6-1-1
S e ction 6 -1
GE Relays Indexed by Device Function Number
Device Number 2 8 15 21 21(+) 24 25 27 30 32 37 38 40 46 46 (+) 47 49 49 (+) 50 51 50/51 50/51 (+) 52 59 60 61 64 66 67 68 69 74 76 78 79 81 85 86 87 87(+) 94 ( ) ( ) Description Time-delay Starting or Closing Relay Control Power Disconnecting Device Speed or Frequency Matching Device Distance Relay Distance Relay System Overexcitation Relay Synchronizing or Synchronism-Check Device Undervoltage Relay Annunciator Relay Directional Power Relay Undercurrent or Underpower Relay Bearing Protective Device Field Relay Reverse-phase or Phase-balance Current Relay Large Generator/Motor Relay System Phase-sequence Voltage Relay Machine or Transformer Thermal Relay Small Generator/Motor Relay Systems Instantaneous Overcurrent or Rate-of-Rise Relay AC Time Overcurrent Relay Instantaneous and Time Overcurrent Relay Overcurrent Relay System AC Circuit Breaker Overvoltage Relay Voltage or Current Balance Relay Machine Split Phase Current Balance Ground Detector Relay Notching or Jogging Device AC Directional Overcurrent Relay Blocking Relay Permissive Control Device Alarm Relay DC Overcurrent Relay Phase-Angle Measuring or Out-of-Step Protective Relay AC Reclosing Relay Frequency Relay Carrier or Pilot-wire Receiver Relay Lockout Relay Differential Protective Relay Differential Relay System Tripping or Trip-free Relay Auxiliary Relay Timing Relay GE Relay Type SAM,IAV PK-2 GTL CEB, CEY, GCX, GCY, GXS, SLY, SLYG, CEYG, GCXG, GCXY DLP, TLS, TYS, SLS, PLS STV GES, IJS, SLJ, GXS CFV, IAV, NGV, SLV, PJV, HGA, HMA, TOV HAA CAP, CCP, CFW, GGP, ICW, TCW CFW, HGC, ICW, PJC IRT CEH IJC, SGC DGP, DMP ICR, NBV IRT, THC, TMC, MRC MGC, MMC CHC, HFC, PJC, SBC, BFC BFC, IAC, IFC, IFCS, IFCV, SFC, DIAC, DIFC, DSFC IAC, IFC, SFC, TOC, DIAC, DIFC, DSFC DDP, MIC, MDP, MCP, DFM, DFP100, DFP200, SR750 CFV, IAV, NGV, PJV, STV, SLV, TOV CFVB, IJC, NBV IFC, IAC, SFC, MDP PJG, IAV, IFV CFC, CJC, CJCG, CLPG, IBC, MOR, IBCG, IBCV, JBC, JBCG, JBCV, CAP, TCC, TCCV CEB, SLY, SLYG HAA, HGA, HMA, NBT PJC CEX + GSY, OST, CEX + NAA HGA18, NLR, NSR, SLR, TRS, MRS, MOR IJF, SFF NAA, SCA, SPA HEA, HFA, HAS BDD, CFD, IFD, IJD, PVD, SBD, SPD, STD, NBD, BUS, TTS, DTP, SR745 DLS, DGP, DTP, SR489, SR745, BUS1000 HFA, HGA, HMA, NGA, SBA HAA, HEA, HFA, HGA, HMA, HSA, NGA, SBA SAM
6-
6-1-2
Device list for FDR1 50/51 Phase overcurrent and short circuit 51N Time delay ground fault 50N Instantaneous ground fault
Qty.
1
Device No.
50/51/ 51N or 50N
Description
Basic Package 3-Phase Digital Overcurrent, Short Circuit & Ground Fault Relay
GE Model No.
MDP or SR735
3 1
Alternate Package (Single Phase Units) Phase Overcurrent & Short Circuit Relay Time Delay Ground Fault Relay Instantaneous Ground Fault Relay Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Recloser Frequency Options Recloser Relay Power Quality Monitoring
79 81THD
SLR12 PQM
6-1-3
Section 6 -1
FEEDER
Protective Relay Zone (FDR2)
Standard Non-directional circuit, with ground sensor relay:
Device list for FDR2 50/51 Phase overcurrent and short circuit 50GS Instantaneous ground fault 51GS Time delay ground fault
6Qty.
