The ControlLogix architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Description Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Cat. No. 1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16 1756-IB16 1756-IB16D 1756-IB16I 1756-IB16IF 1756-IB16IOSE 1756-IB32 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32 1756-OB8 1756-OB8EI
Cat. No. 1756-LSC8XIB8I 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8 1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IEF 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E
Page 205 103 106 109 113 178 125 128 132 135 138 142 146 150 172 175 182 186
DC digital
Contact Analog 1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IT6I 1756-IT6I2 1756-IF8H 1756-IF16H 1756-CFM 1756-HSC 38 42 47 55 62 81 86 90 51 59 196 201
1756-IA8D
ControlLogix AC (79132V) diagnostic input module
Simplified Schematic +5V
Not Used Daisy Chain to Other RTBs 1756-IA8D
2 4 1
L2-0
6 5
IN-0 IN-1
8 7
IN-2 IN-3
12 11
Group 0
L2-0 L2-1
14 13
47 k, 1/2 W 5% Resistor
IN-4 IN-5
16 15
L2-1 L2-1
18 17
IN-6 IN-7
20 19
Group 1
47 k, 1/2 W, 5% Resistor
L2-1
AC INPUT
ST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T
L2-1 L2 L1
DIAG STIC NO
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA16
ControlLogix AC (79132V) input module
1756-IA16
Simplified Schematic IN-O L2-0 GND ControlLogix Backplane Interface Display +5V
Group 0 Daisy Chain to Other RTBs
IN-1
4 3
IN-0 IN-2
6 5
IN-3 IN-5
8 7
IN-4 IN-6
10 9
Group 0
IN-7 L2-0
12 11
L2-0 IN-8
14 13
IN-9 IN-11
16 15
IN-10 IN-12
18 17
AC INPUT
ST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T
Group 1
IN-13 IN-15
20 19
Group 1
IN-14 L2-1
L2-1
DIAG STIC NO
L2
L1
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
C-Tick FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA16I
ControlLogix AC (79132V) isolated input module
Simplified Schematic IN-O L2-0
L2-4 Isolated Wiring L2-0 L2-2 L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 L2-7 Jumper Bar (Cut to Length) L2-8 L2-9 L2-10 L2-11 Nonisolated Wiring L2-12 L2-13 L2-14 L2-15 L2 L2-15 Not used 1756-IA16I
2 4 6 8 10 1 3 5 7 9
+5V
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
L1
AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
10
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
,
C-Tick FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
11
1756-IA32
ControlLogix AC (74132V) input module
Simplified Schematic IN-O L2-0 GND ControlLogix Backplane Interface Display +5V
IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 L2-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 L2-1
1756-IA32
2 4 6 8 10
1 3 5 7 9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 L2-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 L2-1
Group 0
Group 1
Group 1
AC INPUT
ST 0 1 2 3 4 5 6 7
L1
1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6
1 1 1 9 2 7
1 2 2 0 2 8
1 3 2 1 2 9
1 4 2 2 3 0
1 O 5 K 2 3 3 1
L2
12
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
13
1756-IA32
4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
C-Tick KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
14
1756-IB16
ControlLogix DC (1031.2V) input module
Simplified Schematic
?
1756-IB16
IN-1
? ?
IN-0 IN-2
? ?
IN-3
IN-5
? ?
IN-4 IN-6
?
Group 0
IN-7 GND-0
?
GND-0 IN-8
? ?
IN-9 IN-11
IN-10
? ?
DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
Group 1
O K
IN-13
? ?
IN-12 IN14
? ?
Group 1
IN-15 GND-1
GND-1
DC COM
15
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
16
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
17
1756-IB16D
ControlLogix DC (1030V) diagnostic input module
Simplified Schematic Input IN-0 +5V ControlLogix Backplane Interface Display
Daisy Chain to Other RTBs GND-0 Group 0 GND-0 GND-0 GND-0 GND-1 GND-1 GND-1 GND-1 1756-IB16D
2 4 6 8 10 1 3 5 7 9
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used Group Leakage Resistor Group Leakage Resistor Group
Group 1
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Group
GND-2 Group 2 GND-2 GND-2 GND-2 GND-3 GND-3 Group 3 GND-3 GND-3 GND-3 Not Used
DC INPUT
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC
DC COM
18
On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
19
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick
20
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16I
ControlLogix DC (1030V) isolated input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
Isolated Wiring DC-0 (-) DC-1 (-) GND-0 GND-1 GND-2 Source Input Wiring DC-5 (-) DC-6 (-) Jumper Bar (Cut to Length) GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 Nonisolated Wiring GND-12 GND-13 GND-14 GND-15 DC (-) GND-15 Not Used
10
1 3 5 7 9
2 4 6 8
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
(+) (+)
DC (+)
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
21
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
22
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
23
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
24
1756-IB16IF
ControlLogix DC (1030V) sinking or sourcing, isolated, fast input module
Simplified Schematic IN-x GND-x Current Limiter Opto-isolator Display ControlLogix Backplane Interface
Isolated Wiring
GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15 DC (-) GND-15 Not Used
1756-IB16IF
2 4 6 8
10 1 3 5 7 9
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+) DC-1 (+) DC-2 (+)
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
(+) (+)
Nonisolated Wiring
O K
PEER DEVICE
25
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
26
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
27
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB16ISOE
ControlLogix DC (1055V) sequence of events input module
Simplified Schematic Electronic Current Limit Circuit IN-0
Isolated Wiring GND-0 GND-1 +5V GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 (Cut to Length) ControlLogix Display GND-10 Backplane GND-11 Nonisolated Interface GND-12 Wiring GND-13 GND-14 GND-15 Additional jumper bars are available GND-15 DC (-) as cat. no. 1756-JMPR. Not Used DC-0 (-)
2 4 6 8 1 3 5 7
1756-IB16ISOE
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
GND-0
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)
SOE INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
28
On to Off
Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, nom On-state current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
29
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 2.5 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
30
C-Tick KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IB32
ControlLogix DC (1031.2V) input module
Simplified Schematic IN-0 GND-0 GND ControlLogix Display Backplane Interface Current Limiter +5V
IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 GND-1 1756-IB32
