Beruflich Dokumente
Kultur Dokumente
March 2004
by Dave Fetters
Flexible air ducts and flexible air Flexible air connectors shall be
connectors share many of the same limited in length to 14 feet.
traits, yet are different enough that they Flexible air connectors shall not
are uniquely separate products. All of pass through any wall, floor, or
the national codes share similar ceiling.
language, as represented by the
International Mechanical Code, 2003 These last two entries define the
edition (paraphrased): primary difference between the two
products. Air ducts must pass 15 UL
Flexible air ducts and flexible tests, whereas connectors are not
air connectors, both metallic required to pass the flame penetration,
and nonmetallic, shall be tested puncture, or impact tests.
in accordance with UL 181.
Such ducts and connectors shall All Hart & Cooley flexible ducts are
be listed and labeled as Class 0 insulated and have a rectangular label
or Class 1 flexible air ducts or that shows the UL listing mark and
flexible air connectors and shall clearly states that it is an air duct.
be installed in accordance with Hart & Cooley flexible connectors have
the terms of their listing and the no insulation, but have a round label
manufacturer’s installation with the UL listing mark, the words
instructions. “air connector,” and the words “For
installation in length not over 14 ft.”
It goes on to say:
April 2004
by Dave Fetters
May 2004
by Dave Fetters
Everyone has thrown a ball of some We use the term terminal velocity in
kind in their lifetime, and we conjunction with throw to describe
generally pay attention to how far it what the air is doing at the end
traveled as a measure of our (or terminus) of the designated
strength, accuracy, or overall throw. A typical terminal velocity is
abilities. We can see the result of 75 feet per minute (FPM). This
our effort. Similarly, when air flows means that no matter how fast the
out of a supply register, we’d like to air is blown out of the register, the
know the result. Since we cannot throw tells us, at that distance, that
see what is happening (although we the air has slowed to 75 FPM.
might be able to feel it), we use
throw as one indicator of a register’s The supply air velocity measured at
abilities. Throw is a measure of how the register face determines how far
far the supply air stream is blown the throw will be. The faster the air
into the room. exits the face, the farther the air will
travel into the room. The resistance
Throw is measured in feet from the of room air to the supplied air will
face of the register along the primary cause the supply air to slow down.
direction of flow. However, a throw Eventually, the supply air will slow
distance is meaningless unless given enough to become ineffective in
a point of reference. By that I mean, mixing with room air. The point
“What is the air doing at the end of that air velocity becomes ineffective
the designated throw?” Is it is called the terminal velocity. It is
successfully mixing with room air to somewhat arbitrary, but generally
make the occupied space comfort- ranges from 150 down to 50 FPM.
able? To be mixing it has to be
moving, but how fast? (continued on reverse side)
July 2004
by Dave Fetters
August 2004
September 2004
October 2004
Return grilles or filter grilles are just and otherwise doesn’t have its own
as important to the HVAC system as return grille. Bathrooms and
the supply side products. Return air janitor’s closets in some commercial
volume to the air handler must buildings are examples.
equal the supply air volume pumped
out by the fan, or system A common misunderstanding is that
performance will suffer. Air will not return grilles have a dramatic effect
readily flow into a room from a on room air distribution. In fact the
register unless there is a relief opposite is true based on laboratory
opening for the “stale” air to flow research. Return airflow has a
out. This could be as simple as negligible effect on room air patterns
having the door open to a small because of its low-capture velocity.
room for air to drift out to an This means that the sphere of
adjacent room that has a return influence, or the area affected by the
grille. return grille, is limited to a little
over one duct diameter away from
Door grilles, or “transfer grilles” as the face. Within this short distance,
they are sometimes called, allow the air is captured and pulled into
room air to flow out of the room if the grille. Outside this immediate
the door is closed most of the time, area, the capture velocity is so low
November 2004
Hart & Cooley manufactures an that does not have the required
aluminum, corrugated chimney liner two-inch airspace to combustibles
system that is Underwriters (direct contact instead) may also be
Laboratories tested and listed. It used with this liner without further
may only be used with natural or safety concerns because of lack of
propane gas-fired Category I airspace clearances.
appliances listed for use with Type B
gas vent. This aluminum is the When we introduced the chimney
same alloy and thickness as the liner liner product line several years ago,
in our UL-listed B vent. This liner we “required” that masonry
system may not be used with liquid chimneys with at least one wall
(oil) or solid (wood or coal) fuel- exposed to the outdoors be relined
fired equipment. with Type B gas vent instead of
chimney liner. At the time, we were
Our UL listing allows the liner to be being cautious, knowing that in
installed in new or existing masonry order to vent properly chimney
chimneys, as well as existing, but liners must heat up quickly and stay
unused, factory-built chimneys and warm. We felt that chimneys
B vents. The liner may touch the exposed to cold air temperatures
interior surfaces of these flues. An may become too cold to work
incorrectly built masonry chimney properly, resulting in poor venting
January 2005
February 2005
March 2005
Fusible-link Dampers
by Dave Fetters
Most of us understand what a fuse is, lapping tabs are held together with
at least as it relates to electricity— precision solder that is temperature-
a safety device that fails and specific. A fusible-link damper is
interrupts the circuit if the current the result of mounting a fusible link
becomes too great. An old-style fuse to the damper of a register. The end
would melt an encapsulated wire or result is a register damper that is
metal strip due to heat build-up as fully operational as one would
the current exceeded the fuse’s expect, but has the added benefit of
rating. The fuse will no longer closing if the temperature becomes
conduct electricity after failing. too hot.