1
Device No.
50/51/ 51GS or 50GS
Description
Basic Package 3-Phase Digital Overcurrent, Short Circuit & Ground Fault Relay
GE Model No.
MDP / SR735
3 1
Alternate Package (Single Phase Units) Phase Overcurrent & Short Circuit Relay Time Delay Ground Fault Relay Instantaneous Ground Fault Relay Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Recloser Frequency Options Recloser Relay
79
SLR12
6-1-4
Device list for FDR3 67 Directional overcurrent and short circuit 67N Directional time delay and instantaneous ground fault
Qty.
1
Device No.
67/67N
Description
Basic Package Directional Phase & Ground Fault Relay (Optional recloser 79 function is included). Alternate Package (Single Phase Units) Directional Overcurrent Relay Directional Ground Fault Relay Options Recloser Relay
GE Model No.
DFP100 or SR750 / SR760
3 1
67 67N
79
SLR12
6-1-5
Section 6 -1
FEEDER
Protective Relay Zone (FDR4 )
Single source incoming line (no internal generation):
Device list for FDR4 27 Undervoltage 51 Phase overcurrent 51N Residual overcurrent 59 Overvoltage 81L/H Frequency
Qty.
1
Device No.
Description
Basic Package Multifunction Digital Protection System Negative Sequence TOC, Definite Time Phase/Ground TOC Phase/Ground Lowset IOC Phase/Ground Highset IOC Phase/Ground Definite Time mho Phase Distance Negative-sequence dir. Undervoltage Overvoltage Under-frequency Over-frequency Control & Monitoring Metering Cold Load Pickup Breaker Health Monitor Failure to Open/Close Detection Demand Ammeter Event Recording Oscillography Fault Reports Multiple (6) Settings Groups Phase Rotation Selection Options Recloser, option Power Quality Monitoring
GE Model No.
DFP100
6-
46PT, 46PD 51PT, 51NT 50PL, 50NL 50PH, 50NH 51PD, 51ND 21P 67N 27 59 81U 810
1 1
79 81THD
DFP100 PQM
6-1-6
Device list for FDR5 87L Pilot wire line 86L Lockout auxiliary
Qty.
2 2
Device No.
87L 86L
Description
Basic Package Pilot Wire Line Differential Relay Lockout Auxiliary Relay Options Pilot Wire Monitor Relay (sending end) Pilot Wire Monitor Relay (receiving end) Alternate Package Current Differential Relay Lockout Auxiliary Relay
GE Model No.
SPD11 HEA61
1 1
85LM 85LM
SPA11 SPA12
2 2
87L 86L
DLS3 HEA61
6-1-7
Section 6 -1
INCOMING LINE
Protective Relay Zone (IL1)
Single source incoming line (no internal generation) :
Device list for IL1 27 Undervoltage 51 Phase overcurrent 51N Residual overcurrent 59 Overvoltage 81L/H Frequency
6Qty.
1
Device No.
51/51N
Description
Basic Package Phase Overcurrent & Ground Fault Relay First Alternate Package (Single Phase Units) Phase & Ground Overcurrent Relay with High Impedance Ground Fault Detection (Power Quality Option) Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Frequency Options (Single Phase Units) Phase/Ground Overcurrent Relays Undervoltage Relay Overvoltage Relay Over and underfrequency Relay (add if upstream auto-reclosing is a concern) Differential Relay (See Bus Protective Zone for Details)
GE Model No.
MDP
51/51N 74LM
DFM3
4 1 1 1 1
6-1-8
Device list for IL2 51 Phase overcurrent 51G-1 Ground overcurrent 51G-2 Ground overcurrent 60V Voltage unbalance 62 Timer
Qty.
1
Device No.
