC/AWA/PVC Al/XLPE/CTS/PVC/AWA/PVC 6.35/11 kV; 8.7/15 kV;12.7/22 kV; 19/33 kV
Diameter Number of conductors Thickness of and nominal cross of Al wires - Thickness Cable diameter approx. section insulation for armor of sheath

MIDDLE VOLTAGE POWER CABLES

Cu/XLPE/CTS/ PVC/AWA/PVC
Mass of Cu approx. kg/km Cable mass approx. kg/km

Al/XLPE/CTS/PVC/ AWA/PVC
Mass of Al approx. kg/km Mass of cable approx. kg/km

N mm2

mm

mm

mm2

mm

6.35/11 kV 1x50 rm 1x70 rm 1x95 rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm 8,7/15 kV 1x50 rm 1x70 rm 1x95 rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm 12.7/22 kV 1x50 rm 1x70 rm 1x95 rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm 19 / 33 kV 1x50 rm 1x70 rm 1x95 rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3,4 3,4 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

1,6 1,6 1,6 1,6 2.0 2.0 2,0 2.0 2,0 2,5 1.6 2.0 2.0 2.0 2,0 2.0 2.0 2,0 2,5 2,5 1.6 2.0 2.0 2.0 2,0 2.0 2.0 2,5 2,5 2,5 2.0 2.0 2.0 2,0 2.0 2.5 2.5 2,5 2.5 2,5

1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.2 2.4 2.5 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.3 2.5 2.6 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.2 2.2 2.3 2.3 2.4 2.5 2.5 2.6 2.7 2.8

27.4 29.2 30.9 32.5 34.9 36.6 39.2 41.4 44.6 49.2 29.8 32.2 34.1 35.7 37.1 39.0 41.8 43.8 48.2 51.6 32.0 34.4 36.3 37.7 39.3 41.0 43.6 47.2 50.2 53.8 38.2 39.8 41.7 43.2 46.0 47.9 50.3 52.9 56.5 60.1

425 615 855 1080 1330 1665 2190 2715 3475 4445 425 615 855 1080 1330 1665 2190 2715 3475 4445 425 615 855 1080 1330 1665 2190 2715 3475 4445 425 615 855 1080 1330 1665 2190 2715 3475 4445

1265 1550 1850 2160 2600 3000 3660 4310 5245 6585 1405 1750 2100 2415 2740 3190 3855 4510 5650 6830 1545 1900 2255 2555 2905 3340 4045 4880 5850 7065 2060 2350 2720 3035 3565 4045 4755 5480 6605 7715

355 435 520 605 770 895 1085 1280 1530 2080 375 5515 615 695 790 915 1140 1285 1700 2085 340 550 645 730 825 955 1135 1470 1745 2145 545 620 710 795 1025 1165 1365 1560 1820 2170

970 1115 1265 1415 1655 1845 2140 2425 2835 3555 1110 1320 1500 1655 1800 2020 2360 2605 3220 3760 1250 1475 1660 1805 1980 2185 2520 3015 3440 4035 1765 1925 2125 2285 2640 2890 3230 3590 4095 4685

ELKABEL

119

Cu/XLPE/CTS/PVC/SWA/PVC Al/XLPE/CTS/PVC/SWA/PVC

Uo/U - 3.8/6.6 kV; 6.35/11 kV; 8.7/15 kV;12.7/22 kV; 19/33 kV BS 6622

MIDDLE VOLTAGE POWER CABLES

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements ,are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 8.7/15 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to BS 6622 u or Al stranded compacted, according to BS 6360 (IEC 60228) class 2

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at kV Bending radius, min 7.5; According to BS 6360 (IEC228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 3.8/6.6; 6.35/11; 8.7/15; 12.7/22; 19/33 7.2; 12; 17.5; 24; 36 15; 51; 25.5; 35; 76V

Inner semiconductive layer: semi-conductive XLPE compound Insulation Outer semiconductive layer Metal screen over each phase XLPE compound semi-conductive XLPE compound -I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concen trically Three insulated and screened phases are twisted with fillings and tape support PVC compound - type 9 Galvanized steel wires, laid concentrically PVC compound - type 9 to BS 6755-4.2 black

Cable assembly

12.5; 17.5; 25.5; 38 V max. 10pC 12x D cable

Separating layer Armour Sheath Color

Bending radius adjacent to joints or terminations, 10x D cable min Temperature of laying Temperature of exploitation no less than 0 -30 to 50

Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. S-cross section of cores in n-number of cores and mm

120

ELKABEL

Cu or Al cores XLPE insulation Cu screen PVC sheath Armour Al wires PVC sheath
Construction data Cu/XLPE/CTS/PVC/SWA/PVC Al/XLPE/CTS/PVC/SWA/PVC 3.8/6.6 kV; 6.35/11 kV; 8.7/15 kV;12.7/22 kV; 19/33 kV
Number of conductors Thickness Diameter Thickness of Cable diameter and nominal cross of approx. section insulation St wires - of sheath for armor N mm2 mm mm mm2 mm

MIDDLE VOLTAGE POWER CABLES

Cu/XLPE/CTS/ PVC/SWA/PVC
Mass of Cu approx. kg/km Cable mass approx. kg/km

Al/XLPE/CTS/PVC/ SWA/PVC
Mass of Al approx. kg/km Mass of cable approx. kg/km

3.8/6.6 kV 3x35 rm 3x50 rm 3x70 rm 3x95 rm 3x120rm 3x150rm 6.35/11 kV 3x35 rm 3x50 rm 3x70 rm 3x95 rm 3x120rm 8,7/15 kV 3x35 rm 3x50 rm 3x70 rm 3x95 rm 12.7/22 kV 3x50 rm 3x70 rm 3x95 rm 3x120rm 3x150rm 19 / 33 kV 3x50rm 3x70 rm 3x95 rm

2.5 2.5 2.5 2.5 2.5 2.5 3.4 3.4 3.4 3.4 3.4

2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

2.3 2.5 2.6 2.7 2.8 2.9 2.5 2.6 2.7 2.8 3.0

44.0 47.7 51.4 55.7 59.1 62.5 49.5 52.4 56.0 60.1 63.7

1010 1360 1965 2730 3440 4245 1010 1360 1965 2730 3440

3580 4850 5825 7025 7995 9010 4770 5390 6470 7425 8415

295 405 585 810 1020 1255 295 405 585 810 1020

2865 3890 4445 5105 5575 6020 4055 4435 5090 5505 5995

4.5 4.5 4.5 4.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0

2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15 3.15

2.7 2.8 2.9 3.0 2.9 3.0 3.2 3.3 3.4 3.4 3.5 3.6

54.0 57.3 61.0 65.0 62.1 66.0 70.2 74.8 78.4 75.8 79.5 83.5

1010 1360 1965 2730 1360 1965 2730 3440 4245 1360 1965 2730

5365 5920 6770 7835 6355 7265 8400 10765 11890 9020 9940 11095

295 405 585 810 405 585 810 1020 1255 405 585 810

4650 4965 5390 5915 5400 5885 6480 8345 8900 8035 8560 9180

ELKABEL

121

Cu/XLPE/CWS/PE Al/XLPE/CWS/PE

Uo/U - 6.35/11 kV; 19/33 kV BS 7870-4.10

MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6.35/11 and 19/33 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to BS 7870-4.10 u and Al stranded compacted, according to IEC 60228 class 2 and BS 6360 semi-conductive XLPE compound

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature According to IEC60228 class 2 and BS 6360 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6.35/11kV 19/33kV

Inner semiconductive layer Insulation Outer semiconductive layer Metal screen

XLPE compound Nominal voltage Uo/U: semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PE compound type MDPE according to BS 7870 For 11kV - Red For 33kV - Black Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests 12kV 36kV

Separating layer Sheath

25.4kV 76kV max. 10 pC 15x D cable no less than -5 -30 to 50 according to BS 7870-4.10

Color

Al cores - 30*n*S core Cu cores - 50*n*S core Force of strain in laying N , where: max. n- number of cores and -S-cross-section of conductors in mm

122

ELKABEL

Cu or Al conductors XLPE insulation Cu screen PE sheath


Construction data and Al/XLPE/CWS/PE 6.35/11; 19/33 kV
Cu/XLPE/CWS/PE Al/XLPE/CWS/PE

MIDDLE VOLTAGE POWER CABLES

Cu/XLPE/CWS/PE

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6.35/11 kV Cu/XLPE/CWS/PE 1x240rm /35 1x300rm /35 1x400rm /35 1x500 rm /35 Al/XLPE/CWS/PE 1x70rm /35 1x95rm /35 1x150rm /35 1x185rm /35 1x240rm/35 1x300rm /35 19/33 kV 1x120rm /35 1x150rm /35 1x185rm /35 1x240rm /35 1x300rm /35 1x400rm /35 1x500rm /35

3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3.4 3,4 8.0 8.0 8.0 8.0 8.0 8.0 8.0

2.0 2,1 2.2 2,3 1.7 1.8 1.9 1.9 2.0 2.1 2,1 2,2 2,2 2,3 2,4 2,5 2,6

35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35

36.2 38.6 41.1 44.5 27 28.9 32 33.6 36.2 38.6 39.6 41.2 42.9 45.5 47.9 51.5 55.0

36.6 39.1 42.4 45.7 27 29 32.2 34 36.6 39 41.1 43 44.8 47.5 50.0 53.3 56.5

2548 3078 3835 4805 1443 1693 2028 2548 3078 3835 4805

3268 3868 4717 5792 2400 2700 3100 3725 4345 5290 6410 190 260 405 510 665 830 330 405 510 665 830 1060 1410 363 363 363 363 363 363 363 363 363 363 363 363 363 999 1134 1410 1511 1743 1983 1640 1770 1945 2205 2460 2880 4375

ELKABEL

123

Cu/XLPE/CWS/PE - TRIPLEX Al/XLPE/CWS/PE - TRIPLEX

Uo/U - 6.35/11 kV; 19/33 kV BS 7870-4.10

MIDDLE VOLTAGE POWER CABLES

Application
The three single-core cables with insulation of cross-linked polyethylene (XLPE) factory bindled in TRIPLEX, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6.35/11 and 19/33 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen According to BS 7870-4.10 u and Al stranded compacted, according to IEC 60228 class 2 and BS 6360 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PE compound type MDPE according to BS 7870

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to IEC60228 class 2 and BS 6360 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6.35/11kV 19/33kV 6.35/11; 19/33 kV 12kV; 36kV 6.35/11; 19/33kV 25.4kV; 76kV max. 10 pC 15x D cable no less than -5 -30 to 50 according to BS 7870-4.10

Separating layer Sheath

Factory bundled three single-core cables in TRIPLEX factory bindled in TRIPLEX Color For 11kV - Red For 33kV - Black

Al cores - 30*n*S core Cu cores - 50*n*S core Force of strain in laying N , where: max. n- number of cores and -S-cross-section of conductors in mm

124

ELKABEL

Cu or Al conductors XLPE insulation Cu screen PE sheath


Construction data and Al/XLPE/CWS/PE- TRIPLEX
Cu/XLPE/CWS/PE

MIDDLE VOLTAGE POWER CABLES

Cu/XLPE/CWS/PE- TRIPLEX

6.35/11; 19/33 kV
Al/XLPE/CWS/PE

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6.35/11 kV Cu/XLPE/CWS/PE - TRIPLEX 3,4 2.0 3x(1x240rm /35) 3,4 2,1 3x(1x300rm /35) Al/XLPE/CWS/PE - TRIPLEX 3,4 3x(1x70rm /35) 3,4 3x(1x95rm /35) 3,4 3x(1x150rm /35) 3,4 3x(1x185rm /35) 3.4 3x(1x240rm/35) 3,4 3x(1x300rm /35) 19/33 kV Cu/XLPE/CWS/PE - TRIPLEX Al/XLPE/CWS/PE - TRIPLEX 3x(1x120rm /35) 3x(1x150rm /35) 3x(1x185rm /35) 8.0 8.0 8.0 2,1 2,2 2,2 1.7 1.8 1.9 1.9 2.0 2.1

35 35 35 35 35 35 35 35 78.1 83.3 58.0 62.4 69.1 72.4 78.2 83.2 79.1 84.5 58.5 63.0 70.2 73.4 80.0 84.2 7603 9181 9505 11277 570 780 1215 1530 1995 2490

1024 1024 1024 1024 1024 1024

2812 3165 3822 4258 4922 5610

35 35 35

39.6 41.2 92.7

41.1 43 96.7

4329 5079 6084

7200 8100 9300

990 1215 1530

1024 1024 1024

4920 5310 5835

ELKABEL

125

Cu/XLPE/CWS/PE-wb Al/XLPE/CWS/PE-wb

Uo/U - 6.35/11 kV; 19/33 kV BS 7870 - 4.10

MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6.35/11 and 19/33 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to BS 7870-4.10 u and Al stranded compacted, according to IEC 60228 class 2 and BS 6360 semi-conductive XLPE compound

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature According to IEC60228 class 2 and BS 6360 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6.35/11kV 19/33kV 6.35/11; 19/33 kV 12kV; 36kV 6.35/11; 19/33kV 25.4kV; 76kV max. 10 pC 15x D cable no less than -5 -30 to 50 according to BS 7870-4.10

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulating tape -II option - water absorbing powder and a layer of plastic tape PE compound type MDPE according to BS 7870 For 11kV - Red For 33kV - Black Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests

Water resisting element

Sheath

Color

Al cores - 30*n*S core Cu cores - 50*n*S core Force of strain in laying N , where: max. n- number of cores and -S-cross-section of conductors in mm

126

ELKABEL

Cu or Al conductors XLPE insulation Cu screen PE sheath


Construction data and Al/XLPE/CWS/PE-wb 6.35/11; 19/33 kV
Cu/XLPE/CWS/PE Al/XLPE/CWS/PE

MIDDLE VOLTAGE POWER CABLES

Cu/XLPE/CWS/PE-wb

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6.35/11 kV Cu/XLPE/CWS/PE -wb 3,4 1x240rm /35 3,4 1x300rm /35 3,4 1x400rm /35 3,4 1x500 rm /35 Al/XLPE/CWS/PE-wb 3,4 1x70rm /35 3,4 1x95rm /35 3,4 1x150rm /35 3,4 1x185rm /35 3.4 1x240rm/35 3,4 1x300rm /35 19/33 kV Cu/XLPE/CWS/PE -wb Al/XLPE/CWS/PE -wb 8.0 1x120rm /35 8.0 1x150rm /35 8.0 1x185rm /35 8.0 1x240rm /35 8.0 1x300rm /35 8.0 1x400rm /35 8.0 1x500rm /35

2.0 2,1 2.2 2,3 1.7 1.8 1.9 1.9 2.0 2.1

35 35 35 35 35 35 35 35 35 35

36.2 38.6 41.1 44.5 27 28.9 32 33.6 36.2 38.6

36.6 39.1 42.4 45.7 27 29 32.2 34 36.6 39

2548 3078 3835 4805 1443 1693 2028 2548 3078 3835 4805

3298 3910 4760 5820 2414 2730 3130 3756 4399 5334 6450

190 260 405 510 665 830

363 363 363 363 363 363

1015 1164 1440 1551 1793 2020

2,1 2,2 2,2 2,3 2,4 2,5 2,6

35 35 35 35 35 35 35

39.6 41.2 42.9 45.5 47.9 51.5 55.0

41.1 43 44.8 47.5 50.0 53.3 56.5

330 405 510 665 830 1060 1410

363 363 363 363 363 363 363

1664 1810 1986 2236 2501 2922 3418

ELKABEL

127

CuwXLPE/CWS/PE-wb AlwXLPE/CWS/PE-wb

Uo/U - 6.35/11 kV; 19/33 kV BS 7870 - 4.10

MIDDLE VOLTAGE POWER CABLES

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6.35/11 and 19/33 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor with water resisting According to BS 7870-4.10 u and Al stranded compacted, element according to IEC 60228 class 2 and BS 6360 with water powder absorbing semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulating tape PE compound type MDPE according to BS 7870 For 11kV - Red For 33kV - Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to IEC60228 class 2 and BS 6360 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6.35/11kV 19/33kV 6.35/11; 19/33 kV 12kV; 36kV 6.35/11; 19/33kV 25.4kV; 76kV max. 10 pC 15x D cable no less than -5 -30 to 50 according to BS 7870-4.10

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element Sheath

Color

Al cores - 30*n*S core Cu cores - 50*n*S core Force of strain in laying N , where: max. n- number of cores and -S-cross-section of conductors in mm

128

ELKABEL

Cu or Al conductors XLPE insulation Cu screen PE sheath


Construction data and Alw/XLPE/CWS/PE-wb 6.35/11; 19/33 kV
Cu/XLPE/CWS/PE Al/XLPE/CWS/PE

MIDDLE VOLTAGE POWER CABLES

CuwXLPE/CWS/PE-wb

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen max min N mm2 mm mm mm2 mm mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx.

Mass of cable approx. kg/km

kg/km

6.35/11 kV Cuw/XLPE/CWS/PE -wb 3,4 1x240rm /35 3,4 1x300rm /35 3,4 1x400rm /35 3,4 1x500 rm /35 Alw/XLPE/CWS/PE-wb 3,4 1x70rm /35 3,4 1x95rm /35 3,4 1x150rm /35 3,4 1x185rm /35 3.4 1x240rm/35 3,4 1x300rm /35 19/33 kV Cuw/XLPE/CWS/PE -wb Alw/XLPE/CWS/PE -wb 8.0 1x120rm /35 8.0 1x150rm /35 8.0 1x185rm /35 8.0 1x240rm /35 8.0 1x300rm /35 8.0 1x400rm /35 8.0 1x500rm /35

2.0 2,1 2.2 2,3 1.7 1.8 1.9 1.9 2.0 2.1

35 35 35 35 35 35 35 35 35 35

36.2 38.6 41.1 44.5 27 28.9 32 33.6 36.2 38.6

36.6 39.1 42.4 45.7 27 29 32.2 34 36.6 39

2548 3078 3835 4805 1443 1693 2028 2548 3078 3835 4805

3310 3925 4780 5845 2417 2735 3141 3767 4399 5367 6476

190 260 405 510 665 830

363 363 363 363 363 363

1020 1170 1445 1560 1805 2035

2,1 2,2 2,2 2,3 2,4 2,5 2,6

35 35 35 35 35 35 35

39.6 41.2 42.9 45.5 47.9 51.5 55.0

41.1 43 44.8 47.5 50.0 53.3 56.5

330 405 510 665 830 1060 1410

363 363 363 363 363 363 363

1668 1815 1990 2247 2515 2945 3444

ELKABEL

129

EVAVB EVAVB-F2
MIDDLE VOLTAGE POWER CABLES

Uo/U 3.6/6 kV NBN C 33-121 and modifications No 1 and 2

Application
The three-core cables with insulation of polyvinylchloride (PVC) - armored type are designed for transfer and distribution of electrical power in networks with voltage of 6000 V and in industrial plants. For cable EVAVB the sheath is PVC compound and for cable EVAVB - F2 - PVC compound flame retardant . The cables are for fixed assembly in lines with unlimited difference levels, for underground laying, in cable ducts, conduits, trenches, pipes, shafts over shelves and grills directly underground in ditch.

Cable construction
Construction Conductor According to NBN C 33-121 u stranded compacted circular and sector, according to NBN C 33-121 (IEC60228 class 2) PVC compound three insulated phases are twisted with fillings and tape support polymer material of the two steel tapes underneath the tapes for improving the permeability are laid Cu wires for EVAVB -PVC compound for EVAVB - F2 - PVC compound flame retardant black

Technical data
Conductor resistance at 20C Operating temperature Short circuit temperature NBN C 33-121 (IEC60228) class 2 70 continuous operation 160 /5 s max./ 3.6/6kV 6600V at 20-min5.5*1013 cm at 60-min1*1011 cm

Insulation Cable assembly Inner sheath Armour-screen

Nominal voltage Uo/U: Maximum voltage no more than Insulated volume resistance

Outer sheath

Test voltage Between cores and between AC () - 20 min cores and screen (armor) 13kV Bending radius, min Temperature of laying Temperature of exploitation Flame retardant 20x D cable no less than 0 -15 to 70 According to NBN C 30-004 category F2

Color

130

ELKABEL

Cu / Al conductors PVC insulation Armour- st. tapes-screen PVC sheath


Construction data EVAVB, EVAVB-F2 3.6/6 kV EVAVB ; EVAVB-F2 Max. Number of conductors and Thickness Thickness resistance of Thickness of Cable diameter of steel nominal cross section of insulation sheath approx. tapes the armour Mass of Cu approx. kg/km

MIDDLE VOLTAGE POWER CABLES

Mass of cable approx. kg/km

N mm2

mm

mm

km 1.6 1.35 1.15 1.00 0.90 0.80 0.75 0.70 0.65

mm

mm

3x25rm 3x35rm 3x50sm 3x70sm 3x95sm 3x120sm 3x150sm 3x185sm 3x240sm

3.2 3.2 3.2 3.2 3.4 3.4 3.4 3.4 3.6

0.5 0.5 0.5 0.5 0.7 0.7 0.7 0.7 0.7

2.2 2.2 2.2 2.2 2.4 2.6 2.6 2.8 3.0

37.8 40 38.4 41.4 46.4 49.5 52.4 55.1 61.6

850 1170 1640 2260 3030 3800 4710 5780 7440

2670 3075 2980 3720 5020 5920 6880 8070 10150

ELKABEL

131

EXeCWB EAXeCWB
MIDDLE VOLTAGE POWER CABLES

Uo/U - 8.7/15 kV, 12/20kV, 20.8/36 kV NBN C 33 - 323

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power with nominal voltage Uo/U 8.7/15kV , 12/20kV, 20.8/36 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors According to NBN C 3-323 u and Al stranded compacted, according to IEC 60228 cl.2 (NBN C 30-228) semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. - water absorbing insulating tape PE compound tipe HDPE to NBN C 3-323 Black or Red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC ( ) - 5 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to IEC60228 class 2 (NBN C 30-228) 90 continuous operation 120 /100h per year max./ 250 /5 s max./ 8.7/15; 12/20; 20,8/36 kV 8.7/15; 12/20; 20.8/36 kV 17.5 kV; 24 kV; 41.5kV 8.7/15; 12/20; 20.8/36 kV 35 kV; 48 kV; 83 kV max. 5 pC 15x D cable no less than - 15 -30 to 50 according to NBN C 33 323

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element Sheath Color

Force of strain in laying N Al cores - 30*n*S core max. Cu cores - 50*n*S core where: N is number of cores and S is cross section of cores in mm

132

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data EXeCWB; EAXeCWB 8.7/15; 12/20kV; 20.8/36 kV


EXeCWB EAXeCWB

MIDDLE VOLTAGE POWER CABLES

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen N mm2 mm mm mm2 mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

8.7/15 kV 1x25 rm /16 1x50 rm /16 1x95 rm /25 1x150 rm /25 1x240 rm /25 1x400rm /35 12/20kV 1x25 rm /16 1x50 rm /16 1x95 rm /25 1x150 rm /25 1x240 rm /25 1x400rm /35 20.8/36 kV 1x120 rm /25 1x150 rm /25 1x240 rm /25 1x400 rm /35

4.5 4.5 4.5 4.5 4.5 4.5 5.5 5.5 5.5 5.5 5.5 5.5 8,8 8,8 8,8 8,8

2.6 2.6 2.6 2.9 3.1 3.3 2.6 2.6 2.7 3.0 3.1 3.3 3.0 3.2 3.4 3.6

16 16 25 25 25 35 16 16 25 25 25 35 25 25 25 35

26.8 29.0 32.5 35.9 40.0 47.3 29.2 31.4 35.0 38.4 42.7 49.6 43.5 45.3 49.8 56.9

480 690 1120 1595 2455 3835 490 690 1120 1595 2455 3835 1345 1595 2455 3835

939 1200 1723 2308 3311 4953 1017 1285 1828 2425 3430 5084 2555 2896 3970 5705

68 130 260 405 665 1060 68 130 260 405 665 1060 330 405 665 1060

265 265 265 265 265 363 265 265 265 265 265 363 265 265 265 363

782 905 1128 1384 1786 2541 860 989 1233 1500 1905 2672 1805 1971 2445 3293

ELKABEL

133

EXeCVB EAXeCVB
MIDDLE VOLTAGE POWER CABLES

Uo/U - 8.7/15 kV, 12/20kV, 20.8/36 kV NBN C 33 - 323

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements, are designed for transfer and distribution of electrical power with nominal voltage Uo/U U 8.7/15kV , 12/20kV, 20.8/36 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductors According to NBN C 33-323 u and Al stranded compacted, according to IEC 60228 cl.2 (NBN C 30-228) semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. water absorbing insulating tape PVC compound tipe ST2 Red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC ( ) - 5 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests According to IEC60228 class 2 (NBN C 30-228) 90 continuous operation 120 /100h per year max./ 250 /5 s max./ 8.7/15; 12/20; 20,8/36 kV 8.7/15; 12/20; 20.8/36 kV 17.5 kV; 24 kV; 41.5kV 8.7/15; 12/20; 20.8/36 kV 35 kV; 48 kV; 83 kV max. 5 pC 15x D cable no less than - 15 -30 to 50 according to NBN C 33 323

Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen

Water resisting element Sheath Color

Force of strain in laying N Al cores - 30*n*S core max. Cu cores - 50*n*S core where: N is number of cores and S is cross section of cores in mm

134

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data EXeCVB; EAXeCVB 8.7/15; 12/20kV; 20.8/36 kV


EXeCVB EAXeCVB

MIDDLE VOLTAGE POWER CABLES

Nominal Cable diameter Number of conducThicThiccross approx. tors and nominal kness of kness of section of cross section insulation sheath screen N mm2 mm mm mm2 mm

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

Mass of Al approx. kg/km

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

8.7/15 kV 1x25 rm /16 1x50 rm /16 1x95 rm /25 1x150 rm /25 1x240 rm /25 1x400rm /25 12/20kV 1x50 rm /16 1x95 rm /25 1x150 rm /25 1x240 rm /25 1x400rm /35 20.8/36 kV 1x120 rm /25 1x150 rm /25 1x240 rm /25 1x400 rm /35

4.5 4.5 4.5 4.5 4.5 4.5 5.5 5.5 5.5 5.5 5.5 8,8 8,8 8,8 8,8

2.6 2.6 2.6 2.9 3.1 3.3 2.6 2.7 3.0 3.1 3.3 3.0 3.2 3.4 3.6

16 16 25 25 25 35 16 25 25 25 35 25 25 25 35

26.8 29.0 32.5 35.9 40.0 47.3 31.4 35.0 38.4 42.7 49.6 43.5 45.3 49.8 56.9

490 690 1120 1595 2661 4344 690 1120 1595 2661 4344 1345 1595 2455 3835

1048 1319 1858 2473 3510 5204 1414 1979 2607 3641 5348 2772 3136 4252 6047

68 130 260 405 665 1060 130 260 405 665 1060 330 405 665 1060

265 265 265 265 265 363 265 265 265 265 363 265 265 265 363

890 1024 1263 1548 1985 2792 1119 1384 1682 2116 2936 2022 2211 2727 3635

ELKABEL

135

HIGH VOLTAGE POWER CABLES

ELKABEL

HIGH VOLTAGE POWER CABLES

ELKABEL

HIGH VOLTAGE POWER CABLES

2XS(F)2Y A2XS(F)2Y

Uo/U - 26/45/52 V; 38/66/72.5kV IEC 60840 / DIN VDE 0276-632

Application
The single-core cables are designed for transfer and distribution of electrical power with nominal voltage Uo/U 26/45/52, 38/66/72.5 kV and frequency 50 Hz. They are suitable for fixed assembly and indoor installation, in cable ducts and conduits, over shelves and grilles in water and directly underground in ditch and outdoor under shelter.

Cable construction
Construction Conductor According to IEC 60840/VDE 0276-632 u and Al stranded compacted wires according to IEC 60228 cl.2 and VDE 0295 cl.2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulating tape -II option - water absorbing powder and a layer of plastic tape PE compound type ST7 according to IEC 60502 type DMP 2 according to VDE 0276 black

Technical data
Conductor resistance at According to IEC60228 class 2 20C and VDE 0295 class 2 Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 26/45 kV 38/66 kV

Inner semiconductive layer Insulation Outer semiconductive layer Waterresisting element Metal screen

Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 30 min Partial discharge level at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests

52 kV; 26/45 kV 65 kV

72.5 kV 38/66 V 90 kV

Wate resisting element

Sheath

max. 5pC 15x D cable no less than (-5) -30 to 50 according to IEC 60840 according to VDE 0276-632

Color

138

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

HIGH VOLTAGE POWER CABLES

Construction data 2XS(F)2Y, A2XS(F)2Y 26/45/52; 38/66/72.5 kV


Number of conductors and Nominal cross nominal cross section of screen section . mm2 Uo/U/Um 26/45/52 kV 1x240 1x300 1x400 1x500 Uo/U/Um 38/66/72,5 kV 1x240 1x300 1x400 1x500 mm2 35 35 35 35 2S(F)2Y Cable diameter approx. mm 55 58 61 64 Mass of Cu approx. kg/km 2454 2980 3836 4807 Mass of cable approx. kg/km 4050 4800 5600 6800 Mass of Al approx. kg/km 649 812 1043 1374 A2XS(F)2Y Mass of Cu approx. kg/km 363 363 363 363 Mass of cable approx. kg/km

2500 2900 3200 3600

35 35 35 35

64 66 67 70

2454 2980 3836 4807

4600 5300 6300 7800

649 812 1043 1374

363 363 363 363

3600 4100 4400 5300

ELKABEL

139

A2XSY 150rm/16 ELFILT


HIGH VOLTAGE POWER CABLES

U 75 kV similar to IEC 60502 and IEC 60840

Al conductors XLPE insulation Cu screen PVC sheath

Application
The cables are for power supply of electrostatic filters to 75 kV. Conditions for laying - underground, in premises, in cable ducts and conduits and outdoor under shelter.

Cable construction
Construction Conductors Inner semiconductive layer Insulation Outer semiconductive layer Metal screen According to IEC, VDE Al stranded compacted, wires according to IEC 60228 cl.2 VDE 0295 cl..2 semi-conductive XLPE compound XLPE compound semi conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thick ness of 0.1mm. layer of plastic tape PVC compound type ST2 according to IEC 60502 type DMV 6 according to VDE 0276 red

Technical data
Aluminium current core - circular multiwire compacted - nominal cross-section - diameter Insulation thickness Metal screen cross-section Sheath thickness Outer diameter approx. Mass of core Mass of cable Bending radius single bending Electrical characteristics Electrical resistance of core at DC and 20C Electrical resistance of screen at DC and 20C

mm2 50 mm 8.2 mm 9.0 mm2 16 mm 2.5 mm 37.2 kg/km 131 kg/km 1297 m 0.65 m min 60 /km /km 0.641 1.15

Separating layer Sheath

Electrical resistance of insulation M.km 1*105 F/km 0.1387 Operating capacitance Maximum allowed ambiend temperature Tests Test voltage /15 min/ AC voltage DC voltage Partial discharge at U=50 kV - max Dielecttric loss / tg /, max. Increase of tg / tg/ U between 15-38 kV U between 38-89 kV 10.104 10.104 70kV 225kV 5pC 30.104 90 C

Color

140

ELKABEL

A2XSY 150rm/16 ELFILT

U 111 kV similar to IEC 60502 and IEC 60840

HIGH VOLTAGE POWER CABLES

Al cores XLPE insulation Cu screen PVC sheath

Application
The cables are for power supply of electrostatic filters to 111 kV. Conditions for laying - underground, in premises, in cable ducts and conduits and outdoor under shelter.

Cable construction
Construction Conductors Inner semiconductive layer Insulation Outer semiconductive layer Metal screen According to IEC, VDE Al stranded compacted, wires according to IEC 60228 cl.2 VDE 0295 cl..2 semi-conductive XLPE compound XLPE compound semi conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thick ness of 0.1mm. layer of plastic tape PVC compound type ST2 according to IEC 60502 type DMV 6 according to VDE 0276 red

Technical data
Aluminium current core - circular multiwire compacted - nominal cross-section - diameter Insulation thickness Metal screen cross-section Sheath thickness Outer diameter approx. Mass of core Mass of cable Bending radius single bending Electrical characteristics Electrical resistance of core at DC and 20C Electrical resistance of screen at DC and 20C Electrical resistance of insulation Operating capacitance Maximum allowed ambiend temperature Tests Test voltage /15 min/ AC voltage DC voltage Partial discharge at U=50 kV - max Dielecttric loss / tg /, max. Increase of tg / tg/ U between 15-38 kV U between 38-89 kV 10.104 10.104

50 mm2 mm 8.2 mm 11.0 mm2 16 mm 2.5 mm 40.0 kg/km 131 kg/km 1524 m 0.65 m min 60 /km /km 0.641 1.15

Separating layer Sheath

M.km 1*105 F/km 0.11 90 C

Color

111kV 333kV pC 10 30.104

ELKABEL

141

POWER CABLES, FLAME RETARDANT

ELKABEL

POWER CABLES, FLAME RETARDANT

ELKABEL

NYYfr-0/J
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV VDE 0276 part 603

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames. NYYfr-0/J is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other. Note: Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC flame retardant, degree of flame retardancy

Technical data
Conductor resistance at 20 According to VDE 0295 class 1 or 2 (IEC 60228) 70

Max. conductor temperature

Max. short circuit temperature Rated voltage Uo/U

+160 , not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

Core identification according to VDE 0293 Inner sheath Sheath Color tapes and filling compound PVC flame retardant, degree of flame retardancy category A black Test voltage Bending radius -single core -multi core Flame retardancy 15 cable diameter 12 cable diameter BDS IEC 332-3/82, Category A

Color coding
Single core - black or yellow/green Double core - light blue and brown or yellow-green and black 3 - core 4 - core 5 - core Multiple core

brown, black, grey or yellow/green, light blue, brown

light blue, brown, black, grey or yellow/green, brown, black, grey

light blue, brown, black, grey, Black with number marking black or or black with number mark on cores yellow/green, light blue, brown, and yellow/green core in the outer black, grey cover

144

ELKABEL

Cu conductors PVC insulation PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data NYYfr- 0/J


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 1 x 1,5 1 x 2,5 1 x 4,0 1 x 6,0 1 x 10,0 1 x 16,0 1 x 25,0 1 x 35,0 1 x 50,0 1 x 70,0 1 x 95,0 1 x 120,0 1 x 150,0 1 x 185,0 1 x 240,0 1 x 300,0 1 x 400,0 1 x 500,0 2 x 1,5 2 x 2,5 2 x 4,0 2 x 6,0 2 x 10,0 2 x 16,0 2 x 25,0 2 x 35,0 2 x 50,0 2 x 70,0 2 x 95,0 3 x 1,5 3 x 2,5 3 x 4,0 3 x 6,0 3 x 10,0 3 x 16,0 3 x 25,0 3 x 35,0 3 x 50,0 3 x 70,0 3 x 95,0 3 x 120,0 re re re re re re rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re rm rm rm rm rm re re re re re re rm rm rm sm sm sm mm 7,1 7,5 8,4 8,9 9,7 10,7 12,7 13,9 15,4 17,1 19,4 20,8 22,7 25,0 27,8 30,7 34,1 38,1 12,2 12,9 14,9 15,9 17,5 19,4 23,5 25,7 29,1 32,1 38,0 12,1 12,9 15,0 16,1 18,0 20,1 24,4 26,7 30,4 29,2 33,2 35,4 Mass of Cu kg/km 14 23 37 56 94 149 243 337 454 656 911 1147 1415 1770 2327 2887 3692 4725 28 46 75 112 188 298 485 673 908 1312 1822 43 70 112 168 282 447 728 1010 1363 1968 2732 3440 Mass of cable approx kg/km 63 76 104 128 183 247 359 462 603 817 1092 1334 1627 2013 2598 3200 4048 5141 192 229 315 382 509 676 1027 1301 1703 2312 3093 201 247 350 435 606 828 1260 1622 2139 2380 3233 3962

Construction data NYYfr- 0/J


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 3 x 150,0 3 x 185,0 3 x 240,0 3 x 300,0 3 x 25,0+16 3 x 35,0+16 3 x 50,0+25 3 x 70,0+35 3 x 95,0+50 3 x 120,0+70 3 x 150,0+70 3 x 185,0+95 3 x 240,0+120 3 x 300,0+150 4 x 1,5 4 x 2,5 4 x 4,0 4 x 6,0 4 x 10,0 4 x 16,0 4 x 25,0 4 x 35,0 4 x 50,0 4 x 70,0 4 x 95,0 4 x 120,0 4 x 150,0 4 x 185,0 4 x 240,0 4 x 300,0 5 x 1,5 5 x 2,5 5 x 4,0 5 x 6,0 5 x 10,0 5 x 16,0 5 x 25,0 5 x 35,0 5 x 50,0 5 x 70,0 5 x 95,0 sm sm sm sm sm re sm re sm rm sm rm sm rm sm rm sm rm sm rm sm rm sm rm re re re re re re rm rm sm sm sm sm sm sm sm sm re re re re re re rm rm rm rm rm mm 39,2 42,7 48,1 53,5 25,4 27,7 29,2 33,4 37,8 40,8 44,8 49,3 55,3 60,9 12,9 13,8 16,2 17,4 19,5 21,8 27,2 30,1 29,2 33,4 37,8 40,8 44,8 49,3 55,3 60,9 13,7 14,8 17,4 19,0 21,6 24,1 29,9 33,5 38,1 43,3 50,1 Mass of Cu kg/km 4245 5311 6981 8661 876 1159 1605 2304 3187 4096 4901 6222 8128 10076 57 93 149 223 376 595 970 1346 1817 2624 3643 4587 5660 7082 9308 11548 71 116 187 279 470 744 1213 1683 2271 3280 4554 Mass of cable approx kg/km 4867 6046 7869 9702 1422 1790 2091 2820 3824 4779 5685 7163 9227 11363 232 289 419 525 741 1024 1615 2095 2311 3142 4281 5256 6442 8033 10426 12850 272 341 494 635 911 1262 1964 2593 3435 4638 6318

ELKABEL

145

NYCY - FR
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV VDE 0276 part 603

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames. NYCY-FR is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, where greater mechanical protection an protection against accidental contact is required if damaged. Note: Other core configuration and special constructions manufactured upon request.

Cable construction
Construction Conductor Insulation According to VDE 0276 part 603 solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) PVC flame retardant, degree of flame retardancy

Technical data
Conductor resistance at 20 According to VDE 0295 class 1 or 2 (IEC 60228) 70

Max. conductor temperature

Max. short circuit temperature Core identification according to VDE 0293 Inner sheath Sheath Color tapes and filling compound PVC flame retardant, degree of flame retardancy category A black Rated voltage Uo/U Test voltage Bending radius -single core -multi core Flame retardancy

+160 , not more than 5 sec 0.6/1 kV AC - 4 kV 50 Hz

15 cable diameter 12 cable diameter BDS IEC 332-3, Category A

Color coding
Single core - black Double core - light blue and brown

3 - core

4 - core

brown, black, grey

light blue, brown, black, grey

146

ELKABEL

Cu conductors PVC insulation Cu concentric conductor PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data NYCY -FR 0.6/1 kV


Number of wires and nominal cross section N mm2 1 x 1,5/1,5 1 x 2,5/2,5 1 x 4,0/4,0 1 x 6,0/6,0 1 x 10/10 1 x 16/16 1 x 25/25 1 x 35/35 2 x 1,5/1,5 2 x 2,5/2,5 2 x 4,0,/4,0 2 x 6,0/6,0 2 x 10/10 2 x 16/16 2 x 25/25 2 x 35/35 2 x 50/50 3 x 1,5/1,5 3 x 2,5/2,5 3 x 4,0/4,0 3 x 6,0/6,0 3 x 10/10 3 x 16/16 3 x 25/16 3 x 25/25 3 x 35/16 3 x 35/35 3 x 50/25 3 x 35/35 3 x 35/16 3 x 50/25 3 x 50/50 3 x 70/35 3 x 70/70 3 x 95/50 3 x 95/95 3 x 120/70 3 x 120/120 3 x 150/70 3 x 150/150 3 x 185/95 3 x 240/120 4 x 1,5/1,5 4 x 2,5/2,5 4 x 4,0/4,0 4 x 6,0/6,0 4 x 10/10 4 x 16/16 4 x 25/16 4 x 35/16 4 x 50/25 4 x 35/16 4 x 50/25 4 x 70/35 4 x 95/50 4 x 120/70 4 x 150/70 4 x 185/95 4 x 240/120 re re re re re re rm rm re re re re re re rm rm rm re re re re re re rm rm rm rm rm sm sm sm sm sm sm sm sm sm sm sm sm sm sm re re re re re re rm rm rm sm sm sm sm sm sm sm sm Shape Concentric conductor cross section mm2 1,5 2,5 4,0 6,0 10 16 25 35 1,5 2,5 4,0 6,0 10 16 25 35 50 1,5 2,5 4,0 6,0 10 16 16 25 16 35 25 35 16 25 50 35 70 50 95 70 120 70 150 95 120 1,5 2,5 4,0 6,0 10 16 16 16 25 16 25 35 50 70 70 95 120 Outer diameter of cable approx. mm 7,9 8,5 9,4 9,9 11,3 12,8 12,9 16,4 13,0 13,7 15,9 17,1 19,1 21,0 25,1 27,8 31,5 13,5 14,3 16,6 17,7 20,0 22,1 27,8 26,6 29,1 29,4 32,7 27,1 26,6 29,6 30,6 33,6 34,1 38,2 39,4 38,3 41,6 44,7 45,8 49,0 54,5 14,3 16,3 17,8 19,0 21,5 23,8 29,0 32,0 36,4 29,8 33,1 38,4 42,6 43,1 50,7 55,3 62,3 Cu weight kg/km 27 47 74 108 182 297 465 654 45 68 110 164 274 435 703 980 1343 56 90 147 243 365 580 855 938 1127 1317 1581 1339 1161 1593 1819 2265 2584 3151 3692 4038 4443 4827 5543 6051 7881 70 136 183 297 457 725 1090 1456 1998 1495 2044 2911 4041 5162 6214 7826 10150 Cable weight approx. kg/km 98 122 163 203 286 410 606 807 230 273 375 458 619 841 1276 1642 2193 252 305 425 528 724 999 1440 1524 1813 1987 2415 1644 1627 2174 2260 2932 3097 4004 4336 4925 5124 5890 6352 7329 9399 284 382 494 620 860 1196 1764 2246 3024 2060 2730 3758 5054 6246 7548 9374 12124

ELKABEL

147

FG70R
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 600/1000 V IEC 60502-1

Application
Powet cable suitable for transmission of electricity up to 1000 V, used in house and industrial installations. Appropriate for internal installation even in damp surroundings and for outdoor applications-whether there in possibility for direct instalation.

Cable construction
Construction Conductor Insulation According to IEC 60502-1 Cu wires, flexible class 5, according to IEC 60228 rubber compound Type HEPR according to IEC 60502-1 on base HEPR rubber

Technical data
Conductor resistance at 20C Operating temperature max at the conductor max According IEC 60228 class 5 +90oC in operation +250oC in the event of a short circuit 0oC

Temperature minimum Core identification according to VDE 0293 Inner Sheath Outer Sheath Color Flame retarding PVC compound PVC compound fire retardant and reduced corrosive gas emission Grey RAL 7035 Rated voltage Uo/U Test voltage AC, 50 Hz Minimum bending radius

0.6/1kV 4kV 4x cable diameter

Testing according: Flame test

Test class C according IEC 60332-3

Color coding
Number of cores 1 2 3 4 5 5 and above Color of conductors without yellow/green Black or other blue; brown brown, black, grey blue, brown, black, grey blue, brown, black, grey, black black with number mark on cores Color of conductors with yellow/green yellow/green, blue, brown yellow/green, brown, black , grey yellow/green, blue, brown, black, grey black with number mark on cores and yellow/green in the outer cover

148

ELKABEL

Cu conductors HEPR insulation Flame retarding PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data FG7OR 600/1000 V


Number of conductors and nominal cross section N mm2 1x1,5 1x2,5 1x4,0 1x6,0 1x10 1x16 1x25 1x35 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 2x1,5 2x2,5 2x4.0 2x6.0 2x10 2x16 2x25 2x35 2x50 2x70 2x95 2x120 2x150 3x1,5 3x2,5 3x4,0 3x6,0 3x10,0 3x16,0 3x25,0 3x35,0 3x50,0 3x70,0 3x95,0 Outer diameter approx. nom/mm 5.8 6.2 6.7 7.6 8.8 9.8 11.7 13 15.2 17.5 20 21.4 24.3 25.7 30.4 33.6 11.6 12.3 13.4 15.2 17.6 20 23.8 26.4 30.4 35.4 39.6 42.8 47.8 12.1 12.9 14.0 16.0 18.6 21.2 25.2 28.5 32.3 37.7 42.2 Mass of Cu kg/km 11.9 19.8 32.4 48.2 87.3 134.9 206.4 293.7 410.5 584.7 774.3 988.6 1245.5 1507.7 1976.3 2498.0 24.3 40.4 66.0 98.3 177.9 275.0 420.6 598.5 836.5 1191.6 1577.9 2014.8 2538.3 36.4 60.6 99.0 147.5 270.0 412.5 630.0 998.0 1255 1788 2370 Mass of cable approx kg/km 47.4 58.5 76.0 101.4 152.2 210.4 306.6 408.6 564.9 773.2 1003.6 1243.9 1569.6 1859.6 2410.1 2986.3 179.5 212.5 265.8 349.5 501.9 686.5 987.8 1278.2 1724.5 2371.3 2998.4 3672.4 4569.0 199.0 210.0 307.0 408.0 600.0 834.0 1210 1620 2160 2980 3776

Construction data FG7OR 600/1000 V


Number of conductors and nominal cross section N mm2 3x120 3x150 3x185 3x240 4x1.5 4x2.5 4x4 4x6 4x10 4x16 4x25 3x35+25 3x50+35 3x70+35 3x95+50 3x120+70 3x150+95 3x185+95 3x240+150 5x1.5 5x2.5 5x4.0 5x6,0 5x10,0 5x16,0 7x1,5 7x2,5 10x1.5 10x2.5 12x1,5 12x2,5 19x1,5 19x2,5 24x1,5 24x2,5 27x1.5 27x2.5 30x1,5 30x2,5 Outer diameter approx. nom/mm 45.7 51.5 54.9 65.4 12.9 13.7 15.0 17.2 20.1 22.9 27.5 30.3 33.5 38.8 44.1 48.0 54.6 57.2 68.4 13.7 14.6 16.1 18.6 21.8 25.0 14.6 15.7 17.6 19.0 18.0 19.5 20.6 22.4 24.0 26.0 24.5 26.6 25.3 27.5 Mass of Cu kg/km 3022 3808 4610 6040 48.5 81 132.0 197.0 356.0 550.0 840.0 1110 1460.0 2090.0 2790.0 3620.0 4600.0 5400.0 7310.0 60.6 101.0 165.0 246.0 450.0 690.0 85.0 142.0 122.0 202.0 145.5 242.0 230.0 380.0 290.0 485.0 328.0 546.0 365.0 607.0 Mass of cable approx kg/km 4650 5840 6920 9200 225.6 277 360.0 483.0 720.0 990.0 1450.0 1990.0 2560.0 3550.0 4590.0 5700.0 7250.0 8330.0 11350.0 257 320 420.0 570.0 850.0 1200.0 297.0 376.0 410.0 530.0 450.0 580.0 605.0 805.0 770.0 1020.0 820.0 1105.0 890.0 1200.0

ELKABEL

149

2XYRYfr-0/J A2XYRYfr-0/J
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV IEC 60502-1,

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames. 2XYRYfr and A2XYRYfr is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation Color According to IEC 60502-1 solid or multi-strand Al or Cu wires class 1 or 2 acc. IEC 60228 XLPE COMPOUND Double core - light blue and brow or yellow-green and black 3 - core - brown, black, grey or yellow/green, light blue, brown 4 - core - light blue, brown, black, grey or yellow/green, brown, black, grey 5 - core - light blue, brown, black, grey black or yellow/green, light blue, brown black, grey Multiple core - Black with numbered pair in each cover PVC flame retardant, degree of flame retardancy

Technical data
Conductor resistance at 20oC According class 1 or 2 IEC 60228

Max. conductor temperature

90o continuous operation

Overload temperature

130o /100h/per year m./

Short circuit temperature

250o /5 s max./

Nominal voltage Uo/U

0.6/1 kV

Highest system voltage

1.2 kV between cores - 3.5 V

Inner sheath Armour Sheath Color

Test voltage AC - 5 min. galvanized iron wires twisted concentrically PVC flame retardant, degree of flame retardancy category A Black Bending radius, min. Temperature of laying Temperature of exploitation

between core and screen 3.5 V - 15x D cable no less than 0o -30 to 50o

Flame retardancy

BDS IEC 332-3/82, Category A

150

ELKABEL

Cu/Al conductors XLPE insulation PVC sheath Armour St. wires PVC sheath Construction data 2XYRYfr, A2XRYfr 0.6/1 kV
Number of Thickness of Thickness of cond. and nominal cross insulation sheath section mm mm 2 2.5 rm 0.7 1.8 2 4 rm 0.7 1.8 2 10 rm 0.7 1.8 2 16 rm 0.7 1.8 2 25 rm 0.9 1.8 2 50 rm 1.0 1.9 2 x 95 rm 1.1 2.1 3 1.5 rm 0.7 1.8 3 2.5 rm 0.7 1.8 3 4 rm 0.7 1.8 3 6 rm 0.7 1.8 3 10 rm 0.7 1.8 3 16 rm 0.7 1.8 3 25 rm 0.9 1.8 3 35 rm 0.9 1.8 3 50 rm 1.0 1.9 3 70 sm 1.1 2.1 4 2.5 rm 0.7 1.8 4 4 rm 0.7 1.8 4 6 rm 0.7 1.8 4 10 rm 0.7 1.8 4 16 rm 0.7 1.8 4 25 rm 0.9 1.8 4 35 rm 0.9 1.9 4x50 sm 1,4 2.1 4x70 sm 1,4 2,1 4x95 sm 1,6 2,1 4x120 sm 1,6 2,2 4x150 sm 1,8 2,4 4x185 sm 2 2,5 4x240 sm 2.2 2,6 7 x 1.5 rm 0.7 1.8 7 x 2.5 rm 0.7 1.8 12 x 1.5 rm 0.7 1.8 19 x 2.5 rm 0.7 1.8 Cable diameter approx. mm 14.1 15.2 18.9 20.3 24.9 29.2 38.2 16.5 16.5 17.5 17.8 19.8 21.3 25.4 27.8 30.9 34.6 16.6 17.5 19.1 21.2 23.6. 27.5 30.2 34.4 38.9 43.0 47.5 51.8 56.0 62.3 17.0 18.2 20.4 25.6 2XYRYfr Mass of Cu Cable weight approx. approx. kg/km kg 46 421 75 500 188 863 298 1050 485 1584 908 2376 1822 4058 43 596 70 619 112 713 168 774 282 987 447 1234 728 1878 1010 2320 1363 2901 1968 3750 93 933 149 1060 223 1248 376 1576 595 2278 970 3059 1346 3701 1817 3535 2624 4701 3643 6017 4587 7626 5660 9144 7082 10976 9308 13861 96 960 160 1119 165 1294 435 2277 A2XYRYfr Mass of Al Cable weight approx. approx. kg/km kg 14 388 23 448 56 729 90 840 140 1236 269 1730 539 2762 13 566 21 570 36 636 51 656 85 788 135 919 210 1355 290 1593 385 1914 585 2353 28 867 46 956 68 1091 112 1309 180 1859 270 2352 390 2736 520 2225 760 2818 1060 3408 1340 4346 1650 5094 2100 5945 2720 7207 30 894 49 1007 51 1179 133 1972

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

ELKABEL

151

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV 2XYRaY- FR IEC 60502-1 A 2 X Yconductors Y -insulation PVC sheath Armour Al wires PVC sheath R a XLPE F R Cu/Al

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames. 2XYRaY-FR and A2XYRaY-FR is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, where greater mechanical protection an protection against accidental contact is required if damaged.

Cable construction
Construction Conductor Insulation Inner sheath Armour Sheath Color According to IEC 60502-1 solid or multi-strand Al or Cu wires class 1 or 2 acc. IEC 60228 XLPE COMPOUND PVC flame retardant, degree of flame retardancy Al wires twisted concentrically PVC flame retardant, degree of flame retardancy category A Black

Technical data
Conductor resistance at 20oC Max. conductor temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage AC - 5 min. Bending radius, min. Temperature of laying Temperature of exploitation Flame retardancy According class 1 or 2 IEC 60228 90o continuous operation 130o /100h/per year m./ 250o /5 s max./ 0.6/1 kV 1.2 kV between cores - 3.5 V between core and screen - 3.5 V - 15x D cable no less than 0 - 30 to 50o IEC 332-3, Category A

Construction data 2XYRaY-FR , A2XYRaY-FR 0.6/1 kV


Number of Thickness of Thickness of cond. and nominal insulation sheath cross section mm mm 1x25 rm 0.9 1.8 1x35 rm 0.9 1.8 1x50 rm 1.0 1.8 1x70 rm 1.1 1.8 1x95 rm 1.1 1.8 1x120 rm 1.2 1.8 1x150 rm 1.4 1.8 1x185 rm 1.6 1.9 1x240 rm 1.7 2.0 1x300 rm 1.8 2.1 Cable diameter approx. mm 16.3 17.4 18.7 20.5 22.9 24.5 26.3 28.4 31.2 34.6 2XYRaY-FR Mass of Cu Cable weight appr. approx. kg/km kg 229 532 325 657 458 833 648 1073 885 1417 1120 1699 1378 2028 1770 2643 2327 3335 2887 4118 A2XYRaY-FR Mass of Al Cable weight appr. approx. kg/km kg 68 370 95 425 127 498 190 611 260 785 325 896 405 1046 510 1371 665 1656 830 2040

152

ELKABEL

Uo/U - 6/10 kV IEC 60502-2, IEC 60332-3

2XSEY- FR A2XSEY-FR Cu/Al conductors XLPE insulation Cu screen PVC sheath - flame retardant

MIDDLE VOLTAGE POWER CABLES-THREE CORE, FLAME RETARDANT

Application
The three-core cables flame retardant with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10 kV and frequency 50 Hz. The cables are manufactured with sheaths of flame retardant materials. They are suitable for use in distribution installations, electric power stations and substations for fixed indoor assembly in cable ducts and conduits, over shelves and grilles. They should not be laid directly underground or in water. The cables should not be laid in or near nuclear stations.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen Cable assembly Inner sheath According to IEC 60502-2 and IEC 60332-3 u and Al stranded compacted wires to IEC 60228 cl.2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape -I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concentrically three insulated and screenesd phases are twisted with and tape support I -option - fillings and sheat exstruded PVC compound flame retardant - kat A II-option - fillings and tapes kat B and C PVC compound flame retardant black

Technical data
Conductor resistance at 20oC Max. conductor temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Uo/U, no more than Test voltage AC - 5 min. AC (~) - 5 min ~ DC (=) - 15 min Bending radius, min. Temperature of laying Temperature of exploitation Tests Flame retardancy According to IEC 60228 90o continuous operation 130o /100h/per year m./ 250o /5 s max./ 6/10 kV 6/10 kV 12 kV 6/10 kV 21 kV 67 kV - 15x D cable no less than -5 - 30 to 50o IEC 60 502 IEC 332-3, Category A

Sheath Color

Construction data 2XSEY-FR, A2XSEY-FR 6/10 kV


Nominal Number of cond. and Thickness of Thickness of cross-secnominal insulation sheath tion of cross section screen N mm2 mm mm mm2 6/10kV 3x35rm/16 3,4 2.5 16 3x50rm/16 3,4 2.6 16 3x70rm/16 3,4 2.7 16 3x95rm/16 3,4 2.8 16 3x120rm/16 3,4 2.9 16 3x150rm/25 3,4 3.0 25 3x185rm/25 3,4 3.2 25 3x240rm/25 3,4 3.4 25 Cable diameter approx. mm 47.6 50.3 54.4 58.4 61.6 64.4 68.5 74.3 2XSEY-FR A2XSEY-FR Mass of Cu Cable weight Mass of Al Cable weight appr. approx. appr. approx. kg/km kg kg/km kg 1010 1363 1968 2732 3440 4245 5311 6981 3276 3834 4784 5930 6923 8217 9691 11963 298 404 584 809 1023 1257 1579 2071 2619 2923 3470 4103 4627 5379 6144 7331

ELKABEL

153

MIDDLE VOLTAGE POWER CABLES-THREE CORE, FLAME RETARDANT

Uo/U 6/10 kV 2XSEYBY- FR IEC 60502-2 , IEC 60332-3 A/2conductors E Yinsulation Cu-screen R st. tapes PVC sheath flame retardant X S XLPE B Y F Armour Cu Al

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10 and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. The cables are manufactured with sheaths of flame retardant materials. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor according to IEC 60502 -2 u and Al stranded compacted, according to IEC 60228 class 2 Inner semi- conductive layer semi-conductive XLPE compound Insulation XLPE compound Outer semi- conductive layer semi-conductive XLPE compound Metal screen over each phase -I option - Cu tapes laid with overlap over each phase Metal screen -II option - Cu wires laid concentrically Cable assembly Three insulated and screened phases are twisted with fillings and tape support Inner sheatth I -option - exstruded PVC compound flame retardant (bedding) kat A II-option - exstruded PVC compound - kat B and C Armour two steel tapes or two steel galvanized tapes Sheath PVC compound flame retardant Color Black or red

Technical data
Conductor resistance at 20oC Max. conductor temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Um, no more than Test voltage Uo/U AC (~) - 5 min ~ DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min. Temperature of laying Temperature of exploitation Tests Flame retardant According to IEC 60228 90o continuous operation 130o /100h/per year m./ 250o /5 s max./ 6/10 kV 6/10 kV 12 kV 6/10 kV 21 kV 67 kV max. 5 pC - 15x D cable no less than -5 - 30 to 50o according to IEC 60 502-2 IEC 602332-3, Kat A - 7l/m Kat B(3.5l/m)and C(1.5l/m)

Construction data 2XSEYBY-FR, A2XSEYBY-FR 6/10


Nominal Number of cond. and Thickness of Thickness of cross-secnominal insulation| sheath tion of cross section screen 2 N x mm mm mm mm 6/10kV 3x35rm/16 3,4 2,5 16 3x50rm/16 3,4 2,6 16 3x70rm/16 3,4 2,7 16 3x95rm/16 3,4 2.9 16 3x120rm/16 3,4 3.0 16 3x150rm/25 3,4 3.1 25 3x185rm/25 3,4 3.2 25 3x240rm/25 3,4 3.4 25 3x300rm/25 3,4 3.7 25 Cable diameter approx. mm 48.4 51.0 55.0 59.3 62.5 66.4 70.5 76.3 83.2 2XSEYBY-FR A2XSEYBY-FR Mass of Cu Cable weight Mass of Al Cable weight appr. approx. appr. approx. kg/km kg kg/km kg 1010 1363 1968 2732 3440 4245 5311 6981 8661 3639 4203 5117 6239 7178 8433 9831 12001 15023 298 404 584 809 1023 1257 1579 2071 2589 2963 3292 3803 4412 4882 5595 6285 7337 9255

154

ELKABEL

Uo/U - 6/10 kV IEC 60502-2, IEC 60332-3

2XSYRaY- FR A2XSYRaY- FR Cu/Al conductors XLPE insulation Cu screen PVC sheath Armour Al wires PVC sheath flame retardant
MIDDLE VOLTAGE POWER CABLES-THREE CORE, FLAME RETARDANT

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10 kV and frequency 49 Hz to 61 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. The cables are manufactured with sheaths of flame retardant materials They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen Separating layer Armour Sheath Color According to IEC 60502-2 u or Al stranded compacted, according to IEC60228 class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound -I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concentrically PVC compound -flame retardant l wires laid concentrically PVC compound -- flame retardant black or red

Technical data
Conductor resistance at 20oC Max. conductor temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Uo/U, no more than Test voltage AC (~) - 5 min ~ Level of partial discharge at 2*Uo: Bending radius, min Bending radius adjacent to joints or terminations, min Temperature of laying Ambient temperatures Tests: Flame retardancy According to IEC 60228 class 2 90o continuous operation 130o /100h/per year m./ 250o /5 s max./ 6/10 kV 12 kV 6/10 kV 21kV 67 kV m 5pC 15x D cable 12x D cable no less than -5 - 30 to 50o IEC 60332-3 Kat B(3.5l/m)and C(1.5l/m)

Construction data 2XSYRaY-FR, A2XSYRaY-FR 6/10kV


Number of Diameter of cond. and Thickness of Al wires - Thickness of nominal insulation sheath for armor cross section 2 N x mm mm mm mm 6/10kV 1x50 rm 3.4 1.6 1.8 1x70 rm 3.4 1.6 1.9 1x95 rm 3.4 1.6 1.9 1x120rm 3.4 1.6 2.0 1x150rm 3.4 2.0 2.1 1x185rm 3.4 2.0 2.1 1x240rm 3.4 2.0 2.2 1x300rm 3.4 2.0 2.2 1x400rm 3.4 2.0 2.4 1x500rm 3.4 2.5 2.5 Cable diameter approx. mm 27.4 29.2 30.9 32.5 34.9 36.6 39.2 41.4 44.6 49.2 2XSYRaY-FR A2XSYRaY-FR Mass of Cu Cable weight Mass of Al Cable weight appr. approx. appr. approx. kg/km kg kg/km kg 520 720 960 1200 1465 1795 2325 2925 3750 4740 1200 1500 1800 2100 2550 2950 3600 4250 5180 6550 130 190 260 330 405 510 665 830 1060 1410 810 970 1100 1230 1490 1665 1940 2155 2490 3220

ELKABEL

155

EVAVB-F2
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV NBN C 33-121 and comment No 1 and 2

Application
Three-core cables with insulation of polyvinylchloride (PVC) - armored type are designed for transfer and distribution of electrical power networks with voltage of 1000 V. The sheath is flame retardant. The cables are for fixed assembly in lines with unlimited difference levels, for underground, in cable ducts, conduits, shafts, trenches, pipes, shafts, over shelves and grills directly underground in ditch.

Cable construction
Construction Conductor According to NBN C 33-121 u stranded compacted circular and sector, according to NBN C 33-121 (IEC 60228 class 2) PVC compound polymer material two steel tapes, underneath the tapes are laid Cu wires for improving conductivity PVC compound, flame retardant black

Technical data
Conductor resistance at 20oC Operating temperature Overload temperature Nominal voltage Uo/U: Highest system voltage, no more than Test voltage Uo/U AC (~) - 20 min ~ Bending radius, min Temperature of laying Temperature of exploitation Flame retardant NBN C 33-121 (IEC 228) class 2 70 continuous operation 160 /5 s max./ 0.6/1kV 1100 V Between cores and between core and screen (armor)- 13kV 15 x D cable No less than 0 -15 to 70o According to NBN C 30-004 Category F2

Insulation Inner sheath Armour-screen

Sheath Color

Color coding
2-cores: black; blue 3-cores: black; blue; brown or yellow/green; black; blue Neutral core - blue Protective core ( G ) -yellow/green 4-cores: black; blue; brown; black or yellow/green; black; blue; brown;

156

ELKABEL

Cu conductors PVC insulation Armour/screen-st.tapes PVC sheath

LOW VOLTAGE POWER CABLES

Construction data EVAVB-F2


Number of conductors and Thickness of insulation nominal cross section N mm2 4x1.5re 4x2.5re 4x4re 4x6re 4x10re 4x16rm 4x25rm 4x35rm 4x50sm 4x70sm 4x95sm 4x120sm 4x150sm 4x185sm 4x240sm 3x16rm+10re 3x25rm+16rm 3x35rm+16rm 3x50sm+25rm 3x70sm+35rm 3x95sm+50rm 3x120sm+70rm 3x150sm+70tm 3x185sm+95rm 3x240sm+120rm mm 0.8 0.8 0.9 0.9 1.1 1.1 1.3 1.3 1.4 1.4 1.6 1.6 1.8 2.0 2.2 1.1 / 1.1 1.3 / 1.1 1.3 / 1.1 1.4 / 1.3 1.4 / 1.3 1.6 / 1.4 1.6 / 1.4 1.8 / 1.4 2.0 / 1.6 2.2 /1.6 Thickness of steel tapes mm 1.2 1.2 1.2 1.2 1.2 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7 0.7 Armour resistance max. /m 12.1 7.41 4.61 3.08 2.4 2.0 1.6 1.35 1.15 1.0 0.9 0.8 0.75 0.7 0.65 2.0 1.6 1.35 1.15 1.00 0.9 0.8 0.75 0.7 0.65 Thickness of sheath mm 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.2 2.2 2.4 2.4 2.6 2.8 3.0 2.0 2.0 2.0 2.2 2.2 2.2 2.4 2.6 2.8 3.0 15 15.9 17.5 18.7 22.0 25.0 29.5 32.0 34.0 37.3 42.3 46.2 51.0 55.8 62.2 24.5 28.7 31.0 32.9 37.0 42.0 43.1 47.1 51.7 57.6 Cable diameter approx. EVAVB-F2 Mass of Cu approx. kg/km 60 100 160 260 420 720 1000 1520 2140 2960 3980 5000 6210 7630 9840 660 1010 1330 1890 2610 3530 4500 5410 6730 8640 Mass of cable approx. kg/km 500 590 725 860 1200 1550 1900 2600 2960 3860 5100 6400 7750 9450 12000 1460 1740 2400 2730 3500 4500 5850 6900 8500 10650

ELKABEL

157

NHXMH-0 NHXMH-J
LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Uo/U - 300/500 V DIN VDE 0250 part 214

Application
The power insulated conductors flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for Uo/U 300/500 V in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed. The conductors are designed for laying over, in and under plasters in dry and wet premises as well as in brickwork"s and concrete. They are also suitable for outdoor use. The conductors should not be laid directly in vibro concrete or rammed concrete and directly under ground.