Today, however, most of us have
circuit breakers. We are going to Specifically, Hart & Cooley’s fusible
apply this concept of an old-style link is about an inch long with a
fuse to a register damper. standard temperature rating of
165°F or an optional link with a
One form of a fusible link is a set of 212°F rating. We use these on only
overlapping metal tabs with holes at some of our steel multi-shutter
each end for attachment purposes equipped registers like the 661 or
that will separate into two pieces at 682. When the air temperature
a preset temperature. These over- passing over the link approaches the
April 2005
What are effective area and free Face Velocity (Ft³/Min) divided by
area as they apply to grilles, Ft/Min = Ft². The result is the
registers and diffusers? What are effective area (Ak) in square feet.
the differences between these two Notice that all the units match; that
areas and how are they used in our is, both sides of the equation use
industry? “feet” and “minutes.” You have
seen this relationship before in
Effective area, given the abbrevi- TECH TALK TT-08, and you will be
ation Ak (pronounced “A sub k”), is seeing it again in future discussions.
the area of the register, grille, or The engineering data tables for all of
diffuser in square feet that is utilized our products are based on this
by the air flowing through it. This is relationship. In use, the actual CFM
a calculated figure that can only be delivered by one of our products can
determined in our laboratory. It is be determined by measuring the
used in the equation: average face velocity and multiply-
ing it times the Ak for that size
CFM = Face Velocity x Ak product found in our catalog
Engineering Data.
It is calculated by carefully measur-
ing the Airflow Rate in Cubic Feet Free area is the sum of the areas of
per Minute or CFM, and the Face all the spaces between the bars or
Velocity in Feet per Minute or FPM. fins of a grille measured in square
We then divide the Flow Rate by the inches. It is sometimes called the
May 2005
Each year during the summer allowing the hot, humid outside air
season, we receive a number of calls to sneak in. This begs for the air-
about moisture forming on the faces conditioning system to run longer
of our T-bar diffusers or on adjacent and colder, trying to maintain a
T-bars and dripping into the space reasonable inside temperature.
below. In the industry this is
commonly called “sweating.” Sweating occurs on diffusers when
Moisture that drips into an occupied warm, moist room air contacts the
space is annoying, and will cold diffuser face through aspiration
eventually cause rust to form on (drawn by suction) when the supply
steel diffuser faces and adjacent air temperature is at or below the
T-bars. Sweating occurs more in dew point temperature. Dew point
southern states that border the is the temperature at which
coasts or in parts of the country that condensation (moisture formation)
experience high humidity levels as a begins to take place. Most of us
regular occurrence. Business have walked outdoors on a warm
activities that rely on people coming and humid summer day carrying a
and going, like fast-food restaurants, cold drink. It doesn’t take long
seem to be the most susceptible. before the outside of the glass
The doors are regularly opened, becomes wet. Moisture is
June 2005
2,000 CFM
= 2.22 FT²
900 FPM
August 2005
Quite a few of the Hart & Cooley Fiberglass back panels allow for the
lay-in T-bar diffusers and return use of various collar styles like
grilles use a molded fiberglass back spin-in, tab-in, or our own 5400
panel or plenum. The molded Series Collar Ring (6-inch through
fiberglass backs have some 18-inch diameters). The use of the
significant features. 5400 collar allows for the installa-
tion of our 3800, T19, or RD round
Bonded foil vapor barrier
dampers, either at the time of
Prescored for different collar installation or later.
sizes
UL 181 Erosion and Impact
tested
Meets ASTM E84 for 25/50 code
compliance
4-inch deep cavity
“R” values of 4.2 and 6
Approved for the city of
Los Angeles Fiberglass Back Panel
Labeled with code information NOTE: Attachment of molded
fiberglass back and
5400 collar requires
5400PP (push pins).
September 2005
Since we are often asked how to Lightly rubbing the hard, glossy
repaint our registers, the answer finish of our product with fine steel
®
sounded like a good Tech Talk wool or a Scotch-Brite pad allows
subject! the new paint to adhere better.