51/51G
Description
Basic Package Phase Overcurrent & Ground Fault (Bus) Relay First Alternate Package (Single Phase Units) Phase & Ground Overcurrent Relay with High Impedance Ground Fault Detection (Power Quality Option) Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Frequency Options (Single Phase Units) Phase/Ground Overcurrent Relays Voltage Unbalance Relay (add if high side fusing could result in single phase of motors) Timing Auxiliary Relay Ground Fault (transformer secondary) Relay (add for two step trouble-shooting for transformer/bus grounds) Differential Relay (See Bus and Transformer Protective Zone for Details) (For additional options see IL1)
GE Model No.
MDP
51/51G/ 74LM
DFM3
4 1 1 1 1
6-1-9
Section 6 -1
INCOMING LINE
Protective Relay Zone (IL3)
Single source incoming line (no internal generation):
Device list for IL3 27 Undervoltage 51 Phase overcurrent 51N Residual overcurrent 59 Overvoltage 81L/H Frequency
Qty.
1
Device No.
Description
Basic Package Multifunction Digital Protection System Negative Sequence TOC, Definite Time Phase/Ground TOC Phase/Ground Lowset IOC Phase/Ground Highset IOC Phase/Ground Definite Time mho Phase Distance Negative-sequence dir. Undervoltage Overvoltage Under-frequency Over-frequency Metering Cold-Load Pickup Breaker Health Monitor Failure to Open/Close Detection Demand Ammeter Event Recording Oscillography Fault Reports Multiple (6) Settings Groups Options Recloser, option Power Quality Monitoring
GE Model No.
DFP100
6-
46PT, 46PD 51PT, 51NT 50PL, 50NL 50PH, 50HH 51PD, 51ND 21P 67N 27 59 81U 81O
1 1
79 81THD
DFP100 PQM
6-1-10
Device list for IL4 51 Phase overcurrent 51N Residual overcurrent 67 Directional phase overcurrent 67N Directional ground overcurrent 85LM/TT Communication monitor 86L Lockout auxiliary 87L Differential
Qty.
1 1 1 1
Device No.
87L 86L 67/67N 51/51N
Description
Basic Package Pilot Wire Line Differential Relay Lockout Auxiliary Relay Directional Phase and Ground Overcurrent Relay Phase Overcurrent and Ground Fault Relay Alternates Line Differential & Channel Monitor & Transfer Trip Auxiliary Relay Directional Phase Overcurrent Relay (Single Phase Units) Directional Ground Overcurrent Relay (Single Phase Units) Phase/Ground Overcurrent Relays (Single Phase Units) Options Pilot Wire Monitor [different device at send and receive ends] Relay Pilot Wire Monitor and Transfer Trip Auxiliary Relay [different device at send and receive ends] Differential Relay (See Bus Protection Zones for Details) (For additional alternates and options see IL1 and IL2) *Must be selected in accordance with companion relay at opposite end of the line. Pilot wire protective auxiliaries may be required.
GE Model No.
SPD11* HEA61 MOR3 MDP
1 3 1 4
1 1 1
Notes:
6-1-11
Section 6 -1
INCOMING LINE
Protective Relay Zone (IL5)
Dual source incoming line (dual line with internal generation & via utility transformer):
Device list for IL5 27L Undervoltage 32 Power direction 47 Phase undervoltage and reverse phase sequence 50L Instantaneous overcurrent 51B Phase time overcurrent 51BN Residual time overcurrent 51G Ground overcurrent 59B Overvoltage 59L Overvoltage 62 Timer 67 Directional phase overcurrent 67N Directional ground overcurrent 81L/H Frequency
6-
Qty.
1 1 1
Device No.
67/67N 51B/51BN 51G
Description
Basic Package Directional Phase and Ground Overcurrent Relay Phase Overcurrent (Partial Differential) and Ground Fault Relay Ground Overcurrent (for transformer lowside) Relay Options Line Undervoltage (transformer highside) Relay Line Overvoltage (transformer highside) Relay (add 27L & 59L as a means of detecting Delta-Wye transformer highside ground fault after utility seperation.) Power Directional Relay (detects tranf. magnetizing current) Auxiliary Timing Relay (add 32 & 62 in lieu of 27L and 59L as alternate means of detecting system ground faults) Phase Undervoltage and Reverse Phase Sequence Relay (add if required for motor bus monitoring or intertie) Bus Overvoltage Relay (add if required for intertie) Over and Underfrequency Relay (add for intertie or load shedding requirements) Instantaneous Overcurrent Relay (add if highside disconnect is not rated for fault interruption) Differential Relay (See Bus and Transformer Protective Zones for Details) (For additional alternates and options see IL1 and IL2)
GE Model No.