2 4 6 8 10 1 3 5 7 9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Group 1
DC INPUT
ST 0 1 2 3 4 5 6 7
IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 GND-1
Group 0
Group 1
1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6
1 1 1 9 2 7
1 2 2 0 2 8
1 3 2 1 2 9
1 4 2 2 3 0
1 O 5 K 2 3 3 1
DC COM
31
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
32
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
33
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IC16
ControlLogix DC (3060V) input module
1756-IC16
Simplified Schematic
IN-1
IN-0
4 3
+5V
IN-3
IN-2
6 5
Group 0
IN-5
8 7
IN-4 IN-6
10 9
Group 0
IN-7 GND-0
12 11
Display
GND-0 IN-8
14 13
IN-9 IN-11
16 15
IN-10 IN-11
18 17
Group 1
IN-13 IN-15
Group 1
IN-14
20 19
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
GND-1
GND-1
DC COM
34
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
35
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
36
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
37
1756-IF6CIS
ControlLogix sourcing current loop analog input module
1756-IF6CIS 2-wire Transmitter Connected to the Module and the Module Providing 24V DC Loop Power
2 1
1756-IF6CIS 2-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1
VOUT-1
4 3
VOUT-0 IN-0/I
6 5
VOUT-1
4 3
VOUT-0 i
A
IN-1/I RTN-1
8 7
IN-1/I
6 5
IN-0/I RTN-0
8 7
RTN-0 VOUT-2
10 9
i
RTN-1 VOUT-3 Shield Ground
24V DC +
2-wire Transmitter
VOUT-3 IN-3/I
12 11
VOUT-2
10 9
IN-2/I RTN-2
14 13
IN-3/I
12 11
IN-2/I RTN-2
14 13
Shield Ground
VOUT-5 IN-5/I
20 19
VOUT-5 IN-5/I
20 19
IN-4/I RTN-4
IN-4/I RTN-4
RTN-5
RTN-5
Place additional loop devices (such as strip chart recorders) at either A location in the current loop.
1756-IF6CIS 4-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1
VOUT-1
4 3
VOUT-0 IN-0/I
6 5
i
A + +
IN-1/I RTN-1
8 7
RTN-0 VOUT-2
10 9
4-wire Transmitter
24V DC
VOUT-3 IN-3/I
12 11
IN-2/I RTN-2
14 13
Shield Ground
VOUT-5 IN-5/I
20 19
IN-4/I RTN-4
RTN-5
Place additional loop devices (such as strip chart recorders) at either A location in the current loop. User-supplied power supply must not exceed 150VA.
38
39
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
40
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
41
1756-IF6I
ControlLogix isolated voltage/current analog input module
1756-IF6I Current 2-wire
2 1
IN-1/V
4 3
IN-0/V IN-0/I
6 5
+
2-wire Transmitter
IN-1/V
4 3
IN-0/V
IN-1/I RET-1
8 7
i A A
+
IN-0/I
IN-1/I
6 5
A A
4-wire Transmitter
RET-0 IN-2/V
10 9
RET-1
8 7
RET-0 IN-2/V
10 9
IN-3/V IN-3/I
12 11
IN-3/V IN-3/I
12 11
IN-2/I RET-2
14 13
IN-2/I RET-2
14 13
Shield Ground
IN-5/V IN-5/I
20 19
IN-4/I RET-4
RET-5 RET-4
RET-5
Place additional loop devices (such as strip chart recorders) at either A location.
42
IN-1/V
4 3
IN-0/V IN-0/I
6 5
+
User Analog Input Device
IN-1/I RET-1
8 7
RET-0 IN-2/V
10 9
IN-3/V IN-3/I
12 11
ANALOG INPUT
IN-2/I
CAL
RET-2
RET-3
14 13
OK
Not Used
Not Used
16 15
IN-5/V
18 17
IN-4/V IN-4/I
20 19
IN-5/I RET-5
Shield Ground
RET-4
Resolution
43
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
44
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
45
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
46
1756-IF8
ControlLogix voltage/current analog input module
1756-IF8 Differential Current Channel 0 Channel 0 1756-IF8 Differential Voltage
i
A
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground Channel 3 Jumper Wires Shield Ground
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
i
A
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-)
All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.
All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.
47
i
IN-0 IN-1 IN-2
2 4 6 8 10 1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Jumper Wires
Channel 0
+
IN-0
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
IN-3 RTN
i
2-wire Transmitter
IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Shield Ground
Not Used Not Used Not Used Not Used Not Used Not Used Not Used
All terminals marked RTN are connected internally. For current applications, all terminals marked iRTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and i RTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop.
All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring.
48
Input range
Resolution
Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time
Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min
On-board data alarming Scaling to engineering units Real-time channel sampling Data format Module conversion method Isolation voltage
49
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
50
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IF8H
ControlLogix voltage/current analog input module with HART protocol
1756-IF8H Current 1756-IF8H Voltage
Voltage Input +V IN0+
IN0+ IN0IN1+ 4 Wire Current Input IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN72 4 6 8 1 3 5 7 I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC
+ -
+-
2 4 6 8
1 3 5 7
I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC
-V
IN0IN1+ IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN7-
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
+ + Wire + 4 XMTR - - -
51
Resolution Current draw @ 5V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Module HART scan time
Data format Input conversion method Output conversion method Isolation voltage
52
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
53
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
54
1756-IF16
ControlLogix voltage/current analog input module
1756-IF16 Differential Current Channel 0 1756-IF16 Differential Voltage Channel 0 IN-0 IN-1 IN-2 Shield Ground Channel 3 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9
i
A i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15
IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
i
A
Channel 3
Shield Ground
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6 IN-8 (+), IN-9 (-), i RTN-8 IN-10 (+), IN-11 (-), i RTN-10 IN-12 (+), IN-13 (-), i RTN-12 IN-14 (+), IN-15 (-), i RTN-14
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-) IN-8 (+), IN-9 (-) IN-10 (+), IN-11 (-) IN-12 (+), IN-13 (-) IN-14 (+), IN-15 (-)
All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.
All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.
55
i
IN-0 IN-1 IN-2 Shield Ground 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15 Jumper Wires Shield Ground
IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15
i
A
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Shield Ground
All terminals marked RTN are connected internally. For current applications, all terminals marked i RTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and iRTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop.
