Calculation of Stabilizing Resistance for Motor Earth Fault Protection (For SPACOM & RE series Relay) Parameter description

Rated Power Rated Voltage Length of cable connecting CT to Relay DC Resistance of the cable CT Primary Rated Current CT Secondary Rated Current Peak factor for during motor starting Maximum earth fault current Relay input impedance Rated Current Internal Resistance of the CT Magnetizing current of the CT at the voltage Ukn Knee point voltage of CT Motor earth fault setting CT Ratio Startup current (primary value) of the motor Resistance of the longest loop of the CT secondary circuit Primary current at which relay starts Start current(secondary value) of the earth fault protection Magnetizing current of the CT at the voltage Us Relay setting Stabilizing voltage Maximum voltage across relay duting fault (ignoring CT saturation) Peak voltage across relay during fault (considering CT saturation) Stabilizing resistance Power rating of stabilizing resistor Us Uf Upeak Rs Ps n Istart Rm Iprim Is Ie Imax Rr Inm Rct Iekn Ukn Symbol Pnm Unm L Rcable I1 I2 Value = 160 = 0.415 = 10 = 8.82 = 300 = 1 = 7.2 = 400 = 0.1 = 290 = 0.28 = 100 = 20 = 15 = 300 = 2088 = 0.18 = 43.5 = 0.09735 = 15.88 = 0.09735 = 3.176544 = 44.25 = 62.29 = 32.63 = 12.26 Unit kW kV m L&T to verify the value Remarks

/km L&T to verify the value A A A A L&T to put the value

mA L&T to put the value V % A A A mA V V V W Should be less than Relay Permissible Voltage Should be less than Relay Permissible Voltage Result Result L&T to put the value

Calculation of Stabilizing Resistance for Motor Earth Fault Protection (For SPACOM & RE series Relay) Parameter description Rated Power Rated Voltage Length of cable connecting CT to Relay DC Resistance of the cable CT Primary Rated Current CT Secondary Rated Current Peak factor for during motor starting Maximum earth fault current Relay input impedance Rated Current Internal Resistance of the CT Magnetizing current of the CT at the voltage Ukn Knee point voltage of CT Motor earth fault setting CT Ratio Startup current (primary value) of the motor Resistance of the longest loop of the CT secondary circuit Primary current at which relay starts Start current(secondary value) of the earth fault protection Magnetizing current of the CT at the voltage Us Relay setting Stabilizing voltage Us n Istart Rm Iprim Is Ie Imax Rr Inm Rct Iekn Ukn Symbol Pnm Unm L Rcable I1 I2 Value = 132 = 0.415 = 10 = 8.82 = 300 = 1 = 7.2 = 400 = 0.02 = 240 = 0.28 = 100 = 20 = 15 = 300 = 1728 = 0.18 = 36 = 0.08 = 13.14 = 0.08 = 2.628864 = 44.14 = 62.15 = 32.63 = 12.26 Unit kW kV m L&T to verify Remarks

/km L&T to verify A A A A L&T to put the value

mA L&T to put the value V % A A A mA V V V W Should be less than Relay Permissible Voltage Should be less than Relay Permissible Voltage Result Result L&T to put the value

Maximum voltage across relay duting fault (ignoring CT saturation) Uf Peak voltage across relay during fault (considering CT saturation) Stabilizing resistance Power rating of stabilizing resistor Upeak Rs Ps

Calculation of Stabilizing Resistance for Motor Earth Fault Protection (For SPACOM & RE series Relay Parameter description Rated Power Rated Voltage Length of cable connecting CT to Relay DC Resistance of the cable CT Primary Rated Current CT Secondary Rated Current Peak factor for during motor starting Maximum earth fault current Relay input impedance Rated Current Internal Resistance of the CT Magnetizing current of the CT at the voltage Ukn Knee point voltage of CT Motor earth fault setting CT Ratio Startup current (primary value) of the motor Resistance of the longest loop of the CT secondary circuit Primary current at which relay starts Start current(secondary value) of the earth fault protection Magnetizing current of the CT at the voltage Us Relay setting Stabilizing voltage Maximum voltage across relay duting fault (ignoring CT saturation) Peak voltage across relay during fault (considering CT saturation) Stabilizing resistance Power rating of stabilizing resistor Us Uf Upeak Rs Ps n Istart Rm Iprim Is Ie Imax Rr Inm Rct Iekn Ukn Symbol Pnm Unm L Rcable I1 I2 Value = 110 = 0.415 = 10 = 8.82 = 250 = 1 = 7.2 = 400 = 0.02 = 200 = 0.28 = 100 = 20 = 15 = 250 = 1440 = 0.18 = 30 = 0.08 = 13.14 = 0.08 = 2.628864 = 52.97 = 72.63 = 32.63 = 12.26 Unit kW kV m /km A A A A mA V % A A A mA V V V W

nce for Motor Earth Fault Protection (For SPACOM & RE series Relay) Remarks

L&T to verify L&T to verify

L&T to put the value L&T to put the value L&T to put the value

Should be less than Relay Permissible Voltage Should be less than Relay Permissible Voltage Result Result

Calculation of Stabilizing Resistance for Motor Earth Fault Protection (For SPACOM & RE series Relay Parameter description Rated Power Rated Voltage Length of cable connecting CT to Relay DC Resistance of the cable CT Primary Rated Current CT Secondary Rated Current Peak factor for during motor starting Maximum earth fault current Relay input impedance Rated Current Internal Resistance of the CT Magnetizing current of the CT at the voltage Ukn Knee point voltage of CT Motor earth fault setting CT Ratio Startup current (primary value) of the motor Resistance of the longest loop of the CT secondary circuit Primary current at which relay starts Start current(secondary value) of the earth fault protection Magnetizing current of the CT at the voltage Us Relay setting Stabilizing voltage Maximum voltage across relay duting fault (ignoring CT saturation) Peak voltage across relay during fault (considering CT saturation) Stabilizing resistance Power rating of stabilizing resistor Us Uf Upeak Rs Ps n Istart Rm Iprim Is Ie Imax Rr Inm Rct Iekn Ukn Symbol Pnm Unm L Rcable I1 I2 = 90 = 0.415 = 10 = 8.82 = 200 = 1 = 7.2 = 400 = 0.02 = 165 = 0.28 = 100 = 20 = 15 = 200 = 1188 = 0.18 = 24.75 = 0.08 = 13.56 = 0.08 = 2.711016 = 66.21 = 85.99 = 32.63 = 12.26 Value Unit kW kV m /km A A A A mA V % A A A mA V V V W

ance for Motor Earth Fault Protection (For SPACOM & RE series Relay) Remarks

L&T to verify L&T to verify

L&T to put the value L&T to put the value L&T to put the value

Should be less than Relay Permissible Voltage Should be less than Relay Permissible Voltage Result Result