Waterloo manufactures its range of products in England and Holland. The photograph shows the new factory built for Waterloo in 2003.

Diffusers
A complete range of products designed to be installed in various ceiling systems. Most diffusers are made from aluminium, and can be ordered with or without plenum chambers for easy connection to duct work. Diffusers can be ordered in customer specified (PPM/G) colours; standard colour is PPM 9010 (20% gloss white). This range is complemented by the Aircell range of polymer Grilles and Diffusers.

Symbols Used
T Maximum Throw 50mm from the ceiling (for air velocity of 0.1m/s) in isothermal conditions (unless otherwise stated)[m] To Maximum Throw (for air velocity of 0.15 m/s) in occupied zone in isothermal conditions (unless otherwise stated) [m] Terminal Velocity [m/s] vt v Air Velocity 25 mm from the grille face [m/s] Lp NR level is Peak Level on NR curves based on SWL ref 10-12 W less 8dB Room Absorbtion [dB] Lw Uncorrected sound level [dB] qv Air Volume [l/s] or [m3/h] Static Pressure [Pa] Ps W Width [mm] H Height [mm]

Our equipment is suitable for dry, filtered air conditioning systems. Should this not be the case then a suitable maintenance regime should be in operation that reflects the site conditions.

Waterloo 2.0

Tel: +44 (0) 1622 711511

Waterloo
Contents
Linear Diffusers
CS-F, CS-P, CS-S&E, CS-WR Linear Slot Diffusers KCS-F, KCS-L Linear Slot Diffusers . . . . . . . . . . . STKCS, STCS Linear Slot Diffusers . . . . . . . . . . . DSL, DSL-D Linear Diffusers . . . . . . . . . . . . . . . . FCD1, FCD2 Linear Fan Coil Diffusers . . . . . . . . . Plenum Chambers Linear Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 . .8 .10 .12 .14 .16

Square Diffusers
DF, DE, DFA Louvred Face Diffusers . . . . . . . . . . . . . . . . . . . M300, M450, M500, M600, M625 Aircell Polymer Louvre 2300, 2600 Aircell Polymer Diffusers . . . . . . . . . . . . . . . . . LFF, LFM Laminar Flow Diffusers . . . . . . . . . . . . . . . . . . . . . . CPD, CPDE Perforated Face Diffusers . . . . . . . . . . . . . . . . . . KRCP, KRCPE Perforated Face Diffusers . . . . . . . . . . . . . . . . MWVP, MWVPD Perforated Face Diffusers . . . . . . . . . . . . . WPD, MWPD Perforated Face Diffusers . . . . . . . . . . . . . . . . WID Perforated Face Diffusers . . . . . . . . . . . . . . . . . . . . . . . ........... Face Diffusers ........... ........... ........... ........... ........... ........... ........... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 .36 .38 .42 .46 .50 .52 .54 .56

Luminaire Diffusers
LUMDF Luminaire Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

Swirl Diffusers
SDFC, SDFS Circular/Square Fixed Blade Swirl Diffusers . . . . . SDFS-P Perforated Face Fixed Blade Swirl Diffusers . . . . . . . . . SDFCH, SDICH, SDACH High Capacity Circular Swirl Diffusers SDVS, SDVC Vane Swirl Circular / Square Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 .62 .64 .66

Circular Diffusers
RWI, RWI-R Circular Perforated Face Diffusers RWK, RWK-R Circular Plain Face Diffusers . . RWV, RWV-R Circular Plain Face Diffusers . . . MC Small Format Circular Diffusers . . . . . . . . . WR Large Format Circular Diffusers . . . . . . . . . WFO, WFOV Aircell Polymer Floor Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 .72 .74 .76 .78 .80

Jet Diffusers
WDJ Drum Jet Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84 VS3 Supply Air Nozzles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86 RWH, RWH-P Hi-Flo Jet Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88

Supply and Exhaust Valves


VA, VB, VC Steel Supply and Exhaust Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92 RPVB Aircell Polymer Supply and Exhaust Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

Waterloo 2.0

Tel: +44 (0) 1622 711511

Linear Slot Diffusers


CS-F CS-P CS-S&E CS-WR
Introduction
The Waterloo small format continuous slot diffuser series CS has for many years set the industry standard in terms of highest aerodynamic and acoustic performance. The CS range is ideally suited to variable volume applications due to its excellent low flow rate air diffusion characteristics and high air handling capacity. The novel air pattern control element design allows any air diffusion to vertical projection, without any change in the facial appearance. CS diffusers are suitable for all commercial and industrial projects requiring single or multislot diffusers for ceilings, bulkheads or sidewall supply and exhaust. Diffusers are manufactured from aluminium alloy extrusions fixed or clipped to cross stays allowing easy removal of internal vanes and pattern control elements.

Waterloo
E F E F

28

18
C

28

CS-F

CS-P

Product Description
CS-F Wide flanged general purpose CS-P Narrow flange for flush / recess mounting CS-S&E Supply and Exhaust (or dual supply) system diffuser CS-WR Plank Replacement Unit Ends End caps ED Equalising Deflector

Supply = F

Extract = F - 2

Frame alignment strip

Features
High air handling capacity Wide dynamic range for perfect VAV systems Strong coanda effects for good low flow performance Fully adjustable air pattern from horizontal to vertical Hidden flow control vanes for consistent facial appearance Continuous joint detail for ceiling integrations D G

CS-S&E-F

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request 45 - 60

CS-F + PLS

CS-F + PB
Hemmed Plenum

Weights
0.8N + 0.7 kg/m N = number of slots

Riveted Plenum

Sizes
Standard from 1 to 8 slots wide 1500mm long (excluding ends). Continuous diffuser lengths are supplied in sections for butt jointing on site. (Alignment plates supplied)

Type CS-F

Slots
C E F C E Flush E Recess F C E

1
76 57 40 56 50 57 40 -

114 152 190 228 266 304 343 95 133 171 209 247 285 324 79 117 155 193 231 269 307 95 89 96 79 133 127 134 117 171 165 172 155 209 203 210 193 247 241 248 231 285 279 286 269 323 317 324 307

CS-P
G 46 84 122 160 198 236 274 312 34 72 110 148 186 225 263 301

Order Example
CS-F/3000/S1/PPM9010/ENDS Type Length N of slots Finish End caps

PB PLS D
1 2 3 4 5 6 7 8 slot slot slot slot slot slot slot slot

CS-S & E-F


114 152 190 228 266 304 343 95 133 171 209 247 285 324

N of Slots (Supply or Extract) F

40

79

117 155 193 231 269

Waterloo 2.0

Tel: +44 (0) 1622 711511

1.5 8

18

18

18

81.5

Waterloo
Special Products
More information about these products available on request

Linear Slot Diffusers


CS-F CS-P CS-S&E CS-WR

Waterloo 2.0

Tel: +44 (0) 1622 711511

Linear Slot Diffusers


CS-F CS-P CS-S&E

Waterloo

Curved CS unit

See page 16 for plenum reference

X 75 0 X

Standard Diffusers are supplied with flow control vanes in lengths up to 750mm (to suit diffuser length).

Special To provide finer control of the air pattern, flow control vanes may be supplied in any specified length.

Waterloo 2.0

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria
Ceiling height 2.75m, increase throw by 1m for each 1m increase in ceiling height Horizontal diffusion is based on a cooling differential of 11C Vertical projection is based on a heating differential of 11C NR is sound pressure level/Noise Criteria Curve & based on a room absorption of 8dB. Vr = mean room air velocity (m/s) Vt = terminal velocity of supply air jet (m/s)

Linear Slot Diffusers


CS-F CS-P CS-S&E
Selection Example CS2/1800
Total air flow rate 180 I/s = 100 l/s/m 1 Way Throw Minimum throw 2.8m (3.5 x 0.8 factor) Maximum throw 7.2m (9.0 x 0.8 factor) Pressure drop 25Pa Noise level NR29 (NC32 - 3db length correction) 2 Way Throw Minimum throw 2.0m (2.5 x 0.8 factor) Maximum throw 5.2m (6.5 x 0.8 factor) Pressure drop 25Pa Noise level NR25 (NR28 - 3db length correction)

Length Corrections
Active Length (m) 0.5 1.25 NR Reduction -8 -5 Throw multiplier 0.45 0.65 2.0 -3 0.8 2.5 -2 0.9 3.0 0 1.0

Performance Nomogram
AIR FLOW RATE l/s per m length MAXIMUM RADIUS OF DIFFUSION (Horizontal) Vr = 0.10 m/s (Vt = 0.25 m/s) MEDIUM RADIUS OF DIFFUSION (Horizontal) Vr = 0.15 m/s (Vt = 0.5 m/s) MINIMUM RADIUS OF DIFFUSION (Horizontal) Vr = 0.25 m/s (Vt = 0.85 m/s)
25 20 300 20 15 15 12 10 9 8 10 9 100 90 80 70 60 50 40 6 3 1 1 8 7 4 7 6 5 12 10 12 8 7 6 5 4 3 10 8 7 6 5 4 3 2.5 2 55 50 45 40 35 30 25 20 2 200

700 600 500 400

VERTICAL PROJECTION Vt = 0.25 M/S NR LEVEL Horizontal diffusion & exhaust air

N OF SLOTS
1

PRESSURE DROP (Pa) Horizontal Exhaust diffusion


100 75 50 25 12.5 50 37.5 25 12.5 6.25

ple n Exam electio Throw) S y (2 Wa

Selection Example (1 Way Throw)

4 1.25 5 6 7 8

30 3

20

Waterloo 2.0

Tel: +44 (0) 1622 711511

Linear Slot Diffusers


KCS-F KCS-L
Introduction
The Waterloo series KCS is a standard alternative to the infinitely variable CS linear slot diffuser. Available in 1 to 4 slots it comes complete with a black polymer pattern control element and will provide either a one or two way horizontal distribution. Each unit can be supplied with either conventional end caps or polymer flat inserts where a lay-in grid is used. The KCS is suitable for VAV systems or conventional fan coil systems and can be supplied with a plenum box if required. Lengths are available up to 1800mm long in one piece.

Waterloo

Product Description
KCS-F KCS-L FL KPL Flanged linear slot diffuser Recessed frame linear slot diffuser End caps (For KCS-F) Polymer end caps (Suitable for KCS-F and KCS-L)

Features
VAV system compatibility One or two way directional throw Other frame styles available Black pattern control elements

Finishes
PPM9010 (RAL 9010 20% Gloss White) Black polymer blades Other frame colours and anodised finish available on request

Advantages
Two way variable throw characteristics Easily adjustable air pattern Lay-in grid compatible

Weights
0.8N + 0.7 kg/m N = number of slots

Sizes
Standard from 1 to 4 slots wide 1800mm long (excluding ends). Continuous diffuser lengths are supplied in sections for butt jointing on site. (Alignment plates supplied)

KCS Order Example KCS-2F/1800/PPM9010/FL


Type N of slots Outer frame type Length Finish End caps KCS-1F KCS-2F KCS-3F KCS-4F KCS-1L KCS-2L KCS-3L KCS-4L

C
75 113 151 189 46 84 122 160

E
55 93 131 169 48 86 124 162

Plenum Widths D
KCS-1F KCS-2F KCS-3F KCS-4F KCS-1L KCS-2L KCS-3L KCS-4L 46 84 122 160 46 84 122 160

Waterloo 2.0

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria
Ceiling height 2.75m Temperature differential -11C NC is sound pressure level/Noise Criteria Curve & based on a room absorption of 8dB. Vr = mean room air velocity (m/s) Vt = terminal velocity of supply air jet (m/s) Please note that for heating applications the KCS diffusers are limited to a maximum supply air temperature of 50C

Linear Slot Diffusers


KCS-F KCS-L
Selection Example KCS-2F/1800
Total air flow rate 180 I/s Air flow rate per metre = 100 l/s/m Minimum throw 2.8m (3.5 x 0.8 factor) Maximum throw 7.2m (9.0 x 0.8 factor) Pressure drop 25Pa Noise level NC29 (NC32 - 3db length correction)

Length Corrections
Active Length (m) NR Adjustment 0.5 -8 0.45 1.25 -5 0.65 2.0 -3 0.8 2.5 -2 0.9 3.0+ 0 1.0

Performance Nomogram
RADIUS OF DIFFUSION MAXIMUM MINIMUM Vr = 0.10 m/s Vr = 0.25 m/s (Vt = 0.25 m/s) (Vt = 0.85 m/s) 25 NR LEVEL Horizontal diffusion & exhaust air 300 20 12 10 200 15 8 7 6 5 10 9 100 90 80 70 60 50 40 6 1 8 7 2 4 3 55 50 45 40 35 30 25 20

Throw Multiplier

AIR FLOW RATE l/s per m length

PRESSURE DROP (Pa) Horizontal Exhaust Diffusion

N OF SLOTS

100 50 75 38 50 25 30 20 10 5 15 10

3 5 4

30 3

20

Waterloo 2.0

Tel: +44 (0) 1622 711511

Linear Slot Diffusers


STKCS STCS
140

Waterloo
50

Introduction
The Waterloo series STKCS / STCS is a one or two slot diffuser with a front face plate designed to be mounted into 600mm and 1200mm modular T-Bar ceiling systems. The front face plate on both the one and two slot are the same size to provide a uniform facial appearance. The units are supplied with their own plenum boxes as standard.

Product Description
STKCS-1 Single slot diffuser - one way throw with a black polymer pattern control element STKCSI-1 Single slot diffuser - one way throw with 6mm thermal/acoustic lining in the plenum STCS-2 Two slot diffuser - two way throw with a black aluminium pattern control element STCSI-2 Two slot diffuser - two way throw with 6mm thermal/acoustic lining in the plenum 100

275

95 100

100

50

STCS-2
D

Features
Common faceplate width for one and two slot Integrated plenum unit Sizes to suit 600, 1200 & 1500mm T-Bar ceiling systems High induction characteristics VAV compatible Modular design

240

95 100

STKCSI-1
Nom. W - 5

Finishes
Front face plate PPM9010 - 20% Gloss White Other colours available on request

Weights
STCS-1 STCS-2 4.0 kg/m Nom. L + 5 95 5.7 kg/m STKCS-1 3.7 kg/m STKCS-2 5.0 kg/m

Sizes
See tables

Nom. L

ST(K)CS-1

Order Example
STKCS-2/1195/PPM9010/980/125/1 Type No. of slots Diffuser length Finish Plenum length Plenum spigot diameter N of spigots

STKCS-1
Nom. L 420 - 700 840 - 1260 E
D

STKCS-2
Nom. L 420 - 700 840 - 1260 E
D

240 1 x 100 240 1 x 125

275 1 x 125 275 1 x 160

1400 - 1540 240 2 x 100 1680 - 1820 240 2 x 125

1400 - 1540 275 2 x 125 1680 - 1820 275 2 x 160

Waterloo 2.0

10

Tel: +44 (0) 1622 711511

100

Waterloo
Selection Criteria
Ceiling Height 2.7m Temperature Differential -11K Average room velocity Vr 0.15m/s NR is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB

Linear Slot Diffusers


STKCS STCS
Selection Example STKCS-1/1400
Air Volume 50 I/s Throw 4.0 m Pressure Drop 23 Pa Noise Level NR 20

All selections include the plenum

Performance Table STKCS


m3/h l/s W Slots T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp 3.9 11 5.2 18 22 3.9 11 4.9 16 21 5.9 24 25 3.9 11 5.3 14 20 5.6 21 24 3.9 11 4.6 13 20 5.4 19 23 3.9 11 4.6 13 20 5.2 18 22 3.4 10 3.9 11 4.5 13 20 5.6 21 24 3.5 10 3.9 11 4.9 16 21 3.5 10 4.4 13 20 5.3 18 22 560 1 2.8 14 2 1 2.3 9 3.4 18 700 2 1 2.0 7 2.8 14 3.8 21 20 840 2 1 1.7 5 2.5 10 3.2 17 4.1 23 20 Plenum length (mm) 980 2 1120 1 2 1.5 4 2.2 8 2.8 14 3.6 18 1260 1 2 1.3 3 2.0 7 2.6 12 3.2 16 3.8 21 1400 1 2 1.2 2 1.8 6 2.3 9 2.8 14 3.5 17 4.0 23 20 1540 1 2 1.1 1 1.6 5 2.1 7 2.6 11 3.1 15 3.6 18 -

54

15

72

20

108

30

126

35

144

40

180

50

198

55

126

65

252

70

306

85

360

100

For exhaust applications, please multiply the above pressure drops (Ps) by 1.2, and add 3dB to the noise levels.

Waterloo 2.0

11

Tel: +44 (0) 1622 711511

Linear Diffusers
DSL DSL-D
Introduction
The Waterloo large format linear diffusers series DSL are ideal for most commercial supply and exhaust systems and integrate well with ceiling tile and lighting layouts. The clear design provides an extremely low air resistance characteristic and this makes the diffuser ideal for any fan coil or induction system which is pressure sensitive. Single or multislot diffusers are available with fixed 1 or 2 way air patterns; multislot 2 way diffusers may be adjusted to suit site conditions by changing vanes. The diffusers are constructed from aluminium alloy extrusions fixed or clipped to cross stays. Internal vanes are removable for installation, access or cleaning. A

Waterloo

25 C B

DSL
A

Product Description
DSL DSL-D Ends OBSS ED Large format one way discharge Large format two way discharge End caps Allen key operated opposed blade damper Equalising deflector

35 - 60
25

Features
Ultra low pressure loss characteristics suited to fan coil and induction supply systems Single or multislot to suit most air handling requirements Clean design for practical integration with lighting or ceiling systems Fixed 1 or 2 way pattern to prevent unwanted adjustment of air diffusion

C B

DSL-D

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Weights
0.4N + 0.6 kg/m N = number of slots

Sizes
From 1 to 8 slots wide 1500mm long (excluding ends) Continuous diffuser lengths are supplied in sections for butt jointing on site (Alignment plates supplied)

DSL-D + OBSS + Plenum

Type
DSL-1 DSL-2 DSL-3 DSL-4 DSL-5 DSL-6 DSL-7 DSL-8

A
46 84 122 160 198 237 275 313

B
89 127 165 203 241 279 317 355

C
70 108 146 185 222 260 298 336

Type
DSL-D11 DSL-D12 DSL-D22 DSL-D23 DSL-D33 DSL-D34 DSL-D44

A
84 122 160 198 237 275 313

B
154 192 230 268 306 345 382

67

C
137 175 213 251 289 327 365

Order Example
DSL/3000/S1/PPM9010/ENDS Type Length N of slots Finish End caps

*Please specify number of slots in each direction

Waterloo 2.0

12

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria
From a ceiling height of 3.0m, increase throw by 300mm for each 300mm increase in ceiling height. Horizontal diffusion is based on a cooling differential of 11C NR is sound pressure level based on a room absorption of 8dB. Vr = mean room air velocity (m/s) Vt = terminal velocity of supply air jet (m/s)

Linear Diffusers
DSL DSL-D
Selection Example
DSL/2000/S4
Total air flow rate 400 I/s Air flow rate per metre = 200 l/s/m Minimum throw 6.8m (8.5 x 0.8 factor) Maximum throw 12m (15.0 x 0.8 factor) Pressure drop 13Pa Noise level NR22 (NR25 - 3db length correction)

DSL Exhaust Corrections Pressure Loss Multiply x 2 Noise Level +5 dB

Equalizing Deflector Corrections Diffuser Length (m) Throw Multiplier using ED blades 0.5 0.75 1.0 1.5

Length Corrections Active Length (m) NR Correction Throw Multiplier 0.5 1.25 2.0 2.5 3.0 -8 -5 -3 -2 0 0.45 0.65 0.8 0.9 1.0

0.33 0.42 0.48 0.54

Performance Nomogram
AIR FLOW RATE l/s per m length
700 600 500 400

MAXIMUM RADIUS OF DIFFUSION (Horizontal) Vr = 0.10 m/s (Vt = 0.25 m/s)

NC LEVEL Horizontal diffusion & exhaust air


N OF SLOTS PRESSURE DROP (Pa)

MINIMUM RADIUS OF DIFFUSION (Horizontal) Vr = 0.25 m/s (Vt = 0.85 m/s)


30 20 50 40 10 30 10 5 20

300

200

20

50 20 10 5

100 90 80 70 60 50 40 2 3 5

4 1 5 6 7 8

Pivot Line

30

20

Waterloo 2.0

13

Tel: +44 (0) 1622 711511

Linear Fan Coil Diffusers


FCD1 FCD2
Introduction
The Waterloo linear diffuser series FCD has been developed as an alternative form of continuous air distribution product for fan coil or variable air volume applications. Available with either one or two way core configurations, the blade profile is specifically designed to produce jet throw characteristics with a high induction rate, so prompting rapid mixing and diffusion within the room air. The core sections of the diffusers are retained with quick release spring clips and safety cords to allow easy removal during installation and service access. X Wd

Waterloo

56

FCD1

Product Description
FCD1 FCD2 LH RH Ends One way fan coil diffuser Two way fan coil diffuser Left hand end cap for FCD1 Right hand end cap for FCD1 Pair of end caps 56

X Wd

Features
High induction rate Quick release cores Wide size range Tile replacement units available Nom. L + 12 Y

FCD2

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Nom. L + 30 Nom. L

Weights
See Table

Sizes
150mm to 400mm wide in 50mm increments Single lengths of 500mm up to 1500mm, continuous applications are supplied in 1200mm lengths with alignments strips.

Face View

Left hand end cap

Throw direction (FCD1)

Right hand end cap

Order Example
FCD1/3000x250/PPM9010/ENDS Type Length Width Finish End caps

Nom. Width 150 200 250 300 350 400

Wd 151 201 251 301 351 401

X 160 210 260 310 360 410 164 214 264 314 364 414 186 236 286 336 386 436

Y 194 244 294 344 394 444

FCD1 FCD2 FCD1 FCD2

Weight (Kg/m) 2.3 2.8 3.3 3.8 4.3 4.8

Waterloo 2.0

14

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Linear Fan Coil Diffusers


FCD1 FCD2
The following tabulated data is based on tests with a 1.2m diffuser. Correction factors should be applied to the acoustic and throw data for continuous lengths. Noise data is valid for one or two way throw configurations and is expressed in terms of NR level with a room absorption factor of 8dB. Throws are based on a terminal velocity of 0.5 m/s, corresponding to an average room air velocity (Vr) of 0.25 m/s with a cooling differential of 10C. For isothermal or 10C heating conditions apply a factor of 1.15 to the throws. To avoid draughts in the occupied zone, the selection of diffuser sizes and the resulting throws should be related to the ceiling height. The following table provides a general recommendation for maximum throw selections at various ceiling heights. Throw Recommendations 2.0 2.5 +2 +3 3.0 +5 Ceiling Height (m) Max Throw (m) 2.5 4.0 2.7 5.5 3.0 3.5 4.0 6.5 9.5 12.0

Length Corrections Active Length (m) NR Correction Throw Multiplier 0.5 -4 0.7 1.0 -1 0.8

1.1 1.25 1.5

Performance Tables
FCD
Supply Air Volume per metre Nom. H 1 Way Throw 2 Way Throw 150 1 Way Throw Ps Supply Ps Extract Lp (NR) 200 2 Way Throw Ps Supply Ps Extract Lp (NR)

FCD

Supply Air Volume per metre Nom. H 1 Way Throw 250 2 Way Throw 1 Way Throw 2 Way Throw Ps Supply Ps Extract Lp (NR) 300 Ps Supply Ps Extract Lp (NR)

m3/h/m

l/s/m

m3/h/m

l/s/m

270 360 450 540 630 720 810 900 990

75 100 125 150 175 200 225 250 275

3.0 4.2 5.3 6.5 7.9 9.2

2.1 3.1 4.3 5.5 6.8 7.6

2 4 6 8 11 14

4 7 11 15 20 27

20 25 30 33

3.3 4.4 5.3 6.4 7.4

2.4 3.2 4.1 5.0 6.1

3 4 6 8

6 8 11 15

20 24 28

432 504 576 648 720 810 900 990 1080

120 140 160 180 200 225 250 275 300

3.4 2.5 4.1 2.9 4.8 3.5 5.6 4.1 6.2 4.7 7.2 5.5 7.9 6.4 9.1 7.2 10.0 8.5

2 3 3 4 5 6 7 9 11

3 4 5 6 8 10 12 15 18

20 23 25 28 31 33 35

4.2 4.8 5.4 6.2 7.1 7.8 8.7

2.9 3.4 3.9 4.6 5.4 6.2 7.0

2 4 3 5 20 3 6 23 4 8 26 5 10 29 6 12 31 7 14 33

FCD

Supply Air Volume per metre Nom. H 1 Way Throw 350 2 Way Throw 1 Way Throw 2 Way Throw Ps Supply Ps Extract Lp (NR) 400 Ps Supply Ps Extract 6 7 8 10 11 13 15 Lp (NR) 24 26 28 30 32 33 35

m3/h/m

l/s/m

792 864 936 1008 1080 1170 1260 1350 1440

220 240 260 280 300 325 350 375 400

5.5 3.9 6.0 4.4 6.5 4.8 7.0 5.5 7.8 5.9 8.5 6.8 9.0 7.3 10.0 8.3

3 3 4 4 5 6 7 8

6 7 8 9 11 13 14 16

22 25 27 29 30 32 34 36

6.0 6.5 7.0 7.6 8.7 9.2 9.8

4.3 4.8 5.2 6.0 6.5 7.3 7.9

3 3 4 4 5 6 6

Waterloo 2.0

15

Tel: +44 (0) 1622 711511

Linear Diffusers
Plenum Chambers
Introduction
Correct selection and sizing of distribution plenum chambers and neck reducers is critical because terminal air resistance is very low relative to the distribution ductwork resistance. It is therefore recommended that whenever possible terminals are served by low velocity stub ducts from branch ducting systems fitted with correct balancing controls. Where it is necessary to specify and use plenums a generous allowance for commissioned noise generation should be made. A similar effect results from use of neck reducers with circular duct connections because the reduced duct area will cause generally higher velocities and hence increased risk of noise generation.

Waterloo

High-line plenum chamber

Low-line plenum chamber

Control Options

Product Description
PBHL PBLL SE TE EE CC RC LINED High-line Plenum chamber Low-line Plenum chamber Side Entry spigot Top Entry spigot End Entry spigot Circular connection Rectangular connection 6mm Type O fire rated acoustic lining BAFFLE Perforated plate for more even air flow to diffuser

FDC
Cord operated flap damper for mounting within circular spigots to plenum chambers.

OBCO
Cord operated opposed blade damper for installation within square or rectangular plenum spigots.

Installation
The plenum boxes and neck reducers are supported by 4 drop rods through a locating hole positioned near each corner. When ordering plenum chambers please specify length width & height, spigot size and position (top or side entry) and control options. Please note that the plenum height should in general be 100mm greater that the spigot diameter (side entry applications).

FDQ
Flap damper with external quadrant control for mounting within circular spigots to plenum chambers.

OBSS / ED
Standard opposed blade damper for diffuser or duct mounting

Order Example
PBHL/CSF/1200 x 250 x 250/SE/150/2CC/OBSS/Lined Type Diffuser Type Plenum Chamber Length Plenum Chamber Width Plenum Chamber Height Entry Spigot Size Spigot Connections Option Option

Recommended Max Air Volume for NR35 Based on Recommended Spigot Sizes Diameter 100 125 160 200 250 315 400 l/s 28 42 70 100 165 260

Waterloo 2.0

16

Tel: +44 (0) 1622 711511

Waterloo

Linear Diffusers
Plenum Performance Nomogram
Selection Example
Using the CS example from page 5, we have a diffuser handling 180 l/s total with a pressure drop of 25 Pa. Projecting from this volume through the diffuser pressure loss, then pivot on the plenum dimensions to suit the diffuser 2 slot width, which gives a minimum plenum height of approx 280mm. Draw a line from the air flow selection point through the required spigot air velocity and read off the nearest standard spigot size. In this example the spigot diameter exceeds the selected plenum height, so the height now becomes 315+100 = 415mm. Alternatively, to maintain the original height, select a suitably sized rectangular spigot (300 x 200 in the example) or use multiple circular spigots.