All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring.
56
Resolution
Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time
Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F) Offset drift Gain drift with temperature Module error Module input scan time, min
On-board data alarming Scaling to engineering units Real-time channel sampling Data format Module conversion method Isolation voltage
Module keying
57
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
58
UL CSA CE
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IF16H
ControlLogix current analog input module with HART protocol
2 Wire HART Device
2 Wire XMTR 24V DC Power Supply
+ -
+-
2 4 6 8 10
1 3 5 7 9
When a common supply is used you should tie the IN- to RTN.
+ + -
+ -
4 Wire XMTR
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
59
Data format Input conversion method Output conversion method Isolation voltage
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
60
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 3 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
61
1756-IF4FXOF2F
ControlLogix high-speed input/output analog module
1756-IF4FXOF2F Current
(-) i
(+) (+) User Analog Input Device (-) Shield Ground +IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used 1756-IF4FXOF2F Voltage
(+)
2-wire A Transmitter
A
+IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
2 4 6
1 3 5
+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 i I OUT-0 RTN-0 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
A
2 4 6 8
1 3 5 7
+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 I OUT-0 RTN-0 Not Used (-) Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground (+)
8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 24 26 28 21 23 25 27
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
30 29 32 31 34 33 36 35
Module keying
62
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
1756-IF4FXOF2F
4 high-speed, sub-millisecond, differential 10.5V 010.5V 05.25V 021 mA (over-range indication when exceeded) Approx 14 bits across 10.5V DC (21V total) 10.5V range: 1.3 mV/bit, 14-bit effective 010.5V range: 1.3 mV/bit, 13-bit effective 05.25V range: 1.3 mV/bit, 12-bit effective Approx 12 bits across 21 mA 021 mA range: 5.25 A/bit 1 Least Significant Bit (LSB)(1) Voltage: >1 M Current: 249 Positive full-scale reading within 1 s Voltage: 30V DC Current: 8V AC/DC 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months Voltage: 25 ppm/C max Current: 35 ppm/C max 0.2% of range 300 s min(2) Successive approximation
Resolution
Repeatability Input impedance Open circuit detection Overvoltage protection Calibrated accuracy @ 25 C (77 F) Calibration interval Gain drift with temperature Module error Module scan time Input conversion method
(1) Repeatability is defined as the stability of the input channel reading when a steady state signal is applied, for example, 1 LSB is one count (1.3 mV) from the nominal reading. (2) 300 s min for 1756-IF4FXOF2F, Series B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F, Series A, firmware revision 1.x.
63
1756-IF4FXOF2F
2 high-speed voltage or current 10.4V 021 mA 13 bits across 21 mA = 2.8 A/bit 14 bits across 21.8V = 1.3 mV/bit Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: >2000 Current: 0750 < 2 ms to 95% of final value with resistive loads 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months 50 V/ C 1 A/ C Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.2% of range Current: 0.3% of range 1 ms R-Ladder DAC, monotonicity with no missing codes
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
64
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
65
1756-IG16
ControlLogix TTL input module
Standard Wiring
1756-IG16
DC
2 1
CE Compliant Wiring
1756-IG16
I/O Wire
IN-1
IN-0
4 3
IN-1
4 3
IN-0 IN-2
6 5
IN-3
6 5
IN-2 IN-4
8 7
5V DC
IN-3 IN-5
8 7
IN-5
IN-4 IN-6
10 9
I/O Wire
+
TTL Input Device
IN-7
+ DC
DC Power Wire
IN-7
10 9
IN-6
DC COM 0
12 11
DC-0(+) IN-9
14 13
DC-0(+)
12 11
DC COM 0
IN-8 IN-10
16 15
IN-9
14 13
IN-8 IN-10
16 15
IN-11
5V DC Power
IN-11 IN-13
18 17
IN-13
18 17
IN-12 IN-14
20 19
IN-12
IN-15
IN-15
20 19
IN-14
DC COM 1
DC-1(+)
DC COM 1
DC-1(+)
Simplified Schematic
+5 DC 1.5 K IN 1K 74HCT14 560
IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
DC COM
66
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
67
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 1 kV at 5 kHz on signal ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
68
1756-IH16I
ControlLogix DC (90146V) isolated input module
1756-IH16I
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
DC-7 (-) Jumper Bar (Cut to Length) DC-0 (-) Isolated Wiring DC-3 (-) GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15 GND-15 Not Used
2 4 6 8 1 3 5 7
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Ysed
DC-0 (+)
DC-3 (+)
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
D C-7 (+ )
Nonisolated Wiring
DC (-)
DC (+)
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
69
Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type Reverse polarity protection
(1) 90146V DC @ 50 C (122 F),12 channels on 90132V DC @ 55 C (131 F), 14 channels on 90125V DC @ 60 C (140 F), 16 channels on 90146V DC @ 30 C (86 F), 16 channels on. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing
70
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
71
1756-IH16ISOE
ControlLogix DC (90140V) sequence of events input module
Simplified Schematic +5V IN-0
1756-IH16ISOE
Isolated Wiring GND-0 GND-1 GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar ControlLogix Display GND-9 (Cut to Length) Backplane GND-10 Interface GND-11 Nonisolated GND-12 Wiring GND-13 GND-14 Additional jumper bars are available GND-15 as cat. no. 1756-JMPR. GND-15 DC (-) Not Used DC-0 (-)
2 4 6 8 1 3 5 7
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
GND-0
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)
SOE INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O K
On to Off
Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max
72
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
73
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
C-Tick KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
74
1756-IM16I
ControlLogix AC (159265V) input module
Simplified Schematic
Isolated Wiring 1756-IM16I
IN-O L2-0
+5V
L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 L2-7 L2-8 L2-9 L2-10 L2-11
2 4 6 8 10
1 3 5 7 9
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used L1
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Nonisolated Wiring
L2
AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
75
Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type
(1) 159265V AC, 4763Hz @ 30 C (86 F) all channels on 159265V AC, 4763Hz @ 40 C (104 F) 8 points on 159253V AC, 4763Hz @ 45 C (113 F) all channels on 159242V AC, 4763Hz @ 60 C (140 F) all channels on. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
76
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
77
1756-IN16
ControlLogix AC (1030V) input module
Simplified Schematic IN-O L2-0 GND
L2 Group 0 IN-7
10 9
1756-IN16
+5V
IN-1 L1 IN-3
IN-0
4 3
IN-2
6 5
IN-5
8 7
Display
L2-0 IN-9
14 13
IN-8 IN-10
16 15
AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
IN-12 IN-14
20 19
Group 1
IN-15 L2-1
L2-1
78
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
79
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
80
1756-IR6I
ControlLogix temperature sensing analog input module
1756-IR6I 3-wire RTD
2 1
IN-1/A
4 3
IN-0/A IN-0/B
6 5
IN-1/B RTN-1/C
8 7
IN-3/A IN-3/B
12 11
IN-2/B RTN-2/C
14 13
Shield Ground
IN-5/A IN-5/B
20 19
IN-4/B RTN-4/C
RTN-5/C
IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x/B and RTN-x/C are shorted together as shown.
