Software-Specification
S08P IRAN PROJECT
S08P701.000-00ABE / 9609036
Revision Index
Revision Index
Version 1.0 11.08.2004 Reasons for the update First edition Pages all Prepared by: F.Perez / M.Rentsch / J.Quinque J.Quinque
1.1
xx.xx.2004
2-10, 15
Distribution:
Astra
HFG
Pages
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
Table of Contents
6 TEST MODES.....................................................................................15
6.1 Automatic test modes......................................................................................15 6.2 Manual test modes...........................................................................................15
7 ABBREVIATION INDEX.....................................................................17
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
Introduction
The air conditioning system is destined to be mounted on the passenger coaches type Couchette manufactured by Astra Vagoane Calatori for the Iranian Railways. Coaches are Z2 type in accordance with UIC 567-2, able to run with a max. speed of 160 km/hour. Climatic conditions: -25C / 80C (sun) or 55C (shadow); humidity from 13% up to 99%; atmosphere with dust, sand and salt. The comfort conditions in passenger area are in accordance with UIC 553. All passenger coaches are equipped with a fully automatic air conditioning system under frame mounted. Conditioned air is blown into the coach through air outlets arranged along the sidewall (ejecto-convector) and underneath the seats. Basically the functional remains the same as for the project S59L passenger coaches for Romania.
Other documents related to this project: Contract 2538 - S08P Technical Information S08P Technical Conditions Air Conditioning Installation April 2004
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
3
3.1
3B21 3B22 3B24 3B23
Device
3.2
3F52 3F53 3F27 3F28 3F60 3F51 3F50 3F40 3F30 3K24 3F44 3F54 3F4 3F3 3S1 3S1 3F54
Digital inputs
Adr. DI_01 DI_02 DI_03 DI_04 DI_05 P2 A2 B2 A3 B3 A4 Signal DI_MBP1_PD DI_MBP2_PR DI_EH_SC_OK DI_SF_AF_OK DI_CPR_SC_OK Signal name Pressostat MBP1 pump down Pressostat MBP2 power reduction Safety chain heater OK Air flow controller return information Safety chain compressor OK
Device
DI_06 DI_07 DI_08 DI_09 DI_10 DI_11 DI_12 Adr. DI_13 DI_14 DI_15 DI_16 DI_17 DI_18
B4 A5 B5 A6 B6 A7 B7 P3 A2 B2 A3 B3 A4 B4
DI_SF_TH_OK DI_MHP1_CDR DI_TM_COOL DI_TM_HEAT DI_VENT_ON DI_HVAC_ON DI_MHP2_CDR Signal DI_CDR1_TH_OK DI_FPRA DI_400V_OK DI_SF_MSW DI_EH_ESTI_OK
Motor protection + thermostat supply fan (1L=OK) Control pressostat 1 condenser fan Button test mode cooling Button test mode heating Switch ventilation on Switch air conditioning on Control pressostat 2 condenser fan Signal name Thermo junction condenser fan 1 100% return air position 400V 3 phases OK Return information micro switch (MSW) supply fan (1L=OK) ESTI-release heater
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
3.3
3K11 3K12 3K13 3M2 3M2 3K6 3K3 3K4 3F24 3F21 3F23
Digital outputs
Adr. DO_01 DO_02 DO_03 DO_04 DO_05 DO_06 DO_07 DO_08 DO_09 DO_10 DO_11 DO_12 Adr. DO_13 DO_14 DO_15 DO_16 DO_17 DO_18 DO_19 DO_20 DO_21 DO_22 DO_23 DO_24 P4 A1 B1 A2 B2 A4 B4 A5 B5 A7 B7 A8 B8 P5 A1 A2 A3 B3 A4 B4 A6 B6 A7 B7 A8 B8 Signal DO_EH1 DO_EH2 DO_CDR1 DO_CDR2 DO_CDR3 DO_CPR DO_MV1 DO_MV2 DO_CPR_4C DO_CPR_6C Signal name Main heater step 1 Main heater step 2 Condenser fan 1 Condenser fan 2 Condenser fan 3 Compressor on Solenoid valve evaporator 1 Solenoid valve evaporator 2 Compressor 4 cylinders Compressor 6 Cylinders Signal DO_SF_SL DO_SF_MI DO_SF_HI DO_FDRA DO_FDOA DO_PRECOND DO_EH_V1 DO_EH_V2 DO_CPR_OFF DO_SF_OFF DO_EH_OFF Signal name Ventilation low rotation speed Ventilation medium rotation speed Ventilation high rotation speed Flap control direction 100% return air Flap control direction 100% outside air Pre-cooling / pre-heating active Heater entrance 1 + toilet 1 Heater entrance 2 + toilet 2 Message to MSW compressor off because of error Message to MSW supply fan off because of error Message to MSW heater off because of error
Device
Device 3K1 3K2 3K31 3K32 3K33 3K30 3Y1 3Y2 3Y3 3Y4
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
For the Regulation of the HVAC-system there is a FPC24 controller installed, which controls and regulates the air conditioning unit through outside, supply air and room temperature under consideration of the set point given as well as the safety chains for the devices. The regulation takes place automatically to the given set point, depending on the chosen operating mode.
