If the DAP controllers are connected directly to the FieldServer the limit of 32 nodes does not apply. According to the spec, the number of nodes can range from 1-260 under these conditions. Normal RS485 network considerations apply and this can only be achieved with network repeaters. Please refer to the Driver manual for more information.
FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-2269 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 1 of 5
Protocol Driver
Connection Information Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability RS-485 (RS-232 with converter) 2400 or 96002 (Vendor limitation) 8 (Vendor limitation) 1 (Vendor limitation) None Vendor limitation No
Proprietary Physical Interfaces Supported Fieldserver Model Adapter Model # Vendor Physical Medium
Devices tested Device DAP II Panel DA DAP II p/n 160-300-080 RevE Software Revision 9.0-STD Tested (FACTORY, SITE) Factory & Site.
FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-2269 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 2 of 5
Protocol Driver
Connection configurations The FieldServer is connected to the DAP devices as shown in connection drawing. Configure the DAP devices according to manufacturers instructions
+ FG Gnd _
Gnd _
Power
Net 2
Net 1
P8
P7
P6
GRO UND DTR RTS Tx 5 6 7 8
P5
P4
1 2 3 4
P3
Rx CTS DSR GRO UND
P2
P1
RS 23 2 Et hernet 10 Base T R2 R1
8 1
DC AUX Power
Connection Notes The Driver requires two dedicated RS-485 ports (or RS-232 ports with converters) for each DAP device network. FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-2269 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 3 of 5
Protocol Driver
Communications functions - Supported functions at a glance: Device "1" "2" "3" "4' "5" "6" "7" "8" "9" "10" "11" "12" "13" "E" "F" Driver Capability None Yes Yes Yes Yes Yes Yes Yes Yes Description 044 data logger 046 expanded DAP 046 2 mod chiller 046 3 mod chiller 048 DAP, 80-character display 049 DAP, 16-character display 080 DAP II, no relay expansion 080 Chiller II 080 DAP II, with relay expansion Not Defined Not Defined Not Defined Not Defined 080 DAP II, with analog module 080 DAP II, with relay and analog
Yes Yes
FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-2269 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 4 of 5