81
IN-1/A
4 3
IN-0/A IN-0/B
6 5
IN-1/B RTN-1/C
8 7
IN-3/A IN-3/B
12 11
IN-2/B RTN-2/C
14 13
ANALOG INPUT
Shield Ground
CAL OK
IN-5/A IN-5/B
20 19
IN-4/B RTN-4/C
RTN-5/C
Wiring is exactly the same as the 3-wire RTD with one wire left open.
82
Resolution
Sensors supported
Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Open circuit detection time
Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time
83
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
84
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
85
1756-IT6I
ControlLogix temperature sensing analog input module
1756-IT6I
2 1
+
IN-0
IN-0
4 3
RTN-1
IN-2 Thermocouple
IN-3
10 9
ANALOG INPUT
CJC+
Not Used
12 11
CAL
RTN-3
RTN-2
14 13
OK
CJC-
Not Used
16 15
Wire
IN-5
18 17
RTN-4
One CJC, part number 94238301, is shipped with the module. A replacement can be ordered as RP-94238301.
Thermocouples
86
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
87
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
88
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
89
1756-IT6I2
ControlLogix enhanced thermocouple analog input module
1756-IT6I Cold Junction Sensor
Wire
Spade Lug
Thermocouple
Analog Input
CAL OK
?
IN-3 IN-4 IN-5 CJC+ Not used
Wire
Spade Lug
Two CJCs, part number 94286501, are shipped with the module. Replacements can be ordered as RP-94286501.
90
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
91
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
92
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
93
1756-IV16
ControlLogix DC (1030V) sourcing input module
1756-IV16
IN-0
4 3
IN-3
6 5
IN-5 IN-7
10 9
IN-6 DC-0 +
12 11
DC-0 + IN-9
14 13
IN-8 IN-10
16 15
IN-12 IN-14
20 19
Group 1
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 1 1 21 1 5 K 0 11 3 41
IN-15 DC-1 +
DC-1 +
+
Daisy Chain to Other RTBs
DC COM
94
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
95
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
96
1756-IV32
ControlLogix DC (1030V) sourcing input module
Simplified Schematic +5V DC-0+
Group 0 IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 1756-IV32
2 4 6 8 10 1 3 5 7 9
IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 DC-0 (+) IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 DC-1 (+) Group 1 Group 0
IN-0
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Jumper Wire
DC INPUT
ST 0 1 2 1 ST 8 9 0 11 1 ST 6 7 8 22 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 1 3 2 1 2 9 6 1 4 2 2 3 0 7 1 O 5 K 2 3 3 1
Group 1
DC COM
97
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
98
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
99
1756-OA8
ControlLogix AC (74265V) output module
Simplified Schematic +5V L1-0
2 1
1756-OA8
L1-0
4 3
OUT-0 OUT-1
6 5
L1-0
Group 0
L1-0
8 7
OUT-2 OUT-3
10 9
Group 0
L1-0 L1-0
12 11
L1-1
20 A Current
Surge
L1-1 Group 1 L1-1
OUT-5
16 15
OUT-6
18 17
Group 1
L1-1
20 19
2A 0 43 ms
L1-1
Time
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
100
Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
101
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8k V air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
102
1756-OA8D
ControlLogix AC (74132V) diagnostic output module
Simplified Schematic ControlLogix Backplane Interface Diagnostic Control Block with Opto and Transformer Isolation
VAC Short Verify/ No Load GATE
Group 0
2
1756-OA8D
1
L1
Not Used
4 3
L2-0 OUT-0
6 5
L1-0 L1-0
8 7
OUT-1 OUT-2
10 9
Group 0
OUT L2
L1-0 L1-0
Display
OUT-3
12 11
Surge Current Chart 8A Current 5A 1A 500 mA 0 Time Surge @ 30 C (86 F) Surge @ 60 C (140 F) Continuous @ 30 C (86 F) Continuous @ 60 C (140 F) 43 ms
L1-1
14 13
OUT-4 OUT-5
16 15
L1-1 L1-1
OUT-6
18 17
Group 1 L1-1
Group 1 OUT-7
20
19
L1-1
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
FLT 0 1 2 3 4 5 6 7
DIAGNOSTIC
103
On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage
Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
104
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
105
1756-OA8E
ControlLogix AC (74132V) electronically-fused output module
Simplified Schematic ControlLogix Backplane Interface Opto and Transformer Isolation
VAC Short GATE
L1-0
6 5 2
1756-OA8E
1
L1
Not Used
4 3
Group 0
L1-0 L1-0
10 9
Group 0
OUT-2 OUT-3
12 11
OUT-4 OUT-5
16 15
L1-1 L1-1
18 17
OUT-6 OUT-7
20 19
Group 1
L1-1 L1-1
Group 1
L2-1 L2
2A 0 43 ms
Daisy Chain to Other RTBs L1
Time
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7K
ELECTRONICALLY FUSED
106
On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage
Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
107
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1k V line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
108
1756-OA16
ControlLogix AC (74265V) output module
Simplified Schematic ControlLogix Backplane +5V Interface L1-0
OUT-1 Group 0 Daisy Chain to Other RTBs
4 3
1756-OA16
2 1
OUT-0 OUT-2
6 5
OUT-3 OUT-5
8 7
L2-0
OUT-4 OUT-6
10 9
Group 0
OUT-7 L1-0
12 11
L2-0 OUT-8
14 13
OUT-9 OUT-11
16 15
OUT-10 OUT-12
18 17
OUT-13 OUT-15
Group 1
L1 OUT-14
L2-1
20
19
20 A Current 5A 2A 500 mA 0
L2
43 ms Time
AC OUTPUT
ST 0 1 2 3 4 5 6 7 FUSE ST 8 9 10 11 12 13 14 15 FUSE O K
109
On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Surge current per group Load current, min Commutating voltage Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage
Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width
110
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
111
C-Tick FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
112
1756-OA16I
ControlLogix AC (74265V) isolated output module
Simplified Schematic +5V L1-0
1756-OA16I Isolated Wiring L1-0 L1-2 L1-4 L1-0 L1-1 L1-2 L1-3 L1-4 L1-5 L1-6 L1-7 Jumper Bar (Cut to Length) L1-8 L1-9 L1-10 Nonisolated Wiring L1-11 L1-12 L1-13 L1-14 L1-15 L1 L1-15 Not Used
10 1 3 5 7 9 2 4 6 8
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used L2
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
2A 1A 0 Time 43 ms
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
On to Off
113
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
114
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
115
C-Tick FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
116
1756-OB8
ControlLogix DC (1030V) output module
Simplified Schematic DC-0(+) +5V OUT-0
Group 0 Daisy Chain to Other RTBs
2
1756-OB8
1
DC-0 (+)
4 3
OUT-0 OUT-1
6 5
