UR Series, Type-L90 Relay Test Report

Job Number: Customer: Substation: Location: Line: Relay ID:

Nameplate Data
Model #: Serial #: Ratings: Firmware Version: Instruction Booklet: CT / PT Ratio:

System Setup
Current Banks
Ratio-F1 Ibase = 5 :5 0 Ratio-F5 Amps 5 :5

Voltage Bank
Bank F5: Phase

Phase Secondary =

Auxiliary Secondary = 0

Electrical Tests Inputs / Outputs


Check all digital inputs. -AND- Check all output contacts. Check all voltage/current inputs (magnitude and polarity); use metering to view.

Confirm

Minimum PickUp
Category
Phase Current

Element
IOC1 IOC2 TOC1 TOC2 IOC1 + IOC2 + TOC1 TOC2 IOC1 IOC2 TOC1 TOC2 IOC1 IOC2 TOC1 TOC2 UV1 UV2 OV1 OV1 UV1 OV1

Setting

Bank Expected
0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0V 0V 0V 0V 0V 0V

Measured

Time Delay
C Setting Measured

Neutral Current

Ground Current

Negative Sequence

Phase Voltage Neutral Voltage Aux Voltage

Breaker Failure
Category
BF1 PH AMP BF1 N AMP BF2 PH AMP BF2 N AMP
+

BF1: Enabled BF2: Enabled

Element
SUPV HISET LOSET SUPV HISET LOSET SUPV HISET LOSET SUPV HISET LOSET

Setting

Bank Expected
0 0 0 0 0 0 0 0 0 0 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A

Current

Element
Timer 1 Timer 2 Timer 3 Lowset Dropout Timer 1 Timer 2 Timer 3 Lowset Dropout

Time Delay Setting Measured

Note: Neutral IOC is adjusted by 6.25% for I1 restraint. If Power Swing settings enabled, Attach PTS' Out-Of-Step Relay datasheet: 1323 Butterfield Road; Suite 106 Downers Grove, IL 60515 GE-UR-L90, Line Diff.xls Page 1 of 3

Power Technical Services, Inc.

UR Series, Type-L90 Relay Test Report (cont)


Substation: 0 Line: 0 Relay ID: 0

Electrical Tests (Cont) Time-OverCurrent


Element
Phase TOC1

Curve & Time Dial


Curve =

Test Current
2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 0.75 0.50 0.00 0.75 0.50 0.00 0.75 0.50 0.00 x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x= x=

Expected Time

Measured Time C

TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

Phase TOC2
( ___ pu = ____ A)

TDM = Reset = Instantaneous


Curve =

Neutral TOC1 TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

Neutral TOC2 TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

Ground TOC1 TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

Ground TOC2 TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

NegSeq TOC1 TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

NegSeq TOC2 TDM = ( ___ pu = ____ A) Reset = Instantaneous


Curve =

Phase UV1
( ___ pu = ____ A)

TDM = Reset = Instantaneous


Curve =

Phase UV2
( ___ pu = ____ A)

TDM = Reset = Instantaneous


Curve =

Aux UV1
( ___ pu = ____ A)

TDM = Reset = Instantaneous

Zone2 Reach and Timer


Ground
reach RCA Comp Limit Z0/Z1 mag Z0/Z1 ang Direction

K0 x: -1

K0 y:

k0 {mag} =

1 k0 {ang}=

Parameter
Voltage Current @ MTA Impedance Max Torque Angle Circle + Check Delay

Expected Values
V-n A A A Sec

V -n A A A Sec V - A A A Sec

V -n A A A

V -n A A A

Phase
reach RCA Comp Limit Direction

Parameter
Voltage Current @ MTA Impedance** Max Torque Angle Circle + Check Delay **Note: Z = V-/2I

Expected Values
V- A A A Sec

A - B

B - C

V - A A A

C - A

V - A A A

Power Technical Services, Inc.

1323 Butterfield Road; Suite 106 Downers Grove, IL 60515

GE-UR-L90, Line Diff.xls Page 2 of 3

UR Series, Type-L90 Relay Test Report (cont)


Substation: 0 Line: 0 Relay ID: 0

Electrical Tests (Cont) 87L Tests: Adaptive Elliptical Restraint


Minium Pickup (Local Test, only)
(Local test only: Use "Local Loopback" or a fiber-jumper.)

[Current Bank F1 used for tests.]

Formula
PICKUP = 0.20 pu
I = SQRT[2 PU2(1-2 R12)]
(where: PU = PICKUP & R1 = Restraint 1)

Expected
0A

Measured PickUp C

Using Local Loopback

Restraint Test

(Requires communication with, and current synchronized to, the Remote Relay)
(Note: When one relay operates, it sends a DTT across the Fiber Channel, causing simultaneous operation at other relay.)

Restraint 1 = 20% Elliptical Curve Action

Break PT=

5.0

pu

Restraint 2 = 40%

CT Tap 1 =

1.00

Parameter / Formula

Expected Values
0.98 A 0.49 A 0.295 pu 0.290 pu 1.018 32.50 A 17.76 A 2.948 pu 2.934 pu 1.005

Measured Values

Restraint 1 Region

Local Current, [ ILoc ] @ 0 Measure Remote Current, [ IRem ] @ 0

Calculate

Normalized Op Current, Iop [pu] Normalized Restraint**, Irest [pu]

Restraint 2 Region

OPERATE: Iop / Irest [ > 1.00 ] Local Current, [ ILoc ] @ 0 Measure Remote Current, [ IRem ] @ 180

Calculate

Normalized Op Current, Iop [pu] Normalized Restraint**, Irest [pu]

OPERATE: Iop / Irest [ > 1.00 ]

** Formula for Restraint is too complex to list here; refer to Section 8.2 of Manual # 1601-0081 for details.

Synchro-Check
Category
V1 V2 Max Volt Max Angle Max Freq
(Dead) (Live)

SynchCheck 1: Specified
D E A D L I V E

FALSE

Low

High

SynchCheck 2: Specified
D E A D L I V E

FALSE

Low

High

Volts Angle Freq

V (sec) deg Hz AR1: Enabled

Volts Angle Freq

V (sec) deg Hz

AutoReclose Timers
Element
Dead Time 1 Dead Time 2 Dead Time 3 Dead Time 4

Setting

Measured

Element
Add Delay 1 Add Delay 2 Mn Close Delay

Setting

Measured

Element
Reset Lockout Reset Time Incomplete Seq

Setting

Measured

Output & Logic Checks


Output Control Flex Logic

Logic Output Elements Functional Tested Tested**

**Note: Functional Testing may be performed only if operating conditions permit.

Comments
Test Equipment & Calibration Date: Other Comments:

Relay Tested By: Functional Tests By:

Date: Date: 1323 Butterfield Road; Suite 106 Downers Grove, IL 60515

Attach print-out of relay settings:

Power Technical Services, Inc.

GE-UR-L90, Line Diff.xls Page 3 of 3