Beruflich Dokumente
Kultur Dokumente
Protection System
Why it is required? What are the functions? What are the functional characteristics?
Fault Statistics
Over Head Lines Cables Switch gear Transformer CTs & PTs Control Equipment Miscellaneous 50% 10% 15% 12% 2% 3% 8%
FUNCTIONAL CHARACTERISTICS
1. SENSITIVITY 2. SELECTIVITY 3. SPEED 4. RELIABILITY 5. ECONOMY
Primary Relaying
Generator Protection Circuit Breaker Low voltage SG Protection Power Trans. Protection High voltage SG Protection
Transmission
line Prot.
Different types of faults on Tr. Lines L-G faults L-L Faults L-L-G Faults L-L-L Faults 85% 8% 5% 2 or less
Protection Scheme
In 400kV system, protection system will have two protections Main-I & II, both will works in parallel and send trip command to both trip coil I & II of breaker. As per CEA regulations at 400kV level all components should have redundant system DC supply, LT supply, Protection, etc..
If = E/(ZS+ZL) The reach of over current relay is function of Source Impedance which varies considerably, making it difficult to get fast and Selective tripping .
A B A+B No Trip
B A A+B No Trip
A B A+B Trip
B A A+B Trip
0,8s
0,4s
0,8s
0,4s
0,8s
0,4s
0,8s
0,4s
non-selective trip
selectivity
Impedance
Suitable for medium lines Non directional Effected by fault resistance
Mho
Directional Least effected by power swings Effected by fault resistance
Z3 Z2 Z1
Load Area
Lenticular characteristics
The characteristic of lenticular mho will be useful to provide maximum load transfer condition with maximum fault resistance coverage.
Load
Z-3
Quadrilateral characteristic
It is a basically a reactance relay superseded with controlled resistive reach. Quadrilateral characteristic suitable for E/F protection of short/medium lines with strong source of power
Z-3 Z-2 Z-1
Z-1&2
Z-3
Z2
Z3
ZONE -4 : To cover close up back-up non-directional faults generally reverse reach will be provided in relays (10%).
over reach
Relay measured impedance less than the actual fault Impedance. i.e effective reach of the relay increases
Under reach
Relay measured impedance is more than actual impedance. i.e. Effective reach of the relay decreases
S (Is + Ir)
Rf
Consider power flow from S > R Case 1 Is leads V arc Relay at S sees Varc/Is = Rf- jXrf Which indicates capacitive Arc resistance
Ir
Case 2
Ir lags Varc Relay at R sees Varc/ Ir = Rf+jXrf which indicates inductive arc res.
Rf Import end R
Thus the distance relay overreaches for arcing faults where the current Leads the arc voltage and underreaches where the current lags the arc voltage.
I1
B X X I2 X
ACTUAL IMPEDANCE WITH OUT TEED SOURCE IS Za+ Zb WITH TEED SOURCE Z = Za+ Zb + (I2/I1)/Zb ACTUAL IMPEDANCE FURTHER DEPENDS ON RELATIVE PHASE ANGLE OF TEED SOURCE .
X D/y
X X
X X
Y/d
PHASE RELAYS ARE NOT AFFECTED GROUND RELAYS WILL EXPERIENCE AN ERROR OF ABOUT 5.5 % AT 85 % OF LINE LENGTH (Zmo = 0.5 * Zo)
For the fault on the parallel line, fault current also fed from healthy line and this current pass through ground. This current changes the mutual inductance and in turn causes relay measuring impedance to increase and is more than actual fault impedance. This effect will be compensated by connecting neutral current of the line to parallel line. This compensation will not work, if the parallel line neutral current is more than line neutral current.
ZONE - I CHARACTERISTICS
Should isolate the faulted section instantaneously Should cover protected circuit & fault resistance with some margin to take care of errors in measurement Selective phase tripping for 1ph to ground faults for auto reclose of the breaker. Fast operation with secured directional discrimination. Should be stable in the presence of: 1. Fault resistance, arc resistance 2. Errors in CT, CVT and CT saturation 3. Transients in CT & CVT
ZONE-II CHARACTERISTICS
Delayed tripping and non selective phase tripping. Provide back up protection for part of adjacent line.