Group 0
OUT-2
8 7
RTN OUT-0
DC-0 (+)
10 9
RTN OUT-0
4A
Surge
DC-1 (+) Group 1
OUT-4
14 13
OUT-5
16 15
Group 1 OUT-6
Current
Continuous @ 60 C (140 F) 2A
DC-1 (+)
18 17
DC-1 (+)
20 19
RTN OUT-1
0 Time
10 ms
Daisy Chain to Other RTBs
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
117
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
118
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
119
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
120
1756-OB8EI
ControlLogix DC (1030V) electronically-fused, isolated output module
1756-OB8EI
+5V
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0
Nonisolated Wiring
DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Current
Continuous @ 60 C (140 F) 2A
0 Time
10 ms
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7 K
ELECTRONICALLY FUSED
121
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
122
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
123
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
124
1756-OB8I
ControlLogix DC (1030V) isolated output module
+5V Simplified Schematic DC-0(+)
Isolated Wiring 1756-OBI
OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0
Current
Continuous @ 60 C (140 F) 2A
DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used
2 4 6 8
1 3 5 7
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
0 Time
10 ms
DC OUTPUT
ST 01234567 O K
125
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
126
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
127
1756-OB16D
ControlLogix DC (19.230V) diagnostic output module
Simplified schematic +5V +5V Short Circuit Detect Optoisolation +5V + DC
Daisy Chain to Other RTBs +DC-0 +DC-0 +DC-0 +DC-0 Group 0 +DC-0 +DC-0 +DC-0 GND-0 +DC-1 +DC-1 +DC-1 +DC-1 +DC-1 Group 1 +DC-1 +DC-1 GND-1 GND-1 Not Used Daisy Chain to Other RTBs 1756-OB16D
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used Group 1 Group 0
OUT ControlLogix Backplane Interface RTN Display Output Verify/No Load Surge Current Chart 4A Surge
Current
2A
32
34 36
0 Time
10 ms
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC
128
Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
129
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
130
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
131
1756-OB16E
ControlLogix DC (1031.2V) electronically-fused output module
Display Simplified Schematic Optoisolation
1756-OB16E
DC-0(+)
OUT-1 OUT-3
OUT-0
4 3
Group 0
OUT-2
6 5
Group 0
OUT-5
8 7
OUT-4 OUT-6
10 9
OUT-7 DC-0(+)
12 11
OUT-9
OUT-11
16 15
OUT-10 OUT-12
18 17
2A Current 1A
OUT-13
Group 1 OUT-14
Continuous @ 60 C (140 F)
OUT-15
20 19
DC-1(+)
RTN OUT-1
0 Time
10 ms
+
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE K ST 8 9 10 11 12 13 14 15 FUSE ELECTRONICALLY FUSED
132
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
133
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
134
1756-OB16I
ControlLogix DC (1030V) isolated output module
Simplified Schematic
Isolated Wiring 1756-OB16I Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)
DC-0(+) +5V
DC-0 (+) DC-1 (+) DC-2 (+) DC-3 (+) DC-4 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)
Nonisolated Wiring
DC(+)
Current
2A 1A 0 Time
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
135
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing
136
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
137
1756-OB16IEF
ControlLogix DC (1030V) electronically-protected, sinking or sourcing, isolated, fast output module
1756-OB16IEF
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)
DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)
Nonisolated Wiring
Current
DC(+)
DC OUTPUT
ST 0 1 2 3 4 5 6 7 DIAG 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 DIAG 8 9 10 11 12 13 14 15
O K
PEER DEVICE
138
Module keying Fusing Reverse polarity protection Removable terminal block RTB keying Slot width Wire category
139
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
140
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
141
1756-OB16IS
ControlLogix DC (1030V) scheduled, isolated output module
Simplified Schematic
Isolated Wiring 1756-OB16IS
DC-0(+) +5V
Current
DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking Output Wiring DC-5 (+) DC-6 (+) DC-6 (+) + DC-7 (+) Jumper Bar DC-8 (+) (Cut to Length) DC-9 (+) DC-10 (+) DC-11 (+) Nonisolated DC-12 (+) Wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not Used DC-0 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used
DC-6 (-)
DC(-)
0 Time
10 ms
DC OUTPUT
ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 O K
142
Removable terminal block RTB keying Slot width Wire category Wire type North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
143
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
144
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
145
1756-OB32
ControlLogix DC (1031.2V) output module
1756-OB32
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1
Group 0
1A Current 0.5 A 0
Group 1
10 ms Time
_
DC COM
DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 4 11 12 12 90 22 78 5 6 11 3 4 22 1 2 23 9 0 7 1 O 5 K 2 3 3 1
146
Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
147
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
148
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
149
1756-OC8
ControlLogix DC (3060V) output module
Simplified Schematic +5V OUT-0
DC-0 (+) Daisy Chain to Other RTBs
1756-OC8
2 1
DC-0(+)
DC-0 (+)
4 3
OUT-0 OUT-1
6 5
Group 0 OUT-2
DC-0 (+)
10 9
OUT-4
14 13
DC-1(+)
16 15
DC-1(+) DC-1(+)
OUT-7
20 19
Current
2A
Continuous @ 60 C (140 F)
RTN OUT-1
RTN OUT-1
0 Time
10 ms
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
150
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
151
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
152
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
153
1756-OF4
ControlLogix voltage/current output analog module
1756-OF4 Current
2 1
1756-OF4 Voltage
Not Used
4 3
VOUT-0 IOUT-0
6 5
i
A Current Output Load
+
VOUT-0 IOUT-0
Not Used
4 3
Not Used
6 5
RTN VOUT-1
10 9
RTN
8 7
RTN VOUT-1
10 9
IOUT-1 VOUT-2
14 13
IOUT-1
12 11
Shield Ground
Shield Ground
Not Used
14 13
VOUT-2 IOUT-2
16 15
IOUT-2 RTN
18 17
RTN VOUT-3
20 19
VOUT-3 IOUT-3
Not Used
IOUT-3
Place additional loop devices (such as strip chart recorders) at the A location noted above. All terminals marked RTN are connected internally.