MOR3 MDP DIFC
1 1 1 1 1 1 1 1 1
TOV5 or NGV TOV5 or NGV CCP13E SAM201 ICR53A TOV5 or NGV SFF202B or MFF1 PJC11AV or CHC11A
6-1-12
Qty.
1
Device No.
27 47 50 50 51 59 67N/67P 81 50 55 62 46 50/62
Description
Basic Package Multifunction Digital Protection System Bus/Line Undervoltage Negative Sequence Voltage Phase/Neutral/Ground/Neg Seq Loset Inst O/C Phase/Neutral/Ground Hiset Inst O/C Phase/Neutral/Ground/Neg Seq Time O/C Bus/Line Overvoltage Phase/Ground Directional Control Over/Under Frequency Phase/Neutral Current Level Power Factor Definite Time Overcurrent Negative Sequence Overcurrent Breaker Faliure Metering, complete Cold Load Pickup Feature Breaker Operation Failure Trip/Close Circuit Failure Total Breaker Arcing Current VT Failure Demand (A, MW, Mvar, MVA) Analog Input Event Recording Options Recloser, option Power Quality, option High impedance fault, option Lockout Relay Differential Relay (See Bus and Transformer Protective Zones for Details) (For additional alternates and options see IL1 and IL2)
GE Model No.
DFP200
1 1 1 1 1
6-1-13
Section 6 -1
INCOMING LINE
Protective Relay Zone (IL7)
Dual source incoming line (dual line with internal generation & via utility transformer):
Device list for IL7 27L Undervoltage 32 Power direction 47 Phase undervoltage and reverse phase sequence 50L Instantaneous overcurrent 51B Phase time overcurrent 51BN Residual time overcurrent 51G Ground overcurrent 59B Overvoltage 59L Overvoltage 62 Timer 67 Directional phase overcurrent 67N Directional ground overcurrent 81L/H Frequency
6-
Qty.
1 1
Device No.
Description
Basic Package Multifunction Digital Protection System Ground Overcurrent (for transformer lowside) Relay Bus/Line Undervoltage Negative Sequence Voltage Phase/Neutral/Ground Neg Seq Loset Inst O/C Phase/Neutral/Ground Hiset Inst O/C Phase/Neutral/Ground/Neg Seq Time O/C Bus Overvoltage Phase/Ground Directional Control Bus Underfrequency Synchrocheck Phase/Neutral Current Level Power Factor Overfrequency Breaker Open/Close Trip/Close Circuit Failure Total Breaker Arcing Current VT Failure Demand (A, MW, Mvar, MVA) Event Recording Options Recloser, option Bus Transfer Power Quality Monitoring Lockout Relay
GE Model No.
SR750 IFC53A
51G 27 47 50 50 51 59 67 81 25 50 55 81
1 1 1 1
79 81THD 86
6-1-14
Relay and control equipment can be provided to maximize continuity of service to a switchgear load bus by detecting problems with power source (undervoltage, loss of phase, etc.) and transferring the load bus to an alternate or emergency source. Typical two breaker auto throwover schemes are seen in applications were a main breaker losses voltage and an emergency breaker provides power to the lineup. Typical three breaker auto throwover schemes are seen on main-tie-main lineups.
Two/Three breaker automatic transfer scheme: Single phase Basic Package: Hardware relay (no PLC) 2-single phase (27) relays - NGV 4-Agastat timers 1-52 aux switch per M-T-M 2-Lockout (86) relays - HEA 1-Manual/automatic transfer switch (43) 2-Indicating lights and terminal blocks Three phase Basic Package: Hardware relay (no PLC) 2-NGV relay & 2 NBV relays 4-Agastat Timers 1-52 aux switch per M-T-M 2-Lockout (86) relays - HEA 1-Manual/automatic transfer switch (43) 2-Indicating lights and terminal blocks 1-CPT throwover 1-86 lockout to the tie breaker if tit has over current relays on it.
