Sie sind auf Seite 1von 3

Model: Frequency: Fuel Type:

C350 D5 50Hz Diesel

Generator set data sheet 350 kVA Standby

Spec sheet: Noise data sheet (Open/enclosed): Airflow data sheet: Derate data sheet (Open/enclosed): Transient data sheet: Standby

SS9-CPGK ND50-OS550 / ND50-CS550 AF50-550 DD50-OS550 / DD50-CS550 TD50-550 Prime kVA (kW) 320 (256) 1/2 8.0 36 3/4 12.2 56 Full 16.7 76 1/4 4.4 20 1/2 7.9 36 3/4 11.4 52 Full 15.2 69

Fuel consumption
Ratings Load US gph L/hr

kVA (kW) 350 (280) 1/4 4.5 20

Engine
Engine manufacturer Engine model Configuration Aspiration Gross engine power output, kWm BMEP at set rated load, kPa Bore, mm Stroke, mm Rated speed, rpm Piston speed, m/s Compression ratio Lube oil capacity, L Overspeed limit, rpm Regenerative power, kW Governor type Starting voltage

Standby rating Cummins NT855 G6 4 Cycle; In-line; 6 Cylinder Diesel Turbo Charged 310 1765 140 152 1500 7.6 14:1 36 1800 50 22 Electronic 24 Volts DC

Prime rating

280 1600

Fuel flow
Maximum fuel flow, L/hr Maximum fuel inlet restriction, mm Hg Maximum fuel inlet temperature (C) 288 203 70

Air
Combustion air, m3/min Maximum air cleaner restriction, kPa 22.5 6.2 21.7

Web: www.cumminspower.com

Tel: +44(0)1977 658 100 Fax: +44(0)1977 608 111

Diesel Generators
To Power YOUR World
www.adeltd.co.uk

Exhaust
3 Exhaust gas flow at set rated load, m /min Exhaust gas temperature, C Maximum exhaust back pressure, kPa

Standby rating 69.4 607 10.2

Prime rating 64.3 574

Standard set-mounted radiator cooling


Ambient design, C Fan load, KWm Coolant capacity (with radiator), L Cooling system air flow, m3/min @ 12.7mmH2O Total heat rejection, BTU/min Maximum cooling air flow static restriction mmH2O 50 8 45 7.5 9545 19.1 8625

Open set derating factors kVA (kW)


Note: Standard open genset options running at 400V, 150m above sea level. For enclosed product derates, please refer to datasheet - DD50CS550. 27C Standby Prime 350 (280) 318.1 (254.5) 40C 345 (276) 313.6 (250.9) 45C 334.6 (267.7) 304.3 (243.4) Open 3196 3386 50C 324.3 (259.4) 294.9 (235.9) Enclosed 4744 5576 55C 314 (251.2) 285.4 (228.3)

Weights*
Unit dry weight kgs Unit wet weight kgs

* Weights represent a set with standard features. See outline drawing for weights of other configurations

Dimensions
Standard open set dimensions Enclosed set standard dimensions

Length 3549 5110

Width 1100 1563

Height 2078 2447

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

Web: www.cumminspower.com

Tel: +44(0)1977 658 100 Fax: +44(0)1977 608 111

Diesel Generators
To Power YOUR World
www.adeltd.co.uk

Alternator data
Feature code B681 Connection1 Wye, 3 Phase Temp rise degrees C Duty2 163/125 S/P Alternator HC4E Voltage 380-415V

Ratings definitions
Emergency Standby Power (ESP) Limited-Time running Power Applicable for supplying power to Applicable for supplying power to a varying electrical load for the constant electrical load for limited duration of power interruption of a hours. Limited Time Running reliable utility source. Emergency Power (LTP) is in accordance with Standby Power (ESP) is in ISO 8528. accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Prime Power (PRP): Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Base Load (Continuous) Power Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.

Formulas for calculating full load currents:


Three phase output Single phase output

kWx1000 Voltagex1. 73x0.8

kWxSingleP haseFactor x1000 Voltage

Advanced Diesel Engineering Ltd. 14 Langthwaite Business Park South Kirkby, Pontefract WF9 3AP ENGLAND ,

Web: www.cumminspower.com

Tel: +44(0)1977 658 100 Fax: +44(0)1977 608 111