Sie sind auf Seite 1von 3

Doc. No.

Ver: 1.00 Rev: 2

Allen Bradley DH+


FS-8700--12

DESCRIPTION

The DH+ driver allows the FieldServer to transfer data to and from devices using DH+ protocol. The Communications Adapter card is included with the FieldServer. The FieldServer can emulate either a Server or Client. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer. FieldServer Mode Client Server Nodes 254 1 Comments

FORMAL DRIVER TYPE

Fieldbus Client or Server

COMPATIBILITY MATRIX
Compatible with this driver No No No No Yes No No No No No No

FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoCessor FPC-FO2 ProtoNode ProtoCessor FPC-FD2 QuickServer FS-QS-1010 QuickServer FS-QS-1011

CONNECTION INFORMATION
Baud Rates: 110-115200 Baud (Standard Baud Rates Only)

PROPRIETARY PHYSICAL INTERFACES SUPPORTED


Adapter Model # Vendor DH+ Blue Hose Physical Medium

FieldServer Model

DEVICES TESTED
PLC5, SLC5, PLC3

PLC types Supported:

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 3

Doc. No.

Ver: 1.00 Rev: 2

Allen Bradley DH+


FS-8700--12

CONNECTION CONFIGURRATIONS

The FieldServer is connected to the DH+ as shown in connection drawing.


FLASH

Card Slots into FS-X40

DATALINK CARD

CONNECTOR B JUMPER PADS

FieldServer FS-X40
W12 W11 W10 W9 B SERIAL 1 2 3 4 W8 A NET

LEDS

STATNET BUS 5 1 2 3 CFG BUTTON

Configuration PC

DH+ configuration cable. P/N 23083

FS-8917-19

PLC

Connector Pinouts DataCard 3-pin (A NET) connection to PC Datacard Function Signal+ Ground Signal Datacard Pin# Phoenix Connector A1 A2 A3 DH+/RIO Network Phoenix Connector 1 2 3 PLC-5 DH+ Program Port DB 9M Connector 1 7 5 Color Clear Shield Blue

Connector Pinouts DataCard 5-Pin (B Serial) connection to DH+ Configuration Cable Function RX TX GND DB9M Pin# 2 3 5 DH+ 5-pin connector Pin# 5 3 4

7.1

Hardware Connection Tips / Hints

Configure the PLC according to manufacturers instructions and configure checksum to use BCC checksum, not CRC.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 3

Doc. No.

Ver: 1.00 Rev: 2

Allen Bradley DH+


FS-8700--12

8 8.1

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: Data Types Supported:


Description Input Output Bit Integer Counter Timer System Status String Float

Data Type I O B N C T S St F

8.2

Command Support

The following commands are supported by the FieldServer for the various PLC types: PLC_Type File_Type N F B N F B N F SLC5 B I O FN C 1 1 1 1 1 1 A2 A2 A2 A2 A2 Read Range Read Range Read Range Read Range Read Range Read Range Read Protected Typed Logical Read Protected Typed Logical Read Protected Typed Logical Read Protected Typed Logical Read Protected Typed Logical Read FNC 0 0 2 0 67 26 AA AA AB Write Range Write Range Write Bit Write Range Write Typed Write Read Modify Write Protected Typed Logical Write Protected Typed Logical Write Protected Typed Logical Write Typical Command N7: 3, L5 F12: 3, L5 B3/4: 5, l5 N7: 3 , L5 F12: 3, L5 B3/4: 5, L5 N7: 3, L5 B3/4: 5, L7 B3/4: 5, L8 I: 13, L5 O: 13, L5

PLC3

PLC5

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 3