6-1-15
Section 6 -1
INCOMING LINE
Protective Relay Zone (IL9)
Three breaker automatic transfer scheme w/MultiLin SR750 relays:
Basic Package: Hardware relay (no PLC) 1-SR750 meter per main and tie breaker 1-52 aux switch 3 stage, each breaker 1-52 pos switch 3 stage, each breaker 1-HGA aux relay per main breaker - line pts on each main breaker - bus pts on each side of tie breaker - set of (3) cts per breaker 1-CPT throwover SR750 relays will require programming & wiring. The relay has step by step instructions to do this and has the capabilities as part of the standard relay offering. SR750 Relay System ANSI 27 47 50 50 51 59 67 81 Protection / Control Bus/Line Undervoltage Negative Sequence Voltage Phase/Neutral/Ground/Neg Seq Loset Inst O/C Phase/Neutral/Ground Hiset Inst O/C Phase/Neutral/Ground/Neg Seq Time O/C Bus Overvoltage Phase/Ground Directional Control Bus Underfrequency Undervoltage Automatic Restoration Underfrequency Automatic Restoration Breaker Failure with Current Superv. Bus Transfer Programmable Logic Inputs Multiple Setpoint Groups Monitoring / Control Synchrocheck Phase/Neutral Current Level Power Factor Autoreclose (760 only) Overfrequency Breaker Open/Close Manual Close Feature Blocking Cold Load Pickup Feature Blocking Breaker Operation Failure Trip/Close Circuit Failure Total Breaker Arcing Current VT Failure Demand (A, MW, Mvar, MVA) Analog Input Event Recording
6-
25 50 55 79 81
6-1-16
Qty.
1 1
Device No.
51/51N 86B
Description
Basic Package Phase Overcurrent and Ground Fault Relay Lockout Auxiliary Relay Alternate Package (Single Phase Units) Phase Overcurrent Relay Ground Fault Relay Lockout Auxiliary Relay Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Frequency Lockout Auxiliary Relay Options Ground Fault Relay (ungrounded systems)
GE Model No.
MDP or SR735 HEA61
3 1 1
51 51N 86B
HEA61
64
TCCV
6-1-17
Section 6 -1
BUS
Protective Relay Zone (BUS2)
Multiple sources with bus tie breaker:
Qty.
1
Device No.
51/51N
Description
Basic Package Phase Overcurrent and Ground Fault Relay Alternate Package (Single Phase Units) Phase Overcurrent Relay Ground Fault Relay Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Frequency Options Ground Fault Relay (ungrounded systems) Lockout Auxiliary Relay (as many as required)
GE Model No.
MDP or SR735
6-
3 1
51 51N
1 1
64 86B
TCCV HEA61
6-1-18
Qty.
3
Device No.
87B
Description
Basic Package Differential Relay Options Lockout Auxiliary Relay (as many as required)
GE Model No.
PVD21 or SBD11
86B
HEA61
6-1-19
Section 6 -1
BUS
Protective Relay Zone (BUS4)
Multiple sources, bus tie breakers, multi-ratio CTs
Qty.
1
Device No.
87B
Description
Basic Package Differential Relay Options Lockout Auxiliary Relay (as many as required)
GE Model No.
BUS1000
6-
86B
HEA61
6-1-20
Device list for TR1 50/51 Overcurrent & short circuit 50GS Ground fault
Qty.
1
Device No.
50/51/50GS
Description
Basic Package Digital Overcurrent, Short Circuit & Ground Fault Relay Alternate Package (Single Phase Units) Overcurrent and Short Circuit Relay Ground Fault Relay Second Alternate Package Multifunction microprocessor-based relay system including the following functions: Undervoltage Negative Sequence Overcurrent (DFP100 & 200 only) Negative Sequence Voltage (SR750 only) Phase Overcurrent Residual Overcurrent Overvoltage High Impedance Ground (DFP200 only) Frequency Options Lockout Auxiliary Relay
GE Model No.