Performance Nomogram
Spigot diameter (mm) Spigot air velocity (m/s) Air flow rate (l/s) Diffuser pressure loss (Pa) Plenum dimensions

1 slot 50

100

100

Pivot Line

125 600 160 500 450 400 350 300 200 250 5 4 250 315 3 2 300 1 350 400 500 450 500 100 90 80 70 60 50 250 7 slot 3 slot 40 2 slot

Standard CS Slot Widths

Pivot Line

Width (mm)

Height (mm)

100

150 200 200

150

100

250 200 150

Example

250

20 10 6 4 2 1 200 5 slot 150 4 slot 200

300 350 400 450 500

400

250

6 slot

300

350

600 700 800 900 1000 Width (mm)

600

300 8 slot

400 450 500

Height (mm)

Spigot Air Velocity Selection Guide m/s NR 2.0 20 2.5 25 3.0 30 3.5 35 4.0 40

350

400 450 500 600

Rectangular or square spigot

600

Waterloo 2.0

17

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE DFA
Introduction
The Waterloo series D multicone diffusers, constructed from aluminium alloy extrusions with mitred and welded/cleated frames, are ideal for most commercial projects requiring high quality diffusers for integration with a variety of ceiling types. The range is available with 5 frame styles and 14 different air pattern control core designs for vertical and horizontal diffusion. Nom. + 75 Nom. - 3 Nom. - 6

Waterloo

DF DF-T8

Flanged horizontal blow diffuser 8mm Drop tegular tile replacement, core 41 only, 375 & 450mm neck sizes DF-T16 16mm drop tegular tile replacement, core 41 only, 375 & 450 square necks DE Recessed frame horizontal blow diffuser DFA Flanged adjustable diffuser for horizontal or vertical projection (4 way only) OBSS Opposed blade damper OBLL Lever operated damper via the diffuser face PBD Plenum box NR/D Top entry neck reducer

Nom. + 145

DF
Nom. + 75 Nom.

5
12

45 Nom. + 74

Five frame styles for integration with most ceilings 14 core styles to suit required air pattern Lightweight aluminium construction Fixed or adjustable patterns Suits 300, 500 ,600 & 1200 ceiling grid systems

DE
Nom. + 38 Nom.

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Weights
DF/DE/DFA OBSS/ED 12.5 kg/m2 face area 9.5 kg/m2 face area Minimum size - 150 x 150 duct size Maximum size - 1200 x 600 duct size 4.8 Nom. + 73

Sizes
Series DF/DE

Series DF-T8/T16 Miniumum size - 375 x 375 duct size (500mm tile replacement) Maximum size - 450 x 450 duct size (600mm tile replacement) Series DFA Minimum size - 150 x 150 duct size Maximum size - 600 x 600 duct size

DFA

Nominal + 2 i/s stack Nominal - 16 o/s damper

Standard increments of 75mm only

Order Example
DF-41/300x300/PPM9010/OBSS
Type Duct width Duct height Finish Damper

DF-T16 Frame 16

DF-T8 Frame 8 OBSS damper Operated by screwdriver after removing core. Suitable for all types DF - T16 and DF - T8

OBLL damper Lever operation at diffuser face. Suitable for core 41 only

Waterloo 2.0

18

Tel: +44 (0) 1622 711511

78

45

Features

60

75

Product Description

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE
DF41/300x300 Ceiling height 2.7 m Temperature differential -10K Air flow rate 225 l/s Radius of diffusion - Minimum and maximum Throw 2.0 - 4.5m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC25 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Selection Example

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Tables

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw

Core 11

DF DE
Supply

Core 21

150 x 150
34 1.5 - 2.5 45 2.0 - 3.5 56 2.0 - 4.5 20 68 2.5 - 5.5 24 79 3.0 - 6.0 28

225 x 225
76 2.0 - 4.0 101 2.5 - 5.5 20 127 3.5 - 6.5 25 152 4.0 - 8.0 29 177 4.5 - 9.0 32

300 x 300
135 2.5 - 5.5 180 3.5 - 6.5 23 225 4.5 - 8.5 28 270 5.0 - 10.5 32 315 6.5 - 12.0 35

375 x 375
211 3.5 - 6.5 282 4.5 - 8.5 25 352 5.5 - 11.0 30 422 6.5 - 13.5 34 492 7.5 - 15.0 37

450 x 450
304 3.5 - 7.0 405 5.5 - 10.0 25 506 6.5 - 13.0 35 608 7.5 - 16.0 35 709 9.0 - 18.0 40

Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw

150 x 150
34 1.0 - 2.0 45 1.0 - 2.5 56 1.5 - 3.0 20 68 2.0 - 3.5 24 79 2.0 - 4.5 28

225 x 225
76 1.5 - 2.5 101 2.0 - 3.5 20 127 2.5 - 5.0 25 152 2.5 - 5.5 29 177 3.0 - 6.0 32

300 x 300
135 2.0 - 3.5 180 2.5 - 5.0 23 225 3.0 - 6.0 28 270 3.5 - 7.5 32 315 4.5 - 8.5 35

375 x 375
211 2.5 - 4.5 282 3.0 - 6.0 25 352 4.0 - 7.5 30 422 5.0 - 9.5 34 492 5.5 - 11.0 37

450 x 450
304 2.5 - 6.0 21 405 3.5 - 7.5 27 506 4.5 - 9.0 32 608 5.5 - 11.0 35 709 6.5 - 13.0 39

15

15

23

23

33

33

43

43

DF DE
Supply
Total pressure drop (Pa)

Core 31

DF DE
L S = Short side throw L = Long side throw

Core 41

Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 150 x 150
34 1.0 - 1.5 45 1.0 - 2.0 56 1.5 - 2.5 68 1.5 - 3.0 79 2.0 - 3.5 19

150 x 150
34 1.0 - 2.0 1.0 - 2.0 45 1.0 - 2.0 1.0 - 2.0 56 1.0 - 2.0 1.5 - 2.5 20 63 1.5 - 2.5 2.0 - 3.5 24 79 2.0 - 3.5 2.0 - 4.0 28

225 x 225
76 1.0 - 2.0 1.0 - 2.5 101 1.0 - 2.5 2.0 - 3.5 20 127 2.0 - 3.5 2.0 - 4.0 25 152 2.0 - 4.5 2.5 - 5.0 29 177 2.5 - 4.5 2.5 - 6.0 32

300 x 300
135 1.5 - 3.0 2.0 - 3.5 180 2.0 - 4.0 2.0 - 4.5 23 225 2.0 - 4.5 2.5 - 5.0 28 270 2.5 - 5.0 3.5 - 6.5 32 315 3.0 - 6.0 4.0 - 7.5 35

375 x 375
211 2.0 - 3.5 2.0 - 4.0 282 2.0 - 4.5 2.5 - 5.0 25 352 2.5 - 5.5 3.5 - 6.0 30 422 3.5 - 6.5 4.0 - 8.0 34 492 4.0 - 7.5 5.0 - 9.5 37

450 x 450
304 2.5 - 5.0 3.5 - 6.5 21 405 2.5 - 5.0 3.5 - 7.0 27 506 3.5 - 6.5 4.0 - 8.0 32 608 4.0 - 8.0 5.0 - 10.0 35 709 4.5 - 9.0 6.0 - 11.5 39

225 x 225
76 1.0 - 2.0 101 1.5 - 2.5 127 2.0 - 3.5 152 2.0 - 4.0 23 177 2.0 - 4.5 27

300 x 300
135 1.5 - 2.5 180 2.0 - 3.5 20 225 2.0 - 4.5 25 270 2.5 - 5.0 29 315 3.0 - 6.0 32

375 x 375
211 2.0 - 3.5 282 2.0 - 4.5 24 352 2.5 - 5.5 29 422 3.5 - 6.5 33 492 4.0 - 7.5 37

450 x 450
304 2.0 - 4.0 22 405 2.5 - 5.0 28 506 3.5 - 6.5 33 608 4.0 - 8.0 36 709 4.5 - 9.0 40

15

23

33

43

l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

15

23

33

43

For our full range of sizes please refer to the following pages

Waterloo 2.0

19

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 11
Selection Criteria

Waterloo
Selection Example DF11/300x300

Ceiling height 2.7 m Air flow rate 225 l/s Temperature differential -10K Throw 4.5 - 8.5m Radius of diffusion - Minimum and maximum Total Pressure Loss 15 Pa throw which results in an average air Noise level NC23 velocity within the occupied zone of 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB Supply diffuser + OBSS + 3dB 8dB room absorption
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 150 x 150
34 1.5 - 2.5 45 2.0 - 3.5 56 2.0 - 4.5 20 68 2.5 - 5.5 24 79 3.0 - 6.0 28

Core 11

225 x 225
76 2.0 - 4.0 101 2.5 - 5.5 20 127 3.5 - 6.5 25 152 4.0 - 8.0 29 177 4.5 - 9.0 32

300 x 300
135 2.5 - 5.5 180 3.5 - 6.5 23 225 4.5 - 8.5 28 270 5.0 - 10.5 32 315 6.5 - 12.0 35

375 x 375
211 3.5 - 6.5 282 4.5 - 8.5 25 352 5.5 - 11.0 30 422 6.5 - 13.5 34 492 7.5 - 15.0 37

450 x 450
304 3.5 - 7.0 405 5.5 - 10.0 25 506 6.5 - 13.0 35 608 7.5 - 16.0 35 709 9.0 - 18.0 40

525 x 525

600 x 600

15

23

33

43

413 540 4.0 - 8.0 4.5 - 8.5 20 20 551 720 5.5 - 10.0 6.0 - 11.0 30 30 689 900 6.5 - 13.0 7.0 - 14.0 35 35 827 1080 7.0 - 14.0 8.5 - 17.0 40 40 964 1260 9.5 - 18.5 10.0 - 19.0 40 45

Waterloo 2.0

20

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE core 12
Selection Example DF12/450x150

Ceiling height 2.7 m Temperature differential -10K Air flow rate 169 l/s Radius of diffusion - Minimum and maximum Throw 4.0 - 8.0m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC25 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 225 x 150
51 2.0 - 3.5 68 2.0 - 4.5 84 2.5 - 5.5 23 101 3.5 - 6.5 27 118 4.0 - 7.5 30

Core 12

300 x 150
67 2.5 - 4.0 90 2.5 - 5.0 20 113 3.0 - 6.0 25 135 4.0 - 7.0 30 158 4.5 - 8.0 35

375 x 150
84 2.5 - 4.5 113 2.7 - 6.0 20 140 3.5 - 7.0 25 169 4.5 - 8.5 30 197 5.5 - 10.0 35

450 x 150
101 3.0 - 5.0 135 3.0 - 7.0 20 169 4.0 - 8.0 25 202 5.0 - 10.0 30 236 6.0 - 11.0 35

525 x 150
118 3.5 - 5.5 20 158 3.5 - 7.5 25 197 4.5 - 9.0 30 236 5.5 - 10.5 35 275 6.5 - 12.0 35

600 x 150
135 4.0 - 6.0 20 180 4.0 - 8.0 25 225 5.0 - 10.0 30 270 6.0 - 11.0 35

300 x 225
101 2.5 - 5.0 135 3.0 - 6.0 25 169 4.0 - 8.0 30 202 4.5 - 9.0 35

375 x 225
127 3.0 - 5.5 169 3.5 - 6.5 25 211 4.5 - 8.5 30 253 5.0 - 9.5 35

450 x 225
153 3.5 - 6.0 203 4.0 - 7.0 25 253

525 x 225
177 4.0 - 7.0 20 237 4.5 - 8.0 25 295

600 x 225
203 4.5 - 8.0 20 271 5.0 - 9.0 25 337 6.0 - 12.0 30 404 7.0 - 14.0 35

15

23

33

5.0 - 9.0 5.5 - 10.0 30 30 303 354 5.5 - 10.0 6.0 - 12.0 35 35

43

236 295 315 7.0 - 13.0 5.0 - 10.5 5.5 - 11.0 35 35 35

354 413 472 6.0 - 11.5 7.0 - 15.0 8.0 - 16.0 35 40 40

Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw

375 x 300

450 x 300

525 x 300
236 3.5 - 7.0 315 5.0 - 10.0 25 394 6.0 - 12.0 30 473 7.0 - 15.0 35 551 8.0 - 16.0 40

600 x 300
271 4.0 - 8.0 360 6.0 - 11.0 25 441 7.0 - 13.0 30 540 8.0 - 16.0 35 630 9.0 - 18.0 40

450 x 375
253 3.0 - 6.5 338 4.5 - 9.0 25 422 5.5 - 11.0 30 506 6.5 - 13.0 35 590 7.5 - 15.0 40

525 x 375

600 x 375

525 x 450
354 3.0 - 7.0 472 5.0 - 9.5 30 591 6.0 - 12.0 35 709 7.0 - 14.5 40 827 8.5 - 16.0 40

600 x 450

600 x 525

15

23

33

43

169 203 2.5 - 6.0 3.0 - 6.5 225 270 4.0 - 8.0 4.5 - 9.0 24 25 281 338 5.0 - 10.0 5.5 - 11.0 29 30 338 405 6.0 - 12.0 6.5 - 13.0 33 35 394 473 7.0 - 13.5 7.5 - 15.0 36 40

296 339 3.5 - 7.0 4.0 - 8.0 394 450 5.0 - 10.0 6.0 - 11.0 30 25 492 562 6.0 - 12.0 7.0 - 13.0 35 30 591 674 7.0 - 14.0 8.0 - 16.0 40 35 689 788 8.0 - 16.0 9.0 - 18.0 40 40

406 474 4.0 - 8.0 3.0 - 8.5 540 629 6.0 - 11.0 6.0 - 11.0 30 30 675 785 7.0 - 13.0 7.0 - 14.0 35 35 810 942 8.0 - 16.0 9.0 - 18.0 40 40 945 1103 9.0 - 18.0 10.0 - 20.0 40 40

Waterloo 2.0

21

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 13
Selection Criteria

Waterloo
Selection Example DF13/450x150

Ceiling height 2.7 m Temperature differential -10K Air flow rate 169 l/s Radius of diffusion - Minimum and maximum Throw 4.0 - 7.5m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC27 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 225 x 150
51 2.0 - 3.5 68 2.0 - 4.5 84 2.5 - 5.5 23 101 3.5 - 6.5 27 118 4.0 - 7.5 30

Core 13

300 x 150
67 2.0 - 3.5 90 2.5 - 5.0 20 113 3.0 - 6.0 24 135 4.0 - 7.5 28 158 4.5 - 8.5 32

375 x 150
84 2.0 - 4.0 113 2.5 - 6.0 20 140 3.5 - 6.5 26 169 4.0 - 8.0 29 197 5.0 - 10.0 33

450 x 150
101 2.5 - 5.0 135 3.0 - 6.0 22 169 4.0 - 7.5 27 202 4.5 - 9.0 30 236 5.0 - 10.5 34

525 x 150
118 3.0 - 5.5 20 158 3.5 - 7.0 25 197 4.5 - 8.0 30 236 5.0 - 11.0 35 275 6.0 - 12.0 35

600 x 150
135 4.0 - 6.0 20 180 4.5 - 9.0 25 225 5.0 - 10.0 30 270 6.0 - 12.0 35

300 x 225
101 2.5 - 5.0 135 3.0 - 6.0 22 169 4.0 - 7.5 27 202 4.5 - 9.0 30

375 x 225
127 2.5 - 5.5 169 3.5 - 6.5 22 211 4.5 - 8.5 27 253 5.0 - 10.0 32

450 x 225
153 3.0 - 6.0 203 4.0 - 7.0 25 253

525 x 225
177 3.5 - 6.5 237 4.5 - 8.0 24 295

600 x 225
203 4.0 - 7.0 271 5.0 - 9.0 25 337 6.0 - 12.0 30 404 7.0 - 14.0 35

15

23

33

5.0 - 10.0 5.5 - 11.0 30 29 303 354 5.5 - 11.0 6.0 - 12.0 35 33

43

236 295 315 7.0 - 15.0 5.0 - 10.5 6.0 - 12.0 34 35 35

354 413 472 6.5 - 13.0 7.0 - 14.0 8.0 - 16.0 35 37 35

Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw

375 x 300

450 x 300

525 x 300
236 4.0 - 7.0 20 315 5.0 - 9.0 26 394 5.5 - 11.5 30 473 7.0 - 14.0 34 551 8.0 - 16.0 37

600 x 300
271 4.5 - 7.5 360 5.5 - 10.0 25 441 6.0 - 12.0 30 540 7.5 - 15.0 35 630 9.0 - 18.0 40

450 x 375
253 3.0 - 6.5 338 4.5 - 9.0 25 422 5.5 - 11.0 30 506 6.5 - 13.0 35 590 7.5 - 15.0 40

525 x 375

600 x 375

525 x 450
354 3.5 - 7.5 472 5.0 - 10.0 30 591 6.5 - 12.5 35 709 7.5 - 15.0 40 827 9.0 - 16.5 40

600 x 450

600 x 525

15

23

33

43

169 203 2.5 - 6.0 3.5 - 6.5 225 270 4.0 - 8.0 4.5 - 8.5 24 25 281 338 5.0 - 10.0 5.0 - 10.5 29 30 338 405 6.0 - 11.5 6.5 - 13.0 33 34 394 473 7.0 - 13.5 7.5 - 15.0 36 36

296 339 3.5 - 7.0 4.0 - 7.5 394 450 5.0 - 10.0 5.5 - 11.0 25 25 492 562 6.0 - 12.0 6.5 - 13.0 30 30 591 674 7.0 - 14.0 7.5 - 15.0 35 35 689 788 8.0 - 16.0 9.0 - 17.0 40 40

406 474 4.0 - 8.0 3.0 - 8.5 20 540 629 6.0 - 11.0 6.0 - 11.0 30 30 675 785 7.0 - 13.0 7.0 - 14.0 35 35 810 942 8.0 - 16.0 8.5 - 17.5 40 40 945 1103 9.5 - 18.0 10.0 - 20.0 40 40

Waterloo 2.0

22

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE core 21
Selection Example DF21/300x300

Ceiling height 2.7 m Temperature differential -10K Air flow rate 225 l/s Radius of diffusion - Minimum and maximum Throw 3.0 - 6.0m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC28 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 150 x 150
34 1.0 - 2.0 45 1.0 - 2.5 56 1.5 - 3.0 20 68 2.0 - 3.5 24 79 2.0 - 4.5 28

Core 21

225 x 225
76 1.5 - 2.5 101 2.0 - 3.5 20 127 2.5 - 5.0 25 152 2.5 - 5.5 29 177 3.0 - 6.0 32

300 x 300
135 2.0 - 3.5 180 2.5 - 5.0 23 225 3.0 - 6.0 28 270 3.5 - 7.5 32 315 4.5 - 8.5 35

375 x 375
211 2.5 - 4.5 282 3.0 - 6.0 25 352 4.0 - 7.5 30 422 5.0 - 9.5 34 492 5.5 - 11.0 37

450 x 450

525 x 525

600 x 600

15

23

33

43

304 413 540 2.5 - 6.0 3.0 - 6.5 3.5 - 7.0 21 25 25 405 551 720 3.5 - 7.5 4.0 - 8.0 4.5 - 8.5 27 30 30 506 689 900 4.5 - 9.0 5.0 - 10.0 5.5 - 10.5 32 35 35 827 1080 608 5.5 - 11.0 6.5 - 13.0 6.5 - 13.0 40 40 35 964 1260 709 6.5 - 13.0 7.5 - 15.0 7.5 - 15.0 40 40 39

Waterloo 2.0

23

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 22
Selection Criteria

Waterloo
Selection Example DF22/450x150

Ceiling height 2.7 m Temperature differential -10K Air flow rate 169 l/s Radius of diffusion - Minimum and maximum Throw 3.0 - 5.5m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC27 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 225 x 150
51 1.0 - 2.5 68 1.5 - 3.0 84 2.0 - 3.5 23 101 2.0 - 4.5 27 118 2.5 - 5.0 30

Core 22

300 x 150
67 1.5 - 2.5 90 2.0 - 3.5 113 2.0 - 4.5 24 135 2.5 - 5.0 28 158 3.0 - 6.0 32

375 x 150
84 1.5 - 3.0 113 2.5 - 4.0 140 2.5 - 5.0 25 169 3.0 - 5.0 28 197 3.5 - 6.5 30

450 x 150
101 2.0 - 3.0 135 3.0 - 4.5 20 169 3.0 - 5.5 27 202 3.5 - 6.0 30 236 4.0 - 7.0 35

525 x 150
118 2.5 - 3.5 158 3.5 - 5.0 20 197 3.5 - 6.0 30 236 4.0 - 6.5 30 275 4.5 - 8.0 35

600 x 150
135 3.0 - 4.0 180 4.0 - 5.5 20 225 4.0 - 7.0 30 270 4.5 - 8.0 30 315 5.0 - 9.0 35

300 x 225
101 2.0 - 3.5 135 2.0 - 4.5 22 169 2.5 - 5.0 27 202 3.5 - 6.5 30 236 4.0 - 7.5 34

375 x 225
127 2.0 - 3.5 169 2.5 - 5.0 22 211 3.0 - 6.0 27 253 3.5 - 7.5 32 295 4.5 - 8.5 35

450 x 225
153 2.5 - 4.0 203 3.0 - 5.5 25 253 3.5 - 6.5 30 303 4.0 - 8.0 35 354 5.0 - 9.0 40

525 x 225
177 3.0 - 4.5 237 3.5 - 6.0 25 295 4.0 - 7.0 30 354 4.5 - 9.0 35

600 x 225
203 3.5 - 5.0 20 271 4.0 - 6.5 25 337 4.5 - 8.0 30 404 5.0 - 10.0 35

15

23

33

43

413 472 5.5 - 10.0 6.0 - 11.0 40 40

Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw

375 x 300
169 2.0 - 4.0 225 2.5 - 5.5 24 281 3.5 - 7.0 29 338 4.0 - 8.0 33 394 5.0 - 9.5 36

450 x 300
203 2.5 - 4.5 270 3.0 - 6.0 25 338 4.0 - 7.5 30 405 4.5 - 9.0 35 473 5.5 - 10.0 40

525 x 300
236 3.5 - 5.0 315 3.5 - 6.5 25 394 4.5 - 8.0 30 473 5.0 - 10.0 35 551 6.0 - 12.0 40

600 x 300
271 3.5 - 5.5 360 4.0 - 7.0 30 441 5.0 - 9.0 35 540 6.0 - 12.0 40 630 7.0 - 14.0 40

450 x 375

525 x 375

600 x 375

525 x 450

600 x 450

600 x 525

15

23

33

43

253 296 339 2.5 - 5.0 3.0 - 5.5 3.5 - 6.0 20 394 450 338 3.5 - 7.0 4.0 - 8.0 3.0 - 6.5 25 30 25 492 562 422 4.5 - 9.0 5.0 - 10.0 4.0 - 8.5 30 35 30 591 674 506 5.0 - 9.5 5.5 - 10.0 6.0 - 11.0 35 35 35 689 788 590 6.0 - 11.0 6.5 - 12.0 7.0 - 13.0 40 40 40

354 406 474 2.5 - 5.0 3.0 - 5.5 4.0 - 6.0 20 20 472 540 629 3.0 - 6.5 4.0 - 7.0 5.0 - 8.0 30 30 30 591 675 785 4.0 - 8.5 5.0 - 9.0 5.5 - 10.0 35 35 35 709 810 942 5.0 - 9.5 6.0 - 11.0 6.5 - 12.0 40 40 40 827 945 1103 6.0 - 11.5 7.0 - 13.0 8.0 - 14.0 40 40 40

Waterloo 2.0

24

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE core 23
Selection Example DF23/450x150

Ceiling height 2.7 m Temperature differential -10K Air flow rate 169 l/s Radius of diffusion - Minimum and maximum Throw 3.0 - 5.5m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC27 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 225 x 150
51 1.0 - 2.5 68 1.5 - 3.0 84 2.0 - 3.5 23 101 2.0 - 4.5 27 118 2.5 - 5.0 30

Core 23

300 x 150
67 1.5 - 2.5 90 2.0 - 3.5 113 2.0 - 4.5 24 135 2.5 - 5.0 28 158 3.0 - 6.0 32

375 x 150
84 1.5 - 3.0 113 2.0 - 4.0 20 140 2.5 - 5.0 26 169 3.0 - 6.0 29 197 3.5 - 7.0 33

450 x 150
101 2.0 - 3.5 135 2.5 - 4.5 22 169 3.0 - 5.5 27 202 3.5 - 6.5 30 236 4.0 - 7.5 34

525 x 150
118 2.5 - 4.0 158 3.0 - 5.0 20 197 3.5 - 6.0 30 236 4.0 - 7.0 30 275 4.5 - 8.0 35

600 x 150
135 3.0 - 5.0 180 3.5 - 6.0 20 225 4.0 - 7.0 30 270 4.5 - 8.0 30 315 5.0 - 9.0 35

300 x 225
101 2.0 - 3.5 135 2.0 - 4.5 22 169 2.5 - 5.5 27 202 3.5 - 6.5 30 236 4.0 - 7.5 34

375 x 225
127 2.0 - 4.0 169 2.5 - 5.0 22 211 3.0 - 6.0 27 253 3.5 - 7.5 32 295 4.0 - 8.5 35

450 x 225
153 2.5 - 4.0 203 3.0 - 5.5 25 253 3.5 - 6.5 30 303 4.0 - 8.0 35 354 5.0 - 9.0 40

525 x 225
177 3.0 - 4.5 237 3.5 - 6.0 24 295 3.5 - 7.5 29 354 4.5 - 8.5 33

600 x 225
203 3.5 - 5.0 20 271 4.0 - 7.0 30 337 4.5 - 9.0 35 404 5.5 - 110 40

15

23

33

43

413 472 5.0 - 10.0 7.0 - 13.0 37 40

Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw

375 x 300
169 2.0 - 4.0 225 2.5 - 6.0 24 281 3.5 - 7.0 29 338 4.0 - 8.0 33 394 5.0 - 9.5 36

450 x 300
203 2.0 - 4.5 270 3.0 - 6.0 25 338 4.0 - 8.0 30 405 4.5 - 9.0 23 473 5.5 - 10.5 37

525 x 300
236 2.5 - 5.0 20 315 3.5 - 6.5 26 394 4.5 - 9.0 30 473 5.0 - 10.0 34 551 6.0 - 12.0 37

600 x 300
271 3.0 - 6.0 20 360 4.0 - 7.0 30 441 5.0 - 10.0 35 540 5.5 - 12.0 40 630 7.0 - 14.0 40

450 x 375

525 x 375

600 x 375

525 x 450

600 x 450

600 x 525

15

23

33

43

253 296 339 2.5 - 5.0 3.0 - 6.0 3.5 - 6.5 20 20 394 450 338 4.0 - 7.0 4.5 - 8.0 3.5 - 6.5 25 30 26 492 562 422 5.0 - 9.0 5.5 - 10.0 4.5 - 8.5 30 35 31 591 674 506 5.0 - 10.0 5.5 - 11.0 6.0 - 12.0 35 35 35 689 788 590 6.0 - 12.0 7.0 - 13.0 7.5 - 14.0 40 40 38

354 406 474 2.5 - 5.0 3.0 - 5.5 3.0 - 5.5 20 20 472 540 629 3.0 - 6.5 3.5 - 7.0 4.0 - 8.0 30 30 30 591 675 785 4.0 - 8.5 4.5 - 9.0 5.0 - 10.0 35 35 35 709 810 942 5.0 - 9.5 5.5 - 10.0 6.0 - 11.0 40 40 40 827 945 1103 6.0 - 12.0 7.0 - 13.0 7.0 - 14.0 40 40 40

Waterloo 2.0

25

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 25
Selection Criteria

Waterloo
Selection Example DF25/300x300

Ceiling height 2.7 m Temperature differential -10K Air flow rate 225 l/s Radius of diffusion - Minimum and maximum Throw 3.0 - 6.0m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC28 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 150 x 150
34 1.0 - 2.0 45 1.0 - 2.5 56 1.5 - 3.0 20 68 2.0 - 3.5 24 79 2.0 - 4.5 28

Core 25

225 x 225
76 1.5 - 2.5 101 2.0 - 3.5 20 127 2.5 - 5.0 25 152 2.5 - 5.5 29 177 3.0 - 6.0 32

300 x 300
135 2.0 - 3.5 180 2.5 - 5.0 23 225 3.0 - 6.0 28 270 3.5 - 7.5 32 315 4.5 - 8.5 35