154
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
155
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
156
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
157
1756-OF6CI
ControlLogix current loop output analog module
1756-OF6CI 0...550
2 1
1756-OF6CI 551...1000
2 1
OUT-1
4 3
OUT-0
OUT-1
OUT-0
4 3
i
User Analog Output Device
i
User Analog Output Device
ALT-1
6 5
ALT-0 RTN-0
8 7
ALT-1
6 5
ALT-0 RTN-0
8 7
RTN-1 OUT-3
10 9
RTN-1 OUT-3
10 9
OUT-2
OUT-2
ALT-3
12 11
ALT-2 RTN-2
14 13
ALT-3
12 11
ALT-2 RTN-2
14 13
RTN-3
Shield Ground
Not Used
Not Used
16 15
OUT-5
18 17
OUT-4 ALT-4
20 19
OUT-5
18 17
OUT-4 ALT-4
20 19
ALT-5 RTN-5
ALT-5 RTN-5
RTN-4
RTN-4
158
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
159
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
160
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-OF6VI
ControlLogix voltage loop output analog module
1756-OF6VI
2 1
+
OUT-0 Not Used User Analog Output Device
OUT-1
4 3 5
Not Used
6
RTN-1
8 7
RTN-0 OUT-2
10 9
OK
RTN-5
161
Module keying Removable terminal block RTB keying Slot width Wire category
162
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF Immunity IEC 61000-4-6
163
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
164
1756-OF8
ControlLogix voltage/current output analog module
1756-OF8 Current
2 1
1756-OF8 Voltage
2 1
VOUT-4
4 3
VOUT-0 IOUT-0
6 5
i
A
VOUT-4
4 3
VOUT-0 IOUT-0
6 5
IOUT-4 RTN
8 7
RTN VOUT-1
10 9
RTN
8 7
VOUT-5 IOUT-5
12 11
VOUT-5
10 9
IOUT-5 VOUT-6
14 13
VOUT-6 IOUT-6
16 15
VOUT-2 IOUT-2
16 15
IOUT-2 RTN
18 17
IOUT-6 RTN
18 17
RTN VOUT-7
20 19
RTN VOUT-3
20 19
VOUT-3
VOUT-7
IOUT-3
IOUT-7
IOUT-7
IOUT-3
Place additional loop devices (such as strip chart recorders) at the A location noted above. All terminals marked RTN are connected internally.
165
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
166
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
167
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-OF8H
ControlLogix voltage/current output analog module with HART protocol
1756-OF8H
168
Resolution Current draw @ 5V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Output impedance Open circuit detection time Overvoltage protection, max Drive capability Load reactance, max Settling time
Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module output scan time, min Module HART scan time
169
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
170
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
171
1756-OG16
ControlLogix TTL output module
Standard Wiring
1756-OG16
DC
+
2 1
CE Compliant Wiring
1756-OG16
DC Power Wire
2 1 3
OUT-1
4 3
OUT-0 OUT-2
6 5
5V DC Power
OUT-1
4
OUT-0 OUT-2
+5 V DC
OUT-3 OUT-5
8 7
OUT-3
6 5
OUT-4 OUT-6
10 9
OUT-5
8 7 9
OUT-4
10
OUT-7 + DC DC-0(+)
12 11
DC COM 0 OUT-8
14 13
I/O Wire
OUT-7 DC-0(+)
12 11
OUT-9 OUT-11
16 15 17 19
OUT-10
18 20
OUT-9
14 13
OUT-11
Capacitor 0.01 F Typical (See notes below.)
16 15
OUT-10 OUT-12
18 17
OUT-13 OUT-15
20 19
OUT-14 DC COM 1
DC-1(+)
Simplified Schematic
+5 DC 74AC14 OUT
IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.