Cable construction
Construction Conductor According to VDE 0250-214 u wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228) XLPE compound 2XI1 (DIX8) to VDE 0276-604 according to VDE 0250 and VDE 0293 halogen free compound halogen free compound, flame retardant type LTS 1 grey RAL 7035

Technical data
Conductor resistance at 20C Operating temperature Short circuit temperature Nominal voltage Uo/U: Test voltage Bending radius, min Tests flame retardancy according to VDE 0295 (IEC60228) class 1 or 2 70 160 / 5 s max./ 300/500 V - 2kV 4xD cable DIN VDE 0250-214 VDE 0472 804/ ( IEC 3323/and)

Insulation Core identification Inner sheath Sheath Color

-corrosivity of combustion gases pH - min 4.3; VDE 0472813 (IEC 60754-1and 2) -max100 S/cm -density of smoke gases VDE 0472816 (IEC 61034-1and2) 3 - core 4 - core 5 - core blue brown black grey black or yellow/green blue brown black grey multiple cores black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover

Color coding
Single core - black or yellow-green Double core - blue and brown or yellow-green and black

brown blue brown black black grey grey or or yellow/gre yellow/green en brown blue black brown grey

158

ELKABEL

Cu conductors XLPE insulation LSF sheaths

Construction data NHXMH-o/j 300/500 V


Number of conductors and nominal cross section N x mm2 1x1,5 1x2,5 1x4,0 1x6,0 1x10 1x16 2x1,5 2x2,5 2x4,0 3x1,5 3x2,5 3x4,0 3x6,0 3x10 3x16 3x25 3x35 4x1,5 4x2,5 4x4,0 4x6,0 4x10 4x16 4x25 4x35 5x1,5 5x2,5 5x4,0 5x6,0 5x10 5x16 5x25 5x35 7x1,5 7x2,5 Thickness of Thickness of inner insulation sheath mm 0,5 0,5 0,6 0,6 0,7 0,7 0,5 0,5 0,6 0,5 0,5 0,6 0,6 0,7 0,7 0,9 0,9 0,5 0,5 0,6 0,6 0,7 0,7 0,9 0,9 0,5 0,5 0,6 0,6 0,7 0,7 0,9 0,9 0,5 0,5 mm 1,4 1,4 1,4 1,4 1,4 1,4 0,4 0,4 0,4 0,4 0,4 0,4 0,4 0,6 0,8 0,8 1,0 0,4 0,4 0,6 0,6 0,6 0,8 1,0 1,0 0,4 0,4 0,6 0,6 0,6 0,8 1,0 1,2 0,4 0,4 Thickness of sheath Cable diameter approx. Mass of Cu approx. kg/km 14 29 37 55 94 149 28 46 75 43 70 112 168 282 460 728 1010 57 93 149 223 376 614 970 1346 71 116 187 279 470 767 1213 1683 100 163 Mass of cable approx. kg/km 48 61 79 112 160 230 108 140 205 131 178 239 325 503 769 1164 1542 150 211 309 242 630 969 1490 1935 178 240 380 480 730 1145 1798 2495 210 302

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

mm 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,4 1,6 1,6 1,6 1,8 1,8 1,4 1,4 1,6 1,6 1,6 1,6 1,8 1,8 1,4 1,4 1,6 1,6 1,6 1,8 1,8 1,8 1,4 1,6

min 5,0 5,4 6,0 6,4 7,4 8,6 8,0 8,8 10,0 8,4 9,3 10,5 12,0 14,5 17,0 21,0 23,5 9,0 10,0 12,0 13,0 15,5 19,0 23,5 26,5 9,6 10,5 13,0 14,5 17,0 21,0 25,5 28,5 10,0 12,0

max 8,8 9,4 10,0 10,5 12,0 13,5 9,4 10,5 12,0 9,8 11,0 12,5 14,0 16,5 20,5 25,5 28,5 10,5 11,5 14,0 15,5 18,0 22,5 28,0 31,0 11,5 12,5 15,5 16,5 19,5 25,0 30,5 34,5 12,0 14,0

ELKABEL

159

(N)HXH-FE 180
LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Uo/U - 0.6/1 kV DIN VDE 0266

Application
The power cables with retaimnent of insulation 180 min. flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for used in electrical installations for break-downsupply, signalization and control in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport public buildings - hospitals, hotels, theaters, cinemas,public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed The cables are designed for fixed laying in dry and wet premises and outdoor, but not directly underground or in water. Laying in cable duct is allowed in case precautions are taken no water collection in the duct to be guaranteed.

Cable construction
Construction Conductor According to VDE 0266 u wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228) double layer insulation consist ing of mica tape and crosslinked polymer according to VDE 0207 part 23 HI1 tapes or extruded layer plastic compound, type HM4 according to VDE 0207 part.24 orange

Technical data
Conductor resistance at 20C Operating temperature Short circuit temperature Nominal voltage Uo/U: Test voltage Bending radius, min Tests Retainment of insulation according to IEC 331 Temperature range according to VDE 0295 (IEC60228) cl.1 or 2 90 continuous operation 250 / 5 s max./ 0.6/1 V - 4kV 15xD cable according to DIN VDE 0266part 3 and IEC 331 180 min -30 to +70C 5 - core Multiple core

Insulation

Inner sheath Sheath

Color

Color coding
Single core - black or yellow-green Double core - blue and brown or yellow-green and black

3 - core

4 - core

brown; blue; brown; blue; black with number black; brown;black mark on cores black grey grey; black or grey; or or black with number or yellow/gre yellow/green; yellow/green; mark on cores and en; blue; blue; brown; yellow/green core brown brown black; grey in the outer cover black; grey

160

ELKABEL

Cu conductors XLPE insulation LSF sheaths

Construction data (N)HXH FE 180 0.6/1 kV


Number of conductors and nominal cross section Cable diameter approx. Mass of Cu approx. kg/km 37 56 94 149 28 46 75 112 188 43 70 112 168 282 460 728 57 93 149 223 376 614 970 1346 1817 71 116 187 279 470 767 100 171

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Mass of cable approx.

N mm2 1x4,0re 1x6,0re 1x10re 1x16re 2x1,5re 2x2,5re 2x4,0re 2x6,0re 2x10re 3x1,5re 3x2,5re 3x4,0re 3x6,0re 3x10re 3x16rm 3x25rm 4x1,5re 4x2,5re 4x4,0re 4x6,0re 4x10re 4x16rm 4x25rm 4x35rm 4x50rm 5x1,5re 5x2,5re 5x4,0re 5x6,0re 5x10re 5x16rm 7x1,5re 12x1,5re

mm 8 9 10 11 12 13 14 15 16 15 16 17 18 20 22 26 15 16 17 19 20 22 26 29 33 17 19 20 22 24 27 19 23

kg/km 105 130 170 250 190 220 280 340 450 240 290 340 450 620 850 1300 280 350 440 560 760 1100 1600 1940 2570 330 410 520 660 950 1300 380 580

ELKABEL

161

N2XH-0/J
LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Uo/U - 0.6/1 kV VDE 0276-604 (HD 604 S1)

Application
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.

Cable construction
Construction Conductor According to VDE 0276-604 u wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228) XLPE compound 2XI1 (DIX8) to VDE 0276-604 Core identification according to VDE 0276-604 and VDE 0293 halogen free compound halogen free compound, flame retardant type LTS 1 black

Technical data
Conductor resistance at according to VDE 0295 20C (IEC60228) cl.1 or 2 Operating temperature 90 continuous operation Overload temperature 130 /100h per year max/ Short circuit temperature 250 / 5 s max./. Nominal voltage Uo/U 0.6/1 kV no more than 1.2 kV Highest system voltage Test voltage C - 5 min between cores - 3.5 V Bending radius, min 6xD cable Temperature of laying no less than 0 Temperature of exploita-30 to 50 tion VDE 0276-604 Tests VDE 0472 p804/ -flame retardant ( IEC 332-3/ and ) -corrosivity of combustion gases and conductivity VDE 0472p813 (IEC 60754pH - min 4.3; -max100 1and 2 S/cm -density of smoke gases VDE 0472p816 (IEC 61034-1and 2) 3 - core 4 - core 5 - core multiple core

Insulation

Inner sheath Sheath Color

Color coding
Single core - black or yellow/green Double core - brown ; blue or yellow/green; black

brown,bla blue; brown; blue; brown; black with number ck grey black; grey; mark on cores black, grey or black or or yellow/gre yellow/green; or black with number en; blue ; brown;black; yellow/green; mark on cores and brown blue; brown; yellow/green core grey black; in the outer cover grey

162

ELKABEL

Cu conductors XLPE insulation LSF sheaths

Construction data N2XH - 0/j 0.6/1 kV


Number of Cable conductors and diameter nominal cross approx. section N mm2 1x4,0 1x6,0 1x10 1x16 1x25 1x35 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 2x1,5 2x2,5 2x4,0 2x6,0 2x10 2x16 2x25 3x1,5 3x2,5 3x4,0 3x6,0 3x10 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x50/25 3x70/35 3x95/50 3x120/70 3x150/70 3x185/95 3x240/120 mm 9,2 10,2 11,2 12,3 14,2 15,4 16,9 17,8 20,2 22,3 24,4 25,9 28,7 32,8 12,2 12,8 13,4 15,7 16,5 17,6 23,2 12,2 13,2 14,4 15,3 16,5 20,2 23,8 26,9 29,2 32,8 37,3 41,5 45,4 50,2 56,3 32,2 37,4 41,5 42,0 48,5 53,0 63,0 Mass of core approx. kg/km 38 58 97 153 243 337 454 656 911 1147 1415 1770 2327 2887 28 46 75 112 188 298 485 43 70 112 168 282 447 728 1010 1363 1968 2732 3440 4245 5311 6981 1680 2352 3216 4128 4992 6240 8064 Mass of cable approx. kg/km 143 159 212 268 379 492 624 826 1202 1505 1705 2202 2748 3297 182 215 273 342 454 597 981 205 245 332 413 548 794 1205 1604 1805 2495 3303 4048 4895 5110 7805 2205 2948 3908 4805 5745 7210 9155

Construction data N2XH - 0/j 0.6/1 kV


Number of Cable conductors and diameter nominal cross approx. section N mm2 4x1,5 4x2,5 4x4,0 4x6,0 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 5x1,5 5x2,5 5x4,0 5x6,0 5x10 5x16 7x1,5 10x1,5 12x1,5 14x1,5 19x1,5 24x1,5 30x1,5 *16x1.5 7x2,5 10x2,5 12x2,5 14x2,5 19x2,5 24x2,5 30x2,5 7x4,0 12x4,0 mm 13,2 14,2 15,4 16,5 17,6 19,5 26,2 29,2 32,4 37,3 40,6 44,8 50,5 53,0 61,8 14,2 15,2 16,5 17,5 19,3 22,4 14,2 16,2 18,5 19,5 21,3 22,4 23,8 17.7 15,2 18,2 19,5 20,4 21,6 24,5 27,3 17,2 21,5 Mass of core approx. kg/km 57 93 149 223 376 595 970 1346 1817 2624 3643 4587 5660 7082 9308 71 116 187 279 470 744 100 142 171 199 270 341 426 227 163 232 279 325 441 557 697 261 448 Mass of cable approx. kg/km 232 295 385 485 675 934 1442 1903 2305 3205 4204 4306 6355 7805 10295 275 335 453 564 786 1145 315 415 458 535 648 762 897 591 410 545 605 672 844 1048 1235 235 815

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

ELKABEL

163

N2XSH NA2XSH
MIDDLE VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Uo/U - 6/10,12/20kV VDE 0276-622

Application
The single-core cables flame retardant with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz. The cables are manufactured with sheaths of halogen free flame retardant materials. They are suitable for use in distribution installations, electric power stations and substations for fixed indoor assembly in cable ducts and conduits, over shelves and grilles.They should not be laid directly underground or in water. The cables with halogen free materials are with low halogen free smoke emission and corrosivity.The cables should not be laid in or near nuclear stations.

Cable construction
Construction Conductor according to DIN VDE 0276-622 u and Al stranded compacted, wires according to IEC 60228 cl.2 and VDE 0295 cl.2 semi-conductive XLPE compound XLPE compound

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature According to IEC60228 class 2 and VDE 0295 class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max/ 6.35/11 kV 6/10 kV; 12/20 kV 12 kV; 24 kV 6/10 12/20 kV 21 kV; 42 kV 67 kV; 134 kV 15xD cable no less than -5 -30 to 50 VDE 0276-622 VDE 0276-622(VDE 0472-804 method C) - IEC 332-3/B

Inner semiconductive layer Insulation Outer semiconductive layer Metal screen

semi-conductive XLPE compound and semi-conductive tape Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. layer of plastic tape halogen free compound, flame retardant type HM4 to VDE 0276-622 black

Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Bending radius, min Temperature of laying Temperature of exploitation Tests -flame retardant -corrosivity ofcombustion gases - - conductivity -density of smoke gases

Separating layer Sheath

Color

min. 4.3 . 100S/cm VDE 0276-622 method to VDE0472-816

164

ELKABEL

Cu / Al conductors XLPE insulation Cu screen LSF sheath

Construction data N2XSH, NA2XSH 6/10; 12/20 kV


Number of Thickne Thickne Nominal conductors ss of crossss of and nominal insula- sheath section cross section tion of screen N mm2 6/10 kV 1x35/16 1x50/16 1x70/16 1x95/16 1x120/16 1x150/25 1x185/25 1x240/25 1x300/25 1x400/35 1x500/35 12/20 kV 1x35/16 1x50/16 1x70/16 1x95/16 1x120/16 1x150/25 1x185/25 1x240/25 1x300/25 1x400/35 1x500/35 mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 mm2 16 16 16 16 16 25 25 25 25 35 35 16 16 16 16 16 25 25 25 25 35 35 Cable diameter approx. min mm 23 24 26 27 29 30 32 34 36 40 43 27 28 30 31 33 34 36 39 41 44 47 max mm 28 29 31 32 34 35 37 39 41 45 48 32 33 35 36 38 39 41 44 46 49 52 N2XSH Mass of Cu approx kg/km 493 604 793 1033 1255 1596 1930 2454 2980 3836 4807 493 604 793 1033 1255 1596 1930 2454 2980 3836 4807 Mass of cable approx. kg/km 1145 1297 1550 1854 2128 2524 2922 3536 4149 5117 6209 1372 1531 1795 2110 2394 2799 3208 3837 4466 5478 6613 Mass of Al approx. kg/km 94 127 183 254 321 394 495 649 812 1043 1374 94 127 183 254 321 394 495 649 812 1043 1374 NA2XSH Mass of Cu approx. kg/km 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 265 265 265 265 363 363 Mass of cable approx. kg/km 922 996 117 1251 1371 1587 1752 1996 2245 2688 3192 1148 1230 1362 1507 1636 1862 2038 2298 2562 3049 3543

MIDDLE VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

ELKABEL

165

MIDDLE VOLTAGE POWER CABLES-THREE CORE HALOGEN FREE, FLAME RETARDANT

N2XSEH NA2XSEH

Uo/U - 6/10,12/20kV VDE 0276-622

Application
The three-core cables flame retardant with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz. The cables are manufactured with sheaths of halogen free flame retardant materials. They are suitable for use in distribution installations, electric power stations and substations for fixed indoor assembly in cable ducts and conduits, over shelves and grilles. They should not be laid directly underground or in water. The cables with halogen free materials are with low halogen free smoke emission and corrosivity.The cables should not be laid in or near nuclear stations.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen According to DIN VDE 0276-622 u and Al stranded compacted wiresto IEC 60228 cl.2 and VDE 0295 cl.2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound and semi-conductive tape Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase three insulated and screenesd phases are twisted with fillings and tape support PVC compound halogen free compound, flame retardant halogen free compound, flame retardant type HM4 to VDE 0276-622 black

Technical data
Conductor resistance at According to IEC60228 class 2 20C and VDE 0295 class 2 Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Bending radius, min Temperature of laying Temperature of exploitation Tests -flame retardant -corrosivity ofcombustion gases - - conductivity -density of smoke gases 90 continuous operation 130 /100h per year max./ 250 /5 s max/ 6.35/11 kV 6/10 kV; 12/20 kV 12 kV; 24 kV 6/10 12/20 kV 21 kV; 42 kV 67 kV; 134 kV 15xD cable no less than -5 -30 to 50 VDE 0276-622 VDE 0276-622(VDE 0472-804 method C) - IEC 332-3/B

Cable assembly

Inner sheath Sheath

Color

min. 4.3 . 100S/cm VDE 0276-622 method to VDE0472-816

166

ELKABEL

Cu / Al conductors XLPE insulation Cu screen LSF sheath

MIDDLE VOLTAGE POWER CABLES-THREE CORE HALOGEN FREE, FLAME RETARDANT

Construction data N2XSEH, NA2XSEH 6/10 kV


Number of conductors and nominal cross section N x mm2 6/10kV 3x35rm/16 3x50rm/16 3x70rm/16 3x95rm/16 3x120rm/16 3x150rm/25 3x185rm/25 3x240rm/25 3x300rm/25 Thickness Thickness Nominal Cable diameter of of crossapprox. insulation sheath section of screen mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 mm2 16 16 16 16 16 25 25 25 25 mm 46,2 48,8 53,0 57,1 60,6 64,2 68,5 74,3 79,6

N2XSEH
Mass of Cu approx kg/km 1010 1363 1968 2732 3440 4245 5311 6981 8661 Mass of cable approx. kg/km 3276 3834 4784 5930 6923 8217 9691 11963 14294

NA2XSEH
Mass of Al approx. kg/km 298 404 584 809 1023 1257 1579 2071 2589 Mass of cable approx. kg/km 2619 2923 3470 4103 4627 5379 6144 7331 8526

ELKABEL

167

Cu/XLPE/LSF/SWA/LSF

Uo/U - 0.6/1 kV BS 6724-1997

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Application
The power and control cables with insulation of cross-linked polyethylene (XLPE) type LSOH are flame retardant, with low halogen free smoke emission and corrosion at fire conditions and are suitable for use in electrical installations for nominal voltage Uo/U 0.6/1 kV. Cables are designed with sheath of halogen free materials, flame retardant, free smoke emission and corrosion, and non-magnetic armor of l wires. They are suitable for use in distribution networks, electrical power stations (NPP and TPP) and substations, metro. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial sites, indoor installations, in cable ducts, conduits and shafts, over shelves and grills and outdoor shelter.

Cable construction
Construction Conductor According to BS 6724-97 u or Al stranded compacted, wires according to BS 6360 (IEC 228) cl.2 XLPE compound 2-cores - red; black 3-cores - red; yellow; blue 4-cores - red; yellow; blue; black 5-cores - red; yellow; blue; black Control - black with white num bers or white with black numbers halogen free compound steel galvanized wires, laid con centrically Halogen free compound, flame retardant type LTS 1 black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature According to BS 6360 (IEC228) class 2 90 continuous operation 130 /100h per year max/ 250 / 5 s max./. 0.6/1 kV 1.2 kV Between cores - 3.5 V Between core and armor- 3.5 V 6xD cable

Insulation Color

Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage C - 5 min Bending radius, min

Inner sheath Armour Sheath Color

Temperature of laying no less than 0 Temperature of exploitation -30 to 50 Flame retardant According toBS 4066-3 category C (IEC 332-3 category ) Cu cores - 50*n*S core where: n is number of cores and S is nominal cross-section of cores in mm

Force of strain in laying N max.

168

ELKABEL

Cu conductors XLPE insulation LSF sheath Armour st. wires LSF sheath

Construction data Cu/XLPE/LSF/SWA/LSF 0.6/1 kV


Number of conductors and nominal cross section N x mm2 2x1.5rm 2x2.5rm 2x4.0rm 2x6.0rm 2x10rm 2x16rm 2x25rm 2x35rm 3x1.5rm 3x2.5rm 3x4.0rm 3x6.0rm 3x10rm 3x16rm 3x25rm 3x35rm 4x1.5rm 4x2.5rm 4x4.0rm 4x6.0rm 4x10rm 4x16rm 4x25rm 4x35rm 4x35sm 4x50sm 4x70sm 4x95sm 4x120sm 4x150sm 4x185sm 5x1.5rm 5x2.5rm 5x4.0rm 5x6.0rm 5x10rm 5x16rm 5x25rm 5x35rm 7x1.5rm 12x1.5rm 19x1.5rm 27x1.5rm 37x1.5rm 7x2.5rm 12x2.5rm 19x2.5rm 27x2.5rm 37x2.5rm Thickness of insulation Diameter of St wires for armour mm 0.9 0.9 0.9 0.9 0.9 1.25 1.25 1.6 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 0.9 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 0.9 0.9 0.9 1.25 1.25 1.60 1.60 1.60 0.9 1.25 1.25 1.6 1.6 0.9 1.25 1.6 1.6 1.6 Thickness of sheath Cable diameter approx. Mass of Cu approx. kg/km 28 46 75 110 182 303 470 652 42 69 110 165 275 450 700 980 55 92 146 218 363 592 925 1303 1303 1857 2601 3540 4460 5575 6880 69 114 182 275 455 745 1165 1640 96 165 260 373 506 160 525 590 621 845 Mass of cable approx. kg/km 283 347 411 493 647 950 1282 1727 300 379 462 555 847 1111 1575 2113 321 415 513 737 974 1277 1972 2470 2324 2961 4209 5374 6926 8266 9988 367 473 594 850 1127 1662 2349 2964 421 717 922 1361 1629 549 946 1418 1824 2006

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

mm 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7

mm 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.3 1.4 1.4 1.4 1.5 1.6 1.7 1.8 1.3 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.9 2.1 2.2 2.4 2.6 2.6 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 1.4 1.5 1.6 1.7 1.7 1.4 1.6 1.7 1.8 1.8

mm 12.1 12.9 14.7 15.9 18.0 21.9 26.7 29.2 12.8 14.1 15.8 18.0 21.2 23.1 28.2 30.8 13.3 15.0 16.4 18.7 21.1 23..4 28.9 33.7 28.6 32 37.7 41.7 47.1 51.4 56.6 14.3 16.3 19.0 20.9 25.8 28.4 33.5 36.6 15.2 18.5 21.1 26.7 29.0 17.1 22.4 26.6 30.7 33.8

ELKABEL

169

Cu/XLPE/LSF/AWA/LSF

Uo/U - 0.6/1 kV BS 6724 - 1997

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Cu conductors XLPE insulation LSF sheath Armour Al. wires LSF sheath

Application
The single-core power cables with insulation of cross-linked polyethylene (XLPE) type LSOH are flame retardant, with low halogen free smoke emission and corrosion at fire conditions and are suitable for use in electrical installations for nominal voltage Uo/U 0.6/1 kV. Cables are designed with sheath, which do not contain halogen materials, flame retardant, free smoke emission and corrosion, and non-magnetic armor of l wires. They are suitable for use in distribution networks, electrical power stations and substations. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial sites, indoor installations, in cable ducts, conduits and shafts, over shelves and grills and outdoor shelter.

Cable construction
Construction Conductor According to BS 6724-1997 u stranded circular and sec tor, according to BS 6360 (IEC60228) cl. 2 Extruded XLPE compound black or red halogen free compound l wires laid concentrically halogen free compound, flame retardant type LTS 1 black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Uo/U, no more than Test voltage C - 5 min Bending radius, min Temperature of laying Temperature of exploitation Flame retardant According to BS 6360 (IEC60228) class 2 90 continuous operation 130 /100h per year max/ 250 /5 s max./ 0.6/1 kV 1.2 kV Between cores and armor 3.5kV 6x D cable no less than 0 -30 to 500 According to BS 4066-3 Category (IEC 332-3 category ) Cu cores -50*n*S core Where: n is number of cores and S is nominal cross-section of cores in mm

Insulation Color Inner sheath Armour Sheath Color

Force of strain in laying N max.

Construction data Cu/XLPE/LSF/AWA/LSF 0.6/1 kV


Number of conductors and nominal cross section N x mm2 Uo/U0.6/1kV 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm Thickness of insulation mm 1.4 1.6 1.7 1.8 2.0 2.2 Diameter of Al wires for armour mm Thickness of sheath mm 1.7 1.8 1.8 1.9 2.0 2.1 Cable diameter approx. mm 26.3 28.7 31.4 34.1 38.9 42.8 Cu /XLPE/LSF/AWA/LSF Mass of Mass of Cu cable approx. approx. kg/km kg/km 1378 1703 2208 2765 3680 4600 1970 2370 2960 3610 4600 5680

1.6 1.6 1.6 1.6 2.0 2.0

170

ELKABEL

Cu/XLPE/CTS/LSF/AWA/LSF

Uo/U - 6.35/11 kV BS 7835 - 2000

Cu conductors XLPE insulation Cu screen LSF sheath Armour Al wires LSF sheath

MIDDLE VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Application
The single-core power cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6.35/11 kV and frequency 49 Hz to 61 H. Cables are designed with sheath of halogen free materials, flame retardant, free smoke emission and corrosion, and non-magnetic armor of l wires. They are suitable for use in distribution networks, electrical power stations and substations. These cables are for fixed assembly in lines with unlimited difference levels for indoor installations, in cable ducts, conduits and shafts, over shelves and grills and outdoor shelter.

Cable construction
Construction Conductor According to BS 6622-1999 u or Al stranded compacted, wires according to BS 6360 (IEC 60228) class2

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at 12.5 kV Bending radius, min Temperature of laying Temperature of exploitation Flame retardant According to BS 6360 (IEC228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max/ 6.35/11 kV 12 kV; 25.5 V 10pC 15xD cable no less than -5 -30 to 50 According to BS 4066-3 category (IEC 332-3 category ) Al cores- 30*n*S core Cu cores- 50*n*S core where: n is number of cores and S is cross-section of cores in mm

Inner semisemi-conductive XLPE compound conductive layer Insulation XLPE compound

Outer semisemi-conductive XLPE compound conductive layer Metal screen -I option - Cu tapes laid with overlap -II option - Cu wires laid con centrically halogen free compound l cores laid concentrically halogen free fire retardant compound type LTS 1 red, black

Separating layer Armour Sheath Color

Force of strain in laying N max.

Construction data Cu/XLPE/CTS/LSF/AWA/LSF 6.35/11 kV


Number of conductors and nominal cross section N x mm2 Uo/U 6.35/11kV 1x50rm 1x70rm 1x95rm 1x120rm 1x150rm 1x185rm 1x240rm 1x300rm 1x400rm 1x500rm Thickness of insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Diameter of Al wires for armour mm 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 Thickness of sheath mm 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.2 2.4 2.5 Cable diameter approx. mm 28.5 30.4 32.1 33.9 36.3 38.1 40.7 43.0 46.5 50.9 Cu /XLPE/CTS/LSF/AWA/LSF Mass of Mass of Cu cable approx. approx. kg/km kg/km 520 720 960 1200 1465 1795 2325 2925 3750 4740 1200 1550 1850 2150 2650 3100 3700 4400 5250 6800

ELKABEL

171

N2XH
LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Uo/U - 0.6/1 kV VDE 0276-604 (HD 604 S1)

Application
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.

Cable construction
Construction Conductor According to VDE 0276-604 u wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228) XLPE compound 2XI1 (DIX8) to VDE 0276-604 according to VDE 0276-604 and VDE 0293 halogen free compound of plain round copper wires and one or two transverse counter helix of copper tapes halogen free compound, flame retardant type LTS 1 black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage C - 5 min Bending radius, min according to VDE 0295 (IEC60228) cl.1 or 2 90 continuous operation 130 /100h per year max/ 250 / 5 s max./. 0.6/1 kV no more than 1.2 kV between cores - 3.5 V 6xD cable

Insulation Core identification Inner sheath Concentric Conductor Sheath Color

Temperature of laying no less than 0 Temperature of exploitation -30 to 50 Tests -flame retardant -corrosivity of combustion gases and conductivity pH - min 4.3; -max100 S/cm -density of smoke gases VDE 0472p813 (IEC 60754-1 and 2) VDE 0472p816 (IEC 61034-1 and 2) VDE 0276-604 VDE 0472 p804/ ( IEC 332-3/ and )

Color coding
Single core - black or yellow/green Double core - black ; blue or yellow/green; black

3- core

4 - core

5 - core

multiple core

black; blue; black; blue; black with number Black; blue; brown; black; brown; black; mark on cores or brown black black with number or or or mark on cores yellow/green; yellow/green; yellow/green; and yellow/green black; blue black; blue ; core in the outer black; blue brown; brown; black; cover

172

ELKABEL

Cu conductors XLPE insulation Cu concentric conductor LSF sheaths

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Number of wires and nominal cross section

Shape

Concentric Outer diameter conductor of cable cross section approx. mm2 1,5 2,5 4,0 6,0 10 16 25 35 1,5 2,5 4,0 6,0 10 16 25 35 50 1,5 2,5 4,0 6,0 10 16 16 25 16 35 25 35 16 25 50 35 70 50 95 70 120 70 150 95 120 1,5 2,5 4,0 6,0 10 16 16 16 25 16 25 35 50 70 70 95 120 mm 7,9 8,5 9,4 9,9 11,3 12,8 12,9 16,4 13,0 13,7 15,9 17,1 19,1 21,0 25,1 27,8 31,5 13,5 14,3 16,6 17,7 20,0 22,1 27,8 26,6 29,1 29,4 32,7 27,1 26,6 29,6 30,6 33,6 34,1 38,2 39,4 38,3 41,6 44,7 45,8 49,0 54,5 14,3 16,3 17,8 19,0 21,5 23,8 29,0 32,0 36,4 29,8 33,1 38,4 42,6 43,1 50,7 55,3 62,3

Cu weight

Cable weight approx.

N x mm2 1x1,5 1x2,5 1x4,0 1x6,0 1x10 1x16 1x25 1x35 2x1,5 2x2,5 2x4,0 2x6,0 2x10 2x16 2x25 2x35 2x50 3x1,5 3x2,5 3x4,0 3x6,0 3x10 3x16 3x25 3x25 3x35 3x35 3x50 3x35 3x35 3x50 3x50 3x70 3x70 3x95 3x95 3x120 3x120 3x150 3x150 3x185 3x240 4x1,5 4x2,5 4x4,0 4x6,0 4x10 4x16 4x25 4x35 4x50 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240

re re re re re re rm rm re re re re re re rm rm rm re re re re re re rm rm rm rm rm sm sm sm sm sm sm sm sm sm sm sm sm sm sm re re re re re re rm rm rm sm sm sm sm sm sm sm sm

kg/km 27 47 74 108 182 297 465 654 45 68 110 164 274 435 703 980 1343 56 90 147 243 365 580 855 938 1127 1317 1581 1339 1161 1593 1819 2265 2584 3151 3692 4038 4443 4827 5543 6051 7881 70 136 183 297 457 725 1090 1456 1998 1495 2044 2911 4041 5162 6214 7826 10150

kg/km 98 122 163 203 286 410 606 807 230 273 375 458 619 841 1276 1642 2193 252 305 425 528 724 999 1440 1524 1813 1987 2415 1644 1627 2174 2260 2932 3097 4004 4336 4925 5124 5890 6352 7329 9399 284 382 494 620 860 1196 1764 2246 3024 2060 2730 3758 5054 6246 7548 9374 12124

ELKABEL

173

2XBH/2XBH
LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Uo/U - 0.6/1 kV IEC 60502-1 and VDE 0276-604 (HD 604 S1)

Application
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.

Cable construction
Construction Conductor According to IEC 60502-1 Cu solid or stranded wires class 1 or 2 according to IEC 60228 XLPE compound color code acc. to VDE 0276-604 halogen free compound two steel tapes or two galvanized steel tapes halogen free compound, flame retardant type HM4( LTS 1 ) black

Technical data
Conductor resistance Operating temperature Overload temperature Short circuit temperature Nominal voltage Highest system voltage Test voltage, AC 50 Hz Bending radius single core multicore Temperature of laying Temperature of exploitation Tests -flame retardant -corrosivity of combustion According to IEC 60228 90C 130C/100h per year 250C ( 5 sec.) 0.6/1 kV 1.2 kV 4.0 kV 15 x Dcable 15 x Dcable no less than 0
-30 to 70C

Insulation Identification of cores Inner sheath Armour

IEC 60502-1 and VDE 0276604 VDE 0472 p804/ ( IEC 3323/ and )

Sheath

gases and conductivity pH - min 4.3; max100S/cm -density of smoke gases VDE 0472p813 (IEC 607541and2 VDE 0472p816 (IEC 610341and2)

Color

Color coding
Single core - black or yellow-green Double core - blue and brown or yellow-green and black

3 - core

4 - core

5 - core

Multiple core

with blue ; brown; black marknumber on blue; brown; black; grey brown; cores black; grey black black; grey or or or or black with numyellow/green yellow/green yellow/green ber mark on ; brown; ; blue; ; blue; brown black ;grey cores and yelbrown; black; grey low/green core in the outer cover

174

ELKABEL

Cu / Al conductors XLPE insulation Armour-st. tapes LSF sheaths

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Construction data 2XBH


Mass Mass of Number of Cable of conductors Type of diameter cable concore approx. and nominal ductors approx. approx. cross section mm2 mm kg/km N x mm2 5x4,0 5x6,0 5x10 5x16 5x25 5x35 5x50 5x70 7x1,5 8x1,5 10x1,5 12x1,5 14x1,5 16x1,5 19x1,5 20x1,5 21x1,5 24x1,5 27x1,5 30x1,5 37x1,5 7x2,5 8x2,5 10x2,5 12x2,5 14x2,5 16x2,5 19x2,5 20x2,5 21x2,5 24x2,5 27x2,5 30x2,5 37x2,5 7x4,0 8x4,0 10x4,0 7x6,0 8x6,0 10x6,0 re re re re rm rm rm rm re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re 19,6 21,0 23,2 25,7 31,7 34,9 40,1 45,3 16,9 18,2 19,9 20,4 21,2 22,1 23,0 24,0 24,0 26,1 26,6 27,5 29,4 18,0 19,6 21,5 22,0 22,9 23,9 25,0 26,1 26,1 28,6 29,2 30,2 32,3 20,9 22,9 25,4 22,4 19,5 27,4 187 279 470 744 1213 1683 2271 3280 100 114 142 171 199 227 270 284 299 341 384 426 526 163 186 232 279 325 372 441 464 488 557 627 697 859 261 299 373 391 447 559 590 715 955 1270 1925 2455 3390 4455 420 485 575 610 675 725 795 855 865 1005 1055 1125 1300 505 590 705 760 830 905 1005 1080 1095 1290 1360 1465 1700 700 825 1030 885 1045 1270 Number of conductors and nominal cross section N x mm2 2x6,0 2x10 2x16 2x25 2x35 2x50 3x6,0 3x10 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 3x6,0 3x10 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 4x6,0 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240

Construction data A2XBH


Mass Mass of Type of Cable of cable con- diameter core ductors approx. approx. approx. mm2 mm kg/km re re re rm rm rm re re re rm rm rm sm sm sm sm sm sm sm re/re re/re re/re rm/rm rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm re re re rm rm sm sm sm sm sm sm sm 17,5 19,1 21,0 25,1 27,3 30,7 18,3 20,0 22,1 26,6 29,1 32,8 33,0 38,0 40,0 44,2 47,9 53,3 58,7 19,2 21,0 23,2 27,8 30,1 33,0 38,2 42,4 45,6 50,2 54,5 60,9 66,7 19,6 21,5 23,8 29,0 31,9 33,0 38,2 42,4 45,6 50,2 54,5 60,9 38 56 88 144 199 269 56 83 132 216 298 404 584 809 1023 1257 1579 2071 2589 68 102 160 261 343 476 684 944 1218 1452 1848 2412 3008 75 111 176 288 398 539 779 1079 1364 1676 2106 2762 405 480 580 815 960 1200 440 525 640 900 1080 1355 1360 1925 2185 2620 3115 3855 4620 470 560 689 965 1135 1305 1805 2235 2620 3080 3680 4560 5465 500 605 740 1060 1280 1355 1910 2380 2775 3325 3955 4940

mm2

+ + + + + + + + + + + + +

4 6 10 16 16 25 35 50 70 70 95 120 150

ELKABEL

175

2XSsH/(N)2XSsH 2XSH/(N)2XSH

Uo/U - 0.6/1 kV IEC 60 502-1 and VDE 0276-604 (HD 604 S1)

LOW VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Application
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed

Cable construction
Construction Conductor Insulation Core identification Inner sheath Metal screen Sheath According to VDE 0276-604 u wires according toIEC 60228 XLPE compound 2XI1 (DIX8) to VDE 0276-604 according to VDE 0276-604 and VDE 0293 halogen free compound for 2XSsH - copper breid for 2XSsH - copper tape halogen free compound, flame retardant type HM4(LTS 1) Black

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U Highest system voltage Test voltage C - 5 min Bending radius, min according to VDE 0295 (IEC60228) cl.1 or 2 90 continuous operation 130 /100h per year max/ 250 / 5 s max./. 0.6/1 kV no more than 1.2 kV between cores - 3.5 V 6xD cable

Color

Temperature of laying no less than 0 Temperature of exploitation -30 to 50 Tests -flame retardant -corrosivity of combustion gases and conductivity IEC 60502-1 and VDE 0276-604 VDE 0472 p804/ ( IEC 332-3/ and )

pH - min 4.3; -max100 S/cm VDE 0472p813 (IEC 60754-1 and 2) -density of smoke gases VDE 0472p816 (IEC 61034-1 and 2)

Color coding
Single core - black or yellow/green. Double core - black ; blue or yellow/green; black

3- core

4 - core

5 - core

multiple core

black; blue; black; blue; Black with numBlack; blue; brown; black; brown; black; ber mark on cores brown black or or or or yellow/green; yellow/green; black with number yellow/green; black; blue mark on cores black; blue black; and Y / G brown ; brown; blue ; core in the outer black; cover

176

ELKABEL

Uo/U - 6.35/11 kV Cu/XLPE/CTS/LSF/SWA/LSF Standart: BS 7835-2000


Cu conductors* XLPE insulation Cu screen LSF sheath Armour st. wires LSF sheath

MIDDLE VOLTAGE POWER CABLES HALOGEN FREE, FLAME RETARDANT

Application
The three-core power cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6.35/11 kV and frequency 49 Hz to 61 H in urban and district electrical networks and for electrical supply of transformer substations, small and medium industrial plants. Cables are designed with sheath of halogen free materials, flame retardant, free smoke emission and corrosion. They are suitable for use in distribution networks, electrical power stations and substations. These cables are for fixed assembly in lines with unlimited difference levels for indoor installations, in cable ducts, conduits and shafts, over shelves and grills and outdoor shelter.

Cable construction
Construction Conductor Accordlng to BS 6622-1999 Cu or Al stranded compacted, wires according to BS 6360 (lEC 228) class 2

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage AC () - 15 min Level of partial discharge at 12.5 kV Bending radius, min Temperature of laying Temperature of exploitation Flame retardant According to BS 6360 (IEC228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max/ 6.35/11 kV 12 kV; 25.5 V 10pC 15xD cable no less than 0 -30 to 50 According to BS 4066-3 category (IEC 332-3 category ) Al cores- 30*n*S core Cu cores- 50*n*S core where: n is number of cores and S is cross-section of cores in mm

Inner semisemi-conductive XLPE conductive layer compound Insulation XLPE compound

Outer semisemi-conductive XLPE conductive layer compound Metal screen -I option - Cu tapes over each phase laid with overlap -II option - Cu cores laid concentrically Three insulated and screened phases are twisted with fillings and tape support halogen free compound steel galvanized wires laid conhalogen free fire retardant compound type LIS 1 red, black

Cable assembly

Separating layer Armour centrically Sheath Color

Force of strain in laying N max.

Construction data Cu/XLPE/CTS/LSF/SWA/LSF 6.35/11 kV


Number of conductors and nominal cross section N x mm2 Uo/U 6.35/11 kV 3x25rm 3x35rm 3x50rm 3x70rm 3x95rm 3x120rm Thickness of insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 Diameter of St wires for armour mm 2.5 2.5 2.5 2.5 2.5 2.5 Thickness of sheath mm 2.4 2.5 2.6 2.7 2.8 3.0 Cable diameter approx. mm 48.8 51.6 54.6 58.5 62.6 66.6 Cu /XLPE/CTS/LSF/AWA/LSF Mass of Mass of Cu cable approx. approx. kg/km kg/km 850 1140 1560 2140 2855 3570 4200 4900 5600 6500 7500 8500

ELKABEL

177

COMMUNICATION CABLES FOR LONG DISTANCES

ELKABEL

COMMUNICATION CABLES FOR LONG DISTANCES

ELKABEL

-PMZ ... x4x0.9 STI LG A-PMZ ... x4x1.2 STI LG

similar to VDE 0816 part 3.

COMMUNICATION CABLES FOR LONG DISTANCES

Application
These cables are used for construction of trunk cable communication networks and for connecting lines between district telephone exchanges. They are suitable for fixed underground installation in collectors, cable ducts and conduit. The use of these cables for power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath bare copper conductor diameter 0.9 mm and 1.2mm insulation of paper string over which is laid a paper tape each 4 wires are twisted to a quad the quads are stranded into layers of paper tapes of lead to which is added antimony of 0.4 up to 0.6%

Technical data
Conductor diameter Cond. resistance at 20oC - max. Insulation resistance min. Mutual capacitance at 800Hz-nom. Capacitance unbalance at 800Hz: K1 - max. K2-3- max. K9-12- max. E1-2 - max. Test voltage 50Hz, 2 min. wire - wire wire - screen Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. 0.9 28.3 1.2mm 15.85/km

12 000 M.km 34 280 700 210 700 700 2000V 225V 0C +45C -30C +50C 13 cable diameter 35nF/km pF/425m pF/425m pF/425m pF/425m 1000V

Color coding
Side circuit - 1 a - wire white b - wire red Side circuit - 2 a - wire green b - wire blue

The quads are supported with textile thread.In each layer there are two adjacent quads - the one with red color of the supporting spiral - showing the start of counting and the other - with yellow colour - showing the direction of counting.

Type codes outdoor cable paper insulation lead sheath with added hardener star quads in telecommunication cables for long distances without phantom use LG layer stranding P MZ STI

180

ELKABEL

Paper insulation quads stranded in layers lead sheath.

COMMUNICATION CABLES FOR LONG DISTANCES

Cable core construction


Number of quads
First layer

Number of quads in centre and successive layers


Second layer Third layer Fourth layer Fifth layer Sixth layer

3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114

3 4 1 3 4 1 2 3 4 1 2 4 1 3 4 2 4

6 9 10 6 8 9 10 6 8 10 6 9 10 8 10

12 14 15 16 12 14 16 12 15 16 14 16

18 20 22 18 21 22 20 22

24 27 28 26 28

32 34

Construction data A-PMZ ...x4x0.9 STI LG


Number of quads External diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 10.9 12.0 15.0 18.8 19.8 22.4 25.4 26.8 28.0 30.4 33.8 36.5 39.1 43.4 44.7 50.0 53.3 Copper weight kg/km 75 100 175 300 350 474 599 674 749 924 1118 1321 1550 1905 2032 2591 2896 Cable weight approx. kg/km 547 596 829 1207 1311 1616 1961 2182 2330 2666 3387 3772 4389 5163 5373 6719 7299

Construction data A-PMZ ...x4x1.2 STI LG


Number of quads External diameter approx. mm 13.2 14.2 18.0 23.1 24.3 27.4 31.3 32.5 33.8 37.3 42.0 43.6 46.9 52.3 55.7 62.5 66.1 Copper weight kg/km 133 177 310 531 620 841 1063 1196 1329 1639 1983 2343 2749 3379 3605 4596 5137 Cable weight approx. kg/km 695 787 1165 1739 1896 2361 2961 3172 3473 4105 5058 5835 6469 7948 8288 10311 11160

3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114

ELKABEL

181

-PMZBC ... x4x0.9 STI LG A-PMZBC ... x4x1.2 STI LG

similar to VDE 0816 part 3.

COMMUNICATION CABLES FOR LONG DISTANCES

Application
These cables are used for construction of trunk cable communication networks and for connecting lines between district telephone exchanges. They are suitable for installation in ditches, at not big stretch strength and slope of the ground less than 45o. The use of these cables for power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Bedding Armour Protective covering bare copper conductor diameter 0.9 mm and 1.2mm insulation of paper string over which is laid a paper tape each 4 wires are twisted to a quad the quads are stranded into layers of paper tapes of lead to which is added antimony of 0.4 up to 0.6% of bitumen and impregnated cable paper of two steel tapes of bitumen, synthetic yarn and chalk

Technical data
Conductor diameter Cond. resistance at 20C max. Insulation resistance min. Mutual capacitance at 800Hz-nom. Capacitance unbalance at 800Hz: K1 - max K2-3- max K9-12- max E1-2 - max Test voltage 50Hz, 2 min wire - wire wire - screen Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. 0.9 28.3 1.2mm 15.85/km

12 000 M.km 34 280 700 210 700 700 2000V 225V 0C +45C -30C +50C 13 cable diameter 35nF/km pF/425m pF/425m pF/425m pF/425m 1000V

Color coding
Side circuit - 1 a - wire white b - wire red Side circuit - 2 a - wire green b - wire blue

The quads are supported with textile thread.In each layer there are two adjacent quads - the one with red color of the supporting spiral - showing the start of counting and the other - with yellow colour - showing the direction of counting.

Type codes outdoor cable paper insulation lead sheath with added hardener armour protective covering of bitumen and yarn star quads in telecommunication cables for long distances without phantom use LG layer stranding P MZ B STI

182

ELKABEL

Paper insulation quads stranded in layers lead sheath armoured

COMMUNICATION CABLES FOR LONG DISTANCES

Cable core construction


Number of quads
First layer

Number of quads in centre and successive layers


Second layer Third layer Fourth layer Fifth layer Sixth layer

3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114

3 4 1 3 4 1 2 3 4 1 2 4 1 3 4 2 4

6 9 10 6 8 9 10 6 8 10 6 9 10 8 10

12 14 15 16 12 14 16 12 15 16 14 16

18 20 22 18 21 22 20 22

24 27 28 26 28

32 34

Construction data -PMZBC...x4x0.9 STI LG


Number of quads External diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 19.1 20.2 23.2 27.7 28.7 31.1 34.1 35.5 36.7 38.9 42.4 45.0 47.6 51.8 53.0 58.5 63.0 Copper weight kg/km 76 102 178 306 357 484 612 688 765 943 1121 1325 1555 1911 2039 2600 2905 Cable weight approx kg/km 812 909 1188 1760 1888 2232 2617 2828 3002 3405 4020 4528 5074 5908 6286 7695 9121

Construction data A-PMZBC...x4x1.2 STI LG


Number of quads External diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 21.4 22.4 26.9 31.8 33.0 36.1 39.9 41.1 42.4 45.8 50.4 52.0 55.4 62.0 65.3 72.1 75.7 Copper weight kg/km 136 181 317 544 634 861 1087 1223 1359 1676 1993 2356 2763 3398 3624 4621 5165 Cable weight approx kg/km 1019 1132 1698 2345 2528 3019 3650 3883 4195 4876 5783 6294 7298 9378 10161 12346 13746

ELKABEL

183

A-2YF(L)2Y A-2YF(L)2Y A-2YF(L)2Y A-2YF(L)2Y

... ... ... ...

x2x0.4 x2x0.5 x2x0.6 x2x0.7

StIII StIII StIII StIII

Bd Bd Bd Bd

similar to VDE 0816/part 1

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and in PABX's for telephone purposes and for the transmission of signals. The filling of petro jelly does not permit moisture penetration into the cable core. They are suitable for underground installation, in cable ducts and conduit, as well as for interior installations. The use of these cables for power installations is not permitted. These cables may only be used in locations with fire and explosion hazards in conjunction with the appropriate safety precautions.

Cable construction
Conductor Insulation Quad Units Cable core Filing Wrapping Screen Sheath Bare copper conductor diameter 0.4 mm , 0.5mm, 0.6mm, 0.7mm Polyethylene insulation type 2YI2 according to VDE 0207 part 2. each 4 wires are twisted to a quad 5 quads laid up to a basic unit the units are stranded into a compact cable petroleum - based jelly minimum of 1 layer of paper tape. of aluminum tape , thickness 0.2mm, coated with copolymer on both sides of PE compound, low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max. Insulation resistance min. Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire - screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 5G.km 55nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

150V cables with cores 0.4 and 0.5mm cables with cores 0.6 and 0.7mm 220V Temperature range -10C +60C mobile -40C +60C fixed 10 x cable Minimum bending radius approx. diameter

Color coding
Number of quad A2Y F (L)2Y StIII Bd Type codes outdoor cable polyethylene (PE) insulation filled cable core laminated sheath star quad in local cables unit type stranding 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

184

ELKABEL

PE insulation unit stranding jelly filling laminated sheath.

COMMUNICATION CABLES FOR LOCAL NETWORKS

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 Number of quads 3 5 10 15 25 35 50 75 100 Number of units 54 1-st layer 3-quads. 1 2 3 5 1 3 2-nd layer 254

1 6 7 3 4

Construction data A-2YF(L)2Y


Number of pairs x2x0.4 St III Bd 6 10 20 30 50 70 100 150 200 x2x0.5 St III Bd 6 10 20 30 50 70 100 150 200 x2x0.6 St III Bd 6 10 20 30 50 70 100 x2x0.7 St III Bd 6 10 20 30 50 70 100 External diameter approx. mm 8.6 9.3 11.7 12.9 16.2 18.0 21.7 25.7 30.6 9.2 10.5 12.9 15.4 19.9 22.0 25.2 30.8 36.5 10.4 12.2 16.2 18.0 22.9 26.5 30.4 11.4 13.5 17.8 21.7 27.0 30.6 36.1 Copper weight kg/km 15 24 49 73 126 174 252 380 504 23 37 75 113 196 271 392 592 784 32 54 108 163 282 390 564 44 72 148 222 384 532 768 Cable weight approx. kg/km 77 99 159 222 336 449 604 867 1124 98 129 223 306 480 632 864 1264 1630 122 165 292 402 638 851 1187 149 210 362 522 816 1087 1527

ELKABEL

185

A-2Y(L)2Y A-2Y(L)2Y A-2Y(L)2Y A-2Y(L)2Y

... ... ... ...

x2x0.4 x2x0.5 x2x0.6 x2x0.7

St St St St

III III III III

Bd Bd Bd Bd

similar to VDE 0816/part 1

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and in PABX's for telephone purposes and for the transmission of signals. They are suitable for underground installation, in cable ducts and conduit, as well as for interior installations. The use of these cables for power installations is not permitted. These cables may only be used in locations with fire and explosion hazards in conjunction with the appropriate safety precautions.

Cable construction
Conductor Insulation Quad Units Cable core Unit marking Bare copper conductor diameter 0.4 mm , 0.5mm, 0.6mm, 0.7mm PE low density 4 wires are twisted into a quad 5 quads laid up to a basic unit the units are stranded into a compact cable in each layer there is a unit with red supporting spiral from which the counting starts and a unit showing the direction of counting with yellow supporting spiral several layers of plastic tapes of aluminum tape , thickness not less than 0.04mm, one side coat ed with copolymer and 1 tinned cop per wire with diameter 0.5mm under the metal foil. of PE compound low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max. Insulation resistance min. Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire - screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 10 G.km 48 nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

Wrapping Screen

Sheath

150V cables with cores 0.4 and 0.5mm cables with cores 0.6 and 0.7mm 220V Temperature range -10C +60C mobile -40C +60C fixed 10 x cable Minimum bending radius approx. diameter

Color coding
Number of quad A2Y (L)2Y StIII Bd Type codes outdoor cable polyethylene (PE) insulation laminated sheath star quad in local cables unit type stranding 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

186

ELKABEL

PE insulation unit stranding laminated sheath.

COMMUNICATION CABLES FOR LOCAL NETWORKS

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 Number of quads 3 5 10 15 25 35 50 75 100 125 150 200 250 300 350 400 500 600 54 1-st layer 3-quads. 1 2 3 5 1 3 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

6 7 3 4 5 1

5 4 5 1 1 1 3 4 5 6 7 7 8

Construction data A-2Y(L)2Y...


Number of pairs x2x0.4 St III Bd 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 x2x0.5 St III Bd 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 External diameter approx mm 7.4 8.5 10.7 12.4 15.3 17.4 20.5 24.7 26.5 30.4 31.7 37.1 40.4 44.4 47.6 51.0 56.6 61.8 8.7 9.6 11.7 13.9 16.9 19.1 22.5 27.0 29.9 33.7 36.9 40.4 45.6 49.3 52.2 64.0 65.0 69.1 Copper weight kg/km 17 27 51 74 127 174 250 374 494 613 738 983 1235 1476 1722 1968 2454 2941 26 40 78 115 196 269 387 580 766 952 1146 1526 1918 2292 2674 3056 3813 4570 Cable weight approx kg/km 51 73 117 157 249 324 452 642 811 1002 1177 1524 1902 2252 2621 2993 3703 4413 71 97 151 215 332 449 613 880 1141 1389 1640 2161 2718 3197 3720 4247 5258 6271

Construction data A-2Y(L)2Y...


Number of pairs x2x0.6 St III Bd 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000
x2x0.7 St III Bd6

External diameter approx mm 9.3 10.5 13.2 15.4 20.1 22.5 26.7 32.9 35.9 40.5 43.9 50.1 54.7 60.6 64.7 69.2 76.8 10.1 11.8 16.1 18.7 22.7 25.6 31.7 38.1 42.0 47.1 51.3 52.7 66.0 71.9 76.3

Copper weight kg/km 36 57 111 164 281 387 557 834 1102 1371 1650 2197 2761 3300 3851 4401 5491 48 77 150 222 381 526 757 1134 1500 1865 2245 2990 3757 4491 5240

Cable weight approx kg/km 86 120 212 291 469 619 852 1252 1601 1980 2342 3094 3913 4607 5357 6111 7565 107 152 277 390 614 816 1150 1665 2165 2676 3222 4239 5286 6274 7297

6 10 20 30 50 70 100 150 200 250 300 400 500 600 700

ELKABEL

187

J-Y(St)Y ... x2x0.6 Lg J-Y(St)Y ... x2x0.8 Lg

according to VDE 0815

INSTALLATION CABLES FOR TELECOMMUNICATIONS SYSTEMS

Application
These cables are used for installation of equipment of telephone stations. They are suitable for fixed indoor installation and for external walls of buildings. The screen of metal foil protects the cable from external electrical interferences. The use of these cables for power installations and underground installation is not permitted.

Cable construction
Conductor Insulation Pairs Cable core Wrapping Screen bare copper conductor diameter 0.6 mm and 0.8mm PVC insulation type YI1 according to VDE 0207 part 4. each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of aluminum tape one side coated with polyester and 1 tinned copper wire with diameter : 0.4mm for cables up to 10 pairs 0.6mm for cables exceeding 10 pairs of PVC compound type YM1 according to VDE 0207 part 5, grey color according to RAL 7032

Technical data
Conductor diameter Cond. resistance of the loop at 20C - max. Insulation resistance min. Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen Operating voltage peak value Colors b-wire blue yellow green brown black blue yellow green brown black Temperature range mobile fixed Minimum bending radius approx. Type codes installation cable insulation or sheath of PVC static screen laid up in layers 0.6 130 0.8mm 73.2

100M.km 100nF/km

Sheath

300pF/100m

800V 800V 300V

Color coding
Number of pairs. The pairs are counted successively commencing at the outside and counting inwards in the same manner throught all layers 1 6 11 16 21 26 31 36 41 46 2 7 12 17 22 27 32 37 42 47 3 8 13 18 23 28 33 38 43 48 4 9 14 19 24 29 34 39 44 49 5 10 15 20 25 30 35 40 45 50 51 56 61 66 71 76 81 86 91 96 52 57 62 67 72 77 82 87 92 97 53 58 63 68 73 78 83 88 93 98 54 59 64 69 74 79 84 89 94 99 55 60 65 70 75 80 85 90 95 100 Identification of the a-wire for the first pair (counting pair) is red in each layer , and white for all other pairs .

-5C +50C -30C +70C 7.5 x cable diameter

JY (St) Lg

188

ELKABEL

PVC insulation pairs stranded in layers static screen sheath of PVC.

INSTALLATION CABLES FOR TELECOMMUNICATIONS SYSTEMS

Cable core construction


Number of pairs 1 2 3 4 5 6 8 10 12 15 16 20 24 30 40 50 100 2 3 4 5 6 1 2 3 5 5 1 2 4 1 4 2 2 Number of pairs in centre and successive layers 3 4 5 6

7 8 9 10 11 6 8 10 7 10 8

13 14 16 13 15 14

19 21 20

25

31

Construction data J-Y (St) Y


Number of pairs External diameter approx mm x2x0,6 Lg 2 3 4 6 8 10 12 16 20 24 30 40 50 100 5,0 6,2 6,7 7,7 8,1 9,0 9,3 10,4 10,9 12,1 13,7 15,3 16,4 22,9 Copper weight kg/km 12 17 23 33 44 55 67 88 109 131 163 216 269 536 Cable weight approx. kg/km 43 52 57 85 97 116 126 168 198 229 291 368 460 819 x2x0,8 Lg 2 3 4 6 8 10 12 16 20 24 30 40 50 100

Construction data J-Y (St) Y


Number of pairs External diameter approx mm 6,4 8,4 9,1 10,7 11,4 12,8 13,8 15,5 16,9 18,7 20,5 23,6 25,9 35,9 Copper weight kg/km 20 30 39 58 77 96 117 154 192 230 287 382 477 951 Cable weight approx. kg/km 69 86 98 153 172 222 254 323 386 464 566 720 906 1689

ELKABEL

189

LiYY ... x0.25mm2 / 900V; LiYY ... x0.75mm2 / 900V LiYY ... x0.34mm2 / 900V; LiYY ... x1.00mm2 / 900V LiYY ... x0.50mm2 / 900V LiYY ... x1.50mm2 / 900V

According to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

Application
These non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15mm 0.34mm2 = 7x0.25mm 0.50mm2 = 16x0.2mm 0.75mm2 = 24x0.2mm 1.00mm2 = 32x0.2mm 1.50mm2 = 30x0.25mm PVC insulation type YI2 according to VDE 0207,part 4 color coded according to DIN 47 100 Type of lay-up cores laid up in layers of optimum pitch plastic foil overlapping of PVC compound type YM1 according to VDE 0207 part 5 gray, RAL 7032

Technical data
Cross section - mm2 0.25 0.34 0.50 0.75 1.0 1.5

Cond. resistance at 20C - 78 57 39 25.5 19.1 13 max. /km: Capacitance (core/core) 120 120 150 150 150 150 pF/m

Insulation Core identification Wrapping Sheath Sheath color

Mutual capacitance at 800Hz-max. : Insulation resistance min. Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed

150pF/m

200 M .km 2500V 900V

-5C +50C -30C +70C 10 x cable diameter

Color coding
Number of color wires 1 white 2 brown 3 green 4 yellow 5 gray Number of color wires 6 pink 7 blue 8 red 9 black 10 violet

Minimum bending radius

Type codes Li - stranded wire conductor Y - insulation or sheath of PVC

190

ELKABEL

PVC insulation

wires stranded in layers

sheath of PVC.

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

Construction data LiYY...


Number of wires External diameter approx. mm x0,25 900V 2 3 4 5 6 7 8 9 10 x0,34 mm2/ 900V 2 3 4 5 6 7 8 9 10 x0,50 mm2/ 900V 2 3 4 5 6 7 8 9 10 mm2/ 3,7 3,9 4,2 4,6 4,9 4,9 5,4 5,7 6,2 3,9 4,1 4,4 4,8 5,2 5,2 5,7 6,0 6,6 4,7 4,9 5,4 5,9 6,4 6,4 7,1 7,5 8,2 Copper weight kg/km 4,6 7,0 9,3 11,8 14,0 16,5 19,0 21,0 23,5 6,5 9,8 13,1 16,3 20,0 23,0 26,1 30,0 32,6 8,8 13,2 18,0 22,0 26,0 32,0 36,0 40,0 45,0 Cable weight approx. kg/km x0,75 16,0 20,0 25,0 30,0 35,0 39,0 45,0 48,0 53,0 19,0 25,0 30,0 35,0 42,0 47,0 53,0 57,0 65,0 26,0 35,0 42,0 50,0 58,0 65,0 75,0 82,0 90,0 Number of wires

Construction data LiYY...


External diameter approx. mm 900V 2 3 4 5 6 7 8 9 10 x1,0 mm2/ 900V 2 3 4 5 6 7 8 9 10 x1,5 mm2/ 900V 2 3 4 5 6 7 8 9 10 mm2/ 5,1 5,3 5,8 6,4 7,0 7,0 7,8 8,2 10,0 5,4 5,7 6,3 6,9 7,5 7,5 8,4 9,8 10,6 6,4 6,7 7,4 8,2 10,0 10,0 11,0 11,5 12,6 Copper weight kg/km 14,3 22,0 28,5 35,5 42,5 50,0 57,0 64,0 71,0 19,0 28,5 38,0 47,5 56,0 66,0 75,8 85,0 95,0 28,0 42,0 55,0 69,1 83,0 97,0 111,0 125,0 139,0 Cable weight approx. kg/km 32 43 54 66 77 88 99 110 135 39 52 66 80 95 107 122 158 175 53 73 93 114 158 176 200 221 245

ELKABEL

191

LiYY ... x0.50mm2 / 1500V LiYY ... x0.75mm2 / 1500V

according to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

PVC insulation wires stranded in layers sheath of PVC.

Application
These non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms

Cable construction
Conductor Construction of conductor Insulation Core identification Type of lay-up Wrapping Sheath Sheath color plain Cu wires, flexible 0.50mm2 = 16x0.2 0.75mm2 = 24x0.2 PVC insulation type YI2 according to VDE 0207, part 4 color coded according to DIN 47 100 cores laid up in layers of optimum pitch plastic foil overlapping of PVC compound type YM1 according to VDE 0207 part 5 gray, RAL 7032

Technical data
0.50 Cross section - mm2 Cond. resistance at 20C - 39.0 max. /km: 120 Capacitance, pF/m core/core: Mutual capacitance at 150pF/m 800Hz-max. : Insulation resistance min. Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Minimum bending radius 200 M .km 3000V 1500V -5C +50C -30C +70C 10 x cable diameter 0.75 25.5 120

Color coding
Number of color wires 1 white 2 brown 3 green 4 yellow 5 gray Number of color wires 6 pink 7 blue 8 red 9 black 10 violet

Type codes Li - stranded wire conductor Y - insulation or sheath of PVC

Construction data LiYY...


Number of wires x0,50 mm2/1500 V 2 3 4 5 6 7 8 9 10 External diameter approx. mm 5,5 5,8 6,3 7,0 7,6 7,6 8,5 9,9 10,8 Copper weight kg/km 8,8 13,0 17,4 22,0 26,0 30,5 35,0 39,0 43,4 Cable weight approx. kg/km 31 40 50 60 70 79 90 123 136

Construction data LiYY...


Number of wires x0,75 mm2/ 1500 V 2 3 4 5 6 7 8 9 10 External diameter approx. mm 6,3 6,6 7,3 8,0 9,8 9,8 10,8 11,3 12,4 Copper weight kg/km 14,2 21,2 28,3 35,3 42,4 50,0 56,0 64,0 71,0 Cable weight approx. kg/km 42 56 70 85 123 136 154 170 188

192

ELKABEL

LiYY ...2x0.25mm 2, LiYY ...2x0.75mm 2 LiYY ...2x0.34mm 2, LiYY ...2x1.00mm 2 LiYY ...2x0.50mm 2, LiYY ...2x1.50mm 2

according to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

PVC insulation

pairs stranded in layers

sheath of PVC.

Application
These non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms.

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15mm 0.34mm2 = 7x0.25mm 0.50mm2 = 16x0.2mm 0.75mm2 = 24x0.2mm 1.00mm2 = 32x0.2mm 1.50mm2 = 30x0.25mm PVC insulation type YI2 according to VDE 0207,part 4 each 2 wires are twisted to a pair color coded according to DIN 47 100 the pairs are stranded into layer plastic foil overlapping of PVC compound type YM1 accord ing to VDE 0207 part 5 gray, RAL 7032

Technical data
Cross section - mm2 Cond. resistance at 20C max. /km: Capacitance (core/core) pF/m Mutual capacitance at 800Hz-max. 0.25 0.34 0.50 0.75 1.0 1.5 78 57 39 25.5 19.1 13 120 120 150 150 150 150 150pF/m

Insulation Pairs Core identification Cable core Wrapping Sheath Sheath color

Capacitance unbalances at 300pF/m 800Hz; K1 max. Insulation resistance min. Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Minimum bending radius 200 M .km 2000V 500V -5C +50C -30C +70C 10 x cable diameter

Construction data LiYY...


Number of pairs x20,25 mm2 1 2 3 4 5 2x0,34 mm2 1 2 3 4 5 x205 mm2 1 2 3 4 5 External diameter approx. mm 3,7 5,4 5,7 6,3 6,9 3,9 5,7 6,1 6,7 7,4 4,7 7,1 7,5 9,3 10,2 Copper weight kg/km 4,8 9,5 14,0 18,8 23,5 2,9 5,6 8,8 11,0 14,0 8,7 17,5 26,2 35,0 44,0 Cable weight approx. kg/km 28 36 45 54 16 15 26 32 39 47 25 45 60 98 116 Number of pairs 2x0,75 mm2 1 2 3 4 5 x21,0 mm2 1 2 3 4 5 2x1,5 mm2 1 2 3 4 5

Construction data LiYY...


External diameter approx. mm 5,1 7,8 9,3 10,1 11,1 6,4 9,4 9,9 10,8 11,9 6,4 11,0 11,6 12,8 14,1 Copper weight kg/km 14,2 28,4 42,6 56,9 71,0 19,0 38,0 56,0 76,0 95,0 28,0 55,5 83,3 111,1 139,0 Cable weight approx. kg/km 32 60 102 127 152 39 94 122 152 182 53 126 167 210 154

ELKABEL

193

L i Y C Y . . . x 0 . 2 5 m m 2, L i Y C Y . . . x 0 . 7 5 m m 2 L i Y C Y . . . x 0 . 3 4 m m 2, L i Y C Y . . . x 1 . 0 m m 2 L i Y C Y . . . x 0 . 5 0 m m 2, L i Y C Y . . . x 1 . 5 m m 2

According to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

Application
These screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required and transmission of the data must be continuous, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are suitable for voice communication in telecommunications systems. The overall braided screen, consisting of tinned copper wires with a visible coverage of approx. 85% provides protection against external pulses. These cables are also suitable for flexible and permanent installation in dry rooms

Cable construction
Conductor Construction of conductor , 0.25mm2 = 14x0.15mm 0.34mm2 = 7x0.25mm 0.50mm2 = 16x0.2mm 0.75mm2 = 24x0.2mm 1.00mm2 = 32x0.2mm 1.50mm2 = 30x0.25mm PVC insulation type YI2 according to VDE 0207, part 4 color coded according to DIN 47 100 Type of lay-up cores laid up in layers of optimum pitch plastic foil overlapping braid of tinned copper wires, coverage approx. 85% of PVC compound type YM1 accord ing to VDE 0207 part 5 gray, RAL 7032

Technical data
Cross section - mm2 Cond. resistance at 20C max. /km: Capacitance , pF/m (core/core) (core/screen) Insulation resistance min. Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Minimum bending radius 0.25 0.34 0.50 0.75 1.0 1.5 78 57 39 25.5 19.1 13

110 110 120 130 130 130 220 250 260 320 350 360 200 M .km 1200V 500V -5C +50C -30C +70C 15 x cable diameter

Insulation Core identification Wrapping Screen Sheath Sheath color

Color coding
Number of wires 1 Type codes Li - stranded wire conductor Y - insulation or sheath of PVC C - screen of copper wire braid 2 3 4 5 color white brown green yellow gray Number of wires 6 7 8 9 10 pink blue red black violet color

194

ELKABEL

PVC insulation

wires stranded in layers sheath of PVC.

with Cu screen

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

Construction data LiYCY...