Trip the faulty line instantaneously using carrier aided tripping. Time delay is normally 500ms
ZONE-III CHARACTERISTICS
This provides back up protection for the adjacent lines or transformer Time delay is normally 1500ms
ZONE IV CHARACTERISTICS
This provides back up protection for the station faults It is normally in the reverse direction Time delay is normally 1500ms
Distance Schemes:
1 . P . U . R -- Permissive under reach scheme 2. P . O . R -- Permissive Over Reach scheme 3. BLOCKING SCHEME 4. WEAK END FEED
CARRIER SCHEMES - P U R
Z2A Z1A A Z2B CARRIER RELAY CHANNEL Trip = Z1 + Z2.CR+Z3.T3+Z2.T2 CS = Z1 Under reaching zone sends carrier signal RELAY Z1B B Fault
CARRIER SCHEMES - P O R
Z2A Z1A A Z2B RELAY CARRIER Z1B B RELAY Fault
BLOCKING SCHEME
Z3A Z1A Z1B A RELAY Z2B CARRIER B RELAY Z2A Fault
Z3B
Trip = Z1+Z2.t. No signal+Z3.T3 CS = Z3 Reverse reach zone-3 sends signal for blocking protection.
BLOCKING SCHEME
Z3A Z1A Z1B A RELAY Z2B CARRIER B RELAY Z2A Fault
Z3B
Z3 at B sends blocking signal to block relay at A Breakers at A & B will not trip
Fault
B
RELAY
RELAY
CARRIER
CR.Z3(not optd).UV
AUTORECLOSE PHILOSOPHY
NEED FOR AUTO RECLOSE 1. 2. 3. 4. Reducing outage time Improved reliability Restoration of network stability and synchronism Reduction of operating cost because of above factors
AUTORECLOSE PHILOSOPHY
TRANSIENT FAULTS -CHARACTERISTIC Characterized by disappearance after Short dead time or disappears without any Action being taken. TYPES OF TRANSIENT FAULTS 1. 2. 3. 4. Lightning strokes resulting in flashovers Conductor swinging due to high winds Bird fault Temporary contact with foreign objects like tree etc.
AUTORECLOSE PHILOSOPHY FAULT STATISTICS VOLTAGE LEVEL 400 KV 400 KV 400 KV 220 KV 220 KV 220 KV FAULT SINGLE PH TWO PH THREE PH SINGLE PH TWO PH THREE PH STATISTICS 85% 13 % 2% 56 % 27 % 17 %
RECLOSURE STATISTICS SUCCESSFUL RECLOSURES DEFINITIVE TRIPPINGS EQUIPMENT DEFECTS 75.2 % 13.5 % 11.3 %
FACTORS AFFECTING DE IONISING TIME Arcing time Wind conditions Air humming pressures Capacitance coupling to adj. Conductors Circuit voltage DE IONISING TIME KV MIN DE ENERGISATION TIME SEC 66 110 132 0.1 0.15 0.15 220 275 400 0.28 0.3 0.5
CHOICE OF RECLAIM TIME The reclaim time must not be set to such a low value that the intended operating cycle of the breaker is exceeded when Two fault incidents occur close together.
For example the reclaim time for a air blast circuit breakers must allow time for air pressure to recover to its normal value. CHOICE OF DEAD TIME Dead time for EHV system lower limit is decided by de ionising time, upper limit is decided by transient stability.
Power Swing
Power Swing
Power Swings are disturbances in system due to various reasons such as sudden load throw, bad synchronization, auto reclose etc Power swings are characterized by slow power flow oscillations, resulting in swinging of voltages and current flows, resulting in operating point movement into distance relay characteristics, in turn may cause tripping of distance relays. Tripping during power swings may be undesirable since no actual fault is present and moreover a line outage during power swing may cause further deterioration to system stability. Detection of power swing will block the distance protection. Zones 2,3,4. Normally tripping is in Zone-I even after detection of power swing.
Power Swing
X Z3 Z2 Z1 R
Power swing detection zones
Time taken by fault locus to cross the power swing detection zones is more than 40-50ms, then it is called power swing.
Fuse Failure
During the fuse failure, no voltage will be available for distance relay for impedance measurement, hence relay may issue trip. It can be avoided by blocking the distance protection on detection of fuse failure. In modern numerical distance relays, fuse failure is built in feature.
Switch on to fault
This feature provide protection against energisation of the tr. line with fault or dead short. Distance protection will not provide protection in this as voltage is not available for distance measurement. It can be activated by TNC switch or CB aux. binary input or internal detection of current rise. It provides instantaneous 3Ph trip.
Stub Protection
Bus-2 Bus-1
21
Ckt-1
Ckt-2
DEF Protection
It provides back up protection for tr. line. It provides reliable protection for high resistance earth faults. It uses cross polarized voltage for directional discrimination.
Operation of over voltage protection. Operation of bus bar with tie breaker open. Manual tripping of both the breakers (main&Tie) Operation of LBB
On receipt of command through PLCC at other end breakers will trip directly.
Stage II
Setting: 140% Time delay: Instantaneous.