MDP or SR735
3 1
50/51 50GS
86T
HEA61
6-1-21
Section 6 -1
TRANSFORMER (TR)
Protective Relay Zone (TR2)
Protection for transformers 2000KVA and above, medium voltage windings:
Device list for TR2 87T Differential 86T Lockout auxiliary 50/51 Overcurrent & short circuit 50GS Ground fault 63 Integral fault pressure 63X Fault pressure auxiliary
6-
Qty.
1 X 1 1
Device No.
87T 86T 50/51/50GS 63X
Description
Basic Package Microprocessor Transformer Differential Relay Lockout Auxiliary Relay (quantity as required) Overcurrent, Short Circuit and Ground Fault Relay Fault Pressure Auxiliary Relay First Alternate Package Differential Relay (Plus remaining devices listed in Basic Package) Second Alternate Package Differential Relay (Plus remaining devices listed in Basic Package) Third Alternate Package (E/M) Differential Relay Lockout Auxiliary Relay (quantity as required) Overcurrent and Short Circuit Relay Ground Fault Relay Fault Pressure Auxiliary Relay
GE Model No.
DTP1 HEA61 MDP0 HAA16B
87T
TTS-0
87T
STD15C
3 X 3 1 1
6-1-22
Qty.
1
Device No.
87
Description
Basic Package
Microprocessor transformer differential relay Percent current differential Percent restraint range (dual slope SR745) Phase shift compensation Harmonic restraint (harmonics) Unrestrained differential IOC-highset Operating time (cycles) Applicable to transformers CT ratio (5 A) matching tap range Sampling rate (# sample/cycle) Instantaneous overcurrent Time overcurrent TOC curve shapes Underfrequency & rate of change Negative sequence IOC & TOC Overexcitation Restricted Ground Fault Overfrequency Differential currents Ia, Ib, Ic Demand interval Ia Accuracy (percent full scale) Fundamental RMS currents Running and maximum current demand Sequence of events (# events stored) Oscillography (# events/ duration in cycles) Fault reporting Auto configuration of CTs Waveform Capture and Playback Relative cost
GE Model No.
SR745
87/50
50G, 50N, 50P 51G, 51N, 51P 81U 46/50, 46/51 59/81 87TG 810
Options
1 86T Auxiliary Lockout relay (as many as required) HEA61
6-1-23
Section 6 -1
TRANSFORMER (TR)
Additional Transformer Ground Protection
Device list for Additional Transformer Ground Protection 51G Time overcurrent 87N Ground differential
6Qty.
1
Device No.
51G
Description
Basic Package Time Overcurrent Relay Alternate Package (Single Phase Units) Time Overcurrent Relay Ground Differential Relay *Note: The SR745 digital transformer relay includes 87N.
GE Model No.
MIC5
1 1
51G 87N
6-1-24
Qty.
1 1
GE Model No.
IAV54E or TOV5 MDP0 or 735
1 3 1
27 50/51 50GS
1 1
27 46 49 49R 50GS 66
1 1 1 1 1 1 1
6-1-25
Section 6 -1
MOTOR (MTR)
Protective Relay Zone (MTR1A)
Recommended protection for a more important small inductions motor (below 1500 HP): Device list for MTR1A 27 Undervoltage 37 Undercurrent 38 Bearing Overtemperature (RTD) 46 Unbalance or current-reversal 47 Three phase undervoltage and reverse phase sequence 48 Adjustable difinite time time device or timer 49 Overload 49R Winding Overtemperature (Thermistor orRTD) 49S Locked rotor 50 Short circuit 50GS Ground fault 60V Voltage unbalance 62 Timer 66 Successive starts 87M Differential 86, 86M Lockout Auxiliary
6-
Qty.
1
GE Model No.
239 or MMC IAV54E or TOV5
TOV5
1 1
86M 87M
6-1-26
Qty.
1
GE Model No.
269 Plus
1 1
6-1-27
Section 6 -1
MOTOR (MTR)
Protective Relay Zone (MTR3)
Recommended protection for a synchronous motor in addition to that provided in preceding zones MTR1 through MTR2A: Device list for MTR3 26F Winding Overtemperatures 27DC Undervoltage 37 Undercurrent 48 Incomplete sequence 50 Instantaneous overcurrent 55 Power factor 95 Reluctance Torque Sync./Re-Sync.