375 x 375
211 2.5 - 4.5 282 3.0 - 6.0 25 352 4.0 - 7.5 30 422 5.0 - 9.5 34 492 5.5 - 11.0 37

450 x 450

525 x 525

600 x 600

15

23

33

43

304 413 540 2.5 - 6.0 3.0 - 6.5 3.0 - 7.0 21 25 25 405 551 720 3.5 - 7.5 4.0 - 8.0 4.0 - 9.0 27 30 30 506 689 900 4.5 - 9.0 5.0 - 10.0 5.0 - 11.0 32 35 35 827 1080 608 5.5 - 11.0 6.0 - 12.0 6.0 - 13.0 40 40 35 964 1260 709 6.5 - 13.0 7.0 - 14.0 7.0 - 15.0 40 40 39

Waterloo 2.0

26

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE core 26 & 27
Ceiling height 2.7 m Air flow rate 169 l/s Temperature differential -10K Short side throw 2.5 - 4.0m Radius of diffusion - Minimum and maximum Long side throw 3.5 - 6.5m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC30 0.25m/s and 0.10m/s respectively. NC level = peak level on noise criteria Exhaust & OBSS corrections curves based on Sound Power Level less 8dB room absorption Supply diffuser + 0dB
Supply diffuser + OBSS Exhaust diffuser Exhaust diffuser + OBSS
L L

Selection Example DF26/450x150

Performance Table

+ 3dB + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

DF DE
Supply
Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw 225 x 150
51 1.0 - 2.0 1.5 - 2.5 68 1.0 - 2.5 2.0 - 3.5 84 2.0 - 3.5 2.0 - 4.5 23 101 2.0 - 4.0 2.5 - 5.0 27 118 2.0 - 4.5 3.0 - 6.0 30

Core 26
Viewed from face

Core 27
600 x 150
135 2.5 - 3.5 3.0 - 5.5 20 180 2.5 - 3.5 3.5 - 6.5 25 225 3.5 - 5.0 4.0 - 8.0 30 270 3.5 - 5.5 5.5 - 9.5 35 315 3.5 - 6.0 6.0 - 11.0 35

S
Viewed from face

S = Short side throw L = Long side throw

300 x 150
67 1.0 - 2.0 2.0 - 3.5 90 1.0 - 2.5 2.0 - 4.5 113 2.0 - 3.5 2.5 - 5.0 24 135 2.0 - 4.0 3.5 - 6.5 28 158 2.0 - 4.5 4.0 - 7.5 32

375 x 150
84 1.0 - 2.0 2.0 - 4.0 113 1.0 - 2.5 2.5 - 5.0 20 140 2.0 - 3.5 3.0 - 6.0 26 169 2.0 - 4.0 4.0 - 7.5 29 197 2.0 - 4.5 4.5 - 8.5 33

450 x 150
101 1.5 - 2.5 2.5 - 4.5 135 1.5 - 3.0 3.0 - 5.5 20 169 2.5 - 4.0 3.5 - 6.5 30 202 2.5 - 4.5 4.5 - 8.0 30 236 2.5 - 5.0 5.0 - 9.0 35

525 x 150
118 2.0 - 3.0 2.5 - 5.0 158 2.0 - 3.5 3.0 - 6.0 25 197 3.0 - 4.5 4.0 - 7.0 30 236 3.5 - 5.0 5.0 - 8.0 30 275 3.0 - 5.5 5.5 - 10.0 35

300 x 225
101 1.5 - 3.0 2.0 - 4.0 135 2.0 - 4.0 2.5 - 5.0 22 169 2.5 - 5.0 2.5 - 6.0 27 202 2.5 - 6.0 3.5 - 7.5 30 236 3.5 - 6.5 4.5 - 8.0 34

375 x 225
127 2.0 - 3.5 2.5 - 4.5 169 2.5 - 4.5 3.0 - 5.5 25 211 3.0 - 5.5 3.0 - 6.5 30 253 3.0 - 6.5 4.0 - 8.0 30 295 4.0 - 7.0 5.0 - 9.0 35

450 x 225
153 2.5 - 4.0 3.0 - 5.0 203 3.0 - 5.0 3.5 - 6.0 25 253 3.5 - 6.0 3.5 - 7.0 30 303 3.5 - 7.0 4.5 - 9.0 35 354 4.5 - 8.0 5.5 - 9.0 35

525 x 225
177 3.0 - 4.0 3.5 - 5.5 20 237 3.0 - 5.5 4.0 - 7.0 25 295 4.0 - 7.0 4.0 - 8.0 30 354 4.0 - 8.0 5.0 - 10.0 35 413

600 x 225
203 3.0 - 5.0 3.5 - 6.0 20 271 3.0 - 6.0 3.5 - 7.0 25 337 4.0 - 8.0 4.5 - 9.0 30 404 4.5 - 9.0 5.5 - 11.0 35 472

15

23

33

43

5.0 - 9.0 5.5 - 10.0 6.0 - 11.0 7.0 - 12.0 40 40

Total pressure drop (Pa)

375 x 300

450 x 300

525 x 300

600 x 300
271 2.5 - 5.0 3.0 - 6.0 20 360 3.0 - 6.0 4.5 - 8.5 25 441 4.0 - 7.0 5.5 - 11.0 30 540 5.0 - 9.0 6.0 - 12.0 35 630 6.0 - 12.0 8.0 - 15.0 40

450 x 375
253 2.5 - 4.5 3.0 - 5.5 338 3.0 - 5.5 4.0 - 7.5

525 x 375
296 2.5 - 5.0 3.0 - 6.0 20 394 3.0 - 6.0 4.5 - 8.0

600 x 375
339 3.0 - 6.0 3.5 - 6.5 20 450 3.5 - 7.0 5.0 - 8.5 25 562 5.0 - 8.0 6.5 - 12.0 30 674 6.0 - 10.0 7.0 - 14.0 35

15

23

33

43

l/s 169 203 236 S Min - Max (m) 2.0 - 4.0 2.0 - 4.0 2.5 - 4.5 L Min - Max (m) 2.5 - 5.0 2.5 - 5.0 3.0 - 5.5 Lw l/s 225 270 315 S Min - Max (m) 2.5 - 5.0 2.5 - 5.0 3.0 - 5.5 L Min - Max (m) 3.0 - 6.0 3.5 - 7.5 4.0 - 7.5 Lw 24 25 25 l/s 281 338 394 S Min - Max (m) 3.0 - 6.0 3.0 - 6.0 3.5 - 6.5 L Min - Max (m) 4.5 - 7.0 4.5 - 9.0 5.0 - 10.0 Lw 29 30 30 l/s 338 405 473 S Min - Max (m) 4.0 - 7.5 4.0 - 7.5 4.5 - 8.5 L Min - Max (m) 4.5 - 9.0 5.0 - 10.5 5.5 - 11.5 Lw 33 33 35 l/s 394 473 551 S Min - Max (m) 4.5 - 8.5 4.5 - 8.5 5.0 - 9.5 L Min - Max (m) 5.0 - 10.5 6.0 - 12.0 6.5 - 13.0 Lw 36 37 40

25 25 422 492 3.5 - 6.5 4.0 - 7.0 5.0 - 10.0 6.0 - 11.0 30 30 506 591 4.5 - 8.5 5.0 - 9.0 5.5 - 11.5 6.0 - 13.0 35 35

590 689 788 5.0 - 9.5 6.0 - 11.0 7.0 - 12.0 6.5 - 13.0 7.0 - 15.0 8.0 - 16.0 40 40 40

Waterloo 2.0

27

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 31
Selection Criteria

Waterloo
Selection Example DF31/300x300

Ceiling height 2.7 m Temperature differential -10K Air flow rate 225 l/s Radius of diffusion - Minimum and maximum Short side throw 2.0 - 4.5m throw which results in an average air Long side throw 2.5 - 5.0m velocity within the occupied zone of Total Pressure Loss 23 Pa 0.25m/s and 0.10m/s respectively. Noise level NC28 NC level = peak level on noise criteria Exhaust & OBSS corrections curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption
Supply diffuser + OBSS Exhaust diffuser Exhaust diffuser + OBSS + 3dB + 3dB +13dB

Performance Table

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

DF DE
Core 31 Supply
Total pressure drop (Pa) 150 x 150
34 1.0 - 2.0 1.0 - 2.0 45 1.0 - 2.0 1.0 - 2.0 56 1.0 - 2.0 1.5 - 2.5 20 63 1.5 - 2.5 2.0 - 3.5 24 79 2.0 - 3.5 2.0 - 4.0 28

S L L S = Short side throw L = Long side throw

225 x 225
76 1.0 - 2.0 1.0 - 2.5 101 1.0 - 2.5 2.0 - 3.5 20 127 2.0 - 3.5 2.0 - 4.0 25 152 2.0 - 4.5 2.5 - 5.0 29 177 2.5 - 4.5 2.5 - 6.0 32

300 x 300
135 1.5 - 3.0 2.0 - 3.5 180 2.0 - 4.0 2.0 - 4.5 23 225 2.0 - 4.5 2.5 - 5.0 28 270 2.5 - 5.0 3.5 - 6.5 32 315 3.0 - 6.0 4.0 - 7.5 35

375 x 375
211 2.0 - 3.5 2.0 - 4.0 282 2.0 - 4.5 2.5 - 5.0 25 352 2.5 - 5.5 3.5 - 6.0 30 422 3.5 - 6.5 4.0 - 8.0 34 492 4.0 - 7.5 5.0 - 9.5 37

450 x 450
304 2.5 - 5.0 3.5 - 6.5 21 405 2.5 - 5.0

525 x 525
413 3.5 - 7.0 4.5 - 9.0 25 551 3.5 - 7.0

600 x 600
540 4.0 - 8.0 5.5 - 10.0 30 720 4.0 - 8.0 5.5 - 10.0 35 900 5.0 - 8.0 5.0 - 10.0 40 1080 5.0 - 10.0 6.0 - 12.0 40 1260 6.0 - 12.0 7.0 - 14.0 45

15

23

33

43

l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

3.5 - 7.0 5.0 - 9.5 27 30 506 689 3.5 - 6.5 4.0 - 7.0 4.0 - 8.0 5.5 - 9.0 32 35 608 827 4.0 - 8.0 4.5 - 9.0 5.0 - 10.0 5.5 - 11.0 35 40 709 964 4.5 - 9.0 5.0 - 10.0 6.0 - 11.5 6.5 - 12.0 39 45

Waterloo 2.0

28

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE core 32
Selection Example DF32/450x150

Ceiling height 2.7 m Temperature differential -10K Air flow rate 169 l/s Radius of diffusion - Minimum and maximum Short side throw 1.5 - 3.0m throw which results in an average air Short side throw 3.0 - 6.0m velocity within the occupied zone of Total Pressure Loss 23 Pa 0.25m/s and 0.10m/s respectively. Noise level NC27 NC level = peak level on noise criteria Exhaust & OBSS corrections curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption

Performance Table

Supply diffuser + OBSS Exhaust diffuser Exhaust diffuser + OBSS


L

+ 3dB + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

DF DE
Supply
Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw 225 x 150
51 1.0 - 2.0 1.0 - 2.0 68 1.0 - 2.0 1.0 - 2.5 84 1.5 - 3.0 2.0 - 3.5 23 101 2.0 - 3.5 2.0 - 4.0 27 118 2.0 - 4.5 2.5 - 4.5 30

Core 32
300 x 150
67 1.0 - 2.0 1.5 - 2.5 90 1.0 - 2.0 2.0 - 3.5 113 1.5 - 3.0 2.0 - 4.5 24 135 2.0 - 3.5 2.5 - 5.0 28 158 2.0 - 4.5 3.0 - 6.0 32

S S = Short side throw L = Long side throw

375 x 150
84 1.0 - 2.0 2.0 - 3.5 113 1.0 - 2.0 2.0 - 4.5 20 140 1.5 - 3.0 2.5 - 5.0 26 169 2.0 - 3.5 3.5 - 6.5 29 197 2.0 - 4.5 4.0 - 7.5 33

450 x 150
101 1.0 - 2.0 2.0 - 3.5 135 1.0 - 2.0 2.5 - 5.0 22 169 1.5 - 3.0 3.0 - 6.0 27 202 2.0 - 3.5 4.0 - 7.5 30 236 2.0 - 4.5 4.5 - 8.5 34

525 x 150
118 1.5 - 2.5 2.5 - 4.0 158 1.5 - 2.5 3.0 - 5.5 25 197 1.5 - 3.5 3.5 - 6.5 30 236 2.5 - 4.0 4.5 - 8.5 30 275 2.5 - 5.5 5.0 - 9.5 35

600 x 150
135 2.0 - 4.0 3.0 - 4.5 180 2.0 - 3.0 3.5 - 6.0 25 225 2.0 - 4.0 4.0 - 7.0 30 270 3.0 - 4.5 5.0 - 9.0 35 315 3.0 - 6.0 5.5 - 11.0 35

300 x 225
101 1.5 - 3.0 1.5 - 3.0 135 2.0 - 4.0 2.0 - 4.0 22 169 2.0 - 4.5 2.0 - 4.5 27 202 2.5 - 5.0 2.5 - 5.0 30 236 3.0 - 6.0 3.0 - 6.0 34

375 x 225
127 2.0 - 3.0 2.0 - 3.5 169 2.5 - 3.5 2.0 - 4.5 22 211 2.0 - 4.0 2.5 - 5.5 27 253 2.5 - 5.0 3.5 - 6.5 32 295 3.5 - 6.5 4.0 - 8.0 35

450 x 225
153 2.5 - 4.0 2.5 - 4.0 203 3.0 - 4.0 2.5 - 5.0 25 253 2.5 - 5.0 3.0 - 6.0 30 303 3.5 - 6.0 4.0 - 7.0 35 354 4.0 - 7.0 4.5 - 9.0 35

525 x 225
177 3.0 - 5.0 2.5 - 5.0 237 3.5 - 5.0 3.0 - 6.0 24 295 3.0 - 6.0 3.5 - 7.0 29 354 3.5 - 7.0 4.5 - 9.0 33 413

600 x 225
203 3.0 - 6.0 3.0 - 6.0 271 4.0 - 5.5 3.5 - 6.5 25 337 3.5 - 7.0 4.0 - 9.0 30 404 4.0 - 8.0 5.0 - 10.0 35 472

15

23

33

43

5.0 - 8.0 5.5 - 9.0 5.0 - 10.0 5.5 - 12.0 40 37

Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

375 x 300
169 2.0 - 3.5 2.0 - 3.5 225 2.0 - 4.5 2.5 - 5.0 24 281 2.5 - 5.5 2.5 - 6.0 29 338 3.5 - 6.5 3.5 - 7.5 33 394 4.0 - 7.5 4.0 - 8.0 36

450 x 300
203 2.0 - 3.5 2.0 - 4.0 270 2.5 - 5.0 2.5 - 5.0 25 338 2.5 - 6.0 3.5 - 6.5 30 405 3.5 - 7.5 4.0 - 8.0 33 473 4.0 - 8.0 4.5 - 9.0 37

525 x 300
236 2.5 - 4.0 2.5 - 4.5 315 3.0 - 5.5 3.0 - 5.5 25 394 3.0 - 6.5 4.0 - 7.0 30 473 4.0 - 8.0 4.5 - 8.5 35 551 4.5 - 8.5 5.0 - 9.5 40

600 x 300
271 3.0 - 4.5 3.0 - 5.0 20 360 3.5 - 6.0 3.5 - 6.0 30 441 3.5 - 7.0 4.5 - 7.5 35 540 4.5 - 8.5 5.0 - 9.0 35 630 5.0 - 9.0 5.5 - 10.0 40

450 x 375
253 2.0 - 4.0 2.0 - 4.5 20 338 2.5 - 5.0 2.5 - 5.5 25 422 3.5 - 6.5 3.5 - 7.5 31 506 4.0 - 8.0 4.5 - 8.5 35

525 x 375
296 2.5 - 4.5 2.5 - 5.0 20 394 3.0 - 5.5 3.0 - 6.0 30 492 4.0 - 7.0 4.0 - 8.0 35 591 4.5 - 9.0 5.0 - 9.0 35

600 x 375
339 3.0 - 5.0 3.0 - 6.0 25 450 3.5 - 6.0 3.5 - 6.5 35 562 4.5 - 7.5 4.5 - 8.5 40 674 5.0 - 9.5 5.5 - 10.0 40

525 x 450
354 2.5 - 5.0 2.5 - 5.0 22 472 3.0 - 6.0 3.5 - 6.5

600 x 450
406 3.0 - 5.5 3.0 - 5.5 25 540 3.5 - 6.5 4.0 - 7.0

600 x 525
474 3.0 - 5.5 3.0 - 5.5 25 629 3.5 - 6.5 4.0 - 7.0 30 785 4.5 - 8.0 5.0 - 9.0 35 942 5.0 - 9.5 5.5 - 10.5 40

15

23

33

28 30 591 675 4.0 - 7.5 4.5 - 8.0 4.5 - 8.5 5.0 - 9.0 32 35 709 810 4.5 - 9.0 5.0 - 10.0 5.0 - 10.0 5.5 - 11.0 37 40

43

590 689 788 4.5 - 9.0 5.0 - 10.0 5.5 - 11.0 5.0 - 10.0 5.5 - 11.0 6.0 - 12.0 38 40 45

945 1103 827 5.5 - 11.0 6.0 - 12.0 6.0 - 11.5 6.0 - 12.0 6.5 - 13.0 6.5 - 12.5 40 40 40

Waterloo 2.0

29

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 33
Selection Criteria

Waterloo
Selection Example DF33/450x150

Ceiling height 2.7 m Air flow rate 169 l/s Temperature differential -10K Short side throw 2.0 - 3.0m Radius of diffusion - Minimum and maximum Long side throw 3.0 - 5.0m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC30 0.25m/s and 0.10m/s respectively. NC level = peak level on noise criteria Exhaust & OBSS corrections curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption
Supply diffuser + OBSS Exhaust diffuser Exhaust diffuser + OBSS
L

Performance Table

+ 3dB + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

DF DE
Supply

Core 33

S S = Short side throw L = Long side throw

Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

225 x 150
51 1.0 - 1.5 1.0 - 2.0 68 1.0 - 2.0 1.5 - 2.5 84 1.0 - 2.5 2.0 - 3.5 23 101 1.5 - 2.5 2.0 - 4.5 27 118 1.5 - 3.0 2.5 - 5.0 30

300 x 150
67 1.0 - 1.5 1.5 - 2.5 90 1.0 - 2.0 2.0 - 3.5 113 1.5 - 2.5 2.0 - 4.5 24 135 1.5 - 2.5 2.5 - 5.0 28 158 1.5 - 3.0 2.5 - 6.0 32

375 x 150
84 1.0 - 1.5 1.5 - 2.5 113 1.0 - 2.0 2.0 - 3.5 20 140 1.5 - 2.5 2.5 - 4.5 26 169 1.5 - 2.5 2.5 - 5.5 29 197 1.5 - 3.0 3.5 - 6.5 33

450 x 150
101 1.5 - 2.0 2.0 - 3.0 135 1.5 - 2.5 2.5 - 4.0 20 169 2.0 - 3.0 3.0 - 5.0 30 202 2.0 - 3.0 3.0 - 6.0 30 236 2.0 - 3.5 4.0 - 7.0 35

525 x 150
118 2.0 - 2.5 2.5 - 3.5 20 158 2.0 - 3.0 3.0 - 4.5 25 197 2.5 - 3.5 3.5 - 5.0 30 236 2.5 - 3.5 3.5 - 6.5 30 275 2.5 - 4.0 4.5 - 7.5 35

600 x 150
135 2.5 - 3.0 3.0 - 4.0 20 180 2.5 - 3.5 3.5 - 5.0 25 225 3.0 - 4.0 4.5 - 5.0 30 270 3.0 - 6.0 4.0 - 7.0 35 315 3.0 - 4.5 5.0 - 8.0 35

300 x 225
101 1.0 - 2.0 1.5 - 2.5 135 1.5 - 2.5 2.0 - 4.0 25 169 2.0 - 3.5 2.5 - 5.0 30 202 2.0 - 4.0 2.5 - 6.0 30 236 2.5 - 5.0 3.5 - 7.0 35

375 x 225
127 1.0 - 2.0 2.0 - 3.5 169 1.5 - 2.5 2.0 - 4.5 25 211 2.0 - 3.5 2.5 - 5.5 30 253 2.0 - 4.0 3.5 - 6.5 35 295 2.5 - 5.0 4.0 - 8.0 35

450 x 225
153 1.5 - 2.5 2.5 - 4.0 203 2.0 - 3.0 2.5 - 5.0 25 253 2.5 - 4.0 3.0 - 6.0 30 303 2.5 - 4.5 4.0 - 7.0 35 354 3.0 - 5.5 4.5 - 7.0 35

525 x 225
177 2.0 - 3.0 3.0 - 4.5 237 2.5 - 3.5 3.0 - 5.5 25 295 3.0 - 4.5 3.5 - 6.5 30 354 3.0 - 5.0 4.5 - 7.5 35 413 3.5 - 6.0 5.0 - 9.0 35

600 x 225
203 2.5 - 3.5 3.5 - 5.0 271 3.0 - 4.0 3.5 - 6.0 25 337 3.5 - 5.0 4.0 - 7.0 30 404 3.5 - 5.5 5.0 - 8.0 35 472 4.0 - 7.0 5.5 - 10.0 40

15

23

33

43

Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

375 x 300
169 1.5 - 2.5 2.0 - 4.0 225 2.0 - 3.5 2.5 - 5.0 25 281 2.0 - 4.5 3.0 - 6.0 30 338 2.5 - 5.0 4.0 - 7.5 35 394 3.0 - 6.0 4.5 - 8.5 35

450 x 300
203 1.5 - 2.5 2.0 - 4.5 270 2.0 - 3.5 2.5 - 5.5 25 338 2.0 - 4.5 3.5 - 7.0 30 405 2.5 - 5.0 4.0 - 8.0 35 473 3.0 - 6.0 5.0 - 9.5 40

525 x 300
236 2.0 - 3.0 2.5 - 5.0 20 315 2.5 - 4.0 3.0 - 6.0 25 394 2.5 - 5.0 4.0 - 7.5 30 473 3.0 - 5.5 4.5 - 8.5 35 551 3.5 - 6.5 5.5 - 10.0 40

600 x 300
271 2.5 - 3.5 3.0 - 5.5 20 360 3.0 - 4.5 3.5 - 6.5 30 441 3.0 - 5.5 4.5 - 8.0 35 540 3.5 - 6.0 5.0 - 9.0 35 630 4.0 - 7.0 6.0 - 10.5 40

450 x 375
253 2.0 - 3.5 2.5 - 4.5 20 338 2.0 - 4.5 3.0 - 6.0 25 422 2.5 - 5.5 4.0 - 7.5 30 506 3.5 - 6.5 4.5 - 9.0 35

525 x 375
296 2.5 - 4.0 3.0 - 5.0 20 394 2.5 - 4.5 3.5 - 6.5 30 492 3.0 - 6.0 4.5 - 7.5 35 591 4.0 - 7.0 5.0 - 9.5 35

600 x 375
339 3.0 - 4.5 3.5 - 5.5 25 450 3.0 - 5.0 4.0 - 7.0

525 x 450
354 2.0 - 4.0 2.5 - 5.0 25 472 2.5 - 5..0 3.5 - 7.5

600 x 450
406 2.5 - 4.5 3.0 - 5.5 25 540 3.0 - 5.5 4.0 - 8.0

600 x 525
474 2.5 - 4.5 3.0 - 5.5 25 629 3.0 - 5.5 4.0 - 8.5

15

23

33

30 30 591 562 3.5 - 6.5 3.5 - 5.0 4.5 - 9.0 5.0 - 8.0 35 35 674 709 4.0 - 7.5 4.5 - 7.5 5.5 - 10.0 5.0 - 10.5 40 40

30 30 675 785 4.0 - 7.0 4.0 - 7.5 5.0 - 9.5 5.0 - 10.0 35 35 810 942 4.5 - 8.0 4.5 - 8.5 5.5 - 11.0 5.5 - 11.5 40 40 945 1103 5.0 - 9.5 5.0 - 10.0 6.5 - 13.0 6.5 - 14.0 40 45

43

590 827 689 788 4.5 - 9.0 4.0 - 7.5 4.5 - 8.0 5.0 - 9.0 5.0 - 10.5 5.5 - 11.0 6.5 - 11.5 6.0 - 12.5 40 40 40 40

Waterloo 2.0

30

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DF DE core 41
Selection Example DF41/300x300

Ceiling height 2.7 m Temperature differential -10K Air flow rate 225 l/s Radius of diffusion - Minimum and maximum Throw 2.0 - 4.5m throw which results in an average air Total Pressure Loss 23 Pa velocity within the occupied zone of Noise level NC25 0.25m/s and 0.10m/s respectively. Exhaust & OBSS corrections NC level = peak level on noise criteria curves based on Sound Power Level less Supply diffuser + 0dB 8dB room absorption Supply diffuser + OBSS + 3dB
Exhaust diffuser Exhaust diffuser + OBSS + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

Performance Table

DF DE
Supply
Total pressure drop (Pa) 9 l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw l/s Min - Max (m) Lw 150 x 150
34 1.0 - 1.5 45 1.0 - 2.0 56 1.5 - 2.5 68 1.5 - 3.0 79 2.0 - 3.5 19

Core 41

225 x 225
76 1.0 - 2.0 101 1.5 - 2.5 127 2.0 - 3.5 152 2.0 - 4.0 23 177 2.0 - 4.5 27

300 x 300
135 1.5 - 2.5 180 2.0 - 3.5 20 225 2.0 - 4.5 25 270 2.5 - 5.0 29 315 3.0 - 6.0 32

375 x 375
211 2.0 - 3.5 282 2.0 - 4.5 24 352 2.5 - 5.5 29 422 3.5 - 6.5 33 492 4.0 - 7.5 37

450 x 450
304 2.0 - 4.0 22 405 2.5 - 5.0 28 506 3.5 - 6.5 33 608 4.0 - 8.0 36 709 4.5 - 9.0 40

525 x 525

600 x 600

15

23

33

43

413 540 2.5 - 5.0 2.5 - 5.5 25 30 551 720 3.0 - 6.0 3.5 - 7.0 30 35 689 900 4.0 - 8.0 4.5 - 8.5 35 40 827 1080 4.5 - 9.0 5.0 - 10.5 40 45 964 1260 5.0 - 10.5 6.0 - 12.0 45 45

Blanking Plates
B C D E

Waterloo 2.0

31

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


DF DE core 42
Selection Criteria

Waterloo
Selection Example DF42/450x150

Ceiling height 2.7 m Temperature differential -10K Air flow rate 169 l/s Radius of diffusion - Minimum and maximum Short side throw 1.0 - 2.5m throw which results in an average air Long side throw 2.5 - 5.0m velocity within the occupied zone of Total Pressure Loss 23 Pa 0.25m/s and 0.10m/s respectively. Noise level NC25 NC level = peak level on noise criteria Exhaust & OBSS corrections curves based on Sound Power Level less 8dB room absorption Supply diffuser + 0dB
Supply diffuser + OBSS Exhaust diffuser Exhaust diffuser + OBSS
L

Performance Table

+ 3dB + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

DF DE
Supply

Core 42

S S = Short side throw L = Long side throw

Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

225 x 150
51 1.0 - 1.5 1.0 - 2.0 68 1.0 - 2.0 1.0 - 2.5 84 1.0 - 2.5 1.5 - 3.5 101 1.5 - 3.0 2.0 - 3.5 118 2.0 - 3.5 2.0 - 4.5 25

300 x 150
67 1.0 - 1.5 1.0 - 2.5 90 1.0 - 2.0 1.5 - 3.5 113 1.0 - 2.5 2.0 - 3.5 135 1.5 - 3.0 2.0 - 4.5 25 158 2.0 - 3.5 2.5 - 5.0 25

375 x 150
84 1.0 - 1.5 1.5 - 3.0 113 1.0 - 2.0 2.0 - 3.5 140 1.0 - 2.5 2.0 - 4.5 20 169 1.5 - 3.0 2.5 - 5.0 24 197 2.0 - 3.5 3.0 - 6.0 30

450 x 150
101 1.0 - 1.5 1.5 - 3.5 135 1.0 - 2.0 2.0 - 4.0 169 1.0 - 2.5 2.5 - 5.0 25 202 1.5 - 3.0 2.5 - 6.0 25 236 2.0 - 3.5 3.5 - 6.5 30