Number of wires External diameter approx. mm 0,25 2 3 4 5 6 7 8 9 10 x0,34 mm2 2 3 4 5 6 7 8 9 10 0,5 mm2 2 3 4 5 6 7 8 9 10 mm2 4,1 4,3 4,6 5,0 5,3 5,3 6,0 6,3 6,8 3,9 4,1 4,4 4,8 5,2 5,2 5,7 6,0 6,6 5,1 5,3 6,0 6,5 7,0 7,0 7,7 8,1 9,8 Copper weight kg/km 14 16 20 23 25 29 39 44 47 17 22 25 30 38 42 50 55 62 22 26 35 46 52 55 65 72 77 Cable weight approx. kg/km 26 32 37 42 49 52 68 76 78 34 43 52 62 73 83 101 112 120 38 46 60 75 86 90 110 125 148 x0,75 2 3 4 5 6 7 8 9 10 1,0 mm2 2 3 4 5 6 7 8 9 10 x1,5 mm2 2 3 4 5 6 7 8 9 10 mm2 Number of wires

Construction data LiYCY...


External diameter approx. mm 5,7 5,9 6,4 7,0 7,6 7,6 8,4 9,8 10,6 5,4 5,7 6,3 6,9 7,5 7,5 9,4 9,8 10,6 5,4 5,7 6,3 6,9 7,5 7,5 9,4 9,8 10,6 Copper weight kg/km 35 42 52 60 75 80 89 97 108 35 45 53 64 75 83 93 101 112 35 45 53 64 75 83 93 101 112 Cable weight approx. kg/km 55 65 79 92 112 117 142 180 185 56 70 83 100 120 125 174 190 196 56 70 83 100 120 125 174 190 196

ELKABEL

195

LiYCY ...x2 x0.25mm 2; LiYCY ...x2 x1.00mm 2 LiYCY ...x2 x0.50mm 2; LiYCY ...x2 x1.50mm 2 LiYCY ...x2 x0.75mm 2;

According to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

Application
These cables are ideal for voice communication in telecommunication systems, for pulse, signal and data transmission applications. The twisted pairs with optimum pair and layer pitch prevent mutual interaction from neighboring conductor circuits. The overall braided screen, consisting of tinned copper wires with a visible coverage of approx. 85% provides protection against external pulses. These cables are also suitable for flexible and permanent installation in dry and moist rooms.

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15 0.50mm2 = 16x0.25 0.75mm2 = 24x0.20 1.00mm2 = 32x0.20 1.50mm2 = 30x0.25 PVC insulation type YI2 according to VDE 0207, part 4 color coded according to DIN 47 100 each 2 wires are twisted to a pair The pairs are stranded info layers plastic foil overlapping braid of tinned copper wires, coverage approx. 85% of PVC compound type YM1 accord ing to VDE 0207 part 5 gray, RAL 7032

Technical data
Cross section in mm2 0.25 0.34 0.50 0.75 1.0 1.5 Cond. resistance at 20C 78 57 39 25.5 19.1 13 max. /km: Capacitance , pF/m core/core 110 110 120 130 130 130 core/screen 220 250 260 320 350 360 Mutual capacitance 150pF/m at 800Hz-max. Insulation resistance min. Capacitance unbalances at 800 Hz K1 max Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Minimum bending radius 200 M .km 300pF/100m 1200V 500V -5C +50C -30C +70C 15 x cable diameter

Insulation Core identification Pairs Cable core Wrapping Screen Sheath Sheath color

Color coding
Number of pairs Type codes Li - stranded wire conductor Y - insulation or sheath of PVC C - screen of copper wire braid 1 2 3 4 5 white green gray blue black a-wire brown yellow pink red violet b - wire

196

ELKABEL

PVC insulation

pairs stranded in layers sheath of PVC.


Construction data LiYCY...

with Cu screen

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS

Number of pairs

External diameter approx. mm

Copper weight kg/km 15 29 38 44 55 20 40 48 80 93 35 62 75 95 115 38 72 95 117 140 52 98 130 160 195

Cable weight approx. kg/km 26 49 60 72 85 40 80 100 133 155 55 115 138 165 195 58 130 160 198 230 79 170 215 265 310

20,25

mm2

2x0,5 mm2

1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

4,1 6,0 6,3 6,9 7,5 4,7 7,1 7,5 9,3 10,2 5,1 8,8 9,3 10,1 11,1 5,4 9,4 9,9 10,8 11,9 6,4 11,0 11,6 12,8 14,1

20,75 mm2

2x1,0 mm2

21,5 mm2

ELKABEL

197

LiYY-fr ... x0.25mm2 / 900V, LiYY-fr ... x0.75mm2 / 900V LiYY-fr ... x0.34mm2 / 900V, LiYY-fr ... x1.00mm2 / 900V LiYY-fr ... x0.50mm2 / 900V, LiYY-fr ... x1.50mm2 / 900V

According to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS, FLAME RETARDANT

Application
These non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms, when require non-proliferation of flames.

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15mm 0.34mm2 = 7x0.25mm 0.50mm2 = 16x0.2mm 0.75mm2 = 24x0.2mm 1.00mm2 = 32x0.2mm 1.50mm2 = 30x0.25mm PVC insulation type YI2 according to VDE 0207,part 4 color coded according to DIN 47 100 Type of lay-up cores laid up in layers of optimum pitch plastic foil overlapping of PVC compound flame retardant and reduced corrosive gas emmission gray, RAL 7032

Technical data
Cross section - mm2 0.25 0.34 0.50 0.75 1.0 1.5 Cond. resistance at 20C - 78 57 39 25.5 19.1 13 max. /km: Capacitance (core/core) 120 120 150 150 150 150 pF/m Mutual capacitance at 800Hz-max. : Insulation resistance min. M.km Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Flame retardancy Minimum bending radius 150 200 2500 900 -5C +50C -30C +70C BDS IEC 332-3 ; Category C 10 x cable diameter

Insulation Core identification Wrapping Sheath Sheath color

Color coding
Number of wires Type codes Li - stranded wire conductor Y - insulation of PVC Y-fr - sheath of PVC, flame retardant 1 2 3 4 5 color white brown green yellow gray Number of wires 6 7 8 9 10 pink blue red black violet color

198

ELKABEL

PVC insulation

wires stranded in layers

sheath of PVC.

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS, FLAME RETARDANT

Construction data LiYY-fr...


Number of wires External diameter approx. mm x0,25 900V 2 3 4 5 6 7 8 9 10 x0,34 mm2/ 900V 2 3 4 5 6 7 8 9 10 x0,50 mm2/ 900V 2 3 4 5 6 7 8 9 10 mm2/ 3,7 3,9 4,2 4,6 4,9 4,9 5,4 5,7 6,2 3,9 4,1 4,4 4,8 5,2 5,2 5,7 6,0 6,6 4,7 4,9 5,4 5,9 6,4 6,4 7,1 7,5 8,2 Copper weight kg/km 4,6 7,0 9,3 11,8 14,0 16,5 19,0 21,0 23,5 6,5 9,8 13,1 16,3 20,0 23,0 26,1 30,0 32,6 8,8 13,2 18,0 22,0 26,0 32,0 36,0 40,0 45,0 Cable weight approx. kg/km 16,0 20,0 25,0 30,0 35,0 39,0 45,0 48,0 53,0 19,0 25,0 30,0 35,0 42,0 47,0 53,0 57,0 65,0 26,0 35,0 42,0 50,0 58,0 65,0 75,0 82,0 90,0 x0,75

Construction data LiYY-fr...


Number of wires External diameter approx. mm 900V 2 3 4 5 6 7 8 9 10 x1,0 mm2/ 900V 2 3 4 5 6 7 8 9 10 x1,5 mm2/ 900V 2 3 4 5 6 7 8 9 10 mm2/ 5,1 5,3 5,8 6,4 7,0 7,0 7,8 8,2 10,0 5,4 5,7 6,3 6,9 7,5 7,5 8,4 9,8 10,6 6,4 6,7 7,4 8,2 10,0 10,0 11,0 11,5 12,6 Copper weight kg/km 14,3 22,0 28,5 35,5 42,5 50,0 57,0 64,0 71,0 19,0 28,5 38,0 47,5 56,0 66,0 75,8 85,0 95,0 28,0 42,0 55,0 69,1 83,0 97,0 111,0 125,0 139,0 Cable weight approx. kg/km 32 43 54 66 77 88 99 110 135 39 52 66 80 95 107 122 158 175 53 73 93 114 158 176 200 221 245

ELKABEL

199

LiYY-fr ... x0.50mm2 / 1500V, LiYY-fr ... x0.75mm2 / 1500V

according to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS FLAME RETARDANT

Application
These non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms, when require non-proliferation of flames.

Cable construction
Conductor Construction of conductor Insulation Core identification Wrapping Sheath Sheath color plain Cu wires, flexible 0.50mm2 = 16x0.2 0.75mm2 = 24x0.2 PVC insulation type YI2 according to VDE 0207, part 4 color coded according to DIN 47 100 Type of lay-up: cores laid up in layers of optimum pitch plastic foil overlapping of PVC compound flame retardant and reduced corrosive gas emmission gray, RAL 7032

Technical data
Cross section - mm2 0.50 Cond. resistance at 20C - 39.0 max. /km: 120 Capacitance, pF/m core/core: Mutual capacitance at 800Hz-max. Insulation resistance min. Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Flame retardancy Minimum bending radius 150pF/m 200 M .km 3000V 1500V -5C +50C -30C +70C BDS IEC 332-3 Category C 10 x cable diameter 0.75 25.5 120

Color coding
Type codes Li - stranded wire conductor Y - insulation of PVC Y-fr - sheath of PVC, flame retardant Number of wires 1 2 3 4 5 color white brown green yellow gray Number of wires 6 7 8 9 10 pink blue red black violet color

200

ELKABEL

PVC insulation

wires stranded in layers

sheath of PVC.

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS FLAME RETARDANT

Construction data LiYY-fr...


Number of wires External diameter approx. mm x0,50 VZZ 2 3 4 5 6 7 8 9 10 x0,75 mm2/1500 V2 3 4 5 6 7 8 9 10 mm2/1500 5,5 5,8 6,3 7,0 7,6 7,6 8,5 9,9 10,8 6,3 6,6 7,3 8,0 9,8 9,8 10,8 11,3 12,4 Copper weight kg/km 8,8 13,0 17,4 22,0 26,0 30,5 35,0 39,0 43,4 14,2 21,2 28,3 35,3 42,4 50,0 56,0 64,0 71,0 Cable weight approx. kg/km 31 40 50 60 70 79 90 123 136 42 56 70 85 123 136 154 170 188

ELKABEL

201

LiYY-fr ...2x0.25mm 2; LiYY-fr ...2x0.75mm 2 LiYY-fr ...2x0.34mm 2; LiYY-fr ...2x1.00mm 2 LiYY-fr...2x0.50mm 2; LiYY-fr ...2x1.50mm 2

according to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS FLAME RETARDANT

Application
These non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms, when require non-proliferation of flames.

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15mm 0.34mm2 = 7x0.25mm 0.50mm2 = 16x0.2mm 0.75mm2 = 24x0.2mm 1.00mm2 = 32x0.2mm 1.50mm2 = 30x0.25mm PVC insulation type YI2 according to VDE 0207,part 4 each 2 wires are twisted to a pair color coded according to DIN 47 100 the pairs are stranded into layer plastic foil overlapping of PVC compound flame retardant and reduced corrosive gas emmission gray, RAL 7032

Technical data
Cross section - mm2 Cond. resistance at 20C max. /km: Capacitance (core/core) pF/m Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz ; K1 max Insulation resistance min. M.km Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Flame retardancy Minimum bending radius 0.25 0.34 0.50 0.75 1.0 1.5 57 39 25.5 19.1 13 120 120 150 150 150 150 78 150 300 200 2000V 500V -5C +50C -30C +70C BDS IEC 332-3 ; Category C 10 x cable diameter

Insulation Pairs Core identification Cable core Wrapping Sheath Sheath color

Color coding
Type codes Li stranded wire conductor Y insulation of PVC Y-fr - sheath of PVC, flame retardant Number of a-wire pairs 1 white 2 green 3 gray 4 blue 5 black b - wire brown yellow pink red violet

202

ELKABEL

PVC insulation

pairs stranded in layers

sheath of PVC

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS FLAME RETARDANT

Construction data LiYY-fr...


Number of pairs External diameter approx. mm x20,25 1 2 3 4 5 2x0,34 mm2 1 2 3 4 5 x20,5 mm2 1 2 3 4 5 mm2 3,7 5,4 5,7 6,3 6,9 3,9 5,7 6,1 6,7 7,4 4,7 7,1 7,5 9,3 10,2 Copper weight kg/km 4,8 9,5 14,0 18,8 23,5 2,9 5,6 8,8 11,0 14,0 8,7 17,5 26,2 35,0 44,0 Cable weight approx. kg/km 28 36 45 54 16 15 26 32 39 47 25 45 60 98 116 1 2 3 4 5 x21,0 mm2 1 2 3 4 5 2x1,5 mm2 1 2 3 4 5 2x0,75 mm2

Construction data LiYY-fr...


Number of pairs External diameter approx. mm 5,1 7,8 9,3 10,1 11,1 6,4 9,4 9,9 10,8 11,9 6,4 11,0 11,6 12,8 14,1 Copper weight kg/km 14,2 28,4 42,6 56,9 71,0 19,0 38,0 56,0 76,0 95,0 28,0 55,5 83,3 111,1 139,0 Cable weight approx. kg/km 32 60 102 127 152 39 94 122 152 182 53 126 167 210 154

ELKABEL

203

LiYCY-fr ... x0.25mm 2; LiYCY-fr ... x0.75mm 2 LiYCY-fr ... x0.34mm2 LiYCY-fr ... x1.0mm2 LiYCY-fr... x0.50mm 2; LiYCY-fr ... x1.5mm 2

According to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS, FLAME RETARDANT

Application
These screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumptions are required and transmission of the data must be continuous, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are suitable for voice communication in telecommunications systems. The overall braided screen, consisting of tinned copper wires with a visible coverage of approx. 85% provides protection against external pulses. These cables are also suitable for flexible and permanent installation in dry rooms, when require non-proliferation of flames.

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15mm 0.34mm2 = 7x0.25mm 0.50mm2 = 16x0.2mm 0.75mm2 = 24x0.2mm 1.00mm2 = 32x0.2mm 1.50mm2 = 30x0.25mm PVC insulation type YI2 according to VDE 0207, part 4 color coded according to DIN 47 100 cores laid up in layers of optimum pitch plastic foil overlapping braid of tinned copper wires, coverage approx. 85% of PVC compound fire retardant and reduced corrosive gas emmission gray, RAL 7032

Technical data
Cross section - mm2 0.25 0.34 0.50 0.75 1.0 1.5 Cond. resistance at 20C max. /km: 78 57 39 25.5 19.1 13 Capacitance , pF/m (core/core) 110 110 120 130 130 130 (core/screen) 220 250 260 320 350 360 Insulation resistance min. Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Flame retardancy Minimum bending radius 200 M .km 1200V 500V -5C +50C -30C +70C IEC 332-3 ; "" 15 x

Insulation Core identification Type of lay-up Wrapping Screen Sheath Sheath color

Color coding
Type codes Li - stranded wire conductor Y - insulation of PVC C - screen of copper wire braid Y-fr - sheath of PVC, flame retardant Number of wires 1 2 3 4 5 color white brown green yellow gray Number of wires 6 7 8 9 10 color pink blue red black violet

204

ELKABEL

PVC insulation

wires stranded in layers sheath of PVC.

with Cu screen

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS, FLAME RETARDANT

Construction data LiYCY-fr...


Number of wires External diameter approx. mm 0,25 2 3 4 5 6 7 8 9 10 x0,34 mm2 2 3 4 5 6 7 8 9 10 0,5 mm2 2 3 4 5 6 7 8 9 10 mm2 4,1 4,3 4,6 5,0 5,3 5,3 6,0 6,3 6,8 3,9 4,1 4,4 4,8 5,2 5,2 5,7 6,0 6,6 5,1 5,3 6,0 6,5 7,0 7,0 7,7 8,1 9,8 Copper weight kg/km 14 16 20 23 25 29 39 44 47 17 22 25 30 38 42 50 55 62 22 26 35 46 52 55 65 72 77 Cable weight approx. kg/km 26 32 37 42 49 52 68 76 78 34 43 52 62 73 83 101 112 120 38 46 60 75 86 90 110 125 148 x0,75 2 3 4 5 6 7 8 9 10 1,0 mm2 2 3 4 5 6 7 8 9 10 x1,5 mm2 2 3 4 5 6 7 8 9 10 mm2

Construction data LiYCY-fr...


Number of wires External diameter approx. mm 5,7 5,9 6,4 7,0 7,6 7,6 8,4 9,8 10,6 5,4 5,7 6,3 6,9 7,5 7,5 9,4 9,8 10,6 5,4 5,7 6,3 6,9 7,5 7,5 9,4 9,8 10,6 Copper weight kg/km 35 42 52 60 75 80 89 97 108 35 45 53 64 75 83 93 101 112 35 45 53 64 75 83 93 101 112 Cable weight approx. kg/km 55 65 79 92 112 117 142 180 185 56 70 83 100 120 125 174 190 196 56 70 83 100 120 125 174 190 196

ELKABEL

205

LiYCY-fr...x2 x0.25mm 2; LiYCY-fr ...x2 x1.00mm 2 LiYCY-fr ...x2 x0.50mm 2; LiYCY-fr ...x2 x1.50mm 2 LiYCY-fr...x2 x0.75mm2

According to VDE 0812

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS, FLAME RETARDANT

Application
These cables are ideal for voice communication in telecommunication systems, for pulse, signal and data transmission applications. The twisted pairs with optimum pair and layer pitch prevent mutual interaction from neighboring conductor circuits. The overall braided screen, consisting of tinned copper wires with a visible coverage of approx. 85% provides protection against external pulses. These cables are also suitable for flexible and permanent installation in dry and moist rooms , when require non-proliferation of flames.

Cable construction
Conductor Construction of conductor plain Cu wires, flexible 0.25mm2 = 14x0.15 0.50mm2 = 16x0.25 0.75mm2 = 24x0.20 1.00mm2 = 32x0.20 1.50mm2 = 30x0.25 PVC insulation type YI2 according to VDE 0207, part 4 color coded according to DIN 47 100 each 2 wires are twisted to a pair The pairs are stranded info layers plastic foil overlapping braid of tinned copper wires, coverage approx. 85% of PVC compound fire retardant and reduced corrosive gas emmission gray, RAL 7032

Technical data
Cross section in mm2 0.25 0.50 Cond. resistance at 20C max. /km: 80 39 Capacitance , pF/m core/core 130 150 core/screen 220 260 Mutual capacitance 150pF/m at 800Hz-max. Insulation resistance min. Capacitance unbalances at 800 Hz K1 max Test voltage 50Hz, 1 min. Operating voltage peak value Temperature range mobile fixed Flame retardancy Minimum bending radius 0.75 1.0 1.50 26 19.5 13.3

150 150 150 300 300 300

Insulation Core identification Pairs Cable core Wrapping Screen Sheath Sheath color

200 M .km 300pF/100m 1200V 500V -5C +50C -30C +70C BDS IEC 332-3 ; Category C 15 x cable diameter

Colour coding
Li Y C Y-fr Type codes stranded wire conductor insulation of PVC screen of copper wire braid - sheath of PVC, flame retardant Number of a-wire pairs 1 white 2 green 3 gray 4 blue 5 black b - wire brown yellow pink red violet

206

ELKABEL

PVC insulation

pairs stranded in layers sheath of PVC.


Construction data LiYCY-fr...

with Cu screen

FLEXIBLE CABLES FOR INDUSTRIAL ELECTRONICS, FLAME RETARDANT

Number of pairs

External diameter approx mm

Copper weight kg/km 15 29 38 44 55 20 40 48 80 93 35 62 75 95 115 38 72 95 117 140 52 98 130 160 195

Cable weight approx. kg/km 26 49 60 72 85 40 80 100 133 155 55 115 138 165 195 58 130 160 198 230 79 170 215 265 310

20,25

mm2

2x0,5 mm2

1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

4,1 6,0 6,3 6,9 7,5 4,7 7,1 7,5 9,3 10,2 5,1 8,8 9,3 10,1 11,1 5,4 9,4 9,9 10,8 11,9 6,4 11,0 11,6 12,8 14,1

20,75 mm2

2x1,0 mm2

21,5 mm2

ELKABEL

207

INSTRUMENTATION AND CONTROL CABLES

RE-2Y(St)Y ... x2x0.5 mm2/1 class Lg RE-2Y(St)Y ... x2x1.0 mm2/1 class Lg RE-2Y(St)Y ... x2x0.5 mm2/5 class Lg RE-2Y(St)Y ... x2x1.5 mm2/2 class Lg

according to BS 5308 part 1

Application
These cables are used for computers and process control in industrial plant. The screen of metal foil protects the circuits from external interfering signals. The low operating capacity makes possible data transfer to long distances. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings. The use of these cables for power installations and underground installation is not permitted.

Cable construction
Conductor bare copper conductor according to BS 6746, nominal area: 0.5mm2- class 1 - 1/0.8mm 1.0mm2- class 1 - 1/1.13mm 0.5mm2- class 5 - 16/0.2mm 1.5mm2- class 2 - 7/0.53 PE insulation type 03 according to BS 6234 each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of aluminum tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound type TM1 according to BS 6746, colored black

Technical data
Cross section in mm2/class 0.5/1 Cond. resistance max/km Mutual capacitance at 800Hz- max. nF/km Insulation resistance min. Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. 36.8 75 1.0/1 0.5/5 1.5/2 18.4 75 39.7 75 12.3 85

Insulation Pairs Cable core Wrapping Screen Sheath

5 G.km 250pF/250m 1000V 1000V 300V 0C +50C -40C +65C 7.5 x cable diameter

Cable core construction


Number Number of pairs in centre and successive layers of pairs First layer Second layer Third layer Fourth layer 1 1 2 2(quad) 5 5 10 2 8 15 5 10 20 1 6 13 30 4 10 16 50 4 10 15 21

Type codes RE 2Y (St) Y Lg control cable PE insulation static screen PVC sheath laid up in layers

208

ELKABEL

PE insulation

pairs stranded in layers of PVC.


Color coding

static screen

sheath

INSTRUMENTATION AND CONTROL CABLES

Pair no. 1 2 3 4 5 6 7 8 9 10

a - wire white white white white white red red red red red

b - wire blue orange green brown gray blue orange green brown gray

Pair no. 11 12 13 14 15 16 17 18 19 20

a - wire black black black black black yellow yellow yellow yellow yellow

b - wire blue orange green brown gray blue orange green brown gray

Construction data RE - 2Y(St)Y...


Number of pairs External diameter approx. mm x2x0,5 mm2 /1class Lg 1 2 5 10 15 20 30 50 x2x1,0 mm2 /1class Lg 1 2 5 10 15 20 30 50 Copper weight kg/km Cable weight approx. kg/km

Construction data RE - 2Y(St)Y...


Number of pairs External diameter approx. mm x2x0,5 2 /5class Lg 1 2 5 10 15 20 30 50 x2x1,5 2 /2class Lg 1 2 5 10 15 20 30 50 Copper weight kg/km Cable weight approx. kg/km

5,4 6,2 10,7 13,9 16,2 18,5 22,1 28,1 6,5 7,5 13,4 17,6 20,5 23,6 28,1 36,4

14 23 52 99 147 194 289 478 23 42 99 193 280 381 570 947

36 52 121 211 287 373 526 847 51 80 197 344 491 650 928 1547

6,1 7,0 12,3 16,3 19,0 21,4 26,0 33,0 7,4 8,8 15,5 20,7 24,3 27,6 33,4 42,7

13 22 49 94 139 184 274 454 34 64 152 300 448 597 893 1485

40 57 135 236 327 414 605 965 67 112 269 490 714 921 1354 2211

ELKABEL

209

RD-Y(St)Y - x2x0.5 mm 2/5 class Lg RD-Y(St)Y - x2x0.75 mm 2/5 class Lg RD-Y(St)Y - x2x1.5 mm 2/2 class Lg

according to BS 5308 part 2

INSTRUMENTATION AND CONTROL CABLES

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings. The use of these cables for power installations and underground installation is not permitted.

Cable construction
Conductor bare copper conductor according to BS 6746, nominal area: 0.52- class 5 - 6/0.2 0.752- class 5 - 24/0.2 1.52class 2 - 7/0.53 PVC insulation type TI1 according to BS 6746 ach 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of aluminum tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound type TM1 according to BS 6746, colored black

Technical data
Cross section in mm2/class 0.5/5 Cond. resistance - max. /km Mutual capacitance at 800Hz-max. Insulation resistance min. Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. 39.7 250nF/m 100 M .km 250pF/250m 1000V 1000V 300V -5C +50C -40C +65C 7.5 x cable diameter 0.75/5 26.5 1.5/2 12.3

Insulation Pairs Cable core Wrapping Screen Sheath

Cable core construction


Type codes control cable insulation or sheath of PVC static screen laid up in layers Number Number of pairs in centre and successive layers of pairs First layer Second layer Third layer Fourth layer 1 1 2 2(quad) 5 5 10 2 8 15 5 10 20 1 6 13

RD Y (St) Lg

210

ELKABEL

PVC insulation

pairs stranded in layers sheath of PVC.


Color coding

static screen

INSTRUMENTATION AND CONTROL CABLES

Pair no 1 2 3 4 5 6 7 8 9 10

a - wire white white white white white red red red red red

b - wire blue orange green brown gray blue orange green brown gray

Pair no 11 12 13 14 15 16 17 18 19 20

a - wire black black black black black yellow yellow yellow yellow yellow

b - wire blue orange green brown gray blue orange green brown gray

Construction data
Number of pairs External diameter approx. mm x2x0,52 /5class Lg 1 2 5 10 15 20 1 2 5 10 15 20 1 2 5 10 15 20 6,1 7,0 12,3 16,3 19,0 21,4 6,5 7,5 13,2 17,6 20,5 23,3 7,4 8,8 15,5 20,7 24,3 27,6 13 22 49 94 139 184 19 34 78 151 224 298 34 64 152 300 448 597 42 63 148 262 366 465 50 72 171 306 430 550 71 112 269 491 714 920 Copper weight kg/km Cable weight approx. kg/km

x2x0,752 /5class Lg

x2x1,52 /5class Lg

ELKABEL

211

RE-2Y(St)Y-fl
INSTRUMENTATION AND CONTROL CABLES

Standard:EN 50288-7

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings, when require non-proliferation of flames.

Cable construction
Conductor bare copper conductor nominal area: 0.50mm2 - class 2 or 5 0.75mm2 - class 2 or 5 PE insulation each 2 wires are twisted to a pair the pairs are stranded into layers of polyester tapes of aluminium tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound flame retardant black

Technical data
Cross section in mm2/class2 0.5mm2 Cond. resistance - max. /km 36.8 Cross section in mm2/class5 Cond. resistance - max. Mutual capacitance at 800Hz-max. Insulation resistance min. Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen L/R ratio - max. H/ Temperature range mobile fixed Minimum bending radius approx. Flame retardance 0.5mm2 38.2 100nF/km 5G .km 250pF/250m 1000V 1500V 25 -5C to +50C -30C to +65C 10 x cable diameter test according to IEC 60 332-3 class C 0.75mm2 25.0 0.75mm2 25.5

Insulation Pairs Cable core Wrapping Screen Outer sheath Color

Cable core construction


Number Number of pairs in centre and successive layers of pairs First layer Second layer Third layer Fourth layer 1 1 2 2 4 4 8 1 7 12 3 9 16 5 11 20 1 6 13 24 2 8 14

RE 2Y (St) Y-fl

Type codes cable for control insulation of PE static screen sheath of PVC compound flame retardant

212

ELKABEL

PE insulation

pairs, stranded in layers static screen sheath of PVC flame retardant

INSTRUMENTATION AND CONTROL CABLES

Colour coding
Pair no. 1 2 a - wire black with sequential numbering imprint black with sequential numbering imprint b - wire white with sequential numbering imprint white with sequential numbering imprint

Construction data RE - 2Y(St)Y-fl...


Number of pairs External diameter approx. mm Nx2x0.5mm2 / class 2, Lg 1 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

Construction data RE - 2Y(St)Y-fl...


Number of pairs External diameter approx. mm Nx2x0.5mm2 / class 5, Lg 1 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

6.3 6.4 9.2 11.6 13.9 15.6 17.3 18.6

14 23 42 79 117 156 194 232

43 68 99 165 232 292 359 416

6.3 6.4 9.2 11.6 13.9 15.6 17.3 18.6

13 22 40 75 111 147 184 220

38 58 97 161 226 283 349 404

ELKABEL

213

RE-2Y(St)Y-fl PiMF

Standard: EN 50288-7

INSTRUMENTATION AND CONTROL CABLES

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings, when require non-proliferation of flames.

Cable construction
Conductor bare copper conductor nominal area: 0.50mm2 - class 2 or 5 0.75mm2 - class 2 or 5 PE insulation each 2 wires are twisted to a pair wrapping of plastic foil, drain wire 0.6 mm, tinned Cu, Al-PET foil, metal side on the inside, foil wrapping the PiMFpairs are stranded into layers of polyester tapes of aluminium tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound galvanized steel wire of PVC compound fire retardant black or other colour

Technical data
Cross section in mm2/class2 0.5mm2 Cond. resistance - max. /km 36.8 Cross section in mm2/class5 0.5mm2 Cond. resistance - max. Mutual capacitance at 800Hz-max. Insulation resistance min. Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen L/R ratio - max. H/ Temperature range mobile fixed Minimum bending radius approx. Flame retardance 38.2 120nF/km 5G .km 250pF/250m 1000V 1500V 25 -5C to +50C -30C to +65C 10 x cable diameter test according to IEC 60 332-3 class C 0.75mm2 25.0 0.75mm2 25.5

Insulation Pairs PiMF construction: Cable core Wrapping Screen Inner sheath Armour Outer sheath Sheath color

Cable core construction


RE 2Y (St) Y-fl PiMF Type codes instrumental cable insulation of PE static screen sheath of PVC compound fire retardant screened pairs Number Number of pairs in centre and successive layers of pairs First layer Second layer Third layer Fourth layer 1 1 2 2 4 4 8 1 7 12 3 9 16 5 11 20 1 6 13 24 2 8 14

214

ELKABEL

PE insulation

pairs, stranded in layers sheath of PVC


Colour coding

static screen

INSTRUMENTATION AND CONTROL CABLES

Pair no. 1 2

a - wire black with sequential numbering imprint black with sequential numbering imprint

b - wire white with sequential numbering imprint white with sequential numbering imprint

Construction data RE - 2Y(St)Y-fl...


Number of pairs External diameter approx. mm Nx2x0.5mm2 /PiMF class 2, Lg 2 4 8 12 16 20 24 Nx2x0.5mm2 /PiMF class 5, Lg 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

Construction data RE - 2Y(St)Y-fl...


Number of pairs External diameter approx. mm /PiMF class 2, Lg 2 4 8 12 16 20 24 Nx2x0.75mm2 /PiMF class 5, Lg 2 4 8 12 16 20 24 Nx2x0.75mm2 Copper weight kg/km Cable weight approx. kg/km

9.4 10.8 14.7 17.3 19.9 22.1 23.8 9.4 10.8 14.7 17.3 19.9 22.1 23.8

28 51 98 144 191 238 284 27 49 94 139 183 228 273

88 130 233 319 421 515 597 87 128 229 313 413 505 585

10.3 12.2 16.6 19.6 21.9 24.6 27.4 10.3 12.2 16.6 19.6 21.9 24.4 27.4

40 73 139 205 272 338 404 38 67 128 189 250 311 372

107 167 298 417 533 655 780 105 163 291 407 520 626 760

ELKABEL

215

RE-2Y(St)YSWAY-fl

Standard: EN 50288-7

INSTRUMENTATION AND CONTROL CABLES

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings, when require non-proliferation of flames.

Cable construction
Conductor bare copper conductor nominal area: 0.50mm2 - class 2 or 5 0.75mm2 - class 2 or 5 PE insulation each 2 wires are twisted to a pair the pairs are stranded into layers of polyester tapes of aluminium tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound galvanized steel wire of PVC compound fire retardant black

Technical data
Cross section in mm2/class2 0.5mm2 Cond. resistance - max. /km 36.8 Cross section in mm2/class5 0.5mm2 Cond. resistance - max. 38.2 Mutual capacitance at 100nF/km 800Hz-max. Insulation resistance min. 5G .km Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen L/R ratio - max. H/ Temperature range mobile fixed Minimum bending radius approx. Flame retardance 250pF/250m 1000V 1500V 25 -5C to +50C -30C to +65C 10 x cable diameter test according to IEC 60 332-3 class C 0.75mm2 25.0 0.75mm2 25.5

Insulation Pairs Cable core Wrapping Screen Inner sheath Armour Outer sheath Sheath color

Cable core construction


Number Number of pairs in centre and successive layers of pairs First layer Second layer Third layer Fourth layer 1 1 2 2 4 4 8 1 7 12 3 9 16 5 11 20 1 6 13 24 2 8 14

RE 2Y (St) Y-fl SWA

Type codes instrumental cable insulation of PE static screen sheath of PVC compound fire retardant galvanized steel wire

216

ELKABEL

PE insulation

pairs, stranded in layers static screen of PVC armoured sheat of PVC


Colour coding

bedding

INSTRUMENTATION AND CONTROL CABLES

Pair no. 1 2

a - wire black with sequential numbering imprint black with sequential numbering imprint

b - wire white with sequential numbering imprint white with sequential numbering imprint

Construction data R-2Y(St)YSWAY-fl...


Number of pairs External diameter approx. mm Nx2x0.5mm2 / class 2 1 2 4 8 12 16 20 24 Nx2x0.5mm2 / class 5 1 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

Construction data R-2Y(St)YSWAY-fl...


Number of pairs External diameter approx. mm Nx2x0.75mm2 / class 2 1 2 4 8 12 16 20 24 Nx2x0.75mm2 / class 5 1 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

10.3 12.6 13.8 16.4 18.7 21.3 23.2 24.5 10.3 12.6 13.8 16.4 18.7 21.3 23.2 24.5

23 23 42 80 117 155 192 230 22 22 40 76 111 147 182 218

236 307 367 502 628 867 1001 1101 235 306 366 498 623 859 992 1090

10.2 13.1 14.5 17.4 20.0 22.7 24.8 26.4 10.2 13.1 14.5 17.4 20.0 22.7 24.8 26.4

18 32 60 115 171 227 285 341 17 30 56 109 161 213 268 321

224 331 409 573 731 1005 1166 1304 223 329 406 566 721 992 1149 1284

ELKABEL

217

RE-2Y(St)YSWAY-fl - PiMF

Standard: EN 50288-7

INSTRUMENTATION AND CONTROL CABLES

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings , when require non-proliferation of flames.

Cable construction
Conductor bare copper conductor nominal area: 0.50mm2 - class 2 or 5 0.75mm2 - class 2 or 5 PE insulation each 2 wires are twisted to a pair wrapping of plastic foil, drain wire 0.6 mm, tinned Cu, Al-PET foil, metal side on the inside, foil wrapping the PiMF pairs are stranded into layers of polyester tapes of aluminium tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound galvanized steel wire of PVC compound flame retardant black or other colour

Technical data
Cross section in mm2/class2 0.5mm2 Cond. resistance - max. /km 36.8 Cross section in mm2/class5 0.5mm2 Cond. resistance - max. Mutual capacitance at 800Hz-max. Insulation resistancemin. 38.2 100nF/km 5G .km 0.75mm2 25.0 0.75mm2 25.5

Insulation Pairs PiMF construction: Cable core Wrapping Screen Inner sheath Armour Outer sheath Sheath color

Capacitance unbalances at 250pF/250m 800Hz K1- max. Test voltage 50Hz, 1 min. wire - wire wire - screen L/R ratio - max. H/ Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. Flame retardance 1000V 1500V 25 300V -5C to +50C -30C to +65C 10 x cable diameter test according to IEC 60 332-3 class C

Cable core construction


Type codes RE 2Y (St) Y-fl PiMF SWA data cable insulation of PE static screen sheath of PVC compound fire retardant screened pairs galvanized steel wire , armour Number Number of pairs in centre and successive layers of pairs First layer Second layer Third layer Fourth layer 1 1 2 2 4 4 8 1 7 12 3 9 16 5 11 20 1 6 13 24 2 8 14

218

ELKABEL

PE insulation pairs, stranded in layers static screen bedding of PVC Armoured Sheath of PVC

INSTRUMENTATION AND CONTROL CABLES

Colour coding
Pair no. 1 2 a - wire black with sequential numbering imprint black with sequential numbering imprint b - wire white with sequential numbering imprint white with sequential numbering imprint

Construction data RE - 2Y(St)YSWAY-fl


Number of pairs External diameter approx. mm Nx2x0.5mm2 / PiMF class 2 2 4 8 12 16 20 24 Nx2x0.5mm2 / PiMF class 5 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

Construction data RE - 2Y(St)YSWAY-fl


Number of pairs External diameter approx. mm Nx2x0.75mm2 / PiMF class 2 2 4 8 12 16 20 24 Nx2x0.75mm2 / PiMF class 5 2 4 8 12 16 20 24 Copper weight kg/km Cable weight approx. kg/km

14.0 15.6 19.7 23.4 25.8 28.2 29.9 14.0 15.6 19.7 23.4 25.8 28.2 29.9

28 52 100 148 196 243 291 27 50 96 142 188 234 279

268 334 505 780 931 1078 1200 267 332 501 774 923 1068 1189

14.9 17 22.3 25.4 27.8 30.9 34.6 14.9 17 22.3 25.4 28 30.7 34.6

40 73 138 204 270 336 402 38 69 131 194 256 319 381

302 395 729 899 1076 1278 1674 300 391 722 889 1078 1244 1654

ELKABEL

219

RE-2X(St)Y -fr
INSTRUMENTATION AND CONTROL CABLES

Similar to EN 50288

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings , when require non-proliferation of flames.

Cable construction
Conductor bare copper conductor according to IEC 60228, nominal area: 0.5mm2 = 7x 0.3 mm 1.0mm2 = 7x0.43mm, class 2 1.3mm2 = 7x0.49mm, class 2 XLPE according to IEC 60502-1 Black/white with imprinted numbers 1/1, 2/2 etc. each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of aluminium tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound , flame-retardant coloured black

Technical data
Cross section in mm2 0.5 0.75 24.6 60 1.3 14.2 70 Cond. resistance - max. /km 36.8 Mutual capacitance at 800Hz- max. nF/km Insulation resistance min 55 5G .km

Insulation Core identification Pairs Cable core Wrapping Screen Sheath

Max. conductor temperature 70 Test voltage 50Hz, 1 min. wire - wire wire - screen Temperature range mobile fixed Minimum bending radius approx Test Flame rerardant 1500V 1500V -5C to +50C -40C to +70C 7.5 x cable diameter IEC 60502-1 IEC 60332-3 klass C

Type codes RE - control cable 2X XLPE insulation (St) static screen Y-fr sheath of special PVC, flame-retardant

220

ELKABEL

XLPE insulation

pairs pairs stranded in layers sheath of PVC flame retardant


Construction data RE - 2XY(St)Y-fr

static screen

INSTRUMENTATION AND CONTROL CABLES

Number of pairs

External diameter approx. mm

Copper weight kg/km 14 23 42 80 117 155 192 230 342 455 90 115 180 280 365 450 555 625 860 1090 35 60 118 225 335 445 558 669

Cable weight approx. kg/km 78 97 151 225 297 364 429 493 679 857 20 33 59 111 162 215 265 320 475 630 65 113 196 350 496 638 779 918

Nx2x0.5mm2

Nx2x0.75mm2

1 2 4 8 12 16 20 24 36 48 1 2 4 8 12 16 20 24 36 48 1 2 4 8 12 16 20 24

7.5 8.2 11.0 13.4 15.6 17.3 18.9 20.3 24.0 27.0 8.0 8.7 12.0 14.7 17.2 19.2 21.0 22.6 26.8 30.3 6.7 9.9 11.9 15.3 18.2 20.6 22.7 24.7

Nx2x1.3mm2

ELKABEL

221

RE-2X(St)Y - fr PiMF

Similar to EN 50288

INSTRUMENTATION AND CONTROL CABLES

Application
These cables are used for data transfer in measuring and control appliances The screen of metal foil protects the circuits from external interfering signals. The cables are suitable for fixed installation in dry and wet premises as well as for outdoor installation on the walls of buildings , when require non-proliferation of flames

Cable construction
Conductor bare copper conductor according to IEC 60228, nominal area: 0.5mm2 = 7x 0.3 mm 1.3mm2 = 7x0.49mm XLPE according to IEC 60502-1 Black/white with imprinted numbers 1/1, 2/2 etc. each 2 wires are twisted to a pair wrapping of plastic foil drain wire 0.6 mm, tinned Cu, Al-PET foil, metalside on the inside, foil wrapping the pimf pairs are stranded into layers with 1 orange communications core* several layers of plastic tapes of aluminium tape one side coated with polyester and 1 tinned copper wire 0.5mm2 of PVC compound , flame-retardant coloured black or other colour

Technical data
Cross section in mm2 Cond. resistance - max. /km Mutual capacitance at 800Hz- max. Insulation resistance min. 0.5 36.8 120 5G .km 1.3 14.2

Insulation Core identification Pairs Pimf construction: Cable core Wrapping Screen Sheath

Max. conductor temperature 70 Test voltage 50Hz, 1 min. wire - wire wire - screen Cable rated voltage U0/U Temperature range mobile fixed Minimum bending radius approx Test Flame rerardant 1500V 1500V 300/300V -5C to +50C -40C to +70C 7.5 x cable diameter IEC 60502-1 IEC 60332-3 class C

RE 2X (St) Yfr PiMF

Type codes control cable XLPE insulation static screen sheath of special PVC, flame-retardant screened pairs

222

ELKABEL

XLPE insulation screened by pairs pairs stranded in layers static screen sheath of PVC flame retardant

INSTRUMENTATION AND CONTROL CABLES

Construction data RE - 2X(St)Y-fr


Number of pairs External diameter approx. mm Nx2x0.5mm2 PiMF 1 2 4 8 12 1 2 4 8 12 9.6 11.7 12.5 14.7 17.7 7.6 13.5 15.5 20.2 21.5 31 36 61 122 165 33 65 122 232 352 105 130 171 248 355 85 185 275 460 599 Copper weight kg/km Cable weight approx. kg/km

Nx2x1.3mm2 PiMF

ELKABEL

223

PVC/PVC
INSTRUMENTATION AND CONTROL CABLES

Similar to BS 6346

Application
These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.

Cable construction
Conductor Conductor size Insulation -material -radial thickness,nom Cable core Wrapping Inner Sheath Outer sheath Sheath colour solid copper conductor to BS 6360 1.00mm2 =1/1.13mm 1.50mm2 =1/1.38mm PVC type TI1 complying to BS 7655 0.6mm the wires are stranded into layers minimum of 1 layer of plastic tape. PVC compound type TM1 complying to BS 7655, black PVC compound type TM1 complying to BS 7655 orange

Technical data
Cross section in mm2: Cond.resistance at 20oC max.: /km Mutual capacitance at 800Hz. max.nF/km Insulation resistance min. .km Test voltage 50Hz, 1 min. wire - wire Temperature range mobile fixed Minimum bending radius approx. 1.0 18.1 110 100 3500V -5C to +50C -30C to +70C 10 x cable diameter 1.5 12.1 120 100

Cable core construction


Number of wires 4 8 12 16 20 Centre 4 1 2 f f First layer Second layer

PVC

Type codes insulation or sheath of PVC

7 9 5 7

11 13

224

ELKABEL

PVC insulation

wires stranded in layers wraping bedding sheath of PVC


Colour coding

PVC

INSTRUMENTATION AND CONTROL CABLES

Number of wires 1 2 3 4 5 6 7

a-wire red white blue black green yellow brown

Number of wires 8 9 10 11 12 13 14

a-wire orange grey violet white/red blue/red black/red grey/red

Number of wires 15 16 17 18 19 20

a-wire yellow/red brown/red green/red orange/red violet/red blue/ white

Construction data PVC/PVC


Number of wires mm2 4x1.00 8x1.00 12x1.00 16x1.00 20x1.00 4x1.50 8x1.50 12x1.50 16x1.50 20x1.50 External diameter approx. mm 10.1 12.4 14.6 16.1 17.4 10.7 13.4 15.5 17.2 18.7 Copper weight mm 36 72 108 145 180 55 108 162 218 270 Cable weight approx. kg/km 140 218 305 385 457 165 267 378 480 575

ELKABEL

225

PVC/SWA/PVC
INSTRUMENTATION AND CONTROL CABLES

Similar to BS 6346

Application
These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is anticipated.

Cable construction
Conductor Conductor size Insulation -material -radial thickness,nom Cable core Wrapping Inner Sheath Armour Outer sheath Sheath colour solid copper conductor to BS 6360 1.00mm2 =1/1.13mm 1.50mm2 =1/1.38mm PVC type TI1 complying to BS 7655 0.6mm the wires are stranded into layers minimum of 1 layer of plastic.tape PVC compound type TM1 complying to BS 7655, black single layer of galvanized steel wires complying to BS 1442 PVC compound type TM1 complying to BS 7655 orange

Technical data
Cross section in mm2: Cond.resistance at 20oC max.: /km Mutual capacitance at 800Hz. max.nF/km Insulation resistance min. .km Voltage rating: Test voltage 50Hz, 1 min. wire - wire wire - armour Temperature range mobile fixed Minimum bending radius approx. 1.0 18.1 1.5 12.1

120 100

140 100

600/1000V 3500V 3500V -5C to +50C -30C to +70C 15 x cable diameter

Cable core construction


Type codes PVC insulation or sheath of PVC SWA - galvanized steel wires armour Number of wires 4 8 12 16 20 Centre 4 1 2 f f First layer Second layer

7 9 5 7

11 13

226

ELKABEL

PVC insulation

wires stranded in layers wraping ding armour sheath of PVC .


Colour coding

PVC bed-

INSTRUMENTATION AND CONTROL CABLES

Number of wires 1 2 3 4 5 6 7

a-wire brown yellow green red white blue black

Number of wires 8 9 10 11 12 13 14

a-wire orange red/white grey red/blue violet brown/red yellow/red

Number of wires 15 16 17 18 19 20

a-wire grey/red black/red violet/red orange/red green/red blue/ white

Construction data PVC/SWA/PVC


Number of wires mm2 4x1 8x1 12x1 16x1 20x1 4x1.5 8x1.5 12x1.5 16x1.5 20x1.5 Diameter of armour wire mm 0.9 0.9 1.25 1.25 1.25 0.9 0.9 1.25 1.25 1.25 External diameter approx. mm 11.9 14.2 16.9 18.6 19.9 12.5 15.2 18.0 19.7 21.2 Copper weight kg/km 36 72 108 145 180 55 108 162 218 270 Cable weight approx. kg/km 295 415 636 744 855 330 480 735 875 1010

ELKABEL

227

PVC/PVC/SWA/PVC x2x1/0.6

Similar to ESI 09-6, issue 5

OMMUNICATION AND CONTROL CABLE

Application
These cables are preferentially used in outdoor applications, underground and where mechanical damage is not anticipated.

Cable construction
Conductor Insulation Pair Cable core Wrapping Inner sheath Armour Outer sheath solid tinned copper conductor diameter 0.6 mm PVC type TI1 complying to BS 6746; Nominal radial thickness - 0.2mm each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. PVC compound type TM1 complying to BS 6746 single layer of galvanized steel wires complying to BS 1442 PVC compound type TM1 complying to BS 6746, black

Technical data
Conductor diameter 0.6+/- 0.01mm Cond.resistance at 20oC max.: 66M.km Insulation resistance min. 80M.km

Mutual capacitance at 800Hz. max. 120nF/km Capacitance unbalances at 270pF/500m 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire 2000V all wire - eart 5000V Operating voltage peak value 150V Temperature range mobile -5C +50C fixed -30C +70C Minimum bending radius 15 x cable diameter approx.

Cable core construction


Number of pairs 2 5 10 20 30 50 100 First layer 2(quad) 5 2 1 4 4 2 6 8 10 10 8 Number of pairs in centre and successive layers Second layer Third layer Fourth layer Fifth layer Sixth layer

13 16 15 14 21 20

25

31

228

ELKABEL

PVC insulation

pairs stranded in layers PVC bedding armour sheath of PVC


Color coding

OMMUNICATION AND CONTROL CABLE

Number of pair 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise

b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Number of pair 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise

b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Construction data PVC/PVC/SWA/PVC x2x1/0.6


Number of pairs 2x2x1/0.6 5x2x1/0.6 10x2x1/0.6 20x2x1/0.6 30x2x1/0.6 50x2x1/0.6 100x2x1/0.6 Diameter of armour wire mm 0.9 0.9 0.9 0.9 1.25 1.25 1.6 External diameter approx. mm 8.3 10.9 12.7 15.4 18.1 21.8 29.8 Copper weight kg/km 11 27 52 105 160 265 530 Cable weight approx. kg/km 155 255 340 501 748 1040 1948

ELKABEL

229

PVC/PVC/SWA/PVC x2x1/0.8

Similar to ESI 09-6, issue 5

OMMUNICATION AND CONTROL CABLE

Application
These cables are preferentially used in outdoor applications, underground and where mechanical damage is not anticipated.

Cable construction
Conductor Insulation Pair Cable core Wrapping Inner Sheath Armour Outer sheath solid tinned copper conductor diameter 0.8 mm PVC type TI1 complying to BS 6746 each 2 wires are twisted to a pair the pairs are stranded into layers or units minimum of 1 layer of plastic tape. PVC compound type TM1 complying to BS 6746 single layer of galvanized steel wires complying to BS 1442 PVC compound type TM1 complying to BS 6746

Technical data
Conductor diameter 0.8+/- 0.01mm Cond.resistance at 20oC max.: 36.8M.km Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire all wire - eart Operating voltage Temperature range mobile fixed Minimum bending radius approx. 80M.km 150nF/km 300pF/500m 2000V 5000V 150V -5C +50C -30C +70C 15 x cable diameter

Cable core construction


Number of pairs 2 5 10 15 20 30 40 50 Centre 2 5 2 5 1 3 4 5 First layer Second layer

8 10 6 Number of units 10x2

13

Each unit is lappedwith coloured tape for identification as follows: Unit 1 Blue Unit 2 Orange PVC Unit 3 Green SWA Unit 4 Brown Unit 5 Grey

Type codes insulation or sheath of PVC armour

230

ELKABEL

PVC insulation pairs stranded in layers or units bedding armour sheath of PVC
Color coding
Number of pair 1 2 3 4 5 6 7 8 9 10 a-wire white white white white white red red red red red b-wire blue orange green brown grey blue orange green brown grey Number of pair 11 12 13 14 15 66 17 18 19 20 a-wire black black black black black yellow yellow yellow yellow yellow

PVC

OMMUNICATION AND CONTROL CABLE

b-wire blue orange green brown grey blue orange green brown grey

2pair (quad cables) - white, red, blue, orange

Construction data PVC/PVC/SWA/PVC... x2x1/0.8


Number of pairs Diameter of armour wire mm 0.9 0.9 1.25 1.25 1.6 1.6 1.6 External diameter approx. mm 9.5 13.1 16.6 20.6 25.3 27.7 32.2 Copper weight kg/km 19 47 93 186 279 372 472 Cable weight approx. kg/km 193 334 572 839 1261 1500 1874

2x2x0.8 5x2x0.8 10x2x0.8 20x2x0.8 30x2x0.8 40x2x0.8 50x2x0.8

ELKABEL

231

PVC/PVC/SWA/PVC x2x1/0.9

Standard: ESI 09-6, issue 5

OMMUNICATION AND CONTROL CABLE

Application
These cables are preferentially used in outdoor applications, underground and where mechanical damage is not anticipated..

Cable construction
Conductor Insulation Pair Cable core Wrapping Inner sheath Armour Outer sheath solid tinned copper conductor diameter 0.9 mm PVC type TI1 complying to BS 6746; Nominal radial thickness - 0.3mm each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. PVC compound type TM1 complying to BS 6746 single layer of galvanized steel wires complying to BS 1442 PVC compound type TM1 complying to BS 6746, black

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire all wire - eart Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. 0.9+/- 0.01mm 29.67 M.km 80M.km 150nF/km 400pF/500m 2000V 5000V 150V -5C +50C -30C +70C 15 x cable diameter

Cable core construction


Number of pairs 2 5 10 15 20 25 30 50 75 100 First layer 2(quad) 5 2 5 1 2 4 4 3 2 6 10 6 8 10 10 9 8 13 15 16 15 15 14 Number of pairs in centre and successive layers Second layer Third layer Fourth layer Fifth layer Sixth layer

21 21 20

27 25

31

232

ELKABEL

PVC insulation

pairs stranded in layers PVC bedding armour sheath of PVC


Color coding

OMMUNICATION AND CONTROL CABLE

Number of pair 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Number of pairs

a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise

b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Number of pair 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise Copper weight kg/km 24 59 117 177 235 294 353 471 589 442 1201

b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow Cable weight approx. kg/km 207 372 641 796 946 1245 1401 1686 1995 2342 3613

Construction data PVC/PVC/SWA/PVC x2x1/0.9


2x2x1/0.9 5x2x1/0.9 10x2x1/0.9 15x2x1/0.9 20x2x1/0.9 25x2x1/0.9 30x2x1/0.9 40x2x1/0.9 50x2x1/0.9 75x2x1/0.9 100x2x1/0.9 Diameter of armour wire mm 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 External diameter approx. mm 9.7 13.6 17.4 19.5 21.3 23.9 25.5 28.2 31.0 37.0 41.8

ELKABEL

233

PVC/PVC/SWA/HDPE x2x1/0.6

Similar to ESI 09-6, issue 5

OMMUNICATION AND CONTROL CABLE

Application
These cables are preferentially used in outdoor applications, underground and where mechanical damage is not anticipated.

Cable construction
Conductor Insulation Pair Cable core Wrapping Inner sheath Armour Outer sheath solid tinned copper conductor diameter 0.6 mm PVC type TI1 complying to BS 6746 Nominal radial thickness - 0.2mm each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. PVC compound type TM1 complying to BS 6746 single layer of galvanized steel wires complying to BS 1442 PE compound type HDPE black

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire all wire - eart Operating voltage peak value Temperature range mobile fixed Minimum bending radius approx. 0.6+/- 0.01mm 66 M.km 80M.km 120nF/km 270pF/500m 2000V 5000V 150V -5C +50C -30C +70C 15 x cable diameter

Cable core construction


Number of pairs 2 5 10 20 30 50 100 Number of pairs in centre and successive layers First layer 2(quad) 5 2 1 4 4 2 6 8 10 10 8 13 16 15 14 21 20 25 31 Second layer Third layer Fourth layer Fifth layer Sixth layer

234

ELKABEL

PVC insulation

pairs stranded in layers PVC bedding armour sheath of HDPE


Color coding

OMMUNICATION AND CONTROL CABLE

Number of pair 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise

b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Number of pair 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise

b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Construction data PVC/PVC/SWA/HDPE x2x1/0.6


Number of pairs Diameter of armour wire mm 0.9 0.9 0.9 0.9 1.25 1.25 1.6 External diameter approx. mm 8.3 10.9 12.7 15.4 18.1 21.8 29.8 Copper weight kg/km 11 27 52 105 160 265 530 Cable weight approx. kg/km 137 229 303 446 672 924 1731

2x2x1/0.6 5x2x1/0.6 10x2x1/0.6 20x2x1/0.6 30x2x1/0.6 50x2x1/0.6 100x2x1/0.6

ELKABEL

235

PVC/OSCR/PVC/SWA/PVC ...x2x0.8

ESI 09-6, issue 6

OMMUNICATION AND CONTROL CABLE

Applications
These armoured and PVC insulated cables are utilized in electrical instrument circuits to provide communication services.

Cable construction
Conductor Insulation Pair Cable core Wrapping Screen Inner Sheath Armour Outer sheath solid copper conductor diameter 0.8 mm PVC type TI1 complying to BS 6746 each 2 wires are twisted to a pair the pairs are stranded into lears or units minimum of 1 layer of plastic tape. of aluminium tape one side coated with polyester and 1 solid tinned copper wire with diameter 0.8mm PVC compound type TM1 complying to BS 6746 single layer of galvanized steel wires complying to BS 1442 PVC compound type TM1 complying to BS 6746, black

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire wire - screen all wire - eart Operating voltage Temperature range mobile fixed Minimum bending radius approx. 0.8+/- 0.01mm 36.8M.km 80M.km 150nF/km 400pF/500m 500V 2000V 5000V 150V -5C +50C -30C +70C 15 x cable diameter

Cable core construction


Number of pairs 2 5 10 15 20 30 40 50 Centre 2 5 2 5 1 3 4 5 First layer Second layer

8 10 6 Number of units 10x2

13

Each unit is lapped with coloured tape for identification as follows: Unit Unit Unit Unit Unit 1 2 3 4 5 Blue Orange Green Brown Grey Type codes PVC insulation or sheath of PVC SWA - armour OSCR - screen of aluminium tape

236

ELKABEL

PVC insulation pairs stranded into units screen bedding armour sheath of PVC
Color coding
Number of pair 1 2 3 4 5 6 7 8 9 10 a-wire white white white white white red red red red red b-wire blue orange green brown grey blue orange green brown grey Number of pair 11 12 13 14 15 16 17 18 19 20 a-wire black black black black black yellow yellow yellow yellow yellow

PVC

OMMUNICATION AND CONTROL CABLE

b-wire blue orange green brown grey blue orange green brown grey

2pair (quad cables) - white, red, blue, orange

Construction data PVC/PVC/SWA/PVC... x2x1/0.8


Number of pairs Diameter of armour wire mm 0.90 0.90 1.25 1.25 1.25 1.25 1.60 1.60 External diameter approx. mm 10.3 13.7 17.0 18.6 20.8 23.6 26.8 28.8 Copper weight kg/km 24 51 98 144 191 284 377 470 Cable weight approx. kg/km 227 382 617 741 898 1125 1521 1742

2x2x0.8 5x2x0.8 10x2x0.8 15x2x0.8 20x2x0.8 30x2x0.8 40x2x0.8 50x2x0.8

ELKABEL

237

LSZH/LSZH ...x2x1/0.8
HALOGEN - FREE COMUNICATION AND CONTROL CABLE

According to ESI 09-6, issue 6

Application
These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground, where a particular protection against fire and fire damage for human life and equipment is necessary.

Description
Conductor Insulation Pair Cable core Wrapping Inner sheath Outer sheath solid tinned copper conductor diameter 0.8 mm of halogen free polymer compound each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. of halogen free polymer compound complying to BS 7655,part 6.1 halogen free polymer compound complying to BS 7655,part 6.1

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire Operating voltage Temperature range mobile fixed Minimum bending radius approx. 0.8+/- 0.01mm 36.8M.km 100M.km 150nF/km 270pF/500m

2000V 150V -5C +50C -30C +70C 15 x cable diameter

2pair (quad cables) - white, red, blue, orange Unit Unit Unit Unit Unit 1 2 3 4 5 Blue Orange Green Brown Grey Type codes LSZH - of halogen free polymer compound

Identification of cable pairs


Number of pair 1 2 3 4 5 6 7 8 9 10 a-wire white white white white white red red red red red b-wire blue orange green brown grey blue orange green brown grey Number of pair 11 12 13 14 15 16 17 18 19 20 a-wire black black black black black yellow yellow yellow yellow yellow b-wire blue orange green brown grey blue orange green brown grey

238

ELKABEL

LSZH insulation pairs stranded in layers LSZH bedding sheath of LSZH

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Cable core construction


Number of pairs 2 5 10 15 20 Centre 2 5 2 5 1 3x10pair 1 First layer Second layer

8 10 6 Number of units 10x2 5x10pair

13 2x20pair 1

30 40 50

Mechanical data LSZH/LSZH ...x2x0.8


Number of pairs External diameter approx. mm 7.1 7.9 11.3 14.3 15.9 18.1 21.5 24.1 28.0 Copper weight kg/km 10 19 47 93 140 188 280 375 470 Cable weight approx. kg/km 65 85 165 269 350 455 622 788 966

1x2x0.8 2x2x0.8 5x2x0.8 10x2x0.8 15x2x0.8 20x2x0.8 30x2x0.8 40x2x0.8 50x2x0.8

ELKABEL

239

LSZH/LSZH ...x2x1/0.9
HALOGEN - FREE COMUNICATION AND CONTROL CABLE

According to ESI 09-6, issue 5

Application
These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground, where a particular protection against fire and fire damage for human life and equipment is necessary.

Description
Conductor Insulation Pair Cable core Wrapping Inner sheath Outer sheath solid tinned copper conductor diameter 0.9 mm of halogen free polymer compound each 2 wires are twisted to a pair the pairs are stranded into layers Minimum of 1 layer of plastic tape. of halogen free polymer compound complying to BS 7655,part 6.1 halogen free polymer compound complying to BS 7655,part 6.1

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire Operating voltage Temperature range mobile fixed Minimum bending radius approx. 0.9+/- 0.01mm 29.67 M.km 100M.km 150nF/km 270pF/500m 2000V 150V -5C +50C -30C +70C 15 x cable diameter

Cable core construction


Number of pairs 2 5 10 15 20 25 30 50 75 100 First layer 2(quad) 5 2 5 1 2 4 4 3 2 Number of pairs in centre and successive layers Second layer Third layer Fourth layer Fifth layer Sixth layer

8 10 6 8 10 10 9 8

13 15 16 15 15 14

21 21 20

27 25

31

240

ELKABEL

LSZH insulation pairs stranded in layers LSZH bedding sheath of LSZH

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Identification of cable pairs


Number of pair 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow Number of pair 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 a-wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise b-wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Mechanical data LSZH/LSZH ...x2x1/0.9


Number of pairs 2x2x1/0.9 5x2x1/0.9 10x2x1/0.9 15x2x1/0.9 20x2x1/0.9 25x2x1/0.9 30x2x1/0.9 40x2x1/0.9 50x2x1/0.9 75x2x1/0.9 100x2x1/0.9 External diameter approx. mm 8.30 11.8 14.9 17.0 18.8 20.7 22.3 25.0 28.8 33.0 37.8 Copper weight kg/km 24 59 117 177 235 294 353 471 589 442 1201 Cable weight approx. kg/km 99 188 306 418 518 630 735 933 1172 1099 2188

ELKABEL

241

LSZH/LSZH/SWA/LSZH x2x1/0.8

According to ESI 09-6, issue 6

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Applications
These armoured control and signal cables are utilized in industrial areas for installations provided with electronic control or monitoring equipment, expecially when a high mechanical resistance is required.

Description
Conductor Insulation Pair Cable core Wrapping Inner sheath Armour Outer sheath solid tinned copper conductor diameter 0.8 mm of halogen free polymer compound each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. of halogen free polymer compound complying to BS 7655,part 6.1 single layer of galvanized steel wires complying to BS 1442 halogen free polymer compound complying to BS 7655,part 6.1

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire all wire - eart Operating voltage Temperature range mobile fixed Minimum bending radius approx. 0.8+/- 0.01mm 36.8M.km 100M.km 150nF/km 270pF/500m 2000V 5000V 150V -5C +50C -30C +70C 15 x cable diameter

Unit Unit Unit Unit Unit

1 2 3 4 5

Blue Orange Green Brown Grey

Type codes LSZH - of halogen free polymer compound SWA - armour

Cable core construction


Number of pairs 2 5 10 15 20 Centre 2 5 2 5 1 3x10pair 1 First layer Second layer

8 10 6 Number of units 10x2 5x10pair

13 2x20pair 1

30 40 50

Each unit is lappedwith coloured tape for identification as follows:

242

ELKABEL

LSZH insulation pairs stranded in layers LSZH bedding armour sheath of LSZH

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Identification of cable pairs


Number of pair 1 2 3 4 5 6 7 8 9 10 a - wire white white white white white red red red red red b - wire blue orange green brown grey blue orange green brown grey Number of pair 11 12 13 14 15 16 17 18 19 20 a - wire black black black black black yellow yellow yellow yellow yellow b - wire blue orange green brown grey blue orange green brown grey

2pair (quad cables) - white, red, blue, orange

Mechanical data LSZH/LSZH/SWA/LSZH ...x2x0.8


Number of pairs Diameter of armour wire mm 0.90 0.90 0.90 1.25 1.25 1.25 1.25 1.60 1.60 External diameter approx. mm 8.9 10.1 13.1 16.8 18.4 20.6 24.0 27.3 31.2 Copper weight kg/km 10 19 47 93 140 188 280 375 470 Cable weight approx. kg/km 167 219 360 605 729 885 1122 1520 1837

1x2x0.8 2x2x0.8 5x2x0.8 10x2x0.8 15x2x0.8 20x2x0.8 30x2x0.8 40x2x0.8 50x2x0.8

ELKABEL

243

LSZH/LSZH/SWA/LSZH x2x1/0.9

According to ESI 09-6, issue 5

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Applications
These armoured control and signal cables are utilized in industrial areas for installations provided with electronic control or monitoring equipment, expecially when a high mechanical resistance is required.

