Sie sind auf Seite 1von 6

Raychem Heat-Shrinkable Termination System for Cables up to 36 kV Single Core Cable Termination System

Polymeric Insulated Cable Indoor Service

Paper Insulated Cable (Mass Impregnated, Non-Draining) Indoor Service oil barrier, insulating tubing (clear) installed over paper insulation otherwise, installation is the same as for a polymeric insulated cable

Polymeric or Paper Insulated Cable Outdoor Service

void filling compound stress control tubing non-tracking sleeve with sealant layer Its the same system for all types of polymeric cable

rain skirts installed over non-tracking sleeve otherwise, installation is the same as for an indoor termination

Raychem Heat-Shrinkable Termination System for Cables up to 36 kV Three Core Cable Termination System

Polymeric or Papier Insulated Cable Indoor or Outdoor Service

three-core breakout installed at end of cable oversheath otherwise, installation steps are the same as for three single core Terminations The Raychem termination system is compatible with all types of armoured cable. The system includes a complete range of solderless accessories for earthing insulation screens and cable armour and for grounding lead sheaths. Also available are insulators and support brackets, insulating boots for equipment connections and glands for easy entry to cable boxes. For more details please refer to the EPKT (EPP-0282/2) and I(O)XSU-F (EPP-0795 & 0782) Termination brochures. You can ask for our capability brochure (EPP-1102) that exhibits all product families.

RSTI - Screened, separable connection system 630 A up to 24 kV Design and construction

7 8

1 Screened body A thick-walled moulded conductive outer screen is permanently bonded to the silicone rubber insulating material of the body. 2 Inner screen A conductive inner layer, as a faraday cage around the compression or mechanical lug, prevents corona at rated voltage. 3 Compression or mechanical lugs Specially designed DIN and deep indent compression lugs, as well as mechanical lugs with shear bolts for connecting either aluminium or copper conductor cables. 4 Stress cone adapter Relieves electrical stress at the point where the cable screen is cut. The insulated section, extending beyond the wire shielding, provides a convenient point for oversheath testing. 5 Earthing eye and ground lead Provides a connection point for earthing the screen. 6 Threaded pin A threaded pin together with a spring washer and hex nut ensure a high-performance electrical and mechanical contact with the bushing. 7 Rear plug with test point Removable rear plug with capacitive test point. 8 Test point The test point is used to determine whether the circuit is energised; alternatively it can be used for phasing. 9 Conductive endcap Electrical screen and protection of the rear end of the separable connector

9 3 1 2

4 5


(11)


(11)

Non-tracking Tubing (Red)

11kV 3-core XLPE Cable Indoor Termination 11

Stress Control Tubing (Black)

Stress Relief Mastic (Yellow)

Metallic Screen

Red Sealant
Tinned Copper Braid (25sqmm) Roll Spring Cable Breakout Moisture Block

Red Sealant

Bottom Plate of Cable End Box

Cable Gland

Copper Strip to Substation Earth

Armour Clamp Tinned Copper Braid Insulation Tube (Black)

(11)

7 8

9 3 1 2

1 - Screened body 2 - Inner screen 3 - Mechanical lugs 4 - Stress cone adapter 5 - Earthing eye and ground lead 6 - Threaded pin 7 - Rear plug with test point 8 - Test point 9 - Conductive endcap

4 5