525 x 150
118 1.5 - 2.0 2.0 - 4.0 158 1.5 - 2.5 2.5 - 4.5 20 197 1.5 - 3.0 3.0 - 5.5 25 236 2.0 - 3.5 3.0 - 6.5 30 275 2.5 - 4.0 4.0 - 7.0 30

600 x 150
135 2.0 - 2.5 2.5 - 4.5 180 2.0 - 3.0 3.0 - 5.0 20 225 2.0 - 3.5 3.5 - 6.0 25 270 2.5 - 4.0 3.5 - 7.0 30 315 3.0 - 4.5 4.5 - 7.5 35

300 x 225
101 1.0 - 2.0 1.0 - 2.5 135 1.0 - 2.5 2.0 - 3.5 169 2.0 - 3.5 2.0 - 4.5 25 202 2.0 - 4.0 2.5 - 5.0 25 236 2.0 - 4.5 2.5 - 6.0 35

375 x 225
127 1.0 - 2.0 1.5 - 3.0 169 1.0 - 2.5 2.0 - 3.5 20 211 2.0 - 3.5 2.0 - 1.5 25 253 2.0 - 4.0 3.0 - 6.5 30 295 2.0 - 4.5 3.5 - 7.5 35

450 x 225
153 1.0 - 2.0 2.0 - 3.5 203 1.0 - 2.5 2.5 - 4.0 25 253 2.0 - 3.5 2.5 - 5.0 30 303 2.0 - 4.0 3.5 - 7.0 35 354 2.0 - 4.5 4.0 - 8.0 35

525 x 225
177 1.0 - 2.0 2.0 - 4.0 237 1.0 - 2.5 2.5 - 5.0 25 295 2.0 - 3.5 3.0 - 6.0 30 354 2.0 - 4.0 4.0 - 7.5 35 413 2.0 - 4.5 4.5 - 8.5 35

600 x 225
203 1.5 - 2.5 2.5 - 4.5 271 1.5 - 3.0 3.0 - 5.5 25 337 2.5 - 4.0 3.5 - 6.5 30 404 2.5 - 4.5 4.5 - 8.0 35 472 2.5 - 5.0 5.0 - 9.0 35

15

23

33

43

Total pressure drop (Pa) l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw l/s S Min - Max (m) L Min - Max (m) Lw

375 x 300
169 1.0 - 2.5 2.0 - 3.5 225 2.0 - 3.5 2.0 - 4.5 25 281 2.0 - 4.0 2.5 - 5.0 30 338 2.5 - 5.0 3.5 - 6.5 30 394 3.0 - 6.0 4.0 - 7.5 35

450 x 300
203 1.0 - 2.5 2.0 - 3.5 270 2.0 - 3.5 2.5 - 5.0 25 338 2.0 - 4.5 3.0 - 6.0 30 405 2.5 - 5.0 4.0 - 8.0 35 473 3.0 - 6.0 4.5 - 8.0 35

525 x 300
236 1.0 - 2.5 2.0 - 4.5 315 2.0 - 3.5 2.5 - 6.0 25 394 2.0 - 4.5 3.5 - 6.5 30 473 2.5 - 5.0 4.0 - 8.0 35 551 3.0 - 6.0 5.0 - 9.5 40

600 x 300
271 1.5 - 3.0 2.5 - 5.0 20 360 2.5 - 4.0 3.0 - 6.5 25 441 2.5 - 5.0 4.0 - 7.0 30 540 3.0 - 5.5 4.5 - 8.5 35 630 3.5 - 5.5 4.5 - 8.5 40

450 x 375
253 2.0 - 3.5 2.0 - 4.0 20 338 2.0 - 4.5 2.5 - 5.0 25 422 2.5 - 5.5 3.5 - 6.5 30 506 3.5 - 6.5 4.0 - 7.5 35 590 4.0 - 7.5 4.5 - 9.0 40

525 x 375
296 2.0 - 3.5 2.0 - 4.5 20 394 2.0 - 4.5 2.5 - 6.0 30 492 2.5 - 5.5 3.5 - 7.5 35 591 3.5 - 6.5 4.5 - 8.5 35

600 x 375
339 2.5 - 4.0 2.5 - 5.0 25 450 2.5 - 5.0 3.0 - 6.5 30 562 3.0 - 6.0 4.0 - 8.0 35 674 4.0 - 7.0 5.0 - 9.0 40

525 x 450
354 2.0 - 4.0 2.5 - 5.0 25 472 2.5 - 5.0 3.0 - 6.0 30 591 3.5 - 6.5 4.0 - 7.5 35 709 4.0 - 8.0 4.5 - 9.0 40

600 x 450
406 2.0 - 4.0 2.5 - 5.0 25 540 2.5 - 5.0 3.5 - 7.0

600 x 525
474 2.5 - 4.5 3.0 - 5.5 25 629 3.0 - 5.5 4.0 - 7.5

15

23

33

30 5 675 785 3.5 - 6.5 4.0 - 7.0 4.5 - 8.5 5.0 - 9.0 35 40 810 942 4.0 - 8.0 4.5 - 8.5 5.0 - 10.0 5.5 - 10.5 40 40 945 1103 4.5 - 9.0 5.0 - 9.5 6.0 - 12.0 6.5 - 12.5 45 45

43

827 689 788 4.5 - 9.0 4.0 - 7.5 4.5 - 8.0 5.0 - 10.5 5.5 - 11.0 5.0 - 10.5 40 40 40

Waterloo 2.0

32

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Louvred Face Diffusers


DFA core 41
DFA41/300x300 Ceiling height 2.7 m Horizontal Diffusion Temperature differential -10K Air flow rate 225 l/s Radius of diffusion - Minimum and maximum Throw 1.5 - 3.0m throw which results in an average air Total Pressure Loss 21 Pa velocity within the occupied zone of Noise level NC20 0.25m/s and 0.10m/s respectively. NC level = peak level on noise criteria curves based on Sound Power Level less Exhaust & OBSS corrections 8dB room absorption
Supply diffuser Supply diffuser + OBSS Exhaust diffuser Exhaust diffuser + OBSS

Selection Example

Performance Tables

+ 0dB + 3dB + 3dB +13dB

Pa Pa Pa Pa

x x x x

1.0 1.0 1.1 1.15

DFA41
150 x 150

Horizontal diffusion
(Cones fully lowered) t = 10C cooling

DFA41
375 x 375
211 1.5 - 2.5 11 282 1.5 - 3.0 25 21 352 2.0 - 4.0 31 32 422 2.5 - 5.0 37 47 492 3.0 - 5.5 41 65

Isothermal vertical projection


(Cones fully raised)

225 x 225
76 0.5 - 1.5 11 101 1.0 - 2.0 21 127 1.5 - 2.5 22 32 152 1.5 - 3.0 27 47 177 1.5 - 3.0 33 65

300 x 300
135 1.5 - 2.5 11 180 1.5 - 3.0 20 21 225 1.5 - 3.0 26 32 270 2.0 - 4.0 33 47 315 2.5 - 4.5 38 65

150 x 150

225 x 225
76 9.4 17 101 12.5 21 30 127 16.1 28 47 152 20.5 34 67 177 40 90

300 x 300
135 12.5 17 180 16.7 23 30 225 21.5 31 47 270 37 67 315 43 90

375 x 375
211 15.6 20 17 282 20.8 27 30 352 26.8 34 47 422 40 67 492 44 90

l/s Min - Max (m) Lw Pa l/s Min - Max (m) Lw Pa l/s Min - Max (m) Lw Pa l/s Min - Max (m) Lw Pa l/s Min - Max (m) Lw Pa

34 0.5 - 1.0 11 45 0.5 - 1.5 21 56 1.0 - 2.0 20 32 68 1.0 - 2.5 27 47 79 1.5 - 2.5 32 65

l/s Projection Lw Pa l/s Projection Lw Pa l/s Projection Lw Pa l/s Projection Lw Pa l/s Projection Lw Pa

34 6.3 21 45 8.3 22 37 56 10.7 28 60 68 13.6 35 87 79 15.0 40 122

(Cones fully raised) DFA41 t = 10C heating (correct for other temp.)

Heating vertical projection

Terminal Velocities For Isothermal Vertical Projection


Vt (m/s) Factor 0.25 1.00 0.40 0.65 0.60 0.40

150 x 150

225 x 225
76 2.3 17 101 3.3 21 30 127 4.1 28 47 152 4.7 34 67 177 5.4 40 90

300 x 300
135 2.4 17 180 3.6 23 30 225 4.8 31 47 270 5.8 37 67 315 6.6 43 90

375 x 375
211 2.7 20 17 282 3.9 27 30 352 5.1 34 47 422 6.2 40 67 492 7.3 44 90

l/s Projection Lw Pa l/s Projection Lw Pa l/s Projection Lw Pa l/s Projection Lw Pa l/s Projection Lw Pa

Temperature Differentials For Heating Vertical Projection


t (C) Factor 5 1.5 10 1 15 0.85 20 0.7 25 0.6 30 0.5

34 2.0 21 45 2.7 22 37 56 3.4 28 60 68 4.1 35 87 79 4.8 10 122

Waterloo 2.0

33

Tel: +44 (0) 1622 711511

Louvred Face Diffusers


Plenum Chambers and Neck Reducers
Introduction
Correct selection and sizing of distribution plenum chambers and neck reducers is critical because terminal air resistance is very low relative to the distribution ductwork resistance. It is therefore recommended that whenever possible terminals are served by low velocity stub ducts from branch ducting systems fitted with correct balancing controls. Where it is necessary to specify and use plenums a generous allowance for commissioned noise generation should be made. A similar effect results from use of neck reducers with circular duct connections because the reduced duct area will cause generally higher velocities and hence increased risk of noise generation.

Waterloo

Product Description
PBD Plenum chamber NR-D Top entry neck reducer

PBD Side entry plenum box

Features
Plated steel with stitched seam joints. Plenums are available with circular, square or rectangular spigots in either top or side entry applications Neck reducers are available with circular, square or rectangular spigots in top entry only

Installation
The plenum boxes and neck reducers are supported by 4 drop rods through a locating hole positioned near each corner. When ordering plenum chambers please specify length width & height, spigot size and position (top or side entry) and control options. Please note that the plenum height should in general be 100mm greater that the spigot diameter (side entry applications). Neck reducers are available as standard in sizes up to 1200 x 600. The high profile is designed to accommodate an opposed blade damper.

100

NR-D Neck reducer


Diffuser Neck Size (mm) 150x150 225x225 225x150 300x300 300x225 300x150 375x375 375x300 375x225 375x150 450x450 450x375 450x300 525x525 525x450 525x375 525x300 600x600 600x450 600x300 Nominal Diffuser + Plenum + Open OBSS Spigot Maximum flow rate to achieve Size stated noise levels (l/s) (mm) NR25 NR30 NR35 NR40 NR45 150 200 200 250 250 250 350 350 350 350 400 400 400 500 500 500 500 500 500 500 45 75 60 140 90 85 210 160 125 120 230 220 190 290 280 275 235 530 380 350 55 100 80 170 130 110 240 210 170 140 310 280 260 410 380 360 315 620 450 410 65 125 100 210 170 135 290 260 215 170 400 355 330 540 490 460 380 700 540 460 80 150 115 260 210 160 355 330 270 210 500 450 410 670 610 580 480 850 660 560 95 175 130 310 240 185 430 400 330 260 650 590 490 840 810 690 590 1020 850 680 Actual Plenum Dimensions L W H 150 150 250 225 225 300 225 150 300 300 300 350 300 225 350 300 150 350 375 375 375 375 375 375 375 375 450 450 450 450

Plenum chambers
Pressure loss: multiply diffuser pressure loss by 1.25 NR level: based on peak sound power level less 8dB room absorption allowance Note: Actual spigot size = nominal - 3mm

Neck reducers
Pressure loss and noise levels should be based on the spigot air velocity and the nominal diffuser size, ie. if a 450 sq neck diffuser handling 200 l/s is fitted with a neck reducer having a 315 spigot, the inlet air velocity is approximately 2.5 m/s. Referring to the selection tables, at the equivalent air velocity through the diffuser neck the noise level would be NC33 and the pressure loss 23Pa. Throw: use catalogue data providing that the ratio of diffuser to neck size remains less than 1.5:1.

450 450 500 450 450 500 450 450 500 525 525 525 525 525 525 525 525 600 600 600 600

600 600 600 600 600 600 600 600 600

Waterloo 2.0

34

Tel: +44 (0) 1622 711511

Waterloo

Louvred Face Diffusers


Core Configuration Summary

Waterloo 2.0

35

Tel: +44 (0) 1622 711511

Aircell Diffusers
M300 M450 M500 M600 M625
Introduction
The Waterloo Aircell M series presents all the cost and design advantages of the 2000 series with the visual appeal of clean, unbroken lines on the traditional multicone design. The diffusers are available in a range of 5 sizes to integrate with standard 300mm and 600mm ceilings and the 500mm and 625mm European systems.

Waterloo

Product Description
M300 M450 M500 M600 M625 O P F BM R600 300 sq diffuser 450 sq diffuser 500 sq diffuser 600 sq diffuser 625 sq diffuser Black polymer opposed blade damper Black polymer plenum box Fixing kit Blanking kit Reducer with 312 spigot

Features
Contemporary style designed for visual integration with luminaires and other ceiling elements Ease of installation with concealed, single point fixing into P series plenum or rigid ducting Full range of integrated accessories available including directional or core blanking kits, universal plenums and opposed blade dampers

Finishes
Diffusers are self-coloured white Damper and plenum are self-coloured black

Weights
M300 M450 M500 M600 M625 0.6 1.4 1.6 2.6 2.8 kg kg kg kg kg

Authority
Patents: 2221530, 2223840, 8818337 others pending Registered Designs: 1052716, 106216 Fire Rating: BS476 Pt 7 Class 0. BS476 Pt 5, P Rating. BS 2782 Method 508A, Zero Rate of Burn. Performance tested to BS4773 1991, ISO 5219. Maximum supply air temperature must not exceed 50C.

Order Example
Aircell M300/O300/P300/F300/BM300 Type Damper Plenum Fixing Kit Blanking Kit

Aircell M
M300 M450 M500 M600 M625

A
6 6 6 6 6

B
230 307 307 456 456

C
36 36 36 36 36

D
56 56 56 56 56

E
296 446 496 596 621

F
235 375 375 525 525

Waterloo 2.0

36

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Aircell Diffusers
M300 M450 M500 M600 M625
Ceiling Height 2.7 m Temperature Differential -10K Average room velocity vr 0.25 m/s NR level = peak level on noise rating curves based on Sound Power Level less 8dB room absorption

Selection Example Aircell M450


Air Flow Rate 180 l/s Throw 2.0 m Static Pressure Loss 15 Pa Noise level NR23

All performance data includes the plenum box Performance Table

Note: Sizes are overall

M
I/s 34

Supply M300

Supply M450 M500


1.5 9 2.0 15 23 2.2 23 28 2.5 33 33 3.0 43 36

Supply M600 M625

Extract M300

Extract M450 M500

Extract M600 M625

45

56

68

79

135

180

225

270

315

405

506

608

709

T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw

1.0 9 1.2 15 1.5 23 1.6 33 2.0 43 21

1.2 1.6 15 33 1.5 23 1.7 34 20

10 17 25 36 21 2.0 9 25 3.7 26 38 2.2 4.6 12 44 27 45 2.8 17 35 3.7 26 38 4.1 35 41 47 24 10 21 17 26 25 31 36 36 47 39 10 28 17 35 25 40 36 43 47 47

1.5 9 2.0 15 23 2.2 23 28 2.5 33 33 3.0 43 36

1.3 8 2.0 15 23 2.3 25 29 2.7 35 35

1.3 7 1.5 9 1.7 12 2.5 33 33

2.0 9 25 2.5 15 32 3.5 23 37 4.0 33 40 4.5 43 44

1.8 7 22 2.2 12 28 2.5 15 32 3.6 25 39 4.3 38 42

Blanking arrangements
Copyright: Waterloo Air Products 2005 4 way 3 way 2 way 2 way 1 way

Waterloo 2.0

37

Tel: +44 (0) 1622 711511

Aircell Diffusers
2300 2600
Introduction
The Waterloo Aircell 2000 series presents a contemporary diffuser style combining high performance and robust construction with the significant cost advantage of injection moulded engineering polymers. The diffusers are available in 2 sizes to integrate with standard 300mm or 600mm lay-in or concealed T ceiling systems.

Waterloo

Product Description
2300 2600 O P F B 300 sq diffuser 600 sq diffuser Black polymer opposed blade damper Black polymer plenum box Fixing kit Blanking kit

Features
Contemporary style designed for visual integration with luminaires and other ceiling elements Ease of installation with concealed, single point fixing into P series plenum or rigid ducting Full range of integrated accessories available including directional or core blanking kits, universal plenums and opposed blade dampers

Finishes
Diffusers are self-coloured white Damper and plenum are self-coloured black

Weights
2300 2600 0.6 kg 3.2 kg

Authority
Patents: 2221530, 2223840, 8818337 others pending Registered Designs: 1052716, 106216 Fire Rating: BS476 Pt 7 Class 0. BS476 Pt 5, P Rating. BS 2782 Method 508A, Zero Rate of Burn. Performance tested to BS4773 1991, ISO 5219. Maximum supply air temperature must not exceed 50C.

Order Example
Aircell 2300/O300/P300/F300/B300 Type Damper Plenum Fixing kit Blanking kit

Aircell 2000 A
2300 2600 3 6

B
229 459

C
41 31

D
53 56

E
296 596

F
269 546

Waterloo 2.0

38

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria
Ceiling Height 2.7 m Temperature Differential -10K Average room velocity vr 0.25 m/s NR level = peak level on noise rating curves based on Sound Power Level less 8dB room absorption

Aircell Diffusers
2300 2600
Selection Example Aircell 2300-4
Air Flow Rate 75 l/s Throw 1.1 m Static Pressure Loss 17 Pa Noise level NR22 Note: Sizes are overall

All performance data includes the plenum box Performance Table

2000
Air Volume l/s 25 m3/h 90 T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw T (m) Ps Lw

Supply
2300 4 way 3 way 2 way 1 way 0.6 0.7 0.8 1.7 2 5 8 28 30 0.8 1.4 1.7 8 17 28 20 30 1.1 1.7 2.3 17 28 60 22 30 41 1.7 2.2 28 50 30 38 2.0 2.5 44 66 36 43 2.3 60 41

Supply
2600 4 way 3 way 2 way 1 way

Exhaust
2300 2600

4 0.9 10 20 1.8 22 31 2.5 40 38 15 19 30 29 50 35 75 40 100 45 6 12 20 20 29 27 41 32 54 37

50

180

75

270

100

360

125

450

150

540

200

720

250

900

300

1080

350

1260

400

1440

0.3 4 0.5 6 0.9 10 20 1.4 15 26 1.8 22 31 2.2 30 35 2.5 40 38

0.7 8 0.9 10 20 1.6 18 28 2.1 28 33 2.5 40 38

0.9 10 20 1.4 15 26 1.8 22 31 2.5 40 38

Blanking arrangements
Copyright: Waterloo Air Products 2005

4 way

3 way

2 way

2 way

1 way

Waterloo 2.0

39

Tel: +44 (0) 1622 711511

Aircell Diffusers
Controls and Fixing Options
Performance
The unique integrated design of the plenum, damper and diffuser assembly has been specifically developed to promote smooth flow lines, ensuring an exceptional aerodynamic and acoustic performance. Aircell products can be used in any air distribution systems where temperatures do not exceed 50 C. The components have been tested to BS4773 Parts 1 & 2 to provide comprehensive, easy to use selection data for all installation options. B A

Waterloo

Opposed Blade Damper Type O


The O series opposed blade damper is designed to integrate with the plenum and diffuser range to provide a simple means of flow regulation from the diffuser face. The unit is designed to snap fit into the universal plenum, or alternatively can be easily screw or rivet fixed into steel ducting using the inbuilt mounting lugs. Manufactured in black engineering grade polymer, the damper is inherently smooth and positive in operation.

Type 'O' damper

50

Weights
O300 O450 O600 0.5 kg 1.0 kg 2.2 kg C 7

Plenum Type P
The P series plenum is aerodynamically profiled to provide ideal flow conditions with either top or side entry duct arrangements. Manufactured in black engineering grade polymer, the design incorporates features such as internal guide vanes to reduce air turbulence, and snap-in locks to retain the opposed blade damper and diffuser mounting bar. The plenum can be fixed to the ceiling grid or suspended by drop rods from the slab. Either fixing method is carried out using patented mounting brackets which simply slide into the plenum retaining slots.

7 D o/s stack

Type 'P' plenum

312

400

Weights
P300 P450 P600 0.7 kg 1.0 kg 1.7 kg

R600 neck reducer

Neck Reducer R600


The R600 snap-fit neck reducer is available as an option to convert the P600 plenum spigot from 397 to 312.

Model
O300 O450 O600 P300 P450 P600

A
41 41 41 -

B
215 290 440 -

C
245 277 366

D
224 299 449

50

E
197 247 397

Waterloo 2.0

40

Tel: +44 (0) 1622 711511

Waterloo
Installation
Particular attention has been paid to the installation method to minimise site fixing time. The plenum is easily installed using the slide-in brackets as support legs from above the ceiling T, or with drop rods from the slab. The damper and diffuser support bar can then be clipped in place, with the diffuser finally being secured by the single centre fixing screw.

Aircell Diffusers
Installation and Specification

Specification
Ceiling diffusers shall be Aircell 2000 series manufactured from injection moulded engineering polymer, in self-coloured white as standard. Overall diffuser size shall be nominally 300 or 600mm to suit standard ceiling grids. A captive centre line polymer fixing bolt and metal fixing bracket kit shall be provided. Directional blanking is obtained with snap-in plates to provide 1, 2 or 3 way air patterns or reduced area blanking. Opposed blade dampers (type O) is manufactured from injection moulded engineering polymer in self-coloured black as standard, operable through the diffuser face. Plenum box (type P) is manufactured from injection moulded engineering polymer of a universal design and in self-coloured black, incorporating guide vanes and bracket location slots. Note: Specially designed clips mean that you can use a type O damper with a diffuser without a universal Plenum.
Universal plenum type P
Duct or Plenum Z W Y

Damper

Face operated opposed blade damper type O


Diffuser X min

Diffuser fixing bracket type F - for fixing tro plenum or duct

W = Damper depth X = Ceiling opening (+5 -0) Y = Face of T bar to underside of Duct or Plenum (+0 -10) Z = Underside of duct to underside of damper

Aircell diffuser

Captive fixing bolt

Model
2300 2600

W
45 45

X
269 546

Y
41 41

Z
88 88
Removable core

Waterloo 2.0

41

Tel: +44 (0) 1622 711511

Laminar Flow Diffusers


LFF LFM
Introduction
LF diffusers have been designed for use in clean rooms, laboratories, operating theatres, or other applications where critical control of room air movement is necessary. They are also suitable for less critical applications such as animal rooms or kitchens where a vertical flow pattern may be required. The laminar air pattern is achieved by use of a primary baffle within the plenum chamber and a low free area perforated discharge plate at the face of the diffuser. The diffusers are available with either a flanged frame style (type LFF) to suit conventional exposed or concealed T ceilings, or, with a flangeless frame (type LFM) suitable for modular panel constructions. The LFM units can be supplied with a perimeter trim strip to suit the overall dimensions of the panel assembly. Support brackets and mounting plates can also be manufactured to fit suspended light bases used in operating theatres. The units are available in three standard sizes with options for top, side, or end entry inlet spigots and screw operated louvre dampers.

Waterloo
Ceiling opening size = W/H -20
D

o/s Optional LD

75

25 W x H Overall

LFF-TE = Top Entry


A 75 + 125 o/s W x H Overall

150
D

Description
LF laminar flow diffusers are constructed from aluminium extruded frames and assembled using welding and soldering techniques to form a robust construction. The perforated aluminium face plate can be easily removed for cleaning using the hook tool provided. Plenum chambers are manufactured from galvanised sheet steel, with all exposed edges and spot welds protected. LFF Laminar flow panel with flanged frame LFM Laminar flow panel with modular flangeless frame LD Louvre damper 75

LFF-SE = Side Entry LFF-EE = End Entry


D

o/s

Optional LD

Product Description

70

Features
Two frame styles and sizes to suit 600mm and I200mm T ceilings or modular panel assemblies. Side, top, or end entry spigot connections with optional spigot mounted louvre damper. Pivoting, removable face plate for easy maintenance. Easy clean aluminium face plate and frame with durable polyester powder coating.

W x H Overall

LFM-TE = Top Entry


A 75 + 135 o/s W x H Overall

PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

LFM-SE = Side Entry LFM-EE = End Entry

Order Example LFM/900x600/TE/PPM9010/LD


Type Nominal Width Nominal Height Spigot Location Finish Damper (if required)

Type Unit size


LFM LFM LFM LFF LFF 600 900 1200 600 1200 x x x x x 600 600 600 600 600

WxH
600 900 1200 598 1198 x x x x x 600 600 600 598 598

Finishes

13

26

160

A
120 120 165 120 165

Free Area 23%

197 197 312 197 312

Waterloo 2.0

42

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Laminar Flow Diffusers


LFF LFM
Laminar flow diffuser airstreams are characterised by the tendency to reduce in sectional area from the point of discharge, particularly with high cooling differentials. Although this produces a slight initial increase in the core velocity, friction between the airstream boundary and the static room air offsets this, the net result being to maintain a near constant air velocity at distances up to 2.5m from the face. This characteristic is reflected in the data presentation of tables 1 and 2 which give information on the face discharge velocity and the average airstream velocity over this distance. The discharge velocity is based on an average number of vane anemometer readings at the face plate, whilst the airstream velocity is derived from time averaged readings with a 15 probe array at distances of 1m and 2m from the face. In the case of the latter, data is given for cooling differentials of 3C, 5C and 10C. The temperature diffusion data presented in table 3 can be used to determine the approximate airstream temperature by adding the indicated temperature rise to the discharge air temperature. The acoustic data shown in table 5 is presented in terms of sound power based NR levels. To obtain the resulting NRlp level in the occupied zone, room absorption factors should be applied as appropriate to the installation conditions.

Performance Tables
Table 1. Average Face Air Velocity

LFM LFF
m3/h Unit size 600x600 900x600 1200x600 l/s 72 20 0.05 108 30 0.10 0.05 144 40 0.13 0.07 180 50 0.17 0.10 0.05 216 60 0.21 0.13 0.06

Air Flow Rate


288 80 0.30 0.18 0.11 360 100 0.37 0.24 0.15 432 120 0.30 0.19 504 140 576 160 648 180 720 200

0.24

0.28

0.32

0.37

Table 2. Average Airstream Velocity

LFM LFF
m3/h l/s DT -3 C 600x600 -5 C -10 C -3 C 900x600 -5 C -10 C -3 C 1200x600 -5 C -10 C Unit size 72 20 0.09 0.09 0.10 0.07 0.07 0.08 108 30 0.11 0.12 0.13 0.09 0.10 0.11 144 40 0.13 0.15 0.15 0.11 0.13 0.15 180 50 0.16 0.20 0.25 0.12 0.17 0.20 0.05 0.05 0.05 216 60 0.20 0.25 0.32 0.14 0.20 0.24 0.07 0.07 0.10

Air Flow Rate


288 80 0.26 0.31 0.41 0.16 0.25 0.31 0.09 0.10 0.14 360 100 0.33 0.36 0.45 0.22 0.29 0.36 0.10 0.12 0.23 432 120 504 140 576 160 648 180 720 200

0.25 0.32 0.40 0.14 0.16 0.30

0.22 0.25 0.38

0.26 0.30 0.42

0.29 0.35 0.45

0.31 0.39 0.47

Face discharge velocity (table 1) Reduction in airstream section area increases velocity Near constant airstream velocity up to 2.5m from diffuser face (table 2)

Waterloo 2.0

43

Tel: +44 (0) 1622 711511

Laminar Flow Diffusers


LFF LFM
Selection Example
Diffuser selection criteria will be dependent on the application, but as a general guide most sedentary occupants would be tolerant of airstream velocities up to 0.25m/s if the air temperature is 1-2C below that in the room. In applications where there are concentrated heat sources or where the occupants are mostly transitory, this can generally be increased to 0.35 - 0.5m/s. As an example, consider the use of a 1200 x 600 diffuser in an operating theatre where the cooling differential is to be 5C with a supply air temperature of 17C.