DC OUTPUT
ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 O K
74AC14 OUT
DC COM
172
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) TTL outputs are inverted (0 to +0.4V dc = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
173
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
174
1756-OH8I
ControlLogix DC (90146V) isolated output module
Simplified Schematic +5V OUT-0 RTN OUT-0
+
DC-0
Isolated Wiring +
1756-OH8I
DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+)
2 4 6 8 10
1 3 5 7 9
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not used Not used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not used Not used
Continuous @ 60 C (140 F) 2A
Time
10 ms
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
175
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
176
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
177
1756-ON8
ControlLogix AC (1030V) output module
Simplified Schematic +5V L1-0
L1-0
4 3
1756-ON8
1
OUT-0 OUT-1
6 5
L1-0
Group 0
L1-0
8 7
OUT-2 OUT-3
10 9
Group 0
L1-0 L1-0
Not Used
12 11
OUT-4
14 13
20 A Current
Surge
L1-1 Group 1 L1-1
OUT-5
16 15
Group 1 OUT-6
18
17
L1-1
OUT-7
20 19
2A
L1-1
Not Used
L2
Time
43 ms
L1
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
178
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
179
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
180
C-Tick Ex
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
181
1756-OV16E
ControlLogix DC (1030V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation
2
1756-OV16E
1
DC-0(+) OUT-0
Group 0
OUT-1
4 3
OUT-0 OUT-2
6 5
OUT-3 OUT-5
8 7
OUT-4 OUT-6
10 9
Group 0
RTN OUT-0
OUT-7 DC-0(+)
12 11
OUT-9 OUT-11
OUT-10
16 15
OUT-13
18 17
OUT-12 OUT-14
20 19
Group 1
2A Current 1A 0
OUT-15 DC-1(+)
RTN OUT-1
10 ms Time
Daisy Chain to Other RTBs
DC O UTPUT
ST 0 1 2 3 4 5 6 7 FU SE FU SE E C O ALLYFU D LE TR NIC SE O K ST 8 9 1 11 3 1 5 01 21 41
182
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
183
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
184
C-Tick Ex
FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
185
1756-OV32E
ControlLogix DC (1030V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation DC-0(+) OUT-0
Group 0 Daisy Chain to Other RTBs OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11 OUT-13 OUT-15 DC-0(+) OUT-17 OUT-19 OUT-21 1756-OV32E
2 4 6 8 10 1 3 5 7 9
Daisy Chain to Other RTBs OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1 Group 1
RTN OUT-0
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Group 0
2A Current 1A 0
10 ms Time
_
DC COM
DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 6 11 3 4 22 1 2 23 9 0 7 1 5 2 3 3 1 F 0 O K F 1
ELECTRONIC FUSING
186
Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
187
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
188
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
189
1756-OW16I
ControlLogix AC (10265V) DC (5150V) isolated contact module
Simplified Schematic +24V Display ControlLogix Backplane Interface
1756-OW16I Isolated Wiring L1-0
2 4 6 8 10 1 3 5 7 9
L1-0 L1-1 L1 L1-2 L1-2 L1-3 DC-4 (+) L1-4 OUT L1-5 L1-6 L1-7 Jumper Bar L1-8 (Cut to Length) L1-9 L1-10 L1-11 Nonisolated L1-12 Wiring L1-13 Additional jumper bars are available L1-14 as cat. no. 1756-JMPR. L1-15 L1-15 L1 Not Used Daisy Chain to Other RTBs
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not Used Not Used L2
L2-0 L2-2
DC-4 (-)
RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max
190
Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
191
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
C-Tick FM KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
192
1756-OX8I
ControlLogix AC (10265V) DC (5150V) isolated contact module
1756-OX8I
OUT-0 N.C.
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 N.O.
OUT-0 N.C. OUT-0 N.O. OUT-1 N.C. OUT-1 N.O. OUT-2 N.C. OUT-2 N.O. OUT-3 N.C. OUT-3 N.O. OUT-4 N.C. OUT-4 N.O. OUT-5 N.C. OUT-5 N.O. OUT-6 N.C. OUT-6 N.O. OUT-7 N.C. OUT-7 N.O Not Used Not Used L2
L2-0
DC-2 (-)
RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O K
193
Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
194
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
C-Tick FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
195
1756-CFM
ControlLogix configurable flow meter module
1756-CFM Standard Magnetic Pickup
2 1
Z0 12-24V DC
4 3
Z1 12-24V DC Z1 5V DC
6 5
Z0 12-24V DC
4 3
Z1 12-24V DC Z1 5V DC
6 5
Z0 5V DC Z0 Return
8 7
Z0 5V DC Z0 Return
8 7
Z1 RET F1
10 9
Z1 RET F1
10 9
Input Device
+
Shield Ground
F0 F0 Return
12 11
F0 F0 Return
12 11
Customer VCC
+
Load
20
Customer VCC
This wiring diagram can be used in applications with 50 mV (magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds. You must use RSLogix 5000 software to choose the appropriate threshold level for your specific application.
196
The 1756-CFM module provides Totalizer mode for metering applications, or high-speed frequency measurements for speed or rate control applications, on two channels connected to flowmeters.
1756-CFM Standard Prover/Store Count
12-24V DC
1 3 5
Z0 12-24V DC
4
Z1 1224V DC Z1 5V DC
Z0 5V DC
6
Shield Ground
Z0 Return
8 7
Z1 RET F1
10 9
Input Device
+
Shield Ground
F0 F0 Return
12 11
METERING
F 0 Z 0 O O 0 1 F 1 Z 1 O K
Not Used
DC I/O
Output 1 Customer Common Customer Common
Output 0
18 17 19
Customer VCC
20
Customer VCC
Detectors 1 and 2 must be wired in parallel. Customer VCC may be used to power detectors. In this case, though, the maximum current on the wiring arm must be less than 4 A. The wiring example above shows a 12-24V DC standard prover connected to the module. If you use a 5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such as Z0 5V DC).
197
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Flowmeter input impedance Filtering (inputs F0 & F1) Gate input voltage range Gate input on-state current, min Gate input on-state current, nom Mechanical filter debouncing (Z0 & Z1 Inputs) Input sampling period
198
1756-CFM 2 current sourcing Customer supplied 5V operation: 4.55.5V DC for 320 mA load per point 12/24V operation: 1031.2V DC for 40 mA1 A load per point IEC 1A 24V DC 1 A @ 1031.2V DC 20 mA @ 4.55.5V DC(1) 2 A for 50 ms, repeatable every 2 s < 300 A @ 31.2V DC 0.6 x current Any number of outputs is assignable to any of 2 flowmeter channels Each output can have 2 turn-on and turn-off preset values < 50 s turn on, <300 s turn off Outputs triggered by Total; all other turn-on and turn-off times <1ms Electronic (< 4A) Electronic (No indication of fault. Remove overload and toggle output on/off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.)