Description
Conductor Insulation Pair Cable core Wrapping Inner sheath Armour Outer sheath solid tinned copper conductor diameter 0.9 mm of halogen free polymer compound each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. of halogen free polymer compound complying to BS 7655,part 6.1 single layer of galvanized steel wires complying to BS 1442 halogen free polymer compound complying to BS 7655,part 6.1

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire all wire - eart Operating voltage Temperature range mobile fixed Minimum bending radius approx. 0.9+/- 0.01mm 29.67 M.km 100M.km 150nF/km 270pF/500m 2000V 5000 V 150V -5C +50C -30C +70C 15 x cable diameter

Cable core construction


Number of pairs 2 5 10 15 20 25 30 50 75 100 First layer 2(quad) 5 2 5 1 2 4 4 3 2 Number of pairs in centre and successive layers Second layer Third layer Fourth layer Fifth layer Sixth layer

8 10 6 8 10 10 9 8

13 15 16 15 15 14

21 21 20

27 25

31

244

ELKABEL

LSZH insulation pairs stranded in layers LSZH bedding armour sheath of LSZH

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Identification of cable pairs


Number of pair 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 a - wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise b - wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow Number of pair 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 a - wire black black black black black blue blue blue blue blue orange orange orange orange green green green brown brown grey black black black black white white white blue blue blue green green green red red red red red grey grey orange orange yellow yellow brown turquise turquise turquise turquise turquise b - wire blue orange green brown grey white orange green brown grey white green brown grey white brown grey white grey white white red yellow violet red yellow violet red yellow violet red yellow violet grey orange yellow brown violet yellow violet yellow violet brown violet violet black blue red orange yellow

Mechanical data LSZH/LSZH/SWA/LSZH ...x2x1/0.9


Number of pairs 2x2x1/0.9 5x2x1/0.9 10x2x1/0.9 15x2x1/0.9 20x2x1/0.9 25x2x1/0.9 30x2x1/0.9 40x2x1/0.9 50x2x1/0.9 75x2x1/0.9 100x2x1/0.9 Diameter of armour wire mm 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 External diameter approx. mm 10.1 13.6 17.4 19.5 21.3 23.9 25.5 28.2 32.0 37.0 41.8 Copper weight kg/km 24 59 117 177 235 294 353 471 589 442 1201 Cable weight approx. kg/km 215 372 639 792 941 1238 1394 1676 2001 2332 3582

ELKABEL

245

LSZH/SCR/LSZH/SWA/LSZH x2x1/0.8

According to ESI 09-6, issue 6

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Application
These armoured and LSZH insulated cables are utilized in electrical instrument circuits to provide communication services. They can be used in areas where fire could create dense smoke and toxic fumes.

Description
Conductor Insulation Pair Cable core Wrapping Screen Inner sheath Armour Outer sheath Unit Unit Unit Unit Unit 1 2 3 4 5 solid tinned copper conductor diameter 0.8 mm of halogen free polymer compound each 2 wires are twisted to a pair the pairs are stranded into layers minimum of 1 layer of plastic tape. of aluminium tape one side coated with polyester and 1 solid tinned copper wire with diameter 0.8mm of halogen free polymer compound complying to BS 7655,part 6.1 single layer of galvanized steel wires complying to BS 1442 halogen free polymer compound complying to BS 7655,part 6.1 Blue Orange Green Brown Grey

Technical data
Conductor diameter Cond.resistance at 20oC max.: Insulation resistance min. Mutual capacitance at 800Hz. max. Capacitance unbalances at 800Hz: K1 - maximum Test voltage 50Hz, 1 min. wire - wire wire - screen all wire - eart Operating voltage Temperature range mobile fixed Minimum bending radius approx. 0.8+/- 0.01mm 36.8M.km 150M.km 150nF/km 270pF/500m 800V 1000V 5000V 150V -5C +50C -30C +70C 15 x cable diameter

Type codes LSZH - of halogen free polymer compound SWA - armour OSCR - screen of aluminium tape

Cable core construction


Number of pairs 2 5 10 15 20 Centre 2 5 2 5 1 3x10pair 1 First layer Second layer

8 10 6 Number of units 10x2 5x10pair

13 2x20pair 1

30 40 50

Each unit is lappedwith coloured tape for identification as follows:

246

ELKABEL

LSZH insulation pairs stranded in layers screen LSZH bedding armour Sheath of LSZH

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Identification of cable pairs


Number of pair 1 2 3 4 5 6 7 8 9 10 a-wire white white white white white red red red red red b-wire blue orange green brown grey blue orange green brown grey Number of pair 11 12 13 14 15 16 17 18 19 20 a-wire black black black black black yellow yellow yellow yellow yellow b-wire blue orange green brown grey blue orange green brown grey

2pair (quad cables) - white, red, blue, orange

Mechanical data LSZH/OSCR/LSZH/SWA/LSZH x2x0.8


Number of pairs Diameter of armour wire mm 0.90 0.90 0.90 1.25 1.25 1.25 1.25 1.60 1.60 External diameter approx. mm 9.1 10.3 13.3 17.0 18.6 20.8 24.2 27.5 31.6 Copper weight kg/km 14 24 52 99 145 192 285 380 475 Cable weight approx. kg/km 175 230 365 620 745 899 1139 1539 1870

`1x2x0.8 2x2x0.8 5x2x0.8 10x2x0.8 15x2x0.8 20x2x0.8 30x2x0.8 40x2x0.8 50x2x0.8

ELKABEL

247

JE-HCH ...x2x0.8 BD

Standard VDE 0815

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Pairs laid up in bundles with copper braid screen

Application
Safety installation cables are used for the transmission of signals and measuring datas in control circuits, where a particular protection against fire and fire damage for human life and equipment is necessary. Installation cables are not admissible for power installation purposes and direct burial.

Description
Conductor Insulation bare copper conductor diameter 0.8 mm insulation of halogen - free polymer compound type HI 1 according to VDE 0207 part 23 ; thickness 0.3mm each 2 wires are twisted to a pair 4 pairs laid up to a bundle by spirals imprinted numbers bundles laid up in layers layers of polyester foil braid of tinned Cu wires of halogen - free flame-retardant polymer compound , type HM 2 according to VDE 0207 part 24 grey or black

Technical data
73.2 M.km Cond. resistance at 20oC - max. 100M.km Insulation resistance min. Mutual capacitance at 800Hz120nF/km max. Capacitance unbalances at 200pF/100m 800Hz: K1- max. Test voltage 50Hz, 1 min. wire - wire 2000V wire - screen 5000V Operating voltage, peak value 250V Temperature range mobile -5C +50C -30C +70C fixed Testing according to DIN VDE 0472 and IEC Minimum bending radius 7.5 x cable diameter approx. test class C according to Flame test VDE 0472 part 804 and IEC 332 - 3

Pairs Bundle Bundle identification Cable core Wrapping Screen Sheath Sheath

Core identification
Identification of the cores by the colours of the insulation which are repeated in the same manner in each bundle.

Colours of the pairs


Pair Core Colour a blue 2 3 a b a b grey yellow green brown Cables with 2 pairs laid up as a star quad. Each bundle identified by open support spiral with imprinted numbers. b red 1 4 a white b black

Mechanical data JE-HCH ...x2x0.8 BD


No. of pairs Conductor mm 2x2x0.8 4x2x0.8 8x2x0.8 12x2x0.8 40x2x0.8 Thickness of the sheath mm 1.4 1.4 1.4 1.4 1.6 Overall diameter approx. mm 7.4 9.6 11.9 13.7 22.1 Lengths m 1000 1000 1000 1000 1000 Type of drums D/d/L* mm 650/340/530 800/450/530 1000/500/630 1000/500/630 1400/750/880 Copper weight approx. kg/km 40 73 123 173 481 Cable weight approx. kg/km 87 141 218 291 751

Note : D - flange diameter; d - core diameter; L - overall width

248

ELKABEL

JE-LiHCH ...x2x0.5mm2

According to VDE 0815

Halogen-free insulation pairs laid up in bundles with copper braid screen halogen-free sheath

HALOGEN - FREE COMUNICATION AND CONTROL CABLE

Application
Halogen-free installation cables with copper screen are used for telecommunications and information processing systems in environments susceptible to interference and for higher requirements on the signal transmission characteristics for optimum data transmissions. The overall braided screen of tinned copper wires provides against external and electromagnetic interference and ensures a perfect data transmission. These cables are also suitable for flexible and permanent installation in dry rooms. The use of installation cables for power cable applications and underground installation is not permitted.

Description
Conductor Construction of conductor Insulation Core identification Pair Bundle Type of lay-up Wrapping Screen Sheath Sheath colour plain Cu wires, flexible 0.5mm2 = 7x0.3 core insulation of halogen-free polymer compound HI 2 according to VDE 0207,part 23 according to VDE 0815 2 cores twisted to a pair 4 pairs laid up to a bundle Bundles laid up in layers plastic foil overlapping braid of tinned copper wires of halogen-free flame-retardant polymer compound type HM2 accord ing to VDE 0207 part 24 Grey or black

Technical data
Cross section in : Cond. resistance at 20oC max: Insulation resistance min.: Operating capacitance at 800Hz: max.: Capacitance unbalances at 800Hz max.: Test voltage, effective value, 50Hz core/core core/screen Operating voltage, peak value : Temperature range mobile fixed Minimum bending radius Bending once without tensile force:Multiple bending with tensile force Caloric load/flame test: 0.5 mm2 78.4 /km 100M.km 120 1) nF/km 200 2) pF/100m 500V 2000V 225V -5oC to +50oC -30oC to +70oC 2.5 x cable diameter 7.5 x cable diameter

1)The value may be exceeded by 20% by cables with up to 4 pairs.2) 20% of the values, min. one value up to 400pF permitted.

Colours of the pairs


pair 1 2 3 4 Core a b a b a b a b Basic colour blue red grey yellow green brown white black
Bundle: 4 pairs laid up to a bundle; Bundle identification: each bundle identified by open support spiral with imprinted numbers Method of counting: starting at the inner layer with no.1 and counting successively outwards in the same manner through each layer Cables with 2 pairs laid up as a star quad: winding 1: a-core blue; b-core red winding 2: a-core grey; b-core yellow

test class C according to VDE 0472 part 804 and IEC 332-3 according to VDE 0472 part Halogen-free properties : 813 and IEC 754-1 according to VDE 0472 part Smoke density : 816 Type codes JE - cable for industrial electronics Li - stranded wire conductor H - insulation or sheath of halogen-free compound C - screen of copper wire braid Cable weight approx. kg/km 95 161 247 338 421 520 597 750 926 1691

Mechanical data JE-LiHCH...x2x0.5 mm2


Number of pairs 2 4 8 12 16 20 24 32 40 80 External diameter approx. mm 7.7 10.4 12.6 14.9 16.6 18.5 19.9 22.3 24.8 33.6 Copper weight kg/km 42 77 124 176 223 272 314 402 491 916

ELKABEL

249

PE/PE/SWA/PE ...x2x1/0.8
CONTROL CABLE FOR INDUCED VOLTAGE UP TO 5KV

According to ESI 09-6, issue 3

Application
These cables are used for control, protection, signalling, telecommunications, and data transmission purpores associated with power distribution and transmission systems.

Description
Conductor Insulation Pairs Cable core Wrapping Inner sheath Armour Outer sheath solid copper conductor, diameter 0.8mm PE insulation type 03C according to BS 6234 each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of PE compound type 03C according to BS 6234 single layer of galvanized steel wires complying to BS 1442 of PE compound type 03C according to BS 6234 coloured black

Technical data
Conductor diameter Cond. resistance at 20C, max. : Mutual capacitance at 1000Hz -max. Insulation resistance at 20C, min. Capacitance unbalances at 1000Hz - max. Test voltage AC for 1 min. between each conductor & earth Mutual inductance at 5 kHz, max: Attenuation dB/km: at 300 Hz at 1000Hz at 2000Hz at 3000Hz at 4000Hz Characteristic impedance: at 1000Hz at 10 kHz Minimum bending radius approx. 0.8mm 73.6M.km 5 G.km 50nF/km 500pF/500m 5 kV 0.5 mH/100m Induced voltage Upto 5kv : 0.51 0.91 1.25 1.50 1.68 550 200 15 x cable diameter

Cable core construction


Number of pairs in centre and successive layers Number of pairs First layer 4 7 19 37 4 1 1 6 6 6 12 12 18 Second layer Third layer Fourth layer

250

ELKABEL

PE insulation pairs stranded in layer PE bedding armour sheath of PE

CONTROL CABLE FOR INDUCED VOLTAGE UP TO 5KV

Colour coding
Pair no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 a - wire red black orange green orange green orange black red green red green red green red green red green blue black red green red green red green red green red green red green red green red green blue b - wire yellow violet grey brown blue brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown white

Mechanical data PE/PE/SWA/PE ...x2x1/0.8


Number of pairs Diameter of armour wire mm 0.9 0.9 1.60 1.60 External diameter approx. mm 14.1 16.1 24.4 31.0 Copper weight kg/km 38 66 179 345 Cable weight approx. kg/km 325 410 1050 1570

4 7 19 37

ELKABEL

251

PE/PE/SWA/PE ...x2x1/0.8
CONTROL CABLE FOR INDUCED VOLTAGE UP TO 15 KV

According to ESI 09-6, issue 3

Application
These cables are used for control, protection, signalling, telecommunications, and data transmission purpores associated with power distribution and transmission systems.

Description
Conductor Insulation Pairs Cable core Wrapping Inner sheath Armour Outer sheath solid copper conductor, diameter 0.8mm PE insulation type 03C according to BS 6234 each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of PE compound type 03C according to BS 6234 single layer of galvanized steel wires complying to BS 1442 of PE compound type 03C according to BS 6234 coloured black

Technical data
Conductor diameter : Cond. resistance at 20C, max. : Mutual capacitance at 1000Hz - max. Insulation resistance at 20C, min. Capacitance unbalances at 1000Hz - max. Test voltage AC for 1 min. between each conductor & earth Mutual inductance at 5kHz, max: Attenuation dB/km: 300 Hz 1000Hz 2000Hz 3000Hz 4000Hz Characteristic impedance: 1000Hz 10 kHz Minimum bending radius approx. 0.8mm 73.6M.km 5 G.km 40nF/km 500pF/500m 15 kV 0.5 mH/100m Induced voltage 5kv - 15kv: 0.48 0.85 1.15 1.40 1.55 550 200 15 x cable diameter

Cable core construction


Number of pairs 4 7 19 37 First layer 4 1 1 6 Number of pairs in centre and successive layers Second layer Third layer 6 6 12 Fourth layer

12 18

252

ELKABEL

PE insulation pairs stranded in layers PE bedding armour sheath of PE

CONTROL CABLE FOR INDUCED VOLTAGE UP TO 15 KV

Colour coding
Pair no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 a - wire red black orange green orange green orange black red green red green red green red green red green blue black red green red green red green red green red green red green red green red green blue b - wire yellow violet grey brown blue brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown white

Mechanical data PE/PE/SWA/PE ...x2x1/0.8


Number of pairs Diameter of armour wire mm 1.25 1.25 1.60 2.00 External diameter approx. mm 19.2 21.6 31.1 40.4 Copper weight kg/km 38 66 179 348 Cable weight approx. kg/km 580 720 1430 2399

4 7 19 37

ELKABEL

253

PE/PE/SWA/PVC ...x2x1/0.8
CONTROL CABLE FOR INDUCED VOLTAGE UP TO 5KV

According to ESI 09-6, issue 3

Application
These cables are used for control, protection, signalling, telecommunications, and data transmission purpores associated with power distribution and transmission systems..

Description
Conductor Insulation Pairs Cable core Wrapping Inner sheath Armour Outer sheath solid copper conductor, diameter 0.8mm PE insulation type 03C according to BS 6234 each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of PE compound type 03C according to BS 6234 single layer of galvanized steel wires complying to BS 1442 of PVC compound type TM1 according to BS 7655, coloured black

Technical data
Conductor diameter : Cond. resistance at 20C max. Mutual capacitance at 1000Hz -max. Insulation resistance at 20C, min. Capacitance unbalances at 1000Hz - max. Test voltage AC for 1 min. between each conductor & earth Mutual inductance at 5kHz, max: Attenuation dB/km: 300 Hz 1000Hz 2000Hz 3000Hz 4000Hz Characteristic impedance: 1000Hz 10 kHz Minimum bending radius approx. 0.8mm 73.6M.km 5 G.km 50nF/km 500pF/500m 5 kV 0.5 mH/100m Induced voltage Upto 5kv 0.51 0.91 1.25 1.50 1.68 550 200 15 x cable diameter

Cable core construction


Number of pairs 4 7 19 37 First layer 4 1 1 6 Number of pairs in centre and successive layers Second layer Third layer 6 6 12 Fourth layer

12 18

254

ELKABEL

PE insulation pairs stranded in layer PE bedding armour sheath of PVC

CONTROL CABLE FOR INDUCED VOLTAGE UP TO 5KV

Colour coding
Pair no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 a - wire red black orange green orange green orange black red green red green red green red green red green blue black red green red green red green red green red green red green red green red green blue b - wire yellow violet grey brown blue brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown white

Mechanical data PE/PE/SWA/PVC ...x2x1/0.8


Number of pairs Diameter of armour wire mm 0.9 0.9 1.60 1.60 External diameter approx. mm 14.1 16.1 24.4 31.0 Copper weight kg/km 38 66 179 345 Cable weight approx. kg/km 360 450 1110 1660

4 7 19 37

ELKABEL

255

PE/PE/SWA/PVC ...x2x1/0.8
CONTROL CABLE FOR INDUCED VOLTAGE UP TO 15KV

According to ESI 09-6, issue 3

Application
These cables are used for control, protection, signalling, telecommunications, and data transmission purpores associated with power distribution and transmission systems.

Description
Conductor Insulation Pairs Cable core Wrapping Inner sheath Armour Outer sheath solid copper conductor, diameter 0.8mm PE insulation type 03C according to BS 6234 each 2 wires are twisted to a pair the pairs are stranded into layers several layers of plastic tapes of PE compound type 03C according to BS 6234 single layer of galvanized steel wires complying to BS 1442 of PVC compound type TM1 according to BS 7655, coloured black

Technical data
Conductor diameter : Cond. resistance 20C max. Mutual capacitance at 1000Hz -max. Insulation resistance at 20C, min. Capacitance unbalances at 1000Hz - max. Test voltage AC for 1 min. between each conductor & earth Mutual inductance at 5kHz, max: Attenuation dB/km: 300 Hz 1000Hz 2000Hz 3000Hz 4000Hz Characteristic impedance: 1000Hz 10 kHz Minimum bending radius approx. 0.8mm 73.6M.km 5 G.km 40nF/km 500pF/500m 15 kV 0.5 mH/100m Induced voltage 5kv - 15kv: 0.48 0.85 1.15 1.40 1.55 550 200 15 x cable diameter

Cable core construction


Number of pairs 4 7 19 37 First layer 4 1 1 6 Number of pairs in centre and successive layers Second layer Third layer 6 6 12 Fourth layer

12 18

256

ELKABEL

PE insulation pairs stranded in layer PE bedding armour sheath of PVC

CONTROL CABLE FOR INDUCED VOLTAGE UP TO 15KV

Colour coding
Pair no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 a - wire red black orange green orange green orange black red green red green red green red green red green blue black red green red green red green red green red green red green red green red green blue b - wire yellow violet grey brown blue brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown white

Mechanical data PE/PE/SWA/PVC ...x2x1/0.8


Number of pairs Diameter of armour wire mm 1.25 1.25 1.60 2.00 External diameter approx. mm 19.2 21.6 31.1 40.4 Copper weight kg/km 38 66 179 348 Cable weight approx. kg/km 665 820 1660 2780

4 7 19 37

ELKABEL

257

PE/PJF/PE/SWA/PVC ...x2x1/0.8
CONTROL CABLE FOR INDUCED VOLTAGE UP TO 15KV

ESI 09-6, issue 3

Application
These cables are used for control, protection, signalling, telecommunications, and data transmission purpores associated with power distribution and transmission systems..

Description
Conductor Insulation Pairs Cable core Filing Wrapping Inner sheath Armour Outer sheath solid copper conductor, diameter 0.8mm PE insulation type 03C according to BS 6234 each 2 wires are twisted to a pair the pairs are stranded into layers petroleum - based jelly several layers of plastic tapes of PE compound type 03C according to BS 6234 single layer of galvanized steel wires complying to BS 1442 of PVC compound type TM1 according to BS 7655, coloured black

Technical data
Conductor diameter : Cond. resistance at 20C max. Mutual capacitance at 1000Hz -max Insulation resistance at 20C, min. Capacitance unbalances at 1000Hz - max. Test voltage AC for 1 min. between each conductor & earth Mutual inductance at 5kHz, max: Attenuation dB/km: 300 Hz 1000Hz 2000Hz 3000Hz 4000Hz Characteristic impedance: 1000Hz 10 kHz Minimum bending radius approx. 0.8mm 73.6M.km 5 G.km 40nF/km 500pF/500m 15 kV 0.5 mH/100m

Induced voltage 5kv - 15kv: 0.51 0.91 1.25 1.50 1.68 550 200
15 x cable diameter

Cable core construction


Number of pairs 4 7 19 37 First layer 4 1 1 6 Number of pairs in centre and successive layers Second layer Third layer 6 6 12 Fourth layer

12 18

258

ELKABEL

PE insulation pairs stranded into layer jelly filling PE bedding armour sheath of PVC

CONTROL CABLE FOR INDUCED VOLTAGE UP TO 15KV

Colour coding
Pair no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 a - wire red black orange green orange green orange black red green red green red green red green red green blue black red green red green red green red green red green red green red green red green blue b - wire yellow violet grey brown blue brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown white violet yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown yellow brown white

Mechanical data PE/PJF/PE/SWA/PVC ...x2x1/0.8


Number of pairs Diameter of armour wire mm 1.25 1.25 1.60 2.00 External diameter approx. mm 19.2 21.6 31.1 40.4 Copper weight kg/km 38 66 179 345 Cable weight approx. kg/km 662 820 1652 2780

4 7 19 37

ELKABEL

259

PE/PE
LOOP FEEDER CABLES
PE insulation wires stranded in layers sheath of PE

BS 6346/87

Application
For electrical instalations

Description
Conductor Conductor size Insulation -radial thickness, nom Cable core Wrapping Outer sheath Sheath colour solid copper conductor to BS 6360 1.50mm2 =1/1.37mm 2.50mm2 =1/1.78mm PE type 03 complying to BS 6234 0.6mm 2 x N mm2 - pair 4 x N mm2 - quad minimum of 1 layer of plastic tape PE compound type 03 complying to BS 6234 orange

Technical data
Cross section in mm2: 1.5 2.5 12.1.km 7.41.km Cond.resistance at 20C max. Insulation resistance min. 5.km Mutual capacitance at 800Hz max. nF/km: Inductance H/km Test voltage 50Hz, 1 min. wire - wire Voltage rating: Temperature range mobile fixed Minimum bending radius approx. 5.km 2x1.5 4x1.5; 2x2.5 4x2.5 52-42-55-45 505- 685- 490- 670 3500V 600/1000 V -20C +50C +70C 6 x cable diameter

Color coding
2Y Type codes insulation or sheath of PE Number of wires 1 2 a-wire blue blue b-wire brawn brawn black grey c-wire d-wire

Mechanical data PE/PE


Number of wires External diameter approx. mm 2x1.5mm2 4x1.5mm2 2x2.5mm2 4x2.5mm2 8.1 9.1 9.1 10.5 Copper weight kg/km 27 54 43 88 Cable weight approx. kg/km 64 102 88 146

260

ELKABEL

PE/SWA/PE

BS 6346/87

LOOP FEEDER CABLES

PE insulation wires stranded in layers PE bedding armour sheath of PE

Application
These cables are preferentially used in outdoor applications, for indoor instalations, in the open air and underground where mechanical damage is anticipated.

Description
Conductor Conductor size Insulation material Cable core Wrapping Inner Sheath Armour Outer sheath Colour solid copper conductor to BS 6360 1.50mm2 =1/1.37mm 2.50mm2 =1/1.78mm BS 6234 2 x N mm - pair 4 x N mm2 - quad minimum of 1 layer of plastic tape PE type 03 complying to BS 6234, natural single layer of galvanized steel wires complying to BS1442 PE compound type 03 complying to BS 6234 orange
2

Technical data
Cross section in mm2 : 1.5 2.5 12.1.km 7.41.km Cond.resistance at 20C max. Insulation resistance -min. Mutual capacitance at 800Hz max. nF/km: Inductance H/km Test voltage 50Hz, 1 min. wire - wire wire - armour Voltage rating: Temperature range mobile fixed Minimum bending radius approx 5.km 2x1.5 4x1.5; 2x2.5 4x2.5 62-52-62-452 505- 685- 490- 670 3500V 3500V 600/1000 V -20C +50C +70C 7.5 x cable diameter

Color coding
Type codes 2Y insulation or sheath of PE SWA - armour Number of pair 1 2 a-wire blue blue b-wire brawn brawn black grey c-wire d-wire

Mechanical data PE/SWA/PE


Number of wires Diameter of armour wire mm 2x1.5mm 4x1.5mm2 2x2.5mm2 4x2.5mm2
2

External diameter approx. mm 11.4 12.5 12.5 14.0

Coppe rweight kg/km 27 54 43 88

Cable weight approx. kg/km 230 295 290 370

0.9 0.9 0.9 0.9

ELKABEL

261

CONDUCTORS

ELKABEL

CONDUCTORS

ELKABEL

H05V-U/-K
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Cu conductors PVC insulation

Uo/U - 300/500V VDE 0281-3 and BDS HD 21.3 S3

Applications
H05V-U/-K PVC-insulated wiring cable according to VDE 0281 part 3,HD 21.3 S3 and IEC 60227-3. These flexible PVC insulated wiring cables are used for the internal wiring of equipment as well as for protected installation in and to lighting fixtures, in tubes, in conduit, on and under plaster although only for bell circuits and signal systems.

Cable construction
Conductor Insulation: Color copper wires,according to VDE 0295 class 1 or 5 (IEC 60228) PVC, compound Type YI1 according to VDE 0207 part 4 black, red, blue, pink, gray, yellow, green, brown, white, violet, orange Two-color combinations are not permitted except for green/yellow.

Technical data
Conductor resistance at 20OC Core temperature, max: Rated voltage Uo/U Test voltage AC, 50 Hz:: Temperature: mobile: fixed: Bending radius up to 10mm diameter >10mm diameter Flame test: according to VDE 0295 and IEC 60228 70oC in operation 300/500 V 2000 V

- 5 oC to + 70oC - 30oC to + 70oC 10 x cable diameter 15 x cable diameter test class B according to VDE 0472 part 804 and IEC 60 332-1

Construction data H05V-U/-K 300/500V


Nominal cross section mm2 HO5V-U 0,50 0,75 1,00 HO5V-K 0,50 0,75 1,00 2,3 2,5 2,7 4,8 7,1 9,5 9,0 12,4 16,3 2,1 2,3 2,5 4,6 6,7 9,2 8,9 11,6 14,4 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

264

ELKABEL

Uo/U - 450/750 V VDE 0281-3 and BDS HD 21.3.S3

Cu conductors PVC insulation

H07V-U/-R/-K
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Applications
H07V-U/-R/-K PVC-insulated single-core cable according to VDE 0281 part 3,HD 21.3 S3 and IEC 227-3. These PVCinsulated single-core cables are used for the internal wiring of equipment switching systems and distributors as well as for the protected installation in and to lighting fixtures with a rated voltage up to 1000 V alternating current or a direct voltage up to 750 V, earthed.These cables are suitable for installation in dry rooms, switching and distribution systems, in conduit, on, in and under plaster as well as in closed installation ducts. Note (for H07V): These single-core cables may not be used for direct installation on flatbed bodies, ducts or tanks. Approved for use as potential-compensating cable directly on, in and underneath plaster as well as on flatbed bodies or similar.

Cable construction
Conductor Insulation: Color copper wires,according to VDE 0295 class 1, 2 or 5 (IEC 60228) PVC, compound Type YI1 according to VDE 0207 part 4 black, red, blue, pink, gray, yellow, green, brown, white, violet, orange Two-color combinations are not permitted except for green/yellow.

Technical data
Conductor resistance at 20oC Core temperature, max: Rated voltage Uo/U Test voltage AC, 50 Hz: Temperature range mobile: fixed: Bending radius up to 10 mm diameter >10 mm diameter Flame test: according to VDE 0295 and IEC 60228 70oC in operation 450/750 V 2500 V - 5oC to + 70oC - 30oC to + 70oC 10 x cable diameter 15 x cable diameter test class B according to VDE 0472part 804 and IEC 60 332-1

Construction data H07V-U/-R/-K 450/750V


Nominal cross section mm2 HO7V-U 1.5 2.5 4.0 6.0 10 HO7V-R 1.5 2.5 4.0 6.0 10 16 25 35 50 3,1 3,8 4,3 4,9 6,3 7,3 9,1 10,2 12,0 14,4 23 37 56 93 148 234 324 444 23 35 51 72 118 176 278 350 500 2,9 3,5 4,0 4,5 5,8 13,7 23 36 54 91 21 33 48 67 112 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

ELKABEL

265

H 0 7 V - U /-R /-K
CONDUCTORS FOR ELECTRIC INSTALLATIONS
Nominal cross section mm2 70 95 120 150 185 240 300 400 HO7V-K 1,5 2,5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 3,1 3,8 4,4 5,4 6,8 7,9 9,7 11,1 13,4 15,5 18,0 19,5 22,0 24,4 27,8 Approx. outer diameter mm 13,8 16,1 17,7 19,7 22,0 25,1 28,0 31,4

Cu conductors PVC insulation

Uo/U - 450/750 V VDE 0281-3 and BDS HD 21.3.S3

Construction data H07V-U/-R/-K 450/750V


Copper weight kg/m 650 876 1100 1380 1750 2252 2825 3540 14 24 38 57 96 149 232 328 474 669 881 1130 1404 1713 2263 Approx. cable weight kg/km 700 930 1150 1450 1870 2400 3100 3800 22 34 50 73 116 180 310 385 588 790 1000 1400 1600 2000 2500

266

ELKABEL

Uo/U - 230/400 V VDE 0250 part 201

Cu conductors PVC insulation PVC sheath

NYIFY
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Applications
For installation in dry environments only, both in and beneath plaster. The cables must be covered by plaster along their entire length. Installation in cavities of concrete, stone or non-inflammable building materials is allowed. Installations notes:
- The cables cannot be installed on flammable building materials, immediately next to or under wire mesh or similar materials. - For mounting, only materials and procedure shall be used which preclude a deformation or damage of the insulation, e. g. gypsum plaster, adhesives, nails with insulating washers. - Flat house wire cables may only be installed beneath gypsum board if these are subsequently fixed using gypsum plaster - The cables may not be bundled together. Bunching flat webbed building wires to insertion points for electrical equipments is not considered as bunching.

Cable construction
Construction Conductor According to VDE 0250 - 201

Technical data
Conductor resistance at 20oC Core temperature, max: Rated voltage Uo/U Test voltage AC, 50 Hz Temperature range Minimum bending radius Testing Flame test according to VDE 0295 Class1 and IEC 228 Class1 max 70oC in operation 230/400 V 2000 V - 20 C to + 70oC fixed installation 6 x cable diameter according to DIN VDE 0472 test class B according VDE 0472 part 804 and IEC 60 332-I
o

copper wires according to VDE 0295 class1 (IEC 60228) Insulation PVC ,compound type YI 1 according to VDE 0207 part 4 Cores flat in adjacent configuration with a common covering of PVC compound Sheath Color PVC ,compound type YM 1 according to VDE 0207 part 5 white, black, gray

Color coding
Number of core 2 core 3 core 4 core 5 core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green blue, brown brown, black , gray blue, brown, black, gray black, blue, brown, black, gray

Construction data NYIFY 230/400V


Number of wires and nominal cross section mm2 NYIFY - O 2x1,5 2x2,5 2x4.0 NYIFY - J 3x1,5 3x2,5 3x4.0 4x1,5 4x2,5 5x1,5 5x2,5 4 x 18 4,6 x 19,8 5,5 x 23,0 4 x 25 4,6 x 27,5 4 x 32 4,6 x 35 40 66 106 54 88 68 110 109 155 217 148 210 188 265 4 x 11 4,6 x 12,2 5,5 x 14 27 44 71 69 99 140 Outer dimensions approx. mm Copper weight kg/m Approx. cable weight kg/km

ELKABEL

267

H03VV-F; H03VVH2-F
CONDUCTORS FOR ELECTRIC APPLIANCES

Cu conductors PVC insulation PVC sheath

Uo/U - 300/300 V VDE 0281-5 and BDS HD 21.5.S3

Applications
H03VV-F PVC-insulated sheathed cable according to VDE 0281 part 5,HD 21.5 S3 and IEC 227-5. The cables are suitable for connection of light small duty appliances, i. e. desk-instructions of the lamps, fairy-lamps, house vacuum cleaners, radio sets etc. as far as this is allowed in the instructions of the electrical appliances. The cables with cross-section 0.5 and 0.75 mm2 are not suitable for use in industrial electrical equipment, in agriculture and in open spaces.

Cable construction
Conductor copper wires according to VDE 0295 Class 5 and IEC 60228 Class 5 PVC, compound Type TI2 , according to VDE 0207 part 4 PVC, compound type TM2 according to VDE 0207 part 5 black or white as standard color,

Technical data
Conductor resistance at 20 Core temperature max Rated voltage for for three-phase and alternating current systems for direct current systems Test voltage AC, 50 Hz: Temperature range mobile: fixed: Testing Flame test: according to VDE 0295 cl. 5 and IEC 60228 cl. 5 70C in operation Uo/U 300/300 V Uo/U 300/500 V 2000 V 2000 V -5 to +70 -40 to +70 according to VDE 0472 test class B ,VDE 0472part 804 and IEC 332-1

Insulation: Sheath Color:

Different colors available upon request.

Color coding
Number of core 2 core 3 core 4 core 5 core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green blue, brown brown, black, gray blue, brown, black , gray black , blue , brown , black , gray

Construction data H03VV-F/H03VVH2-F 300/300V


Number of wires and nominal cross section mm2 HO3VV-F 2x0,50 2x0,75 3x0,50 3x0,75 4x0,50 4x0,75 HO3VVH2-F 2x0,50 2x0,75 3,3x5,3 3,5x5,8 8,8 14,2 29 41 5,3 5,8 5,6 6,2 6,1 6,7 8,8 14,8 13,2 21,5 17,6 27,8 40 50 47 59 56 72 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

268

ELKABEL

Uo/U - 300/500 V VDE 0281-5 and BDS HD 21.5. S3

Cu conductors PVC insulation PVC sheath

H05VV-F; H05VVH2-F
CONDUCTORS FOR ELECTRIC APPLIANCES

Applications
H05VV-F PVC-insulated sheathed cable according to VDE 0281 part 5,HD 21.5 S3 and IEC 227-5. The cables are suitable for connection of medium duty appliances in houses, kitchens and offices, for house appliances in wet premises i.e. refrigerators, washing machines, centrifuges as far as this is allowed in the instructions of the electrical appliances. It is allowed they to be used for connection of electrical heating appliances providing the conductors are not in contact with the heated parts and they shall not be subject of other thermal effects. The cables can be installed in furniture, finished building elements and in decorative edgings. The cables are not suitable for use in open spaces, in agriculture and industry, for connection of industrial electrical appliances, but they are allowed for use in tailoring workshops.

Cable construction
Conductor copper wires according to VDE 0295 Class 5 and IEC 60228 Class 5 PVC, compound Type TI2 , according to VDE 0207 part 4 PVC, compound type TM2 according to VDE 0207 part 5 black or white as standard color

Technical data
Conductor resistance according to VDE 0295 cl. 5 and at 20 IEC 60228 cl. 5 Core temperature max 70C in operation Rated voltage for Uo/U Uo/U 300/500 V for three-phase and alternating current: 330/550 V for direct current systems: 495/825 V Test voltage AC, 50 Hz:H05VV-F 2000 V Temperature range mobile -5C to +70C fixed installation -40C to +70C Testing according to VDE 0472 test class B ,VDE 0472part 804 Flame test: and IEC 332-1

Insulation: Sheath Color:

Different colors available upon request.

Color coding
Number of core 2 core 3 core 4 core 5 core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green blue, brown brown, black, gray blue, brown, black , gray black , blue , brown , black , gray

Construction data H05VV-F/H05VVH2-F 300/500V


Number of wires Approx. and nominal outer diamecross section ter mm2 mm HO5VV-F 2x0,75 6,4 2x1,0 7.0 2x1,5 7,9 2x2,5 9,6 2x4,0 11,0 3x0,75 6,8 3x1,0 7,4 3x1,5 8,6 3x2,5 10,4 3x4,0 12,0 4x0,75 7,4 4x1,0 8,2 4x1,5 9,7 4x2,5 11,3 Copper weight kg/m 14,8 19,5 28,5 47,6 76,8 21,9 29,2 42,8 71,4 115,2 29,1 38,9 57,0 95,2 Approx. cable weight kg/km 65 78 102 155 214 77 92 126 192 270 94 113 160 231

Construction data H05VV-F/H05VVH2-F 300/500V


Number of wires Approx. and nominal outer diamecross section ter mm2 mm 4x4,0 13,0 5x0,75 8,3 5x1,0 9,0 5x1,5 10,8 5x2,5 12,6 5x4,0 14,6 HO5VVH2-F 2x0,75 4,1x6,5 Copper weight kg/m 153,6 36,4 48,7 71,2 119,0 192,0 14,2 Approx. cable weight kg/km 325 118 140 203 295 418 49

ELKABEL

269

H05RR-F
CONDUCTORS FOR ELECTRIC APPLIANCES

Cu conductors EPR insulation EPR sheath

Uo/U - 300/500 V BDS HD 22.4 S4 and VDE 0282-4

Applications
These cables are used for connecting electrical equipment such as kitchen appliance, cookers, soldering irons and vacuum cleaners, for low medium mechanical loads.

Cable construction
Construction Conductor Insulation According to VDE 0282 part 4 Cu wires ,flexible, class 5, acc. to VDE 0295 (IEC 60228)

Technical data
Max. operating temperature of the conductor Rated voltage Uo/U Test voltage AC, 50 Hz Ambient temperature during exploitation Bending radius, min. approx. Testing acc. to Flame test Resistance to oil +60 2000 V 0.75-1 mm2-1500V 1.5-4 mm2-2000V - 30 to +50 12 diameter cable VDE 0472 12xD cable Test class B according VDE 0472 part 804 Test class A according VDE 0472 part 805

Silane crosslinked rubber compound on base EPR rubber Core identification according to VDE 0293 Sheath Color Silane ceosslinked rubber compound Type EM-3 on base EPR rubber black

Resistance to ozone

Color coding
Number of core 2 3 4 5 Without yellow/green blue, brown brown, black, grey blue, brown,black, grey blue, brown,black, grey,,black With yellow/green yellow/green, blue, brown yellow/green, brown,black, grey yellow/green, blue, brown,black,grey

270

ELKABEL

Construction data H05RR-F 300/500 V


Number of wires and nominal cross section mm2 H05RR-F 2x0,75 2x1,0 2x1,5 2x2,5 3x0,75 3x1,0 3x1,5 3x2,5 3x4,0 3x6,0 4x0,75 4x1,0 4x1,5 4x2,5 4x4,0 4x6,0 5x0,75 5x1,0 5x1,5 5x2,5 5,7 6,1 7,6 9,0 6,2 6,5 8,0 9,6 11,3 12,8 6,8 7,1 9,0 10,7 12,7 14,2 7,6 8,0 9,8 11,9 7,4 8,0 9,8 11,6 8,1 8,5 10,4 12,4 14,5 16,3 8,8 9,3 11,6 13,8 16,2 18,1 9,9 10,3 12,7 15,3 15 20 29 48 22 30 43 72 117 176 30 40 58 97 156 234 37 50 72 121 47 56 85 125 60 75 110 160 230 330 80 100 140 210 280 420 100 120 160 240 Approx. outer diameter min (mm) max (mm) Copper weight kg/m Cable weight approx. kg/km

CONDUCTORS FOR ELECTRIC APPLIANCES

ELKABEL

271

H05VV5-F
OIL RESISTANT PVC SHEATED CONDUCTORS

Uo/U - 300/500 V VDE 0281-5 and BDS HD 21.13. S1

Application
Unscreened HAR and UL/CSA approved numbered control cable for use as connection cable for control devices of machine tools, assembly lines, conveyor belts and installations, in power stations, plant construction and for production lines. It can be used with medium mechanical stress for fixed laying and flexible application, with unrestricted movement, without tensile stress or forced movement control, in dry, damp and wet rooms. The identification of cores by successive numbers avoids mistakes when installing .

Cable construction
Conductor Insulation: bare copper flexible Class 5according to IEC 228 PVC, compound Type TI2 , according to VDE 0207 part 4

Technical data
Conductor resistance at 20 Core temperature max Insulation resistance, min Rated voltage for Test voltage AC, 50 Hz : Temperature range mobile: fixed: Testing according to HD 383, IEC 228 70C in operation 150 C in the event of a short circuit 20 M.km Uo/U 300/500 V 2000V - 5 oC to + 70oC - 40oC to + 70oC according to VDE 0472 test class B ,VDE 0472part 804 and IEC 60 332-1

Core Identification: -2 conductors: black numbered. -3 or more conductors: black numbered + green/yellow Sheath PVC compound type TM5 according to VDE 0207 part 5 - oil resistant gray , RAL 7001

Color:

Flame test: Different colors available upon request.

Construction data H05VV5-F Uo/U - 300/500 V


Number of wires and nominal cross section mm2 20.5 3G0.5 4G0.5 5G0.5 6G0.5 7G0.5 8G0.5 10G0.5 12G0.5 14G0.5 16G0.5 18G0.5 20G0.5 21G0.5 25G0.5 30G0.5 34G0.5 40G0.5 50G0.5 Outer diameter approx. mm2 5.7 6.1 6.8 7.4 8.3 8.3 9.3 10.8 11.2 12.1 12.7 13.4 14.2 14.4 15.7 17.1 18.2 19.7 22.0 Copper weight kg/m 9 13 18 22 27 31 35 44 53 62 71 80 88 93 110 133 150 177 221 Cable weight approx. kg/km 45 58 76 90 110 121 143 180 206 241 269 297 332 346 410 488 554 647 808

272

ELKABEL

Cu conductors PVC insulation PVC sheath, oil resistant

OIL RESISTANT PVC SHEATED CONDUCTORS

Construction data H05VV5-F Uo/U - 300/500 V


Number of wires and nominal cross section mm2 61G0.5 20.75 3G0.75 4G0.75 5G0.75 6G0.75 7G0.75 8G0.75 10G0.75 12G0.75 14G0.75 16G0.75 18G0.75 20G0.75 21G0.75 25G0.75 34G0.75 41G0.75 42G0.75 50G0.75 61G0.75 21 3G1 4G1 5G1 6G1 7G1 8G1 10G1 12G1 14G1 16G1 18G1 20G1 21G1 25G1 34G1 411 501 611 21.5 3G1.5 4G1.5 5G1.5 6G1.5 7G1.5 8G1.5 10G1.5 12G1.5 14G1.5 16G1.5 18G1.5 20G1.5 21G1.5 25G1.5 48G2.5 22.5 3G2.5 4G2.5 5G2.5 6G2.5 7G2.5 8G2.5 10G2.5 122.5 142.5 162.5 182.5 202.5 212.5 252.5 482.5 Outer diameter approx. mm 24.1 6.4 6.7 7.3 8.2 8.9 9.1 10.1 11.9 12.2 13.0 13.9 14.6 15.5 15.8 17.2 19.9 21.9 22.1 24.0 26.5 6.7 7.1 7.7 8.7 9.6 9.6 10.8 12.5 12.9 14.0 15.0 15.5 16.6 16.9 18.4 21.3 23.4 25.7 28.3 8.2 8.7 9.6 10.7 11.8 12.0 13.2 14.8 15.3 16.5 17.6 18.5 19.5 19.9 22.6 29.7 9.3 9.8 11.0 12.2 13.5 13.7 15.1 17.2 18.0 19.3 20.6 21.7 22.9 23.5 25.9 34.3 Copper weight kg/m 269 14 22 29 36 43 50 58 72 87 101 115 130 144 151 180 245 296 303 360 440 19 29 38 48 58 67 77 96 115 135 154 173 192 202 241 327 394 481 587 25 37 49 62 74 86 99 123 148 173 197 222 247 259 308 592 41 62 82 103 123 144 165 206 247 288 329 370 411 432 514 1001 Cable weight approx. kg/km 971 59 77 96 120 140 161 183 238 272 310 356 393 440 458 542 731 886 904 1066 1299 66 87 110 137 166 185 216 272 313 365 418 453 516 538 636 857 1036 1247 1517 90 105 129 155 182 194 224 293 332 382 432 478 526 554 667 1214 126 150 185 222 261 281 324 429 491 566 640 709 781 826 973 1807

ELKABEL

273

H05VVC4V5-K
OIL RESISTANT PVC SHEATED CONDUCTORS

Uo/U - 300/500 V VDE 0281-13, BDS HD 21.13. S1

Application
These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air. These are designed as control and connecting cables to machines, tool machineries, conveyor belts and production lines. These cables have been tested according to DIN VDE 0207 and 0473 and found to be totally oil resistant These cables are not effected to the chemical influences. Cables for moist and wet rooms, specially used for machines in breweries, bottling plants and car washing stations. Note: These cables may be allowed to move once installed provided that the cables are not mechanically stressed during movement. The interconnection of parts of machines used for manufacturing purposes including machine tools where some degree of protection against electromagnetic interference is required.

Cable construction
Conductor Insulation: bare copper flexible Class 5according to IEC 228 PVC, compound Type TI2 , according to VDE 0281 part 1

Technical data
Conductor resistance at 20 Core temperature max Insulation resistance, min Rated voltage for Test voltage AC, 50 Hz: core/core core/screen Temperature range mobile: fixed: Radiation resistance Testing Flame test: -5C to +70C -40C to +70C up to 80 Mrad VDE 0281-13: test class B ,VDE 0472part 804 and IEC 60 332-1 according to HD 383, IEC 228 70C in operation. 150C in the event of a short circuit 20 M.km Uo/U 300/500 V

Core Identification: -2 conductors: black numbered. -3 or more conductors: black numbered + green/yellow Type of lay-up Inner sheath Screen Sheath cores laid up in layers of optimum pitch TM2 to DIN VDE 0281 parti1 Tinned copper braided screening, covering approx. 85% PVC, compound type TM5 according to VDE 0207 part 5, oil resistant. gray , RAL 7001

2000V, 5min 2000V, 5min

Color:

Different colors available upon request.

Construction data H05VVC4V5-K Uo/U - 300/500 V


Number of wires and nominal cross section mm2 2x0,5 3G0.5 4G0.5 5G0.5 6G0.5 7G0.5 8G0.5 9G0.5 12G0.5 Outer diameter approx. mm 8,0 8,4 9,1 10,1 10,7 11,4 12,5 12,5 13,5 Copper weight kg/m 30 36 42 48 58 64 72 80 105 Cable weight approx. kg/km 92 109 126 156 176 192 211 230 280

274

ELKABEL

Cu conductors PVC insulation PVC sheath Cu screen PVC sheath, oil resistant

OIL RESISTANT PVC SHEATED CONDUCTORS

Construction data H05VVC4V5-K Uo/U - 300/500 V


Number of wires and nominal cross section mm2 14G0.5 18G0.5 25G0.5 27G0.5 34G0.5 36G0.5 41 G 0,5 50G0.5 61 G 0,5 65G0.5 2x0,75 3G0.75 4G0.75 5G0.75 6G0.75 7G0.75 8G0.75 9G0.75 12G0.75 14G0.75 18G0.75 2x1,5 3G1.5 4G1.5 5G1.5 6G1.5 7G1.5 8G1.5 9G1.5 12G1.5 14G1.5 18G1.5 19G1.5 25G1.5 27G1.5 32G1.5 34G1.5 36G1.5 37G1.5 41G1.5 2x2,5 3G2.5 4G2.5 5G2.5 7G2.5 8G2.5 12G2.5 14G2.5 18G2.5 25G2.5 27G2.5 Outer diameter approx. mm 14,2 15,8 18,6 18,6 20,8 20,8 23,0 25,0 26,8 28,4 8,3 8,8 9,8 10,8 11,4 12,1 12,7 13,8 14,3 14,4 16,9 9,1 10,2 10,9 11,6 12,4 13,5 15,6 15,6 16,8 18,3 20,0 20,4 24,2 24,6 26,0 26,3 27,7 27,7 29,1 11,4 11,7 12,8 13,9 15,9 18,7 20,6 22,5 24,3 29,0 29,8 Copper weight kg/m 114 137 210 236 298 317 349 470 530 563 41 48 55 66 75 85 98 112 135 151 190 69 75 90 108 130 157 173 185 240 283 355 366 448 516 702 754 778 790 805 81 104 134 175 225 289 375 415 522 897 971 Cable weight approx. kg/km 302 384 556 599 634 620 770 970 1072 1198 102 115 150 173 195 235 268 285 327 362 488 146 176 207 235 279 314 345 380 500 560 707 723 950 1014 1133 1204 1261 1300 1453 190 243 280 342 439 489 760 890 1052 1375 1507

ELKABEL

275

OPVC-JZ-CY
OIL RESISTANT PVC SHEATED CONDUCTORS

Uo/U - 300/500 V VDE 0281-13

Application
These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air. These are designed as control and connecting cables to machines, tool machineries, conveyor belts and production lines. These cables have been tested according to DIN VDE 0207 and 0473 and found to be totally oil resistant These cables are not effected to the chemical influences. Cables for moist and wet rooms, specially used for machines in breweries, bottling plants and car washing stations. Note: These cables may be allowed to move once installed provided that the cables are not mechanically stressed during movement. The interconnection of parts of machines used for manufacturing purposes including machine tools where some degree of protection against electromagnetic interference is required.

Cable construction
Conductor Insulation: bare copper flexible Class 5according to IEC 228 PVC, compound Type TI2 , according to VDE 0281 part 1

Technical data
Conductor resistance at 20 Core temperature max Insulation resistance, min Rated voltage for Test voltage AC, 50 Hz: core/core core/screen Temperature range mobile: fixed: Radiation resistance Testing Flame test: -5C to +70C -40C to +70C up to 80 Mrad according to VDE 0472 test class B ,VDE 0472part 804 and IEC 60 332-1 according to HD 383, IEC 228 70C in operation. 150C in the event of a short circuit 20 M.km Uo/U 300/500 V

Core Identification: -2 conductors: black numbered. -3 or more conductors: black numbered + green/yellow Type of lay-up Inner sheath Screen Sheath cores laid up in layers of optimum pitch TM2 to DIN VDE 0281 parti1 Tinned copper braided screening, covering approx. 85% PVC, compound type TM5 according to VDE 0207 part 5, oil resistant grey , RAL 7001 or transparent

2000V, 5min 2000V, 5min

Color:

Different colors available upon request.

Construction data OPVC-JZ-CY Uo/U - 300/500 V


Number of wires and nominal cross section mm2 2x0,5 3G0.5 4G0.5 5G0.5 6G0.5 7G0.5 8G0.5 9G0.5 12G0.5 14G0.5 Outer diameter approx. mm 8,0 8,4 9,1 10,1 10,7 11,4 12,5 12,5 13,5 14,2 Copper weight kg/m 30 36 42 48 58 64 72 80 105 114 Cable weight approx. kg/km 92 109 126 156 176 192 211 230 280 302

276

ELKABEL

Cu conductors PVC insulation PVC sheath Cu screen PVC sheath, oil resistant

OIL RESISTANT PVC SHEATED CONDUCTORS

Construction data OPVC-JZ-CY Uo/U - 300/500 V


Number of wires and nominal cross section mm2 18G0.5 25G0.5 27G0.5 34G0.5 36G0.5 41 G 0,5 50G0.5 61 G 0,5 65G0.5 2x0,75 3G0.75 4G0.75 5G0.75 6G0.75 7G0.75 8G0.75 9G0.75 12G0.75 14G0.75 18G0.75 2x1,5 3G1.5 4G1.5 5G1.5 6G1.5 7G1.5 8G1.5 9G1.5 12G1.5 14G1.5 18G1.5 19G1.5 25G1.5 27G1.5 32G1.5 34G1.5 36G1.5 37G1.5 41G1.5 2x2,5 3G2.5 4G2.5 5G2.5 7G2.5 8G2.5 12G2.5 14G2.5 18G2.5 25G2.5 27G2.5 Outer diameter approx. mm 15,8 18,6 18,6 20,8 20,8 23,0 25,0 26,8 28,4 8,3 8,8 9,8 10,8 11,4 12,1 12,7 13,8 14,3 14,4 16,9 9,1 10,2 10,9 11,6 12,4 13,5 15,6 15,6 16,8 18,3 20,0 20,4 24,2 24,6 26,0 26,3 27,7 27,7 29,1 11,4 11,7 12,8 13,9 15,9 18,7 20,6 22,5 24,3 29,0 29,8 Copper weight kg/m 137 210 236 298 317 349 470 530 563 41 48 55 66 75 85 98 112 135 151 190 69 75 90 108 130 157 173 185 240 283 355 366 448 516 702 754 778 790 805 81 104 134 175 225 289 375 415 522 897 971 Cable weight approx. kg/km 384 556 599 634 620 770 970 1072 1198 102 115 150 173 195 235 268 285 327 362 488 146 176 207 235 279 314 345 380 500 560 707 723 950 1014 1133 1204 1261 1300 1453 190 243 280 342 439 489 760 890 1052 1375 1507

ELKABEL

277

OPVC - JZ
OIL RESISTANT PVC SHEATED CONDUCTORS

Uo/U - 300/500 V VDE 0281-13

Application
Unscreened HAR and UL/CSA approved numbered control cable for use as connection cable for control devices of machine tools, assembly lines, conveyor belts and installations, in power stations, plant construction and for production lines. It can be used with medium mechanical stress for fixed laying and flexible application, with unrestricted movement, without tensile stress or forced movement control, in dry, damp and wet rooms. The identification of cores by successive numbers avoids mistakes when installing .

Cable construction
Conductor Insulation: bare copper flexible Class 5 according to IEC 228 PVC, compound Type TI2 , according to VDE 0207 part 4

Technical data
Conductor resistance at 20 Core temperature max Insulation resistance, min Rated voltage for Test voltage AC, 50 Hz: Thickness of Insulation up 0.6mm Thickness of Insulation over 0.6mm Temperature range mobile: fixed: Radiation resistance Testing Flame test: according to HD 383, IEC 228 70C in operation. 150C in the event of a short circuit 20 M.km Uo/U 300/500 V 1500V 2000V -5C to +70C -40C to +70C up to 80 Mrad according to VDE 0472 test class B ,VDE 0472part 804 and IEC 60 332-1

Core Identification: -2 conductors: black numbered. -3 or more conductors: black numbered + green/yellow Sheath PVC, compound type TM5 according to VDE 0207 part 5, oil resistant grey , RAL 7001

Color:

Different colors available upon request.

Construction data OPVC - JZ Uo/U - 300/500 V


Number of wires and nominal cross section mm2 20.5 3G0.5 4G0.5 5G0.5 6G0.5 7G0.5 8G0.5 10G0.5 12G0.5 14G0.5 16G0.5 18G0.5 20G0.5 21G0.5 25G0.5 30G0.5 34G0.5 40G0.5 50G0.5 Outer diameter approx. mm 5.7 6.1 6.8 7.4 8.3 8.3 9.3 10.8 11.2 12.1 12.7 13.4 14.2 14.4 15.7 17.1 18.2 19.7 22.0 Copper weight kg/m 9 13 18 22 27 31 35 44 53 62 71 80 88 93 110 133 150 177 221 Cable weight approx. kg/km 45 58 76 90 110 121 143 180 206 241 269 297 332 346 410 488 554 647 808

278

ELKABEL

Cu conductors PVC insulation PVC sheath, oil resistant

OIL RESISTANT PVC SHEATED CONDUCTORS

Construction data OPVC - JZ Uo/U - 300/500 V


Number of wires and nominal cross section mm2 61G0.5 20.75 3G0.75 4G0.75 5G0.75 6G0.75 7G0.75 8G0.75 10G0.75 12G0.75 14G0.75 16G0.75 18G0.75 20G0.75 21G0.75 25G0.75 34G0.75 41G0.75 42G0.75 50G0.75 61G0.75 21 3G1 4G1 5G1 6G1 7G1 8G1 10G1 12G1 14G1 16G1 18G1 20G1 21G1 25G1 34G1 411 501 611 21.5 3G1.5 4G1.5 5G1.5 6G1.5 7G1.5 8G1.5 10G1.5 12G1.5 14G1.5 16G1.5 18G1.5 20G1.5 21G1.5 25G1.5 48G2.5 22.5 3G2.5 4G2.5 5G2.5 6G2.5 7G2.5 8G2.5 10G2.5 122.5 142.5 162.5 182.5 202.5 212.5 252.5 482.5 Outer diameter approx. mm 24.1 6.4 6.7 7.3 8.2 8.9 9.1 10.1 11.9 12.2 13.0 13.9 14.6 15.5 15.8 17.2 19.9 21.9 22.1 24.0 26.5 6.7 7.1 7.7 8.7 9.6 9.6 10.8 12.5 12.9 14.0 15.0 15.5 16.6 16.9 18.4 21.3 23.4 25.7 28.3 8.2 8.7 9.6 10.7 11.8 12.0 13.2 14.8 15.3 16.5 17.6 18.5 19.5 19.9 22.6 29.7 9.3 9.8 11.0 12.2 13.5 13.7 15.1 17.2 18.0 19.3 20.6 21.7 22.9 23.5 25.9 34.3 Copper weight kg/m 269 14 22 29 36 43 50 58 72 87 101 115 130 144 151 180 245 296 303 360 440 19 29 38 48 58 67 77 96 115 135 154 173 192 202 241 327 394 481 587 25 37 49 62 74 86 99 123 148 173 197 222 247 259 308 592 41 62 82 103 123 144 165 206 247 288 329 370 411 432 514 1001 Cable weight approx. kg/km 971 59 77 96 120 140 161 183 238 272 310 356 393 440 458 542 731 886 904 1066 1299 66 87 110 137 166 185 216 272 313 365 418 453 516 538 636 857 1036 1247 1517 90 105 129 155 182 194 224 293 332 382 432 478 526 554 667 1214 126 150 185 222 261 281 324 429 491 566 640 709 781 826 973 1807

ELKABEL

279

H07Z-U/R/K
CONDUCTORS FOR ELECTRIC INSTALLATIONS WITH LOW EMISSION OF SMOKE AND CORROSIVE GASES WHEN AFFECTED BY FARE

Cu conductors insulation LSOH

Uo/U - 300/500 V BS 7211

Application
Suitable for use in conduit and for fixed, protected installation. In particular for installation where fire, smoke emission and toxic fumes create a potential threat.

Cable construction
Conductor Insulation: Color copper wires,according to BS 6360 ;class 1,2 or 5 Type EI 5 , low smoke, zero halogen, termosetting insulation black, red, blue, pink, gray, yellow, green, brown, white, violet, orange Two-color combinations are not permitted except for green/yellow.

Technical data
Conductor resistance at 20 Core temperature max Insulation resistance Rated voltage Uo/U Test voltage AC, 50 Hz: Temperature range mobile: fixed: Bending radius up to 10mm diameter >10 mm diameter Flame propagation: Smoke emission according to BS 6360 90C in operation. according to BS 7211 450/750 V 2500 V -5C to +70C -40C to +70C 10 x cable diameter 15 x cable diameter test according to BS 4066-1 test according BS 7622-2

Construction data H07Z-U/R/K 450/750V


Number of wires and nominal cross section mm2 HO7Z-U 1.5 2.5 4.0 6.0 10 HO7Z-R 1.5 2.5 4.0 6.0 10 16 25 35 50 70 985 120 150 185 Outer diameter approx. mm 2.8 3.0 3.8 4.3 5.5 3.0 3.6 4.1 4.7 5.7 6.7 8.3 9.4 10.9 12.5 14.6 16.0 17.8 19.9 Copper weight kg/m 14 22 36 54 90 13 22 35 52 87 139 221 306 416 601 835 1056 1302 1629 Cable weight approx. kg/km 20 29 45 64 107 21 33 48 68 112 165 259 349 474 666 922 1148 1418 1773

Construction data H07Z-U/R/K 450/750V


Number of wires and nominal cross section mm2 240 300 400 500 600 HO7Z-K 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 Outer diameter approx. mm 22.7 25.3 28.5 32.1 38.1 3.0 3.6 4.1 5.0 6.6 7.6 9.5 11.4 12.8 14.9 17.4 19.6 21.1 22.5 27.4 Copper weight kg/m 2145 2694 3448 4428 5782 13 22 35 52 95 147 224 331 446 636 842 1075 1354 1639 2148 Cable weight approx. kg/km 2323 2909 3709 4742 6135 20 31 45 67 118 173 265 377 509 706 921 1160 1451 1739 2287

280

ELKABEL

BARE STRANDED CONDUCTORS

ELKABEL

BARE STRANDED CONDUCTORS

Multiwire copper and aluminium conductors class 2

IEC 60228; DIN VDE 0295; BS 6360

MULTIWIRE CONDUCTORS

Application
Multi- wire copper and aluminium conductors for cables and conductors.

Construction data Cu/Al conductors class 2


Nominal cross-section mm2 0,50 0,75 1,00 1,50 2,50 4,0 6,0 10,0 16,0 25 35 50 70 95 120 150 185 240 300 400 500 Stranding and wire diameter N mm 7x0,31 7x0,37 7x0,44 7x0,53 7x0,67 7x0,85 7x1,03 7x1,35 7x1,70 7x2,14 7x2,50 19x1,78 19x2,14 19x2,50 37x2,03 37x2,25 37x2,50 61x2,25 61x2,50 61x2,85 61x3,20 Electrical resistance at 20, max Copper conductors (/km) Aluminium conductors (/km) 36,0 24,5 18,1 12,1 7,41 4,61 3,08 1,83 1,15 0,727 0,524 0,387 0,268 0,193 0,153 0,124 0,0991 0,0754 0,0601 0,0470 0,0366 7,41 4,61 3,08 1,91 1,20 0,868 0,641 0,443 0,320 0,253 0,206 0,164 0,125 0,100 0,0778 0,0605

282

ELKABEL

BDS 904-84

Multiwire copper conductors class 4

MULTIWIRE CONDUCTORS

Application
Flexible copper wires for cables and conductors.

Construction data Cu conductors class 4


Nominal cross-section mm2 0,12 0,14 0,20 0,25 0,35 0,50 0,75 1,00 1,50 2,50 4,00 6,00 10,0 16,0 25,0 35,0 50,0 70,0 95,0 120 150 185 240 300 400 500 Stranding and wire diameter N mm 7x0,15 8x0,15 7x0,20 8x0,20 7x0,25 7x0,30 11x0,30 14x0,30 12x0,40 20x0,40 20x0,50 30x0,50 7x7x0,50 7x8x0,60 7x12x0,60 7x14x0,67 12x12x0,67 12x16x0,67 19x14x0,67 19x18x0,67 19x14x0,85 30x11x0,85 37x11x0,85 37x14x0,85 61x11x0,85 61x14x0,85 Electrical resistance at 20, max Copper conductors (/km) Tinned copper conductors (/km) 158,35 138,52 89,30 77,95 57,01 39,60 25,20 19,80 12,70 7,64 4,89 3,26 2,00 1,21 0,809 0,550 0,375 0,281 0,203 0,158 0,126 0,103 0,0798 0,0647 0,0499 0,0392 162,93 142,52 91,65 80,19 58,65 40,70 25,90 20,40 13,00 7,79 4,99 3,32 2,04 1,24 0,824 0,561 0,382 0,286 0,207 0,161 0,128 0,104 0,0814 0,0660 0,0509 0,0400

ELKABEL

283

Multiwire copper conductors class 5

IEC 60228; DIN VDE 0295; BS 6360

MULTIWIRE CONDUCTORS

Application
Flexible copper wires for cables and conductors.

Construction data Cu conductors class 5


Nominal cross-section mm2 0,50 0,75 1,00 1,50 2,50 4,00 6,0 10,0 16,0 25,0 35,0 50,0 70,0 95,0 120 150 185 240 300 400 500 Stranding and wire diameter N mm 16x0,20 24x0,20 32x0,20 30x0,25 50x0,25 56x0,30 84x0,30 7x12x0,38 (80x0,40) 7x18x0,40 7x28x0,40 12x23x0,40 19x21x0,40 19x19x0,50 19x25x0,50 19x32x0,50 36x21x0,50 37x25x0,50 37x33x0,50 61x25x0,50 61x33x0,50 61x29x0,60 Electrical resistance at 20, max Copper conductors (/km) Tinned copper conductors (/km) 39,0 26,0 19,5 13,3 7,98 4,95 3,30 1,91 1,21 0,780 0,554 0,386 0,272 0,206 0,161 0,129 0,106 0,0801 0,0641 0,0484 0,0384 40,1 26,7 20,0 13,7 8,21 5,09 3,39 1,95 1,24 0,795 0,565 0,393 0,277 0,210 0,164 0,132 0,108 0,0817 0,0654 0,0495 0,0391

284

ELKABEL

IEC 60228; DIN VDE 0295; BS 6360

Multiwire copper conductors class 6

MULTIWIRE CONDUCTORS

Application
Flexible copper wires for cables and conductors.

Construction data Cu conductors class 6


Nominal cross-section mm2 0,50 0,75 1,00 1,50 2,50 4,00 6,00 10,0 16,0 25,0 35,0 50,0 70,0 95,0 120 150 Stranding and wire diameter N mm 28x0,15 42x0,15 56x0,15 7x12x0,15 (84x0,15) 7x20x0,15 7x32x0,15 7x26x0,20 7x44x0,20 19x26x0,20 19x40x0,20 27x40x0,20 19x36x0,30 27x36x0,30 37x34x0,30 37x44x0,30 37x56x0,30 Electrical resistance at 20, max Copper conductors (/km) Tinned copper conductors (/km) 39,0 26,0 19,5 13,3 7,98 4,95 3,30 1,91 1,21 0,780 0,554 0,386 0,272 0,206 0,161 0,129 40,1 26,7 20,0 13,7 8,21 5,09 3,39 1,95 1,24 0,795 0,565 0,393 0,277 0,210 0,164 0,132

ELKABEL

285

Bare copper conductors

DIN 48201 part 1

BARE COPPER CONDUCTORS FOR OVERHEAD LINES

Application
For overhead electric power transmission systems.

Construction data Cu conductors


Nominal cross-section mm2 10 16 25 35 50 70 95 120 150 185 240 300 400 500 Stranding and wire diameter N mm 7x1,35 7x1,70 7x2,10 7x2,50 19x1,80 19x2,10 19x2,50 19x2,80 37x2,25 37x2,50 61x2,25 61x/2,50 61x2,89 61x3,23 Breaking load min kN 4,02 6,35 9,72 13,77 19,38 26,38 37,39 46,90 58,98 72,81 97,23 120,04 160,42 200,38 Net weight of copper Electrical resistance aprox. at 20C, max kg/km 90 143 218 310 437 596 845 1060 1337 1649 2209 2725 3640 4545 (/km) 1,806 1,139 0,746 0,527 0,376 0,276 0,195 0,155 0,124 0,100 0,075 0,061 0,042 0,036

286

ELKABEL

BS 7884

Bare copper conductors

BARE COPPER CONDUCTORS FOR OVERHEAD LINES

Application
For overhead electric power transmission systems.