6Qty.
1 26F 27DC 37 50 55 86 95 96
GE Model No.
SPM
6-1-28
Qty.
1
GE Model No.
469
HEA61
87M
CFD22A or DTP1
6-1-29
Section 6 -1
MOTOR (MTR)
Protective Relay Zone (MTR4)
Minimum protection for a small synchronous motor (below 1500 HP): Device list for MTR4 26 Apparatus thermal 27 Time undervoltage 40 Loss-of-field 47 Undervoltage and reverse phase sequence 48 Incomplete sequence timer 49/50 Thermal overcurrent 49R Winding overtemperature (RTD) 49S/50 Time and instantaneous overcurrent (locked rotor) 50GS Instantaneous overcurrent ground sensor 50/51 Time and Instantaneous Overcurrent 55 Power factor 60V Voltage unbalance 62 Timing auxiliary
6-
Qty.
1 1 1
Device
26 27 40
Description
Basic Package Ammortisseur Winding Protection (include if field is accessible and this function is not part of excitation/controls for motor) Undervoltage Relay Loss-of-field Protection (DC undercurrent) (Include in place of 55 if field is accessible and the motor is part of motor/generator set and this function is not part of excitation/controls for motor.) Overload, Short Circuit and Ground Fault Relay Out of Step Protection (include if not part of excitation controls for motor) First Alternate Package Undervoltage Relay Overload and Short Circuit Relay Ground Fault Relay (Plus remaining devices listed in Basic Package.) Second Alternate Package Undervoltage Relay Overload and Short Circuit Protection Ground Fault Relay (plus remaining devices listed in Basic Package.) Options (See options for MTR1 and MTR2)
GE Model No.
IAV54E or TOV5 -
1 1
50/51/50GS 55
MDP0 -
1 3 1
27 50/51 50GS
1 1 1
27 49/50 50GS
6-1-30
Qty.
1
GE Model No.
MMCI
1 1 1
TOV5
40
1 1
51R 81L
IAC60A SFF201
1 1
86M 87M
HEA61 CFD22A
6-1-31
Section 6 -1
Generator (GEN)
Protective Relay Zone (GEN1)
Minimum protection for a small machine with low resistance grounding: Device list for GEN1 27 Undervoltage 32 Power Direction 40 Loss of Excitation 46 Current Unbalance 49R Overload (RTD) 50GS Instantaneous Overcurrent Ground 51GN Time Overcurrent Ground 51V Time Overcurrent (V Restraint) 59 Overvoltage 64B Bus Ground Detection 81L/H Frequency 86G Lockout Auxiliary 87G Differential
6Qty.
3 1
Device
51V 51GN
Description
Basic Package Voltage-restrained Time Overcurrent Relay Neutral Ground Overcurrent Relay Options Undervoltage Relay Reverse Power Relay (detects losses over 5%) or Reverse Power Relay (detects losses below 5%) Loss-of-excitation Relay Negative Sequence Relay Stator Overtemperature Relay (RTD input) Ground Sensor Overcurrent Relay (in place of 51GN where system ground is not generator neutral) Voltage-controlled Overcurrent Relay (in place of 51V) Overvoltage Relay Generato4 Ground Overvoltage Relay (in place of 51GN where generator is ungrounded) Under/Overfrequency Relay Lockout Auxiliary Relay Self-balancing Current Differential Relay (for connections see MTR1A figure) or Percentage Current Differential Relay
GE Model No.
IFCV51AD DIFC or IFC53A
1 1 1 1 1 1 3 1 1 1 1 1
TOV5 or IAV54 ICW51A CEH51A SGC21C IRT51E DIFC or HFC21 IFCS51AD TOV5 or IFV71AD TOV5 or IFV51DD SFF202B HEA61 MDP or CFD22A
6-1-32
Qty.
1
GE Model No.