October 2005
November 2005
For whatever reason, you may not be able location using dual multi-shutter dampers
to find the exact model of Hart & Cooley to change the air pattern as necessary.
grille, register, or diffuser product you Linears offer the greatest available range
had hoped to. Given the fact that you of lengths (almost unlimited) and widths,
may not have the option to change the are made of extruded aluminum, can be
size of the desired model to get by, what used as a supply or return, and can be
options do you have to substitute another used in the floor, on the wall, or in the
model for the one you wanted? Since ceiling. The Linear series has a large
Hart & Cooley has the broadest product matrix of possible sizes, when you
offering in the industry, chances are very consider that widths are available in half-
good that a suitable substitution can be inch increments from 1½ to 12 inches
found. Allow me to offer some (for floor applications) and up to
suggestions for substitutions without 24 inches for wall or ceiling use combined
concern for the obvious variable of cost. with infinite lengths. The 210 supply
registers and 265 return grilles could be
This discussion should help broaden your used as substitutes for sizes of floor
product knowledge about the use of registers that are not available in the 421,
alternates. Materials, construction, 411 or 531 styles.
designs, and features may change, but the
end effect of adequate (or enhanced) Baseboard: Baseboard diffusers do not
performance will still be achievable. have the luxury of a wide range of
common sizes. However, the 654, 655,
Floor: An alternate for our popular 421 and 664 are interchangeable, for the most
steel floor diffuser could be a 411, 531, or part. We offer 406, 462, and 464 base-
a Linear in an ascending order of board diffusers, as well, in longer lengths
capability. The steel 411 is more robust and various materials and finishes.
than the 421 and could be used in high
traffic areas. A 531 is constructed of Sidewall/Ceiling: Alternates for our
extruded aluminum for a premium look, louvered sidewall/ceiling registers, like the
has high strength, and offers a unique way 661 ⅓-inch and 682 ½-inch fin-spaced
to both heat and cool from the same designs, would be one for the other if you
©2005 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
were not concerned with blade spacing. RHF45, REF5, and RCBF—are more
An option for these steel registers is the robust, being assembled of steel or
plastic RZ680 series that has the extruded aluminum, and offer many more
advantages of molded-in color and rust sizes.
resistance, but the size offering is limited.
The ultimate in sidewall/ceiling products Ceiling Diffusers: Round ceiling diffusers
are the 92 series in steel and the HV are limited to our 16, RZ16, or 20
series in extruded aluminum. These diffusers. A square diffuser could be
products offer the widest range of sizes substituted for a round diffuser with little
and options, including stronger construc- change in performance. The 16 is a non-
tion, multiple damper choices, single or adjustable, steel, step-down diffuser. The
double deflection, adjustable blades, and RZ16 is a plastic flush diffuser with a 12-
matching returns and filter grilles. inch face, but it has built-in 6-, 7-, and 8-
inch collars. These come with a cam-lock
Curved-blade registers start with the installation method, removable core, and
300/A300 series, progress to the built-in damper. The 20 diffuser is a
A611-A614MS/OB adjustable curved- heavy duty, adjustable core diffuser for
blade registers, and finally extend to the commercial and industrial applications.
C series extruded aluminum registers.
The 300/A300 series of stamped, fixed- Square diffusers include the 24, RZ500,
blade registers have a multi-shutter SD, the A500 directional series, the MCD
damper. The assembled A600 series modular core diffuser, and the SR/AR
adjustable blade registers offer a choice of series, again in ascending order of
multi-shutter and opposed-blade features and size offerings. The 24 is a
dampers. Faces and blades are made of steel, step-down diffuser with butterfly
aluminum with painted galvanized steel and opposed-blade damper options. The
dampers. The C series of adjustable RZ500 is the square equivalent of the
curved-blade registers also have a choice RZ16 described above. The SD step-down
of multi-shutter and opposed-blade is an all-aluminum diffuser that can be
dampers, as well as a comprehensive size used in high humidity applications. An
matrix in 2-inch increments. White and MCD modular core diffuser is made from
satin anodized aluminum finishes are extruded aluminum and allows for 1-, 2-,
available. These are assembled using 3-, 4-, and 2-way corner airflow patterns.
premium aluminum extrusions. It is offered in two margin styles, nine
sizes, plus an available T-bar mounting,
Return Grilles: The 650 and 672 with or without damper. The SR/AR
stamped-face, louvered return grilles series has the greatest number of options
could be substituted for one another of sizes and face styles in both steel and
(as before, there is a difference in blade aluminum for any ceiling diffuser in our
spacing) before moving to the 94, 94A, lineup of products. Not all of these are
RCB, RE5, RH90, or RH45 return grilles. suited for residential applications,
The latter group is usually considered however.
“commercial” because these are
assembled rather than stamped. They A substitution may not always be avail-
have stronger construction and offer more able or welcome, but if the opportunity
features, especially size options. occurs, the preceding should be helpful.
December 2005
©2005 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
instructions. Codes usually do not installers and to inspectors on
prevent the use of materials, portions of codes that apply to our
methods, or procedures not products.
specifically prescribed by it, but
they may require evidence to Whenever someone calls for help,
substantiate claims of equivalent we need to deal with clear and
performance or safety of concise facts. Be prepared to
alternatives. provide comprehensive and detailed
information with documentation if
The Inspector is the authority necessary. We can only deal with
having jurisdiction designated by the the information provided to us. If
governmental agency. The inspector the information is inaccurate or
administers and enforces codes by incomplete, it could affect the
inspecting installations during outcome of the disagreement.
construction, or at least before use
or occupancy. Call us, fax us, or contact us by
e-mail through our web site at
Installers and inspectors, working www.hartandcooley.com.
together, will minimize conflicts.