Construction data conductors


Nominal cross-section mm2 10 14 16 16 25 32 32 35 50 50 70 70 95 100 120 125 150 150 185 185 Stranding and wire diameter N mm 7x1,35 7x1,60 3x/2,65 7x1,70 7x2,10 3x/3,75 7x2,46 7x2,50 7x3,00 19x1,80 7x3,55 19x2,10 19x2,50 7x4,30 19x2,80 19x2,90 19x3,20 37x2,25 19x3,55 37x2,50 Breaking load min kN 3,752 5,267 6,194 5,946 9,073 12,40 12,442 12,860 18,520 17,700 25,930 24,090 34,140 36,540 42,830 45,940 55,940 53,880 68,860 66,490 Net weight of copper Electrical resistance aprox. at 20C, max kg/km 89,82 126,2 148,3 142,4 217,3 296,9 298,2 308,0 443,5 435,8 621,1 593,2 840,7 911,2 1055 1131 1377 1334 1695 1647 (/km) 1,788 1,273 1,082 1,128 0,7391 0,5405 0,5386 0,5215 0,3622 0,3727 0,2586 0,2738 0,1932 0,1763 0,1540 0,1436 0,118 0,1233 0,09582 0,09981

ELKABEL

287

BDS 1133 - 89 Bare aluminium conductors and aluminum conductors, steel reinforced

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Application
For overhead power transmission.

Construction data
Nominal crosssection mm2 16 25 35 50 70 95 120 150 185 240 300 400 500 600 Stranding and wire diameter N mm 7x1,70 7x2,12 7x2,50 7x3,00 7x3,55 7x4,12 19x2,80 19x3,15 19x3,50 19x4,00 37x3,20 37x3,69 37x4,15 61x3,55 Conductor diameter mm Type "A" 5,10 6,36 7,50 9,00 10,65 12,36 14,00 15,75 17,50 20,00 22,40 25,83 29,05 31,95 2,838 4,249 5,778 7,944 10,663 14,185 18,783 23,351 28,480 36,292 46,927 60,895 76,073 88,031 1,804 1,160 0,834 0,579 0,414 0,307 0,246 0,195 0,158 0,121 0,097 0,073 0,058 0,048 44 68 94 136 190 256 322 407 503 657 820 1091 1380 1668 Breaking load, Electrical oresist- Weight of conducmin ance at 20 C, max tor, approx. kN /km kg/km

Construction data
Nominal Stranding and cross-section wire diameter mm2 N mm Al St 6x1,80+1x1,80 6x2,20+1x2,20 6x2,80+1x2,80 6x3,20+1x3,20 6x3,80+1x3,80 6x4,50+1x4,50 28x2,29+7x2,00 28x2,59+7x2,20 28x2,87+7x2,50 28x3,29+7x2,80 28x3,66+7x3,20 28x4,24+19x2,20 Al St 24x2,8+7x1,80 24x3,1+7x2,00 24x3,59+7x2,40 54x2,62+7x2,60 54x3,04+7x3,00 54x3,37+19x2,00 Conductor diameter mm Breaking load, min kN Type "AC" 16 25 35 50 70 95 120 150 185 240 300 400 150 185 240 300 400 500 5,40 6,60 8,40 9,60 11,40 13,50 15,16 16,96 18,98 21,55 24,24 27,95 16,60 18,40 21,56 23,52 27,24 30,22 5,83 1,882 8,652 1,260 13,38 0,778 17,02 0,595 23,59 0,422 32,98 0,301 46,58 0,251 57,19 0,196 70,47 0,160 89,038 0,121 110,77 0,098 149,20 0,073 Type "ACO" 46.17 56.24 77.04 93.48 120.48 150.02 0,195 0,159 0,119 0,099 0,074 0,060 42 62 101 132 187 263 319 407 500 657 814 1092 408 500 670 805 1083 1332 20 30 48 53 88 124 172 209 269 338 441 568 139 172 248 291 388 469 62 92 149 63 275 387 511 616 769 995 1255 1660 547 672 918 1096 1471 1801 Electrical resistance at 20oC, max /km Weight Al Weight St Weight of conductor, approx. kg/km

kg/km

kg/km

288

ELKABEL

VDE 48201 Part 5

Bare aluminium stranded conductors

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Application
For overhead electric power transmission systems.

Construction data
Nominal crosssection mm2 16 25 35 50 50 70 95 120 150 185 240 300 400 500 Stranding and wire diameter N mm 7x1,70 7x2,10 7x2,50 7x3,00 19x1,80 19x2,10 19x2,50 19x2,80 37x2,25 37x2,50 61x2,25 61x/2,50 61x/2,89 61x3,23 Conductor diameter mm Al conductors 5,1 6,3 7,50 9,0 9,0 10,5 12,5 14,0 15,8 17,5 20,3 22,5 26,0 29,1 Breaking load, Electrical oresist- Weight of conducmin ance at 20 C, max tor, approx. kN 2,84 4,17 5,78 7,94 8,45 11,32 15,68 18,78 25,30 30,54 39,51 47,70 60,86 74,67 /km 1,802 1,181 0,833 0,579 0,635 0,437 0,309 0,246 0,196 0,1587 0,1194 0,0965 0,0722 0,0578 kg/km 43 66 94 135 133 181 256 322 406 500 670 827 1104 1379

ELKABEL

289

Bare aluminium conductors, steel reinforced

DIN 48 204

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Application
For overhead electric power transmission systems.

Construction data
Nominal Stranding and cross-section wire diameter mm2 N mm Al St 6x1,80+1x1,80 6x2,25+1x2,25 6x2,70+1x2,70 14x2,00+7x2,40 6x3,20+1x3,20 12x2,33+7x2,33 26x1,85+7x1,44 26x2,15+7x1,67 12x3,20+7x3,20 14x3,10+19x2,25 26x2,44+7x1,90 12x3,60+7x3,60 30x2,33+7x2,33 26x2,70+7x2,10 30x2,70+7x2,70 26x3,00+7x2,33 26x3,20+7x2,49 30x3,00+7x3,00 24x3,50+7x2,33 26x3,45+7x2,68 24x3,74+7x2,49 26x3,86+7x3,00 54x2,68+7x2,68 48x3,00+7x2,33 54x3,00+7x3,00 48x3,20+7x2,49 54x3,20+7x3,20 48x3,45+7x2,68 54x3,40+7x3,40 45x3,74+7x2,49 48x3,68+7x2,87 54x3,60+7x3,60 48x3,86+7x3,00 45x4,02+7x2,68 Conductor diameter mm Breaking load, min kN Electrical resistance at 20oC, max /km Weight Al Weight St Weight of conductor, approx. kg/km

kg/km

kg/km

Al/St reinforced conductors 16/2,5 25/4 35/6 44/32 50/8 50/30 70/12 95/15 95/55 105/75 120/20 120/70 125/30 150/25 170/40 185/30 210/35 210/50 230/30 240/40 265/35 300/50 305/40 340/30 380/50 385/35 435/55 450/40 490/65 495/35 510/45 550/70 560/50 570/40 5,4 6,8 8,1 11,2 9,6 11,7 11,7 13,6 16,0 17,5 15,5 18,0 16,3 17,1 18,9 19,0 20,3 21,0 21,0 21,8 22,4 24,5 24,1 25,0 27,0 26,7 28,8 28,7 30,6 29,9 30,7 32,4 32,2 32,2 5,81 9,02 12,70 45,46 17,18 44,28 26,31 35,17 80,20 106,69 44,94 98,16 57,86 54,37 77,01 66,28 74,94 92,25 73,09 86,46 82,94 105,09 99,30 92,56 120,91 104,31 136,27 120,19 152,85 120,31 134,33 167,42 146,28 137,98 1,8793 1,2028 0,8353 0,6573 0,5946 0,5644 0,4130 0,3058 0,2992 0,2736 0,2374 0,2364 0,2259 0,1939 0,1682 0,1571 0,1380 0,1363 0,1249 0,1188 0,1094 0,0949 0,0949 0,0851 0,0757 0,0748 0,0666 0,0644 0,0590 0,0584 0,0566 0,0526 0,0514 0,0506 42 66 95 122 133 142 193 261 267 293 336 338 354 412 475 508 578 586 638 672 723 841 843 938 1056 1067 1201 1240 1356 1366 1411 1520 1552 1578 20 31 45 249 63 234 90 121 442 594 156 559 234 190 315 234 267 388 234 310 268 388 310 234 388 268 442 310 498 268 355 559 388 310 62 97 140 373 196 378 284 383 714 899 494 904 590 604 794 744 848 979 874 985 998 1233 1155 1174 1448 1336 1647 1553 1860 1636 1770 2085 1943 1889

290

ELKABEL

IEC 1089

Bare aluminium conductors

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Application
For overhead power transmission.

Construction data
Nominal crosssection mm2 10 16 25 40 63 100 125 160 200 250 315 400 450 500 560 630 Stranding and wire diameter N mm 7x1,35 7x1,71 7x2,13 7x2,70 7x3,39 19x2,59 19x2,89 19x3,27 19x3,66 19x4,09 37x3,29 37x3,71 37x3,94 37x4,15 37x4,39 61x3,63 Conductor diameter mm Breaking load, Electrical oresist- Weight of conducmin ance at 20 C, max tor, approx. kN /km 2,8633 1,7896 1,1453 0,7158 0,4545 0,2877 0,2302 0,1798 0,1439 0,1151 0,0916 0,0721 0,0641 0,0577 0,0515 0,0458 kg/km 27,4 43,8 68,4 109,4 172,3 274,8 343,6 439,8 549,7 687,1 867,9 1102 1239,8 1377,6 1542,9 1738,3

Al conductors 4,05 1,95 5,12 3,04 6,40 4,50 8,09 6,80 10,20 10,39 12,90 17,00 14,50 21,25 16,40 26,40 18,30 32,00 20,50 40,00 23,0 51,97 26,0 64,00 27,5 72,00 29,0 80,00 30,7 89,60 32,6 100,80

ELKABEL

291

Bare aluminium and aluminium steel reinforced stranded conductors

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Application
For overhead electric power transmission systems.

Construction data
Nominal crosssection mm2 16-AL1 24- AL1 34- AL1 49- AL1 48- AL1 66- AL1 93- AL1 117- AL1 147- AL1 182- AL1 243- AL1 299- AL1 400- AL1 500- AL1 Stranding and wire diameter N mm 7x1.70 7x2.10 7x2.50 7x3.00 19x1.80 19x2.10 19x2.50 19x2.80 37x2.25 37x2.50 61x2.25 61x2.50 61x2.89 61x3.23 Conductor diameter mm Breaking load, Electrical oresist- Weight of conducmin ance at 20 C, max tor, approx. kN /km 1.7986 1.1787 0.8317 0.5776 0.5944 0.4367 0.3081 0.2456 0.1960 0.1588 0.1193 0.0966 0.0723 0.0579 kg/km 43.4 66.3 93.9 135.2 132.9 180.9 256.3 321.5 405.7 500.9 671.1 828.5 1107.1 1382.9

Type AL1 conductors 5.10 3.02 6.30 4.36 7.50 6.01 9.00 8.41 9.0 8.94 10.5 11.85 12.5 16.32 14.0 19.89 15.8 26.48 17.5 31.78 20.3 43.66 22.5 52.40 26.0 68.02 29.1 82.47

Construction data
Nominal Stranding and cross-section wire diameter mm2 N mm Conductor diameter mm Breaking load, min kN Electrical resistance at 20oC, max /km Weight Al Weight St Weight of conductor, approx. kg/km

kg/km

kg/km

Type AL1/St1A conductors Al St 15-AL1/3-St1A 6x1,80+1x1,80 24-AL1/4-St1A 6x2,25+1x2,25 34-AL1/6-St1A 6x2,70+1x2,70 44-AL1/32-St1A 14x2,00+7x2,40 48-AL1/8-St1A 6x3,20+1x3,20 51-AL1/30-St1A 12x2,33+7x2,33 70-AL1/11-St1A 26x1,85+7x1,44 94-AL1/15-St1A 26x2,15+7x1,67 97-AL1/56-St1A 12x3,20+7x3,20 106-AL1/76-St1A 14x3,10+19x2,25 5,40 6,75 8,1 11,2 9,60 11,7 11,7 13,6 16,0 17,5 5.80 8.95 12.37 44.24 16.81 42.98 26.27 34.93 77.85 105.82 1,8769 1,2012 0,8342 0,6574 0,5939 0,5644 0,4132 0,3060 0,2992 0,2742 41.85 65.39 94.16 121.3 132.26 141.14 192.76 260.35 266.22 292.2 19.85 31.01 44.66 248.1 62.73 233.87 89.32 120.14 441.12 593.8 61.7 96.4 138.82 369.4 194.99 375.1 282.1 380.49 707.34 886

292

ELKABEL

BDS EN 50182

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Construction data
Nominal Stranding and cross-section wire diameter mm2 N mm Al St 26x2,44+7x1,90 12x3,60+7x3,60 30x2,33+7x2,33 26x2,70+7x2,10 30x2,70+7x2,70 26x3,00+7x2,33 26x3,20+7x2,49 30x3,00+7x3,00 24x3,50+7x2,33 26x3,45+7x2,68 24x3,74+7x2,49 26x3,86+7x3,00 54x2,68+7x2,68 48x3,00+7x2,33 54x3,00+7x3,00 48x3,20+7x2,49 54x3,20+7x3,20 48x3,45+7x2,68 54x3,40+7x3,40 45x3,74+7x2,49 48x3,68+7x2,87 54x3,60+7x3,60 48x3,86+7x3,00 45x4,02+7x2,68 Conductor diameter mm Breaking load, min kN Electrical resistance at 20oC, max /km Weight Al Weight St Weight of conductor, approx. kg/km

kg/km

kg/km

Type AL1/St1A conductors 122-AL1/20-St1A 122-AL1/71-St1A 128-AL1/30-St1A 149-AL1/24-St1A 172-AL1/40-St1A 184-AL1/30-St1A 209-AL1/34-St1A 212-AL1/49-St1A 231-AL1/30-St1A 243-AL1/39-St1A 264-AL1/34-St1A 304-AL1/49-St1A 305-AL1/39-St1A 339-AL1/30-St1A 382-AL1/49-St1A 386-AL1/34-St1A 434-AL1/56-St1A 449-AL1/39-St1A 490-AL1/64-St1A 494-AL1/34-St1A 511-AL1/45-St1A 550-AL1/71-St1A 562-AL1/49-St1A 571-AL1/39-St1A 15,5 18,0 16,3 17,1 18,9 19,0 20,3 21,0 21,0 21,8 22,4 24,4 24,1 25,0 27,0 26,7 28,8 28,7 30,6 29,9 30,7 32,4 32,2 32,2 44.50 97.92 56.41 53.67 74.89 65.27 73.36 92.46 72.13 85.12 81.04 105.09 96.80 91.71 121.30 102.56 133.59 119.05 150.81 117.96 133.31 166.32 146.28 136.40 0,2376 0,2364 0,2260 0,1940 0,1683 0,1571 0,1381 0,1363 0,1250 0,1188 0,1095 0,0949 0,0949 0,0852 0,0758 0,0749 0,0666 0,0644 0,0590 0,0584 0,0566 0,0526 0,0515 0,0506 335.32 336.94 353.09 410.6 474.13 506.91 576.75 585.35 636.44 670.38 726.72 839.19 841.20 937.4 1054.1 1066.51 1199.3 1239.7 1353.92 1365.5 1410.47 1517.9 1551.8 1577.7 155.51 558.3 233.87 189.97 314.03 233.87 267.09 387.7 233.87 309.4 267.09 387.7 309.40 233.87 387.7 267.09 441.12 309.40 497.98 267.09 354.83 558.29 387.7 309.4 490.83 895.24 586.96 600.57 788.16 741.0 843.84 973.05 870.31 979.78 993.81 1226.89 1150.6 1171.2 1440.44 1333.6 1641.3 1549.1 1851.9 1632.6 1765.3 2076.2 1939.5 1887.1

ELKABEL

293

Bare aluminium conductors andand BS 215 part 1 BS 215 part 2 aluminum conductors, steel reinforced

BARE ALUMINIUMCONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

Application
For overhead power transmission.

Construction data
Nominal crosssection mm2 22 50 60 100 150 200 250 300 400 Stranding and wire diameter N mm Conductor diameter mm Breaking load, Electrical oresist- Weight of conducmin ance at 20 C, max tor, approx. kN /km kg/km 64 145 174 290 434 587 731 888 1145

ALUMINIUM STRANDED CONDUCTORS - BS 215 part 1 7x2,06 6,18 3,99 1,227 7x3,10 9,30 8,28 0,5419 7x3,40 10,20 9,90 0,4505 7x4,39 13,17 16,00 0,2702 19x3,25 16,25 25,70 0,1825 19x3,78 18,90 32,40 0,1349 19x4,22 21,10 40,40 0,1083 19x4,65 23,25 48,75 0,08916 37x3,78 26,46 63,10 0,06944

Construction data
Nominal crosssection mm2 25 30 40 50 70 100 150 150 175 175 200 200 400 Stranding and wire Conductor diame- Breaking load, Electrical oresist- Weight of conducdiameter ter min ance at 20 C, max tor, approx. N mm mm kN /km kg/km 106 128 172 214 538 394 726 506 842 587 974 671 1621 ALUMINIUM CONDUCTORS, STEEL REINFORCED - BS 215 part 2 6x2,36+1x2,36 7,08 9,61 1,093 6x2,59+1x2,59 7,77 11,45 0,9077 6x3,00+1x3,00 9,00 15,20 0,6766 6x3,35+1x3,35 10,05 18,35 0,5426 12x2,79+7x2,79 13,95 61,20 0,3936 6x4,72+7x1,57 14,15 32,70 0,2733 30x2,59+7x2,59 18,13 69,20 0,1828 18x3,35+1x3,35 16,75 35,70 0,1815 30x2,79+7x2,79 19,53 79,80 0,1576 18x3,61+1x3,61 18,05 41,10 0,1563 30x3,00+7x3,00 21,00 92,25 0,1363 18x3,86+1x3,86 19,30 46,55 0,1367 54x3,18+7x3,18 28,62 131,90 0,0674

294

ELKABEL

CABLES AND WIRES ACCORDING TO BDS

ELKABEL

CABLES AND WIRES ACCORDING TO BDS

SVT
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Cable costruction
Construction Conductor Insulation Sheath Color re rm sm According to BDS 16291-85. solid or twisted copper wires, class 1 or 2 according to BDS 904-84 (IEC 60228). PVC compound. PVC compound. *cable is produced without or with joint filling. Grey or black. Conductors type circular solid conductor. circular stranded conductor. sector stranded conductor.

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test 3- core 4- core According to BDS 904-84 +70 +160 , not more than 5 sec. 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 10 D cable -5 C -30 to +50 BDS IEC 332-1 5- core Multiple core

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request. Double core -light blue and brown or yellow-green and black. Other constructions according to table.

blue brown brown black black grey grey or yelor low/green yellow/green blue brown brown black grey

blue brown black with number mark on black grey cores black or or yellow/green black with number mark on and blue brown coresin theyellow/green core outer cover black grey

296

ELKABEL

Cu conductors

PVC insulation

PVC sheath

LOW VOLTAGE POWER CABLES

Construction data SVT 0.6/1 kV


Number of wires and nominal cross section N mm2
1 1.5 1 2.5 1 4.0 1 6.0 1 10 1 16 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 1.0 2 1.5 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 2 35 2 50 3 1.0 3 1.5 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 2.5 + 1.5 3 4.0 + 2.5 3 6.0 + 4.0 3 10 + 6.0 3 16 + 10 3 25 + 16 3 35 + 16 3 50 + 25 3 70 + 35 3 95 + 50 3 120 + 70 3 150 + 70 3 185 + 95 3 240 + 120 4 1.0 4 1.5 re re re re re re rm rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re re rm rm rm re re re re re re re rm rm rm sm sm sm sm sm sm re/re re/re re/re re/re re/re rm/re rm/re rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm re re

Construction data SVT 0.6/1 kV


Number of wires and nominal cross section N mm2
4 2.5 4 4.0 4 6.0 4 10 4 16 4 25 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 5 1.0 5 1.5 5 2.5 5 4.0 5 6.0 5 10 5 16 5 25 5 35 5 50 5 70 5 95 7 1.5 8 1.5 10 1.5 12 1.5 14 1.5 16 1.5 19 1.5 24 1.5 30 1.5 37 1.5 7 2.5 8 2.5 10 2.5 12 2.5 14 2.5 16 2.5 19 2.5 24 2.5 30 2.5 37 2.5 7 4.0 10 4.0 7 6.0 7 10 re re re re re rm rm rm sm sm sm sm sm sm re re re re re re re rm rm rm sm sm re re re re re re re re re re re re re re re re re re re re re re re re

Shape

Outer diameter of cable approx. mm


7.2 7.6 8.0 8.5 9.3 10.8 10.8 11.9 13.0 14.2 16.7 18.4 19.9 21.9 24.3 27.2 30.3 33.8 37.9 9.3 10.0 10.6 12.1 13.2 15.2 17.8 21.5 23.8 27.0 9.6 10.2 11.0 12.8 14.0 16.0 18.9 22.8 25.3 28.9 28.8 33.1 35.9 39.3 43.4 48.9 11.2 13.4 14.4 16.7 19.5 24.4 27.1 30.8 31.8 36.8 40.1 44.3 49.3 55.4 10.4 11.0

Cu weight kg/km
14 23 37 55 93 148 148 229 325 458 648 885 1120 1378 1703 2208 2765 3680 4600 20 28 46 75 110 182 303 470 652 928 28 42 69 110 165 275 450 700 980 1390 1950 2650 3350 4185 5160 6720 82 132 202 330 540 850 1130 1630 2280 3120 4010 4850 6070 7840 37 55

Cable weight approx. kg/km


69 82 102 125 178 253 253 350 462 598 810 1100 1385 1610 2020 2565 3200 4035 5180 100 120 150 210 260 370 558 810 1057 1408 119 122 154 260 349 480 682 1078 1298 1895 2400 3225 4010 4830 6035 7818 203 293 380 545 870 1245 1590 2175 2785 3680 4730 5620 7090 9150 140 165

Shape

Outer diameter of cable approx. mm


11.9 13.6 14.4 16.8 19.2 25.2 28.0 32.0 33.0 37.3 41.2 45.2 49.5 56.4 11.2 11.8 12.8 15.5 16.8 19.2 23.2 27.9 32.4 36.9 42.0 48.7 12.0 13.1 14.7 15.4 16.1 17.1 18.0 21.2 22.6 24.4 13.0 14.1 16.5 17.1 18.1 19.8 20.3 24.1 25.3 27.4 15.8 20.4 17.3 20.0

Cu weight kg/km
92 146 218 363 582 925 1303 1857 2601 3540 4460 5575 6880 8928 45 69 114 182 275 455 745 1165 1640 2330 3260 4430 96 110 140 165 195 220 260 330 410 506 160 182 228 275 320 365 435 546 685 845 255 365 384 640

Cable weight approx. kg/km


216 317 408 593 951 1285 1778 2307 3101 4250 5210 6385 7960 10310 160 195 260 380 500 735 1150 1700 2360 3130 4230 5640 230 265 315 365 415 470 550 690 840 1090 315 365 445 525 590 670 780 995 1210 1485 470 668 630 965

ELKABEL

297

SVT-s
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation , with conditions of work to atmosphere influence and sunlight radiation at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Cable costruction
Construction Conductor Insulation Sheath Color re rm sm According to BDS 16291-85. solid or twisted copper wires, class 1 or 2 according to BDS 904-84. (IEC 60228). PVC compound. PVC compound UV steadily. *cable is produced without or with joint filling. black. Conductors type circular solid conductor. circular stranded conductor. sector stranded conductor.

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test 3- core 4- core 5- core

According to BDS 904-84 +70 +160 , not more than 5 sec. 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 10 D cable -5 -30 to +50 BDS IEC 332-1 Multiple core

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request. Double core - black and blue. Other constructions according to table.

blue brown blue brown black with number mark on brown black black grey black grey cores black grey or yelor or or low/green yellow/green yellow/green black with number mark on blue brown brown black blue brown cores and yellow/green grey core in the outer cover black grey

298

ELKABEL

Cu conductors

PVC insulation

PVC sheath - UV steadily

LOW VOLTAGE POWER CABLES

Construction data SVT-s 0.6/1 kV


Number of wires and nominal cross section N mm2 1 1.5 1 2.5 1 4.0 1 6.0 1 10 1 16 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 1.0 2 1.5 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 2 35 2 50 3 1.0 3 1.5 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 2.5 + 1.5 3 4.0 + 2.5 3 6.0 + 4.0 3 10 + 6.0 3 16 + 10 3 25 + 16 3 35 + 16 3 50 + 25 3 70 + 35 3 95 + 50 3 120 + 70 3 150 + 70 re re re re re re rm rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re re rm rm rm re re re re re re re rm rm rm sm sm sm sm sm sm re/re re/re re/re re/re re/re rm/re rm/re rm/rm sm/rm sm/rm sm/rm sm/rm Shape Outer diameter of cable approx. mm 7.2 7.6 8.0 8.5 9.3 10.8 10.8 11.9 13.0 14.2 16.7 18.4 19.9 21.9 24.3 27.2 30.3 33.8 37.9 9.3 10.0 10.6 12.1 13.2 15.2 17.8 21.5 23.8 27.0 9.6 10.2 11.0 12.8 14.0 16.0 18.9 22.8 25.3 28.9 28.8 33.1 35.9 39.3 43.4 48.9 11.2 13.4 14.4 16.7 19.5 24.4 27.1 30.8 31.8 36.8 40.1 44.3 Cu weight kg/km 14 23 37 55 93 148 148 229 325 458 648 885 1120 1378 1703 2208 2765 3680 4600 20 28 46 75 110 182 303 470 652 928 28 42 69 110 165 275 450 700 980 1390 1950 2650 3350 4185 5160 6720 82 132 202 330 540 850 1130 1630 2280 3120 4010 4850 Cable weight approx. kg/km 69 82 102 125 178 253 253 350 462 598 810 1100 1385 1610 2020 2565 3200 4035 5180 100 120 150 210 260 370 558 810 1057 1408 119 122 154 260 349 480 682 1078 1298 1895 2400 3225 4010 4830 6035 7818 203 293 380 545 870 1245 1590 2175 2785 3680 4730 5620

Construction data SVT-s 0.6/1 kV


Number of wires and nominal cross section N mm2 3 185 + 95 3 240 + 120 4 1.0 4 1.5 4 2.5 4 4.0 4 6.0 4 10 4 16 4 25 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 5 1.0 5 1.5 5 2.5 5 4.0 5 6.0 5 10 5 16 5 25 5 35 5 50 5 70 5 95 7 1.5 8 1.5 10 1.5 12 1.5 14 1.5 16 1.5 19 1.5 24 1.5 30 1.5 37 1.5 7 2.5 8 2.5 10 2.5 12 2.5 14 2.5 16 2.5 19 2.5 24 2.5 30 2.5 37 2.5 7 4.0 10 4.0 7 6.0 7 10 sm/rm sm/rm re re re re re re re rm rm rm sm sm sm sm sm sm re re re re re re re rm rm rm sm sm re re re re re re re re re re re re re re re re re re re re re re re re Shape Outer diameter of cable approx. mm 49.3 55.4 10.4 11.0 11.9 13.6 14.4 16.8 19.2 25.2 28.0 32.0 33.0 37.3 41.2 45.2 49.5 56.4 11.2 11.8 12.8 15.5 16.8 19.2 23.2 27.9 32.4 36.9 42.0 48.7 12.0 13.1 14.7 15.4 16.1 17.1 18.0 21.2 22.6 24.4 13.0 14.1 16.5 17.1 18.1 19.8 20.3 24.1 25.3 27.4 15.8 20.4 17.3 20.0 Cu weight kg/km 6070 7840 37 55 92 146 218 363 582 925 1303 1857 2601 3540 4460 5575 6880 8928 45 69 114 182 275 455 745 1165 1640 2330 3260 4430 96 110 140 165 195 220 260 330 410 506 160 182 228 275 320 365 435 546 685 845 255 365 384 640 Cable weight approx. kg/km 7090 9150 140 165 216 317 408 593 951 1285 1778 2307 3101 4250 5210 6385 7960 10310 160 195 260 380 500 735 1150 1700 2360 3130 4230 5640 230 265 315 365 415 470 550 690 840 1090 315 365 445 525 590 670 780 995 1210 1485 470 668 630 965

Note: Cable may be produced without joint filling.

ELKABEL

299

SAVT
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Cable costruction
Construction Conductor Insulation Sheath Color re rm sm According to BDS 16291-85. solid or twisted aluminum wires class 1 or 2, according to BDS 904-84 (IEC 60228). PVC compound. PVC compound. *cable may be with or without joint filling. gray. Conductors type circular, solid conductor. circular, stranded conductor. sector, stranded conductor.

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test

According to BDS 904-84 +70 +160 , not more than 5 sec. 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 10 D cable -5 -30 to +50 BDS IEC332-1

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request. Double core - blue and brown or yellow-green and black. Other construction according to table.

3- core

4- core

5- core

Multiple core

blue brown blue brown black with number mark on brown black black grey black grey cores black grey or yelor or or low/green yellow/green yellow/green black with number mark on blue brown brown black blue brown cores and yellow/green grey core in the outer cover black grey

300

ELKABEL

Al conductors

PVC insulation

PVC sheath

LOW VOLTAGE POWER CABLES

Construction data SAVT 0.6/1 kV


Number of wires and nominal cross section N mm2 1 4.0 1 6.0 1 10 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 re re re re re rm rm rm rm rm rm rm rm rm rm rm re re re re re re re re re re re re rm rm sm sm sm sm sm sm Shape Outer diameter of cable approx. mm 8.1 8.6 9.4 10.2 11.4 13.0 14.2 16.7 18.4 19.9 21.9 24.3 27.2 30.3 33.8 37.9 10.3 12.2 13.3 14.8 16.8 20.3 11.0 12.8 14.0 15.8 18.2 21.6 25.3 28.8 28.8 33.1 35.9 39.3 43.8 49.4 Al weight kg/km 12 17 28 45 68 95 127 190 260 325 405 510 665 830 1060 1410 14 23 34 56 90 137 21 36 51 85 135 210 290 385 585 810 1020 1255 1560 2035 Cable weight approx. kg/km 78 91 115 150 187 225 265 360 465 550 680 830 1065 1305 1595 2070 120 160 185 245 340 470 130 185 225 290 380 610 740 950 1090 1490 1710 2060 2610 3320

Construction data SAVT 0.6/1 kV


Number of wires and nominal cross section N mm2 Shape Outer diameter of cable approx. mm Al weight kg/km Cable weight approx. kg/km 205 240 320 475 630 825 1025 1250 1680 2010 2415 2975 3805 152 216 260 340 460 670 905 1180 1390 1860 2210 2710 3320 4110 180 270 320 430 580 855 1210 1470 1955

3 4.0 + 2.5 re/re 13.4 42 3 6.0 +4.0 re/re 14.4 63 3 10 + 6.0 re/re 16.7 101 3 16 + 10 re/re 19.2 165 3 25 + 16 re/re 23.0 255 3 35 + 16 rm/re 26.8 340 3 50 + 25 rm/rm 30.8 480 3 70 + 35 sm/rm 31.8 670 3 95 + 50 sm/rm 37.0 910 3 120 + 70 sm/rm 40.1 1180 3 150 + 70 sm/rm 44.3 1405 3 185 + 95 sm/rm 49.3 1780 3 240 + 120 sm/rm 55.4 2310 4 2.5 re 11.9 28 4 4.0 re 14.1 46 4 6.0 re 15.4 68 4 10 re 17.4 112 4 16 re 19.8 180 4 25 re 23.8 270 4 35 rm 28.0 390 4 50 rm 32.0 520 4 70 sm 33.0 760 4 95 sm 38.1 1060 4 120 sm 41.4 1340 4 150 sm 46.0 1650 4 185 sm 51.1 2100 4 240 sm 58.0 2720 5 2.5 re 12.8 35 5 4.0 re 15.5 58 5 6.0 re 16.8 85 5 10 re 19.2 140 5 16 re 23.2 225 5 25 re 27.9 345 5 35 rm 32.4 480 5 50 rm 36.9 650 5 70 sm 42.0 965 Note: Cable may be produced without joint filling

ELKABEL

301

SVTT
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Cable costruction
Construction Conductor Insulation Inner sheath Outer sheath Color re rm sm According to BDS 16291-85. solid or twisted copper wires, class 1 or 2, BDS 904-84 (IEC 60228). PVC compound. PVC compound. PVC compound. Gray or black. Conductors type circular, solid conductor. circular, stranded conductor. sector, stranded conductor.

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test According to BDS 904-84 +70 +160 , not more than 5 sec. 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 10 D cable -5 -30 to +50 BDS IEC332-1 5- core Multiple core

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request. Double core - blue and brown or yellow-green and black. Other constructions according to table.

3- core

4- core

blue brown black with number mark on blue brown black black brown black grey cores grey or black grey or or or yellow/green yellow/green yellow/green black with number mark on brown black blue brown and grey blue brown coresin theyellow/green core outer cover black grey

302

ELKABEL

Cu conductors

PVC insulation

PVC sheath

LOW VOLTAGE POWER CABLES

Construction data SVTT 0.6/1 kV


Number of wires and nominal cross section N mm2 1 1.5 1 2.5 1 4.0 1 6.0 1 10 1 16 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 1.0 2 1.5 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 2 35 2 50 3 1.0 3 1.5 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 2.5 + 1.5 3 4.0 + 2.5 3 6.0 + 4.0 3 10 + 6.0 3 16 + 10 3 25 + 16 3 35 + 16 3 50 + 25 3 70 + 35 3 95 + 50 3 120 + 70 re re re re re re rm rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re re rm rm rm re re re re re re re rm rm rm sm sm sm sm sm sm re/re re/re re/re re/re re/re rm/re rm/re rm/rm sm/rm sm/rm sm/rm Shape Outer diameter of cable approx. mm 9.5 9.9 10.3 10.8 11.6 13.2 13.2 14.3 15.4 16.6 18.4 20.4 22.0 23.9 26.2 29.3 32.0 35.6 39.9 10.3 10.8 11.5 13.4 14.2 16.1 19.1 22.2 24.2 27.6 10.7 11.2 12.0 14.0 15.0 16.9 20.2 23.2 25.6 29.1 30.0 34.5 37.3 40.9 45.4 51.0 12.5 14.6 15.7 17.5 19.6 24.9 27.1 30.8 33.2 38.2 41.5 Cu weight kg/km 14 23 37 55 93 148 148 229 325 458 648 885 1120 1378 1703 2208 2765 3680 4600 20 28 46 75 110 182 303 470 652 928 28 42 69 110 165 275 450 700 980 1390 1950 2650 3350 4185 5160 6720 82 132 202 330 540 850 1130 1630 2280 3120 4010 Cable weight approx. kg/km 108 124 143 170 221 308 308 412 524 659 880 1161 1430 1752 2156 2735 3412 4324 5432 132 158 182 250 305 418 587 875 1235 1510 145 170 214 295 374 520 765 1125 1465 1960 2450 3310 4065 4950 6160 7950 230 330 390 590 895 1303 1661 2228 2859 3875 4829

Construction data SVTT 0.6/1 kV


Number of wires and nominal cross section N mm2 Shape Outer diameter of cable approx. mm Cu weight kg/km Cable weight approx. kg/km

3 150 + 70 sm/rm 44.9 4850 5750 3 185 + 95 sm/rm 50.9 6070 7250 3 240 + 120 sm/rm 55.7 7840 9330 4 1.0 re 11.4 37 164 4 1.5 re 12.0 55 198 4 2.5 re 12.9 92 250 4 4.0 re 15.1 146 351 4 6.0 re 16.2 218 450 4 10 re 18.2 363 645 4 16 re 22.0 582 980 4 25 rm 25.5 925 1450 4 35 rm 28.3 1303 1860 4 50 rm 32.6 1857 2476 4 70 sm 34.4 2601 3205 4 95 sm 39.6 3540 4360 4 120 sm 43.0 4460 5340 4 150 sm 47.6 5575 6545 4 185 sm 53.0 6880 8175 4 240 sm 60.0 8928 10625 5 1.0 re 12.2 45 198 5 1.5 re 12.8 69 235 5 2.5 re 13.8 114 300 5 4.0 re 16.4 182 430 5 6.0 re 17.6 275 560 5 10 re 19.8 455 798 5 16 re 24.3 745 1230 5 25 rm 28.9 1165 1830 5 35 rm 33.2 1640 2420 5 50 rm 37.3 2330 3280 5 70 sm 42.9 3260 4390 5 95 sm 49.4 4430 5940 7 1.5 re 13.8 96 290 8 1.5 re 14.8 110 318 10 1.5 re 16.5 140 378 12 1.5 re 17.2 165 420 14 1.5 re 18.0 195 480 16 1.5 re 18.7 220 560 19 1.5 re 19.6 260 620 24 1.5 re 22.7 330 760 30 1.5 re 23.9 410 900 37 1.5 re 25.8 506 1190 7 2.5 re 14.8 160 348 8 2.5 re 15.9 182 405 10 2.5 re 18.4 228 520 12 2.5 re 18.7 275 590 14 2.5 re 19.6 320 660 16 2.5 re 20.8 365 740 19 2.5 re 21.7 435 845 24 2.5 re 25.1 546 1050 30 2.5 re 26.5 685 1290 37 2.5 re 28.6 845 1520 7 4.0 re 17.4 255 540 10 4.0 re 21.8 365 780 7 6.0 re 19.0 384 735 7 10 re 21.4 640 1070 Note: During the extrusion it is permitted simultaneous laying of the inner and outer sheath.

ELKABEL

303

SAVTT
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Cable costruction
Construction Conductor Insulation Inner sheath Outer sheath Color re rm sm According to BDS 16291-85. solid or twisted Al wires, class 1 or 2 according to BDS 904-84 (IEC 60228). PVC compound. PVC compound. PVC compound. Gray or black. Conductors type circular, solid conductor. circular, stranded conductor. sector, stranded conductor.

Technical data
Conductor resistance at 20 Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test According to BDS 904-84 +70 +160 , not more than 5 sec. 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 10 D cable -5 -30 to +50 BDS IEC332-1 5- core Multiple core

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request. Double core - blue and brown or yellow-green and black. Other constructions according to table.

3- core

4- core blue brown black grey or yellow/green brown black grey

brown black grey or yellow/green blue brown

blue brown black with number mark on black grey cores black or or yellow/green black with number mark on and blue brown coresin theyellow/green core outer cover black grey

304

ELKABEL

Al conductors

PVC insulation

PVC sheath

LOW VOLTAGE POWER CABLES

Construction data SAVTT 0.6/1 kV


Number of wires and nominal cross section N mm2 1 4.0 1 6.0 1 10 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 4.0 + 2.5 re re re re re rm rm rm rm rm rm rm rm rm rm rm re re re re re re re re re re re re rm rm sm sm sm sm sm sm re/re Shape Outer diameter of cable approx. mm 10.3 10.8 11.6 13.2 14.3 15.4 16.6 18.4 20.4 22.0 23.9 26.2 29.3 32.0 35.6 39.9 11.5 13.4 14.3 15.9 17.7 21.4 12.0 14.0 15.0 16.7 18.7 22.0 25.5 29.1 30.0 34.5 37.3 40.9 45.4 51.0 14.6 Al weight kg/km 12 17 28 45 68 95 127 190 260 325 405 510 665 830 1060 1410 14 23 34 56 90 137 21 36 51 85 135 210 290 385 585 810 1020 1255 1560 2035 42 Cable weight approx. kg/km 120 134 160 210 247 295 355 465 575 663 785 951 1193 1450 1834 2265 155 212 248 307 389 545 165 233 277 345 444 626 817 1075 1156 1557 1823 2285 2730 3405 241

Construction data SAVTT 0.6/1 kV


Number of wires and nominal cross section N mm2 Shape Outer diameter of cable approx. mm Al weight kg/km Cable weight approx. kg/km

3 6.0 + 4.0 re/re 15.7 63 284 3 10 + 6.0 re/re 17.5 101 364 3 16 + 10 re/re 19.6 165 495 3 25 + 16 re/re 24.9 255 676 3 35 + 16 rm/re 27.1 340 900 3 50 + 25 rm/rm 30.8 480 1095 3 70 + 35 sm/rm 33.2 670 1360 3 95 + 50 sm/rm 38.2 910 1840 3 120 + 70 sm/rm 41.5 1180 2210 3 150 + 70 sm/rm 44.9 1405 2735 3 185 + 95 sm/rm 50.9 1780 3245 3 240 + 120 sm/rm 55.7 2310 4276 4 2.5 re 12.9 28 152 4 4.0 re 15.1 46 216 4 6.0 re 16.2 68 260 4 10 re 18.2 112 340 4 16 re 22.0 180 460 4 25 re 25.5 270 670 4 35 rm 28.3 390 905 4 50 rm 32.6 520 1180 4 70 sm 34.4 760 1390 4 95 sm 39.6 1060 1860 4 120 sm 43.0 1340 2210 4 150 sm 47.6 1650 2710 4 185 sm 53.0 2100 3320 4 240 sm 60.0 2720 4110 5 2.5 re 13.8 35 180 5 4.0 re 16.4 58 270 5 6.0 re 17.6 85 320 5 10 re 19.8 140 430 5 16 re 24.3 225 580 5 25 re 28.9 345 855 5 35 rm 33.2 480 1210 5 50 rm 37.3 650 1470 5 70 sm 42.9 965 1955 5 95 sm 49.4 1345 2545 Note: During the extrusion it is permitted simultaneous laying of the inner and outer sheath.

ELKABEL

305

SVBT
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transfer and distribution of electrical power for switching installation and in static installations, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.These cables are used for indoor installations, in the open air, in ditches, tunnels, canals and shafts.

Cable design
Construction Conductor According to BDS 16291-85 solid or twisted copper wires, class 1 or 2, BDS 904-84 (IEC 60228) PVC compound PVC compound Steel tapes PVC compound Gray or black circular, solid conductor circular, stranded conductor sector, stranded conductor

Technical data
Conductor resistance at 20 C Max. conductor temperature According to BDS 904-84 +70 C

Insulation Inner sheath Armour Outer sheath Color Conductors type re rm sm

Max. short circuit tempera- +160 C, not more than 5 ture sec. Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 15 D cable. -5 C -30 C to +50 C BDS IEC332-1

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request Double core - blue and brown or yellow-green and black Other constructions according to table

5 - core Multiple core blue blue brown brown brown black black with number black black grey mark on cores grey grey black or or or or black with number yellow/gre yellow/gre yellow/gre mark on cores and yelen en en low/green core in the blue brown blue outer cover brown black brown grey black grey

3 - core

4 - core

306

ELKABEL

Cu conductors PVC insulation Armour St tapes PVC sheath

LOW VOLTAGE POWER CABLES

Constructive data SVBT 0.6/1 kV


Number of conductors and nominal cross section N x mm2 1 10 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 2 2.5 24 26 2 10 2 16 2 25 2 35 2 50 3 1.5 3 2.5 34 36 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 2.5 + 1.5 3 4 + 2.5 36+4 3 10 + 6 3 16 + 10 3 25 + 16 3 35 + 16 3 50 + 25 3 70 + 35 3 95 + 50 3 120 + 70 3 150 + 70 3 185 + 95 re rm rm rm rm rm rm rm rm rm rm re re re re re rm rm rm re re re re re re rm rm rm sm sm sm sm sm sm re+re re+re re+re re+re re+re rm+re rm+re rm+rm sm+rm sm+rm sm+rm sm+rm sm+rm Shape Outer cable diameter approx. mm 12.5 13.5 15.3 16.4 17.6 19.9 21.6 23.3 25.1 27.7 30.6 12.7 14.6 15.7 17.3 19.3 23.7 25.9 29.4 12.4 13.2 15.4 16.4 18.3 20.3 25.0 27.5 31.3 32.2 36.7 39.5 43.1 47.6 53.4 13.7 16.0 17.1 19.1 21.2 26.3 29.1 33.0 35.4 40.2 43.7 48.1 53.3 Copper weight kg/km 93 148 229 325 458 648 885 1120 1378 1703 2208 46 75 110 182 303 470 652 928 42 69 110 165 275 450 700 980 1390 1950 2650 3350 4185 5160 6720 82 132 202 330 540 850 1130 1630 2280 3120 4010 4850 6070 Cable weight approx. kg/km 302 381 515 624 771 1025 1305 1575 1890 2307 2935 261 346 415 538 711 1038 1315 1706 252 297 410 490 660 880 1326 1685 2210 2754 3670 4452 5368 6635 8501 295 450 545 736 996 1514 1890 2499 3212 4180 5260 6220 7786

Constructive data SVBT 0.6/1 kV


Number of conductors and nominal cross section N x mm2 3 240 + 120 4 1.5 4 2.5 44 46 4 10 4 16 4 25 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 5 1.5 5 2.5 54 56 5 10 5 16 5 25 5 35 5 50 5 70 7 1.5 8 1.5 10 1.5 12 1.5 14 1.5 16 1.5 19 1.5 24 1.5 30 1.5 37 1.5 7 2.5 8 2.5 10 2.5 12 2.5 14 2.5 16 2.5 19 2.5 24 2.5 30 2.5 37 2.5 sm+rm re re re re re re rm rm rm sm sm sm sm sm sm re re re re re re rm rm rm rm re re re re re re re re re re re re re re re re re re re re Shape Outer cable diameter approx. mm 59.6 13.2 14.1 16.5 17.6 19.8 22.0 27.4 30.4 34.4 36.6 42.0 45.4 50.0 55.2 62.2 14.0 15.2 17.7 19.2 21.4 24.0 30.7 33.4 38.7 43.7 15.2 16.2 18.3 18.8 19.5 20.5 21.3 24.5 25.7 27.7 16.3 17.3 19.9 20.4 21.4 22.6 23.5 27.0 28.4 30.8 Copper weight kg/km 7840 55 92 146 218 363 582 925 1303 1857 2601 3540 4460 5575 6880 8928 69 114 182 275 455 745 1165 1640 2330 3260 96 110 140 165 195 220 260 330 410 506 160 182 228 275 320 365 435 546 685 845 Cable weight approx. kg/km 9910 286 350 480 580 800 1080 1642 2175 2762 3478 4791 5800 7975 8117 10080 331 413 567 708 970 1324 2048 2758 3840 5128 421 465 571 610 675 740 814 1042 1180 1370 508 570 719 778 838 941 1050 1354 1551 1820

ELKABEL

307

SAVBT
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV BDS 16291-85

Application
Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz. These cables are used for indoor installations, in the open air, in ditches, tunnels, canals and shafts.

Cable design
Construction Conductor According to BDS 16291-85 solid or twisted aluminum wires class 1 or 2, according to BDS 904-84 (IEC 60228) PVC compound PVC compound steel tapes PVC compound Gray or black circular, solid conductor circular, stranded conductor sector, stranded conductor

Technical data
Conductor resistance at 20 C Max. conductor temperature Max. short circuit temperature Rated voltage Test voltage Bending radius, min. Temperature of laying Temperature range Flame test According to BDS 904-84 +70 C +160 C, not more than 5 sec. 0,6/1 kV AC - 4 kV 50 Hz DC - 12 kV 15 D cable -5 C -30 C to +50 C BDS IEC332-1

Insulation Inner sheath Armour Sheath Color Conductors type re rm sm

Color coding
Single core - black, brown, blue,yellow/green or other colors upon request Double core - blue and brown or yellow-green and black Other constructions according to table

5 - core Multiple core blue blue brown brown brown black with number black black black mark on cores grey grey grey or black or or black with number or yellow/gre yellow/gre yellow/green mark on cores and yelen en low/green core in the blue blue brown outer cover brown brown black black grey grey

3 - core

4 - core

308

ELKABEL

Al conductors PVC insulation Armour St. tapes PVC sheath

LOW VOLTAGE POWER CABLES

Constructive data SAVBT 0.6/1 kV


Number of conductors and nominal cross section N x mm2 1 10 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 2 2.5 24 26 2 10 2 16 2 25 3 2.5 34 36 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 4 + 2,5 36+4 re re re rm rm rm rm rm rm rm rm re re re re re re re re re re re re rm rm sm sm sm sm sm sm re+re re+re Shape Outer cable diameter Al weight approx. mm 12.5 13.5 14.6 16.4 17.6 19.9 21.6 23.3 25.1 27.7 30.6 12.7 14.6 15.7 17.3 19.3 23.7 13.2 15.4 16.4 18.3 20.3 25.0 27.5 31.3 32.2 36.7 39.5 43.1 47.6 53.4 16.0 17.1 kg/km 28 45 68 95 127 190 260 325 405 510 665 14 23 34 56 90 137 21 36 51 85 135 210 290 385 585 810 1020 1255 1560 2035 42 63 Cable weight approx. kg/km 240 280 332 407 476 595 710 824 963 1152 1426 232 298 341 412 510 687 253 335 380 473 585 699 1014 1290 1469 1889 2205 2607 3160 3948 360 413

Constructive data SAVBT 0.6/1 kV


Number of conductors and nominal cross section N x mm2 3 10 + 6 3 16 + 10 3 25 + 16 3 35 + 16 3 50 + 25 3 70 + 35 3 95 + 50 3 120 + 70 3 150 + 70 3 185 + 95 3 240 + 120 4 2,5 44 46 4 10 4 16 4 25 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 5 2.5 54 56 5 10 5 16 5 25 5 35 5 50 re+re re+re re+re rm+re rm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm re re re re re rm rm sm sm sm sm sm sm sm re re re re re re rm rm Shape Outer cable diameter Al weight approx. mm 19.1 21.2 26.3 29.1 33.0 35.4 40.2 43.7 48.1 53.3 59.6 14.1 16.5 17.6 19.8 22.0 27.4 30.4 34.4 36.6 42.0 45.4 50.0 55.2 62.2 15.2 17.7 19.2 21.4 24.0 30.7 33.4 38.7 kg/km 101 165 255 340 480 670 910 1180 1405 1780 2310 28 46 68 112 180 270 390 520 760 1060 1340 1650 2100 2720 35 58 85 140 225 345 480 650 Cable weight approx. kg/km 514 638 874 929 1349 1697 2183 2562 3006 3683 4565 286 381 434 549 683 935 1223 1540 1855 2415 2811 3391 4082 5149 334 445 520 652 829 1245 1600 2160

ELKABEL

309

SVOBT
LOW VOLTAGE POWER CABLES

U to 1kV BDS 11303-83

Application
These cables are used in signaling systems, automatics and block systems in the railway transport.

Cable design
Construction Conductor Insulation Insulation color Filling Led sheath Inner sheath Armour Sheath Color According to BDS 11303-83 copper, single core according to BDS 904-84 class1 PVC compound according to BDS 5792-84 according to BDS 11303-83 PVC compound according to BDS 4712-84 thermoplastic material Steel tapes PVC compound according to BDS 5792-84 gray

Technical data
Conductor resistance at 20 C Operating temperature Nominal voltage Test voltage AC, 50 Hz Temperature of exploitation Bending radius, min, Fixed Tests according to BDS 11303-83 max 70 C to 1 V 4 V

- 25 C to + 50 C

15 x D cable BDS 11303-83

Color coding
3- core 4- core blue brown black grey or yellow/green brown black grey 5- core blue brown black grey black or yellow/green blue brown black grey Multiple core

brown black grey or yellow/green blue brown

black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover

310

ELKABEL

Cu conductors PVC insulation Pb sheath Armour St. tapes PVC sheath

LOW VOLTAGE POWER CABLES

Constructive data SVOBT up to 1 kV


Number of conductors and nominal cross section N x mm2 3x1.5 3x2.5 4x1.5 4x2.5 44.0 51.5 61.5 71.5 72.5 81.5 84.0 101.5 104.0 121.5 141.5 142.5 161.5 191.5 192.5 241.5 242.5 301.5 302.5 371.5 Outer cable diameter approx. mm 18.0 19.5 17.7 19.8 21.0 18.8 19.6 19.6 21.5 20.6 25.0 22.8 28.4 23.4 24.0 27.0 25.0 25.9 29.3 29.3 33.5 30.7 35.0 32.7 Copper weight kg/km 42 70 55 92 146 70 85 98 160 110 280 140 365 165 195 320 220 260 435 330 546 410 685 506 Cable weight approx. kg/km 840 960 850 1050 1220 960 1052 1068 1290 1140 1700 1360 2150 1450 1550 1900 1650 1765 2300 2185 2870 2435 3200 2850

ELKABEL

311

SAPEmT-et
LOW VOLTAGE POWER CABLES

Uo/U - 0.6/1 kV U(=) 3 kV BDS 2581-86

AL conductors PE insulation u screen PVC sheath

Application
The single-core cables with polyethylene (PE) insulation Cu screen are used mainly for electrical systems with nominal voltage 3 V and are applicable for electrical public and metropolitan transportation. They can be used for transfer, distribution and electrical power supply with nominal voltage Uo/U 0.6/1 kV and frequency of 50Hz. The cables are for fixed assembly in lines with unlimited difference levels, underground, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelter.

Cable construction
Construction Conductor Insulation Metal screen Sheath Color According to BDS 2581-86 l solid round multi cores BDS 2581-86( IEC 60228 ) class 2 PE compound copper tapes PVC compound type P-1 gray

Technical data
Conductor resistance at 20C Operating temperature Overload temperature .100h/per year Short circuit temperature Nominal voltage -alternating -constant Highest system voltage Uo/U no more than Test voltage AC - 5 min Bending radius, min. Temperature of laying Temperature of exploitation According to BDS 904 (IEC 60228) class 2 90 continuous operation 130 250 /5 s max/ 0.6/1 kV 3 V 0.6/1 V 1.2 kV Between core and screen 3.5kV 15x D cable no less than -5

-30 to 50 l cores - 30*n*S core n- number of cores and Force of strain in laying N S- cross section of cores in Max. mm

Construction data SAPEmT-et 0.6/1 kV U(=) 3 kV


Number of conductors and nominal cross section N mm2 Uo/U 0.6/1kV U(=) 3kV 1x300 1x400 1x500 Thickness of insulation mm Nominal cross section of Thickness of Cable diameter screen sheath approx. min. mm2 mm mm

SAPEmT-t
Mass of Al approx. kg/km Cable weight approx. kg/km

2.4 2.6 3.0

2.5 2.5 2.5

2.0 2.1 2.2

30.8 34.3 38.3

830 1060 1410

1358 1691 2158

312

ELKABEL

SAHEmT-et

Uo/U - 0.6/1 kV U(=) 3 kV BDS 2581-86

LOW VOLTAGE POWER CABLES

Application
The single-core cables with cross-linked polyethylene (XLPE) insulation Cu screen are used mainly for electrical systems with nominal voltage 3 V and are applicable for electrical public and metropolitan transportation. They can be used for transfer, distribution and electrical power supply with nominal voltage Uo/U 0.6/1 kV and frequency of 50Hz. The cables are for fixed assembly in lines with unlimited difference levels, underground, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelter.

Cable construction
Construction Conductor According to BDS 2581-86 l solid round stranded BDS 2581-86 (IEC 60228) class 2 LPE compound copper tapes PVC compound type P-5 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature .100h/per year Short circuit temperature Nominal voltage -alternating -constant Highest system voltage Uo/U no more than Test voltage AC - 5 min Bending radius, min. Temperature of laying Temperature of exploitation According to BDS 904 (IEC 60228) class 2 90 continuous operation 130 250 /5 s max/ 0.6/1 kV 3 V 0.6/1 V 1.2 kV Between core and screen 3.5kV 15x D cable no less than -5

Insulation Metal screen Sheath Color

-30 to 50 l cores - 30*n*S core Force of strain in laying N n- number of cores and S- cross section of cores in Max. mm

Construction data SAHEm-et 0.6/1 kV


Number of conductors and nominal cross section N mm2 Uo/U 0.6/1kV U(=) 3kV 195 1120 1150 1185 1x240 1x300 1x400 1x500 Thickness of insulation mm

U(=) 3 kV SAHEm-et
Mass of Al approx. kg/km Cable weight approx. kg/km

Nominal cross Thickness of Cable diamsection of eter sheath screen approx. min. mm2 mm mm

2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0

25 25 25 25 25 25 25 25

2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0

22.9 24.3 25.8 27.5 29.9 34.2 39.9 37.0

260 325 405 510 665 830 1060 1410

735 1255 943 1084 1287 1628 1920 2323

ELKABEL

313

MIDDLE VOLTAGE POWER CABLES

SHEkT SAHEkT

Uo/U - 3.6/6; 6/10; 12/20; 18/30; 20/35 kV BDS 2581-86

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 6/10; 12/20; 18/30; 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen According to BDS 2581-86 u and Al stranded compacted, according to BDS 904 ( IEC60228 ) class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. Layer of plastic tape PVC compound type P-5 red

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max/ 3.6/6;6/10;12/20;18/30;20/35kV 3.6/6; 6/10; 12/20; 18/30;20/35kV 7.2kV;12kV; 24kV; 36kV; 42kV 3.6/6; 6/10; 12/20; 18/30;20/35kV 11kV; 15kV; 30kV; 45kV; 50kV 29kV; 48kV; 96kV; 144kV; 160kV max. 5 pC 15x D cable no less than -5

Separating layer Sheath Color

-30 to 50 Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

Construction data SHEkT, SAHEkT 3.6/6; 6/10; 12/20; 18/30; 20/35 kV


Cable Nominal Number of con- Thickness Thickness cross-sec- diameter ductors and nomof of approx. tion of inal cross section insulation sheath screen N mm2 mm mm mm2 mm SHEkT Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAHEkT Mass of Cu approx. kg/km Mass of cable approx. kg/km

Uo/U 3.6/6kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16* 1x185rm/16* 1x240rm/16*

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

16 16 16 16 16 16* 16* 16*

21.5 22.5 24.5 26 27.5 29 30.5 33.0

490 600 790 1030 1255 1505 1840 2365

805 940 1170 1445 1695 1995 2365 2970

95 130 190 260 330 405 510 665

176 176 176 176 176 176 176 176

580 640 735 840 940 1060 1200 1430

314

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PVC sheath Construction data SHEkT, SAHEkT 3.6/6; 6/10; 12/20; 18/30; 20/35 kV
Cable Nominal Number of con- Thickness Thickness cross-sec- diameter of ductors and nom- of insulaapprox. tion sheath tion of inal cross section screen N mm2 mm mm mm2 mm SHEkT Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAHEkT

MIDDLE VOLTAGE POWER CABLES

Mass of Cu approx. kg/km

Mass of cable approx. kg/km

1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 6/10kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16* 1x185rm/16* 1x240rm/16* 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 12/20kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16* 1x185rm/16* 1x240rm/16* 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 18/30kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 20/35kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16* 1x185rm/16* 1x240rm/16* 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

2.5 2.5 2.6 2.8 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.7 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.7

25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16* 16* 16* 25 25 25 25 35 35

29.5 31 33.5 36.0 39.5 43.0 23 24 26 27 29 30 32 34 30.5 32.5 34.5 37 40 43 27 28 30 32 33.5 35 37 39.5 35.5 37.5 40 42 45 48 35 36 37 39 40 42 44 40.5 42.5 44.5 47 50.5 54 35.5 37 39 41 41.5 43.5 46 42 44 46.5 48.5 52 55.5

1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805

2080 2455 3055 3670 4635 5750 930 1075 1310 1590 1855 2150 2530 3120 2240 2620 3210 3800 4730 5740 1115 1260 1510 1805 1995 2385 2775 3370 2465 2860 3465 4070 5025 6125 1505 1765 2078 2358 1515 1845 2355 1595 1930 2450 2980 3835 4805 1515 1775 2100 2400 2720 3140 3775 2800 3225 3870 4500 5500 6660

405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 130 190 260 330 405 510 665 405 510 665 830 1060 1410 130 190 260 330 405 510 665 405 510 665 830 1060 1410

265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 265 265 265 265 363 363

1145 1285 1515 1770 2205 2610 700 770 875 990 1100 1210 1360 1580 1300 1450 1670 1890 2300 2650 870 940 1070 1190 1230 1440 1600 1840 1530 1690 1920 2150 2580 2970 1205 1330 1475 1600 1740 1905 2150 1820 1990 2245 2520 2995 3415 1215 1340 1500 1640 1785 1970 2240 1865 2055 2335 2595 3070 3520

ELKABEL

315

MIDDLE VOLTAGE POWER CABLES

SHEk(vn)P SAHEk(vn)P

Uo/U-3.6/6; 6/10; 12 /20; 18/30; 20/35 kV BDS 2581-86 and additional 4

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 6/10; 12/20; 18/30; 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Water resisting element Metal screen According to BDS 2581-86 and additional N 4 u and Al stranded compacted, according to BDS 904 (IEC60228) class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. -I option - water absorbing insulating tape -II option - water absorbing powder and a layer of plastic tape PE type MDPE Black

Technical data
Conductor resistance at 20C According to BDS904 (IEC60228) class 2

Water resisting element Sheath Color

Operating temperature 90 continuous operation Overload temperature 130 /100h per year max./ Short circuit temperature 250 /5 s max/ 3.6/6;6/10;12/20;18/30;20/35kV Nominal voltage Uo/U: Highest system voltage 3.6/6; 6/10; 12/20; 18/30;20/35kV Uo/U, no more than 7.2kV;12kV; 24kV; 36kV; 42kV Test voltage Uo/U 3.6/6; 6/10; 12/20; 18/30;20/35kV AC () - 5 min 11kV; 15kV; 30kV; 45kV; 50kV DC (=) - 15 min 29kV; 48kV; 96kV; 144kV; 160kV Level of partial discharge at 2*Uo max. 5 pC Bending radius, min 15x D cable Temperature of laying no less than -5 Temperature of exploitation -30 to 50 Al cores - 30*n*S core Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where: -S-cross-section of conductors in mm

Construction data SHEk(vn)P, SAHEk(vn)P 3.6/6; 6/10; 12/20; 18/30; 20/35 kV


Cable Nominal Number of con- Thickness Thickness cross-sec- diameter ductors and nom- of insulation of approx. tion of inal cross section sheath screen N mm2 mm mm mm2 mm SHEk(vn)P Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAHEk(vn)P Mass of Cu approx. kg/km Mass of cable approx. kg/km

Uo/U 3.6/6kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

16 16 16 16 16 16* 16* 16* 25 25 25

22 23 25 26.5 28 29.5 31.5 33.5 30 32 34

490 600 790 1030 1255 1505 1840 2365 1595 1930 2450

795 930 1155 1430 1690 1980 2360 2950 2060 2440 3040

95 130 190 260 330 405 510 665 405 510 665

176 176 176 176 176 176 176 176 265 265 265

570 625 720 825 935 1040 1190 1415 1120 1270 1500

316

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath Construction data SHEk(vn)P, SAHEk(vn)P 3.6/6; 6/10; 12/20; 18/30; 20/35 kV
Cable Nominal Number of con- Thickness Thickness cross-sec- diameter of ductors and nom- of insulation sheath approx. tion of inal cross section screen N mm2 mm mm mm2 mm SHEk(vn)P Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAHEk(vn)P Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 6/10kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 12/20kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 18/30kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 20/35kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

2.5 2.5 2.6 2.8 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8

25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35 16 16 16 16 16* 16* 16* 25 25 25 25 35 35

30 32 34 37 41 45 24 25 27 29 31 32 34 36 32 34 36 38.5 42 45 28 29 31 33 34 36 37.5 40 36 38 40.5 42.5 46 49 35.5 36.5 37.5 39.5 41 43 45 48 51.5 55 36.5 38 40 42 43 44 47 43.5 45 47.5 50 53.5 56.5

1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805

2060 2440 3040 3650 4610 5990 905 1045 1275 1560 1820 2115 2490 3080 2200 2570 3160 3750 4680 5720 1080 1225 1470 1760 1950 2340 2730 3400 2420 2810 3400 4010 4950 6050 1460 1720 2030 2305 2705 3105 3725 4360 5345 6480 1480 1750 2065 2355 2690 3080 3720 2770 3175 3815 4450 3830 4800

405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 130 190 260 330 405 510 665 830 1060 1410 130 190 260 330 405 510 665 405 510 665 830 1060 1410

265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 265 265 265 265 363 363

1120 1270 1500 1745 2180 2560 670 745 845 950 1060 1180 1325 1540 1260 1405 1625 1850 2250 2600 855 925 1040 1165 1195 1400 1560 1875 1500 1640 1875 2110 2535 2920 1160 1285 1425 1550 1770 1935 2185 2455 2915 3340 1185 1320 1460 1600 1750 1915 2175 1830 2000 2270 2250 3010 3430

ELKABEL

SHEk(v)P SAHEk(v)P
MIDDLE VOLTAGE POWER CABLES

Uo/U - 6/10; 12/20 kV BDS 2581-86 and additional 4

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductiv.layer Water resisting element Metal screen Water resisting element Radial protection from Sheath Color According to BDS 2581-86 and additional N 4 u and Al stranded compacted, according to BDS 904 (IEC60228) class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. - water absorbing powder Al foil with copolymer moisture ingress layer PE type MDPE Black

Technical data
Conductor resistance at According to BDS904 20C (IEC60228) class 2 Operating temperature 90 continuous operation Overload temperature 130 /100h per year max./ Short circuit temperature 250 /5 s max./ 6/10;12/20 kV Nominal voltage Uo/U: Highest system voltage 6/10; 12/20 kV Uo/U, no more than 12kV; 24kV kV Test voltage Uo/U 6/10; 12/20 kV AC () - 5 min 15kV; 30kV kV DC (=) - 15 min 48kV; 96kV kV Level of partial discharge at 2*Uo max. 5 pC Bending radius, min 15x D cable Temperature of laying Temperature of exploitation Force of strain in laying N max where: Tests - water penetration in the region of metallic screen no less than - 20 -30 to 50 Al cores - 30*n*S core Cu cores - 50*n*S core N is number of cores and S is cross section of cores in mm IEC 60502-2 annex D

Construction data SHEk(v)P, SAHEk(v)P 3.6/6; 6/10; 12/20; 18/30; 20/35 kV


Nominal Number of con- Thickness Thickness cross-sec- Cable diameter ductors and nom- of insulaof tion of approx. inal cross section tion sheath screen N mm2 mm mm mm2 mm SHEk(v)P Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx.. kg/km SAHEk(v)P Mass of Cu approx. kg/km Mass of cable approx. kg/km

Uo/U 3.6/6kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

16 16 16 16 16 16* 16* 16*

22 23 25 26.5 28 29.5 31.5 33.5

490 600 790 1030 1255 1505 1840 2365

795 930 1155 1430 1690 1980 2360 2950

95 130 190 260 330 405 510 665

176 176 176 176 176 176 176 176

570 625 720 825 935 1040 1190 1415

318

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath Construction data SHEk(v)P, SAHEk(v)P 3.6/6; 6/10; 12/20; 18/30; 20/35 kV
Cable Nominal Number of con- Thickness Thickness cross-sec- diameter ductors and nom- of insulation of approx. tion of inal cross section sheath screen N mm2 mm mm mm2 mm SHEk(v)P Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAHEk(v)P Mass of Cu approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 6/10kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 12/20kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 18/30kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 20/35kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