Waterloo
Reference to table 2 shows that the maximum air flow rate to achieve an average airstream velocity of 0.25m/s would be 140l/s. Airstream temperatures at distances of 1m and 2m from the diffuser face can be found from table 3; in this case, at 140l/s, the supply air temperature will rise by 3.5C and 4.5C respectively, giving moving air temperatures of 20.5C and 21.5C at the two heights. The diffuser noise level can be found from table 5, which, assuming a fully open damper, would be less than NRlw20 at 140l/s.

Performance Tables
Table 3. Airstream Temperature Rise (C)

LFM LFF
m3/h l/s Unit size DT -3C 600 x 600 -5C -10C -3C 900 x 600 -5C -10C -3C 1200 x 600 -5C -10C D 1m 2m 1m 2m 1m 2m 1m 2m 1m 2m 1m 2m 1m 2m 1m 2m 1m 2m 2.5 3.0 4.5 5.0 8.5 9.5 2.5 3.0 4.5 5.0 8.0 9.5 2.5 3.0 4.5 5.0 8.0 9.5 3.0 3.0 4.5 5.0 9.5 9.5 2.5 3.0 4.0 4.5 8.0 9.0 3.0 3.0 4.5 5.0 9.0 9.5 2.0 2.5 3.5 4.0 7.5 8.5 2.5 3.0 4.0 4.5 8.5 9.0 72 20 108 30 144 40 180 50 216 60

Air Flow Rate 288 80 2.0 2.5 3.0 3.5 6.5 8.0 2.5 2.5 3.5 4.5 8.0 8.5 360 100 1.0 2.0 2.5 3.0 6.0 7.0 2.0 2.5 3.0 4.0 7.0 8.0 2.5 2.5 4.0 5.0 9.5 9.5 1.5 2.0 2.5 3.5 5.5 7.0 2.5 2.5 4.0 4.5 9.0 9.5 2.0 2.5 3.5 4.5 8.0 9.0 2.0 2.5 3.0 4.0 7.5 8.5 1.5 2.0 2.5 3.0 6.5 8.0 1.0 1.5 2.0 2.5 5.5 7.0 432 120 504 140 576 160 648 180 720 200

3.0 3.0 3.0 3.0 5.0 4.5 5.0 5.0 10.0 9.5 10.0 10.0

3.0 3.0 3.0 3.0 3.0 2.5 4.5 4.5 4.5 5.0 5.0 5.0 10.0 10.0 10.0 10.0 10.0 10.0

Table 4. Diffuser Static Pressure Loss (Pa) (open damper)

LFM LFF
m3/h Unit size 600x600 900x600 1200x600 l/s 72 20 1 1 108 30 1 1 144 40 1 1 180 50 2 2 1 216 60 2 2 1

Air Flow Rate 288 80 4 4 1 360 100 5 5 2 432 120 7 2 504 140 576 160 648 180 720 200

Table 5. Acoustic Data (Noise Level) (NR) (open damper)

LFM LFF
m3/h Unit size 600x600 900x600 1200x600 l/s 72 20 108 30 144 40 180 50 <20 216 60 20 <20

Air Flow Rate 288 80 24 23 360 100 28 27 432 120 30 <20 <20 504 140 576 160 648 180 720 200

Waterloo 2.0

44

Tel: +44 (0) 1622 711511

Waterloo

Laminar Flow Diffusers


LFF LFM

LFM - Flangeless frame

OPTIONAL TOP, END OR SIDE ENTRY SPIGOTS LINK PLATES

8mm HOLES FOR DROP SUPPORT

FACE PLATE REMOVAL TOOL

PRE-DRILLED FRAMES FOR MODULAR ASSEMBLY

LFF - Flanged frame


OPTIONAL LOUVRE DAMPER 8mm HOLES FOR DROP SUPPORT

Waterloo 2.0

45

Tel: +44 (0) 1622 711511

Perforated Face Diffusers


CPD CPDE
Introduction
The Waterloo CPD range of diffusers have been designed for use in commercial applications and are particularly suited to projects with high air change rates and high cooling differentials. CPD diffusers are suitable for installation in 300, 600 and 1200mm tile module systems and the range includes square and rectangular types. W o/a W - 52

Waterloo

H - 52 A x B o/s nominal duct size 132 72 H - 52

The aluminium face plate may be pivoted down and removed to ease installation, commissioning and maintenance and is held closed by spring clips. The diffusers are constructed from aluminium extruded frames and perforated face plates with plated steel, square, rectangular and circular connections suitable for top entry ducts.

Product Description
CPD2 CPD3 CPD4 CPDE OBSS LD 2 way perforated face supply diffuser 3 way perforated face supply diffuser 4 way perforated face supply diffuser Exhaust air perforated face diffuser Opposed blade damper for square / rectangular connections Louvre damper for circular connections

Features
Integrate with 300, 600 and 1200mm tile sizes All aluminium face construction Pivoting, removable face plate Range of four sizes High air handling capacity Supply or exhaust diffusers visually compatible

CPD/OBSS
D o/s nominal duct size

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Free Area 54%

Ceiling opening = H - 20

CPD/LD

Order Example
Type Unit size W x H
CPD/4/300x300/150 DIA/PPM9010/LD Type Pattern Nominal Width Nominal Height Spigot Size Finish Damper
CPD 300 x 300 295 CPD 600 x 600 595 CPD 600 x 300 595 CPD 1200 x 600 1195 CPDE 300 x 300 295 CPDE 600 x 600 595 CPDE 600 x 300 595 CPDE 1200 x 600 1195 x x x x x x x x 295 595 295 595 295 595 295 595 D 147 297

A x B Weight (kg)
147 297 297 597 147 447 447 597 x x x x x x x x 147 297 147 297 147 447 147 297 2.0 3.4 2.8 6.5 2.0 3.4 2.8 6.5

Waterloo 2.0

46

Tel: +44 (0) 1622 711511

H o/a

Waterloo
Selection Criteria
Ceiling height up to 2.8 m Radius of diffusion is based on terminal velocities of 0.75 m/s (minimum) and 0.10 m/s (maximum) to achieve mean room air velocities of 0.25 m/s and 0.10 m/s respectively. NR level is based on diffuser sound power level less 8dB room absorption.

Perforated Face Diffusers


CPD CPDE
Selection Example

CPD4/300x300/150
Air Flow Rate 88 l/s Throw 0.8 - 1.9m Static Pressure Loss 7 Pa Noise Level NR 33

Square Neck Supply Diffuser Corrections


CPD/300x300/150 x 150 as 150 - 6dB Pa x 0.65 CPD/600x600/300 x 300 as 300 - 6dB Pa x 0.65

Performance Tables

CPD
Sizes Spigot size Air Flow Rate m3/h l/s 300x300 150 126 35 0.2-0.5 1 191 53 0.4-0.9 22 3 252 70 0.6-1.4 28 5 317 88 0.8-1.9 33 7 382 106 1.1-2.6 38 10 446 124 1.4-3.3 41 14 508 141 1.7-4.0 44 19 508 141

4 way
600x600 300 600x300 300x150 324 90 0.8-1.8 1.0-2.3 16 4 486 135 1.3-3.1 1.9-4.4 28 4 648 180 1.9-4.4 2.8-6.6 32 14 810 225 2.5-5.8 3.8-8.9 40 21 972 270 2.9-6.9 4.7-11.0 45 31 1200x600 600x300 1296 360 1.0-3.2 1.7-4.0 31 18 1944 540 1.8-4.0 2.6-5.0 42 40 2592 720 2.7-5.0 3.3-6.0 51 70 3240 900 3.3-5.3 4.0-6.3 61 105 300x300 150 126 35 0.3-0.6 16 2 191 53 0.5-1.1 24 4 252 70 0.7-1.7 30 7 317 88 1.0-2.3 35 10 382 106 1.3-3.0 39 15 446 124 1.6-3.8 42 20 508 141 2.0-4.6 45 27

3 way
600x600 300 508 141 1.0-2.3 19 3 763 212 1.5-3.6 28 6 1015 282 2.1-5.0 36 11 1282 356 2.7-6.2 44 17 1526 424 3.3-7.7 53 25 600x300 300x150 324 90 0.8-1.8 1.0-2.3 19 4 486 135 1.3-3.1 1.9-4.4 26 9 648 180 1.9-4.4 2.8-6.6 32 17 810 225 2.5-5.8 3.8-8.9 40 26 972 270 2.9-6.9 4.7-11.0 45 38

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate m3/h l/s

1.0-2.3 18 3 763 212 1.5-3.6 27 6 1015 282 2.1-5.0 36 10 1282 356 2.7-6.2 44 16 1526 424 3.3-7.7 53 23

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate m3/h l/s

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate m3/h l/s

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate m3/h l/s

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate m3/h l/s

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate m3/h l/s

Throw Short Side Min.-Max. [m] Throw Long Side Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa]

Waterloo 2.0

47

Tel: +44 (0) 1622 711511

Perforated Face Diffusers


CPD CPDE

Waterloo
Selection Example

Selection Criteria

CPD2/300x300/150 Ceiling height up to 2.8 m Air Flow Rate 70 l/s Radius of diffusion is based on terminal Throw 2.0 - 4.6m velocities of 0.75 m/s (minimum) and Static Pressure Loss 13 Pa 0.10 m/s (maximum) to achieve mean Noise level NR 34 room air velocities of 0.25 m/s and 0.10 m/s respectively. NR level is based on diffuser sound power level less 8dB room absorption. Square Neck Supply Diffuser Corrections
CPD/300x300/150 x 150 as 150 - 6dB Pa x 0.65 CPD/600x600/300 x 300 as 300 - 6dB Pa x 0.65

Performance Tables

CPD
Sizes Spigot size Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] Air Flow Rate Throw Min.-Max. [m] Noise Level [NR] Static Pressure Loss [Pa] m3/h l/s m3/h l/s m3/h l/s m3/h l/s m3/h l/s m3/h l/s m3/h l/s 300x300 150 126 35 0.8-1.8 20 3 191 53 1.3-3.1 29 8 252 70 2.0-4.6 34 13 317 88 2.7-6.3 38 21 382 106 3.5-8.2 41 30 446 124 4.3-10.2 44 40 508 141 5.0-12.2 47 53

2 way
600x600 300 508 141 1.4-3.3 23 4 763 212 2.3-5.4 32 9 1015 282 3.2-7.6 38 16 1282 356 4.1-9.7 45 25 1526 424 5.1-12.0 53 27 600x300 300x150 324 90 1.1-2.5 21 6 486 135 2.5-5.8 29 12 648 180 3.8-9.0 36 22 810 225 5.4-12.7 41 34 972 270 6.6-15.5 45 50 300x300 150x150 162 45 6 241 67 10 324 90 19 14 403 112 27 20 486 135 33 40 565 157 38 50

Exhaust
600x600 450x450 486 135 6 727 202 15 10 972 270 25 14 1213 337 33 20 1458 405 39 40 1699 472 44 50 600x300 450x150 1458 405 6 2185 607 19 10 2916 810 29 14 3636 1010 37 20 4374 1215 43 40 5112 1420 48 50 1200x600 600x300 1296 360 6 1944 540 20 10 2592 720 28 14 3240 900 36 20

Waterloo 2.0

48

Tel: +44 (0) 1622 711511

Waterloo
Deflection Patterns
CPD4
4 way

Perforated Face Diffusers


CPD CPDE
CPD3
3 way

Ceiling opening = W-20 x H -20 Drop rod fixing by others

CPD2
2 way

Exhaust

CPDE

FLUSH

Nominal Size (mm)


300x300 600x600 600x300 1200x600

Deflecting Pad Size CPD4 CPD3 CPD2


150x150 195x150 200x200 370x200 300x150 420x150 950x200 240x150 540x200 540x150 -

600 T Bar Centres

Installation
Drop rod (or tie wire) support method is recommended for concealed T and flush mounting options.

LAY-IN / EXPOSED T BAR


4 Holes 9.5 for drop rods

300/600/1200 Centres

W dr - 10 op 0 ce rod ntr es

00 - 1 od r H p o s dr ntre e c

CONCEALED T BAR

Waterloo 2.0

49

Tel: +44 (0) 1622 711511

Perforated Face Diffusers


KRCP KRCPE
Introduction
The Waterloo KRCP range of diffusers have been designed to suit 600mm square ceiling modules of Burgess type, lay-in T and concealed T arrangements. The diffuser incorporates an easily removable perforated face plate and adjustable inner multicone pattern control cores which produce an efficient 4, 3, 2 or 1 way air diffusion pattern. Matching exhaust units are available. The control cores are available as separate items to facilitate simple on site changes. This diffuser may be applied to most commercial projects, but as the frame detail incorporates an antismudge ring it is ideal for kitchen and restaurant applications. The range is suitable for systems involving air change rates up to 20 per hour and cooling differentials up to 14C.

Waterloo
596 SQUARE O/A 450 SQUARE FACE OPENING

Product Description
KRCP KRCPE OBSS LD Perforated face supply diffuser Perforated face exhaust diffuser Opposed blade damper for square connections Louvre damper for circular connections

297

O/S

Features
Easy maintenance Anti-smudge frame Pivoted front plate Adjustable pattern control cores Versatile ceiling integration

KRCP
450 I/S NECK

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

KRCPE 450 SQ OBSS OPTION

Sizes
All diffusers are 596 x 596mm overall. Available spigot sizes are as follows:KRCP 300 KRCPE 450 x 450, 300 x 300 or 300

Weights
75

KRCP KRCPE OBSS

5.7 kg 3.7 kg 4.0 kg

KRCPE 300 SQ OBSS OPTION

97

Order Example
KRCP/600x600/300 DIA/PPG9010/LD Type
Nominal Width Nominal Height Spigot Size Finish Damper

Waterloo 2.0

50

22

KRCPE LD OPTION

Tel: +44 (0) 1622 711511

6.5

Waterloo
Selection Criteria

Perforated Face Diffusers


KRCP KRCPE
Selection Example KRCP/600x600/300
4 way throw
Air Flow Rate 210 l/s Throw 0.7 - 2.0m Static Pressure Loss 7 Pa Noise level NR 28

Ceiling Height 3.0 m Radius of diffusion is based on terminal velocities of 0.75 m/s (minimum) and 0.10 m/s (maximum) respectively. NR level is based on diffuser sound power level less 8dB room absorption. Data is based on testing in accordance with BS 4773 Part 1 and 2 for isothermal air conditions. Data is directly applicable to cooling and heating applications.

Performance Tables

KRCP
m3/h l/s T 504 140 Pa Lw T 756 210 Pa Lw T 1008 280 Pa Lw T 1260 350 Pa Lw

Supply
4 way throw 3 way throw long side 3 way throw short side 2 way throw 1 way throw

KRCPE
m3/h l/s Pa Lw Pa Lw Pa Lw Pa Lw Pa Lw

Exhaust
Spigot 450x450 Spigot 300

0.3-1.1 4 17 0.7-2.0 7 28 1.2-2.5 17 37 1.7-3.5 26 44

0.3-1.3 4 17 1.0-3.0 7 28 1.6-3.5 17 37 2.1-4.0 26 44

0.3-0.8 4 17 0.5-1.6 7 28 0.7-2.0 17 37 1.2-2.5 26 44

0.3-1.8 4 17 0.6-2.5 7 28 1.2-3.5 17 37 1.7-4.5 26 44

0.4-2.5 4 17 1.8-3.5 7 28 3.2-5.5 17 37 4.5-8.0 26 44

504 140 1008 280 1512 420 2016 560 2520 700

1 4 9 18 15 30 23 40

6 22 50 23 88 33 125 41

Core Patterns
1 way 2 way corner 2 way opposite 3 way 4 way Exhaust

Installation Options
600 T Bar centres 600 T Bar centres 600 T Bar centres

BURGESS TYPE MOUNT

LAY-IN / EXPOSED T BAR

CONCEALED T BAR

Waterloo 2.0

51

Tel: +44 (0) 1622 711511

Perforated Face Diffusers


MWVP MWVPD
Introduction
The MWVP(D) is a high induction multidirectional (through blanking plate arrangement) ceiling diffuser with a perforated frontplate. The diffuser is suitable for both supply and extract applications, with chilled, warm or isothermal air. It is delivered with an acoustically lined plenum attached as standard. The plenum also has a sound attenuation blade specially designed to have a minimal effect on pressure, helping to reduce noise levels even further. Extract diffusers can have an optional EU2 filter fitted, which conform to the Eurovent norm.

Waterloo

MWVPD

Product Description
MWVPD-4 MWVPD-3 MWVPD-2 MWVP-4 MWVP-3 MWVP-2 MWVPD-R MWVPD-RF MWVP-R MWVP-RF Side-Entry, 4-Way Perforated Plate Supply Diffuser Side-Entry, 3-Way Perforated Plate Supply Diffuser Side-Entry, 2-Way Perforated Plate Supply Diffuser Top-Entry, 4-Way Perforated Plate Supply Diffuser Top-Entry, 3-Way Perforated Plate Supply Diffuser Top-Entry, 2-Way Perforated Plate Supply Diffuser Side-Entry Perforated Plate Extract Diffuser Side-Entry Perforated Plate Extract Diffuser With Filter Top-Entry Perforated Plate Extract Diffuser Top-Entry Perforated Plate Extract Diffuser With Filter

MWVP-R
MWVPD WxH 240x240 300x300 380x380 480x480 560x560 D1 125 160 200 250 315
oval* oval*

MWVP S 72 90 110 102 99 D 125 160 200 250 315 E 87 92 92 97 107

E 235 270 300 295 295

Features
Supply and extract functionality Suitable for chilled, isothermal or warmed air. Ideal for modular ceiling tile replacement High entrainment and mixing of surrounding air. Short throw

*The perimeter of the oval is equivalent to the circumference of a circle


of the stated diameter

Finishing
Front plate is PPM 9010 (20% gloss white) as standard Other colours are available on request

Sizes
See Table

MWVP-RF

MWVPD-RF

Order Example
Type

MWVPD-3-200/PPM9010

WxH 340x340

E E Filter Size MWVP MWVPD 100 100 296 296 335x335 435x435

S 110 117

Number of Directions Inlet Spigot Diameter Finish

200
oval*

440x440 250

*The perimeter of the oval is equivalent to the circumference of a circle


of the stated diameter

Waterloo 2.0

52

Tel: +44 (0) 1622 711511

Waterloo

Perforated Face Diffusers


MWVP MWVPD
Selection Criteria
Ceiling Height 2.7 m Temperature Differential (Room/Supply air) -10K Air Velocity In The Comfort Zone 0.15 m/s Lp dB(A) = Lw less 8 dB Room Damping

Selection Example
MWVP(D)-4-250
Air Volume 111 l/s or 400 m3/h Throw 1.1 m Pressure Drop 9 Pa Sound Level < NR 20

Performance Table
MWVP(D)
m3/h l/s T 100 28 Ps Lp T 150 42 Ps Lp T 200 56 Ps Lp T 250 69 Ps Lp T 300 83 Ps Lp T 400 111 Ps Lp T 500 139 Ps Lp T 600 167 Ps Lp T 750 208 Ps Lp T 1000 278 Ps Lp

4-Way Supply
125 160 200 250 315 0.5 0.4 8 3 -

3-Way Supply
125 160 200 250 315 0.5 0.4 11 5 -

2-Way Supply
125 160 200 250 315 0.6 17 16 1.3 0.9 40 16 29 14 5 -

Extract
125 160 200 250 315

Extract With Filter


200 250

3 -

0.8 0.6 16 22 7 -

0.8 0.7 24 10 24 -

6 -

1.0 0.8 0.7 33 12 30 16 5 -

1.1 0.9 0.8 24 18 33 20 8 -

2.0 1.1 0.8 68 30 12 40 24 25 11 17 9 -

1.3 1.0 0.8 0.5 48 18 39 24 8 3 -

1.1 0.8 0.5 28 12 27 5 -

1.6 1.0 0.7 44 17 31 18 8 39 16 23 13 3 -

1.2 1.0 0.8 28 12 33 15 5 -

1.3 1.1 0.9 40 18 34 18 7 -

2.1 1.3 1.1 64 27 11 39 23 56 21 27 9 18 5 -

1.3 1.1 0.9 20 26 9 4 -

1.4 1.3 1.0 30 12 28 18 5 -

2.1 1.3 1.0 48 20 31 23 8 31 15 22 29 9 -

1.6 1.4 1.2 32 13 32 20 6 -

1.7 1.7 1.3 48 20 7

2.6 2.1 30 11 29 19 3.5 2.6 44 18 35 24 3.3 28 31 54 22 11 28 31 28 35 14 21 5 55 20 27 23 44 24 10 28 18 41 44 22 -

37 26 15 2.1 1.6 28 17 31 19 2.0 18 28 2.7 28 36

1.7 1.4 18 9

27 16 1.7 13 24 2.3 24 35

36 14 24 -

56 35

Waterloo 2.0

53

Tel: +44 (0) 1622 711511

Perforated Face Diffusers


WPD MWPD
Introduction
The Waterloo high-induction ceiling diffuser type WPD has a perforated faceplate and easily adjustable air pattern settings. The diffuser is made from aluminium extrusions with the plenum manufactured from galvanised steel. The complete unit has been specifically designed to ensure a constant air pattern, resulting in optimal mixing with room air at a very low noise level. An optional mounting plate is available to suit 600 x 600 ceiling systems (the overall size of the mounting plate is 595 x 595).

Waterloo

Product Description
WPD-4 WPD-3 WPD-2 WPD-R MWPD WKDV WKDVI WKRV MPV WWM Square ceiling diffuser with 4 way air pattern Square ceiling diffuser with 3 way air pattern Square ceiling diffuser with 2 way air pattern Square ceiling diffuser for return air Square diffuser mounted in perforated modular plate Supply air plenum Insulated supply air plenum Return air plenum Modular plate Fixing set

Features
Supply and exhaust applications of warm, cool and isothermal air High induction characteristics Variety of air patterns Suitable for modular ceiling systems Excellent free-jet performance Adjustable 3 position faceplate
WxH
K

PPM9010 (RAL 9010 20% Gloss White) Other colours available on request

40

Advantages
Excellent aerodynamic performance Good mixing with room air Can be used for full tile replacement Short throw
K 40

D1 595 x 595

WPD + MPV-600

WxH

D1 595 x 595

MWPD

Order Example:
WPD-4-200-WKDV Type Diffuser Pattern Spigot Diameter Plenum Type

WxH
210x210 210x210 310x310 410x410 510x510

D1
125 160 200 250 315

D2
125 160 200 250 315

E
243 243 290 355 435

K
33 33 40 55 70

X
0/ 7.5/15 0/ 7.5/ 15 0/ 7.5/ 15 0/ 7.5/ 15 0/ 7.5/ 15

Waterloo 2.0

54

Tel: +44 (0) 1622 711511

60

60

Finishes

Waterloo
Selection Criteria

Perforated Face Diffusers


WPD MWPD
Ceiling Height 2.7 m Temperature Differential -10K Room Velocity Vr 0.15 m/s Lw based on diffuser sound power level minus 8 dB room absoption.

Selection Example WPD-4-125 4 way supply


Air Volume 56 I/s Throw 1.0 m Pressure Drop 33 Pa Noise Level NR 31
T Throw (m) Pressure (Pa) Noise level (NR)

All selections include the plenum


Faceplate Height Corrections
X (mm)

Performance Tables
WPD
m3/h l/s T 100 28 Ps Lp T 150 42 Ps Lp T 200 56 Ps Lp T 250 69 Ps Lp T 300 83 Ps Lp T 400 111 Ps Lp T 500 139 Ps Lp T 600 167 Ps Lp T 750 208 Ps Lp T 1000 278 Ps Lp

0 7.5 15

x 1.0 x 0.9 x 0.8

x 1.0 x 0.9 x 0.6

0 -2 -3

Supply 4 way
125 160 200 250 315 0.5 0.4 8 16 23 3 7 5 8 3 5 9 4 6 9 1.7 13 25 2.3 24 36

Supply 3 way
125 160 200 250 315 0.5 0.4 11 5 0.6 17 17

Supply 2 way
125 160 200 250 315

Exhaust
125 160 200 250 315 5 14 25 11 18 8 -

0.8 0.6

0.8 0.7 24 10 25 8 5 7 5 7 1.1 0.9 0.8 24 18 34 21

1.3 0.9 40 16 30 2.0 1.1 0.8 68 30 12 41 25 1.6 1.0 0.7 44 17 32 19 39 16 24 9 -

1.0 0.8 0.7 33 12 31 17 48 18 40 25

1.3 1.0 0.8 0.5

1.1 0.8 0.5 28 12 28 -

1.2 1.0 0.8 28 12 34 16 20 27

1.3 1.1 0.9 40 18 35 19

2.1 1.3 1.1 64 27 11 40 24 8 2.1 1.3 1.0 48 20 32 24 31 15 23 56 21 28 -

1.3 1.1 0.9

1.4 1.3 1.0 30 12 29 19 48 20

1.6 1.4 1.2 32 13 33 21 18

1.7 1.7 1.3 38 27 16 2.1 1.6 28 17 32 20 2.0 18 29 2.7 28 37

2.6 2.1 30 11 30 20 3.5 2.6 44 18 36 25 3.3 28 32 54 22 11 29 35 14 22 5 44 24 10 29 19 -

1.7 1.4 28 17

36 14 25 -

Accessories

M6 Nut M6 Washer

Support Frame Spring Clip Set The WWM fixing set consists of 2 support frames, 4 spring clip sets and 4 M6 nuts and washers.

Diffuser Frame

WPD + WWM-Set WWM-Set

Waterloo 2.0

55

Tel: +44 (0) 1622 711511

Perforated Face Diffusers


WID

Waterloo

Introduction
The Waterloo high-induction ceiling diffuser type WID has a perforated faceplate and easily adjustable air pattern settings. The diffuser is made from aluminium extrusions with the plenum manufactured from galvanised steel. The complete unit has been specifically designed to ensure a constant air pattern, resulting in optimal mixing with room air at a very low noise level. An optional mounting plate is available to suit 600x600 ceiling systems (the overall size of the mounting plate is 595x595).

Product Description
WID-4 Square ceiling diffuser with 4 way air pattern WID-3 Square ceiling diffuser with 3 way air pattern WID-2 Square ceiling diffuser with 2 way air pattern WID-R Square ceiling diffuser for return air WKDV Supply air plenum WKDVI Insulated supply air plenum WKRV Return air plenum MPV Modular plate WWM Fixing set

Features
Supply and exhaust applications of warm, cool and isothermal air High induction characteristics Variety of air patterns Suitable for modular ceiling systems Excellent free-jet performance

Finishes
PPM9010 (RAL 9010 20% Gloss White) Other colours available on request

Advantages
Excellent aerodynamic performance Good mixing with room air Can be used for full tile replacement Short throws WxH
D1

40 K

595 x 595

WID + MPV

Order Example:
WID-3-200-WKDVI Type Diffuser Pattern Spigot Diameter Plenum Type

W x H D1
210x210 210x210 310x310 410x410 510x510 125 160 200 250 315

D2
125 160 200 250*oval 315*oval

E
196 231 270 288 288

K
33 33 40 55 70 20 20 20 20 20

60

X
27.5 27.5 27.5 27.5 27.5 35 35 35 35 35

* The perimeter of the oval is equivalent to the circumference of a circle of the stated diameter

Waterloo 2.0

56

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Perforated Face Diffusers


WID
Ceiling Height 2.7 m Temperature Differential -10K Room Velocity Vr 0.15 m/s Lw based on diffuser sound power level minus 8 dB room absoption.

