HRC DIN Fuses

Type

Standard DIN and Striker Fuses


SM...-GL/... SM...-GL/...K Cable and Line protection Full Range gL/gG 500 VAC

Semiconductor Fuses
SM...-UF/... Semiconductor protection Short Circuit only aR 660 VAC

Motor Rated Fuses


SM...-AM/... Motor protection Short Circuit only aM 500 VAC

CT Mount Fuses
SMCT...-GL/... Cable and Line protection Full Range gL/gG 400 VAC

D-Type Fuses

Cylindrical House Service Fuses


SKR... Cable and Line protection Full Range gL/gG 690 VAC (100A 500V) (125A 400V)

Reference Utilisation Protection Type Characteristic Rated Voltage

GLD...Cable and Line protection Full Range gL/gG 500 VAC

Maximum Voltage at 500 VAC at 220/440 VDC Construction Body Blade Contacts Fuse Element

550 VAC 484 VDC

690 VAC

550 VAC 484 VDC

Rated Breaking Capacity


120 kA 25 kA 100 kA 120 kA 25 kA 50 kA 50 kA

Seatite Silver Plated Copper Alloy Silver Plated Strip Flap indicator

None

None

Fuse Blown Indication

Notes :

Characteristics/Standards gL VDE0636 gG IEC269 aR VDE0636 Part 23, IEC269 Part 4 aM VDE0636 Part 2011, IEC 269

Page 48

Technical Information

Jean Mller

HRC DIN Fuses


Fuses for Motor Protection
1. Fuses with aM characteristic The rated Fuse current must be rated motor current. 2. Fuses with gL/gG characteristic The following table shows fuse ratings for short circuit protection of 3 Phase motors, 1500 rpm and internal or surface cooling Direct Starting : max start current 6 x rated motor current, max start time 5 seconds Star/Delta Starting : max start current 2 x rated motor current, max start time 15 seconds Ratings for Star/Delta starting also apply for 3 phase slip-ring motors

Motor Rating @ 400V

Fuse Rating aM (Amps) Rated Motor Current Amps


0.64 0.8 1.6 2 2.6 5 6.6 8.5 15.5 22.5 30 43 58 72 104 142 169 204 243 292 368

Fuse Rating gL/gG (Amps) D.O.L Start


2 4 4 6 6 10 16 20 32 40 63 80 100 125 200 200 250 315 400 400 500

kW
0.18 0.25 0.55 0.75 1.1 2.2 3.0 4.0 7.5 11 15 22 30 37 55 75 90 110 132 160 200

cos
0.7 0.7 0.75 0.8 0.83 0.83 0.84 0.84 0.86 0.87 0.86 0.87 0.87 0.87 0.88 0.88 0.88 0.88 0.88 0.88 0.88

Eff %
62 62 69 74 77 81 81 82 85 87 87 89 90 90 91 91 92 92 92 93 93

D.O.L Start
2 2 2 4 4 6 10 10 16 25 32 50 63 80 125 160 200 250 250 315 400

Star-Delta Start
2 2 2 4 6 10 10 16 25 32 50 63 80 125 160 200 200 250 315 400

Jean Mller

Technical Information

Page 49

HRC DIN Fuses


Time/Current Characteristics gL Curve

Page 50

Technical Information

Jean Mller

HRC DIN Fuses


Time/Current Characteristics aM Curve Seconds

Amps

Jean Mller

Technical Information

Page 51

HRC DIN Fuses


Time/ Current Characteristics uf1 Curve 16A-400A Seconds

Amps 160-630A Seconds

Amps

Page 52

Technical Information

Jean Mller

HRC DIN Fuses


I2T Values - gL Curve

I2T Values - aM Curve

Jean Mller

Technical Information

Page 53