Misunderstandings will occur and
disputes will arise, but letting the
issue become confrontational is
inadvisable. Usually, it becomes a
matter of discussing the issues for
resolution. Contractors/installers
should know the product, the
installation instructions, and which
codes apply.
January 2006
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
Big deal, you say? Have you ever tried to find the 12- and 6-inch dimensions on
a register? They aren’t there! The dimensions are called nominal, meaning
“in name only.” The nominal dimensions or “listed size” of a register refer to
the hole, boot, stack head, or duct opening. The industry builds the damper on
the back of a register undersized with reference to the nominal dimensions so
that the damper will fit into the opening. A submittal drawing of the part may
3
show the damper dimensions as “listed size minus /8” which means that for our
example, the damper dimension would be 115/8 by 55/8 inches.
February 2006
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
These tests are oriented toward a The amount of static pressure that
vent system operating with a builds up around a horizontal vent
negative pressure. These UL cap depends on wind speed, wind
standards do not address direction, and how close the cap is
performance of these same caps for mounted to the sidewall. Both
a horizontal, positive pressure vent. increasing wind speed and shorter
cap distances to the wall will
Horizontal vent performance increase static pressure to a point
requirements for the gas-fired where the furnace may not vent
appliance certification process are properly. Clearly, the appliance
part of the ANSI Z21 series of manufacturer does not want a vent
standards. When an appliance is termination to extend out from a
tested with a horizontal vent system, building wall 4 feet just to overcome
the appliance manufacturer must the cap’s poor performance in the
specify which cap(s) should be used wind test. Six to 12 inches is
with their appliance, based on these usually an acceptable distance that
test results. In other words, for the will work with a proper cap tested
Hart & Cooley caps to be used for with the appliance.
sidewall vented appliances, they
must have been tested and approved Again, our caps have not been
for use with that appliance. To date, tested for use as horizontal
our RHW and RM caps have not terminations.
been tested with any appliance, that
we know of, and should not be used
for sidewall vent terminations
without the approval of the
appliance manufacturer.
March 2006
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
Special consideration must be given A 20x20 grille has 400 square inches
to master bedroom suites and home of gross area. If the “2 CFM/square
theater rooms where lower velocities inch” rule is used, 800 CFM is what
may have to be considered to the grille will handle with a low
guarantee no noise. Assembled enough face velocity to avoid noise.
grilles using heavier steel or For our 650 grille, using this method
extruded aluminum will not share results in a face velocity of about
the humming noise with their 430 FPM. This rule is a little
stamped-face cousins, but can make conservative for grilles, but much
airflow noises closer for filter grille performance.
if the velocity
creeps up
(Model RH45).
The room
activity and
background
noise level
will help
dictate how
RH45 Grille high the face
velocity may
extend. A noisy cafeteria or busy
lobby can afford higher velocities
than executive offices or libraries.
April 2006
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
Sizing charts and calculators for Cubic feet per minute airflow rate
duct sizing are available from many still equals the air velocity times the
sources. Hart & Cooley has a Sheet area of the duct in which the air is
Metal Duct Friction Loss Calculator flowing. Increasing the area of the
on one side of a slide chart with a duct will slow the velocity of the air
Flexible Duct Friction Loss and reduce pressure loss. Keep in
Calculator on the other side that we mind that the long-term system
make available. We also have an performance will be affected by the
interactive flex duct calculator on up-front, one-time cost of the flex
our web site. Spending a few duct. Increasing flex duct one size
minutes with these aids can quickly to offset its higher pressure loss
demonstrate the differences between compared to smooth duct is
the friction losses for galvanized prudent.
verses flexible duct. It is worth
noting that for a fixed duct diameter,
as the velocity in the duct increases,
the friction loss increases twice as
fast. So if the velocity were to
double, the friction loss would be
four times greater! A handy rule
that is very effective and reliable is
to increase the size of flex duct one
diameter to neutralize the added
friction loss compared to that of
galvanized duct for the same CFM.
May 2006
Cleaning Chimneys
by Dave Fetters
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
ignited, can create a severe chimney Thoroughly brushing the chimney is
fire—that’s dangerous! usually adequate to mechanically
remove any buildup of soot or
Soot, on the other hand, is not creosote from the interior of the
normally thought of chimney for intermittent
as “dangerous,” nor cleaning during the
does it build up heating season. We
layers thick enough recommend a final pass
to affect the draft. down the chimney be
It’s only thought of as made with the brush
annoying, if it is wrapped in a rag. At the
thought about at all. end of the season, spray
But left alone, soot the rag-wrapped brush
containing harmful with WD-40 for the very
acidic compounds last pass down and back
can harm the chimney. up the chimney. This will help
remove all residual soot from the
Oil and coal fuels contain sulfur. surface and leave a protective film
When burned, the sulfur becomes on the interior throughout the
sulfites and sulfates that end up summer.
being carried out in the flue gases.