4.1
Operating modes
position 0 : position : position 1 : everything is off ventilation and exhaust cooling or heating mode automatically selected by the controller
These are reached by switching the supply voltage of the fan. The following outputs of the FPC24 are being used in Ventilation mode: DQ_01 DQ_02 DQ_03 DQ_15 Ventilation low speed Ventilation medium speed Ventilation high speed Exhaust air fan
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
4.2
The set point for the platform and toilets is fixed at 22C. For the compartments the set point is defined as the lowest value given by the compartment modules plus ( 0,25 * ( Te - 19C ) ), if the outside temperature is higher than 19C.
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
5
5.1
The fan will be controlled if 400V are present System is set to Ventilation mode OR to Air conditioning mode Control of outputs Operation Mode Preheating Precooling Heating Cooling External Temp. -25<Te<-15 10<Te<26 Te>26 -25<Te<-5 -5Te<19 10Te<26 26Te<50 50Te<52 Te52 26Te<50 50Te<52 Te52 High Ventilation Speed Slow Middle High Slow Middle High Flap Position (0) 0m3/h closed (4) 615m3/h t#54s (3) 820m3/h t#44s (2) 615m3/h t#25s (1) 410m3/h t#2s (0) 205m3/h closed (3) 615m3/h (2) 410m3/h (1) 205m3/h Exhaust Fan Stopped DI_400V_OK = 1L DI_VENT_ON = 1L OR DI_HVAC_ON = 1L
in Operation
Expected return information Air flow controller reports air flow Motor protection + thermostat supply fan OK Micro switch supply fan not activated The fan will be locked if Motor protection or thermostat triggered Air flow controller reports no air flow while fan is running DI_SF_TH_OK = 0L DI_SF_AF_OK = 0L AND (DO_SF_SL = 1L (DQ_01) OR DO_SF_MI = 1L (DQ_02) OR DO_SF_HI = 1L (DQ_03)) DI_SF_AF_OK = 1L AND (DO_SF_SL = 0L (DQ_01) AND DO_SF_MI = 0L (DQ_02) AND DO_SF_HI = 0L (DQ_03)) DI_SF_EMRG = 1L DI_SF_MSW = 1L DI_SF_AF_OK = 1L DI_SF_TH_OK = 1L DI_SF_MSW = 0L
Air flow controller reports air flow while fan is turned off
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
Error! Style not defined. Error! Style not defined. 5.2 Entrance heaters
The heaters will be controlled if 400V are present System is set to Air conditioning mode Air flow controller reported air flow for 60sec Control of outputs Heater entrance 1 + toilet 1 on (3min cycle length) DO_EH_V1 = 1L (DQ_07) Heater entrance 2 + toilet 2 on (3min cycle length) DO_EH_V2 = 1L (DQ_08) DI_400V_OK = 1L DI_HVAC_ON = 1L DI_SF_AF_OK = 1L (for 60sec)
5.3
Main heater
The heater will be controlled if 400V are present System is set to Air conditioning mode Air flow controller reported air flow for 60sec Control of outputs Main heater step 1 on Main heater step 2 on Expected return information Safety chain heater OK ESTI for heater OK Micro switch heater not activated The heater will be locked if Safety chain heater not OK ESTI for heater not OK Micro switch heater activated DI_EH_SC_OK = 0L DI_EH_ESTI_OK = 0L DI_EH_MSW = 1L DI_EH_SC_OK = 1L DI_EH_ESTI_OK = 1L DI_EH_MSW = 0L DO_EH1 = 1L (DQ_13) DO_EH2 = 1L (DQ_14) DI_400V_OK = 1L DI_HVAC_ON = 1L DI_SF_AF_OK = 1L (for 60sec)
An error code/message will be created if Duct temperature does not increase by 3K in 3min AI_Td < 3K (in 3min)
5.4
Compressor
The compressor will be controlled if 400V are present System is set to Air conditioning mode Air flow controller reported air flow for 60sec Control of outputs S08P IRAN PROJECT
S08P701.000-00ABE / 9609036 Issue: Version: Author
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