2.5 2.5 2.6 2.8 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8

25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35 16 16 16 16 16* 16* 16* 25 25 25 25 35 35

30 32 34 37 41 45 24 25 27 29 31 32 34 36 32 34 36 38.5 42 45 28 29 31 33 34 36 37.5 40 36 38 40.5 42.5 46 49 35.5 36.5 37.5 39.5 41 43 45 48 51.5 55 36.5 38 40 42 43 44 47 43.5 45 47.5 50 53.5 56.5

1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805

2060 2440 3040 3650 4610 5990 905 1045 1275 1560 1820 2115 2490 3080 2200 2570 3160 3750 4680 5720 1080 1225 1470 1760 1950 2340 2730 3400 2420 2810 3400 4010 4950 6050 1460 1720 2030 2305 2705 3105 3725 4360 5345 6480 1480 1750 2065 2355 2690 3080 3720 2770 3175 3815 4450 3830 4800

405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 130 190 260 330 405 510 665 830 1060 1410 130 190 260 330 405 510 665 405 510 665 830 1060 1410

265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 265 265 265 265 363 363

1120 1270 1500 1745 2180 2560 670 745 845 950 1060 1180 1325 1540 1260 1405 1625 1850 2250 2600 855 925 1040 1165 1195 1400 1560 1875 1500 1640 1875 2110 2535 2920 1160 1285 1425 1550 1770 1935 2185 2455 2915 3340 1185 1320 1460 1600 1750 1915 2175 1830 2000 2270 2250 3010 3430

ELKABEL

319

SvHEk(v)P SAvHEk(v)P
MIDDLE VOLTAGE POWER CABLES

Uo/U - 6/10; 12/20 kV BDS 2581-86 and additional 4

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Water resisting element Inner semiconductive layer Insulation Outer semiconductiv.layer Water resisting element Metal screen Water resisting element Radial protection from moisture ingress Sheath Color According to BDS 2581-86 and additional N 4 u and Al stranded compacted, according to BDS 904 (IEC60228) class 2 with water powder absorbing semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. - water absorbing powder Al foil with copolymer layer PE type MDPE Black

Technical data
Conductor resistance at According to BDS904 20C (IEC60228) class 2 Operating temperature 90 continuous operation Overload temperature 130 /100h per year max./ Short circuit temperature 250 /5 s max./ Nominal voltage Uo/U: 6/10;12/20 kV Highest system voltage 6/10; 12/20 kV Uo/U, no more than 12kV; 24kV kV Test voltage Uo/U 6/10; 12/20 kV AC () - 5 min 15kV; 30kV kV DC (=) - 15 min 48kV; 96kV kV Level of partial discharge at 2*Uo max. 5 pC Bending radius, min 15x D cable Temperature of laying Temperature of exploitation Force of strain in laying N max where: Tests - water penetration in the region of metallic screen no less than - 20 -30 to 50 Al cores - 30*n*S core Cu cores - 50*n*S core N is number of cores and S is cross section of cores in mm IEC 60502-2 annex D

Construction data SvHEk(v)P, SAvHEk(v)P 3.6/6; 6/10; 12/20; 18/30; 20/35 kV


Nominal Number of con- Thickness Thickness cross-sec- Cable diameter ductors and nom- of insulaof tion of approx. inal cross section tion sheath screen N mm2 mm mm mm2 mm SvHEk(v)P Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAvHEk(v)P Mass of Cu approx. kg/km Mass of cable approx. kg/km

Uo/U 3.6/6kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

16 16 16 16 16 16* 16* 16*

22 23 25 26.5 28 29.5 31.5 33.5

490 600 790 1030 1255 1505 1840 2365

795 930 1155 1430 1690 1980 2360 2950

95 130 190 260 330 405 510 665

176 176 176 176 176 176 176 176

570 625 720 825 935 1040 1190 1415

320

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

Construction data SvHEk(v)P, SAvHEk(v)P


Nominal Number of con- Thickness Thickness cross-sec- Cable ductors and nom- of insulaof diameter tion of inal cross section tion sheath approx. screen N mm2 mm mm mm2 mm

3.6/6; 6/10; 12/20; 18/30; 20/35 kV


SvHEk(v)P SAvHEk(v)P Mass of Al approx. kg/km Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of cable approx. kg/km

MIDDLE VOLTAGE POWER CABLES

Mass of Cu approx. kg/km

1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 6/10kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 12/20kV 1x35rm/16 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 18/30kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35 Uo/U 20/35kV 1x50rm/16 1x70rm/16 1x95rm/16 1x120rm/16 1x150rm/16 1x185rm/16 1x240rm/16 1x150rm/25 1x185rm/25 1x240rm/25 1x300rm/25 1x400rm/35 1x500rm/35

2.5 2.5 2.6 2.8 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8

25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 16 16* 16* 16* 25 25 25 25 35 35 16 16 16 16 25 25 25 25 35 35 16 16 16 16 16* 16* 16* 25 25 25 25 35 35

30 32 34 37 41 45 24 25 27 29 31 32 34 36 32 34 36 38.5 42 45 28 29 31 33 34 36 37.5 40 36 38 40.5 42.5 46 49 35.5 36.5 37.5 39.5 41 43 45 48 51.5 55 36.5 38 40 42 43 44 47 43.5 45 47.5 50 53.5 56.5

1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 490 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1595 1930 2450 2980 3835 4805 600 790 1030 1255 1505 1840 2365 1595 1930 2450 2980 3835 4805

2060 2440 3040 3650 4610 5990 905 1045 1275 1560 1820 2115 2490 3080 2200 2570 3160 3750 4680 5720 1080 1225 1470 1760 1950 2340 2730 3400 2420 2810 3400 4010 4950 6050 1460 1720 2030 2305 2705 3105 3725 4360 5345 6480 1480 1750 2065 2355 2690 3080 3720 2770 3175 3815 4450 3830 4800

405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 95 130 190 260 330 405 510 665 405 510 665 830 1060 1410 130 190 260 330 405 510 665 830 1060 1410 130 190 260 330 405 510 665 405 510 665 830 1060 1410

265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 176 265 265 265 265 363 363 176 176 176 176 265 265 265 265 363 363 176 176 176 176 176 176 176 265 265 265 265 363 363

1120 1270 1500 1745 2180 2560 670 745 845 950 1060 1180 1325 1540 1260 1405 1625 1850 2250 2600 855 925 1040 1165 1195 1400 1560 1875 1500 1640 1875 2110 2535 2920 1160 1285 1425 1550 1770 1935 2185 2455 2915 3340 1185 1320 1460 1600 1750 1915 2175 1830 2000 2270 2250 3010 3430

ELKABEL

321

SHEa(v)P SAHEa(v)P
MIDDLE VOLTAGE POWER CABLES

Uo/U - 6/10; 12/20 kV BDS 2581-86 and additional 4

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to BDS 2581-86 and additional N 4 u and Al stranded compacted, according to BDS 904 (IEC60228) class 2 semi-conductive XLPE compound XLPE compound semi-conductive XLPE compound Layer of semi-conductive water absorbing tapes Al foil with copolymer layer section Al foil - 25mm2 equivalency Cu - 16mm2 PE type MDPE Black where:

Technical data
Conductor resistance at 20C Operating temperature Overload temperature Short circuit temperature Nominal voltage Uo/U: Highest system voltage Uo/U, no more than Test voltage Uo/U AC () - 5 min DC (=) - 15 min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Force of strain in laying N max According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max./ 6/10;12/20 kV 6/10; 12/20 kV 12kV; 24kV kV 6/10; 12/20 kV 15kV; 30kV kV 48kV; 96kV kV max. 5 pC 15x D cable no less than - 20 -30 to 50 Al cores - 30*n*S core Cu cores - 50*n*S core N is number of cores and S is cross section of cores in mm

Inner semiconductive layer Insulation Outer semiconductiv.layer Water resisting element Metal screen and Radial protection from moisture ingress Sheath Color

Tests - water penetration in the region of metallic screen

IEC 60502-2 annex D

322

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PE sheath

MIDDLE VOLTAGE POWER CABLES

Construction data SHEa(v)P, SAHEa(v)P 6/10 and 12/20 kV


Cable Number of con- Thickness Thickness Nominal diameter of ductors and nom- of insula- sheath cross-sec- approx. tion tion of inal cross section screen N mm2 mm mm mm2 mm SAHEa(v)P Mass of Al approx. kg/km Mass of cable approx. kg/km Mass of Cu approx. kg/km SHEa(v)P Mass of Al approx. kg/km Mass of cable approx. kg/km

Uo/U 6/10kV 1x185rm/25 Uo/U 12/20kV 1x95rm/25 1x120rrm/25 1x150rm/25 1x185rm/25 5.5 5.5 5.5 5.5 2.5 2.5 2.5 2.5 25(Cu16) 25(Cu16) 25(Cu16) 25(Cu16) 32 33.5 35 37 334 404 479 586 989 1064 1224 1384 854 1079 1329 1664 74 74 74 76 1584 1774 2164 2554 3.4 2.5 25(Cu16) 33 584 1150 1664 74 2315

ELKABEL

323

S H E m e T Uo/U - 3.6/6; 6/10; 12/20;18/30; 20/35 kV BDS 2581-86 SAHEmeT


MIDDLE VOLTAGE POWER CABLES - THREE CORE

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 6/10; 12/20; 18/30; 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor Inner semiconductive layer Insulation Outer semiconductive layer Metal screen According to BDS 2581-86 u and Al stranded compacted, according to BDS 904 (IEC60228) class 2 semi-conductive XLPE compound

Technical data
Conductor resistance at 20C Operating temperature Overload temperature According to BDS904 (IEC60228) class 2 90 continuous operation 130 /100h per year max./ 250 /5 s max/ 3.6/6;6/10;12/20;18/30;20/35kV

XLPE compound Short circuit temperature semi-conductive XLPE compound Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase Three insulated and screenesd phases are twisted with fillings and tape support PVC compound PVC compound type P-5 according to IBDS 2581 red Nominal voltage Uo/U:

Highest system voltage 3.6/6; 6/10; 12/20; 18/30;20/35kV Uo/U, no more than 7.2kV;12kV; 24kV; 36kV; 42kV Test voltage Uo/U 3.6/6; 6/10; 12/20; 18/30;20/35kV AC () - 5 min 11kV; 15kV; 30kV; 45kV; 50kV DC (=) - 15 29kV; 48kV; 96kV; 144kV; 160kV min Level of partial discharge at 2*Uo Bending radius, min Temperature of laying Temperature of exploitation Tests max. 5 pC 15x D cable no less than -5

Cable assembly

Inner sheatth Sheath Color

-30 to 50 according to BDS 2581 Al cores - 30*n*S core

Force of strain in laying N Cu cores - 50*n*S core max. n- number of cores and where:

-S-cross-section of conductors in mm

324

ELKABEL

Cu / Al conductors XLPE insulation Cu screen PVC sheath

MIDDLE VOLTAGE POWER CABLES - THREE CORE

Construction data SHEmeT, SAHEmeT 3.6/6; 6/10; 12/20; 18/30; 20/35 kV


Nominal Number of con- Thickness Thickness cross-sec- Cable ductors and nom- of insulaof diameter tion of inal cross section tion sheath approx. screen N mm2 mm mm mm2 mm SHEmeT Mass of Cu approx. kg/km Mass of cable approx. kg/km Mass of Al approx. kg/km SAHEmeT Mass of Cu approx. kg/km Mass of cable approx. kg/km

Uo/U 3.6/6kV 3x35rm/16 3x50rm/16 3x70rm/16 3x95rm/16 3x120rm/16 3x150rm/16 3x185rm/16 3x240rm/16 3x150rm/25 3x185rm/25 3x240rm/25 Uo/U 6/10kV 3x35rm/16 3x50rm/16 3x70rm/16 3x95rm/16 3x120rm/16 3x150rm/16 3x185rm/16 3x240rm/16 3x150rm/25 3x185rm/25 3x240rm/25 Uo/U 12/20kV 3x35rm/16 3x50rm/16 3x70rm/16 3x95rm/16 3x120rm/16 3x150rm/16 3x185rm/16 3x240rm/16 3x150rm/25 3x185rm/25 3x240rm/25 Uo/U 18/30kV 3x50rm/16 3x70rm/16 3x95rm/16 3x120rm/16 3x150rm/25 Uo/U 20/35kV 3x50rm/16 3x70rm/16 3x95rm/16 3x120rm/16 3x150rm/25

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 8.0 8.0 8.8 8.8 8.8 8.8 8.8

2.5 2.5 2.5 2.7 2.8 2.9 3.0 3.2 2.9 3.0 3.2 2.5 2.5 2.6 2.8 2.9 3.0 3.1 3.3 3.0 3.2 3.4 2.8 2.9 3.0 3.1 3.2 3.4 3.5 3.7 3.4 3.5 3.7 3.3 3.4 3.5 3.7 3.8 3.4 3.5 3.7 3.8 3.9

16 16 16 16 16 16 16 16 25 25 25 16 16 16 16 16 16 16 16 25 25 25 16 16 16 16 16 16 16 16 25 25 25 16 16 16 16 25 16 16 16 16 25

42 44 48 52 55 58.5 62.5 68 59 63 68.5 45 47.5 52.5 56.0 59 62 65 72 62.5 65.5 73 55.5 57.5 62 66 68 72 76 82 73 77 83 70 74 78 82 86 74 78 82 86 89

1155 1565 2125 2825 3525 4360 5335 6895 4450 5425 6985 1155 1565 2125 2825 3525 4360 5335 6895 4450 5425 6985 1155 1565 2125 2825 3525 4360 5335 6895 4450 5425 6985 1565 2125 2825 3525 4450 1565 2125 2825 3525 4450

2605 3075 3900 4910 5785 6860 8180 10235 6940 8265 10330 2905 3405 4275 5305 6195 7295 8655 10730 7380 8740 10815 3790 4345 5245 6330 7275 8475 9875 12065 8565 9965 12155 5625 6610 7790 8815 10185 6075 7080 8280 9345 10720

295 405 585 810 1020 1255 1560 2055 1255 1560 2055 295 405 585 810 1020 1255 1560 2055 1255 1560 2055 295 405 585 810 1020 1255 1560 2055 1255 1560 2055 405 585 810 1020 1255 405 585 810 1020 1255

176 176 176 176 176 176 176 176 265 265 265 176 176 176 176 176 176 176 176 265 265 265 176 176 176 176 176 176 176 176 265 265 265 176 176 176 176 265 176 176 176 176 265

1930 2165 2590 3085 3485 4025 4635 5570 4105 4720 5665 2230 2495 2965 3480 3895 5105 6060 5105 5195 6150 7135 3115 3430 3930 4500 4975 5635 6330 7400 5725 6420 7490 4710 5295 5960 6520 7345 5165 5765 6455 7050 7885

ELKABEL

325

SVBT SAVBT
MIDDLE VOLTAGE POWER CABLES

Uo/U - 3.6/6 kV BDS 16291-85

Application
The three-core cables with insulation of polyvinylchloride (PVC) are designed for distribution of electrical power and for electrical supply of consumers with nominal voltage Uo/U 3.6/6 kV and frequency 50 Hz. They are suitable for distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, for indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Cable construction
Construction Conductor According to BDS 16291-85 u and Al stranded compacted, according to BDS 904 (IEC60228) class 2 PVC compound Three insulated phases are twisted with fillings and tape support Polymer material Two steel tapes PVC compound type P-1 gray

Technical data
Conductor resistance at According to 20C BDS904 (IEC60228) class 2 Operating temperature 70 continuous operation Short circuit temperature 160 /5 s max/ Nominal voltage Uo/U: 3.6/6kV Highest system voltage, 7.2kV no more than Test voltage AC () - 5 min 11kV DC (=) - 15 min 29kV Bending radius, min Temperature of laying Temperature of exploitation Force of strain in laying N max. where: 15x D cable no less than -5 -30 to 50 Al cores - 30*n*Score Cu cores - 50*n*S core n-number of cores and S-cross section of cores in mm

Insulation Cable assembly Inner sheath Armour-screen Sheath Color

Construction data SVBT, SAVBT


Number of conductors and Thickness of nominal cross insulation section N mm2 mm Armour Cable diameter section approx. equivalent to copper mm2 mm SVBT Mass of Cu approx. kg/km

3.6/6 kV
SAVBT Mass of Al approx. kg/km Mass of cable approx. kg/km

Mass of cable approx. kg/km

Uo/U 3.6/6kV 3x25rm/6 3x35rm/6 3x50sm/6 3x70sm/6 3x95sm/6 3x120sm/6 3x150sm/6 3x185sm/6 3x240sm/6

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

6 6 6 6 6 6 6 6 6

37.7 40.0 43.2 42.6 45.6 48.6 51.6 55.1 60.0

700 680 1390 1950 2650 3350 4185 5160 6720

2685 3155 3600 4170 5080 5980 6920 8175 10110

210 290 385 585 810 1020 1255 1560 2035

2150 2535 2700 2945 3380 3818 4250 4830 5660

326

ELKABEL

SVVn/A
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames.

Cable construction
Construction Conductor According to FN KI 02.001-96 Copper solid or twisted, class 1 or class2, according to BDS 904-84 (IEC 60228) PVC compound, according to BDS 5792-84 Filling, flame retardant PVC flame retardant, degree of flame retardancy category A black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Test voltage alternating or direct Temperature range laying and installing exploitation and storage Operating temperature

Insulation

4kV 12kV -5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category 10 D cable

Inner sheath Sheath

Color

Type codes
SVpower cable PVC insulation power cable PVC insulation sheath of PVC flame retardant Short circuit temperature for no more than 5 sec. Flame retardancy Bending radius, min

Vn- sheath of PVC flame retardant

Color coding
Number of cond. 1 2 3 4 Color of conductors without yellow/green random color brown, blue brown , black, blue, grey blue, brown, black, grey Neutral conductor - blue Color of conductors with yellow/green yellow/green, blue, brown yellow/green, brown, black, grey

328

ELKABEL

Cu conductors PVC insulation PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SVVn/ 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 1 1.5 1 2.5 1 4.0 1 6.0 1 10 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 1.5 2 2.5 2 4.0 2 6.0 2 10 2 16 2 16 2 25 2 35 2 50 2 70 2 95 3 1.5 3 2.5 3 4.0 3 6.0 3 10 3 16 3 16 3 25 3 35 3 50 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 2.5+1.5 3 4.0+2.5 3 6.0+4.0 3 10+6.0 3 16+10 3 25+16 3 25+16 3 35+16 3 35+16 3 35+16 3 50+25 3 70+35 3 95+50 3 120+70 3 150+70 3 185+95 3 240+120 3 300+150 4 1.5 4 2.5 4 4.0 re re re re re re rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re rm rm rm rm rm rm re re re re re re rm rm rm rm sm sm sm sm sm sm sm re/re re/re re/re re/re re/re rm/re rm/rm rm/re rm/rm sm/re rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm re re re mm 8.0 8.6 9.5 10.0 11.7 12.6 14.7 15.8 17.4 19.1 21.3 22.8 24.7 26.9 30.0 30.7 34.1 38.1 12.1 12.9 14.8 15.8 17.5 19.3 20.2 23.5 25.7 29.1 33.1 37.9 12.1 12.9 15.0 16.1 18.1 20.1 20.9 24.3 26.7 30.4 32.2 31.2 35.8 38.0 42.0 46.0 51.4 14.5 15.6 17.0 18.8 21.0 25.4 25.6 27.7 27.7 28.0 32.2 36.0 40.1 43.2 48.0 52.3 58.7 64.3 12.9 13.8 16.2 Mass of Cu kg/km 14 23 37 55 93 148 229 325 458 648 885 1120 1378 1703 2208 2765 3680 4600 28 46 73 110 182 303 303 470 652 928 1288 1748 42 69 110 165 275 450 450 700 980 1390 1400 1950 2650 3350 4185 5160 6720 82 132 202 330 540 850 850 1130 1131 1141 1630 2280 3120 4010 4850 6070 7840 9928 55 92 146 Mass of cable approx kg/km 74 89 135 164 214 285 425 535 692 920 1225 1485 1793 2200 2830 3485 4390 5478 210 248 340 410 525 714 720 1085 1310 1720 2330 3130 230 290 384 473 642 873 920 1352 1738 2335 2350 2625 3585 4345 5300 6590 8500 316 435 550 738 1008 1569 1570 1975 1976 1986 2595 3155 4195 5180 6420 7771 9990 12466 270 329 455

Construction data SVVn/ 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 4 6.0 4 10 4 16 4 16 4 25 4 35 4 50 4 70 4 95 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 4 300 re re re rm rm rm rm rm rm sm sm sm sm sm sm sm sm sm mm 17.4 19.5 21.8 23.0 27.2 30.1 34.8 39.1 45.3 28.0 31.2 36.0 40.2 43.3 48.2 53.8 58.8 64.4 Mass of Cu kg/km 218 363 582 588 925 1303 1857 2592 3540 1303 1857 2601 3540 4460 5575 6880 8928 11060 Mass of cable approx kg/km 569 782 1162 1198 1690 2190 2978 3937 5317 2980 3940 3490 4660 5680 7035 8895 11255 13722

ELKABEL

329

SVVn/A
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001-96

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames.

Cable construction
Construction Conductor According to FN KI 02.001-96 Copper solid or twisted, class 1 or 2, according to BDS 904-84 (IEC 60228) PVC insulation according to BDS 5792-84 filling, flame retardant PVC flame retardant, degree of flame retardant category A black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Insulation Test voltage alternating Inner sheath Sheath or direct Temperature range laying and installing exploitation and storage Operating temperature

4kV 12kV -5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category 10 D cable

Color

Type codes
SVVnpower cable PVC insulation sheath of PVC flame retardant Short circuit temperature for no more than 5 sec. Flame retardancy Bending radius, min

Color coding
Number of cond. Color of conductors without yellow/green Color of conductors with yellow/green

blue, brown, black, grey, black

yellow/green, blue, brown, black,grey yellow/green and the other black with number marking

6 and over 6

black with number marking

330

ELKABEL

Cu conductors PVC insulation PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SVVn/ 0.6/1 kV


Number of cond. and nominal cross section N mm2 5 1.5 5 2.5 5 4.0 5 6.0 5 10 5 16 5 16 5 25 5 35 5 50 5 70 5 95 6 1.5 6 2.5 6 4.0 6 6.0 6 10 7 1.5 7 2.5 7 4.0 8 1.5 8 2.5 8 4.0 10 1.5 10 2.5 10 4.0 12 1.5 12 2.5 12 4.0 14 1.5 14 2.5 14 4.0 16 1.5 16 2.5 19 1.5 19 2.5 20 1.5 20 2.5 21 1.5 21 2.5 24 1.5 24 2.5 25 1.5 25 2.5 27 1.5 27 2.5 30 1.5 30 2.5 37 1.5 37 2.5 re re re re re re rm rm rm rm rm rm re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re Form of conductor Cable diameter approx. mm 13.9 14.8 17.6 19.1 21.7 24.2 25.2 30.2 33.6 38.2 43.4 50.2 15.5 16.6 20.2 21.1 23.5 14.8 16.6 19.5 16.1 17.4 21.5 18.6 19.8 23.9 18.4 19.8 24.6 19.2 20.8 25.8 19.9 21.8 21.2 22.9 22.1 24.1 21.2 24.2 24.5 26.4 24.6 26.5 24.6 26.8 25.5 27.8 27.2 30.2 Mass of Cu kg/km 69 114 182 275 455 745 745 1165 1640 2330 3260 4430 84 138 222 330 558 96 160 255 110 182 296 140 228 365 165 275 444 195 320 518 220 365 260 435 280 460 294 483 330 546 350 575 378 621 410 685 506 845 Mass of cable approx kg/km 305 380 540 680 939 1318 1328 2090 2740 3670 4875 6550 356 446 642 805 1122 345 435 671 399 502 845 462 588 991 510 660 1086 567 740 1207 631 827 706 938 775 1025 799 1060 862 1155 905 1188 1110 1347 1118 1375 1205 1655

ELKABEL

331

SVVn/C
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001-2006

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames.

Cable construction
Construction Conductor According to FN KI 02.001-96 Copper solid or twisted, class 1 or class2, according to BDS 904-84 (IEC 60228) PVC compound, according to BDS 5792-84 PVC flame retardant, degree of flame retardancy category C black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Test voltage alternating

Insulation Sheath Color

4kV 12kV

or direct Temperature range laying and installing exploitation and storage Operating temperature

-5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category C 10 D cable

Type codes
SVVnpower cable PVC insulation sheath of PVC flame retardant Short circuit temperature for no more than 5 sec. Flame retardancy Bending radius, min

Color coding
Number of cond. 1 2 3 4 Neutral conductor - blue Color of conductors without yellow/green random color light blue; brown brown, black, grey blue, brown, black, grey Color of conductors with yellow/green yellow/green, blue, brown yellow/green, brown, black, grey

332

ELKABEL

Cu conductors PVC insulation PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SVVn/C 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 1 1.5 1 2.5 14 16 1 10 1 16 1 16 1 25 1 35 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 1.0 2 1.5 2 2.5 24 26 2 10 2 16 2 25 2 35 2 50 3 1.0 3 1.5 3 2.5 34 36 3 10 3 16 3 25 3 35 re re re re re re m rm rm rm rm rm rm rm rm rm rm rm rm re re re re re re re rm rm rm re re re re re re re rm rm mm 7.2 7.6 8.0 8.5 9.3 10.8 10.8 11.9 13.0 14.2 16.7 18.4 19.9 21.9 24.3 27.2 30.3 33.8 37.9 9.3 10.0 10.6 12.1 13.2 15.2 17.8 21.5 23.8 27.0 9.6 10.2 11.0 12.8 14.0 16.0 18.9 22.8 25.3 Mass of Cu kg/km 14 23 37 55 93 148 148 229 325 458 648 885 1120 1378 1703 2208 2765 3680 4600 20 28 46 75 110 182 303 470 652 928 28 42 69 110 165 275 450 700 980 Mass of cable approx kg/km 69 82 102 125 178 253 253 350 462 598 810 1100 1385 1610 2020 2565 3200 4035 5180 100 120 150 210 260 370 558 810 1057 1408 119 122 154 260 349 480 682 1078 1298

Construction data SVVn/C 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 2.5 + 1.5 3 4,0 + 2.5 3 6,0 + 4,0 3 10 + 6 3 16 + 10 3 25 + 16 3 35 + 16 3 50 + 25 3 70 + 35 3 95 + 50 3 120 + 70 3 150 + 70 3 185 + 95 3 240 + 120 4 1.0 4 1.5 4 2.5 44 46 4 10 4 16 4 25 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 rm sm sm sm sm sm sm re+re re+re re+re re+re re+re rm+re rm+re rm+rm sm+rm sm+rm sm+rm sm+rm sm+rm sm+rm re re re re re re re rm rm rm sm sm sm sm sm sm mm 28.9 28.8 33.1 35.9 39.3 43.4 48.9 11.2 13.4 14.4 16.7 19.5 24.4 27.1 30.8 31.8 36.8 40.1 44.3 49.3 55.4 10.4 11.0 11.9 13.6 14.4 16.8 19.2 25.2 28.0 32.0 33.0 37.3 41.2 45.2 49.5 56.4 Mass of Cu kg/km 1390 1950 2650 3350 4185 5160 6720 82 132 202 330 540 850 1130 1630 2280 3120 4010 4850 6070 7840 37 55 92 146 218 363 582 925 1303 1857 2601 3540 4460 5575 6880 8928 Mass of cable approx kg/km 1895 2400 3225 4010 4830 6035 7818 203 293 380 545 870 1245 1590 2175 2785 3680 4730 5620 7090 9150 140 165 216 317 408 593 951 1285 1778 2307 3101 4250 5210 6385 7960 10310

ELKABEL

333

SAVVn/
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001-96

Application
These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames

Cable construction
Construction Conductor According to FN KI 02.001-96 Aluminum solid or twisted cores, class 1 or class 2, according to BDS 904-84 PVC insulation, according to BDS 5792-84 Flame retardant filling PVC flame retardant, degree of flame retardant category A black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Test voltage alternating or direct Temperature range laying and installing exploitation and storage Operating temperature

Insulation Inner sheath Sheath Color

4kV 12kV

-5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category A 10 D cable

Type codes
SAVVnpower cable aluminum conductors PVC insulation sheath of PVC flame retardant Flame retardancy Bending radius, min Short circuit temperature for no more than 5 sec.

Color coding
Number of cond. 1 2 3 4 5 Color of conductors without yellow/green random color brown, blue brown , black, blue, grey blue, brown, black, grey blue, brown, black, grey, black Neutral conductor - blue Color of conductors with yellow/green yellow/green, blue, brown yellow/green, brown, black, blue yellow/green, blue, brown, black, grey

334

ELKABEL

Al conductors PVC insulation PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SAVVn/ 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 1 2.5 14 16 1 10 1 16 1 25 1 35 1 50 1 50 1 70 1 95 1 120 1 150 1 185 1 240 1 300 1 400 1 500 2 2.5 24 26 2 10 2 16 2 25 2 35 2 35 2 50 2 70 2 95 3 2.5 34 36 3 10 3 16 3 25 3 35 3 50 3 50 3 70 3 95 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 4+2.5 3 6+4 re re re re re re re re rm rm rm rm rm rm rm rm rm rm re re re re re re re rm rm rm rm re re re re re re re re rm rm rm sm sm sm sm sm sm sm re/re re/re mm 7.5 8.4 9.1 9.1 10.6 12.2 13.2 14.6 17.4 19.2 21.4 22.8 24.7 24.9 30.1 30.6 34.0 38.1 12.9 14.9 16.1 17.4 19.3 22.4 24.3 25.4 29.1 33.1 37.9 13.5 15.6 17.0 18.3 20.4 23.7 25.8 29.2 31.0 32.0 40.4 27.8 31.2 35.8 38.0 41.8 45.8 51.2 16.2 17.9 Mass of Al kg/km 8 12 17 28 45 68 95 127 127 190 260 325 405 510 665 830 1060 1410 14 23 34 56 90 137 190 190 254 380 520 21 36 51 85 135 210 290 385 385 570 780 385 585 810 1020 1255 1560 2035 42 63 Mass of cable approx kg/km 72 93 107 128 158 210 252 315 330 522 648 755 882 925 1325 1402 1748 2235 218 292 346 407 510 695 832 883 1160 1517 1995 240 326 385 465 582 790 966 1240 1310 1761 2295 1035 1351 1805 2059 2530 3107 3905 348 425

Construction data SAVVn/ 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 3 10+6 3 16+10 3 25+16 3 35+16 3 50+25 3 50+25 3 50+25 3 70+35 3 70+35 3 95+50 3 35+16 3 50+25 3 70+35 3 95+50 3120+70 3150+70 3185+95 3240+120 3300+150 4 2.5 44 46 4 10 4 16 4 25 4 35 4 50 4 50 4 70 4 95 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 4 300 5 2.5 54 56 5 10 5 16 5 25 5 35 5 50 5 70 5 95 re/re re/re re/re re/re re/re rm/re rm/m rm/m rm/rm rm /rm sm/re sm/re sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm re re re re re re re re rm rm rm sm sm sm sm sm sm sm sm sm re re re re re re rm rm rm rm mm 19.4 21.5 24.9 26.7 30.5 32.6 28.8 37.0 36.6 42.3 28.0 31.2 36.0 40.2 43.2 48.0 52.3 58.7 64.3 14.4 16.8 18.3 19.8 22.1 25.8 28.2 32.5 34.7 39.1 45.2 28.0 31.2 36.0 40.2 43.2 48.0 53.7 58.7 64.3 15.4 18.1 19.7 21.4 24.0 28.1 33.0 38.1 43.3 49.8 Mass of Al kg/km 101 165 255 340 480 485 485 665 660 907 340 453 670 910 1180 1405 1780 2310 2895 28 46 68 112 180 270 390 520 520 760 1040 390 520 760 1060 1340 1650 2100 2720 3320 35 58 85 140 225 345 480 650 965 1345 Mass of cable approx kg/km 510 645 878 1040 1374 1475 1495 1899 1889 2495 977 1225 1637 2086 2476 2999 3647 4598 5577 269 375 445 540 693 944 1163 1537 1660 2134 2851 1050 1321 1763 2276 2678 3105 4268 5120 6157 309 429 513 630 795 1120 1520 1983 2604 3497

ELKABEL

335

SVBVn/A
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001-96

Application
Armored cable for fixed installation and construction of electrical networks and installations, intended for transfer and distribution of electrical power with nominal voltage U 0 / U 0. 6/1 kV, frequency of 50Hz and flame retardant surroundings. Armored cable for fixed installation and construction of electrical networks and installations, intended for transfer and distribution of electrical power with nominal voltage U 0 / U 0. 6/1 kV, frequency of 50Hz and flame retardant surroundings.

Cable construction
Construction Conductor According to FN KI 02.001-96 Copper solid or twisted cores, class 1 or class 2, according to BDS 904-84(IEC 60228) PVC insulation, according to BDS 5792-84 flame retardant filling steel tapes PVC flame retardant, degree of flame retardancy category A black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Test voltage alternating

Insulation Inner sheath Armour Sheath Color

4kV 12kV

or direct Temperature range laying and installing exploitation and storage Operating temperature Short circuit temperature for no more than 5 sec. Flame retardancy Bending radius, min

-5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category A 10 D cable

Type codes
SVBVnpower cable PVC insulation armor sheath of PVC flame retardant

Color coding
Number of cond. 1 2 3 4 Color of conductors without yellow/green random color brown, blue brown , black, blue, grey blue, brown, black, grey Neutral conductor - blue Color of conductors with yellow/green yellow/green, blue, brown yellow/green, brown, black, grey

336

ELKABEL

Cu conductors PVC insulation Armour-st. tapes PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SVBVn/A 0.6/1 kV


Number of cond. and nominal cross section N mm2 2 1.5 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 2 35 2 50 3 1.5 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 300 3 2.5+1.5 3 4.0+2.5 3 6.0+4.0 3 10+6.0 3 16+10 3 25+16 3 25+16 3 35+16 3 50+25 3 50+25 3 70+35 3 95+50 3 120+70 3 150+70 3 185+95 3 240+120 3 300+150 4 1.5 4 2.5 4 4.0 4 6.0 4 10 4 16 4 25 4 35 4 50 4 50 4 70 4 95 4 120 4 150 4 185 4 240 4 300 re re re re re re rm rm rm re re re re re re rm rm rm sm sm sm sm sm sm sm re/re re/re re/re re/re re/re rm/re rm/rm rm/rm rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm re re re re re re rm rm rm sm sm sm sm sm sm sm sm Form of conductor Cable diameter approx. mm 12.8 13.0 16.2 17.2 18.8 20.6 25.1 27.4 31.0 13.7 14.5 16.7 18.0 20.0 22.0 26.5 29.2 32.8 33.0 38.0 40.0 44.2 47.9 53.3 58.7 16.2 17.8 19.2 21.1 23.2 27.6 27.8 30.1 34.2 34.2 38.2 42.4 45.6 50.2 54.4 60.9 66.7 14.5 15.7 18.3 19.5 21.5 23.7 29.0 31.8 36.7 33.0 38.2 42.4 45.6 50.2 54.5 61.0 66.7 Mass of Cu kg/km 28 46 73 110 182 303 470 652 928 42 69 110 165 275 450 700 980 1390 1950 2650 3350 4185 5160 6720 8295 82 132 202 330 540 850 850 1131 1630 1630 2280 3120 4010 4850 6070 7840 9928 55 92 146 218 363 582 925 1303 1857 1857 2601 3540 4460 5575 6880 8928 11060 Mass of cable approx kg/km 315 360 478 561 680 862 1299 1570 2016 350 420 529 631 820 1022 1555 2023 2648 2940 3984 4786 5841 7125 9098 11198 461 618 699 922 1223 1805 1812 2266 2978 2978 3542 4538 5596 6933 8356 10620 13422 390 466 621 734 975 1275 1938 2522 3335 3338 3845 5132 6250 7740 9510 11928 14655

ELKABEL

337

SVBVn/A
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001-96

Application
Armored cable for fixed installation and construction of electrical networks and installations, intended for transfer and distribution of electrical power with nominal voltage U 0 / U 0. 6/1 kV, frequency of 50Hz and flame retardant surroundings. Armored cable for fixed installation and construction of electrical networks and installations, intended for transfer and distribution of electrical power with nominal voltage U 0 / U 0. 6/1 kV, frequency of 50Hz and flame retardant surroundings.

Cable construction
Construction Conductor According to FN KI 02.001-96 Copper solid or twisted cores, class 1 or class 2, according to BDS 904-84(IEC 60228) PVC insulation, according to BDS 5792-84 flame retardant filling steel tapes PVC flame retardant, degree of flame retardancy category A black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Test voltage alternating

Insulation Inner sheath Armour Sheath Color

4kV 12kV

or direct Temperature range laying and installing exploitation and storage Operating temperature Short circuit temperature for no more than 5 sec. Flame retardancy Bending radius, min

-5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category A 10 D cable

Type codes
SVBVnpower cable PVC insulation armor sheath of PVC flame retardant

Color coding
Number of cond. 5 Color of conductors without yellow/green blue, brown, black, grey, black Color of conductors with yellow/green yellow/green, blue, brown, black,grey yellow/green and the other core black with number marking

6 and over 6

black with number marking

338

ELKABEL

Cu conductors PVC insulation Armour-st. tapes PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SVBVn/A 0.6/1 kV


Number of cond. and nominal cross section N mm2 5 1.5 5 2.5 5 4.0 5 6.0 5 10 5 16 5 25 5 35 5 50 5 70 6 1.5 6 2.5 6 4.0 6 6.0 7 1.5 7 2.5 7 4.0 7 6.0 8 1.5 8 2.5 8 4.0 8 6.0 10 1.5 10 2.5 10 4.0 10 6.0 12 1.5 12 2.5 14 1.5 14 2.5 16 1.5 16 2.5 19 1.5 19 2.5 20 1.5 20 2.5 21 1.5 21 2.5 24 1.5 24 2.5 27 1.5 27 2.5 30 1.5 30 2.5 37 1.5 37 2.5 re re re re re re rm rm rm rm re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re re Form of conductor Cable diameter approx. mm 15.9 16.9 19.5 15.7 23.1 25.6 31.7 34.8 40.1 45.3 16.8 18.0 20.9 22.4 16.8 18.0 20.9 22.4 19.1 19.6 22.9 23.5 20.1 21.5 25.4 27.4 20.4 22.1 21.2 22.9 22.1 23.9 23.1 25.0 24.1 26.1 24.1 26.1 26.1 28.6 26.6 29.2 27.5 24.8 29.4 32.3 Mass of Cu kg/km 69 114 182 275 455 745 1165 1640 2330 3260 84 138 222 330 96 160 255 384 110 182 296 440 140 228 365 550 165 275 195 320 220 365 260 435 280 460 294 483 330 546 378 621 410 685 506 845 Mass of cable approx kg/km 430 520 710 856 1025 1320 2340 3125 4180 5200 507 608 835 1013 502 630 865 1055 578 715 1020 1250 665 814 1225 1520 741 890 805 960 880 1080 930 1215 1055 1310 1065 1320 1135 1485 1295 1672 1460 1720 1566 1986

ELKABEL

339

SAVBVn/A
POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Uo/U - 0.6/1 kV FN KI 02.001-96

Application
Armored cables for fixed assembly installation of electrical power networks and installations, designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames.

Cable construction
Construction Conductor According to FN KI 02.001-96 Aluminum solid or twisted cores, class 1 or class 2, according to BDS 904-84 PVC insulation, according to BDS 5792-84 flame retardant filling PVC flame retardant, degree of flame retardant category A black class 1 class 2

Technical data
Cross section of conductor, mm2 from 1.5 to 16 from 25 to 500 According to BDS 904-84

Conductor resistance Test voltage alternating

Insulation Inner sheath Sheath Color

4kV 12kV

or direct Temperature range laying and installing exploitation and storage Operating temperature

-5oC -30oC to +50oC +70oC +160oC BDS IEC 332-3/82 Category A 10 D cable

Type codes
SAVBVnpower cable aluminum conductors PVC insulation Steel tape armor sheath of PVC flame retardant

Short circuit temperature for no more than 5 sec. Flame retardancy Bending radius, min

Color coding
Number of cond. 1 2 3 4 5 6 and above Color of conductors without yellow/green random color brown, blue brown , black, blue, grey blue, brown, black, grey blue, brown, black, grey, black black with number marking Color of conductors with yellow/green yellow/green, blue, brown yellow/green, brown, black, grey yellow/green, blue, brown, black,grey yellow/green and the other core black with number marking

340

ELKABEL

Al conductors PVC insulation Armour-st. tapes PVC sheath

POWER CABLES LOW VOLTAGE, FLAME RETARDANT

Construction data SAVBVn/A 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 2 2.5 2 4.0 2 6.0 2 10 2 16 2 25 2 35 2 50 3 2.5 3 4.0 3 6.0 3 10 3 16 3 25 3 35 3 50 3 50 3 70 3 95 3 120 3 150 3 185 3 240 3 300 34.0+2.5 36.0+4.0 3 10+6.0 3 16+10 3 25+16 3 35+16 3 35+16 3 50+25 3 50+25 3 50+35 3 70+35 3 95+50 3120+70 3150+70 re re re re re rm rm rm re re re re re rm rm rm sm sm sm sm sm sm sm sm re/re re/re re/re re/re re/re re/re rm/rm rm/rm sm/rm sm/rm sm/rm sm/rm sm/rm sm/rm mm 16.4 16.5 17.5 19.1 21.0 25.1 27.4 30.7 16.3 17.2 18.3 20.1 22.1 26.6 29.1 32.8 29.6 33.0 38.0 40.0 44.2 47.9 53.3 58.7 12.6 19.2 21.0 23.2 27.8 27.1 30.1 34.2 33.0 33.0 38.2 42.4 45.6 50.2 Mass of Al approx. kg/km 14 23 34 56 90 137 190 254 21 36 51 85 135 210 290 385 385 585 810 1020 1255 1560 2035 2490 42 63 101 165 255 340 340 480 480 507 670 910 1180 1405 Mass of cable approx. kg/km 433 440 499 593 719 995 1174 1468 430 481 540 651 794 1104 1324 1652 1325 1665 2548 2653 3194 3780 4662 5530 496 579 694 887 1185 1205 1396 1791 1572 1604 2194 2684 3164 3721

Construction data SAVBVn/A 0.6/1 kV


Number of Form of Cable cond. and conductor diameter nominal approx. cross section N mm2 3185+95 3240+120 3300+150 4 2.5 4 4.0 4 6.0 4 10 4 16 4 25 4 35 4 50 4 70 4 95 4 120 4 150 4 185 4 240 4 300 5 1.5 5 2.5 5 4.0 5 6.0 5 10 5 16 5 25 5 35 5 50 5 70 7 1.5 8 1.5 10 1.5 12 1.5 14 1.5 16 1.5 19 1.5 20 1.5 21 1.5 24 1.5 sm/rm sm/rm sm/rm re re re re re re re re sm sm sm sm sm sm sm re re re re re re rm rm rm rm re re re re re re re re re re mm 54.5 60.9 66.7 16.4 18.4 19.6 21.5 23.8 29.1 31.9 36.7 38.2 42.4 45.6 50.2 54.5 60.9 66.7 15.9 16.8 19.6 21.0 23.2 25.7 31.7 34.9 40.1 45.3 16.9 18.3 19.9 20.4 21.2 22.1 23.0 24.0 24.0 26.1 Mass of Al approx. kg/km 1780 2310 2895 28 46 68 112 180 270 390 520 760 1060 1340 1650 2100 2720 3320 25 35 58 85 140 225 345 480 650 950 35 40 51 61 71 81 95 101 105 120 Mass of cable approx. kg/km 4425 5460 6554 431 539 613 749 921 1305 2874 5070 2310 2884 3358 4031 4822 5980 7098 415 461 607 696 852 1056 1519 1837 2571 3265 456 528 625 651 706 748 807 870 873 1021

ELKABEL

341

MKG ... x4x1.2


HIGH FREQUENCY COMMUNICATIONS CABLES FOR TRUNK CABLE NETWORKS

BDS 5052-90.

Paper band insulation quads, stranded in layers lead sheath

Application
These cables are used for building trunk cables networks with the possibility for sealing the transmitted signals up to 552 kHz. They are intended for fixed installation in collectors, canals or pipes. The use of these cables for high power installations and for direct laying in ground is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Bare copper conductor, diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are stranded into layers Several layers of paper tapes Lead containing antimony of 0.4 to 0.6%

Technical data
Conductor diameter Resistance of side circuit at 20oC-max Ohmic asymmetry - max. Insulation resistance - min. Mutual capacitance at 800Hznom. Attenuation of near end between all side-circuits at 552kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuit at 552kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire white red green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral M trunk cable K paper band insulation G no protective sheath Type codes

62dB/425 57dB/425m

70dB/425m 66dB/425m 1000V 2000V 225V -20oC +50oC -30oC +70oC 20 D cable

Cable core construction


Number of quads 3 4 7 Number of quads in the layers 1 2 3 4 1 6

Construction data MKG...x4x1.2


Number of quads 3 4 7 Outer diameter approx mm 18.8 19.8 25.1 Copper weight kg/km 134 179 313 Cable weight approx kg/km 1049 1146 1678

342

ELKABEL

BDS 5052-90

Paper band insulation quads stranded in layers lead sheath armour of steel tapes protective layer of yarn

MKBs ... x4x1.2

HIGH FREQUENCY COMMUNICATIONS CABLES FOR TRUNK CABLE NETWORKS

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for using multi-channel systems with a frequency range of up to 552 kHz. They are suitable for laying in ditches, where there is less force of strain and inclined terrain less than 45. The use of these cables for power installations high voltage is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Pad Armour Protective covering Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 cores are twisted into quad Quads are twisted concentrically into layers Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Bitumen and impregnated cable paper Two steel tapes of bitumen, synthetic yarn and chalk

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry - max. Insulation resistance - min. Mutual capacitance at 800Hznom. Attenuation of near end between all side-circuits at 552kHz no less than: 90% of all combinations 100% of all combinations Protection of far end between all side-circuit at 552kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km

62dB/425 57dB/425m

Cable core construction


Number of quads 3 4 7 Number of quads in the layers 1 2 3 4 1 6

70dB/425m 66dB/425m 1000V 2000V 300V 0oC +45oC -30oC +50oC 20 D cable

Color coding
Side circuit - 1 - wire b- wire red white Side circuit - 2 - wire b- wire green blue

In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M K B s trunk cable paper band insulation steel tape armour protective sheath of bitumen and yarn

Construction data MKBs...x4x1.2


Number of quads Outer diameter approx. mm 3 4 7 27.7 28.5 33.8 Copper weight kg/km 134 179 313 Cable weight approx. s kg/km 1613 1741 2341

ELKABEL

343

MKBP ... x4x1.2


HIGH FREQUENCY COMMUNICATIONS CABLES FOR TRUNK CABLE NETWORKS

BDS 5052-90.

Paper band insulation quads stranded in layers lead sheath steel tape armour protective PE sheath

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for using multi-channel systems with a frequency range of up to 552 kHz. They are suitable for laying in ditches in all types of grounds, where there is less force of strain and inclined terrain less than 45. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Pad Armour Protective sheath Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted concentrically into layers Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry - max. Insulation resistance - min. Mutual capacitance at 800Hz-nom. Attenuation of near end between all side-circuits at 552kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuit at 552kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km

62dB/425 57dB/425m

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M trunk cable K paper band insulation B steel tape armour P polyethylene protective sheath

70dB/425m 66dB/425m 1000V 2000V 300V -5oC +50oC -40oC +70oC 20 D cable

Cable core construction


Number of quads 3 4 7 Number of quads in the layers 1 2 3 4 1 6

Construction data MKBP...x4x1.2


Number of quads 3 4 7 Outer diameter approx mm 27.7 28.3 34.0 Copper weight kg/km 134 179 313 Cable weight approx. kg/km 1624 1858 2364

344

ELKABEL

BDS 5052-90 and TU "ELKABEL"

MKEmPBP ... x4x1.2


HIGH FREQUENCY COMMUNICATIONS CABLES FOR TRUNK CABLE NETWORKS WITH LOW REDUCTION FACTOR

Paper band insulation quads stranded in layers lead sheath screen steel tape armour protective PE sheath

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for using multi-channel systems with a frequency range of up to 252 kHz. They are suitable for laying in ditches, where there is less force of strain and inclined terrain less than 45, in areas with high electro magnetic influence (fields). The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Screen Inner sheath Pad Armour Protective covering Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted concentrically into layers Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Two layers of copper tapes Polyethylene Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry - max. Insulation resistance - min. Mutual capacitance at 800Hznom. Attenuation of near end between all side-circuits at 252kHz no less than: 90% of all combinations 100% of all combinations Protection of far end between all side-circuit at 252kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Reduction factor, Inductive voltage 50 to 400 V and frequency 50Hz, no more than Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km

62dB/425 57dB/425m

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M trunk cable K paper band insulation Em copper tape screen P PE sheath B steel tape armour P Protective PE sheath

70dB/425m 66dB/425m 1000V 2000V 0.3 300V -5oC +50oC -40oC +70oC 20 D cable

Cable core construction


Number of quads 4 Number of quads in the layers 4

Construction data MKEmPBP...x4x1.2


Number of quads Outer diameter approx. mm 4 36 Copper weight kg/km 765 Cable weight approx. kg/km 3006

ELKABEL

345

MKKG 4x4x1.2 + 1541.2

BDS 5052-90

Paper band insulation quads stranded in layers lead sheath

COMBINED COMMUNICATION CABLES WITH HF AND LF QUADS FOR TRUNK NETWORKS

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for transferring of HF and LF, and HF quads may be compressed in frequency range up to 252 kHz. These cables are suitable for fixed installations in collectors, cable ducts and pipes. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Twisted in the middle are 4HF quads and around them are twisted concen trically 15 LF quads Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6%

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry of HF quads max. Insulation resistance - min. Mutual capacitance at 800Hz-nom. HF quads LF quads Attenuation of near end between all side-circuits of HF quads at 552kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuits of HF at 552kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km 35 nF/km

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M trunk cable K combined K paper band insulation G no protective sheath

62dB/425 57dB/425m

70dB/425m 66dB/425m 1000V 2000V 300V -5oC +50oC -40oC +70oC 20 D cable

Cable core construction


Cross section 4x4x1.2+15x4x1.2 Number of quads in the layers 1 2 4 HF quads 15 LF quads

Construction data MKKG 4x4x1.2+1541.2


Cross section Outer diameter approx. mm 441.2+1541.2 30.8 Copper weight kg/km 789 Cable weight approx. kg/km 2613

346

ELKABEL

BDS 5052-90

MKKBs 4x4x1.2 + 1541.2

Paper band insulation quads stranded in layers lead sheath steel tape armour protective sheath of yarn

COMBINED COMMUNICATION CABLES WITH HF AND LF QUADS FOR TRUNK NETWORKS

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for transferring of HF and LF, where HF quads may be compressed in a frequency range of up to 252 kHz. They are suitable for laying in ditches in all types of grounds, where there is less force of strain and inclined terrain no less than 45. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Pad Armour Protective sheath Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Twisted in the middle are 4HF quads and around them are twisted concen trically 15 LF quads Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Bitumen and impregnated cable paper Two steel tapes of bitumen, synthetic yarn and chalk

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry of HF quads max. Insulation resistance - min. Mutual capacitance at 800Hz-nom. HF quads LF quads Attenuation of near end between all side-circuits of HF quads at 552kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuits of HF at 552kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km 35 nF/km

62dB/425 57dB/425m

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M trunk cable K combined K paper band insulation B steel tape armour s protective sheath of bitumen and synthetic yarn

70dB/425m 66dB/425m 1000V 2000V 300V 0oC +45oC -30oC +50oC 20 D cable

Cable core construction


Cross section 4x4x1.2+15x4x1.2 Number of quads in the layers 1 2 4 HF quads 15 LF quads

Construction data MKKBs 4x4x1.2+1541.2


Cross section Outer diameter approx.
mm

Copper weight
kg/km

Cable weight approx.


kg/km

441.2+1541.2

39.3

807

3369

ELKABEL

347

MKKBP 4x4x1.2 + 1541.2

BDS 5052-90

COMBINED COMMUNICATION CABLES WITH HF AND LF QUADS FOR TRUNK NETWORKS

Paper band insulation quads stranded in layers lead sheath steel tape armour protective PE sheath

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for transferring of HF and LF, where HF quads may be compressed in a frequency range of up to 252 kHz. They are suitable for laying in ditches in all types of grounds, where there is less force of strain and inclined terrain less than 45. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape Quad 4 wires are twisted into a quad Cable core Twisted in the middle are 4HF quads and around them are twisted concentrically 15 LF quads Wrapping Several layers of paper tapes Sheath of lead, containing antimony of 0.4 to 0.6% Pad Bitumen and impregnated cable paper Armour Two steel tapes Protective sheath PE low density with 2.5% carbon black

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry of HF quads max. Insulation resistance - min. Mutual capacitance at 800Hz-nom. HF quads LF quads Attenuation of near end between all side-circuits of HF quads at 552kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuits of HF at 552kHz no less than 90% of all combinations 100% of all combinations Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km 35 nF/km

62dB/425 57dB/425m

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M trunk cable K combined K paper band insulation B steel tape armour P PE protective sheath

70dB/425m 66dB/425m 1000V 2000V 300V -5oC +50oC -40oC +70oC 20 D cable

Cable core construction


Cross section 4x4x1.2+15x4x1.2 Number of quads in the layers 1 2 4 HF quads 15 LF quads

Construction dataMKKBP 4x4x1.2+1541.2


Cross section Outer diameter approx.
mm

Copper weight
kg/km

Cable weight approx.


kg/km

441.2+1541.2

39.9

807

3654

348

ELKABEL

BDS 5052-90 and TU"ELKABEL".

MKKEmPBP 4x4x1.2 + 1541.2

Paper band insulation quads stranded in layers lead sheath screen steel tape armor protective PE sheath

COMBINED COMMUNICATION CABLES WITH HF AND LF QUADS AND LOW REDUCTION FACTOR

Application
These cables are used for construction of trunk cable communication network and connection lines between automatic telephone exchanges, with the possibility for transferring of HF and LF, where HF quads may be compressed in a frequency range of up to 552 kHz. They are suitable for laying in ditches in all types of grounds, where there is less force of strain and inclined terrain less than 45, in areas with high electro-magnetic influence. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Screen Inner sheath Pad Armour Protective sheath Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Twisted in the middle are 4HF quads and around them are twist ed concentrically 15 LF quads Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Two layers of copper tapes PE Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry of HF quads max. Insulation resistance - min. Mutual capacitance at 800Hznom. HF quads LF quads Attenuation of near end between all side-circuits HF quads at 552kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuits of HF at 552kHz no less than 90% of all combinations 100% of all combinations Reduction factor, Inductive voltage 50 to 400 V and frequency 50Hz, no more than Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km 35 nF/km

62dB/425 57dB/425m

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral Type codes M trunk cable K combined K paper band insulation Em copper tape screen P PE sheath B steel tape armor P protective PE sheath

70dB/425m 66dB/425m 0.3

1000V 2000V 300V -5oC +50oC -40oC +70oC 20 D cable

Cable core construction


Cross section 4x4x1.2+15x4x1.2 Number of quads in the layers 1 2 4 HF quads 15 LF quads

Construction data MKKEmPBP 4x4x1.2+1541.2


Cross section Outer diameter approx.
mm

Copper weight
kg/km

Cable weight approx.


kg/km

441.2+1541.2

47.5

1571

5059

ELKABEL

349

MKKEmPBPj 4x4x1.2 + 1541.2

Paper band insulation quads stranded in layers lead sheath steel tape armour protective PE sheath

BDS 5052-90 and TU "ELKABEL".

COMBINED COMMUNICATION CABLES WITH HF AND LF QUADS AND LOW REDUCTION FACTOR FOR RAILWAY TRANSPORT

Application
These cables are used for construction of trunk cable communication network, which are close to electrical railway lines, with the possibility for transferring HF and LF signals, and HF quads may be compressed in frequency range up to 252 kHz. They are suitable for laying in ditches in all types of grounds, where there is less force of strain and inclined terrain less than 45, in areas with high electro-magnetic influence (fields). The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Screen Inner sheath Pad Armour Protective sheath Bare copper conductor diameter 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Twisted in the middle are 4HF quads and around them are twisted concen trically 15 LF quads Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Two layers of copper tapes PE Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
Conductor diameter Resistance of side circuits at 20oC-max Ohmic asymmetry of HF quads max. Insulation resistance - min. Mutual capacitance at 800Hznom. HF quads LF quads Attenuation of near end between all side-circuits of HF quads at 252kHz no less than 90% of all combinations 100% of all combinations Protection of far end between all side-circuits of HF at 252kHz no less than 90% of all combinations 100% of all combinations 1.2mm 31.7 /km 0.13/425m 12 000 M.km 26.5nF/km 35 nF/km

62dB/425 57dB/425m

70dB/425m 66dB/425m 0.1 1000V 2000V 8600 300V -5oC +50oC -40oC +70oC 20 D cable

Color coding
Side circuit - 1 Side circuit - 2 - wire b- wire - wire b- wire red white green blue In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral
Type codes M trunk cable; K combined ;K paper band insulation Em copper tape screen; P PE sheath; B steel tape armour P PE protective sheath; j for railway transport

Reduction factor, Inductive voltage 50 to 400 V and frequency 50Hz, no more than Test voltage 50Hz, 2 min. wire-wire wire-sheath sheath - screen Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx.

Cable core construction


Cross section 4x4x1.2+15x4x1.2 Number of quads in the layers 1 4 HF quads 2 15 LF quads

Construction data MKKEmPBPj 4x4x1.2+1541.2


Cross section Outer diameter approx.
mm

Copper weight
kg/km

Cable weight approx.


kg/km

441.2+1541.2

51.4

1644

5776

350

ELKABEL

TZG ... x4x0.9 TZG ... x4x1.2


COMMUNICATION CABLES FOR LONG DISTANCES

BDS 5052-90.

Application
These cables are used for construction of inter city cable communication networks and connection lines between automatic telephone exchanges, where there is transfer of low frequency signals. These cables are suitable for fixed installations in collectors, cable ducts and pipes. The use of these cables for high voltage installations and for direct laying underground is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Bare copper conductor diameter 0.9 mm and 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted concentrically into layers Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6%

Technical data
Conductor diameter Conductor resistance at 20C-max Insulation resistance - min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 - max. K2-3- max. K9-12- max. E1-2 - max. 0.9 1.2mm 28.3 15.85/km 12 000 M.km 34 35nF/km

280 700 210 700

pF/425m pF/425m pF/425m pF/425m

Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx.

700

1000V 2000V 225V

Color coding
Side circuit - 1 - wire white b- wire
red

-20 C +50 C -30 C +70 C 20 D cable

Side circuit - 2 - wire green b- wire blue T Z G

In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral

Type codes telephone cable twisted into star quad no protective sheath

352

ELKABEL

Paper band insulation quads stranded in layers lead sheath

COMMUNICATION CABLES FOR LONG DISTANCES

Cable core construction


Number of quads Number of quads in the layers

1 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 3 4 1 3 4 1 2 3 4 1 2 4 1 3 4 2 4

6 9 10 6 8 9 10 6 8 10 6 9 10 8 10

12 14 15 16 12 14 16 12 15 16 14 16

18 20 22 18 21 22 20 22

24 27 28 26 28

32 34

Construction data TZG...x4x0.9


Number of quads Outer diameter approx. mm 10.9 12.0 15.0 18.8 19.8 22.4 25.4 26.8 28.0 30.4 33.8 36.5 39.1 43.4 44.7 50.0 53.3 Copper weight kg/km 75 100 175 300 50 474 599 674 749 924 1118 1321 1550 1905 2032 2591 2896 Cable weight approx. kg/km 547 596 829 1207 1311 1616 1961 2182 2330 2666 3387 3772 4389 5163 5373 6719 7299

Construction data TZG...x4x1.2


Number of quads Outer diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 13.2 14.2 18.0 23.1 24.3 27.4 31.3 32.5 33.8 37.3 42.0 43.6 46.9 52.3 55.7 62.5 66.1 Copper weight kg/km 133 177 310 531 620 841 1063 1196 1329 1639 1983 2343 2749 3379 3605 4596 5137 Cable weight approx. kg/km 695 787 1165 1739 1896 2361 2961 3172 3473 4105 5058 5835 6469 7948 8288 10311 11160

3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114

ELKABEL

353

COMMUNICATION CABLES FOR LONG DISTANCES

TZBs ...x4x0.9 TZBs ...x4x1.2

BDS 5052-90

Application
These cables are used for construction of inter city cable communication networks and connection lines between automatic telephone exchanges, where there is transfer of low frequency signals. They are suitable for laying in ditches, where there is less force of strain and inclined terrain less than 45. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Pad Armour Protective sheath Bare copper conductor diameter 0.9 mm and 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted concentrically into layers Several layers of paper tapes of lead, containing antimony of 0.4 to 0.6% Bitumen and impregnated cable paper Two steel tapes of bitumen, synthetic yarn and chalk

Technical data
Conductor diameter Conductor resistance at 20C-max Insulation resistance min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 - max. K2-3- max. K9-12- max.. E1-2 - max. Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage Bending radius, min. approx. 0.9 28.3 1.2mm 15.85/km

12 000 M.km 34 35nF/km

280 700 210 700 700

pF/425m pF/425m pF/425m pF/425m 1000V 2000V 225V

Color coding
Side circuit - 1 - wire white b- wire
red

0C +45C -30C +50C 20 D cable

Side circuit - 2 - wire green b- wire blue T Z B s

In each layer there is a quad with red supporting and a quad Quad marking spiral from which the counting startswith yellow showing the direction of counting supporting spiral

Type codes telephone cable twisted into star quad steel tape armour protective sheath of bitumen and synthetic yarn

354

ELKABEL

Paper band insulation quads stranded in layers lead sheath steel tape armour protective sheath of yarn

COMMUNICATION CABLES FOR LONG DISTANCES

Cable core construction


Number of quads Number of quads in the layers

1 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 3 4 1 3 4 1 2 3 4 1 2 4 1 3 4 2 4

6 9 10 6 8 9 10 6 8 10 6 9 10 8 10

12 14 15 16 12 14 16 12 15 16 14 16

18 20 22 18 21 22 20 22

24 27 28 26 28

32 34

Construction data TZBs...x4x0.9


Number of quads Outer diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 19.1 20.2 23.2 27.7 28.7 31.1 34.1 35.5 36.7 38.9 42.4 45.0 47.6 51.8 53.0 58.5 63.0 Copper weight kg/km 76 102 178 306 357 484 612 688 765 943 1121 1325 1555 1911 2039 2600 2905 Cable weight approx. kg/km 812 909 1188 1760 1888 2232 2617 2828 3002 3405 4020 4528 5074 5908 6286 7695 9121

Construction data TZBs...x4x1.2


Number of quads Outer diameter approx. mm 21.4 22.4 26.9 31.8 33.0 36.1 39.9 41.1 42.4 45.8 50.4 52.0 55.4 62.0 65.3 72.1 75.7 Copper weight kg/km 136 181 317 544 634 861 1087 1223 1359 1676 1993 2356 2763 3398 3624 4621 5165 Cable weight approx. kg/km 1019 1132 1698 2345 2528 3019 3650 3883 4195 4876 5783 6294 7298 9378 10161 12346 13746

3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114

ELKABEL

355

COMMUNICATION CABLES FOR LONG DISTANCES

TZBP ... x4x0.9 TZBP ... x4x1.2

BDS 5052-90

Application
These cables are used for construction of inter city cable communication networks and connection lines between automatic telephone exchanges, where there is transfer of low frequency signals. They are suitable for laying in ditches in all types of grounds, where there is less force of strain and inclined terrain less than 45. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Pad Armour Protective sheath Bare copper conductor diameter 0.9 mm and 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted into layers Paper tapes of lead, containing antimony of 0.4 to 0.6% Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
'Conductor diameter Conductor resistance at 20C-max Insulation resistance min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 -max. K2-3- max. K9-12- max. E1-2 - max. Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Temperature range laying and installing exploitation and storage 0.9 28.3 1.2mm 15.85/km

12 000 M.km 34 35nF/km

280 700 210 700 700

pF/425m pF/425m pF/425m pF/425m 1000V 2000V 225V

0C +45C -30C +50C 20 D cable

Color coding
Side circuit - 1 - wire white b- wire
red

Side circuit - 2 - wire green b- wire blue T Z B P

Bending radius, min. approx.

In each layer there is a quad with red supporting spiral from which the counting starts and a quad Quad marking showing the direction of counting - with yellow supporting spiral

Type codes telephone cable twisted into star quad steel tape armour protective PE sheath

356

ELKABEL

Paper band insulation quads stranded in layers lead sheath steel tape armour protective PE sheath

COMMUNICATION CABLES FOR LONG DISTANCES

Cable core construction


Number of quads Number of quads in the layers

1 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 3 4 1 3 4 1 2 3 4 1 2 4 1 3 4 2 4

6 9 10 6 8 9 10 6 8 10 6 9 10 8 10

12 14 15 16 12 14 16 12 15 16 14 16

18 20 22 18 21 22 20 22

24 27 28 26 28

32 34

Construction data TZBP...x4x0.9


Number of quads Outer diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 18.7 19.7 22.8 27.6 28.6 31.0 34.3 35.5 36.9 39.5 42.9 45.9 48.7 53.1 54.4 59.7 64.9 Copper weight kg/km 76 102 178 306 357 484 612 688 765 943 1121 1325 1555 1911 2039 2600 2905 Cable weight approx. kg/km 798 891 1179 1737 1869 2204 2598 2790 2966 3393 3879 4479 5019 5891 6215 7438 9081

Construction data TZBP...x4x1.2


Number of quads Outer diameter approx. mm 3 4 7 12 14 19 24 27 30 37 44 52 61 75 80 102 114 20.9 22.0 26.7 32.0 33.2 36.0 40.5 41.8 43.1 46.5 51.7 53.3 56.9 63.8 67.4 74.4 78.2 Copper weight kg/km 136 181 317 544 634 861 1087 1223 1359 1676 1993 2356 2763 3398 3624 4621 5165 Cable weight approx. kg/km 998 1107 1683 2327 2508 2970 3631 3883 4182 4851 6219 6253 7083 9173 10137 12321 13755

ELKABEL

357

COMMUNICATION CABLES FOR LONG DISTANCES WITH LOW REDUCTION FACTOR

TZEmPBP ... x4x0.9 TZEmPBP ... x4x1.2

BDS 5052-90 and TU "ELKABEL"

Application
These cables are used for construction of inter city cable communication networks and connection lines between automatic telephone exchanges, where there is transfer of low frequency signals. They are suitable for laying in ditches, where there is less force of strain and inclined terrain less than 45, in areas with higher electro magnetic fields. The use of these cables for high voltage power installations is not permitted.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Screen Inner sheath Pad Armour Protective sheath Bare copper conductor diameter 0.9 mm and 1.2mm Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted into layers Paper tapes of lead, containing antimony of 0.4 to 0.6% Two layers of copper tapes PE Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Insulation resistance min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 - max K2-3- max K9-12- max E1-2 - max Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Reduction factor, Inductive voltage 50 to 350 V and frequency 50Hz, no more than Temperature range laying and installing exploitation and storage 0.9 28.3 1.2mm 15.85/km

12 000 M.km 34 280 700 210 700 700 2000V 225V 0.3 35nF/km pF/425m pF/425m pF/425m pF/425m 1000V

5C +50C -40C +70C 20 D cable

Color coding
Side circuit - 1 - wire white b- wire
red

Bending radius, min. approx.