Selection Example WID-4-125 4 way supply


Air Volume 125 m3/h (35 I/s) Throw 0.4 m Pressure Drop 22 Pa Noise level Lw 25
Ps (Pa) Noise level (Lw)

All selections include the plenum


Faceplate Height Corrections
X (mm) T Throw (m)

Performance Tables
WID
m3/h l/s T 50 14 Ps Lp T 75 21 Ps Lp T 100 28 Ps Lp T 125 35 Ps Lp T 150 42 Ps Lp T 200 56 Ps Lp T 250 69 Ps Lp T 300 83 Ps Lp T 400 111 Ps Lp T 500 139 Ps Lp T 600 167 Ps Lp T 750 208 Ps Lp T 1000 278 Ps Lp T 1250 347 Ps Lp 0.2 10 0.3 14 21 0.4 0.3 22 10 25 0.5 0.4 29 15 28 20 0.7 0.6 0.5 45 25 12 34 24 0.7 0.6 33 19 29 9 0.9 0.8 0.7 48 23 32 21

20 27.5 35

x 1.0 x 0.9 x 0.8

x 1.0 x 0.6 x 0.5

+0 -2 -2

Supply 4 way
125 160 200 250 315 0.4 7 0.5 12 0.6 19 24

Supply 3 way
125 160 200 250 315 0.6 9 0.7 15 22 0.8 22 27

Supply 2 way
125 160 200 250 315

Exhaust
125 160 200 250 315

6 8 13 23 18 5 9 2 4 5 8 2 3 6 9 2 4 5 9 -

0.7 0.5 26 12 28 0.9 0.7 35 18 32 21 1.2 0.9 0.7 57 28 16 41 25 1.2 0.9 40 21 30 19 1.4 1.2 1.1 52 27 12 34 23 1.6 1.5 46 26 28 23 2.0 1.8 1.6 60 27 12 32 26 22 2.2 2.0 40 18 30 26 2.8 2.4 60 25 38 30 3.1 40 36 3.8 57 40

0.9 1.2 32 16 33 1.0 0.8 43 22 36 25 1.4 1.2 1.1 69 35 18 44 27 18 1.6 1.5 50 25 33 22 2.0 1.7 1.5 66 35 15 38 26 21 2.4 2.1 57 26 33 26 3.1 2.6 2.3 85 38 15 40 30 24 3.2 2.7 53 19 33 28 3.3 28 33 4.4 46 38 84 38 15 36 23 48 21 28 75 31 13 34 22 52 21 29 15 91 34 14 35 23 52 19 29 36 13 24 -

1.2 1.0 37 17 26 20 1.5 1.3 1.1 50 24 11 30 24 21 1.5 1.3 33 16 28 24 1.9 1.6 50 22 34 28 2.3 36 34 2.9 52 38

60 24 29 19

Waterloo 2.0

57

Tel: +44 (0) 1622 711511

Luminaire Diffusers
LUMDF
Introduction
The Waterloo Luminaire unit is a technically advanced form of light and air terminal which provides multidirectional supply air capability. Available in both supply and extract versions, the units are designed as a tile replacement fitting which simply drops into any standard 600mm square T grid. Furthermore, the use of a special lightweight plenum construction limits the overall weight of the supply unit to 9.6kg for the basic unit and 10.3kg with the emergency pack, thereby eliminating the requirement for additional overhead support. Plenums are provided with a quick fix clip enabling the inlet spigot to be conveniently configured to suit the supply duct arrangement. Both supply and extract units are available with optional emergency power supplies and all come pre-wired with 2m of flying lead. Supply units can be specified with optional cord operated dampers, which together with the calibration port on the light case (accessible after removal of the light diffuser), make site commissioning a quick and simple procedure.
6.5mm cable grommet for mains power and emergency power pack connection 157 50 Supply with 2m of cable pre-wired to fitting

Waterloo

486 i/s recess 596 o/a 600 grid centres

575 x 575

Features
Multi-directional air throw capability, quickly and easily adjustable from face of unit Lightweight construction Clip fixed plenum for on-site versatility Integrated commissioning port All units supplied complete with pre-wired flying lead Innovative heat extraction system from light fitting LGC 3 Cat fitting c/w airhandling linear slot diffuser

255

Benefits
Can be installed in central areas or adjacent to walls without degredation of performance or appearance Units can be quickly and easily relocated and re-commissioned if site layouts alter Supply and extract versions can be fitted into ceiling grid without overhead support Simple air flow measurement on site via built in port Aids reduction of heat load from lighting in occupied zone

Quick fix plenum clips

36W, TC-L compact fluorescent, cap: 2G11

Finishes
Plenum Box: Diffuser : Class O rated fire retardant board. Galvanised Steel

Order Example
LUMDF-S/PPM9010/0001/EP/FDC
Type Supply Finish Project Reference Optional Emergency Pack Optional Damper

Standards
Designed and manufactured to comply with EN 605982.1. Emergency versions with louvre or TP(a) diffuser attachments compy with EN 60598 .2.22. Class 1 Electrical, CIBSE LG3 VDT, CE Mark

Waterloo 2.0

58

Tel: +44 (0) 1622 711511

596 x 596

Lamp Types

120

390

Pitot measurement point (remove light diffuser for access)

Waterloo
Performance

Luminaire Diffusers
LUMDF
Jet throws are based on the horizontal distance from the centre of the unit to the point where the jet velocity has decayed to 0.5 m/s. Data is valid for isothermal conditions or cooling differentials of up to 10C. Noise levels are based on peak sound power level plotted onto NR and assume a typical room absorption allowance of 8dB (LRlp ref 8dB abs.) Octave band sound power level data is available on request.

Performance Data

Photometric Data
90 90

4 Way Pattern
Throw (m) Pressure (Pa) Noise Level NRLP

Air flow rate (l/s)


40 50 60 70 80 90 3.0 24 28 1.25 1.5 6 8 2.0 2.25 2.5 11 15 21 19 25

60

60

30

30

3 Way Pattern
Throw (m) Pressure (Pa) Noise Level NRLP

Air flow rate (l/s)


40 1.5 8 50 60 70 80 90 2.0 2.75 3.5 12 17 20 22 25

Emergency factor
Room index LP
1 2 3 4 5 0.09 0.10 0.10 0.10 0.10

2 Way Pattern
Throw (m) Pressure (Pa) Noise Level NRLP

Air flow rate (l/s)


40 2.5 13 50 3.0 20 22 60 4.0 28 28 70 80 90

URF
C
0.6

W
0.6 0.5 0.3

0.2 0.58 0.65 0.67 0.68 0.69 0.56 0.63 0.66 0.66 0.69 0.53 0.61 0.65 0.64 0.67 0.2 0.57 0.64 0.66 0.68 0.68 0.55 0.63 0.65 0.67 0.67 0.53 0.61 0.64 0.65 0.66 0.2 0.58 0.62 0.64 0.65 0.65 0.54 0.61 0.63 0.64 0.65 0.53 0.59 0.62 0.63 0.64 Pressure (Pa)

Exhaust

Air flow rate (l/s)


40 4 50 6 60 8 70 10 80 13 90 16

0.7

0.6 0.5 0.3

0.8

0.6 0.5 0.3

For additional lighting information refer to leaflets LAL011/1 issue 3 and LAL011/2 issue 3, copies of which are available upon request.

Waterloo 2.0

59

Tel: +44 (0) 1622 711511

Fixed Blade Swirl Diffusers


SDFC SDFS
Introduction
Waterloo Air Products range of fixed blade swirl diffusers presents an attractive and aerodynamically efficient alternative to conventional circular or square ceiling air terminals. The diffusers are designed to produce a horizontal, radial air pattern with a turbulent, high induction jet characteristic and are ideally suited for applications with high heating or cooling differentials. Manufactured from aluminium with press formed blades, the units are available in a range of six ISO sizes in either circular (type SDFC) or square format (types SDFS) and can be supplied complete with a duct mounting collar for easy assembly. The steel duct mounting collar can be used as a means of fixing and supporting the diffuser from rigid ductwork, or alternatively, ceiling support brackets (supplied as standard) can be fitted for use with flexible ducting.

Waterloo
SDFC
G D1 o/s Duct mounting collar Ceiling support brackets 65 D1 o/s

SDFS

65

Edge detail to suit grid type as shown below

To suit nominal grid type & size

Product Description
SDFC SDFS DM*** WTP*** FDC1 FDQ1 LINED Circular face swirl diffuser Square face swirl diffuser Duct collar Side entry plenum box (*** is replaced with nominal size) - see order example Cord operated flap damper Quadrant operated flap damper 6mm Class O fire rated acoustic lining

SDFC

To suit nominal grid type & size

SDFS

*75

Please note the duct collar is not required when ordering diffusers with plenums. See table
20

Sizes Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request
C

D2

50

12

*125 WITH QUADRANT OPERATED FLAP DAMPERS.

SDFS Frame Styles and Grid Sizes


SDFC Size
125 160 200 250 315 400

Diffuser + Collar
0.3 kg 0.4 kg 0.6 kg 0.7 kg 1.0 kg 1.5 kg

Plenum
1.6 kg 1.9 kg

Exposed 'T' - E

Tegular frame - T8

Tegular frame - T16

12

5.1 kg 7.4 kg 9.5 kg

Frame size 295, 495, 595, 745 300, 500, 600, 750 Nom Grids

Frame size 483,583, 733 500, 600, 750 Nom Grids

Frame size 483,583, 733 500, 600, 750 Nom Grids

SDFS Grid Size


300 x 300 500 x 500 600 x 600 750 x 750

Diffuser + Collar
1.1 kg 1.5 kg 2.1 kg 3.2 kg

Plenum For plenum weights use data above based on nominal neck size

Order Example
SDFS-250/T16/500/PPM9010 /DM /WTP/FDC1/LINED

Please note a 300x300 grid is only available for an exposed lay-in type, and with neck sizes up to 250. Nom. Available Grid Sizes A for SDFS Size 125 160 200 250 315 400
200 250 300 350 450 535 300, 500, 600 or 750 300, 500, 600 or 750 300, 500, 600 or 750 300, 500, 600 or 750 500, 600 or 750 500, 600 or 750

C
215 240 275 315 370 435

D1 D2 123 158 198 248 313 397 97 122 157 197 247 312

E
320 320 420 420 520 580

F
300 300 400 400 500 560

G 160 200 250 300 370 460

H
25 25 25 25 30 30

Type Nominal Size Frame Style & Grid (if square diffuser) Colour Finish Duct Collar (DM) or Plenum (WTP) Plenum Spigot Damper (if required) Acoustic Plenum Lining (if required)

Waterloo 2.0

60

Tel: +44 (0) 1622 711511

16

4.5 kg

50

Waterloo
Selection Criteria

Fixed Blade Swirl Diffusers


SDFC SDFS

Jet throw data is expressed in metres and is based on a terminal velocity of 0.5m/s and a 10C cooling differential. For isothermal or 10C heating conditions apply a factor of 1.15 to the throws. NR levels are based on sound pressure levels with an assumed 8dB room absorption factor allowed. Pressure loss data is shown in terms of static pressure loss (Pa) based on a diffuser fitted with a DM collar, or for a diffuser installed in a WTP plenum.

Selection Example SDFC/315


Air flow rate 120 l/s Ducted Diffuser Jet throw 1.9m Static Pressure Loss 25 Pa Noise level NR 30 Plenum Mounted Diffuser Jet throw 1.9m Static Pressure Loss 31 Pa Noise level NR 32

Performance Table
SDFC SDFS
Diameter

Supply Air Volume


m3/h l/s Jet Throw Lw Duct 36 10 72 20 108 30 144 40 180 50 216 60 252 70 288 80 324 90 360 100 432 120 504 140 576 160 648 180 720 200 810 225 900 250 990 275 1080 300

0.3 20 22 16 20

0.5 34 36 47 59 0.4 10 12 0.4 4 5 0.6 24 26 21 26 0.6 9 11 1.0 33 35 25 31 0.9 20 22 15 19 0.6 5 6 1.3 39 41 55 69 1.3 27 29 22 28 1.0 8 10 0.8 5 6 1.5 32 34 30 38 1.3 20 11 14 1.0 7 9 1.8 36 38 40 50 1.4 21 23 15 19 1.2 9 11 1.6 24 26 19 24 1.3 20 11 14 1.8 28 30 24 30 1.4 22 24 14 17 2.1 31 33 29 36 1.6 25 27 17 21 1.0 3 4 2.3 37 39 40 50 1.9 30 32 25 31 1.2 5 6 2.2 35 37 33 41 1.3 6 8 2.4 38 40 41 51 1.7 8 10 2.2 20 11 14 2.4 22 24 13 16 2.6 25 27 17 21 3.0 28 30 20 25 3.4 30 32 24 30 3.6 33 35 29 36

125

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

160

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

200

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

250

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

315

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

400

Lw Plenum Ps Duct Ps Plenum

For exhaust applications add 3dB to the NR level and multiply pressure loss by 1.1

Waterloo 2.0

61

Tel: +44 (0) 1622 711511

Perforated Face Swirl Diffusers


SDFS-P
Introduction
Waterloo Air Products range of perforated face, fixed blade swirl diffusers presents an attractive and aerodynamically efficient alternative to conventional circular or square ceiling air terminals. The diffusers are designed to produce a horizontal, radial air pattern with a turbulent, high entrainment jet characteristic and are ideally suited for applications with high heating or cooling differentials. Manufactured from aluminium with press formed blades, the units have an aesthetically pleasing perforated face which has 4.5mm holes on an 8mm 45 pitch, giving a free area of 49.7%. They are available in a range of 4 standard ISO sizes in 3 different frame configurations to suit 4 nominal ceiling grid sizes. The steel duct mounting collar can be used as a means of fixing and supporting the diffuser from rigid ductwork, or alternatively, ceiling support brackets (supplied as standard) can be fitted for use with flexible ducting.
110 Perforated supply diffuser
D

Waterloo
Perforated extract diffuser (for ceiling void return only) Duct mounting collar Hanging brackets Removable Faceplate Hanging brackets 38 Removable Faceplate

SDFS-P

SDFS-P-E

Frame size

Frame size

Frame size

Frame size

Product Description
SDFS-P SDFS-P-E DM*** WTP*** Perforated face swirl diffuser Perforated face extract diffuser Duct collar Side entry plenum box (*** is replaced with nominal size) - see order example Cord operated flap damper Quadrant operated flap damper 6mm Class O fire rated acoustic lining
SDFS-P Perforated supply diffuser with WTP plenum
A
D1

FDC1 FDQ1 LINED

D1

Please note the duct collar is not required when ordering diffusers with plenums.

Sizes
SDFS-P diffusers are available in ISO duct sizes ranging from 160mm to 400mm diameter, with 3 frame options to suit ceiling grid sizes of 300, 500, 600 & 750 square.

Modular Frame Styles and Grid Sizes


Exposed 'T' - E Tegular frame - T8 Tegular frame - T16

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours are available on request
Nom Neck & Grid Size Diffuser + Collar Plenum

70
21.5

75

27.5

21.5

Frame 295, 495, 595, Size 745 o/a


300, 500, 600, 750 Nom. Grid

Frame 483, 583, 733 Size


500, 600, 750 Nom. Grid

Frame 483, 583, 733 Size


500, 600, 750 Nom. Grid

160/300x300 250/500x500 315/500x500 315/600x600 400/600x600 400/750x750

1.6 kg 2.5 kg 2.5 kg 3.6 kg 3.6 kg 5.4 kg

1.9 kg 5.1 kg 7.4 kg 7.4 kg 9.5 kg 9.5 kg

Order Example
SDFS-P-250/500/T16/PPM9010 /DM /WTP/FDC1/LINED

Nom. Size
160 250 315 315 400 400

Grid Size
300 x 300 500 x 500 500 x 500 600 x 600 600 x 600 750 x 750

D1

A
300 400 500 500 560 560

B
320 420 520 520 580 580

H
255 330 380 380 445 445

158 248 313 313 397 397

122 197 247 247 312 312

Type Nominal size Frame style & grid Colour finish Duct collar (DM) or Plenum (WTP) Plenum spigot damper (if required) Acoustic plenum lining (if required)

Waterloo 2.0

62

Tel: +44 (0) 1622 711511

16

Waterloo

Perforated Face Swirl Diffusers


SDFS-P
Selection Criteria
Jet throw data is expressed in metres and is based on a terminal velocity of 0.5m/s and a 10C cooling differential. For isothermal or 10C heating conditions apply a factor of 1.15 to the throws. NR levels are based on sound pressure levels with an assumed 8dB room absorption factor allowed. Pressure loss data is shown in terms of static pressure loss (Pa) based on a diffuser fitted with a DM collar, or for a diffuser installed in a WTP plenum.

Selection Example
SDFS-P-315/E/600
Air Flow Rate 125 l/s Ducted Diffuser Jet Throw 1.2m Static Pressure Loss 11 Pa Noise level NR 23 Plenum Mounted Diffuser Jet Throw 1.2m Static Pressure Loss 18 Pa Noise Level NR 26

Performance Table
SDFS-P
Diameter Grid Size m3/h l/s Jet Throw Lw Duct 160 300 x 300 Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct 250 500 x 500 Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct 315 500 x 500 Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct 315 600 x 600 Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct 400 600 x 600 Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct 400 750 x 750 Lw Plenum Ps Duct Ps Plenum 108 30 0.6 22 22 14 18 144 40 1.0 31 31 27 33 0.4 4 5 180 50 1.3 37 37 44 54 0.5 7 8 0.7 10 12 0.4 3 5 1.0 28 28 19 23 0.7 6 8 0.7 4 8 1.7 35 35 30 36 0.9 9 12 0.9 7 12 0.5 4 5 1.2 25 27 14 19 1.2 23 26 11 18 0.8 6 8 0.8 6 7 1.8 31 33 19 27 1.8 29 31 17 26 1.2 8 10 1.2 8 10 2.5 36 38 26 35 2.5 33 36 22 35 1.5 23 11 14 1.5 22 24 11 14 1.8 24 27 14 18 1.8 26 28 15 19 2.1 29 32 18 23 2.1 30 32 18 25 2.3 33 35 23 30 2.3 33 35 23 32 2.7 37 39 26 35 2.7 36 37 28 38

Supply Air Volume


216 60 288 80 360 100 450 125 540 150 630 175 720 200 810 225 900 250 990 275

Exhaust Air Volume


Grid Size 300 x 300 500 x 500 600 x 600 750 x 750 (All selections <Lw 20) m3/h l/s Pressure loss Pa 108 30 2 144 40 3 180 50 5 216 60 8 1 288 80 15 2 1 1 3 2 2 5 2 2 7 3 3 10 4 4 6 6 7 7 9 9 11 11 360 100 450 125 540 150 630 175 720 200 810 225 900 250 990 275

Waterloo 2.0

63

Tel: +44 (0) 1622 711511

High Capacity Swirl Diffusers


SDFCH SDICH SDACH
Introduction
The Waterloo SDFCH are high capacity fixed blade swirl diffusers designed to produce a horizontal, radial air pattern with a turbulent, high entrainment jet characteristic and are ideally suited for applications with high heating or cooling differentials. The Waterloo SDICH is based on the SDFCH but allows the individual adjustment of blades to create a specifically required air pattern. The Waterloo SDACH is also based on the SDFCH but provides adjustment to the angle of all of the blades in unison in order to create the required air pattern. This can also be controlled remotely with an optional motor. Both the SDICH and the SDACH allow a continual adjustment from providing coanda effect to vertical dumping. They are particularly useful in areas that experience a varied thermal load, for example areas that are effected heavily by the changes in season. All products in the high capacity swirl diffuser range are suitable for ceilings up to 15m.
D

Waterloo

A overall

B ceiling cutout C neck

Features
Large size range Profiled frame Optional standard side entry plenum

Perforated Baffle

(125 with FDQ option) D2 i/s

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Advantages
High air volume capacity Standard top entry neck, or side entry with plenum box

J*

* Please note the total installed height assumes an overlap of 30mm on the diffuser neck / plenum connection. Nom A Size 200 250 315 400 500 630 280 330 430 530 650 790

Order Example
SDFCH/200/PPM9010/SDP/FDC1/LINED Type Nominal size Finish Plenum (if required) Plenum spigot damper Plenum acoustic lining

D
90 100 115 130 185 200

E
5 5 5 5 8 8

F
395 445 520 595 695 820

G
375 425 500 575 675 800

63

H
290 340 405 490 590 720

J*
413 473 553 653 808 953

D1 D2

225 275 360 450 550 680

197 247 312 397 497 627

197 247 312 397 497 627

200 250 315 400 500 630

Waterloo 2.0

64

Tel: +44 (0) 1622 711511

75

SDFCH Large format, high capacity fixed swirl diffuser SDICH Large format, high capacity swirl diffuser with individually adjustable blades SDACH Large format, high capacity swirl diffuser with connected adjustable blades SDP Side entry plenum box FDC1 Cord operated flap damper FDQ1 Quadrant operated flap damper LINED 6mm Class O fire rated acoustic lining M Optional actuator- for the SDACH only

E
F

Product Description

G i/s D1 o/s

FDC, FDQ damper options

75

Waterloo
Selection Criteria

High Capacity Swirl Diffusers


SDFCH SDICH SDACH
Selection Example SDFCH/500
Air Flow Rate 500 l/s Ducted Diffuser Jet Throw 4.0m Static Pressure Loss 21 Pa Noise Level NR 21 Plenum Mounted Diffuser Jet Throw 4.0m Static Pressure Loss 32 Pa Noise Level NR 27 Plenum(kg) 5.5 7.0 9.0 13.5 18.5 25 Jet throw data is for a ceiling mounted diffuser and is based on a cooling differential of 10C and a jet terminal velocity of 0.5m/s For isothermal conditions apply a factor of 1.1 to the throws. For 10C heating applications apply a factor of 1.2 to the throws. For duct mounted installations without a ceiling reduce jet throws by a factor of 0.7 Ps is the static pressure loss in Pa and is shown for a ducted diffuser or for a diffuser installed in an SDP plenum. NR levels are based on sound pressure levels with an assumed 8dB room absorption allowance. Nom Size 200 250 315 400 500 630 Diffuser (kg) 0.5 0.7 1.2 1.7 3.5 4.5

Performance Table
SDFCH
Diameter m3/h l/s Jet Throw Lw Duct

Also suitable for the SDICH and SDACH when set in the optimum coanda effect position Supply Air Volume

72 144 216 288 360 432 540 630 720 810 900 1080 1260 1440 1620 1800 2160 2520 2880 3240 3600 3960 4320 20 40 60 80 100 120 150 175 200 225 250 300 350 400 450 500 600 700 800 900 1000 1100 1200

0.4 0.9 1.3 1.6 1.9 3 3 10 23 40 12 27 47 8 22 22 14 62 70 30 30 22 33 50 66 26 40 59 80 7 9 24 29 23 30 35 11 15 21 14 20 27 22 20 25 5 6 6 8 28 35 27 30 9 11 35 43 31 34 11 14 43 56 34 37 14 18 20 25 22 27 35 26 29 10 13 21 35 47 32 35 13 18 25 45 58 37 40 4.7 5.3 30 40 27 37 12 16 21 40 54 32 42 7.0 7.7 8.2 34 44 29 36 40 52 32 39 49 62 35 42 16 22 25 21 28 21 29 26 36 25 33 17 22 29 6 9 21 27 21 32 8 11 -

200

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

1.1 1.3 1.6 1.8 2.0 2.2 10 17

250

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

1.4 1.6 1.8 2.0 2.4 2.8 3.3

315

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

1.7 1.9 2.2 2.4 2.8 3.5 3.8 4.2 4.7

400

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

3.2 3.5 3.7 4.0

500

Lw Plenum Ps Duct Ps Plenum Jet Throw Lw Duct

2.8 3.1

3.8 4.4 5.4 6.1

630

Lw Plenum Ps Duct Ps Plenum

For exhaust applications add 3dB to the NR level and multiply pressure loss by 1.1

Waterloo 2.0

65

Tel: +44 (0) 1622 711511

Vane Swirl Diffusers


SDVS SDVC
Introduction
The Waterloo vane swirl diffusers are designed for areas where rapid mixing of supply air is required in rooms of ceiling height between 2.6m and 4m.

Waterloo
SDVSA-V / SDVCA-V
B A

Product Description
SDVSA Square plate vane swirl diffuser with radial pattern (angled slot) SDVCA Circular plate vane swirl diffuser with radial pattern (angled slot) SDVSB Square plate vane swirl diffuser with radial pattern (normal slot) SDVCB Circular plate vane swirl diffuser with radial pattern (normal slot) S Side entry plenum V Top entry plenum 200 D x D / D

SDVSA-S / SDVCA-S
CxC 60

Features
A G D x D / D

High air volume capacity Standard top entry neck, or side entry with plenum box Reversible polymer blades enabling different discharge directions Flat or ribbed blade appearance Attractive lightweight design Side or top entry plenums available In order to keep the same appearance the same design is used for supply and extract diffusers. Meaning that there is no requirement to identify this on the order.

60

Finishes
Black or white polymer vanes (to be specified on order) PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Advantages
Suitable for high ceilings (relative to other diffusers) Rapid induction of supply air

Air discharge - all left / all right

Order Example
SDVSA-600-24/PPM9010/S Type Frontplate size Front face pattern Finish Plenum type Air discharge left Air discharge right

Waterloo 2.0

66

Tel: +44 (0) 1622 711511

H F

Waterloo
SDVSA
SDVSA-300-8
298

Vane Swirl Diffusers


SDVS SDVC
SDVCA
SDVCA-300-8

SDVSB
298

SDVCB
SDVCB-300-8

300

SDVSB-300-8

SDVSA-400-16 SDVSA-500-16 SDVSA-600-16 SDVSA-625-16


398/498 598/623

SDVCA-400-16 SDVCA-500-16 SDVCA-600-16 SDVCA-625-16


298

298

300

SDVSA-500-24

SDVCA-500-24

498

398/498 598/623

398/498 598/623

398/498 598/623

400/500 600/625

SDVSB-400-16 SDVSB-500-16 SDVSB-600-16 SDVSB-625-16

SDVCB-400-16 SDVCB-500-16 SDVCB-600-16 SDVCB-625-16

400/500 600/625

SDVSB-500-24
498

SDVCB-500-24

500

SDVSA-600-24 SDVSA-625-24

SDVCA-600-24 SDVCA-625-24

598/623

498

498

500

SDVSB-600-40 SDVSB-625-40

SDVCB-600-40 SDVCB-625-40

SDVSA-600-48 SDVSA-625-48

SDVCA-600-48 SDVCA-625-48

598/623

598/623

598/623

598/623

600/625

600/625

SDVSB-800-64 SDVSB-825-64

SDVCB-800-64 SDVCB-825-64

598/623

600/625

SDVSA-800-72 SDVSA-825-72

SDVCA-800-72 SDVCA-825-72

798/823

798/823

800/825

Fixing
Sizes 300 - 600 (inclusive) 1 screw central Sizes 625 - 825 (inclusive) 4 screws
798/823

800/825

Waterloo 2.0

67

Tel: +44 (0) 1622 711511

Vane Swirl Diffusers


SDVS SDVC
Performance Table
SDVSA SDVCA
m3/h l/s T 54 15 Ps Lp T 72 20 Ps Lp T 90 25 Ps Lp T 108 30 Ps Lp T 144 40 Ps Lp T 180 50 Ps Lp T 216 60 Ps Lp T 252 70 Ps Lp T 288 80 Ps Lp T 360 100 Ps Lp T 450 125 Ps Lp T 540 150 Ps Lp T 720 200 Ps Lp T 900 250 Ps Lp T 1080 300 Ps Lp T 1260 350 Ps Lp T 1440 400 Ps Lp T 1620 450 Ps Lp T 1800 500 Ps Lp T 2160 600 Ps Lp

Waterloo
Exhaust with side entry plenum
400-16 600-24 600-48 800-72 500-16 300-8 500-24 600-16 625-24 625-48 825-72 625-16 300-8

Supply
400-16 600-24 600-48 800-72 500-16 300-8 500-24 600-16 625-24 625-48 825-72 625-16

Exhaust with top entry plenum


400-16 600-24 600-48 800-72 500-16 500-24 600-16 625-24 625-48 825-72 625-16

0.7 3 0.9 6 1.1 9 10 1.3 12 15 1.6 22 22 1.9 34 28 2.1 50 33 2.4 68 37 2.6 88 40 1.1 3 1.3 6 1.4 9 13 1.6 14 17 1.7 18 21 1.8 24 25 2.0 38 31 2.3 59 37 1.1 3 1.3 4 1.4 6 12 1.6 8 16 1.7 11 19 2.0 17 25 2.3 26 31 2.6 38 35 1.3 2 1.4 3 1.5 4 7 1.7 7 13 1.9 11 19 2.1 15 23 2.5 27 31 2.8 42 37 1.8 5 1.9 7 13 2.0 10 18 2.2 18 26 2.4 28 31 2.5 41 36 1.9 3 2.1 6 15 2.3 9 21 2.5 13 25 2.6 17 29 2.8 23 33 2.9 29 36 3.0 35 39 45 36 45 32 65 37 93 39 36 33 91 40 37 28 91 40 73 36 28 29 86 41 72 36 29 25 70 36 56 32 22 25 66 37 55 32 22 21 118 42 51 31 41 27 16 21 108 41 48 33 40 27 16 16 82 37 36 26 29 21 11 15 75 36 34 27 28 22 11 10 85 37 52 30 23 19 18 15 7 8 67 37 48 29 21 20 18 15 48 28 29 21 13 10 38 28 27 20 12 12 10 6 103 37 33 23 20 15 73 35 26 22 19 14 8 6 66 30 21 16 13 9 47 28 17 16 12 8 42 23 14 9 30 22 11 9 32 19 23 18 24 15 17 13 16 9 12 7 7 4 -

Waterloo 2.0

68

Tel: +44 (0) 1622 711511

Waterloo
Performance Table

Vane Swirl Diffusers


SDVS SDVC
Supply
400-16 500-16 600-16 625-16

SDVSB SDVCB
300-8 m3/h 54 l/s 15 T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp 0.6 3 0.8 5 0.9 6 1.0 8 1.2 12 25 1.4 21 31 1.6 30 36 1.8 41 41 2.2 54 45

500-24

600-40 625-40

800-64 825-64

72

20

90

25

108

30

144

40

180

50

1.2 17 27 1.4 24 31 1.6 30 36 1.9 40 40 2.3 62 45 1.0 7 1.1 9 22 1.3 11 26 1.5 17 32 1.8 26 39 2.1 38 43 1.0 6 22 1.5 11 27 1.6 19 32 2.1 34 40 2.5 56 46 0.9 1 1.1 7 21 1.5 14 29 1.8 22 35 2.2 31 39 2.5 43 44

216

60

252

70

288

80

360

100

450

125

540

150

720

200

900

250

1080

300

1260

350

Waterloo 2.0

69

Tel: +44 (0) 1622 711511

Circular Perforated Face Diffusers


RWI

Waterloo
WxH 50

Introduction
The Waterloo high induction, perforated face circular diffuser type RWI, has an adjustable radial diffusion pattern and provides excellent induction characteristics. The diffuser and faceplate are manufactured from aluminium with the plenum being zintec steel, and have been designed with modern ceiling types in mind. With their perforated face design, these diffusers ensure that the primary air is already mixed inside the diffuser with the room air, which results in a rapid temperature decay and short throw.