If these compounds trapped in the
soot are allowed to sit in the
chimney for long periods of time,
say all summer, the moisture in the
air will combine with the sulfur
compounds to form acids. These
acids then begin to eat away at the
stainless steel.
June 2006
Tape
As an added service to our flexible Generic “Duct Tape” is sold and
duct and connector customers, used for many applications other
Hart & Cooley sells an than for sealing ducts.
Underwriters There are different
Laboratories-listed tape grades and levels of
specifically for use with performance, but, unless
flexible duct as required it is UL-listed 181B, it is
by national standards. not approved for flexible
This tape is labeled duct applications.
“UL 181B-FX” both on There is a UL 181A tape
the package and on the specific for duct board,
tape. We offer rolls in and neither should be
both black and silver to substituted for the
match the color of our other.
flexible duct jackets.
Tape is used for both Generic tape is mostly
sealing the duct to cloth-backed with a
collars, as our instruc- water soluble, rubber-
tions state, and to seal based adhesive that is
rips and tears in the sold in 60-yard rolls.
jacket should they Hart & Cooley’s duct
occur. tape is a polypropylene film with a
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
solvent-based adhesive that is sold Ducts must be reasonably airtight to
in a 120-yard roll. It also has higher prevent leakage and noise for
tack and adhesion, a longer shelf reasons of energy efficiency,
life, and a flame and smoke rating of humidity control, cost, temperature
25/50—suitable for commercial control, reduced maintenance and
applications. It is a tough material, general acceptability. Since most
yet can be torn by hand. The systems are not pressure-tested
functional temperature range is -35° before being approved, the codes
to +260°F—better than cloth tapes. insist on the use of UL-listed
materials and prescriptive methods
Non-metallic clamps of attachment and sealing that, if
Non-metallic air ducts and followed, will ensure consistently
connectors are required by industry tight joints.
installation instructions to clamp
the core to the collar. This can be
accomplished with either metallic
hose clamps or with listed non-
metallic clamps labeled in
accordance with UL standard 181B
and marked “181B-C.” This UL
standard is a relatively recent
development for these non-metallic
clamps. Prior to this portion of the
standard, each flexible duct
manufacturer would have to test at
significant expense each non-
metallic clamp to be specified. We
now have a list of 9 different
manufacturers that have multiple
models listed with UL.
July 2006
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
We were curious about these Anyone following Hart & Cooley’s
instruments, so we tried a few over Tech Talk newsletters should know
the years in our laboratory and by now the CFM = Velocity x Area
compared them to our expensive, relationship that I’ve mentioned in
calibrated, hot-wire anemometers. previous issues—Numbers 8, 14 and
In a word, they perform well enough 16. The units of the quantities on
for one to get a good idea of the air both sides of the equal sign must be
velocity. Some are more accurate the same. Cubic feet per minute
than others, with accuracy declining appear on the left of the equal sign.
toward the low velocity readings. Velocity on the right side is in feet
A little experience is helpful in the per minute. Therefore, the area
use of these devices, but does not must also be in square feet—
significantly improve the outcome. effective area in square feet to be
More important to proper use is to accurate.
understand a little about airflow and
the expected result, at least within We provide the effective area (Ak) in
the ballpark! square feet in the performance data
for all our products. This is what
The single biggest shortcoming that should be entered into these meters,
we saw on a consistent basis was in NOT the free area typically given in
the lack of clarity of instruction square inches (if one can find it at
manuals. Reading face velocity with all). We did not find any meter that
these instruments is straightforward. would accept free area in square
One of the keys to obtaining a good inches and convert it internally to
face velocity is by averaging many the square feet that is required.
readings covering the entire face.
However, when the instructions say Beyond the above, which remains
how to obtain CFM, some make a very important for good results, we
glaring error by asking the operator found the meters to be adequate for
to enter the free area. Not only that, the job and certainly better than
but the instructions may not clearly nothing.
state whether this area should be in
square inches or square feet.
August 2006
We’ve all seen them – ceiling supply air. This dirt suspended in
diffusers that are dirt-stained, and room air, called an “atmospheric
the dirt stains usually extend to the aerosol,” can then be entrained
surrounding ceiling surface. It is (drawn) into the discharge of the
unsightly, especially if one is waiting diffuser. Additionally, diffusers with
for a meal in a restaurant. A first tumbling air patterns that contact
reaction from the ceiling, such as
those outside our the RENPS, are more
industry is “Wow,
the filters need to
…dirty or poorly likely to generate
smudging on the
be changed.” functioning filters ceiling. This is in
Hopefully, those of contrast to a register
us involved in are not the sole or that blows air angled
HVAC businesses
know that dirty or
most common away from the
mounting surface,
poorly functioning cause. such as the 682,
filters are not the although dirt may
sole or most still stain the diffuser.
common cause.
