Sie sind auf Seite 1von 1

Preliminary Heat Exchanger Design (U.S.

units) Estimation of Heat Transfer Area Needed

Inputs
Fluid1 mass flow rate, m1 = 25,000 lb/hr

Calculations
Heat Transfer Rate, Q = 925,000 Btu/hr

Log Mean Temp Fluid1 temp. in, T1in = 190


o

79.6

Diff, DTlm =

Fluid1 temp. out, T1out =

140

Heat Transfer Area, A =

96.9

ft2

Fluid1 sp. heat, Cp1 =

0.74

Btu/lb-oF

Fluid2 mass flow rate, m2 = 13,214 lb/hr

Fluid2 temp. in, T2in =

50

Fluid2 temp. out, T2out =

120

Fluid2 sp. heat, Cp2 = Overall heat transf. coeff. estim., U =

1.0

Btu/lb-oF

120

Btu/lhr-ft2-oF

Equations used for calculations:


Q = + (m1)(Cp1)(T1in - T1out) Q = + (m2)(Cp2)(T2in - T2out) DTlm = [(T1in - T2out) - (T1out - T2in)]/ln[(T1in - T2out)/(T1out - T2in)] Q = U A DTlm