Beruflich Dokumente
Kultur Dokumente
Paper Insulated Cable (Mass Impregnated, Non-Draining) Indoor Service oil barrier, insulating tubing (clear) installed over paper insulation otherwise, installation is the same as for a polymeric insulated cable
void filling compound stress control tubing non-tracking sleeve with sealant layer Its the same system for all types of polymeric cable
rain skirts installed over non-tracking sleeve otherwise, installation is the same as for an indoor termination
Raychem Heat-Shrinkable Termination System for Cables up to 36 kV Three Core Cable Termination System
three-core breakout installed at end of cable oversheath otherwise, installation steps are the same as for three single core Terminations The Raychem termination system is compatible with all types of armoured cable. The system includes a complete range of solderless accessories for earthing insulation screens and cable armour and for grounding lead sheaths. Also available are insulators and support brackets, insulating boots for equipment connections and glands for easy entry to cable boxes. For more details please refer to the EPKT (EPP-0282/2) and I(O)XSU-F (EPP-0795 & 0782) Termination brochures. You can ask for our capability brochure (EPP-1102) that exhibits all product families.
7 8
1 Screened body A thick-walled moulded conductive outer screen is permanently bonded to the silicone rubber insulating material of the body. 2 Inner screen A conductive inner layer, as a faraday cage around the compression or mechanical lug, prevents corona at rated voltage. 3 Compression or mechanical lugs Specially designed DIN and deep indent compression lugs, as well as mechanical lugs with shear bolts for connecting either aluminium or copper conductor cables. 4 Stress cone adapter Relieves electrical stress at the point where the cable screen is cut. The insulated section, extending beyond the wire shielding, provides a convenient point for oversheath testing. 5 Earthing eye and ground lead Provides a connection point for earthing the screen. 6 Threaded pin A threaded pin together with a spring washer and hex nut ensure a high-performance electrical and mechanical contact with the bushing. 7 Rear plug with test point Removable rear plug with capacitive test point. 8 Test point The test point is used to determine whether the circuit is energised; alternatively it can be used for phasing. 9 Conductive endcap Electrical screen and protection of the rear end of the separable connector
9 3 1 2
4 5
(11)
(11)
Metallic Screen
Red Sealant
Tinned Copper Braid (25sqmm) Roll Spring Cable Breakout Moisture Block
Red Sealant
Cable Gland
(11)
7 8
9 3 1 2
1 - Screened body 2 - Inner screen 3 - Mechanical lugs 4 - Stress cone adapter 5 - Earthing eye and ground lead 6 - Threaded pin 7 - Rear plug with test point 8 - Test point 9 - Conductive endcap
4 5