Side circuit - 2 - wire green b- wire blue T Z P B P Type codes telephone cable twisted into star quad copper tape screen protective PE sheath steel tape armour protective PE sheath

Quad marking

In each layer there is a quad with red supporting spiral from which the counting starts and a quad showing the direction of counting - with yellow supporting spiral

358

ELKABEL

Paper band insulation quads stranded in layers lead sheath screen steel tape armour protective PE sheath

COMMUNICATION CABLES FOR LONG DISTANCES WITH LOW REDUCTION FACTOR

Cable core construction


Number of quads in the layers Number of quads

1 3 4 7 12 14 19 24 27 30 37 3 4 1 3 4 1 2 3 4 1

6 9 10 6 8 9 10 6 12 14 15 16 12

18

Construction data TZEmPBP...x4x0.9


Number and Number and thickNumber of quads thickness of copness of steel tapes per tapes 7 14 24 30 37 N mm 2x0.2 2x0.3 2x0.3 2x0.3 2x0.3 N mm 2x0.5 2x0.8 2x0.8 2x0.8 2x0.8 Outer diameter approx. mm 28.1 34.9 40.2 43.4 47.0 Copper weight kg/km 392 778 1150 1360 1592 Cable weight approx. kg/km 1824 3027 3928 4503 5040

Construction data TZEmPBP...x4x1.2


Number and Number and thickNumber of quads thickness of copness of steel tapes per tapes N mm 3 4 7 12 14 19 24 27 30 37 2x0.2 2x0.2 2x0.3 2x0.3 2x0.3 2x0.3 2x0.3 2x0.3 2x0.3 2x0.3 N mm 2x0.5 2x0.5 2x0.8 2x0.8 2x0.8 2x0.8 2x0.8 2x0.8 2x0.8 2x0.8 Outer diameter approx. mm 26.3 27.5 33.5 39.1 40.4 43.3 48.0 49.5 50.9 54.5 Copper weight kg/km 327 386 708 1041 1157 1439 1755 1918 2082 2467 Cable weight approx. kg/km 1550 1692 2722 3604 3844 4446 5297 5598 5976 6815

ELKABEL

359

TZEmPBPe ... x4x0.9


COMMUNICATION CABLES FOR LONG DISTANCES WITH LOW REDUCTION FACTOR FOR ENERGETICS

BDS 5052-90 and TU "ELKABEL"

Application
These cables are used for construction of inter city cable communication networks and connection lines between automatic telephone exchanges, where there is transfer of low frequency signals. They are suitable for laying in ditches, where there is less force of strain and inclined terrain less than 45, in areas with higher electro magnetic fields. The cables are higher electric strength with low reduction factor for energetics.

Cable construction
Conductor Insulation Quad Cable core Wrapping Sheath Screen Inner sheath Pad Armour Protective sheath Bare copper conductor diameter 0.9 mm . Paper string insulation, over which there is a paper tape 4 wires are twisted into a quad Quads are twisted into layers Paper tapes of lead, containing antimony of 0.4 to 0.6% Two layers of copper tapes PE Bitumen and impregnated cable paper Two steel tapes PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Insulation resistance min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 - max. K2-3- max. K9-12- max. E1-2 - max. Test voltage 50Hz, 2 min. wire-wire wire-sheath Operating voltage peak value Reduction factor, Inductive voltage 30 to 500 V and frequency 50Hz, no more than: 0.9 mm 28.3 /km 12 000 M.km 34 nF/km 280 700 210 700 pF/425m pF/425m pF/425m pF/425m 700 4000V 225V

0.3 up to 1440.9 0.1 over 1940.9 5C +50C -40C +70C 20 D cable

Color coding
Side circuit - 1 - wire white b- wire
red

Temperature range laying and installing exploitation and storage b- wire blue T Z P B P Bending radius, min. approx. Type codes telephone cable twisted into star quad copper tape screen protective PE sheath steel tape armour protective PE sheath for energetics

Side circuit - 2 - wire green

Quad marking

In each layer there is a quad with red supporting spiral from which the counting starts and a quad showing the direction of counting - with yellow supporting spiral

360

ELKABEL

Paper band insulation quads stranded in layers lead sheath screen steel tape armour protective PE sheath

COMMUNICATION CABLES FOR LONG DISTANCES WITH LOW REDUCTION FACTOR FOR ENERGETICS

Cable core construction


Number of quads in the layers Number of quads

1 3 4 7 12 14 19 24 27 30 37 3 4 1 3 4 1 2 3 4 1

6 9 10 6 8 9 10 6

12 14 15 16 12

18

Construction data TZEmPBPe...x4x0.9


Number of quads Outer diameter approx. mm 3 4 7 12 14 19 24 27 30 25.2 26.3 30.8 35.8 37.0 39.4 43.5 44.5 45.7 Cable weight approx. kg/km 1537 1663 2474 3205 3385 3825 4498 4698 4911

ELKABEL

361

TPP ... x2x0.4; TPP ... x2x0.6 TPP ... x2x0.5; TPP ... x2x0.7

BDS 9096-83

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and PABX's for telephone purposes and for transmission of signals. They are suitable for underground installations, in cable ducts and conduit, as well as for interior installations. The use of these cables for power installations is not permitted. These cables may only be used in locations with fire and explosion hazards in accordance with the appropriate safety precautions.

Cable construction
Conductor Insulation Quad Units Unit marking Bare copper conductor diameter 0.4 mm , 0.5mm, 0.6mm, 0.7mm PE low density 4 wires are twisted into a quad 5 quads are twisted to a basic unit In each layer there is a unit with red supporting spiral form at which the counting starts and a unit showing the direction of counting - with yellow supporting spiral. The units are stranded into a cable Several layers of plastic tapes aluminum tape, thickness no less than 0.04mm, one side coated with copolymer and 1 tinned copper wire with diameter of 0.5mm under the aluminum foil PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max. Insulation resistance - min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire-screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 10G.km 48nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

Cable core Wrapping Screen

Sheath

150V Cables with cores 0.4 and 0.5mm 220V Cables with cores 0.6 and 0.7mm Temperature range -10C +60C laying and installing -50C +60C exploitation and storage 10 x cable Bending radius, min. approx. diameter

Color coding
Number of quad Type codes telephone cable polyethylene insulation polyethylene sheath 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

T P P

362

ELKABEL

Polyethylene insulation unit stranding laminated sheath

COMMUNICATION CABLES FOR LOCAL NETWORKS

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 Number of quads 3 5 10 15 25 35 50 75 100 125 150 200 250 300 350 400 500 600 54 1-st layer 3-quads 1 2 3 5 1 3 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

6 7

3 4 5 1

4 5 1 1 1 3 4

5 6 7 7 8

Construction data TPP...


Number of pairs x2x0.4 Outer diameter approx. mm 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 x2x0.5 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 7.4 8.5 10.7 12.4 15.3 17.4 20.5 24.7 26.5 30.4 31.7 37.1 40.4 44.4 47.6 51.0 56.6 61.8 8.7 9.6 11.7 13.9 16.9 19.1 22.5 27.0 29.9 33.7 36.9 40.4 45.6 49.3 52.2 64.0 65.0 69.1 Copper weight kg/km 17 27 51 74 127 174 250 374 494 613 738 983 1235 1476 1722 1968 2454 2941 26 40 78 115 196 269 387 580 766 952 1146 1526 1918 2292 2674 3056 3813 4570 Cable weight approx. kg/km 51 73 117 157 249 324 452 642 811 1002 1177 1524 1902 2252 2621 2993 3703 4413 71 97 151 215 332 449 613 880 1141 1389 1640 2161 2718 3197 3720 4247 5258 6271 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 x2x0.7 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 x2x0.6 Number of pairs

Construction data TPP...


Outer diameter approx. mm 9.3 10.5 13.2 15.4 20.1 22.5 26.7 32.9 35.9 40.5 43.9 50.1 54.7 60.6 64.7 69.2 76.8 10.1 11.8 16.1 18.7 22.7 25.6 31.7 38.1 42.0 47.1 51.3 52.7 66.0 71.9 76.3 Copper weight kg/km 36 57 111 164 281 387 557 834 1102 1371 1650 2197 2761 3300 3851 4401 5491 48 77 150 222 381 526 757 1134 1500 1865 2245 2990 3757 4491 5240 Cable weight approx. kg/km 86 120 212 291 469 619 852 1252 1601 1980 2342 3094 3913 4607 5357 6111 7565 107 152 277 390 614 816 1150 1665 2165 2676 3222 4239 5286 6274 7297

ELKABEL

363

TPPP ... x2x0.4; TPPP ...20.6 TPPP ... x2x0.5; TPPP ...20.7

BDS 9096-83

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and PABX's for telephone purposes and for transmission of signals. They are suitable for installations in cable ducts. The use of these cables for power installations is not permitted. These cables may only be used in locations with fire and explosion hazards in accordance with the appropriate safety precautions.

Cable construction
Conductor Insulation Quad Units Unit marking Bare copper conductor diameter 0.4 mm , 0.5mm, 0.6mm, 0.7mm PE low density 4 wires are twisted into a quad 5 quads are twisted to a basic unit In each layer there is a unit with red supporting spiral form at which the Counting starts and a unit showing the direction of counting - with yellow supporting spiral. The units are stranded into a cable Several layers of plastic tapes aluminum tape, thickness no less than 0.04mm, one side coated with copolymer and 1 tinned copper wire with diameter of 0.5mm under the aluminum foil PE low density with 2.5% carbon black PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max. Insulation resistance - min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire-screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 10G.km 48nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

Cable core Wrapping Screen

Sheath Protective sheath

150V Cables with cores 0.4 and 0.5mm 220V Cables with cores 0.6 and 0.7mm Temperature range -10C +60C laying and installing -50C +60C exploitation and storage 10 x cable Bending radius, min. approx. diameter

Color coding
Number of quad 1 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

T P P P

Type codes telephone cable polyethylene insulation polyethylene sheath polyethylene protective sheath

2 3 4 5

364

ELKABEL

PE insulation unit stranding laminated sheath PE protective sheath

COMMUNICATION CABLES FOR LOCAL NETWORKS

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 Number of quads 3 5 10 15 25 35 50 75 100 125 150 200 250 300 350 400 500 600 54 1-st layer 3-quads 1 2 3 5 1 3 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

6 7

3 4 5 1

4 5 1 1 1 3 4

5 6 7 7 8

Construction data TPPP


Number of pairs x2x0.4 Outer diameter approx. mm 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 x2x0.5 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 10.2 11.3 13.5 15.1 18.3 20.2 23.1 26.5 29.0 33.4 34.7 40.3 45.2 48.1 51.6 55.0 61.1 66.5 11.2 12.2 13.9 15.6 18.8 21.8 24.1 28.6 32.0 36.3 37.8 43.3 48.8 52.7 55.1 59.3 68.6 73.5 Copper weight kg/km 17 27 51 74 127 174 250 374 494 613 738 983 1235 1476 1722 1968 2454 2941 26 40 78 115 196 269 387 580 766 952 1146 1526 1918 2292 2674 3056 3813 4570 Cable weight approx. kg/km 79 108 155 200 288 370 499 718 884 1100 1268 1652 2035 2405 2767 3127 3932 4671 105 133 190 250 373 498 669 951 1225 1506 1774 2292 2866 3377 3884 4416 5553 6587 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 x2x0.7 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 x2x0.6 Number of pairs

Construction data TPPP


Outer diameter approx. mm 11.9 13.0 15.7 17.8 22.1 24.9 28.2 35.7 38.9 43.7 47.0 53.6 58.3 64.8 68.9 73.6 12.6 14.3 18.5 21.1 25.1 28.0 34.3 41.0 45.0 50.4 55.7 62.3 70.3 76.5 81.1 Copper weight kg/km 36 57 111 164 281 387 557 834 1102 1371 1650 2197 2761 3300 3851 4401 48 77 150 222 381 526 757 1134 1500 1865 2245 2990 3757 4491 5240 Cable weight approx. kg/km 120 157 247 335 512 669 920 1363 1730 2135 2511 3300 4081 4888 5647 6446 145 194 326 438 663 867 1250 1811 2325 2873 3429 4450 5599 6663 7699

ELKABEL

365

TPPV ... x2x0.4; TPPV ...20.6 TPPV ... x2x0.5; TPPV ...20.7

BDS 9096-83

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and PABX's for telephone purposes and for transmission of signals. They are suitable for laying in collectors, with higher mechanical load. The use of these cables for power installations is not permitted.

Cable construction
Conductor nsulation Quad Units Unit marking Bare copper conductor diameter 0.4 mm , 0.5mm, 0.6mm, 0.7mm PE low density 4 wires are twisted into a quad 5 quads are twisted to a basic unit In each layer there is a unit with red supporting spiral form at which the counting starts and a unit showing the direction of counting - with yellow supporting spiral. The units are stranded into a cable Several layers of plastic tapes aluminum tape, thickness no less than 0.04mm, one side coated with copolymer and 1 tinned copper wire with diameter of 0.5mm under the aluminum foil PE low density with 2.5% carbon black PVC plastic - color gray

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire-screen Operating voltage peak value cables with cores 0.4 and 0.5mm cables with cores 0.6 and 0.7mm Temperature range laying and installing exploitation and storage Bending radius, min. approx. 0.4 0.5mm 95/km 150 0.6 0.7mm 49/km 65 48nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V 150V 220V +4C +60C -30C +60C 10 x cable diameter

Cable core Wrapping Screen

Sheath Protective sheath

Color coding
Number of quad T P P V Type codes telephone cable polyethylene insulation polyethylene sheath protective sheath of polyvinylchloride 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

366

ELKABEL

Polyethylene insulation unit stranding laminated sheath polyvinylchloride protective sheath

COMMUNICATION CABLES FOR LOCAL NETWORKS

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 Number of quads 3 5 10 15 25 35 50 75 100 125 150 200 250 300 350 400 500 600 54 1-st layer 3-quads 1 2 3 5 1 3 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

6 7

3 4 5 1

4 5 1 1 1 3 4

5 6 7 7 8

Construction data TPPV...


Number of pairs x2x0.4 Outer diameter approx. mm 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 x2x0.5 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 10.1 11.8 13.5 15.1 18.3 20.2 23.1 26.5 29.0 33.4 34.7 40.3 45.2 48.1 51.6 55.0 61.1 66.5 11.2 12.2 13.9 15.6 18.8 21.8 24.1 28.6 32.0 36.3 37.8 43.3 48.8 52.7 55.1 59.3 68.6 73.5 Copper weight kg/km 17 27 51 74 127 174 250 374 494 613 738 983 1235 1476 1722 1968 2454 2941 26 40 78 115 196 269 387 580 766 952 1146 1526 1918 2292 2674 3056 3813 4570 Cable weight approx. kg/km 99 132 182 232 325 413 547 779 948 1176 1349 1757 2156 2546 2918 3295 4145 4919 128 158 219 282 414 546 723 1015 1298 1597 1877 2412 3013 3545 4066 4622 5820 6890 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 x2x0.76 12.6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 x2x0.6

Construction data TPPV...


Number of pairs Outer diameter approx. mm 11.9 13.0 15.7 17.8 22.1 24.9 28.2 35.7 38.9 43.7 47.0 53.6 58.3 64.8 68.9 73.6 48 14.3 18.5 21.1 25.1 28.0 34.3 41.0 45.0 50.4 55.7 62.3 70.3 76.5 81.1 Copper weight kg/km 36 57 111 164 281 387 557 834 1102 1371 1650 2197 2761 3300 3851 4401 171 77 150 222 381 526 757 1134 1500 1865 2245 2990 3757 4491 5240 Cable weight approx. kg/km 144 185 280 373 561 724 983 1450 1830 2257 2650 3472 4281 5128 5916 6749 223 367 484 718 930 1331 1917 2453 3029 3614 4676 5878 6986 8058

ELKABEL

367

TPPBP ... x2x0.4; TPPBP ...20.6 TPPBP ... x2x0.5; TPPBP ...20.7

BDS 9096-83

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and PABX's for telephone purposes and for transmission of signals. Cables are suitable for laying in all types grounds. The use of these cables for power installations is not permitted.

Cable construction
Conductor Insulation Quad Units Unit marking Bare copper conductor diameter 0.4 mm, 0.5mm, 0.6mm and 0.7mm PE low density 4 wires are twisted into a quad 5 quads are twisted to a basic unit In each layer there is a unit with red supporting spiral form at which the counting starts and a unit showing the direction of counting - with yellow supporting spiral. The units are stranded into a cable Several layers of plastic tapes aluminum tape, thickness no less than 0.04mm, one side coated with copolymer and 1 tinned copper wire with diameter of 0.5mm under the aluminum foil PE low density with 2.5% carbon black Two steel tapes - thickness 0.3mm PE low density with 2.5% carbon black

Technical data
Conductor diameter 0.4 0.5mm Conductor resistance at 20C-max 150 95/km Conductor diameter 0.6 0.7mm Conductor resistance at 20C-max 65 49/km 10G.km Insulation resistance - min. Mutual capacitance at 800Hz-nom. 48nF/km Capacity unbalances at 800Hz: 980pF/500m K1 100% of all values 420pF/500m 95% of all values 800pF/500m K9-K12 100% of all values 200pF/m 90% of all values Test voltage 50Hz, 2 min. wire-wire 500V wire-screen 2000V Operating voltage peak value cables with cores 0.4 and 0.5mm 150V 220V cables with cores 0.6 and 0.7mm Temperature range laying and installing -10C +60C exploitation and storage -50C +60C 10 x cable Bending radius, min. approx. diameter

Cable core Wrapping Screen

Sheath Armour Protective sheath

Color coding
Number of quad T P P B P Type codes telephone cable polyethylene insulation polyethylene sheath steel tape armour PE protective sheath 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

368

ELKABEL

Polyethylene insulation unit stranding laminated sheath armour PE protective sheath Cable core construction
Number of pairs 3 5 10 15 25 35 50 75 100 125 150 200 250 300 350 400 500 600 Number of quads 3-quads 1 2 3 5 1 3 54 1-st layer 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

COMMUNICATION CABLES FOR LOCAL NETWORKS

6 7

3 4 5 1

4 5 1 1 1 3 4

5 6 7 7 8

Construction data TPPBP...


Number of pairs x2x0.4 Outer diameter approx. mm 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 x2x0.5 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 1000 1200 11.2 13.0 14.7 16.5 19.9 21.8 24.9 28.5 31.1 35.6 37.7 42.7 46.2 50.4 52.6 55.4 63.2 68.3 12.6 13.7 15.6 17.1 20.8 23.9 26.4 31.1 34.7 39.2 40.4 46.2 51.7 54.4 58.0 62.0 71.4 76.5 Copper weight kg/km 17 27 51 74 127 174 250 374 494 613 738 983 1235 1476 1722 1968 2454 2941 26 40 78 115 196 269 387 580 766 952 1146 1526 1918 2292 2674 3056 3813 4570 Cable weight approx. kg/km 176 229 289 359 493 604 766 1061 1257 1533 1718 2482 2620 3044 3441 3828 4735 5568 221 263 345 423 594 764 967 1324 1652 1991 2290 2877 3517 4079 4633 5202 6472 7588 6 10 20 30 50 70 100 150 200 250 300 400 500 600 700 800 x2x0.7 6 10 20 30 50 70 100 150 200 250 300 400 500 600 x2x0.6

Construction data TPPBP...


Number of pairs Outer diameter approx. mm 13.1 14.1 17.4 19.8 24.2 27.2 30.7 38.4 41.5 46.4 49.9 56.4 59.5 67.5 71.9 76.6 14.1 15.9 20.4 23.3 27.4 30.5 36.9 43.7 47.8 53.2 57.6 65.8 73.2 79.5 Copper weight kg/km 36 57 111 164 281 387 557 834 1102 1371 1650 2197 2761 3300 3851 4401 48 77 150 222 381 526 757 1134 1500 1865 2245 2990 3757 4491 Cable weight approx. kg/km 241 277 422 545 784 985 1288 1840 2238 2722 3146 4009 4820 5745 6569 7366 277 352 545 697 981 1223 1700 2343 2926 3549 4159 5138 6554 7695

ELKABEL

369

T P P B P e . . . x 2 x 0 . 4 ; T P P B P e . . . x 2 x 0 . 6 BDS 9096-83 TPPBPe... x2x0.5; TPPBPe... x2x0.7

COMMUNICATION CABLES FOR LOCAL NETWORKS WITH LOW REDUCTION FACTOR

Application
These cables are used as connecting cables in local networks and in PABX's for telephone purposes and for the transmission of signals. These cables are suitable for laying in ditches, in all types of grounds, in areas with high electromagnetic influences. The use of these cables for power installations is not permitted. .

Cable construction
Conductor Insulation Quad Units Cable core Wrapping Screen Bare copper conductor diameter 0.4 mm, 0.5mm, 0.6mm and 0.7mm PE low density 4 wires are twisted into a quad 5 quads are twisted to a basic unit The units are stranded into a cable Several layers of plastic tapes aluminum tape, thickness no less than 0.04mm, one side coated with copolymer and 1 tinned copper wire with diameter of 0.5mm under the aluminum foil PE low density with 2.5% carbon black Several layers of aluminum tapes thickness 0.2mm Two galvanized steel tapes thickness 0.5mm PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20oC-max Conductor diameter Conductor resistance at 20oC-max Insulation resistance - min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire-screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 10G.km 48nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

Sheath Additional screen Armour Protective sheath

Color coding
Number of quad 1 2 3 4 5 Unit marking Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

150V Cables with cores 0.4 and 0.5mm Cables with cores 0.6 and 0.7mm 220V Reduction factor, at: Inductive voltage from 40 to 350 V/km, and frequency 50Hz no more than: - cable with D above sheath up to 16mm - cables with D above sheath over 0.6 16mm to 37mm 0.5 - cables with D above sheath > 37mm 0.4 Temperature range -10C +60C laying and installing -50C +60C exploitation and storage Bending radius, min. approx. 15 x cable diameter

In each layer there is a unit with red supporting spiral from which the counting starts and a unit showing the direction of counting - with yellow supporting spiral

T P P B P

Type codes telephone cable polyethylene insulation polyethylene sheath steel tape armor PE protective sheath areas with higher electromagnetic influences

370

ELKABEL

Polyethylene insulation unit stranding laminated sheath screen armour PE protective sheath Cable core construction
Number of pairs 20 30 50 70 100 150 200 300 Number of quads 10 15 25 35 50 75 100 150 54 1-st layer 2 3 5 1 3 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

COMMUNICATION CABLES FOR LOCAL NETWORKS WITH LOW REDUCTION FACTOR

6 7

3 4 1

Construction data TPPBP...


Number of pairs x2x0.4 Diameter over sheath mm 20 30 50 70 100 150 200 300 20 30 50 70 100 150 200 300 20 30 50 70 100 150 200 300 20 30 50 70 100 150 200 300 10.7 12.3 15.5 17.4 20.3 23.7 27.3 32.5 11.5 13.7 16.9 19.1 22.3 26.1 30.5 35.7 13.6 15.8 20.1 22.3 26.2 31.3 36.2 43.3 15.3 17.9 23.0 25.6 30.7 36.3 42.4 50.9 Outer diameter approx. kg/km 17.5 19.3 23.5 25.4 28.5 32.1 35.9 41.3 18.3 20.7 24.9 27.3 30.7 34.7 39.3 44.7 20.6 23.8 28.3 30.7 34.8 40.1 45.2 54.1 22.3 25.9 31.4 34.0 39.5 45.3 53.0 62.1 Copper weight kg/km 51 74 127 174 250 374 494 738 78 115 196 269 387 580 766 1146 111 164 281 387 557 834 1102 1650 150 222 381 526 757 1134 1500 2245

x2x0.5

x2x0.6

x2x0.7

ELKABEL

371

TPJP... x2x0.4; TPJP... 20.6 TPJP... x2x0.5; TPJP... 20.7

FN KI 05 001-96

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and in PABX's for telephone purposes and for the transmission of signals. The filling of petrol jelly does not permit moisture penetration into the cable core. They are suitable for laying in cable pipes and conduits. The use of these cables for power installations is not permitted. These cables may only be used in locations with fire and explosion hazards in accordance with the appropriate safety precautions.

Cable construction
Conductor Insulation Quad Units Cable core Filling Wrapping Screen Sheath Bare copper conductor diameter 0.4 mm, 0.5mm, 0.6mm and 0.7mm PE insulation type 2YI2, according to VDE 0207 part 2. 4 wires are twisted into a quad 5 quads are twisted to a basic unit The units are stranded into a cable Petroleum jelly Minimum one layer of paper tape aluminum tape, thickness 0.15mm, coated with copolymer on both sides PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max Insulation resistance - min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 100% of all values 95%of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire-screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 5G.km 55nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

150V cables with cores 0.4 and 0.5mm cables with cores 0.6 and 0.7mm 220V Temperature range -10C +60C laying and installing -40C +60C exploitation and storage Bending radius, min. approx. 10 cable diameter

Color coding
Number of quad T P J P Type codes telephone cable polyethylene insulation petroleum jelly filling polyethylene sheath 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

372

ELKABEL

PE insulation unit stranding jelly filling laminated sheath.

COMMUNICATION CABLES FOR LOCAL NETWORKS

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 300 400 500 600 700 800 1000 1200 Number of quads 3 5 10 15 25 35 50 75 100 150 200 250 300 350 400 500 600 54 1-st layer 3-quads 1 2 3 5 1 3 2-nd layer Number of units 254 1-st layer 2-nd layer 50x4 1-st layer 2-nd layer

6 7

3 4 1

4 5 1 1 1 3 4

5 6 7 7 8

Construction data TPJP...


Number of pairs x2x0.4 Outer diameter approx. mm 6 10 20 30 50 70 100 150 200 300 400 500 600 700 800 1000 1200 x2x0.5 6 10 20 30 50 70 100 150 200 300 400 500 600 700 800 1000 8.6 9.3 11.7 12.9 16.2 18.0 21.7 25.7 30.6 35.4 42.3 43.4 50.9 54.3 57.9 64.1 69.8 9.2 10.5 12.9 15.4 19.9 22.0 25.2 30.8 36.5 42.5 45.5 52.0 56.5 62.0 67.0 76.0 Copper weight kg/km 15 24 49 73 126 174 252 380 504 724 965 1212 1449 1692 1934 2413 2893 23 37 75 113 196 271 392 592 784 1131 1508 1894 2260 2644 3022 3773 Cable weight approx. kg/km 77 99 159 222 336 449 604 867 1124 1570 2054 2514 2997 3480 3931 4923 5856 98 129 223 306 480 632 864 1264 1630 2320 3047 3772 4554 5210 5937 7373 6 10 20 30 50 70 100 150 200 300 400 500 600 700 800 x2x0.7 6 10 20 30 50 70 100 150 200 300 400 500 600 700 x2x0.6 Number of pairs

Construction data TPJP..


Outer diameter approx. mm 10.4 12.2 16.2 18.0 22.9 26.5 30.4 36.5 41.8 48.9 56.8 63.0 67.3 73.6 78.5 11.4 13.5 17.8 21.7 27.0 30.6 36.1 42.0 48.9 58.5 65.3 74.7 79.1 81.9 Copper weight kg/km 32 54 108 163 282 390 564 818 1085 1628 2170 2727 3261 3806 4351 44 72 148 222 384 532 768 1114 1476 2215 2953 3710 4437 5240 Cable weight approx. kg/km 122 165 292 402 638 851 1187 1656 2170 3225 4267 5283 6287 7298 8311 149 210 362 522 816 1087 1527 2193 2874 4311 5654 7012 8388 10211

ELKABEL

373

TPJPBP ... x2x0.4; TPJPBP ... x2x0.6 TPJPBP ... x2x0.5; TPJPBP ... x2x0.7

FN KI 05 001-96

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and in PABX's for telephone purposes and for the transmission of signals. The filling of petrol jelly does not permit moisture penetration into the cable core. They are suitable for laying in conduits in all types of grounds. The use of these cables for power installations is not permitted.

Cable construction
Conductor Insulation Quad Units Cable core Filling Wrapping Screen Sheath Armour Protective sheath Bare copper conductor diameter 0.4 mm, 0.5mm, 0.6mm and 0.7mm PE insulation type 2YI2, according to VDE 0207 part 2. 4 wires are twisted into a quad 5 quads are twisted to a basic unit The units are stranded into a cable Petroleum jelly Minimum one layer of paper tape aluminum tape, thickness 0.15mm, coated with copolymer on both sides PE low density with 2.5% carbon black 2 steel tapes, thickness of 0.3mm PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max Insulation resistance - min. Mutual capacitance at 800Hz-nom. Capacity unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire-screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 5G.km 55nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

150V cables with cores 0.4 and 0.5mm cables with cores 0.6 and 0.7mm 220V Temperature range -10C +60C laying and installing -40C +60C exploitation and storage Bending radius, min. approx. 10 cable diameter

Color coding
Number of quad T P J P B P Type codes telephone cable polyethylene insulation petroleum jelly filling polyethylene sheath steel tape armour PE protective sheath 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

374

ELKABEL

PE insulation unit stranding petrol filling laminated sheath armour protective PE sheath Cable core construction
Number of pairs 6 10 20 30 50 70 100 150 200 Number of quads 3 5 10 15 25 35 50 75 100 Number of units 54 1-st layer 3-quads. 1 2 3 5 1 3 2-nd layer 254

COMMUNICATION CABLES FOR LOCAL NETWORKS

6 7

1 3 4

Construction data TPJPBP...


Number of pairs s Outer diameter approx. mm 6 10 20 30 50 70 100 150 200 6 10 20 30 50 70 100 150 200 6 10 20 30 50 70 100 6 10 20 30 50 70 100 12.6 13.3 15.9 17.1 20.6 22.4 26.3 30.7 35.8 13.2 14.5 17.1 19.8 24.5 26.6 30.0 36.0 42.1 14.4 16.4 20.6 22.4 27.7 31.5 35.6 15.6 17.7 22.2 26.3 32.0 35.8 41.5 Copper weight kg/km 15 24 49 73 126 174 252 380 504 23 37 75 113 196 271 392 592 784 32 54 108 163 282 390 564 44 72 148 222 384 532 768 Cable weight approx. kg/km 231 263 366 442 615 748 980 1332 1713 250 312 443 568 842 1015 1311 1856 2375 303 350 574 716 1056 1361 1762 350 451 685 931 1583 1699 2302

x2x0.5

x2x0.6

x2x0.7

ELKABEL

375

T P J P P . . . x 2 x 0 . 4 ; T P J P P . . . 2 0 . 6 FN KI 05 001-96 TPJPP ... x2x0.5; TPJPP ...20.7

COMMUNICATION CABLES FOR LOCAL NETWORKS

Application
These cables are used as connecting cables in local networks and in PABX's for telephone purposes and for the transmission of signals. The filling of petro jelly does not permit moisture penetration into the cable core. They are suitable for underground installation, in cable ducts and conduit. The use of these cables for power installations is not permitted. These cables may only be used in locations with fire and explosion hazards in conjunction with the appropriate safety precautions

Cable construction
Conductor Insulation Quad Units Cable core Filing Wrapping Screen Sheath Protective sheath Bare copper conductor diameter 0.4 mm , 0.5mm, 0.6mm, 0.7mm Polyethylene insulation type 2YI2 according to VDE 0207 part 2. each 4 wires are twisted to a quad 5 quads laid up to a basic unit the units are stranded into a compact cable petroleum - based jelly minimum of 1 layer of paper tape. of aluminum tape , thickness 0.15mm, coated with copolymer on both sides PE low density with 2.5% carbon black PE low density with 2.5% carbon black

Technical data
Conductor diameter Conductor resistance at 20C-max Conductor diameter Conductor resistance at 20C-max. Insulation resistance min. Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz: K1 100% of all values 95% of all values K9-K12 100% of all values 90% of all values Test voltage 50Hz, 2 min. wire-wire wire - screen Operating voltage peak value 0.4 0.5mm 150 95/km 0.6 0.7mm 65 49/km 5G.km 55nF/km 980pF/500m 420pF/500m 800pF/500m 200pF/m 500V 2000V

150V cables with cores 0.4 and 0.5mm cables with cores 0.6 and 0.7mm 220V Temperature range -10C +60C mobile -40C +60C fixed 10 x cable Minimum bending radius approx. diameter

Color coding
Number of quad T P J P P Type codes telephone cable polyethylene insulation petroleum jelly filling polyethylene sheath polyethylene protective sheath 1 2 3 4 5 Side-circuit -1 a-wire white yellow gray brown black b-wire red red red red red Side-circuit -2 a-wire green green green green green b-wire blue blue blue blue blue

376

ELKABEL

PE insulation unit stranding filling laminated sheath protective PE

Cable core construction


Number of pairs 6 10 20 30 50 70 100 150 200 Number of quads 3 5 10 15 25 35 50 75 100 Number of units 54 1-st layer 3-. 1 2 3 5 1 3 2-nd layer 254

COMMUNICATION CABLES FOR LOCAL NETWORKS

6 7

1 3 4

Cable construction TPJPP...


Number of pairs x2x0.4 External diameter approx. mm 6 10 20 30 50 70 100 150 200 6 10 20 30 50 70 100 150 200 6 10 20 30 50 70 100 6 10 20 30 50 70 100 11.4 12.1 14.5 15.7 19.0 20.8 24.5 28.5 33.6 12.0 13.3 15.7 18.2 22.7 24.8 28.0 33.8 39.7 13.2 15.0 19.0 20.8 25.7 29.3 33.4 14.2 16.3 20.6 24.5 29.8 33.6 39.3 Copper weight kg/km 15 24 49 73 126 174 252 380 504 23 37 75 113 196 271 392 592 784 32 54 108 163 282 390 564 44 72 148 222 384 532 768 Cable weight approx. kg/km 120 143 220 280 408 528 699 1223 1264 141 178 282 375 567 727 972 1405 1810 170 220 364 482 737 964 1326 201 271 440 616 931 1227 1703

x2x0.5

x2x0.6

x2x0.7

ELKABEL

377

PPVR
RADIO TRANSMISSION WIRE
PE insulation PVC sheath

ON 75713-83

Application
These wires are intended for maintenance and construction of radio relay system networks.

Cable construction
Conductor Insulation Sheath Copper stranded cores, 0.75mm2 class 4 Solid PE insulation, according to BDS 10086-82 Two parallel laid cores with differ ent color are covered with sheath of PVC, colored black type P-1, according to BDS 5792-84

Technical data
Conductor construction Circuit resistance at 20C - max., /km Insulation resistance min,M.km Mutual capacitance -max., pF/m Nominal voltage, V 110.30 52 200 55 250 1000 -30C +50C

Color coding
Two cores with different color

Test voltage 50Hz, 1 min., V Temperature range During exploitation and storage

Type codes PPVRwire PE insulation PVC sheath for radio communication N mm

Construction data
Outer diameter mm mm 2x0.75mm2 3.5 6.9 Copper weight kg/km 15 Cable weight kg/km 34

378

ELKABEL

PPVAR
PE insulation PVC sheath

ON 75713-83

RADIO TRANSMISSION WIRE

Application
These wires are intended for maintenance and construction of radio relay system networks.

Cable construction
Conductor Insulation Sheath Copper stranded cores, 0.35mm2 class 4 Solid PE insulation, according to BDS 10086-82 Two parallel laid cores with different color are covered with sheath of PVC, color black type P-1, according to BDS 5792-84

Technical data
Conductor construction Circuit resistance at 20C - max., /km nsulation resistance min,M.km Mutual capacitance -max., pF/m Nominal voltage, V Test voltage 50Hz, 2 min., V 70.25 170 100 80 100 500 -30C +50C

Color coding Two cores with different color


PPVRType codes wire PE insulation PVC sheath subscriber loop for radio communication

Temperature range During exploitation and storage

Construction data
N mm Outer diameter mm mm 2x0.35mm2 4.3 Copper weight kg/km 7 Cable weight kg/km 26

ELKABEL

379

PMVSUR x0.4 ;PMVSUR x0.6 ; PMVSUR x0.5 ,PMVSUR x0.8 PMVS 0.4, 0.5, 0.6, 0.8
INSTALLATION WIRES FOR COMMUNICATION SYSTEMS AND INFORMATION PROCESSING SYSTEMS

BDS 11292-87

Tinned copper conductor PVC insulation single or stranded

Application
Installation cables are with copper tinned conductors and PVC insulation. Cables are intended for indoor electrical installation of communication equipment and installation systems of electrical constructive groups and equipment, as well as processing information systems. These cables are not to be used for high power installation systems. Maximum allowed heat temperature of the conductors is +70C.

Cable construction
Conductor Insulation PMVS PMVSUR - pairs - triples - quads tinned copper conductor, diameter 0.4 mm , 0.5mm, 0.6 mm and 0.8mm PVC insulation class 1, according to BDS 5792-84 1 wire 2 wires are twisted into a pair 3 wires are twisted into a triple 4 wires twisted into a quad

Technical data
Conductor diameter, mm Conductor resistance at 20C - max.,/km Insulation resistance min., M .km Nominal voltage, V Test alternating voltage, 1 min. V 0.4 144 300 380 1500 0.5 92 300 380 1500 0.6 64 300 660 2500 0.8 36.6 300 660 2500

Color coding
PMVSUR 2 ... 3 ... 4 ... wire -white wire -white wire -white wire b-brown wire b-brown wire b-brown wire -green wire -green wire d-yellow PMVS 1 ... white brown green yellow gray blue red N x mm

Construction data
Outer diameter approx. mm mm PMVSUR 2x0.4 2x0.5 2x0.6 2x0.8 3x0.4 3x0.5 3x0.6 3x0.8 4x0.4 4x0.5 4x0.6 4x0.8 PMVS 1x0.4 1x0.5 1x0.6 1x0.8 1.6 1.82 2.4 2.8 1.7 2.0 2.6 3.0 1.9 2.2 2.9 3.4 0.8 0.9 1.2 1.4 Copper weight kg/km 2.30 3.80 5.70 9.20 3.50 5.60 7.90 13.60 4.60 7.70 11 18.50 1.20 1.80 2.60 4.60 Wire weight approx. kg/km 3.30 5.00 7.90 11.80 5.10 7.50 11 18 6.70 11 15 24.50 1.65 2.80 3.70 6.00

PM V S U R

Type codes wire installation PVC insulation for communication systems stranded for coupling

380

ELKABEL

PTPV 2x0.5
PE insulation PVC sheath

BDS 5627-80

TELEPHONE WIRE

Application
The telephone cable PTPV is used for connecting telephones and loudspeakers to terminal equipments of city and local telephone and radio relay system lines, for indoor and outdoor laying.

Cable construction
Conductor Insulation Sheath Bare copper conductor diameter 0.5mm Solid PE insulation according to BDS 10086-82 Over 2 parallel laid cores with dif ferent colors, there is unified sheath of polyvinylchloride, colorwhite, black, gray type P-1 according to BDS 5792-84

Technical data
Conductor diameter Conductor resistance at 20C - max., /km Insulation resistance after 3 hour idle time in water with temperature 20+/- 5 measured between each core and water, and between both cores, min., M.km Rated operating voltage with frequency 50Hz, V Tested voltage, V: Cable insulation after 30min. idle time in water with temperature of 20 5 should withstand alternating current with frequency of 50Hz for a period of 3 min., applied between each wire and water, and between both wires Temperature range During exploitation and storage 0.5mm 95

200

100

Color coding
Two different colored cores Type codes PT P V wire telephone PE insulation PVC sheath

500

-30C +50C

Construction data
No. mm Outer diameter approx. max. mm mm 4.4 Copper weight kg/km 3.6 Cable weight approx. kg/km 22

2x0.5

ELKABEL

381

JUMPER WIRE

YV YV

x 0.4 / 0.8 x 0.5 / 0.9

According to VDE 0812

PVC insulation wires stranded

Application
The jumper wire is used for wiring telephone and signal distributors. Tinned copper conductor with a diameter of 0.4, and 0.5mm PVC insulating cover. The operating voltages of the cables are 500 V.

Cable construiction
Conductor Insulation Cable core solid tinned copper conductor diameter : 0.4 and 0.5mm PVC insulation typeYI3 according to VDE 0207, part4 the wires are stranded into pairs, triples, quads and quintuples

Technical data
Conductor diameter, mm Cond. resistance at 20C max /km - single-wire, /km - multi-wire, Insulation resistance min. Test voltage 50Hz, 1 min. : Operating voltage peak value Temperature range mobile fixed 0.4 144 148 0.5 92.2 95.0

200M .km 1200V 500V -30C +50C -5C +60C 10 x cable diameter

Color coding
Number Wire color of wires 1 brown ,red, yellow. green, blue ,gray ,white ,black 2 white/brown, white/green, white/blue 3 white/black/greena 4 white/yellow/black/green 5 white/yellow/black/green/gray

Minimum bending radius approx.

Construction data
Number of wires External diameter approx mm mm YV x 0,4/0,8 1 2 3 4 5 YV x 0,5/0,9 1 2 3 4 5 0,8 1,6 1,7 1,9 2,2 0,9 1,8 1,9 2,2 2,4 Copper weight kg/km 1,1 2,2 3,3 4,4 5,5 1,7 3,5 5,2 7,0 8,7 Cable weight approx. kg/km 1,6 3,2 4,8 6,4 8,0 2,3 4,8 7,0 9,2 11,6

Type codes V - tinned copper conductor Y - insulating cover of PVC

382

ELKABEL

TSV//V 20.4, TSV//V 30.4 TSV//V 20.5, TSV//V x30.5

According to FN KI 05 002-96 and BDS 11509-79

INSTALLATION CABLES FOR TELECOMMUNICATIONS SYSTEMS

Application
These cables are used for installation of equipment of telephone stations. They are suitable for fixed indoor installation and for external walls of buildings. The screen of metal foil protects the cable from external electrical interferences. The use of these cables for power installations and underground installation is not permitted.

Cable construction
Conductor Insulation Units - pairs - triples Cable core Wrapping Screen Sheath Bare copper conductor diameter 0.4 mm and 0.5mm PVC insulation class 1, according to BDS 5792-84 2 wires are twisted to a pair 3 wires are twisted to a triple the units are stranded into layers of plastic tape of aluminum tape one side coated with copolymer and 1 tinned copper wire with diameter 0.5 mm PVC class 2 according to BDS 5792-84 Color gray

Technical data
Conductor diameter Conductor resistance at 20C - max. Insulation resistance - min. Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz K1- max. Test voltage 50Hz, 1 min. 0.4 150 0.5mm 95

500M.km

120nF/km

50pF/100m

Color coding
Number of units.The units are counted succes- Colors sively commencing at the outside and counting b- wires inwards in the same manner throught all layers 1 2 3 4 5 51 52 53 54 55 6 7 8 9 10 56 57 58 59 60 11 12 13 14 15 61 62 63 64 65 16 17 18 19 20 66 67 68 69 70 21 22 23 24 25 71 72 73 74 75 26 27 28 29 30 76 77 78 79 80 31 32 33 34 35 81 82 83 84 85 36 37 38 39 40 86 87 88 89 90 41 42 43 44 45 46 blue 47 yellow 48 green 49 brown 50 black blue yellow green brown black

1000V

Temperature range laying and installing exploitation and storage

-5C +50C -20C +70C

91 96 92 97 93 98 94 99 95 100

Bending radius, min. approx.

7.5 cable diameter

Identification of the a-wire for the first unit (counting unit) is red in each layer , and white for all other units . When the units are triples,the colour for a c-wire is turquoise

TSV(A)

Type codes telephone cable installation cable insulation or sheath of PVC static screen of aluminium tapes

384

ELKABEL

PVC insulation pairs (triples) stranded in layers sheath of PVC

INSTALLATION CABLES FOR TELECOMMUNICATIONS SYSTEMS

Cable core construction


Number of pairs (triples) Number of pairs (triples) in layers Number of pairs (triples)

Cable core construction


Number of pairs (triples) in layers

1 1 2 3 4 5 6 1 2 2 3 5 5 1

1 1 1 1 2 2 4 1 1 4 4 1 4 2

2 6 7 8 8 8 10 6 7 10 10 6 10 8

3 13 13 13 14 15 16 11 13 15 16 12 16 14

1 2 3 4 5 6 8 10 11 12 15 16 18

7 8 9 9 10 11 6

11

20 21 22 24 25 30 35 40 50 52 60 80 100

17 19 21 22 18 22 20

23 28 25

31

Construction data TSV/A/V


Number of pairs Outer diameter mm x2x0.4 1 2 3 4 5 6 8 10 11 12 15 16 18 20 22 24 25 30 40 50 52 60 80 100 x2x0.5 1 2 3 4 5 6 8 10 11 12 15 16 18 4.1 4.4 5.4 5.8 6.2 6.6 6.9 7.6 7.7 7.9 8.5 8.7 9.1 9.5 9.8 10.1 10.3 11 12.8 13.9 14.1 15.0 16.8 18.9 4.3 4.5 5.8 6.2 6.7 7.1 7.4 8.2 8.3 8.6 9.3 9.5 9.9 Copper weight kg/km 3.5 5.9 8.30 10.60 13 15.35 20 25 28 30 37 39.10 47.30 48.30 53 58 60.10 72 96 119 124 143 190 237 4.8 8.50 12.30 11 19.50 23.20 30.50 38 41.60 45.50 56.30 60.20 67 Cable weight kg/km 15.90 32 36.80 42.60 50 57 61.30 74 78 83 97 103 114 118.80 128 137 141 162 217 258 266.20 299 380 479 24.50 37 43.50 45.50 60 70 77.30 92 98 104.30 128 131.50 143 20 22 24 25 30 40 50 52 60 80 100 x3x0.4 5 6 10 11 15 16 18 20 21 22 24 25 35 x3x0.5 5 6 10 11 15 16 18 20 21 22 24 25 35

Construction data TSV/A/V


Number of pairs Outer diameter mm 10.3 10.7 11.1 11.3 12.1 14.0 15.3 15.6 16.5 19.0 20.8 6.6 7.3 8.5 8.5 9.5 9.7 10.1 10.5 10.7 10.9 11.3 11.5 13.5 7.2 7.9 9.2 9.2 10.3 10.6 11.1 11.5 11.8 12.0 12.4 12.6 14.9 Copper weight kg/km 75 82 89 92.20 112 146 185 192 217.50 290 368 18 21 35 38 52 55 62 69 73 76 83 86 121 27 34 55 62 82 88 97 110 117 122 130 135 190 Cable weight kg/km 156 165.20 180 185 212 286 341 353 401 533 640 56 64 87 92 118 124 133 146 152 158 166 175 148 69 89 115 128 155 165 178 195 216 224 225 235 335

ELKABEL

385

PVU-1
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Cu conductors PVC insulation

Uo/U - 300/500 V; Uo/U - 450/750 V BDS 4305-90

Applications
Installation in lighting installations, power and distribution systems, machines, apparatus and other. For fixed

Cable construction
Construction Conductor According to BDS 4305-90 copper wires according to BDS 904-84, class 1 (IEC 60228) PVC compound, type I-2 according to BDS 5792-84

Technical data
Conductor resistance at 20oC Operating temperature of the conductor, max. Rated voltage 0.35 mm2 to 1 mm2 1.5 mm2 to 4 mm2 Test voltage AC, 50 Hz: 0.35 mm2 to 1 mm2 1.5 mm2 to 4 mm2 Temperature of exploitation Minimum bending radius Fixed installation Testing Flame test according to BDS 904-84 class1 70oC Uo/U 300/500 V Uo/U 450/750 V 2000 V 2500 V - 25 C to + 50oC
o

Insulation

Insulated cores are twisted

6 x cable diameter BDS 4305-90 BDS IEC 332-1

Color coding
Number of core 2 core 3 core With yellow/green yellow/green , blue , brown Without yellow/green Blue, brown brown ,black , gray

Construction data PVU-1 300/500V 450/750V


Number of wires and nominal cross section mm2 PVU-1 300/500V 20.35 20.50 20.75 21.0 21.5 22.5 24.0 PVU-1 450/750V 30.35 30.50 30.75 31.0 31.5 32.5 34.0 4.3 4.6 5.0 5.2 6.2 7.5 8.4 11 13.8 20.1 27.6 41.4 66 106.5 22 28 39 49 75 115 157 4.0 4.2 4.5 4.8 5.8 7.0 7.8 6.6 9.2 13.4 18.4 27.6 44 71 16 19 24 31 45 70 100 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

386

ELKABEL

Uo/U - 300/500 V; Uo/U - 450/750 V BDS 4305-90

Cu conductors PVC insulation

PVU-2
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Applications
For fixed installation in lighting installations, power and distribution systems, machines, apparatus and other.

Cable construction
Construction Conductor According to BDS 4305-90 copper wires according to BDS 904-84, class 5 (IEC 60228) PVC compound, type I-2 according to BDS 5792-84

Technical data
Conductor resistance at 20oC Operating temperature of the conductor, max. Rated voltage 0.35 mm2 to 1 mm2 1.5 mm2 to 4 mm2 Test voltage AC, 50 Hz: 0.35 mm2 to 1 mm2 1.5 mm2 to 4 mm2 Temperature of exploitation Minimum bending radius fixed installation Testing Flame test according to BDS 904-84 class 5 70oC Uo/U 300/500 V Uo/U 450/750 V 2000 V 2500 V - 25 C to + 50oC
o

Insulation

Insulated cores are twisted

4 x cable diameter BDS 4305-90 BDS IEC 332-1

Color coding
Number of core 2 core 3 core With yellow/green yellow/green , blue , brown Without yellow/green black , brown Brown, black, gray

Construction data PVU-2 300/500V 450/750V


Number of wires and nominal cross section mm2 PVU-2 300/500V 20.35 20.50 20.75 21.0 21.5 22.5 24.0 PVU-A2 450/750V 30.35 30.50 30.75 31.0 31.5 32.5 34.0 4.1 4.5 4.8 5.1 6.2 7.3 8.4 4.5 4.9 5.2 5.6 6.7 7.9 9.1 7 9.2 15 19.2 28 48 76 10 14 20.5 27.6 41.4 66 107 15.5 18 25 29 44 68 100 23 28 39 49 75 115 157 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

ELKABEL

387

PVV-3
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Uo/U - 300/500 V; Uo/U - 450/750 V BDS 4305-90

Applications
For fixed installation in lighting installations, power and distribution systems, machines, apparatus and other.

Cable construction
Construction Conductor According to BDS 4305-90 copper wires according to BDS 904-84 (IEC 60228) class 1 - 0.5 mm2 to 10mm2 class 2 - 16 mm2 to 35 mm2 PVC compound, type I-2 according to BDS 5792-84 PVC compound, type P-1 according to BDS 5792-84 black, gray, white

Technical data
Conductor resistance at 20oC Operating temperature of the conductor, max. Rated voltage 0.5 mm2 to 1 mm22 1.5 mm2 to 35 mm Test voltage AC, 50 Hz: 0.5 mm2 to 1 mm2 1.5 mm2 to 35 mm2 Temperature range Bending radius up to fixed installation Testing Flame test according to BDS 904-84 class 1 or 2 70oC Uo/U 300/500 V Uo/U 450/750 V 2000 V 2500 V - 25oC to + 50oC 6 x cable diameter BDS 4305-90 BDS IEC 332-1

Insulation Sheath Color

Color coding
Number of core 2 core 3 core 4 core 4 core with reduction core 5 core * reduction core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green*, brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green blue, brown brown, black, gray blue, brown, black, gray blue*, brown, black, gray black , blue , brown , black , gray

Construction data PVV-3 300/500V 450/750V


Number of wires and nominal cross section mm2 PVV-3 300/500V 20.50 20.75 21.0 PVV-3 450/750V 21.5 22.5 24.0 26.0 210 216 225 235 7.4 8.6 9.9 11.3 13.7 16.7 20.4 22.7 28 44 71 110 176 280 440 610 78 112 190 222 320 436 661 856 5.5 5.8 6.1 9 13.5 19 35 48 55 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

388

ELKABEL

Cu conductors PVC insulation PVC sheath

CONDUCTORS FOR ELECTRIC INSTALLATIONS

Construction data PVV-3 300/500V 450/750V


Number of wires and nominal cross section mm2 PVV-3 300/500V 30.50 30.75 31.0 PVV-3 450/750V 31.5 32.5 34.0 36.0 310 316 325 335 PVV-3 300/500V 40.50 40.75 41.0 PVV-3 450/750V 41.5 42.5 44.0 46.0 410 416 425 435 325+16 335+25 PVV-3 300/500V 50.50 50.75 7.6 8.0 22 34 74 92 9 10.4 11.9 13.5 16.3 20 24 27.2 23 26.5 55 89 142 218 358 580 880 1236 809 1130 132 190 250 351 580 890 1235 1683 1150 1550 6.8 7.2 7.5 18 27 37 62 78 90 8.3 9.5 10.9 12.4 14.9 18.2 22.2 24.7 41 66 107 165 264 425 660 927 108 152 210 298 442 642 957 1275 6.2 6.6 6.9 14 21 28 50 60 72 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

ELKABEL

389

PVV-MB1
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Cu conductors PVC insulation PVC sheath

Uo/U - 220/380 V BDS 4305-90

Applications
For fixed installation in power and distribution installations for home buildings and production buildings, underneath wall plastering.

Cable construction
Construction Conductor Insulation According to BDS 4305-90 copper wires according to BDS 904-84, class 1 (IEC 60228) PVC compound, type I-2 according to BDS 5792-84

Technical data
Conductor resistance at 20oC Operating temperature of the conductor, max. Rated voltage Uo/U Test voltage AC, 50 Hz Temperature of exploitation Minimum bending radius Fixed installation Testing Flame test according to BDS 904-84 class 1 max 70oC 220/380 V 2000 V - 25 C to + 50oC 6 x narrow side of conductor BDS 4305-90 BDS IEC 332-1
o

Insulated cores are parallel in between in a unified sheath Sheath Color PVS compound, type P-1 according to BDS 5792-84 white, gray, black

Color coding
Number of core 2 core 3 core 4 core 5 core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green blue, brown brown, black, gray blue, brown, black , gray black , blue , brown , black , gray

Construction data PVV-MB1 220/380V


Number of wires and nominal cross section mm2 21.0 2x1.5 2x2.5 2x4.0 26.0 31.0 3x1.5 3x2.5 3x4.0 36.0 41.0 4x1.5 4x2.5 51.0 5x1.5 5x2.5 Outer dimensions approx. mm 3.4 9.8 3.9 10.8 4.6 12.2 5.2 13.6 6.2 15.4 3.4 16.2 3.9 17.7 4.6 19.8 5.3 21.9 6.2 24.6 3.4 22.6 3.9 24.6 4.6 27.4 3.4 29.0 3.9 x 31.5 4.6 x 35.0 Copper weight kg/m 18 27 44 71 110 27 41 66 110 165 36 54 88 45 68 110 Approx. cable weight kg/km 45 69 99 140 180 70 109 155 217 280 95 148 210 120 188 265

390

ELKABEL

U - 660V BDS 6767-81

Cu conductors PVC insulation Pb sheath PVC sheath

PVOT-2
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Applications
For fixed laying installation over, on and underneath plaster, in dry and wet rooms, as well outdoor where there is no danger of mechanical impact during installation and exploitation. These cables can also be used if present are steam, gases, and acid, which can be very destructive to the lead sheath, but which cannot damage the thermoplastic protective sheath. The cables can be used in all types of fire hazardous and explosion hazardous premises, with the exception of cables class BI.

Cable construction
Construction Conductor According to BDS 6767-81 copper wires according to BDS 904-84 (IEC 60228) class 1 - 0.5 mm2 to 6 mm2 class 1 and 2 - 10 mm2 Insulation PVC compound, type I-2 according to BDS 5792-84 Filling rubber or PVC compound Lead sheath according to BDS 4712 Underneath the lead sheath are laid one or several bare copper conductors with total nominal cross section no less than 1 mm2 Sheath PVC compound, type P-1 according to BDS 5792-84 Color gray, black

Technical data
Conductor resistance at 20oC Operating temperature of the conductor, max. Rated voltage Test voltage AC, 50 Hz Temperature of exploitation Minimum bending radius fixed installation Testing
o

according to BDS 904-84 class 1 or 2 max 70oC 660 V 2500 V - 30 C to + 50oC 6 x cable diameter BDS 6767-81

Color coding
Number of core 2 core 3 core 4 core 4 core with reduction core 5 core * reduction core With yellow/green yellow/green , blue, brown yellow/green, brown, black , gray yellow/green*, brown, black , gray yellow/green, blue, brown , black , gray Without yellow/green black , blue blue, black , brown blue, black , brown , black blue, black , brown , black blue, black , brown , black , black

Construction data PVOT-2 660V


Number of wires Approx. and nominal outer diamecross section ter mm2 mm 21.0 10.3 2x1.5 10.8 2x2.5 12.0 2x4.0 13.8 26.0 14.8 210 17.3 31.0 10.6 3x1.5 11.2 3x2.5 12.9 3x4.0 14.4 36.0 15.7 310 19.6 Copper weight kg/m 28 37 55 82 120 185 37 53 78 125 171 273 Approx. cable weight kg/km 343 406 450 570 660 1020 370 410 520 631 800 1100

Construction data PVOT-2 660V


Number of wires Approx. and nominal outer diamecross section ter mm2 mm 31.5+1.0 11.6 32.5+1.5 13.4 34+2.5 15.0 36+4.0 16.6 310+6.0 20.7 41.0 11.0 4x1.5 11.9 4x2.5 13.8 44.0 15.6 46.0 17.0 410 22.0 Copper weight kg/m 61 90 142 210 280 48 67 99 149 225 360 Approx. cable weight kg/km 445 560 690 890 1260 449 500 620 810 960 1300

ELKABEL

391

Cu/PVC/PVC
CONDUCTORS FOR ELECTRIC INSTALLATIONS

Cu conductors PVC insulation PVC sheath

Uo/U - 300/500V BS 6004

Applications
For fixed installation in lighting installations, power and distribution systems.

Cable construction
Construction Conductor According to BS 6004 copper wires according to BS 6360 (IEC 60228) class 1 - 1 mm2 to 2.5mm2 class 2 - 1.5 mm2 to 35 mm2 PVC compound, type TI 1 according to BS 7655 - 3.1 red or black PVC compound, type 6 according to BS 7655 - 4,2 gray or black

Technical data
Conductor resistance at 20oC Operating temperature of the conductor, max. Rated voltage Uo/U Test voltage AC, 50 Hz: Temperature of exploitation Minimum bending radius Fixed installation Testing acc. to Flame test according to BS 6360 class 1 or 2 70oC 300/500 V 2000 V - 25oC to + 50oC 6 x cable diameter BS 6004 IEC 60 332-1

Insulation Insulation color Sheath Color

Construction data Cu/PVC/PVC 300/500V


Number of wires and nominal cross section mm2 class 1 1.0 1.5 2.5 class 2 1.5 2.5 4.0 6.0 10 16 25 35 4.7 5.3 6.0 6.6 7.9 8.8 10.6 11.7 14.4 23 37 56 93 152 228 320 36 52 80 115 145 230 340 400 4.0 4.5 5.0 9.2 13.8 23 28 36 50 Approx. outer diameter mm Copper weight kg/m Approx. cable weight kg/km

ELKABEL

Uo/U - 0.6/1 kV FN KI 06 003-06

Cu conductors PVC insulation

PVO
CONDUCTORS FOR OVERHEAD LINES

Application
For connecting home and other electrical installations to open-air electrical distribution network.

Cable construction
Construction Conductor According to FN KI 06 003-06 copper wires according to BDS 904-84 (IEC 60228) class 1 - 6 mm2 and 10mm2 class 2 - 16 to 70 mm2 PVC compound, type I according to BDS 5792-84 black

Technical data
Conductor resistance at 20C Operating temperature of the conductor, max. Rated voltage Uo/U Test voltage AC, 50 Hz Temperature of exploitation Minimum bending radius Fixed installation Testing Flame test according to BDS 904-84 70C 0.6/1 kV 4 kV - 30C to + 50C 6 x cable diameter FN KI 06 003-06 BDS IEC 332-1

Insulation Insulation color

Construction data PVO 0.6/1 kV


Nominal cross section mm2 6 10 16 25 35 50 70 Outer diameter approx. mm 4.8 6.0 7.5 9.3 10.4 12.1 13.9 Copper weight kg/m 55 91 152 225 315 420 620 Cable weight approx. kg/km 73 120 191 300 400 530 745

ELKABEL

393

ShKPSS
CONDUCTORS FOR ELECTRIC TELPHERS

Cu conductors EPR insulation St core EPR sheath

Uo up to 380 V BDS 11321-90

Application
ShKPSS are used for command chains of electric telphers with nominal voltage up to 380V. Cables for 380V can be used also for 500V.

Cable construction
Construction Conductor Insulation Cable core Sheath Color According to BDS 11321-90 Cu wires , flexible, class 5 according to BDS 904-84 Silane crosslinked EPR rubber compound supporting steel cord, insulated with rubber compound Silane crosslinked EPR rubber compound black

Technical data
Operating temperature of the conductor, max. Rated voltage Test voltage AC, 50 Hz Ambient temperature during exploitation For ShKPSS For ShKSSN and ShKPSSM-T Testing Testing: Insulation resistance Testing: Resistance to oil +60C up to 380 V 2000 V - 40 to +50 - 30 to +50 BDS 1986-82 BDS 6200-83

Core identification according to BDS 11321-90

Color coding
Number of cores 3 4 5 Without yellow/green brown ,black, gray blue, brown, black, gray black, blue, brown, black, gray With yellow/green yellow/green, blue, brown yellow/green, brown, black, gray yellow/green, blue, brown, black, gray

Construction data ShKPSS


Number of Outer diameter Copper conductors and nominal cross approx. weight section mm2 220 V (mm) 380 V (mm) kg/m 3x0.75 4x0.75 5x0.75 6x0.75 7x0.75 8x0.75 9x0.75 3x1.0 4x1.0 5x1.0 6x1.0 7x1.0 8x1.0 9x1.0 3x1.5 4x1.5 11.0 11.5 12.0 12.5 13.0 14.0 15.0 12.0 12.5 13.0 13.5 14.0 14.5 15.5 13.0 13.5 20.0 27.0 35.0 40.0 48.0 55.0 60.0 27.0 35.0 45.0 55.0 62.0 70.0 80.0 39.0 51.0 Cable weight approx. 220 V 380 V kg/km kg/km 100 105 115 130 150 170 190 105 120 130 150 170 190 220 140 170

Construction data ShKPSS


Number of Outer diameter Copper conductors and nominal cross approx. weight section mm2 220 V (mm) 380 V (mm) kg/m 5x1.5 6x1.5 7x1.5 8x1.5 9x1.5 10x1.5 11x1.5 12x1.5 14.0 14.5 15.0 17.0 17.5 18.5 19.5 20.5 65.0 77.0 90.0 103.0 115.0 129.0 142.0 155.0 Cable weight approx. 220 V 380 V kg/km kg/km 190 210 240 270 300 330 380 420

394

ELKABEL

Uo/U . . 300/500 V .. OVE / ONORM E 8241-55

Cu conductors PVC insulation PVC sheath, cold - resistant

XYMM K35
CONDUCTORS WITH COLD-RESISTANT PVC

Application
The cables are suitable for connection of medium duty appliances in houses, kitchens and offices, for house appliances in wet premises i.e. refrigerators, washing machines, centrifuges as far as this is allowed in the instructions of the electrical appliances. It is allowed they to be used for connection of electrical heating appliances providing the conductors are not in contact with the heated parts and they shall not be subject of other thermal effects. The cables can be installed in furniture, finished building elements and in decorative edgings.

Cable construction
Conductor Insulation: Sheath Color: copper wires according to IEC 60228 Class 5 PVC, compound Type TI4 , according to HD 21.1 PVC, compound type TM4 according to HD 21.1 black or white as standard color,

Technical data
Conductor resistance at 20C Core temperature max Rated voltage for Uo/U Test voltage AC, 50 Hz Temperature range mobile: fixed: Flame test according to and IEC 60228 cl. 5 70C in operation 150C in the event of a short circuit 300/500 V 2000 V -25C to +70C -40C to +70C test class B ,VDE 0472part 804 and IEC 60 332-1

Different colors available upon request.

Color coding
Number of core 2 core 3 core 4 core 5 core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green blue, brown brown, black , gray blue, brown, black , gray black , blue , brown , black , gray

Construction data XYMM K35 Uo/U - 300/500 V


Number of wires and nominal cross section mm2 21.5 31.5 41.5 51.5 32.5 42.5 52.5 44 54 46 56 410 510 Outer diameter approx. mm 8.4 8.9 9.6 10.9 10.6 11.6 12.8 13.1 15.1 14.9 16.5 19.3 21.4 Copper weight kg/m 25 37 49 62 62 82 103 134 168 200 250 362 453 Cable weight approx. kg/km 95 114 138 173 170 207 250 286 365 377 459 650 789

ELKABEL

395

SPC
SPLIT CONCENTRIC CABLE

Uo/U - 600/1000 V

Cu conductors PVC insulation Split concentric neutral sheath of PVC

Application
Cables can be used for household and street lightning, suitable for fixed installations in direct burial.