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1k Hz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz
199
C-Tick KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
200
1756-HSC
ControlLogix high-speed counter module
1756-HSC to Allen-Bradley 845 Incremental Encoder
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12..24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10
1 3 5 7 9
Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10
1 3 5 7 9
Z1 (12...24V)
Whit
Z1 (5V) Blue Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) Black A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+) 12...24V
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Jumper
The 1756-HSC module provides four high-speed, output-switching, on-off windows. The module uses pulses for counting and frequency.
1756-HSC to Allen-Bradley 8723-wire DC Proximity Sensor
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) Black A0 (12...24V) A0 (5V) Blue A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10
1 3 5 7 9
Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12...24V DC
COUNTER
A B Z 0 0 0 O O 0 1 A B Z 1 1 1 O K O O 2 3
12...24V DC Return
DC I/O
201
Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Count range Counting frequency, max Input current, min Input current, nom
202
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
203
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
204
1756-LSC8XIB8I
ControlLogix 24V low-speed counter module
Simplified Schematic Current Limiter IN-x or CTR-x GND-x or CTR GND-x Opto-isolator Display ControlLogix Backplane Interface
Isolated Wiring
GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 CTR-GND-0 CTR GND-1 CTR GND-2 CTR GND- 3
1756-LSC8XIB8I
2 4 6 8
10 1 3 5 7 9
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 CTR-0 CTR-1 CTR-2 CTR-3 CTR-4 CTR-5 CTR-6 CTR-7 Not Used Not Used DC (+) DC-1 (+) DC-2 (+)
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
(+) (+)
Nonisolated Wiring
DC (-)
O K
PEER DEVICE
205
The following diagram shows how to wire a proximity sensor to the modules eight counters or eight hardware inputs. Counters use incoming pulses for counts and frequency with two user-configurable On/Off windows per counter. Hardware inputs provide standard input or counter control functionality.
1224V DC
Brown
1224V DC Return
Blue
GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 CTR-GND-0 CTR GND-1 CTR GND-2 CTR GND- 3 CTR GND-4
2 4 6 8
10
1 3 5 7 9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
1224V DC
Brown
Counters 07
1224V DC Return
Blue
Black
CTR GND- 5 CTR GND-6 CTR GND- 7 CTR GND-7 Not Used
206
Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
207
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
C-Tick Ex
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
208
1756-PLS
ControlLogix programmable limit switch module
1756-PLS Inputs - Left Side
2 1
OUTPUT 0
4 3
INPUT 0 INPUT 1
6 5
OUTPUT 8
4 3
INPUT 8 INPUT 9
6 5
OUTPUT 1 OUTPUT 2
8 7
OUTPUT 9
INPUT 2 INPUT 3
10 9
+ _
10...30V DC
OUTPUT 10
8 7
INPUT 10 INPUT 11
10 9
OUTPUT 4 OUTPUT 5
16 15
OUTPUT 12 OUTPUT 13
INPUT 5 INPUT 6
18 17
INPUT 13
16 15
OUTPUT 6 OUTPUT 7
20 19
+ _
OUTPUT 14
18 17
INPUT 14 INPUT 15
20 19
DC PWR 4...7
DC COM 12...15
+ _
The 1756-PLS module supports enhanced packaging applications. The module requires three contiguous slots in the chassis.
1756-PLS Resolver
Do Not Use
4 3
Do Not Use
F (S3)
Sine +
Do Not Use
16 15
Sine
18 17
Cosine + Cosine
A (R1) B (R2)
Reference
209
OUT 0 1 2 3 4 5 6 7
O IN 0 1 2 3 4 5 6 7 K
O K
OUT 8 9 10 11 12 13 14 15
O IN 8 9 10 11 12 13 14 15 K
DC I/O
RESOLVER
DC I/O
Current draw at 5.1V Current draw at 24V Total backplane power Power dissipation, nom Power dissipation, max Thermal dissipation, nom Thermal dissipation, max Isolation voltage
Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
210
On to Off Power dissipation, inputs, nom Power dissipation, inputs, max Thermal dissipation, inputs, nom Thermal dissipation, inputs, max On-state voltage, min On-state voltage, nom On-state voltage, max Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Reverse polarity protection
211
1756-PLS 16 (2 groups of 4 per I/O section) 12/24V DC 1031.2V DC < 15 s @ 60 C (140 F) < 25 s @ 60 C (140 F) 5.4 W @ 30 C (86 F) 3.2 W @ 60 C (140 F) 6 W @ 30 C (86 F) 3.8 W @ 60 C (140 F) 18.43 BTU/hr @ 30 C (86 F) 10.93 BTU/hr @ 60 C (140 F) 21.48 BTU/hr @ 30 C (86 F) 11.93 BTU/hr @ 60 C (140 F) 3.2 W @ 60 C (140 F) 10.93 BTU/hr @ 60 C (140 F) <10 A @ 60 C (140 F) 300 mA @ 60 C (140 F) 10V DC 10.826.4V DC 31.2V DC 0.55V DC 1 A @ 30 C(1) (86 F) 4 A @ 30 C(2) (86 F) 8 A @ 30 C(3) (86 F) <4A 2 A for 10 ms every 1 s @ 60 C (140 F) 40 mA Switching 1 A @ 24V DC Electronic (No indication of fault. Remove load and toggle on/off to restore.) Yes, current limited. (If wired incorrectly, outputs may be permanently disabled.)
212
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on unshielded I/O and power ports 2 kV at 5 kHz on shielded resolver ports 1 kV line-line (DM) and 2 kV line-earth (CM) on unshielded I/O and power ports 2 kV line-earth (CM) on shielded resolver ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
213
C-Tick Ex
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
For more information on chassis, see ControlLogix Chassis Specifications Technical Data, publication 1756-TD006. For more information on power supplies, see ControlLogix Power Supply Specifications Technical Data, publication 1756-TD005.
214
Screwdriver width
N/A
N/A
N/A
(1) Maximum wire size requires extended housing, catalog number 1756-TBE.
215
Wiring Systems
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system of the following: Interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables that match the I/O module to the IFM. Analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the pre-wired cables that match the I/O module to the AIFM. I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The other end has individually color-coded conductors that connect to a standard terminal block.
RTB Pre-wired Cable Connector I/O Module Factory-wired Field Wiring Interface Module (IFM)
216
Notes:
217
Documentation Feedback