Compressor on with 4 cylinders Compressor on with 6 cylinders If outside temperature is higher than 40C, 2min forerun before compressor start Condenser fan 1 on OR Condenser fan 2 on OR Condenser fan 3 on If power reduction is activated OR outside temperature is higher than 52C OR one condenser fan defective Compressor runs with 4 cylinder max. If two or more condenser fans are defective Compressor runs with 2 cylinders max. If compressor runs with 2 cylinders Open solenoid valve 1 (50% cooling capacity) OR Open solenoid valve 2 (50% cooling capacity) If compressor runs with 4 or more cylinders Open solenoid valve 1 (50% cooling capacity) AND Open solenoid valve 2 (50% cooling capacity) Pump down mode Close solenoid valve 1 (50% cooling capacity) AND Close solenoid valve 2 (50% cooling capacity) Pressostat power reduction activated Switch from 6 to 4 cylinders (if compressor is running with 6 cylinders) Pressostat pump down activated OR max 2min after pump down mode start Turn off compressor Expected return information Safety chain compressor OK Micro switch compressor not activated The compressor will be locked if Safety chain compressor not OK Micro switch compressor activated An error code/message will be created if Duct temperature does not decrease by 3K in 3min
DO_MV1 = 1L (DQ_19) OR DO_MV2 = 1L (DQ_20) DO_MV1 = 1L (DQ_19) AND DO_MV2 = 1L (DQ_20) DO_MV1 = 0L (DQ_19) AND DO_MV2 = 0L (DQ_20) DI_MBP2_PR = 1L
DI_CPR_SC_OK = 1L DI_CPR_MSW = 0L
DI_CPR_SC_OK = 0L DI_CPW_MSW = 1L
5.5
Condenser fans
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
5.6
Flap
The flap will be controlled if System is set to Ventilation mode OR to Air conditioning mode Control of outputs Operation Mode Preheating Precooling Heating Cooling External Temp. -25<Te<-15 10<Te<26 Te>26 -25<Te<-5 -5Te<19 10Te<26 26Te<50 50Te<52 Te52 Ventilation Speed Slow Middle High Slow Middle High Flap Position (0) 0m3/h closed (4) 615m3/h t#54s (3) 820m3/h t#44s (2) 615m3/h t#25s (1) 410m3/h t#2s (0) 205m3/h closed Exhaust Fan Stopped DI_VENT_ON = 1L DI_HVAC_ON = 1L
in Operation
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
5.7
Error Memory
Function Fault sensor AI_02 Temperature V1 Fault sensor AI_03 Temperature V2 Reason Comment (emergency routine) Temperature V2 as reference value Temperature V1 as Reference value Switch outside temperature to fixed value 18C Switch from Duct- to Roomregulation and 50% heating capacity No air conditioning possible
Code Slot
Fault sensor AI_04 Outside Short or open circuit temperature Fault sensor AI_05 Duct temperature Supply fan thermal fault DI_20_SF_TH_OK Supply fan fault DI_17_SF_MSW Supply fan fault air flow DI_04_SF_AF_OK Air flow controller fault DI_04_SF_AF_OK Supply fan emergency switch DI_14_SF_EMRG free Compressor fault safety chain DI_05_CPR_SC_OK Compressor fault DI_19_CPR_MSW Function Activation safety chain compressor D_DF_CPR_SC Micro switch compressor was not activated by FPC24 D_DF_CPR_MSW_NOK Reason
Issue: Version: Author
101
005
102
006
Micro switch supply fan was not activated by FPC24 No air conditioning possible D_DF_SF_MSW_NOK No return information supply fan air flow controller D_DF_SF_AF_NOK Return information air flow controller w/o supply fan D_DF_AF_NOK Activation emergency switch ventilation D_DF_SF_EMRG No air conditioning possible No air conditioning possible No air conditioning possible
105
007
107
008
109
009
010
200
011
202
012
Code Slot
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
261
014
271
015
281
016
300
017
303
018
306
019
308
020
180
021
181
022
Fault final pos. outside-/return Final pos. remains active air flap despite flap movement DI_15_FPRA D_DF_FP_POS CAN bus failure or PTM No data connection to PTM 1 defective > t#5min DF_COM_PTM1 No data connection to PTM 2 > t#5min DF_COM_PTM2 No data connection to PTM 3 > t#5min DF_COM_PTM3 No data connection to PTM 4 > t#5min DF_COM_PTM4 Function Reason
Issue: Version: Author
Transmission of a message Compartment is being ignored in the power demand calculation Compartment is being ignored in the power demand calculation Compartment is being ignored in the power demand calculation Compartment is being ignored in the power demand calculation Comment (emergency
821
023
822
024
CAN bus failure or PTM defective CAN bus failure or PTM defective CAN bus failure or PTM defective
823
025
824
026
Code Slot
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
826
028
827
029
828
030
829
031
830
032
831
033
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
861
045
Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM1 not active calculation > t#3min NO_SEN_PTM1 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM2 not active calculation > t#3min NO_SEN_PTM2 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM3 not active calculation > t#3min NO_SEN_PTM3 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM4 not active calculation > t#3min NO_SEN_PTM4 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM5 not active calculation > t#3min NO_SEN_PTM5 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM6 not active calculation > t#3min NO_SEN_PTM6 Sensor set to not active by Compartment is being ignored service staff at PTM7 in the power demand Sensor from PTM7 not active calculation > t#3min NO_SEN_PTM7 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM8 not active calculation > t#3min NO_SEN_PTM8 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand Sensor from PTM9 not active calculation > t#3min NO_SEN_PTM9 Sensor from PTM10 not active > t#3min Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand calculation NO_SEN_PTM10 Sensor set to not active by Compartment is being ignored service staff at PTM in the power demand
Issue: Version: Author
862
046
863
047
864
048
865
049
866
050
867
051
868
052
869
053
870 871
054 055
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
6
6.1
Test modes
Automatic test modes
To start an automatic test mode, either push the button Testmode cooling or Testmode heating. The test mode will end after 10 minutes or when another test mode is being chosen.
6.2
TM_CPR_4CYL
Supply fan medium speed on Compressor with 4 cylinders on Condenser fans on if demanded Open solenoid valve 1 and 2
TM_CPR_6CYL
Supply fan medium speed on Compressor with 6 cylinders on Condenser fans on if demanded Open solenoid valve 1 and 2
Message Cooling defective on Close solenoid valve 1, if test mode Cooling is active Close solenoid valve 2, if test mode Cooling is active Condenser fan 1 on Condenser fan 2 on Condenser fan 3 on Supply fan medium speed on Heater step 1 on Supply fan medium speed on Heater step 2 on Message Heating defective on
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
Test mode TM_EH_V1 TM_EH_V2 TM_FDOA TM_FDOA_TIME TM_FDRA TM_FDRA_TIME TM_EH_PTM1 TM_EH_PTM2 TM_EH_PTM3 TM_EH_PTM4 TM_EH_PTM5 TM_EH_PTM6 TM_EH_PTM7 TM_EH_PTM8 TM_EH_PTM9 TM_EH_PTM10 TM_EH_PTM11
Reaction Supply fan medium speed on Heater entrance 1 on Supply fan medium speed on Heater entrance 2 on Flap moves to position outside air Flap moves in direction outside air corresponding to entered time Flap moves to position return air Flap moves in direction return air corresponding to entered time Electrical heater department 1 Electrical heater department 2 Electrical heater department 3 Electrical heater department 4 Electrical heater department 5 Electrical heater department 6 Electrical heater department 7 Electrical heater department 8 Electrical heater department 9 Electrical heater department 10 Electrical heater department 11
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
Abbreviation index
Meaning Internal analogue variable Internal analogue constant Analogue input variable Analogue output variable Internal digital variable Internal digital constant Default variable Digital input variable Digital output variable Internal message variable Internal timer variable Analogue input variable Meaning Condenser temperature Duct air temperature Average duct air temperature Outside air temperature Average outside air temperature Evaporator temperature Heater surface temperature Room air temperature Setpoint room temperature Average room air temperature Switch box inside air temperature Meaning Signal state inactive Signal state active Air heater Auxilary power Auxilary power missing Condition mode Battery
Issue: Version: Author
Abbreviation A_ AC_ AI_ AQ_ D_ DC_ DF_ DI_ DQ_ M_ T_ AI_4_20 Abbreviation Tc Td(x) Tdm Te(x) Tem Tev Th Ti(x) Tic Tim Tisb(x) Abbreviation 0L 1L AH AP APM BA BAT
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque
xx.xx.2004
1.1 F.Perez/M.Rentsch/ J.Quinque