Cable construction
Conductor Conductor size Insulation material Phase conductor solid copper conductor to BS 6360 accorting to BS 6360 PVC type TI1 complying to BS 7655 phase conductor, class 2

Technical data
Conductor resistance at 20 Insulation resistan min. M.km Voltage rating Test voltage 50Hz, 1 min. wire - wire wire - eart Temperature range, mobile Temperature range, fixed Minimum bending radius approx. 3500V 3500V -5C to +50C - 30C to +70C 15 x cable diameter According to BS 6360 100 600/1000 V

Neutral conductor split concentric cables, class 1 Eart conductor Outer sheath Sheath colour split concentric cables, class 1 PVC compound type TM1 complying to BS 7655-4.1 Black or violet

Identification of cable wires


Single phase conductor Neutral conductor Eart conductor brawn blue plain annealed copper wires

Construction data SPC Uo/U - 600/1000 V


Number of wires and nominal cross section mm2 14/4+4 16/6+6 110/10+10 116/16+16 125/25+16 135/35+25 Outer diameter approx. mm 10 11.5 13.0 15.0 18.0 22.0 Copper weight kg/m 113 178 277 441 608 855 Cable weight approx. kg/km 201 277 391 576 790 1097

396

ELKABEL

TECHNICAL DATA

ELKABEL

TECHNICAL DATA

398
TECHNICAL DATA

ELKABEL

Wooden drums as per BDS maximal length in meters


KD DMIN DMAX ** ** D d H D9 H9 ** ** ** ** ** 107 A3a 650 340 400 676 530 109 A4 800 450 400 838 530 111 A5 1000 500 500 1048 630 112 A6 1200 600 500 1248 630 115 A7 1400 750 700 1464 880 117 A8 1700 900 750 1764 940 118 A9 1800 1100 900 1864 1120 120 A10 2000 1200 1000 2064 1230 124 A11 2200 1300 1000 2280 1300 125 A12 2450 1500 1300 2550 1600 126 A13 2600 1500 1500 2720 1820 130 A14 300 1800 1800 3150 2200

TECHNICAL DATA

kg

250

400

700

1000

1600

2200

2800

3500

4000

5000

7000

10000

126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152

1.9510 2.0610 2.2010 2.3010 2.4010 2.5010 2.6010 2.8010 3.0010 3.2010 3.4010 3.6010 3.8010 4.0010 4.2010 4.4010 4.7010 5.0010 5.3010 5.6010 5.9010 6.2010 6.6010 7.0010 7.4010 7.8010 8.3010

2.0600 2.2000 2.3000 2.4000 2.5000 2.6000 2.8000 3.0000 3.2000 3.4000 3.6000 3.8000 4.0000 4.2000 4.4000 4.7000 5.0000 5.3000 5.6000 5.9000 6.2000 6.6000 7.0000 7.4000 7.8000 8.3000 8.8000

14430 12609 11675 10580 9828 9036 7910 6741 6449 5571 5011 4473 3999 3698 3259 2997 2611 2246 2044 1849 1688 1417 1277 1209 1072 946 825

0 0 0 15178 14176 13111 11319 9778 9170 8010 7262 6541 5908 5301 4720 4192 3686 3356 2936 2673 2329 2098 1908 1826 1639 1364 1203

0 0 0 0 0 0 0 0 0 0 15489 13641 12596 11281 10301 9063 7963 7149 6219 5753 5163 4558 4038 3751 3472 3001 2703

0 0 0 0 0 0 0 0 0 0 0 0 0 0 14634 13050 11644 10294 9112 8234 7482 6475 5815 5485 4920 4321 3752

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14805 13460 11844 10654 10068 9010 8025 7082

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14848 13345 11652

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 15377 13720

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

ELKABEL

399

Wooden drums as per BDS maximal length in meters

TECHNICAL DATA

KD

DMIN ** 8.8010 9.3010 9.8100 10.4100 11.0100 11.6100 12.3100 13.0100 13.8100 14.6100 15.5100 16.4100 17.4100 18.4100 19.5100 20.6100 22.0100 23.5100 25.0100 26.5100 28.0100 29.5100 31.0100 32.5100 34.0100 35.5100 37.0100 38.5100 40.0100 41.5100 43.0100 44.5100 46.0100 47.5100 49.0100 50.5100

DMAX ** 9.3000 9.8000 10.4000 11.0000 11.6000 12.3000 13.0000 13.8000 14.6000 15.5000 16.4000 17.4000 18.4000 19.5000 20.6000 22.0000 23.5000 25.0000 26.5000 28.0000 29.5000 31.0000 32.5000 34.0000 35.5000 37.0000 38.5000 40.0000 41.5000 43.0000 44.5000 46.0000 47.5000 49.0000 50.5000 52.0000

107 A3a 800 687 599 516 494 419 399 331 324 262 270 212 206 164 158 121 116 111 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

109 A4 1075 1013 896 785 680 649 553 466 455 375 385 309 299 215 236 188 180 137 130 123 116 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

111 A5 2323 2137 1922 1714 1551 1363 1217 1079 948 825 749 711 623 519 506 412 401 334 306 247 236 197 187 176 142 133 124 125 127 0 0 0 0 0 0 0

112 A6 3444 3205 2767 2496 2154 1914 1729 1554 1386 1228 1136 987 879 828 728 608 523 507 405 389 319 324 259 245 248 191 179 181 182 134 135 124 125 126 0 0

115 A7 6271 5758 5026 4565 3967 3555 3219 2901 2423 2192 2030 1810 1745 1496 1303 1126 960 942 788 673 627 524 506 488 396 379 383 301 286 289 273 276 206 208 194 196

117 A8 10412 9349 8352 7397 6775 5911 5188 4752 4099 3705 3510 3203 2834 2374 2114 1872 1592 1567 1352 1151 1005 978 841 814 688 662 636 524 529 505 405 408 386 390 302 304

118 A9 12139 10760 9472 8638 7565 6911 6277 5364 4802 4345 4047 3612 3196 2868 2495 2151 1881 1805 1508 1318 1249 1074 1010 852 826 800 658 634 610 486 490 468 446 449 343 345

120 A10 0 0 13823 12156 11292 9904 8593 7863 6791 6135 5808 5267 4745 3963 3506 3082 2683 2591 2217 1925 1652 1619 1365 1333 1143 1112 1038 907 878 848 695 668 672 645 511 514

124 A11 0 0 0 0 14008 12412 10895 9613 8795 7634 7279 6298 5708 5145 4604 4100 3622 3247 2812 2474 2155 1916 1816 1594 1554 1346 1257 1268 1079 1042 870 836 842 808 656 661

125 A12 0 0 0 0 0 0 0 15261 14036 12156 11258 10164 9241 7899 7190 6417 5682 5079 4502 3954 3517 3027 2984 2597 2234 2191 2084 1815 1772 1521 1480 1440 1212 1175 1137 974

126 A13 0 0 0 0 0 0 0 0 0 0 0 14281 13033 11270 10286 8858 7871 7163 5948 5314 4708 4575 4093 3633 3505 3074 2670 2624 2576 2202 2155 1872 1827 1782 1522 1480

130 A14 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14203 12210 11110 9318 8463 7639 6848 6093 5820 5221 4649 4496 4051 3903 3401 3344 2952 2821 2764 2408 2354

153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188

400

ELKABEL

Wooden drums as per BDS maximal length in meters

TECHNICAL DATA

KD

DMIN ** 52.0100 53.5100 50.0100 56.5100 58.0100 59.5100 61.0100 62.5100 64.0100 65.5100 67.0100 68.5100 70.0100 71.5100 73.0100 74.5100 76.0100 77.5100 79.0100 80.5100 82.0100 83.5100 85.0100 86.5100 88.0100 89.5100 91.0100 92.5100 94.0100 95.5100 97.0100 98.5100 100.0100 101.5100 103.0100 104.5100

DMAX ** 53.5000 55.0000 56.5000 58.0000 59.5000 61.0000 62.5000 64.0000 65.5000 67.0000 68.5000 70.0000 71.5000 73.0000 74.5000 76.0000 77.5000 79.0000 80.5000 82.0000 83.5000 85.0000 86.5000 88.0000 89.5000 91.0000 92.5000 94.0000 95.5000 97.0000 98.5000 100.0000 101.5000 103.0000 104.5000 106.0000

107 A3a 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

109 A4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

111 A5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

112 A6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

115 A7 150 139 140 141 130 131 131 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

117 A8 306 286 288 213 214 216 217 200 201 153 140 141 142 142 143 129 130 131 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

118 A9 327 328 309 311 240 225 226 227 211 212 213 198 141 142 142 131 131 132 132 121 121 121 122 0 0 0 0 0 0 0 0 0 0 0 0 0

120 A10 490 493 469 378 358 359 361 340 342 245 246 247 231 232 232 233 216 217 155 155 143 143 144 144 145 132 132 133 133 133 134 134 121 122 122 122

124 A11 630 634 499 502 475 477 480 363 364 342 343 345 322 323 248 249 231 232 232 233 215 215 216 217 218 141 141 142 142 142 143 143 129 130 130 130

125 A12 940 906 911 876 698 702 672 675 644 647 495 497 499 473 475 477 451 452 348 327 328 329 331 310 311 312 313 207 208 208 209 210 273 274 275 276

126 A13 1490 1251 1212 1172 1179 966 971 936 900 905 868 722 691 694 697 665 669 509 511 513 486 488 490 492 465 356 357 336 337 338 339 340 319 320 321 322

130 A14 2300 1973 1922 1933 1882 1584 1538 1546 1498 1232 1238 1196 1202 1159 966 929 933 896 899 862 865 869 666 669 671 639 641 644 612 614 616 618 585 587 589 556

189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224

ELKABEL

401

DESIGNATION CODE FOR POWER CABLES


according to DIN VDE 0271/0276

TECHNICAL DATA

Construction reference
Identification of Designation N DIN VDE standard (N) similar to DIN VDE standard IEC 502 Conductor Material A aluminium conductor copper conductor Insulating Materials Y PVC 2X cross-linked PE (XLPE) Concentric conductor (screen) C concentric conductor of copper CE concentric conductor of copper over each individual core S screen of copper wires SE screen of copper wires over each individual core H conductive layers (F) longitudinally water-proof screen (FL) longitudinally and radial water-proof screen Armouring B steel tape armouring R armour of galvanized round steel wires Sheath Y 2Y H Material PVC PE halogen-free thermoplastic polymer

Protective Conductor I with protective conductor O without protective conductor Number of Cores Conductor Cross Section in mm2 Conductor Type r... circular conductor .. m stranded conductor s... sector conductor /V compact conductor ..e... circular, solid conductor Rating Voltage 0.6/1 kV 3.6/6 kV 6.0/10 kV 12/20 kV 18/30 kV

Examples: NYY-J 4x1.5 RE 0.6/1 kV - VDE 0276-603 Cable according to standard, PVC-insulated, sheath PVC, with green-yellow marked core, 4 cores with nominal cross-section 1.5 mm2, circular conductor, solid, rating voltage 0.6/1 kV. A2XS2Y 1x35 RM/16 6/10 kV - IEC 60502-2 Single core XLPE-insulated cable with PE-sheath according to standard, circular, stranded aluminium conductor with nominal cross-section 35 mm2, covered with copper-screen 16 mm2 and rating vpltage (Uo/U) 6/10 kV.

402

ELKABEL

Current Carrying Capacity and Indications for Calculation of Power Cables and Wires
The guidelines for current carrying capacities of copper and aluminium are valid DIN VDE 0298 part 4 as well as DIN VDE 0276 part 603 and for the conversion factors DIN VDE 0276 part 1000. The current carrying capacity of a cable should be limited in such a degree that all locations in a cable system which causes the generated heats under given proportions to lead safely in the environment. The heat flow depends on the inner heat-resistance between conductor and outer surface of the cable and as well as from the heat emission to the surroundings. The following recommended values are the current carrying capacity of cables for laying in earth and in air at normal operating conditions. Hints for the deviated operating conditions, see DIN VDE 0298 table 4 and DIN VDE 0276 part 603 and part 1000.

TECHNICAL DATA

Indications for Calculation


For Laying in Earth Deviating operating conditions with both conversion factors are to be considered, as these depend on both of specific heat resistance and the grade of load. EVU-load (load grade) is the maximum load factor of 0.7. The conversion factors for the load grades 0.5, 0.6, 0.85 and 1.0 are to be taken in tables DIN VDE 0276 part 603 and part 1000. Intermediate values can be interpolate (1.0 used for permanent load). Laying depth 0.7 m. The load capacity decreases with increasing of the laying depth. Usual depth of laying is 0.7 to 1.2 m. As normal value of the specific ground thermal resistivity in moist areas is selected with 1.0 K.m/W. For dry areas the chosen value is 2.5 K.m/W, under consideration of the applied usual bedding materials of sands. For favourable ground conditions or with thermal resisted bedding materials, lower value under well consolidation can be achieved. For individual case, the values and upon that the resulted current carrying loads are to be determined. For Laying in Air The values stated in the tables for outdoor laying in the air are defined for permanent operation. The arrangement of the cables is corresponded the presentation in table 3, DIN VDE 0276 part 1000. Conversion factors for other laying conditions and the heaping of cables are shown in tables 10 and 11, DIN VDE 0276 part 1000. The current carrying capacities of multi-core cables can be calculated by using the current load value for 3-core cables according to table 13 with help of the conversion factors. By using the cable channels of cable board underlays, etc., the air temperature will be increased. In this case the conversion factors according to table 12 for deviating air temperature should be used. For outdoor installation in air, the ambient temperature is based on 30 oC. Radiation of heats and solar influence must be taken into consideration, where a good air circulation is needed. A sufficient large distance is to be retained between the cables and the heating elements, because badly insulated heating elements often raise additionally the temperature of the cable. Distance between the cable and the wall, floor or ceiling Distance between the cables being laid one above the other = 2 cm =2xD

Distance between the cable systems being laid one above the other = 20 cm Distance between the cables being laid side by side Specific Ground - very moist area - moist area - dry area - very dry area Thermal Resistivity = 0.7 K.m/W = 1.0 K.m/W = 2.0 K.m/W = 3.0 K.m/W =2xD

ELKABEL

403

INSTALLATION METHODS AND OPERATING CONDITIONS - Power Cables and Insulated Wires for Fixed Installation

TECHNICAL DATA

Installation method type A1


Single core cables in insulation tube in a thermally insulated wall.

Installation method A2
Multicore cables or multicore plastic sheathed cables in the insulation tube in a thermally insulated wall, whereby the walls for the methods of installation employed comprise an outer weatherproof board, thermal insulation and an inner 2 board of wood or materials similar to wood, having a temperature lag of 0.1 m .K/W. The plastic or metal insulation tube is mounted so that it is very close to the inner wall without actually being in conduct with the wall.

Installation method B1
Single core cables in insulation tube on a wooden wall.

Installation method B2
Multicore cables or multicore plastic sheath cables in insulation tube on a wooden wall. For both installation methods, the insulation tube must be secured so that the space between conduit and the wall surface is less than 0.3 times the diameter of the insulation tube. The plastic or metal insulation tube can be installed directly on the masonry construction or plastered surface, whereby the current carrying capacity of the cables or wires can then be higher. This problem is still being investigated by CENELEC.

Installation method C
Single core or multicore cables, or single core or multicore plastic-sheathed cables on a wooden wall. The cables or insulated wires shall be mounted so that the space from the wall surface is less than 0.3 times the outer diameter of the cable or insulated wire. The current carrying capacity can be increased when installed directly on or in the masonry construction as well as underneath the plaster.

Installation methods E, F and G


Single core or multicore cables, or single core or multicore plastic-sheathed cables, installed in the open air. The cable or insulated wire shall be installed so that the dissipation of heat is not impeded, whereby allowance shall be made for heating by other sources and for irradiation by sunshine. Natural convection shall not be obstructed. The space from the cable or insulated wire by each bordering surface shall be 0.3 times the outside diameter. A space equal to the one of the outside diameter is sufficient for single core cables and plastic-sheathed wires in order to meet the current carrying requirements for an installation in the open air.

404

ELKABEL

Laying Conditions for Power Cables


As laying depth, the mathematical distance to the cable axis - for triangular bunched laying, the distance of the bundle axis to the earth surface of 70 cm is chosen. With increased laying depth the load ratings will be mathematically reduced. Hereby the same temperature and the same thermal earth resistances are to be presumed. Normal operation conditions and indications for deviating operation conditions.

TECHNICAL DATA

Normal Operation Conditions


Laid in Earth
1 Multicore cable 1 Single core cable in direct currentsystem 3 Single core cables in 3-phase system, side by side, with a space of 7 cm 3 Single core cables in 3-phase system, in bundle form1) Bedding in sand or earth shove and if necessary covering with bricks, cement plates or with flat to light curved thin covering of plastic Ambient Conditions - Ground temperature at installation depth: 20 oC - Soil-thermal resistivity of moist area: 1.0 K.m/W - Soil-thermal resistivity of dry area: 2.5 K.m/W Connecting and earthing of metal sheaths or screens on both ends

Laid in Air
1 Multicore cable 1 Single core cable in direct currentsystem 3 Single core cables in 3-phase system, side by side, with a space of a cable 3 Single core cables in 3-phase system, in bundle form 1) - Laid in open air, i.e. unhindered heat radiation will be ensured at: Distance of cable from wall, floor or ceiling 2 cm - For cables laying side by side: Space at least two times of the cable - For cables laying one above the other: Vertical space of the cable at least two times of the cable cable length at least 30 cm - Consideration of thermal loss in cable, the incresed air temperature of sufficient big and ventilated rooms - Protection against direct heat radiation of sunlight, etc. - Air temperature 30 oC Adequate big or ventilated rooms, due to that the power loss of the cable not be noticeable increased Connecting and earthing of metal sheaths or screens on both sides

Indications
Conversion factors see the following tables as of collective laying conditions see the following tables

7 cm

d d

Conversion factors for laying in earth: - covering hood with air cavity = 0.9 laid in conduit = 0.85 Conversion factors for laying in air: - alternating ambient temperatures - as of collecting laying conditions - for laying in conduits - see tables and indications according to DIN VDE 0298

1)

In "bunched" or triangle touching arrangement.

ELKABEL

405

Current ratings for installation A1, A2, B1 and B2 Cables for fixed installation within buildings

TECHNICAL DATA

Operating temperature at conductor 70 oC; Ambient temperature 30 oC


Type designation H07V-U, -R, -K H07V3-U, -R, -K NYM, NYBUY N05VV-U, N05VV-R NHXMH NYY, NYCY 1) Multicore sheathed cables in insulating tubes, in a thermally insulated walls H07V-U, -R, -K H07V3-U, -R, -K NYM, NYBUY N05VV-U, N05VV-R NHXMH NYY, NYCY1) Multicore cables or multicore sheathed cables in insulating tubes on a wall

Installation: * in thermally insulated walls * in insulating tubes

Single core cables in insulating tubes, in a thermally insulated walls

Single core cables in insulating tubes on a wall

Installation in thermally insulated walls

Installation in insulating tubes

Installation method 2) Number of loaded cores Cross-section, mm2 1.5 2.5 4 6 10 10 16 25 35 50 70 95 120 150 185 240 300

A1 2

A2 B1 2 3 2 Current ratings in Ampere (A) 15.5 18.5 25 32 43 57 75 92 110 139 167 192 219 248 291 334 13.0 17.5 23 29 39 52 68 83 99 125 150 172 196 223 261 298 17.5 24 32 41 57 76 101 125 151 192 232 269 -

B2 2

15.5 19.5 26 34 46 61 80 99 119 151 182 210 240 273 320 367

3)

13.5 18.0 24 31 42 56 73 89 108 136 164 188 216 245 286 328

15.5 21 28 36 50 68 89 110 134 171 207 239 -

16.5 23 30 38 52 69 90 111 133 168 201 232 -

15.0 20 27 34 46 47.17 62 80 99 118 149 179 206 -

4)

Conversion factors for deviating ambient temperature. grouping. installation under the ceiling. multicore cables and insulated wires - see DIN VDE 0298 part 4. 1) The current ratings are valid for cables with concentric conductor. only for versions. 2) For further installation methods - see DIN VDE 0298 part 4. 3) See DIN VDE 0298 part 4. 4) Not permitted for the installation on a wooden wall and not for application of the conversion factors. see DIN VDE 0298 part 4.

406

ELKABEL

Current ratings for installation conditions C, E, F and G


Cables for fixed installation within buildings Operating temperature at conductor 70oC; Ambient temperature 30o C
Type designation NYM, NYIF, NYIFY, NYBUY, N05W-U, N05W-R, NHXMH, NYY, NYCY 1) NYY

TECHNICAL DATA

Installation: * directly * in open air

Singlecore or multicore cables or single or multicore sheathed cables on a wall

Multicore cables or multicore sheathed cables with a space of minimum 0,3x diameter d to wall

Single core cables or single core sheathed cables with a space of minimum 1x diameter d to wall; with contact with gap d

or

d
or

0,3d

direct installation Installation method Number of loaded Cross-section, mm2 1.5 2.5 4 4 6 10 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
2)

installation in open air E 2 F 3 2 Current ratings in Ampere (A) 18.5 25 34 43 60 80 101 126 153 196 238 276 319 364 430 497 131 162 196 251 304 352 406 463 546 629 754 868 1005 G 3 114 143 174 225 275 321 372 427 507 587 689 789 905 110 137 167 216 264 308 356 409 485 561 656 749 855 146 181 219 281 341 396 456 521 615 709 852 982 1138 130 162 197 254 311 362 419 480 569 659 795 920 1070

C 2 19.5 27 36 46 63 85 112 138 168 213 258 299 344 392 461 530 -

3 17.5 24 32 33.02 41 57 59.43 76 96 119 144 184 223 259 299 341 403 464 -

3)

3)

22 30 40 51 70 94 119 148 180 232 282 328 379 434 514 593 -

Conversion factors for deviating ambient temperature. grouping. installation under the ceiling. multicore cables and insulated wires - see DIN VDE 0298 part 4. The current ratings are valid for cables with concentric conductor. only for multicore versions. For further installation method - see DIN VDE 0298 part 4. 3) See DIN VDE 0298 part 4.
1) 2)

ELKABEL

407

Current ratings for installation conditions


Cables for fixed installation within buildings A1, A2, B1 and B2

TECHNICAL DATA

Operating temperature at Conductor 90 oC; Ambient temperature 30 oC


Type designation H07V2-U, -K H07Z-U, -R, -K N12XY, N2XY, , NHXHX N2X2Y, N2XH, N2XCH FE180 NHXCHX FE180 NHXH FE180 NHXCH FE180 NHXHX, NHXCHX Multicore sheathed cables in insulating tubes, in a thermally insulated walls H07V2-U, -K H07Z-U, -R, -K N12XY, N2XY, N2X2Y N2XH, N2XCH FE180 NHXHX FE180 NHXCHX NHXH FE180 NHXCH FE180 NHXHX, NHXCHX Multicore cables or multicore sheathed cables in insulating tubes on a wall

Installation: * in thermally insulated walls * in insulating tubes

Single core cables, in insulating tubes in a thermally insulated walls

Single core cables in insulating tubes on a wall

Installation in thermally insulated walls

Installation in insulating tubes

Installation method 1) Number of loaded cores Cross-section, mm2

A1 2

A2 2

B1 2

B2 3

Current ratings in Ampere (A) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 19.0 26 35 45 61 81 106 131 158 200 241 278 318 362 424 486 17.0 23 31 40 54 73 95 117 141 179 216 249 285 324 380 435 18.5 25 33 42 57 76 99 121 145 183 220 253 290 329 386 442 16.5 22 30 38 51 68 89 109 130 164 197 227 259 295 346 396 23 31 42 54 75 100 133 164 198 253 306 354 20 28 37 48 66 88 117 144 175 222 269 312 22 30 40 51 69 91 119 146 175 221 265 305 19.5 26 35 44 60 80 105 128 154 194 233 268 -

Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multucore cables and insulated wires - see DIN VDE 0298 part 4. 1) For further installation conditions - see DIN VDE 0298 part 4.

408

ELKABEL

Current ratings for installation conditions

C, E, F and G

Cables for fixed installation within buildings

TECHNICAL DATA

Operating temperature at conductor 90 oC; Ambient temperature 30 oC


Type designation N12XY, N2XY, N2X2Y N2XH, N2XCH 1), NHXHX FE180 NHXH FE180, NHXCH FE180 1) NHXHX FE180, NHXCHX FE180 NHXHX, NHXCHX 1) NHXHX N12XY, N2XY, N2X2Y N2XH NHXH FE180
1)

Installation: * directly * in open air

Single core or multicore cables or single or multicore sheathed cables on a wall

Multicore cables or multicore sheathed cables with a space of minimum 0,3x diameter d to wall

Single core cables or single core sheathed cables with a space of minimum 1x diameter d to wall with contact with gap d

or

d
or

0,3d

direct installation

installation in open air

Installation method Number of l Loaded cores Cross-section, mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

2)

C 2

E 2

F 2

G 3

Current ratings in Ampere (A) 24 33 45 58 80 107 138 171 209 269 328 382 441 506 599 693 22 30 40 52 71 96 119 147 179 229 278 322 371 424 500 576 26 36 49 63 86 115 149 185 225 289 352 410 473 542 641 741 23 32 42 54 75 110 127 158 192 246 298 346 399 456 538 621 161 200 242 310 377 437 504 575 679 783 940 1083 1254 141 176 216 279 342 400 464 533 634 736 868 998 1151 135 169 207 268 328 383 444 510 607 703 823 946 1088 182 226 275 353 430 500 577 661 781 902 1085 1253 1454 161 201 246 318 389 454 527 605 719 833 1008 1169 1362

Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multicore cables and insulated wires - see DIN VDE 0298 part 4. 1) The current ratings are valid for cables with concentric conductor, only for multicore versions. 2) For further installation methods - see DIN VDE 0298 part 4.

ELKABEL

409

Current ratings for NYY, NAYY, NYCY, NAYCY 0,6/1 kV

TECHNICAL DATA

Current carrying capacity in Ampere (A), laying in ground (20 oC)


Nominal cross-section mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500
1)

Copper conductor NYY


1)

NYCY

Aluminium conductor NAYY


1)

NAYCY

30 39 50 62 83 107 138 164 195 238 286 325 365 413 479 541 614 693

27 36 47 59 79 102 133 159 188 232 280 318 359 406 473 535 613 687

41 55 71 90 124 160 208 250 296 365 438 501 563 639 746 848 975 1125

31 40 51 63 84 108 139 166 196 238 281 315 347 385 432 473 521 574

27 36 47 59 79 102 133 160 190 234 280 319 357 402 463 518 579 624

106 127 151 185 222 253 284 322 375 425 487 558

102 123 144 179 215 245 275 313 364 419 484 553

160 193 230 283 340 389 436 496 578 656 756 873

108 129 153 187 223 252 280 314 358 397 441 489

103 123 145 180 216 246 276 313 362 415 474 528

Rated current for direct current systems with a far-distanced return conductor

Current carrying capacity in Ampere (A), laying in air (30 oC)


Nominal cross-section mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500
1)

Copper conductor NYY


1)

NYCY

Aluminium conductor NAYY


1)

NAYCY

21 28 37 47 64 84 114 139 169 213 264 307 352 406 483 557 646 747

19.5 25 34 43 59 79 106 129 157 199 246 285 326 374 445 511 597 669

27 35 47 59 81 107 144 176 214 270 334 389 446 516 618 717 843 994

22 29 39 49 67 89 119 146 177 221 270 310 350 399 462 519 583 657

19,5 26 34 44 60 80 108 132 160 202 249 289 329 377 443 504 577 626

87 107 131 166 205 239 273 317 378 437 513 600

82 100 119 152 186 216 246 285 338 400 472 539

110 135 166 210 259 302 345 401 479 555 653 772

91 112 137 173 212 247 280 321 374 426 488 556

83 101 121 155 189 220 249 287 339 401 468 524

Rated current for direct systems with a far-distanced return conductor

Conversion factors for multicore cable ( 5 cores)


The conversion factors are to be used for laying the cables in ground or in air, to the values given in above tables. Number of loaded cores n 5 7 10 14 19 24 40 61 Note: Valid for cross-section 1,5 to 10 mm2. Laying in ground f 0.70 0.60 0.50 0.45 0.40 0.35 0.30 0.25 Laying in air f 0.75 0.65 0.55 0.50 0.45 0.40 0.35 0.30

410

ELKABEL

Current ratings for N2XY, NA2XY; N2XCY; NA2XCY; N2X2Y; NA2X2Y; N2XC2Y, NA2XC2Y; N2XH, NA2XH; N2XCH; NA2XCH
Current carrying capacity in Ampere (A), laying in ground (20 oC)
Aluminium conductor NA2XY; NA2X2Y NA2XCY; NA2XC2Y
1)

TECHNICAL DATA

Nominal crosssection mm2


1)

Copper conductor N2XY; N2X2Y N2XCY; N2XC2Y

1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500

48 63 82 102 136 176 229 275 326 400 480 548 616 698 815 927 1064 1227

31 40 52 64 86 112 145 174 206 254 305 348 392 444 517 585 671 758

33 42 54 67 89 115 148 177 209 256 307 349 393 445 517 583 663 749

31 40 52 65 87 113 146 176 208 256 307 349 391 442 509 569 637 691

33 43 55 68 91 117 150 179 211 257 304 341 377 418 469 514 565 623

177 212 252 310 372 425 476 541 631 716 825 952

112 135 158 196 234 268 300 342 398 457 529 609

114 136 162 199 238 272 305 347 404 457 525 601

113 136 159 197 236 269 302 342 397 454 520 584

116 138 164 201 240 272 303 340 387 430 479 531

1)

Rated current for direct current systems witn a far-distanced retum conductor.

ELKABEL

411

Current carrying capacity in Ampere (A)


laying on air (30 oC)

TECHNICAL DATA

Nominal Crosssection mm2

Copper conductor N2XY; N2X2Y; N2XH N2XCY; N2XC2Y; N2XCH


1)

Aluminium conductor NA2XY; NA2X2Y; NA2XH NA2XCY NA2XC2Y; NA2XCH

1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500

33 43 57 72 99 131 177 217 265 336 415 485 557 646 774 901 1060 1252

24 32 42 53 74 98 133 162 197 250 308 359 412 475 564 649 761 866

26 34 44 56 77 102 138 170 207 263 325 380 437 507 604 697 811 940

25 33 43 54 75 100 136 165 201 255 314 364 416 480 565 643 737 807

27 36 47 59 81 109 146 179 218 275 336 388 438 501 580 654 733 825

136 166 205 260 321 376 431 501 600 696 821 971

102 126 149 191 234 273 311 360 427 507 600 695

106 130 161 204 252 295 339 395 472 547 643 754

104 128 152 194 239 278 316 365 430 506 575 682

112 137 169 214 263 308 349 401 469 535 615 700

1)

Rated current for direct systems with a far-distanced return conductor.

Electrical characteristics of PVC and XLPE insulated Low


Voltage Power Cables, 0,6/1kV
Short-circuit current carrying capacity up to 0,6/1kV
Cross-section Insulation - PVC Conductor temperature: 70 oC Short-circuit temperature: 160 oC Short-circuit time: 1 s with Cu-conductors 0.17 0.29 0.46 0.69 1.15 1.84 2.88 4.03 5.75 8.05 10.93 13.80 17.25 21.27 27.60 30.90 41.20 51.50 with Al-conductors 1.90 2.66 3.80 5.32 7.22 9.12 11.40 14.06 18.24 20.40 27.20 34.00 Insulation - XLPE Conductor temperature: 90 oC Short-circuit temperature: 250 oC Short-circuit time: 1 s with Cu-conductors 0.21 0.36 0.57 0.86 1.43 2.29 3.57 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 with Al-conductors 2.35 3.29 4.70 6.58 8.93 11.28 14.10 17.39 22.56 28.20 37.60 47.00

mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500

412

ELKABEL

Current ratings - Conversion factors


for grouping of single core cables or cables on troughs and trays

TECHNICAL DATA

Number of three-phase systems with single core cables Installation method Perforated cable troughs with contact

Used as multiplier for ratings value for

Number of troughs or trays

2 3 Conversion factors

Three-cores cable in horizontal-surface arrangement

1 2 3

0,98 0,96 0,95

0,91 0,87 0,85

0,87 0,81 0,78

300 mm

20 mm

with contact

Three-cores cablet vertical-surface arrangemen

1 2

0,96 0,95

0,86 0,84

225 mm

Cable trays

with contact Three-cores cable in horizontale surface arrangement


300 mm

1 2 3

11,00 0,98 0,97

0,97 0,93 0,90

0,96 0,89 0,86

20 mm

Perforated cable troughs


300 mm

d 2d

1 2 3

1,00 0,97 0,96

0,98 0,93 0,92

0,96 0,89 0,86

20 mm

2d d 225 mm

Three-core cables in vertical-surface triangle arrangement

1 2

1,00 1,00

0,91 0,90

0,89 0,86

Cable trays
d
2d

1 2 3

1,00 0,97 0,96

1,00 0,95 0,94

1,00 0,93 0,90

300 mm

20 mm

Note: The conversion factors are used only for cables of one layer grouping arrangement. These are not valied when the cables are installed with contact one upon another or the given sprees between the cable toughs or cable trays, are not followed, in such cases the conversion factors can be reduced. To parallel current circuits each group of three conductors of the parallel circuit is regarded as single circuit.

ELKABEL

413

Current ratings - conversion factors


for grouping of multicore cables or cables on troughs and trays

TECHNICAL DATA

Number of multicore cables Installation method

1 2 Number of troughs or trays

4 6 Conversion factors

300 mm

Non-perforated cable troughs

with contact

1 2 3 6
20 mm

0,97 0,97 0,97 0,97

0,84 0,83 0,82 0,81

0,78 0,76 0,75 0,73

0,75 0,72 0,71 0,69

0,71 0,68 0,66 0,63

0,68 0,63 0,61 0,58

Perforated cable troughs

with contact
300 mm

1 2 3 6
20 mm

1,00 1,00 1,00 1,00

0,88 0,87 0,86 0,84

0,82 0,80 0,79 0,77

0,79 0,77 0,76 0,73

0,76 0,73 0,71 0,68

0,73 0,68 0,66 0,64

with space
300 mm

1 2 3

1,00 1,00 1,00

1,00 0,99 0,98

0,98 0,96 0,95

0,95 0,92 0,91

0,91 0,87 0,85

20 mm

with contact

1 2

1,00 1,00

0,88 0,88

0,82 0,81

0,78 0,76

0,73 0,71

0,72 0,70

225 mm

with space
d d

1 2

1,00 1,00

0,91 0,91

0,89 0,88

0,88 0,87

0,87 0,85

225 mm

Cable trays

with contact

300 mm

1 2 3 6

1,00 1,00 1,00 1,00

0,87 0,86 0,85 0,83

0,82 0,81 0,79 0,76

0,80 0,78 0,76 0,73

0,79 0,76 0,73 0,69

0,78 0,73 0,70 0,66

20 mm

with space 300 mm

1 2 3

1,00 1,00 1,00

1,00 0,99 0,98

1,00 0,98 0,97

1,00 0,97 0,96

1,00 0,9 0,93

20 mm

Note: The conversion factor are used for cables of one layer grouping arrangement. These are not valid when the cables are installed with contact one upon another or the given spaces between the cable troughs or cable trays can not meet in such cases the conversion factor can be reduced.

414

ELKABEL

N2XSY NA2XSY
Conductor material Arrangement U0/U crosssection mm2 25 35 50 70 95 120 150 185 240 300 400 500 6/10 kV 157 187 220 268 320 363 405 456 526 591 662 744 179 212 249 302 359 405 442 493 563 626 675 748 Copper conductor

Medium Voltage Power Cables 6/10 kV, 12/20 kV, 18/30 kV N2XS2Y NA2XS2Y N2XS(F)2Y NA2XS(F)2Y

Power ratings for XLPE-insulated

TECHNICAL DATA

Current carrying capacity in Amperes (A) in ground (20 oC)


Aluminium conductor

12/20 kV 189 222 271 323 367 409 461 532 599 671 754 213 250 303 360 407 445 498 568 633 685 760

18/30 kV 225 274 327 371 414 466 539 606 680 765 251 304 362 409 449 502 574 640 695 773

6/10 kV 12/20 kV Current ratings in Ampere (A) 145 171 208 248 283 315 357 413 466 529 602 165 194 236 281 318 350 394 452 506 558 627 172 210 251 285 319 361 417 471 535 609 195 237 282 319 352 396 455 510 564 634

18/30 kV 174 213 254 289 322 364 422 476 541 616 195 238 283 321 354 399 458 514 570 642

This factors are also valid for longitudinally water-tight cable

Current carrying capacity* in Amperes (A) in air (30 oC)


Conductor material Arrangement U0/U cross-section mm2 25 35 50 70 95 120 150 185 240 300 400 500
*

Copper conductor

Aluminium conductor

6/10 kV

12/20 kV

18/30 kV

6/10 kV

12/20 kV

18/30 kV

Current ratings in Ampere (A) 163 197 236 294 358 413 468 535 631 722 827 949 194 235 282 350 426 491 549 625 731 831 920 1043 200 239 297 361 416 470 538 634 724 829 953 235 282 351 426 491 549 625 731 830 923 1045 241 299 363 418 472 539 635 725 831 953 282 350 425 488 548 624 728 828 922 1045 153 183 228 278 321 364 418 494 568 660 767 182 219 273 333 384 432 496 583 666 755 868 185 231 280 323 366 420 496 569 660 766 219 273 332 384 432 494 581 663 753 866 187 232 282 325 367 421 496 568 650 764 219 273 331 382 429 492 578 659 750 861

This factors are also valid for longitudinally water-tight cable

ELKABEL

415

Electrical characteristics of XLPE-insulated


Medium Voltage Power Cables, 6 - 30 kV

TECHNICAL DATA

Conductor resistance 20 oC
maximum value cross-section mm2 25 35 50 70 95 120 150 185 240 300 400 500 Cu-conductor Ohm/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 Alu-conductor Ohm/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605

Conversion factors for the conductor temperatures


Temperature at oC Cu-conductor Alu-conductor 60 1.157 1.161 65 1.177 1.181 70 1.196 1.202 80 1.236 1.242 90 1.275 1.282

Conversion formula:
R= R20 . 234.5 + for Cu-conductor 254.5 R = R20 . 228 + 248 for Alu-conductor

Conductor temperature at oC = Conductor resistance at C in Ohm/km = R Conductor resistance at 20 oC in Ohm/km = R20

416

ELKABEL

Electrical characteristics of XLPE-insulated


Medium Voltage Power Cables, 6 - 30 kV

TECHNICAL DATA

Effective resistance at 50 Hz (Alternating-current resistance)


Copper conductor
Nominal voltage Cross-section mm2 35 50 70 95 120 150 185 240 300 400 500 0.671 0.497 0.345 0.249 0.198 0.163 0.132 0.102 0.082 0.068 0.055 6/10 kV 12/20 kV 0hm/km 0.673 0.498 0.346 0.251 0.200 0.165 0.134 0.104 0.085 0.071 0.058 0.671 0.496 0.345 0.249 0.198 0.163 0.131 0.101 0.082 0.067 0.055 0.672 0.498 0.346 0.250 0.200 0.165 0.133 0.103 0.084 0.070 0.058 0.496 0.344 0.249 0.198 0.162 0.131 0.101 0.082 0.067 0.054 18/30 kV

0.497 0.346 0.250 0.199 0.164 0.133 0.103 0.084 0.069 0.057

Aluminium conductor
Nominal voltage Cross-section mm2 35 50 70 95 120 150 185 240 300 400 500 1.12 0.825 0.571 0.413 0.327 0.269 0.215 0.165 0.133 0.106 0.085 6/10 kV 12/20 kV 0hm/km 1.12 0.826 0.572 0.415 0.329 0.271 0.217 0.167 0.135 0.109 0.088 1.12 0.825 0.571 0.413 0.327 0.268 0.215 0.165 0.133 0.106 0.084 1.12 0.826 0.572 0.414 0.329 0.270 0.217 0.167 0.135 0.109 0.087 0.824 0.571 0.413 0.327 0.268 0.214 0.164 0.133 0.106 0.084 18/30 kV

0.826 0.572 0.414 0.328 0.270 0.216 0.166 0.135 0.108 0.087

Inductive resistance at 50 Hz
Nominal voltage Cross-section mm2 35 50 70 95 120 150 185 240 300 400 500 0.144 0.136 0.129 0.123 0.118 0.114 0.110 0.105 0.102 0.097 0.094 6/10 kV 12/20 kV 0hm/km 0.153 0.145 0.138 0.131 0.126 0.121 0.117 0.112 0.108 0.103 0.100 0.168 0.159 0.152 0.145 0.140 0.135 0.131 0.126 0.123 0.117 0.114 0.154 0.147 0.139 0.134 0.129 0.125 0.120 0.115 0.110 0.106 18/30 kV

0.158 0.150 0.143 0.137 0.132 0.128 0.124 0.120 0.116 0.111 0.108

0.169 0.161 0.154 0.148 0.143 0.139 0.134 0.130 0.124 0.120

ELKABEL

417

Electrical characteristics of XLPE-insulated


Medium Voltage Power Cables, 6 - 30 kV

TECHNICAL DATA

Mutual capacitance
Nominal voltage Cross-section mm2 35 50 70 95 120 150 185 240 300 400 500 6/10 kV F/km 0,22 0,25 0,28 0,31 0,23 0,37 0,40 0,44 0,48 0,55 0,60 12/20 kV F/km 0,16 0,18 0,20 0,22 0,23 0,25 0,27 0,30 0,32 0,36 0,40 18/30 kV F/km 0,14 0,15 0,17 0,23 0,19 0,20 0,22 0,24 0,27 0,29

Inductance
Nominal voltage Cross-section mm2 35 50 70 95 120 150 185 240 300 400 500 6/10 kV 12/20 kV 18/30 kV

mH/km 0,45 0,42 0,39 0,38 0,36 0,35 0,34 0,32 0,31 0,30 0,29

mH/km 0,76 0,73 0,70 0,67 0,65 0,63 0,61 0,59 0,57 0,55 0,53

mH/km 0,48 0,45 0,43 0,41 0,39 0,38 0,36 0,35 0,33 0,33 0,31

mH/km 0,76 0,74 0,70 0,68 0,65 0,63 0,62 0,59 0,58 0,55 0,53

mH/km 0,48 0,45 0,43 0,42 0,41 0,39 0,37 0,36 0,34 0,33

mH/km 0,75 0,71 0,68 0,66 0,64 0,63 0,60 0,59 0,56 0,54

418

ELKABEL

Electrical characteristics of XLPE-insulated


Medium Voltage Power Cables, 6 - 30 kV
Short-circuit current carrying capacity up to 30 kV Conductor temperature: 90 oC Short-circuit temperature: 250 oC Cable with Cu-conductors
crosssection mm2 0,1 0,2 0,3 0,4 0,5 short-circuit time in s (seconds)

TECHNICAL DATA

0,6

0,7

0,8

0,9

1,0

1,5

2,0

3,0

4,0

5,0

permissible short-circuit in kA 25 35 50 70 95 120 150 185 240 300 400 500 11,3 15,8 22,6 31,7 43,0 54,3 67,8 83,7 108,5 135,7 180,9 226,1 8,0 11,2 16,0 22,4 30,4 38,4 48,0 59,2 76,7 95,9 127,9 159,9 6,5 9,1 13,1 18,3 24,8 31,3 39,2 48,3 62,7 78,3 104,4 130,5 5,7 7,9 11,3 15,8 21,5 27,1 33,9 41,8 54,3 67,8 90,4 113,1 5,1 7,1 10,1 14,2 19,2 24,3 30,3 37,4 48,5 60,7 80,9 101,1 4,6 6,5 9,2 12,9 17,5 22,2 27,7 34,2 44,3 55,4 73,8 92,3 4,3 6,0 8,5 12,0 16,2 20,5 25,6 31,6 41,0 51,3 68,4 85,5 4,0 5,6 8,0 11,2 15,2 19,2 24,0 29,6 38,4 48,0 64,0 79,9 3,8 5,3 7,5 10,6 14,3 18,1 22,6 27,9 36,2 45,2 60,3 75,4 3,6 5,0 7,2 10,0 13,6 17,2 21,5 26,5 34,3 42,9 57,2 71,5 2,9 4,1 5,8 8,2 11,1 14,0 17,5 21,6 28,0 35,0 46,7 58,4 2,5 3,5 5,1 7,1 9,6 12,1 15,2 18,7 24,3 30,3 40,4 50,6 2,1 2,9 4,1 5,8 7,8 9,9 12,4 15,3 19,8 24,8 33,0 41,3 1,8 2,5 3,6 5,0 6,8 8,6 10,7 13,2 17,2 21,5 28,6 35,8 1,6 2,2 3,2 4,5 6,1 7,7 9,6 11,8 15,3 19,2 25,6 32,0

Cable with Alu-conductors


crosssection mm2 0,1 0,2 0,3 0,4 0,5 0,6

short-circuit time in s (seconds) 0,7 0,8 0,9 1,0 1,5 2,0 3,0 4,0 5,0

permissible short-circuit in kA 25 7,4 35 10,4 50 14,9 70 20,8 95 28,2 120 35,7 150 44,6 185 55,0 240 71,3 300 89,2 400 118,9 500 148,6 5,3 7,4 10,5 14,7 20,0 25,2 31,5 38,9 50,4 63,1 84,1 105,1 4,3 6,0 8,6 12,0 16,3 20,6 25,7 31,7 41,2 51,5 68,6 85,8 3,7 5,2 7,4 10,4 14,1 17,8 22,3 27,5 35,7 44,6 59,5 74,3 3,3 4,7 6,6 9,3 12,6 16,0 19,9 24,6 31,9 39,9 53,2 66,5 3,0 4,2 6,1 8,5 11,5 14,6 18,2 22,5 29,1 36,4 48,5 60,7 2,8 3,9 5,6 7,9 10,7 13,5 16,9 20,8 27,0 33,7 44,9 56,2 2,6 3,7 5,3 7,4 10,0 12,6 15,8 19,4 25,2 31,5 42,0 52,5 2,5 3,5 5,0 6,9 9,4 11,9 14,9 18,3 23,8 29,7 39,6 49,5 2,4 3,3 4,7 6,6 8,9 11,3 14,1 17,4 22,6 28,2 37,6 47,0 1,9 2,7 3,8 5,4 7,3 9,2 11,5 14,2 18,4 23,0 30,7 38,4 1,7 2,3 3,3 4,7 6,3 8,0 10,0 12,3 16,0 19,9 26,6 33,2 1,4 1,9 2,7 3,8 5,2 6,5 8,1 10,0 13,0 16,3 21,7 27,1 1,2 1,6 2,4 3,3 4,5 5,6 7,1 8,7 11,3 14,1 18,8 23,5 1,1 1,5 2,1 2,9 4,0 5,0 6,3 7,8 10,1 12,6 16,8 21,0

ELKABEL

419

Electrical characteristics of XLPE-insulated


Medium Voltage Power Cables, 6 - 30 kV

TECHNICAL DATA

Short-circuit to ground
Nominal voltage cross-section mm2 35 50 70 95 120 150 185 240 300 400 500 6/10 kV A/km 1,2 1,4 1,5 1,7 1,9 2,0 2,2 2,4 2,6 3,0 3,3 12/20 kV A/km 1,7 1,9 2,1 2,4 2,6 2,7 3,0 3,3 3,5 4,0 4,3 18/30 kV A/km 2,3 2,5 2,7 2,9 3,1 3,3 3,7 4,0 4,4 4,8

Short-cirguit current carrying capacity of copper screens Short-circuit temperature: 350 oC


Short-circuit time in seconds s 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,5 2,0 3,0 4,0 5,0 bei 16 mm kA 9,7 6,9 5,7 5,0 4,5 4,2 3,9 3,5 3,4 3,3 2,7 2,3 1,9 1,7 1,5
2

Load of short-circuit current in kA 25 mm2 kA 15,1 10,7 8,9 7,7 7,0 6,4 6,0 5,6 5,3 5,1 4,2 3,6 2,9 2,6 2,3 35 mm2 kA 21,2 15,1 12,5 10,9 9,8 9,0 8,4 7,9 7,5 7,2 5,9 5,1 4,2 3,6 3,2

Coordination of screen-cross-section
conductor cross-section mm2 35 bis 120 150 bis 300 400 und 500 screen-cross-section mm2 16 25 35

420

ELKABEL

Conversion factor for Medium Voltage Power Cables, 6 - 30 kV

TECHNICAL DATA

Load rating for cables laid in ground Load factor 0,7 and 1,0
Fundamental conditions* Ground temperature 20 oC Thermal resistivity 1,0 K . m/W Distance between cables or systems 7 cm Single core cables laid in trefoil touching arrangement

Load factor 0,7


Type of insulation
PVC

Cable design

Nominal voltage
0,6/1 bis bis 0,6/1 bis bis 3,6/6 6/10 3.6/6 6/10 kV kV kV kV

2
0,86 0,87 0,85 0,83 0,85 0,85

Number of cables or systems 4 6 8 10


0,71 0,71 0.70 0,66 0,70 0,70 0,64 0,63 0,63 0,57 0,63 0,63 0,60 0,59 0,59 0,53 0,59 0,58 0,57 0,54 0,56 0,49 0,56 0,56

Multicore cables Three core cables Single core cables Single core cables Multicore cables Single core cables

VPE

0,6/1 bis 18/30 kV 0,6/1 bis 18/30 kV

Load factor 1,0


Type of insulation
PVC

Cable design

Nominal voltage
0,6/1bis bis 0,6/1 bis bis 0,6/1 bis 0,6/1 bis 3,6/6 6/10 3.6/6 6/10 kV kV kV kV

1
0,81 0,82 0,79 0,78 0,83 0,81

2
0,66 0,67 0,65 0,62 0,67 0,66

Number of cables or systems 4 6 8 10


0,52 0,51 0.51 0,47 0,53 0,52 0,46 0,45 0,46 0,40 0,47 0,47 0,43 0,41 0,42 0,36 0,44 0,43 0,40 0,37 0,40 0,33 0,41 0,41

Mehradrige Kabel Dreiadride Kabel Einadrige Kabel Einadrige Kabel Mehradrige Kabel Einadrige Kabel

VPE

18/30 kV 18/30 kV

Build-up of systems:
for single core cables 7 cm for multicore cables 7 cm

* Conversion factors for multicore cables ( 5 cores), Conductor cross-section from 1,5 to 10 mm2
Numbers of loaded cores Conversion factors for the values of 1,5 to 10 mm2 to the belonging table Earth Air
0,7 0,6 0,5 0,45 0,4 0,35 0,3 0,25 0,75 0,65 0,55 0,5 0,45 0,4 0,35 0,3

5 7 10 14 19 24 40 61

* For other conditions e. g. ground, temperature grouping, load factor, thermal resistance, the rating factors should be calculated according to DIN VDE 0276 part 1000.

ELKABEL

421

Rating conversion factors for installation of


Voltage Cables, 6 - 30 kV

Medium

TECHNICAL DATA

Rating conversion factors for laying in air*) Multicore cable and single core dirrect current cable
Arrangement of cables in laying condition Number cables troughs or trays Without inter-contact Space = cable d Distance from wall 2 cm Number of cables Installation method on the ground
d d

With inter-contact contact with wall

Number of cables 6 Installation method 1 2 3 4 6 9

1
a 20 mm

0,97
a

0,96 0,94

0,93

0,90
a 20 mm

0,97
a

0,85

0,78 0,75

0,71 0,68

on nonperforated cable troughs (restricted air circulation)

1 2 3 6

d d

0,97 0,97 0,97 0,97


a

0,96 0,95 0,94 0,93

0,94 0,92 0,91 0,90

0,93 0,90 0,89 0,88

0,90 0,86 0,84 0,83

0,97 0,97 0,97 0,97


a 20 mm

0,85 0,84 0,83 0,81

0,78 0,76 0,75 0,73

0,75 0,73 0,72 0,69

0,71 0,68 0,66 0,63

0,68 0,63 0,61 0,58

300 mm

300 mm

a 20 mm

2d 2d

300 mm

d d

300 mm

on perforated cable troughs

1 2 3 6

1,00 1,00 1,00 1,00


a

1,00 0,99 0,98 0,97

0,98 0,96 0,95 0,94

0,95 0,92 0,91 0,90

0,90 0,87 0,85 0,84

1,00 1,00 1,00 1,00


a
a 20 mm

0,88 0,87 0,86 0,84

0,82 0,80 0,79 0,77

0,79 0,77 0,76 0,73

0,76 0,73 0,71 0,68

0,73 0,68 0,66 0,64

a 20 mm

on cable trays or on cable ladders (unrestricted air circulation)

300 mm

1 2 3 6

d d

1,00 1,00 1,00 1,00


a

1,00 0,99 0,98 0,97

1,00 0,98 0,97 0,96

1,00 0,97 0,96 0,94

1,00 0,96 0,93 0,91

1,00 1,00 1,00 1,00


a 20 mm

0,87 0,86 0,85 0,83

0,82 0,80 0,79 0,76

0,80 0,78 0,76 0,73

0,79 0,76 0,73 0,69

0,78 0,73 0,70 0,66

300 mm

a 20 mm

on platform or on wall or on perforated cable tray

d d

1 2

1,00 1,00

0,91 0,89 0,91 0,88

0,88 0,87

0,87 0,85

1,00 1,00

0,88 0,88

0,82 0,78 0,81 0,76

0,73 0,72 0,71 0,70

225 mm

laid on platform or on the wall

225 mm

0,95

0,78

0,73 0,72

0,68 0,66

2 cm

1)

In narrow rooms or for bigger grouping, the air temperature is increased due to energy losses of cable, so the additional conversion factors for deviating air-temperatures are to be taken in the given table.

422

ELKABEL

20 cm

Arrangements, for which a reduction not necessary1

Number of cable arranged one over another is optoinal

Number of cable arraanged side-by-syde is optoinal

2 cm

2d d

d 2d

Rating conversion factors for installation


of Medium Voltage Cables, 6 -30 kV

TECHNICAL DATA

Rating conversion factors for laying in air*) Single core cables in 3-phase systems
Arrangement of cables in laying condition Number of cables troughs or trays on top of each other For laying on plain surface Space = cable d Distance from wall 2 cm Number of systems 1 2 3 Installation method
d d

For installation in grouping Space = 2x cable d Distance from wall 2 cm Number of systems 1 2 Installation method
2d 2d

on the ground on nonperforated cable troughs (restricted air circulation) on perforated cable troughs

a 20 mm

0,92 0,89 0,88

a 20 mm
2d 2d

0,98 0,96 0,94

1 2 3 6

300 mm

d d

0,92 0,87 0,84 0,82


a

0,89 0,84 0,82 0,80

0,88 0,83 0,81 0,79

0,98 0,95 0,94 0,93 a 20 mm


2d 2d a

0,96 0,91 0,90 0,88

0,94 0,87 0,85 0,82

a 20 mm

300 mm

a 20 mm

300 mm

1 2 3 6

d d

1,00 0,97 0,96 0,94

0,93 0,89 0,88 0,85

0,90 0,85 0,82 0,80

300 mm

1,00 0,97 0,96 0,95

0,98 0,93 0,92 0,90

0,96 0,89 0,85 0,83

a 20 mm
2d 2d

300 mm

on cable trays or on cable ladders (unrestricted air circulation)

d d

300 mm

1 2 3 6

1,00 0,97 0,96 0,94

0,97 0,94 0,93 0,91

0,96 0,93 0,92 0,90

1,00 0,97 0,96 0,95


a

1,00 0,95 0,94 0,93

1,00 0,93 0,90 0,87

a 20 mm

a 20 mm

225 mm Arrangements, for which a reduction not necessary 1) For the installation on plain surface with greather distance, the muntual heating, is lower for this occur the additional sheath or screen-losses. Because of that no particulars can be made for reduction-free arrangements.

2d

on platform or on the wall

d d

0,94 0,91 0,89 0,94 0,90 0,86

1,00 0,91 0,89 1,00 0,90 0,86

225 mm

* Conversion factors for deviating ambient temperature


TemperatureoC 10 15 20 25 30 35 40 45 50 XLPE-cable 1,15 1,12 1,08 1,04 1,0 0,96 0,91 0,87 0,82 PVC-cable 1,22 1,17 1,12 1,06 1,0 0,94 0,87 0,79 0,71 *1) In narrow rooms or for bigger grouping, the air temperature is increased due to energy losses of cable, so the additional conversion factors for deviating air-temperatures are to be taken in the given table.

ELKABEL

423

Designation Code for Harmonized Cables


According to DIN VDE 0281/DIN VDE 0292

TECHNICAL DATA

Construction reference
Identifications of Designation A Authorized national standards H Harmonized standards Nominal 01 03 05 07 Voltage U 100 V 300/300 V 300/500 V 450/750 V

05

V5

25

0.75

Insulation Material B G N2 R S V V2 V3 V4 Z (EPR) Ethylene-Propylene Rubber (EVA) Ethylene-Vinylacetat Copolymer (CR) Chloroprene Rubber for welding cables (NR a./o. SR) Natural a./o. Synthetic Rubber (SiR) Silicone Rubber (PVC) Polyvinyl Chloride (PVC) Polyvinyl Chloride heat-resistant (PVC) Polyvinyl Chloride low-temperature (PVC) Polyvinyl Chloride cross-linked (PE) Polyethylene cross-linked

Structural Elements C Q4 T T6 Screen (PA) Additional polymide core jacket Additional textile braiding over laid-up cores Additional textile braiding over individual cores

Sheath/Jacket Material B J N N2 N4 Q R T T2 V V2 V3 V4 V5 (EPR) Ethylene-Propylene Rubber Glass Fibre Braid (CR) Chloroprene Rubber (CR) Chloroprene Rubber for welding cables (CR) Chloroprene Rubber heat-resistant (PUR) Polyurethane (NR a./o. SR) Natural a./o. Synthetic Rubber Textile braid Textile braid with flame retardant compound (PVC) Polyvinyl Chloride (PVC) Polyvinyl Chloride heat-resistant (PVC) Polyvinyl Chloride low-temperature (PVC) Polyvinyl Chloride cross-linked (PVC) Polyvinyl Chloride oil-resistant

Special Structural Features D3 D5 FM H H2 H6 H7 H8 Stress-relieving element (support wire) Centre core (no supporting elements) Telecommunications cores integrated in power cables Flat, separable cable (twin cable) Flat, non-separable cable (two-core sheathed cable) Flat, non-separable cable (multi-core and multiple sheathed cable) Two-layer insulating jacket Spiral cables
Examples: H07V-U 2.5 black (according to DIN VDE 0281) Harmonized PVC-insulated single-core sheathed cable, 2.5 mm2 single-core, nominal voltage 750 V H07RN-F 3G, 1,5 (according to DIN VDE 0282) Harmonized rubber-sheathed cable for medium tensile loads, three-core 1.5 mm2, finely stranded, green-yellow earth core, nominal voltage 750 V

Conductor Type D E F H K R U Y Finely stranded, for welding cables (Very) finely stranded, for welding cables Finely stranded, for cables for fixed installation (Very) finely stranded, for flexible cables Finely stranded, for cables for fixed installation Multiple-wire, round, class 2 Single-wire, round, class 1 Tinsel wire, DIN 47104

Number of cores Earth Core G X With earth core Without earth core

Conductor Nominal Cross Section in mm2

424

ELKABEL

Comparison of Harmonized Cables With IEC, DIN VDE and HD

TECHNICAL DATA

PVC-Insulated Cables According to DIN VDE 0281 in Comparison with IEC and HD
Designation Accord. Short Short Nominal Nominal to VDE Designation Designation Cross-Sec- Voltage Part... New Old tion Uo/U (v) VDE 0250 (mm2)
0281 part 3 0281 part 3 0281 part 3 0281 part 3 0281 part 3 0281 part 5 0281 part 5 0281 part 5 0281 part 5 H 05V-U H 05V-K H 07V-U H 07V-R H 07V-K H 03VH-Y H 03VH-H H 03VV-F H 03VVH2-F NYFA, NYA NYFAF, NYAF NYA NYA NYAF NLYZ NYZ NYLHY rund NYLHY flach 0.5 to 1.0 300/500

According Comparative to HD design to IEC

PVC-Wiring Cables Single Wire Fine Wires PVC-Insulated Cables Single Wire Multi-Stranded Wires Fine Wires Light PVC-Twin Cables Twin Cables PVC-Sheathed Cables 03VV-F round flat

HD 21.3 S3

227 IEC 05 227 IEC 06 227 IEC 01 227 IEC 01 227 IEC 02 227 IEC 41 227 IEC 42 227 IEC 52 227 IEC 52

1.5 to 10 1.5 to 40 1.5 to 240 0.1 0.5+0.75 0.5+0.75 0.5+0.75

450/750 300/300 300/300 300/300

HD21.3 S3 HD 21.5 S3 HD 21.5 S3 HD 21.5 S3

PVC-Sheathed Cables 05 VV-F round 0281 part 5 flat PVC-Flat Cable 05VV-H6 PVC-Flat Cable 07VV-H6 0281 part 5 0281 part 403 0281 part 404

H 05VV-F H 05VVH2-F H 05VVH6-F H 07VVH6-F

NYMHY rund NYMHY rund NYMHY flach NYFLY NYFLY

0.75+2.5 1 to 2.5 0.75 0.75 to 1 1.5 to 25

300/500 HD 21.5 S3 300/500 300/500 450/750 -

227 IEC 53 227 IEC 53 -

ELKABEL

425

up to 1000 V and heat resistant cables Permissible operating temperature oat conductor 40o C to 180 oC as per type Ambient temperature 30 oC to 150 C, as per type

Current ratings for cables and insulated wires


Type designation H05V-U, -K H07V-U, -R, -K H07V3-U, -R, -K H05V2-U, H05V2-K H07V2-U, H07V2-K H05S-U, H05S-K H05RN-F, H07RN-F H03RT-F, A03RT-F H05RR-F, A05RR-F H05RN-F, A05RN-F H07RN-F, A07RN-F H03VH-Y 1),H03VH-H H03W-F, A03W-F, H03WH2-F H05W-F, A05W-F, H05WH2-F N2GMH2G H07RN-F, A07RN-F H05W5-F, H05WC4V5-K

TECHNICAL DATA

Installation: *in open air *upon or on surface

in open air

upon or on surface

d d

Number of loaded cores Cross-section, mm 0,5 0,75 1 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500
2

3 Current ratings in Ampere (A)

2 or 3

15 19 24 32 42 54 73 98 129 158 198 245 292 344 391 448 528 608 726 830

3 6 10 16 25 32 40 63 -

3 6 10 16 20 25 -

9 12 15 18 26 34 44 61 82 108 135 168 207 250 292 335 382 453 523 -

Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multicore cables and insulated wires - see DIN VDE 0298 part 4.
1)

Nominal cross-sectional area 0,1 mm2, loadable with 0,2 A, independent of the ambient temperature.

426

ELKABEL

Permissible Minimum Bending Radius


according to DIN VDE Specifications
The indicated values for bending radius stated in the following table are not permitted to fall below the value. For noncomplience of the values a short longevity is to be expected.

TECHNICAL DATA

Permissible Minimum Bending Radius for Power Cables according to DIN 0298 - Part 3 - Nominal Votage 0.6/1 kV

Cables for Fixed Installations


Outer of Cables or Thickness of Flat Cable in mm (D) Method of Laying
- for permanent laying - to form out

Up to 10 mm
4xD 1xD

> 10 to 25 mm
4xD 2xD

> 25 mm
4xD 3xD

For Flexible Cables


- for fixed installation - for free movement - to the inlet - for forced guiding operation (such as trailing) - Operation for trolly cable - operation in power drag chain - operation for return sheave

up to 8 mm
3xD 3xD 3xD 5xD 3xD 4xD 7.5xD

> 8 mm to 12 mm
3xD 4xD 4xD 5xD 4xD 4xD 7.5xD

>12 to 20 mm
4xD 5xD 5xD 5xD 5xD 5xD 7.5xD

>20 mm
4xD 5xD 5xD 6xD 5xD 5xD 7.5xD

D = outer of cables or thickness of flat table

ELKABEL

427

DESIGNATION CODE FOR TELEPHONE CABLES, JUMPER WIRES AND STRANDED HOOK-UP WIRES
according to DIN VDE 0271/0276

TECHNICAL DATA

Construction reference
Basic cable Type with additional Information A outdoor cable I installation cable YV/Li ... jumper wires/hook-up wires Insulation P dry paper Y PVC (Polyvinylchloride) 2Y PE (Polyethylene) 02Y foamed PE (cellular) 02YS foam-skin insulation Screening C screen of braided tinned copper wires F filling of cable core with petrol-jelly (St) screen of plastic coated metallic foil (L) aluminium tape Sheath L M (L)2Y Mz Material smooth aluminium sheath lead sheath copolymer coated aluminium lead alloy sheath moisture barrier sheath

Protective Coating Y PVC sheath 2Y PE sheath Number of Stranding Elements ..x1x single core ..x2x pair (double core) ..x3x triple ..x4x quad ..x5x five-core Conductor Diameter in mm Type of Stranding Components St I P PiMF St III star quad without phantom circuit twisted pair pair in metal foil star quad in local (Subscriber) cable

Stranding Layout Lg layer stranded concentric Bd unit stranding Armouring Wire b armouring B armouring of steel band for inductive protection 1B 0.3 1 layer steel tape, thickness 0.3 mm 2B 0.5 2 layers steel tape, thickness 0.5 mm

428

ELKABEL

STRUCTURE OF TELECOMMUNICATION CABLES


A-2Y(L)2Y; A-2YF(L)2Y; A-02YSF(L)2Y

TECHNICAL DATA

1. Quad formation and colour scheme

No. 1 White quad

No. 2 Yellow quad

No. 3 Gray quad

No. 4 Brown quad

No. 5 Black quad

2. Sub-unit formation
Each sub-unit consists of 5 quads (10 pair sub-unit)

3. Unit formation
1. 50 pairs units consist of 5 sub-units 2. 100 pairs units consist of 10 sub-units Colour of sub-unit binding tapes

Gray Yellow Yellow Brown Red White Black Yellow Red 5x4 (10x2) Blue Green White Blue White Blue Green Red Yellow White Blue

25x4 (50x2)

50x4 (100x2)

ELKABEL

429

STRUCTURE OF TELECOMMUNICATION CABLES


A-2Y(L)2Y; A-2YF(L)2Y; A-02YSF(L)2Y

TECHNICAL DATA

4. Core formation
Colour of unit binding tapes

3
Colour code Red Yellow Blue White Green 150x2

1 2

1 4 3
200 x 2

No. of units 1 2 3 4 5

1 5
Number of pairs
150 200 250 300 400 500 600 700 800 1000 1200

1 2 5 1 4
300x2

2 3

Core arrangement Number of units 1st layer 2nd layer


Units Units Units Units Units Units Units Units Units Units Units 50 pairs 50 pairs 50 pairs 50 pairs 100 pairs 100 pairs 100 pairs 100 pairs 100 pairs 100 pairs 100 pairs 3 4 5 1 4 5 1 1 1 3 4

4
250x2

1
5 6 7 7 8

1 2 5 4
500x2

4 3
400x2

2 3

1 5 4 1

2 3 3

1 1 1 5 4 2 3 4 3 5
800x2

2 3 4

600x2

700x2

1 1 4 3 1 5 2 3 4 3 4 3 2 5 1 4 5 2

2 3 3 4

430

ELKABEL

Das könnte Ihnen auch gefallen