Product Description
RWI RWI-R UKDV UKDVI UKRV UKRVI Circular supply diffuser with perforated faceplate Circular return diffuser with perforated faceplate Supply air plenum Insulated supply air plenum Return air plenum Insulated return air plenum 7.5
D1 X A

RWI + UKDVI
WxH 50

Features
Supply and exhaust applications for heating, cooling and isothermal conditions Variety of air patterns Suitable for modular ceiling systems E

Finishes
PPM9010 (RAL 9010 20% Gloss White) Other colours are available on request Excellent aerodynamic performance No ceiling effect required Short throw 7.5

Advantages

D1 X A

RWI-R + UKRV

Z 7.5
D1 X A

D2

Excellent induction characteristics

D2

RWI
Nom Size WxH D1
100 125 160 200 250 315 210x210 210x210 310x310 310x310 410x410 510x510

Order Example
RWI-200/UKDV-160 Type Diameter Plenum Type Plenum Spigot Diameter

D2

overall aperture 190 230 270 370 470 570 175 215 255 345 440 535

E
205 215 295 295 365 435

K
55 60 65 70 75 90

L
12.5 20.0 27.5 27.5 35.0 35.0 19 19 19 19 19 19 / / / / / /

Z
26.5 26.5 26.5 26.5 26.5 26.5 / / / / / / 34 34 34 34 34 34

100 125 160 200 250 315

Waterloo 2.0

70

Tel: +44 (0) 1622 711511

Waterloo

Circular Perforated Face Diffusers


RWI
Selection Criteria
Ceiling Height 2.7m Temperature Differential -11K Average room velocity Vr 0.15m/s NC is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB

Selection Example RWI-200


Air Volume 111 I/s Throw 1.2 m Pressure Drop 37 Pa Noise Level NR 26

All selections include the plenum

Faceplate Height Corrections

Z (mm)

T Throw (m)

Pressure (Pa)

Noise level (NR)

19 26.5 34

x 1.0 x 0.9 x 0.8

x 1.0 x 0.6 x 0.5

+0 -1 -2

Performance Table RWI


m3/h 50 l/s 14 T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw 100 Dia 0.2 10 0.3 22 24 0.4 35 28 0.5 56 33 125 Dia

Supply
160 Dia 200 Dia 250 Dia 315 Dia

Exhaust
100 125 160 Dia Dia Dia 7 200 250 315 Dia Dia Dia

75

21

100

28

125

35

150

42

200

56

0.2 10 0.3 14 21 0.4 22 25 0.5 29 28 0.7 45 34

21 22 30 26 0.3 10 0.4 15 20 0.6 25 24 0.7 33 29 1.1 48 32 46 31 6 10 13 0.5 12 0.6 19 0.9 23 21 1.2 37 26 1.5 50 30 23 18 36 24 0.8 9 1.0 17 20 1.3 24 24 1.5 33 28 1.9 50 34 52 29 91 35 1.1 11 21 1.3 16 24 1.6 22 28 2.3 36 34 2.9 52 38 5 9 13 19 34 23 52 29 75 34 2 4 5 8 14 21 15 31 22 48 28 84 36 2 3 6 9 13 21 38 23 60 29 2 4 5 9 15 24 19

250

69

300

83

400

111

500

139

600

167

750

208

1000 278

1250 347

Waterloo 2.0

71

Tel: +44 (0) 1622 711511

Circular Diffusers
RWK

Waterloo
WxH 50

Introduction
The Waterloo circular diffuser type RWK has an adjustable radial diffusion pattern and provides excellent induction characteristics. The diffuser and faceplate are manufactured from aluminium and the plenum is zintec steel. The shape of both the plenum and the adjustable faceplate ensure an excellent air pattern, and the internal control disc can also be adjusted to achieve high induction rates and a low sound power level.

Product Description
RWK RWK-R UKDV UKDVI UKRV UKRVI Circular supply diffuser with plain faceplate Circular return diffuser with plain faceplate Supply air plenum Insulated supply air plenum Return air plenum Insulated return air plenum 7.5
D1 X A

RWK + UKDVI
WxH 50

Features
Supply and exhaust applications for heating, cooling and isothermal conditions Excellent induction characteristics Variety of air patterns E Suitable for modular ceiling systems

Finishes
Z 7.5
D1 X A

PPM9010 (RAL 9010 20% Gloss White) Other colours are available on request

Advantages
Excellent aerodynamic performance No ceiling effect required Short throw

RWK-R + UKRV

7.5

D1 X A

RWK

Order Example
RWK-250/UKDV-250 Type Diameter Plenum Type Plenum Spigot Diameter

Nom Size WxH D1


100 125 160 200 250 315 210x210 210x210 310x310 310x310 410x410 510x510

D2

overall aperture 190 230 270 370 470 570 175 215 255 345 440 535

E
205 215 295 295 365 435

K
55 60 65 70 75 90

L
12.5 20.0 27.5 27.5 35.0 35.0 19 19 19 19 19 19 / / / / / /

Z
26.5 26.5 26.5 26.5 26.5 26.5 / / / / / / 34 34 34 34 34 34

100 125 160 200 250 315

Waterloo 2.0

72

Tel: +44 (0) 1622 711511

D2

D2

Waterloo
Selection Criteria
Ceiling Height 2.7m Temperature Differential -11K Average room velocity Vr 0.15m/s NC is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB

Circular Diffusers
RWK
Selection Example RWK-125
Air Volume 42 I/s Throw 1.1 m Pressure Drop 29 Pa Noise Level NR 20

All selections include the plenum

Faceplate Height Corrections

Z (mm)

T Throw (m)

Pressure (Pa)

Noise level (NR)

19 26.5 34

x 1.0 x 0.9 x 0.8

1.0 x 0.6 x 0.5

0 -1 -2

Performance Table RWK


m3/h
50

Supply
100 125 160 200 250 315 Dia Dia Dia Dia Dia Dia T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw 0.5 6 0.6 0.5 20 7 0.8 0.7 36 12 20 1.0 0.9 0.7 50 20 8 24 1.1 0.8 29 12 20 1.3 1.1 48 18 31 1.4 28 23 1.7 40 27

Exhaust
100 125 160 200 250 315 Dia Dia Dia Dia Dia Dia 7 17 27 39 21 51 27 10 16 22 40 20 9 13 23 36 21 53 20 8 14 20 36 56 24 80 28 12 18 21 26 24 39 30 10 14 23 24 29 32 32

l/s
14

75

21

100

28

125

35

150

42

200

56

250

69

300

83

400

111

500

139

600

167

750

208

1000

278

1250

347

1.3 12 1.5 1.4 16 7 1.9 1.7 30 13 24 21 2.3 2.1 1.2 45 20 7 29 26 2.5 1.5 30 10 31 21 3.1 2.1 48 15 40 28 2.7 30 34 3.5 54 40

60 26

Waterloo 2.0

73

Tel: +44 (0) 1622 711511

Circular Plain Faced Diffusers


RWV

Waterloo
WxH 50

Introduction
The Waterloo circular plain faced diffuser type RWV has a solid circular face providing a 360 air pattern with excellent air induction characteristics. This all aluminium diffuser is fully adjustable allowing horizontal and vertical discharge patterns. With their high induction ratios these diffusers ensure rapid primary and secondary air mixing with low noise levels. The diffusers are available with zintec steel plenums with the option of thermal insulation lining on supply plenums. E

Product Description
RWV RWV-R UKDV UKDVI UKRV UKRVI Circular supply diffuser with plain faceplate Circular return diffuser with plain faceplate Supply air plenum Insulated supply air plenum Return air plenum Insulated return air plenum

7.5

D1 X A

RWV + UKDVI
WxH 50

Features
and isothermal conditions Excellent induction characteristics Variety of air patterns Suitable for modular ceiling systems E
D2

Supply and exhaust applications for heating, cooling

Finishes
7.5 PPM9010 (RAL 9010 20% Gloss White) Other colours are available on request
D1 X A

Advantages
Excellent aerodynamic performance No ceiling effect required Short throw

RWV-R + UKRV

7.5

D1

Horizontal Jet (Lowered Face Plate)

Vertical Jet (Raised Face Plate) Nom Size D1


100 125 160 200 250 315

X A

RWV
WxH
210x210 210x210 310x310 310x310 410x410 510x510
D2 A X

Order Example
RWV-160/UKDV-160 Type Diameter Plenum Type Plenum Spigot Diameter

overall aperture 190 230 270 370 470 570 175 215 255 345 440 535

E
205 215 295 295 365 435

D2

K
55 60 65 70 75 90

L
12.5 20.0 27.5 27.5 35.0 35.0

100 125 160 200 250 315

Waterloo 2.0

74

Tel: +44 (0) 1622 711511

Waterloo

Circular Plain Faced Diffusers


RWV
Selection Criteria
Ceiling Height 2.7m Temperature Differential -11K Average room velocity Vr 0.15m/s NC is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB

(Horizontal throw)
Air Volume 139 I/s Throw 3.6m Pressure Drop 28 Pa Noise Level NR 30

Selection Example RWV-200

All selections include the plenum

Performance Table RWV


m3/h 50 l/s

Horizontal
100 125 160 200 250 315 Dia Dia Dia Dia Dia Dia T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw T Ps Lw 0.7 6 1.2 12 1.6 1.3 20 7 21 2.1 1.5 1.4 31 11 4 27 2.5 1.7 1.6 42 16 6 32 20 2.1 2.0 28 11 27 2.3 16 2.7 23 25 1.4 5 1.8 8 2.2 1.8 11 8 2.9 2.2 18 14 22 3.6 2.5 2.2 28 21 8 30 20 4.3 2.9 2.7 40 30 18 33 26 3.5 3.3 45 26 34 25 4.0 47 34 4.7 70 40

Vertical
100 125 160 200 250 315 Dia Dia Dia Dia Dia Dia 1.2 20 1.8 44 20 2.7 2.0 80 40 26 3.8 3.0 2.0 125 60 16 32 22 3.9 2.6 90 24 26 5.2 3.7 150 42 32 22 5.0 65 26 6.4 90 31 2.9 20 4.0 32 20 5.2 4.6 46 22 23 7.8 6.7 81 39 28 22 10.0 9.5 7.6 127 61 24 34 27 12.0 10.0 87 35 32 22 14.0 12.0 136 54 36 27 14.0 96 33

Exhaust
100 125 160 200 250 315 Dia Dia Dia Dia Dia Dia 4 10 17 26 24 33 30 5 9 13 23 25 39 40 52 37 4 9 14 20 22 33 34 7 10 16 21 24 27 34 32 11 18 26 28 40 34 6 14 21 25 31 32

14

75

21

100

28

125

35

150

42

200

56

250

69

300

83

400

111

500

139

600

167

750

208

1000

278

1250

346

Waterloo 2.0

75

Tel: +44 (0) 1622 711511

Small Format Circular Diffusers


MC
Introduction
The Waterloo MC diffuser has been designed for both supply and exhaust applications requiring compact circular diffusers; unlike conventional high aspiration diffusers the MC has a small overall to neck size ratio. The diffusers are adjustable to produce horizontal or vertical air patterns.
C Ceiling cut out

Waterloo

DUCT TO CEILING FACE DUCT TO CEILING FACE

Manufacture
The MC diffusers are constructed from steel spinnings retained on aluminium spider braces. Horizontal diffusion
A Duct / Diffuser size

Product Description
MC LD ED&LD Blind Fix Small format circular diffuser Butterfly type louvre damper Equalising deflector & louvre damper Special blind fixing (see below)

Compact frame design Robust steel construction Adjustable for vertical or horizontal air patterns Vertical Projection

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White)) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Weights
MC/150 MC/200 MC/300 MC/450 1.0 2.1 3.4 4.8 kg kg kg kg

Accessories
B

Diffuser O/A size

LD - Standard arrangement for supply ducts. Adjustable through diffuser face.

ED&LD - Equalisation at stub duct take off with volume control at diffuser face.

Standard Screw through duct

Special Blind fixing Specify when ordering

Order Example
MC/150/PPM9010/LD
Type Diffuser Size Finish Extras

Diffuser & Overall Ceiling Duct Size Diameter Opening A B C 150 200 300 450 228 305 381 533 203 280 356 508

Waterloo 2.0

76

Tel: +44 (0) 1622 711511

57

89

Features

57

89

Waterloo
Selection Criteria

Small Format Circular Diffusers


MC
Selection Example
MC/200
Total air flow rate 94 l/s Horizontal Supply Application Throw Min - Max 1.5 - 3.0m Noise Level NC21 Pressure Loss 21Pa Exhaust Application Noise Level NC23 Pressure Loss 31Pa Supply Vertical Projection Projection downward throw to a terminal velocity vt = 0.5 m/s

NC level: equal to the peak sound power level on an NC curve less 8dB for normal room absorption. Pressure Loss (Pa): static pressure loss of the diffuser. Throw: radius of diffusion and projection see individual tables Supply Horizontal Diffusion Radius of diffusion. Minimum space covered by one diffuser which results in a mean room air movement of 0.25 m/s Maximum space covered by one diffuser which results in a mean room air movement of 0.10 m/s

Performance Tables

MC
m3/h 150 Dia 65

Air Volume
126 191 252 317 150 Dia

MC
m3/h l/s Projection (m) Lw Ps m3/h l/s Projection (m) Lw Ps m3/h l/s Projection (m) Lw Ps m3/h l/s Projection (m) Lw Ps 65 18 0.9 4 112 31 1.3 4 256 71 2.0 5 572 159 3.2 8 35 1.5 17 14

Air Volume
126 191 53 2.5 28 33 338 94 3.0 31 38 763 212 4.6 34 48 1717 477 7.6 40 75 252 70 3.5 36 56 454 126 4.3 39 65 1016 282 6.3 43 80 2290 636 10.1 48 128 317 88 4.6 43 91 565 157 5.2 46 105 1271 353 7.8 49 125 2862 795 14.2 55 200

l/s 18 35 53 70 88 Min - Max (m) 0.5-1.0 0.8-1.5 1.0-2.1 1.5-3.0 2.0-4.0 Lw 18 26 34 Ps 2 9 21 37 58 112 227 338 454 565 m3/h l/s 31 63 94 126 157 Min - Max (m) 0.5-1.0 0.9-1.8 1.5-3.0 2.0-4.0 2.5-5.0 Lw 21 31 40 Ps 2 9 21 37 58 256 508 763 1016 1271 m3/h l/s 71 141 212 282 353 Min - Max (m) 0.7-1.5 1.4-2.8 2.1-4.2 2.8-5.6 5.0-10 Lw 18 29 39 46 Ps 2 9 21 37 58 572 1145 1717 2290 m3/h l/s 159 318 477 636 Min - Max (m) 1.3-2.5 2.5-5.0 3.8-7.6 5.0-10 Lw 21 35 45 Ps 4 18 41 72 2862 795 6.0-12 53 112

200 Dia

200 Dia

227 63 2.1 19 17 508 141 3.1 22 20 1145 318 5.0 27 32

300 Dia

300 Dia

450 Dia

450 Dia

Exhaust

MC
150 Dia m3/h l/s Lw Ps m3/h l/s Lw Ps m3/h l/s Lw Ps m3/h l/s Lw Ps 65 18 3 112 31 4 256 71 6 572 159 10

Air Volume
126 35 11 227 63 15 508 141 17 23 1145 318 27 35 191 53 18 23 338 94 23 31 763 212 32 49 1717 477 42 74 252 70 26 38 454 126 33 51 1016 282 42 80 2290 636 52 120 317 88 35 56 565 157 41 76 1271 353 50 120 2862 795 180

200 Dia

300 Dia

450 Dia

Waterloo 2.0

77

Tel: +44 (0) 1622 711511

Large Format Circular Diffusers


WR
Introduction
The Waterloo WR series is suitable for ceiling or exposed ductwork mounting and includes a rotating central core adjustment feature to provide settings for projection heating and spot cooling or conventional horizontal diffusion. Manufactured from aluminium spinnings, the diffusers are available with a range of dampers and equalising grids for effective control of air distribution.

Waterloo

DUCT

Product Description
WR LD WDD SD/ED Large format circular diffuser Butterfly type louvre damper (sizes 6-18 only) Opposed blade damper (sizes 21-24 only) Splitter damper/Equalising deflector
H

A (DUCT SIZE)

Features
High air handling capacity Easily removable central core assembly Simple installation Maintenance free, quality product Core adjustment feature Range of accessories Suitable for supply and exhaust

REMOVABLE CORE B G (OPENING SIZE) C

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Weights
WR-6 WR-8 WR-10 WR-12 WR-15 WR-18 WR-21 WR-24 1.2 kg 1.5 kg 2.3 kg 3.3 kg 5.5 kg 7.8 kg 10.5 kg 14.0 kg

Installation
Remove core from bayonet fixing and offer diffuser frame into opening. Screw fix through diffuser stack into duct. Replace core ensuring the bayonet fixing is secure.

Size A
6 8

E
5 5 5 6 6

J
61 74 96

152 305 340 51 203 407 457 64

136 320 85 149 430 85 171 530 85

Order Example
WR-15/PPM9010/LD
Type Diffuser size Finish Extras

10 254 508 569 86 12 305 610 680 95 15 381 762 851 121

180 640 85 105 206 800 85 131

18 457 914 1040 146 24 246 950 100 156 21 534 10801148 173 18 273 1100 100 183 24 610 10801170 173 18 273 1100 100 183

Waterloo 2.0

78

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Large Format Circular Diffusers


WR
Radius of Diffusion: The minimum and maximum throw covered by one diffuser which results in an average air velocity in the occupied zone of 0.25 m/s and 0.10 m/s respectively (based on 3.0m mounting height and 10C cooling) NC Level: Peak level on Noise Criteria curves based on sound power level re 10-12 W less 8dB room absorption. Pressure Loss (Pa): Static pressure loss at the supply duct. Cone Settings: Setting B: Flush for general applications producing horizontal diffusion (performance as table) Setting A: Projection setting multiply tabulated Ps x 1.7, add 2dB to NC values. Setting C: Exposed duct setting multiply tabulated Ps x 0.8, subtract 2dB from NC values. Exhaust: Ps (exhaust) = Ps (supply) x 1.2 NC (exhaust) = NC (supply) + 3dB Vertical Projection Data: Projection is based on isothermal supply conditions with a terminal velocity of 0.5 m/s. Correct for heating, cooling and other Vt. For projection use graph below. For required throw corrected for temperature differential select suitable size and neck velocity. Noise generation and Pressure loss: Use the table for horizontal diffusion corrected for cone setting.

Selection Example
Size 12 WR diffuser handling 350 l/s produces a horizontal throw range of 2.1 - 3.9m and an NC level of 34 with pressure loss of 25 Pa. With vertical projection (setting A) the resulting throw would be 10m for isothermal conditions and an NC level of 36 with a pressure of 42 Pa.

Performance Tables
Horizontal Diffusion: Supply

WR

Air Volume
457 522 127 145 1.5-2.7 1.5-3.0 39 43 72 95 806 922 224 256 2.2-4.0 2.2-4.5 40 43 64 84 1278 1458 355 405 2.4-4.8 2.7-3.9 43 47 53 70 1840 2106 511 585 2.7-3.9 3.0-6.0 45 49 50 65 2873 3283 798 912 3.3-6.6 3.9-7.5 44 48 39 51 652 181 2.1-3.9 50 141 1152 320 3.0-5.5 50 131 1825 507 3.6-6.7 54 109 2632 731 3.9-7.5 56 102 4104 1140 4.8-9.5 55 80

Heating Dt (C)

10

15

20

25

30

263 328 392 m3/h l/s 73 91 109 Min - Max (m) 1.0-1.5 1.0-1.8 1.2-2.4 Lw 19 27 34 Ps 24 37 53 468 583 677 m3/h l/s 130 162 188 Min - Max (m) 1.2-2.1 1.5-2.7 1.8-3.3 Lw 24 30 36 Ps 21 33 47

Projection Factor 0.98 0.95 0.85 0.75 0.62 0.50 Terminal Velocity Vt (m/s) 0.75 0.50 0.40 0.30 Correction Factor 0.80 1.0 1.11 1.30

Projection Factor for Cooling t= 10C - 1.15

731 907 1095 m3/h l/s 203 252 304 10 Min - Max (m) 1.5-2.7 1.8-3.3 2.1-3.9 Lw 25 32 38 Ps 17 27 39 1015 1282 1577 m3/h l/s 292 366 438 12 Min - Max (m) 1.5-3.0 2.1-3.9 2.4-4.8 Lw 26 34 40 Ps 16 25 37 1642 2052 2448 m3/h l/s 456 570 680 15 Min - Max (m) 1.8-3.6 2.4-4.8 3.0-6.0 Lw 28 34 40 Ps 13 20 29 2362 2952 3543 m3/h l/s 656 820 984 18 Min - Max (m) 2.4-4.5 3.0-6.0 3.6-7.0 Lw 28 35 41 Ps 10 16 23

Vertical Projection - Cone setting A


Size 6 8 10 12 15 18 21 24

10

Vn Neck velocity (m/s)

5 4

Example

4133 4723 5908 1148 1312 1641 4.2-8.1 4.8-9.3 6.0-12.0 46 50 57 32 42 65

10

20

30

Projection (m)

3226 4032 4838 5645 6451 8064 m3/h l/s 896 1120 1344 1568 1792 2240 21 Min - Max (m) 4.2-8.4 4.8-9.7 5.4-10.8 6.0-12.0 6.6-13.2 8.1-16.5 Lw 33 40 46 50 54 61 Ps 7 12 17 23 30 46 4205 5256 6300 7362 8424 10512 m3/h l/s 1168 1460 1750 2045 2340 2920 24 Min - Max (m) 5.0-10.0 5.5-11.0 6.0-12.0 6.5-13.0 8.0-16.0 10.0-20.0 Lw 35 41 47 51 55 62 Ps 13 21 30 41 56 84

A B C

Waterloo 2.0

79

Tel: +44 (0) 1622 711511

Aircell Polymer Floor Diffusers


WFO WFOV
Introduction
The Waterloo Aircell WFO series floor diffuser offers the choice of horizontal or vertical air patterns with its flip over design, as well as a host of other unique & patented features. The WFOV low pressure vertical supply disc offers vertical projection with a 50% increase in air volume capacity, compared with standard WFO units. The WFO diffuser disc is 200mm and it has been designed to resist permanent deformation when subjected to point loads up to 500 kg and all materials used are fire retardant. The WFOV diffuser disc is suitable for point loads up to 300kg.

Waterloo

Product Description
WFO Pressurised Floor Void - Tile installation suitable for fitting into standard floor tile thicknesses of up to 50mm, supplied with a locking collar which is screw fixed to the underside of the tile. WFOV As above but with low pressure vertical air pattern disc WFOS Pressurised Void - Slab floor installation supplied with a steel adaptor collar which is cast into the floor slab. The diffuser can then be installed into the collar with concealed spring clips. WFOP Ducted installation with plenum supplied with a plenum which simply snap fits onto the locking collar. The plenum features a dual spigot connection to suit 100mm or 125mm diameter ducting. WFOPV As above but with low pressure vertical air pattern disc WFOD Step Drilled Installation The diffuser disc only is supplied, suitable for installation into pre-cut holes in floor tiles.

50 Max. Tile

23 Min. Tile

O/A 211 cutout 200

225

holes on 245 PCD

A 150

Features
Unique flip-over design Memory locating peg Easy fit locking collar Concealed fixing bracket for concrete / slab flooring Combined damper / dirt tray with incremental damper positioning Heavy duty glass reinforced polycarbonate construction Snap fit aerodynamic compact plenum 221
100 Nom. 125 Nom.

336

WFOP WFOPV

Finish
WFO diffusers are available in a slate grey finish specified subject to a minimum quantity.
201

125

hole

Advantages
Ability to change between horizontal and vertical settings instantly Commissioning settings are retained once set using the memory locating peg Reduced installation time with easy fit locking collar Quick fit plenum 20

190

WFOD

Order Example WFOP


Type

Waterloo 2.0

80

Tel: +44 (0) 1622 711511

30 min

(RAL 7037 Mid Grey) as standard. Other colours can be

Waterloo

Aircell Polymer Floor Diffusers


WFO Standard Performance

Selection Example
WFO
(Horizontal Setting) Air Volume 25 I/s Jet velocity at 1m from the diffuser will be 0.26 m/s for 3C cooling Pressure Drop 25Pa Noise Level NR 24

Performance Graph
VERTICAL DIFFUSION AT 3C COOLING VERTICAL DIFFUSION AT 6C COOLING

1.0 0.9 0.8 0.7

0.5 m 0.7 5 1.0 m 1.7 1.5 1.25 m 5m m m

1.0 0.9 0.8 0.7

AIR VELOCITY (m/s)

0.6 0.5 0.4 0.3

AIR VELOCITY (m/s)

0.6 0.5 0.4 0.3

0.2

0.2
5m

0.1 5 10 15 20 30 40

0.1 5 10 15 20 30 40

AIR FLOW RATE (l/s)

AIR FLOW RATE (l/s)

HORIZONTAL DIFFUSION
0.5 0.4 DATA SHOWN IS VALID FOR TEMPERATURE CONDITIONS RANGING FROM ISOTHERMAL TO 6C COOLING

Pressure Loss Data - Both Settings


Air Flow Rate (l/s) 10 15 20 25 30 35 40 Static Pressure Loss (Pa)
Tr = Ts (-3C)

AIR VELOCITY (m/s)

0.3

Example

0.2

Tr = Ts (-6C)
0. 5m 0 1. 0m .75 m 1. 25 m

WFO WFOS WFOP WFOD

5 5 7 4

10 10 17 7

17 17 29 12

25 27 45 19

1.25m

35 38 64 26

1.75m

1.0m

0.5

0.7

45 50 35

56 45

All pressure loss data is based on a fully open damper

1.5

1.7

Acoustic Data - Horizontal Setting


Air Flow Rate (l/s) 10 15 20 25 30 35 40

0.1

10

15

20

5m

25 30

40

50

AIR FLOW RATE (l/s) The dotted lines represent the approximate distances from the diffuser where the jet air temperature (Ts) is the same as the room air temperature (Tr).