Dirt particles can be composed of
Investigations have shown that both natural and man-made
“smudging,” as we call the materials that are generally common
deposition of dirt particles on the air in the immediate area. The amount
outlet and surrounding surfaces, is varies with the geography, season,
more likely to be generated from weather, room furnishings, room
room activity that releases dirt into construction, and activity. Dust,
the room air rather than from dirty carpet fibers, tobacco smoke, greasy
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
fumes, lint, and pollen Another potential solution
are some of the is to use our Surfaire® or
particles deposited. REN4 diffusers that
The smallest particle generate a very thin air
sizes are the worst stream tight to the ceiling
offenders. Heavy foot that prevents dirt-laden
traffic through a room room air from entering the
will stir up these fine SRS/ARS minimal space between
particles and keep the supply stream and the
them in suspension. ceiling. Some dirt will still
Cooking, printing, deposit on the aluminum
paper dust, and face at the edges of the air
smoking are some pattern and in the center
other contributing where there is little
activities to smudging. airflow. These stains on
One interesting an aluminum diffuser are
example occurred in a ®
Surfaire /REN4 easy to wipe off compared
new local food store to ceiling materials.
near our offices. Dust from the
coffee grinder produced an obvious What we are trying to do is prevent
brown blossom on the ceiling the entrained room air that
around the diffuser that was located suspends the dirt particles from
above the grinder with nothing reaching the ceiling surface where
appearing on the more remote the forces of electrostatics, vapor
outlets, even though they were on pressure, direct impingement, and
the same air system. temperature difference cause the
dirt to stick. The (relatively) high
How can we control (notice I didn’t velocity of the supply air stream
say “eliminate”) smudging in creates a localized lower pressure
susceptible areas? A combination of that the room air-suspended dirt will
keeping the air filters clean, frequent want to flow toward. As my wife
mopping and vacuuming of floors, likes to say, “Nature abhors a
and room air cleaners can all help, vacuum” (which she learned from
but may not be practical in many me). That’s another way of stating
areas. A careful selection and that air will flow from a region of
mounting of air diffusers will high pressure to one at a lower
minimize dirt smudging, but pressure. Keeping this supply jet off
recognize that we are addressing the the ceiling surface can help reduce
symptoms, not the problem. staining.
September 2006
I know what you are thinking: “Oh sizes that are not listed based on sizes
no, here comes another math lesson. that are. I also mentioned using a
I don’t even know what those big calculator to find a listed size register
words mean!” Well, you’re right. that has similar gross square inches as
This is going to involve math to some the unlisted size. By using the data
degree, but only simple addition and for the register that is close in
multiplication. It’s more about equivalent area, you will have a good
teaching you the concept of sizing a idea of its performance. This is
register or grille for a size not shown sometimes called “the equal area
in our performance data tables, based method.” This is an iterative process
on data for a size that is shown (to in that it requires a “trial-and-error”
interpolate or extrapolate). approach until a solution is found.
Interpolate means working within the We will again use the 821/92/HV
maximum and minimum table entries series products as examples, although
to find data for a size that falls this same discussion can be applied to
between two listed sizes. Extrapolate many other products as well. These
means to project known data from a products lend themselves to the
listed size for a size that falls beyond discussion because of the numerous
the largest size listed. sizes that are listed, with which I will
demonstrate both interpolation and
Previously in Tech Talk TT-19, I extrapolation.
mentioned the alternate sizing graph
in the back of our catalog as one Let me begin by saying that any
means of finding performance data for alternate sizing must remain not only
the 821/92/HV series products for within the same deflection (A, C, E, or
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
G) table, but also under the same Examples: An 18 x 12 is not a size
column of face velocity. My examples that is listed, but a 36 x 12 is. If we
will all be from the Deflection A take half the CFM of a 36 x 12, it will
performance data and in the 400 Feet- represent the CFM for the 18 x 12 at
per-Minute face velocity column for the same face velocity. CFM for an
simplicity. The principles apply to unlisted 36 x 24 will be twice that of
any deflection and face velocity, the listed 36 x 12 and for an unlisted
however. 36 x 36, three times that of the
36 x 12.
A 24 x 12 register will be twice as
large as a 24 x 6 register. A 24 x 24 is Be sure to keep in mind what
two times larger than a 24 x 12 and constitutes twice the size as opposed
four times larger than the 24 x 6. But to four times the size of a register.
a 12 x 6 is ¼ the size of a 24 x 12. Doubling one dimension only will
See the representation below. double the size while doubling both
dimensions will quadruple (4x) the
24 size.
12 x 6 12 x 6
12 One last comment: To determine a
12 x 6 12 x 6 rough throw result, use the
multiplication factors below.