MID100 MGC
MIC7/TOV4
1 1 1
27 32 81L/H
6-1-33
Section 6 -1
Generator (GEN)
Protective Relay Zone (GEN2)
Recommended protection for a small machine with low/high resistance grounding:
Device list for GEN2 12 Overspeed 24 Overexcitation, Volts/Hz 27 Undervoltage 50/27 Inadvertent generator energization 32 Reverse power for anti-motoring 38 Bearing overtemperature 39 Bearing vibration (analog inputs) 40Q Loss of field 46 Negative Sequence Overcurrent (I 22t) 47 Voltage phase reversal 49 Stator thermal (RTD and thermal model) 50BF Breaker failure detection 50S Instantaneous overcurrent (during startup) 50/51GN Instantaneous or definite time overcurrrent 51V Voltage restrained phase overcurrent 59 Overvoltage 59GN/ 100% stator ground 27TN 60FL VT fuse failure detection 81 over and underfrequency 87G Phase differential 86G Lockout Auxiliary
6-
Qty.
1
Device
51V 12 24 27 50/27 32 38 39 40Q 46 47 49 50BF 50S 50/51GN 51V 59 59GN/27TN 60FL 81 87G 86G
Description
Basic Package
Multifunction microprocessor-based protection including the following functions: Overspeed Overexcitation, Volts/Hz Undervoltage Inadvertent generator energization Reverse power for anti-motoring Bearing overtemperature Bearing vibration (analog inputs) Loss of field Negative Sequence Overcurrent (I 22t) Voltage phase reversal Stator thermal (RTD and thermal model) Breaker failure detection Instantaneous overcurrent (during startup) Instantaneous or definite time overcurrent) Voltage restrained phase overcurrent Overvoltage 100% stator ground VT fuse failure detection Over and underfrequency Phase differential Sequential tripping logic Trip coil supervision
GE Model No.
SR489
Options
1 Lockout Relay (For additional options, see GEN1 package) HEA61
6-1-34
Time Overcurrent (V Restraint) Overvoltage Voltage Balance Ground (field) Ground (stator) Out-of-Step Frequency Lockout Auxiliary Differential
If no external fault source exists, exchange connections of protection from line side CTs to neutral side CTs and vice versa.
Qty.
1
GE Model No.
DGP-BA 0005
1 1 1 1 1 1
6-1-35
Section 6 -1
Generator (GEN)
Protective Relay Zone (GEN4)
Recommended protection for a more important large machine with high resistance grounding: Device list for GEN4 21G Distance 21GX 24 27 27TN Aux to 2G Overexcitation Undervoltage Undervoltage (Third Harmonic) 32 Power Direction 40 Loss of Excitation 46 Current Unbalance 49R Overload (RTD) 51GN Time Overcurrent (Ground )
**
51V Time Overcurrent (V Restraint) 59 Overvoltage 60V Voltage Balance 64F Ground (field) 64G Ground (stator) 78 Out-of-Step 81L/H Frequency 86G Lockout Auxiliary 87G Differential
If no external fault source exists, exchange connections of protection from line side CTs to neutral side CTs and vice versa.
6-
Qty.
1
GE Model No.
DGPCA
86G
HEA61
6-1-36
METERING
Power Quality Metering and Monitoring
EPM
Application
n n Energy and demand billing meter Three or four-wire 3 phase systems n
PQM
Applications
Metering of distribution feeders, transformers, generators, capacitor banks and motors Medium and low voltage systems Commercial, industrial, utility Flexible control for demand load shedding, power factor, etc. Power quality analysis
n n n n
n n n n n
Metering / Control
n n n n n n A V W var VA varh Wh PF Hz unbalance A W var VA demand Load shedding Power factor control Pulse input totalizing Pulse output based on kWh, kvarh or kVAh
User Interface
n n n n 2 line LCD display 3 button keypad Programming security code ModBus RTU protocol (optional)
Monitoring
n n n n n Harmonic analysis through 63rd with THD and TIF Event recorder Waveform capture Data logger Triggered trace memory
Features
n n n Pulse initiation (optional) Easy retrofit Drawout S1 case
Communications
n n n n n Ports: RS232 front, dual RS485 rear ModBus RTU protocol Mini RTU: digital 4 in / 4 out Analog 1 in / 4 out Local/remote display of all values
6-1-37