NRLP (Ref. 8dB Room Absorption)


WFO WFOS WFOP WFOD <15 <15 19 <15 15 21 <15 18 25 <15 <15 <15 24 26 30 20 29 30 35 24 33 34 28 36 32

All acoustic data is based on a fully open damper and horizontal diffusion. Reduce tabulated figures by NR3 for vertical diffusion.

Waterloo 2.0

81

Tel: +44 (0) 1622 711511

Aircell Polymer Floor Diffusers


WFOV Low Pressure Disc Performance
Selection Example WFOV

Waterloo

Air Volume 35 I/s Jet velocity at 1.75m vertically from the diffuser will be 0.39 m/s for 3C cooling Pressure Drop 20Pa Noise Level NR 18

Performance Graph
VERTICAL DIFFUSION AT 3C COOLING VERTICAL DIFFUSION AT 6C COOLING

1.0 0.9 0.8 0.7

1.0 0.9 0.8 0.7

AIR VELOCITY (m/s)

0.6 0.5 0.4 0.3

AIR VELOCITY (m/s)

0.6 0.5 0.4 0.3

Example

0.2

1.7

1.2

0.

0.2

0.1 5 10 15 20 30 40 50

0.1 5 10 15 20 30 40 50

AIR FLOW RATE (l/s)

AIR FLOW RATE (l/s)

Pressure Loss Data


Air Flow Rate (l/s) 10 15 20 25 30 35 40 Static Pressure Loss (Pa)
WFOV WFOPV 2 7 4 17 7 29 11 45 15 64 20 26

Acoustic data
Air Flow Rate (l/s) 10 15 20 25 30 35 40 NRLP (Ref. 8dB Room Absorption)
WFOV WFOPV <15 18 25 <15 18 22 30 35

All pressure loss data is based on a fully open damper

All acoustic data is based on a fully open damper.

Waterloo 2.0

82

1.25

m 1.75 m

5m

m 5m

5m

5m

5m 0.7

1.5

1.0

0.

1.0

75

0.

Tel: +44 (0) 1622 711511

Waterloo
Type WFO & WFOV (Tile installation)

Aircell Polymer Floor Diffusers


Installation

Type WFO & WFOV Diffusers are suitable for installation into floor tiles from 23mm to 50mm thick. A 211mm diameter hole is drilled/cut through the tile. Ensuring the aperture is free from shavings/rough edges etc, insert the mounting frame into the hole. Locate locking collar onto the underside body of the mounting frame and using the webs screw upwards and tighten to the underside of the tile. The main body of the unit should now be firmly held in position, screw holes are provided in the locking collar should additional fixing be required. The combined damper/dirt tray can now be positioned into the mounting frame. Ensure that the damper airways are open and place location peg into the slot provided to lock in position. Finally select the air pattern required either vertical or horizontal by referring to the disc location tab and place into the aperture ensuring alignment tab engages with the cut out in the mounting frame. To remove the disc use the tool provided.

211

WFOP WFOPV

Type WFOP & WFOPV (Tile installation with plenum)


Installation as described for WFO. Select plenum inlet spigot size, if 125 diameter cut off square around markings with a hacksaw, remove swarf with a file and connect to ductwork with a flexible tie. Snap on plenum onto the ridge situated on the locking collar. To remove the disc use the tool provided.

Type WFOS (Slab floor or wall installation)


The steel sleeve is positioned to the customers requirements and cast into concrete floor/wall slab. Ensure that the sleeve and face flange are free from debris, fit the mounting clamps, screws and cylinder nuts as shown, to the mounting frame, insert into steel sleeve, gradually tighten the screw head clockwise until the cylinder nut has expanded the clip into the sleeve groove. Establish that the mounting frame is secure and insert damper/dirt tray locking pin, and diffuser disc. There is no requirement for the locking collar so this can be disposed of. To remove the disc use the tool provided.

WFOS

Type WFOD (Diffuser disc only)


Drill/cut a 211mm diameter hole in the floor, 20.5 mm deep. Ensure the aperture is free of shavings/debris and place the disc into position. To remove the disc use the tool provided.
20.5

201

190

WFOD

Waterloo 2.0

83

Tel: +44 (0) 1622 711511

>30mm

50 Max. Tile

WFO WFOV

23 Min. Tile

Drum Jet Diffusers


WDJ
Introduction
The Waterloo WDJ Drum Jet diffuser is a high capacity unit specifically designed for warehouses, sports halls or factory units etc where a long throw is required. The WDJ is fully adjustable to provide a full jet spread and directional control. The unit is constructed from aluminium extrusions and comes complete with brush strips to provide a low friction, airtight seal. Standard installation is screw fixing through the face flange. 75 Blade Pitch A

Waterloo

Adjustable Vanes

Product Description
WDJ Drum Jet Diffuser OBSS Opposed blade damper

Features
Fully adjustable air pattern Suitable for sidewall or exposed duct applications 14 Fully adjustable drum Brush Strip Seal W Duct Width

Finishes
RAL 9010 White Satin Anodised Aluminium 6 D

Advantages
Long throws Low resistant friction on drum Ease of adjustment

30

30

Adaptor Frame

WDJ

WDJ + OBSS

No Order Example WDJ-1806/OBSS


Type Number Damper 906 1206 1806 2406 2010 2510 3010 3510

A
300 376 529 681 579 706 833 960

B
217 217 217 217 319 319 319 319

W
261 337 490 642 540 667 794 921

H
170 170 170 170 271 271 271 271

C
36 36 36 36 63 63 63 63

D
87 87 87 87 138 138 138 138

E
146 146 146 146 207 207 207 207

Weight
1.5kg 1.7kg 2.0kg 2.5kg 5.5kg 6.5kg 7.0kg 7.5kg

Waterloo 2.0

84

Tel: +44 (0) 1622 711511

H Duct Height

Waterloo
Selection Criteria
Temperature differential - 0C (Isothermal) Terminal velocity - 0.25m/s NR level with a room absorption factor of 8dB.

Drum Jet Diffusers


WDJ

Selection Example WDJ-2406


Air flow rate 400 I/s Throw 17.0 m Pressure drop 45Pa Noise level NR26

Throw Correction Factor


Vane Angle Factor 0 1.0 5 10 20 30 40 60 0.9 0.82 0.68 0.6 0.52 0.4

Performance Table
Air Volume

WDJ

m3/h l/s Jet Throw Pa NC Jet Throw

360 100 3.5 20 13 2 12

720 200 16 75 26 9.5 45 22 5 24 16 3.5 10 10 1.8

1080 300

1440 400

2160 600

2880 800

3600 1000

4320 1200

906

22 100 32 15 48 25 9 25 18 4 12 14 3 10 11 2.2 26 77 31 17 45 26 8 22 20 5 12 15 4 10 10 3.2 36 98 34 18 50 28 14 26 24 10 18 20 7.5 14 18 34 80 35 25 50 30 18 40 27 15 25 25 37 75 35 28 50 32 22 40 30 50 105 38 40 75 30 30 55 33

1206

Pa NC Jet Throw

1806

Pa NC Jet Throw

2406

Pa NC Jet Throw

2010

Pa NC Jet Throw

2510

Pa NC Jet Throw

3010

Pa NC Jet Throw

3510

Pa NC

Waterloo 2.0

85

Tel: +44 (0) 1622 711511

Supply Air Nozzles


VS3
Introduction
The Waterloo supply air nozzles series VS3 are used for supplying air into areas requiring long jet throws and low noise levels. By arranging individual nozzles in a bank, corresponding throw distances are considerably increased.
A+68 A-2 A

Waterloo
L3

Product Description
VS3Supply air nozzle P Plain connection D Connection to square duct R Connection to circular duct M Regulating damper (125,160 & 220 only) B1 Belimo LM24 motor B2 Belimo LM230 motor B3 Belimo LM24-SR motor

60

9 L1

VS3/P

Features
Large range 3 duct connection types Low noise levels Motorised version available
A+68 A+64

Extended throws when arranged in banks

Finishes
Natural aluminium as standard Other colours available on request
L2

Advantages
High air handling capacity Easy to install Remote seasonal adjustment on motorised versions Easy to clean aesthetic appearance

VS3/M/P (with regulating damper)

VS3/D (without motor) VS3/D/B* (with motor)

Circular Duct Size Availabilities


Dim. R315 R500 R630 R800
80 100 125 160 220

VS3/R (without motor) VS3/R/B* (with motor)

Order Example Dim. D VS3/M/D/B2/125


Type Regulating Damper Duct Connection Type Motor Type (if required) Nominal Size 80 100 125 160 220 80 100 125 160 220 125 155 225 315 375 107 120 120 150 150 102 115 115 145 145 160 200 250 315 400

L1

L2

L3

Waterloo 2.0

86

Tel: +44 (0) 1622 711511

Waterloo

Supply Air Nozzles


VS3
Selection Example VS3/125
Air Volume 200 I/s Throw 30.0 m Terminal Velocity 0.48m/s Pressure Drop 140 Pa Noise Level NC 33

Correction Factor for Multiple Units


N of Units NR Level Addition Throw Factor 1 0 1.0 2 +3 1.4 3 +5 1.9 4 +6 2.0

Performance Graphs
THROW 2.5 2 Vt (m/s) 1.5 1 0.7 0.5 0.4 0.3 0.2 220 160 125 100 80
L= 5m 10 m 20 m 30 m

Size

15

30 40

55

85 110 140

200 280

420 560

700

750

Q (l/s)

NOISE LEVEL & PRESSURE DROP 300 40 250 200 p(Pa) 150 100 70 50 40 30 25 20 25 30 40 85 140 Q (l/s) 200 280 560 830
C N 25

80 45

100

125

160

35 32 30 28 27

220

10

Waterloo 2.0

87

Tel: +44 (0) 1622 711511

Hi-Flo Jet Diffusers


RWH RWH-P
Introduction
The Waterloo RWH diffusers have been designed to handle high air flow rates and provide relatively long throws which make them particularly suitable for conditioning of large spaces such as halls, auditoria, terminal buildings, warehouses and factories. The diffusers are versatile in application by virtue of the novel reversible and rotatable core design which allows the air jet to be adjusted for both pattern and deflection. Units may be mounted individually or in banks, in bulkhead arrangements or directly into stub ducts. The diffusers are constructed from aluminium spinnings supported on a studding and spacer assembly. The core may be rotated through 180 to expose either a straight or diffused core assembly. In addition, the diffuser spigot may be rotated within the mounting plate (if supplied) to enable a full 360 adjustment, by releasing the tension bolts.
Screw fixing through plate to ceiling or wall 15 F

Waterloo

30

Product Description
RWH Complete diffuser assembly including diffuser core, spigot and mounting plate (wall or ceiling mounting). RWH-P Diffuser core and spigot only (suitable for mounting onto bulkheads or stub ducts thus eliminating the large mounting plate).

RWH assembly Diffuser setting


1.5 - 15 can be increased with longer screw Clamp fixing to panel

RWH assembly Jet setting

Screw or rivet to ducting

Features
Simple and effective air diffusion for large spaces Long throw characteristics High air handling capacity Easy to install and adjust Reversible core to produce long throw jet or short throw diffuser patterns Core rotatable through 360 for eyeball jet direction Jet may be deflected off axis by up to 15 Available in four sizes Multiple outlet arrangements
A

Ceiling or wall panel

Cut out

Duct

Duct

Ducting (By others)

RWH-P assembly

RWH-P assembly

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Weights
Size 200 250 315 380 RWH 1.6 kg 2.5 kg 4.2 kg 5.3 kg RWH-P 1.2 kg 1.8 kg 3.1 kg 4.1 kg

RWH Diffuser setting

Order Example RWH-P/380/PPM9010


Type Duct & Diffuser Size Finish

Nom. size A
200 250 315 380 247 312 377 447

B 198 248 313 378

C 235 285 350 415

D
92 104 124 159

E
98 116 154 155

F
22 34 47 80

G
28 34 68 65

Waterloo 2.0

88

Tel: +44 (0) 1622 711511

Waterloo

Hi-flo Jet Diffusers


RWH RWH-P

RWH-P Diffuser Setting

RWH-P Jet Setting

RWH Diffuser Setting

RWH Jet Setting

All data is for the diffuser set for 0 deflection and operating under isothermal conditions in either jet or diffuser pattern. Correction factors for 15 deflection are given below. When diffusers are mounted on a common plate/plenum the noise level and throw will increase. Correction factors

are given in the table below. NR level = Peak level on NR curves based on SWL ref 10-12 W less 8dB room absorption. Throw = Forward distance to the point where the jet velocity has retarded to a terminal velocity of 0.5 m/s. Ps = Static pressure loss (Pa). Air Volume

Performance Table
RWH RWH-P
m3/h l/s Throw(m) Lw Ps Throw(m) Lw Ps Throw(m) Lw Ps Throw(m) Lw Ps Throw(m) Lw Ps Throw(m) Lw Ps Throw(m) Lw Ps Throw(m) Lw Ps 360 100 5.7 18 2.8 18 4.0 6 2.0 6 450 125 7.0 18 28 3.5 28 5.1 17 10 2.6 10 540 150 8.2 24 40 4.1 20 40 6.0 22 14 3.0 14 14 5.0 4 2.5 4 720 200 11.5 32 65 5.8 31 65 7.2 30 21 3.6 24 21 6.8 8 3.4 8 5.4 3 2.7 3 900 250 15.0 38 110 7.5 39 110 10 36 31 5.0 32 31 8.5 19 13 4.3 13 6.8 5 3.4 5 1080 300 17.0 44 160 8.5 46 160 12.0 41 48 6.0 38 48 9.8 24 18 4.9 20 18 8.0 7 4.0 7 1440 400 1800 500 2160 600 2880 800 3600 1000 4320 1200

Jet

200 Dia
Diffuser

Jet

250 Dia
Diffuser

Jet

315 Dia
Diffuser

Jet

380 Dia
Diffuser

16.5 48 80 8.3 49 80 13.0 33 30 6.5 31 30 10.5 21 12 5.3 14 12

16.0 39 45 8.0 39 45 14.0 28 20 7.0 23 20

20.0 44 60 10.0 46 60 16.4 33 30 8.2 30 30

26.0 53 105 13.0 57 105 22.0 41 50 11.0 41 50

28.0 48 70 14.0 50 70

35.0 53 100 17.5 57 100

SWL Spectrum Correction Data By Octaves


Frequency (Hz) 125 Diffuser/ 0 -1 Diffuser/ 15 0 Jet/ 0 -3 Jet/ 15 +1 250 +1 +2 -1 +3 500 +3 +4 +3 +4 1K +8 +8 +8 +7 2K +7 +7 +6 +6 4K 0 +2 +5 +1

Multiple Unit Correction Factors


No. of units NR addition Throw factor 1 0 1.0 2 +3 1.37 3 +5 1.86 4 +6 2.06

15 Core Setting Correction Factors


NR addition Pressure Loss Factor Jet +11dB 1.25 Diffuser +4dB 1.25

Terminal Velocity Correction Factors


Vt (m/s) Factor 0.2 2.5 0.3 1.7 0.4 1.25 0.5 1.0 1.0 0.5 1.5 0.3

The above data is based on isothermal supply air conditions. To estimate maximum Vertical projection under warming conditions multiply jet throw data above by the relevant factor below.

Heating Differential
Size RWH-200 RWH-250 RWH-315 RWH-380 5C 1.30 1.20 1.10 1.00 10C 0.90 0.85 0.75 0.65 20C 0.65 0.60 0.55 0.45

To estimate vertical projection under cooling conditions multiply throw (to relevant terminal velocity) by factors as follows:10C cooling x 1.15 5C cooling x 1.10

Waterloo 2.0

89

Tel: +44 (0) 1622 711511

Hi-flo Jet Diffusers


RWH RWH-P
Plenums
Full details of standard plenums are available from Head Office.

Waterloo

Typical standard plenum arrangement with optional circular or rectangular connections

Special designs are available to suit non standard applications, for example, rooftop air handling units and high level ducting.

Waterloo 2.0

90

Tel: +44 (0) 1622 711511

Waterloo
Mounting Plates
B1 O/S = =

Hi-flo Jet Diffusers


RWH RWH-P

1 Element
Size
200 250 315 380

15 O/S

A
299 349 399 499

B1
299 349 399 499

D
235 285 350 415

A O/S

1 Element

2 Element
Size
200 250

B2 O/S C

15 O/S

B2
598 698 798 998

C
299 349 399 499

299 349 315 399 380 499

A O/S

235 285 350 415

2 Element

3 Element
Size
200

B3 O/S C C

15 O/S

B3

299 897 299 250 349 1047 349 315 399 1197 399 380 499 1497 499

A O/S

235 285 350 415

3 Element

4 Element
Size
200

B4 O/S C

15 O/S

B4
1196 1396 1596 1996

C
299 349 399 499

299 250 349 315 399 380 499

A O/S

235 285 350 415

4 Element

Waterloo 2.0

91

Tel: +44 (0) 1622 711511

Supply and Exhaust Valves


VA VB VC
Introduction
A range of high quality valves for supply and exhaust applications for commercial and industrial projects. Series V valves are best applied to air distribution systems handling relatively low air flow rates within small circular ductwork. The valves provide high initial resistance with wide throttling capability which is necessary to offset the relatively high system resistances. All valves are constructed from steel spinnings protected by a polyester powder gloss white finish. Flanges are fitted with sealing gaskets and all units are supplied as standard with plated steel mounting subframes. H

Waterloo

Product Description
VA Supply valve with spindle locknut VB Exhaust valves with spindle locknut VC Exhaust valve with tamper proof screw locking of inner core Supply Valve - VA

Installation
All units are supplied with a steel mounting subframe which should be fixed to the prepared opening. Cut aperture to suit subframe size shown in table below Screw subframe into aperture Offer valve body into subframe and rotate into bayonet fixing
D

Finishes
Standard - polyester powder gloss white Other colours are available on request

Exhaust Valve - VB
H

H
A B

Subframe
D B

Subframe
100 125 160 200

B A H

100 130 28

125 155 29

160 190 31

200 236 33

Exhaust Valve - VC

Order Example
VA/125 Type Size
D

VA
100 125 160 200 100

VB
125 160 200 100

VC
125 160 200

S B H

137 74 94 47

161 97 110 49

212 127 145 80

249 156 194 75

137 74 75 47

161 97 100 49

212 127 130 60

248 156 157 64

135 87 50

165 103 47

197 130 47

240 155 47

Waterloo 2.0

92

Tel: +44 (0) 1622 711511

Waterloo
Selection Criteria

Supply and Exhaust Valves


VA VB VC
Throw is the radius of diffusion (Vt = 0.2 m/s) (Supply valve VA only). Ps is the static pressure loss (Pa). dBA is the A weighted sound pressure level based on 8dB room absorption.

Selection Example VA/200


Air Volume 80 I/s Throw 2.0 m Pressure Drop 27 Pa Noise Level NR25

Performance Table
Air Volume

VA

m3/h l/s Throw (m) Ps Lw Throw (m) Ps Lw Throw (m) Ps Lw Throw (m) Ps Lw

36 10 0.8 7 -

72 20 1.2 19 20 1.4 7 -

108 30 1.9 42 25 2.0 18 20 0.8 8 -

144 40 2.2 70 45 2.4 27 26 1.1 18 23 1.1 8 -

180 50

216 60

288 80

360 100

432 120

504 140

100 Dia

125 Dia

2.8 45 32 1.5 30 28 1.4 13 -

3.2 65 37 1.7 40 32 1.6 17 2.1 75 42 2.0 27 25 2.6 120 47 2.3 42 32 2.7 55 37 3.0 72 43

160 Dia

200 Dia

Air Volume

VB
100 Dia 125 Dia 160 Dia 200 Dia Ps Lw Ps Lw Ps Lw Ps Lw

m3/h l/s

36 10 9 8 -

72 20 38 20 30 15 -

108 30 88 32 70 24 35 20

144 40 145 40 130 32 55 24 7 -

180 50

216 60

288 80

360 100

432 120

504 140

170 37 95 30 13 -

130 35 19 -

32 27

55 33

70 37

90 41

Air Volume

VC
100 Dia 125 Dia 160 Dia 200 Dia Ps Lw Ps Lw Ps Lw Ps Lw

m3/h l/s

36 10 22 8 6 -

72 20 75 24 32 21 20 -

108 30 150 33 55 25 42 20 9 20

144 40

180 50

216 60

288 80

360 100

432 120

504 140

95 29 75 26 16 22

130 34 120 33 24 24

180 40 160 37 34 27

55 32

85 37

110 43

150 47

Waterloo 2.0

93

Tel: +44 (0) 1622 711511

Polymer Supply and Exhaust Valves


RPVB
Introduction
The Waterloo Aircell RPV air valves are an attractive and versatile form of air terminal for use as either a side wall grille or ceiling diffuser in supply or extract applications. Moulded in ABS engineering polymer to achieve a high quality finish, the units are available in 100mm or 125mm diameter neck sizes and can be supplied with optional pre-set flow regulators. The RPV valve comprises a flanged frame with either a plain or perforated snap-fit fascia. The perforated fascia can be configured to give either horizontal diffusion or a projection jet using a concealed deflection pad. Both fascia types are fitted with a removable internal baffle to limit the jet spread angle when wall mounted or when ceiling mounted close to a wall. This internal baffle may be simply snapped off to give 360 jet spread. The optional air flow regulators (AR) are designed to push fit into the frame to control air in either supply or extract mode and are available in three flow settings for each size. The units maintain a constant flow over a pressure range of 50-200 Pa.
Perforated snap fit fascia with removable deflection pad and direction baffle

Waterloo
Adjustable tabs to suit installation method Installation collar suitable for wall or ceiling mounting

TYPE RPVB
Wall or ceiling installation Max Tile Thickness 20

Reversible air flow regulator (AR) suitable for supply or extract

Product Description
RPVB AR121 AR171 AR251 AR175 AR255 AR335 DC1 DC5 Wall or ceiling application - perforated fascia 12 l/s regulator for 100 17 l/s regulator for 100 25 l/s regulator for 100 17 l/s regulator for 125 25 l/s regulator for 125 33 l/s regulator for 125 Installation collar for 100 Installation collar for 125

184

15 42
MAX

L2 L1

CEILING MOUNTING

WALL MOUNTING 300 MAX

Installation
RPV valves simply push fit into circular ducting or optional installation collar when using flexible ducting. Suitable for mounting in wall or ceiling tiles.
3 4 (SUPPLY) 4 (EXTRACT) 1 2 REMOVE DIRECTION BAFFLE FOR FULL RADIAL AIR PATTERN 1 FIT FACIA WITH BAFFLE BELOW
1. 2. 3. 4. FRAME/FACIA DEFLECTION PAD INSTALLATION COLLAR OPTIONAL FLOW REGULATOR

1 4 3

Finishes
White - standard All others subject to minimum order quantity

Order Example
RPVB125/AR335/DC5/White Type Size Regulator (if required) Installation Collar Colour

L1
140 150

L2
85 85

RPV100 110 RPV125 135

97 122

Waterloo 2.0

94

Tel: +44 (0) 1622 711511

Waterloo

Polymer Supply and Exhaust Valves


RPVB
Selection Criteria
Throw data is presented in table 1 for ceiling and wall installations and is based on isothermal conditions to a terminal air velocity of 0.25m/s. The ceiling installation data is for a partial radial pattern with the internal baffle fitted and the fascia in a lowered position. Removing the baffle produces a full radial pattern and reduces the throws by a factor of 0.85. Data for wall installations is based on a confined jet and assumes that the valve is mounted within 300mm of the ceiling. Static pressure loss data presented in tables 1 & 2 is valid for wall or ceiling valve configurations and is based on units fitted with the internal baffle. Removal of the baffle reduces the pressure loss by a factor of 0.65. Noise data is shown in terms of sound power based NR levels (NRlw). Corrections factors should be applied as appropriate to the installation conditions to obtain the average sound pressure based NR level. The data is based on units fitted with the internal baffle.

Selection Example RPVB/125


Air Volume 25 I/s Throw ceiling 5.5 m, wall 5.6m Ps pressure drop 16 Pa NRlw <20

Performance Tables
Table 1: Supply Air Valve Data - Ceiling and Wall Installation Air Volume

RPVB
RPVB 100 Dia

RPVB 125 Dia

m3/h l/s Throw (m) ceiling Throw (m) wall Ps Lw Throw (m) ceiling Throw (m) wall Ps Lw

36 10 3.6 3.3 2 -

54 15 4.7 4.1 4 -

72 20 5.7 4.7 8 5.0 4.9 10 -

90 25

108 30

126 35

144 40

5.5 5.6 16 -

6.0 6.2 24 20

6.2 6.9 33 26

6.6 7.5 43 32

Table 2 : Extract Air Valve Data Air Volume

RPVB
RPVB 100 Dia RPVB 125 Dia Ps Lw Ps Lw

m3/h l/s

36 10 3 -

54 15 5 -

72 20 10 13 -

90 25

108 30

126 35

144 40

21 20

31 26

43 32

56 38

Table 3 : Air Regulator Acoustic Data at 50 Pa - Supply and Extract Air Volume

RPVB
RPVB 100 Dia RPVB 125 Dia Supply Extract Supply Extract

m3/h l/s

43 12 40 25

61 17 47 31 36 22

90 25 53 40 37 27

119 33

38 32

Waterloo 2.0

95

Tel: +44 (0) 1622 711511

W aterloo
GRILLES

Waterloo Air Products Plc Mills Road Aylesford Maidstone Kent ME20 7NB Tel: +44 (0)1622 717861 Fax:+44 (0)1622 710648 web: www.waterloo.co.uk email: mail@waterloo.co.uk

A complete range of products suitable for all wall, ceiling and floor applications. Most grilles are made from aluminium, and have a range of fixed or moveable blades designed to give performance whilst remaining aesthetically pleasing to the eye. Grilles are made to customer specified sizes, and colours (PPM/G); standard colour is PPM9010 (20% gloss white). This range is complemented by the Aircell range of polymer Grilles and Diffusers.

DIFFUSERS
A complete range of products designed to be installed in various ceiling systems. Most diffusers are made from aluminium, and can be ordered with or without plenum chambers for easy connection to duct work. Diffusers can be ordered in customer specified (PPM/G) colours; standard colour is PPM 9010 (20% gloss white). This range is complemented by the Aircell range of polymer Grilles and Diffusers.

ACTIVE BEAMS
The finest quality range of high output active beams, used for ventilated heating and cooling applications. These units have 4 pipe coils to allow heating and cooling circuits to run simultaneously, giving constant and responsive control. The design allows a large optimum capacity, and also allows the customer to specify the nozzle type and pitch for individual circumstances. Active beams are made from steel to a large range of customer specified sizes and as such are suitable for various different ceiling systems. Standard finish is PPM 9010, however other (PPM/G) colours are available on request.

AIR VOLUME DAMPERS


A complete range of pressure independent Variable air Volume and Constant air Volume dampers. Most volume dampers are regulated with an electronic motor and sensors, and are calibrated to customer specifications before delivery. The constant air volume damper requires no power source as it is controlled via a mechanical device it is also calibrated before delivery. All volume dampers are made from Zintec plate and all units (except CVD) can be ordered with a single or double (with insulation) skin.

EXTERNAL LOUVRES
The finest quality range of products for external wall applications. Rain water leakage is controlled through the use of specially designed blades that direct the flow. Made from aluminium, with birdscreen or insect screen options. All louvres are made to customer specified sizes and (PPM/G) colours; standard colour is PPM 9006 (matt silver)

All products conform to the Terms and Conditions of Waterloo Air Products Plc a copy of which are available upon request. Due to our continuous research and development programme, Waterloo Air Products plc reserve the right to alter products and prices without prior notification. Copyright Waterloo Air Products plc 2005 Designed, Produced and Published by Waterloo Air Products pl,c, UK & Waterloo Bv NL Printed in the Netherlands September 2005 Waterloo declare that, at the time of print , all products are in accordance with relevant directives, as identified by HEVAC and other European Organisations, and will display the CE Marking where required.

Waterloo 2.0

Tel: +44 (0) 1622 711511

Das könnte Ihnen auch gefallen