October 2006
A611 adjustable A612 adjustable All three series offer all four
deflections. The C series, made from
extruded aluminum, is the premium
product because of its considerable
strength advantage over the roll-
formed product. In addition, the C
series is offered as a grille
(no damper) and as a register with
A613 adjustable A614 adjustable either a multi-shutter or
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
opposed-blade damper in 2-inch don’t understand the concepts of air
increments from 6 x 6 to 36 x 36— pattern adjustments or they don’t
a much larger matrix of sizes and bother. My guess is the former in
options than the A600 series. These most cases because they have never
are some of the reasons why the C been shown the advantages of
series costs more than the A600 adjusting air deflection to suit the
series—added features. seasonal demands.
The performance data of the A600 Since the blade setting has so much
and C series product lines are very impact on performance, we have
similar, providing that the blades are chosen a blade setting for general
set to the same opening dimension. purpose cooling. The gap is specified
The 300 series is not included in this at 13/32 of an inch for our data
discussion since the blades are fixed. gathering purposes (it happened to be
A significant advantage of adjustable the width of the scale in my pocket at
curved-blade registers is the ability to the time!). We show this
open or close the blades to suit the dimensioned gap for the C series in
room comfort requirements. our catalog. We did not choose to
Consequently, performance depends generate data at other blade settings
on how far the blades are open with due to resource constraints. This has
respect to how much air is available at proven to be acceptable based on my
the face. With this in mind, consider feedback.
a narrow blade opening for a ceiling-
mounted register. A small gap You may direct your questions,
between blades constricts the airflow, comments, or suggestions for future
which usually increases the velocity articles to me at any time. See our
and resistance (for a set CFM, web site at www.hartandcooley.com
reducing the area increases the for contact information.
velocity if the fan can work against
the added resistance). The result is
an air pattern that is tight to the
ceiling surface at a somewhat
increased velocity that will maximize
the throw. This is a great cooling
pattern.
CH1 adjustable CH2 adjustable
At the extreme opposite blade setting
with all the blades open to the
maximum, the air is no longer
deflected into discreet directions
along the ceiling, but allowed to blow
straight downward or outward. This is
the best way to introduce warm air
from the ceiling into the occupied C3 adjustable C4 adjustable
space with this type product. Since
conditioned air above ambient
temperature is so buoyant, it needs to
be blown downward from ceiling
outlets to provide good air mixing and
to avoid stagnation near the floor.
November 2006
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
So my response is a cautionary “Yes, Our testing has shown that a B-vent
you may use it.” I immediately skin temperature will not exceed
qualify my answer with a discussion about 200ºF measured near the
about some issues that affect appliance when the vent is fired at
performance and acceptance by the its maximum input temperature on a
building owner or mechanical continuous basis. Cycling appli-
inspector. ances with normally lower flue gas
temperatures will not generate this
Listing: Foremost is the fact that much skin temperature, especially
these flashings are not UL-listed for when measured near the termina-
use with B-vent, and may not be tion. Unlisted appliances or those
acceptable to the authority having not approved for use with B-vent
inspection jurisdiction. For the may easily cause skin temperatures
most part, my experience indicates to exceed 212ºF, depending on the
that use with Type B gas vent is firing conditions. This will exceed
almost universally accepted by the EPDM rubber maximum
inspectors. However, these flashings temperature.
shall not be used with our factory-
built chimney system because of our An option other than using a soft-
UL-listing and associated cone flashing for profiled roofing
performance requirements. I systems is to build or purchase a
suspect all other chimney custom roof curb with integral
manufacturers’ systems have listed cricket, such as the Roof Products &
flashings that preclude the use of Systems brand from Commercial
these unlisted flexible flashings. Products Group in Bensenville, IL
(800.624.8642 phone). This
Sealing: Rubber cones have to be provides a smooth, flat surface to
made to fit the pipe diameter by mount a factory-made flashing.
cutting or pulling tear-off rings.
A tear-off will have a smoother
sealing surface than a cut edge,
which affects how well the cone
seals to the pipe. The smoother and
tighter it is, the better it will seal,
since a storm collar is generally not
used. However, no matter how well
the cone might fit without sealant,
water will find its way along the
vertical lock seam on B-vent and run
down the pipe. I encourage a little
dab of silicone at that point to
prevent water leakage.
December 2006
A recurring theme in my work is the B vent sizing tables are so important! With
question from many quarters about why the Department of Energy likely to increase
condensation is occurring in a Type B gas efficiency requirements of gas-fired
vent and what to do about it. appliances by 2 percentage points in the
Unfortunately, the near future,
condensation adhering to the
usually drips out of tables to
an elbow in the The vent, through proper design and prevent
attic, wets the sizing, must keep the moisture in the condensation
insulation, and becomes
stains a bedroom
vapor state until it exits the vent. critical.
ceiling before it is This is one reason why the B vent The following is
noticed elsewhere. sizing tables are so important! a list of reasons
Condensate will for condensate
form in the coldest development in
part of the vent (near the termination) the approximate order of priority, based on
when the flue gas cools to its dew point my experience.
temperature. This is the temperature at
which the flue gas, with its heavy load of 1. Single-wall connectors used with 80%
moisture in the form of water vapor, starts appliances. It’s okay to use single-wall
to condense (“dew” forms) on the cooler connectors with these non-draft hood-
walls of the vent. equipped appliances, IF one uses the
proper sizing table. The FAN MIN
A 100,000-BTUH furnace burning for one input from the single-wall connector
hour will generate a gallon of water in the sizing table must be met or exceeded to
form of vapor in the flue gas. The vent, prevent condensation. Be careful of
through proper design and sizing, must 2-stage and modulating equipment. Use
keep the moisture in the vapor state until it the lowest firing rate for determining
exits the vent. This is one reason why the FAN MIN.
