Calculations for volume of storage reservoir at

(Change values only in the hilighted cells)

Flow at Inlet (L/s)


=
0.22
Av Daily Demand (L/s) =
0.22
Q = Inlet (l/s)
Period
0.22
Liters (1)
Seconds
5.30 - 8.30
10,800
2,376
8.30 - 11.30
10,800
2,376
11.30 - 13.30 7,200
1,584
13.30 - 16.00 9,000
1,980
16.00 - 21.00 18,000
3,960
21.00 - 5.30
30,600
6,732
Daily inlet =
19,008

D = Outlet (lit/day)
Difference Water level
19,008
(+/-)
in liters
Liters
(2)
%
{3}
{4)
30
5,702
(3,326)
(3,326)
10
1,901
475
(2,851)
15
2,851
(1,267)
(4,118)
10
1,901
79
(4,039)
30
5,702
(1,742)
(5,782)
5
950
5,782
Daily demand =
19,008
100

Figures in () indicates -ve sign

Min storage capacity =


5782 (lit) =
5.7816 (cu.m)
Tank is filled within
7.30 hours (must be less than 10 hours)
Taking 8 hours as min ret. Time, capacity of the tank =
6336 (lit) =
Hence Choosing this as the required capacity of the tank
Effec. Depth (Pl.Specify)
=
1.52 Mtr
=
5.00 Ft
2
=
Surface Area
=
4.16 M
44.76 Ft2
L/W (Pl.Specify)
=
1.00
W
=
2.04 Mtr
=
6.69 Ft Say
L
=
2.04 Mtr
=
6.69 Ft Say
Actual Capacity

245 cft

(cu.m)

7
7

6937 Lit------------------O.K.

Final Dimensions (with a free board of 1 ft in below supply)


L= 7
210
cm
W= 7
210
cm
D = 6.00
180
cm

(1) = Q x seconds
(2) = D x %
(3) = (1) - (2)
(4) = sum of (3)

6.336

Water level: Indicate whether -ve or +ve


Min. storage capacity = smallest (4), (negative)

Das könnte Ihnen auch gefallen