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
2. Water heater connector is too small. 6. An interior masonry chimney venting
In multiple-appliance systems, a 3-inch 80% appliances. Neither single nor
diameter connector will not accommo- multiple fan-assisted 80% appliance(s)
date water heater inputs greater than shall be vented into an interior masonry
about 35,000 BTUH, even though water chimney without a dedicated relining
heaters with inputs as high as 50,000 system.
BTUH still use 3-inch draft hood collars.
7. Venting into exterior masonry chim-
Use a 4-inch connector on every 3-inch
neys. Even though the National Fuel
water heater collar to eliminate this
Gas Code has sizing tables for this
problem. Do not assume that because
scenario, they are very complicated and
the water heater has a 3-inch draft hood
restrictive. The best choice, especially
collar that 3-inch connector is always
for the northern tier states, is to plan
appropriate.
for and install a properly sized, listed
3. Offsets (laterals, horizontal runs) in gas appliance relining system approved
connectors and common vents that are for this use.
too long. A single-appliance vent sizing
8. Not properly accommodating appli-
table provides data that tells you how
ances with vent dampers. An appliance
far the horizontal run may be.
with a built-in powered vent damper
However, for a multiple-appliance
must be sized using NAT MAX in
connector or for the common vent in
combination with FAN MIN from the
multiple-appliance systems, the limit is
sizing tables.
1½ feet of horizontal run per inch of
connector or vent diameter. This can
Insulating B vent to try to solve a con-
be a significant limitation, especially for
densation problem will not work, and
common vents, but, if exceeded, leads
B vent manufacturers do not want their
directly to condensate formation.
B vents insulated. The insulation is
4. Combustion and make-up air issues. treating the symptom, not the problem.
The code is very clear about how to
calculate and provide proper openings Although condensate formation may
for combustion and make-up air. These manifest itself in the vent extremities, the
days with tight homes, larger bath fans, cause more often than not may be in the
fancy cooking appliances, dryers, and mechanical
decorative gas-fired appliances room. The
consuming indoor air, it becomes Hart & Cooley
imperative to provide air for the heating Gas vent,
appliances in the required amounts. chimney
Condensation is only one sign of sizing &
restricted air. Spillage, no draft, and, in application
a worst case, carbon monoxide are guide has a
other consequences. lot of good
information,
5. The common vent is too small, too
which
large, or exposed on an outside wall.
includes
A common vent that is too small will
sizing tables
obviously have to be made larger, have
and combustion air opening requirements.
an appliance removed from the system,
To receive a free copy, please contact your
or be engineered to work. To prevent a
Customer Service Representation. Or, if
common vent from being too large, its
you prefer, you can view the guide on our
area shall not be more than 7 times the
web site at www.hartandcooley.com.
area of the smallest connected appli-
ance collar. A vent shall not be exposed
to the outdoors below the roofline.
These are existing fuel gas code require-
ments and have been for some time.
January 2007
Vent Offsets
by Dave Fetters
A loyal reader of these Tech Talk Notice that the definition avoids any
newsletters suggested that I address mention of the angle or slope of the
vent offsets as a topic. Even though I offset. However, buried in the text of
have other Tech Talks already written the paragraphs of Chapter 13, where
and could have used for this month, this the code discusses sizing, is some
topic excited me and is a worthy insight into what angle the code refers
subject for discussion. Only an to when it mentions lateral. Paragraph
engineer can get “excited” about such 13.1.3 for single-appliance venting says
matters. Others are merely interested. “…venting with lateral lengths include
two 90° elbows.” Clearly, this
The National Fuel Gas Code (NFGC) statement means that a lateral is
and International Fuel Gas Code are not horizontal pipe between two 90°
explicit in their definitions of what elbows. The horizontal offset is
constitutes an offset in a vent system. measured along this horizontal run
A typical definition of vent offset is this from the same point on each end
one from the NFGC (2006 edition) (centerline to centerline or outside wall
Paragraph 3.3.107: “Vent Offset. to the same outside wall at the other
An arrangement of two or more fittings end).
and pipe installed for the purpose of
locating a vertical section of vent pipe The code also speaks about offsets that
in a different but parallel plane with can be pipe-installed at angles less than
respect to an adjacent section of 90° (30° or 45° from vertical for
vertical vent pipe.” instance) as stated in paragraph 13.2.5
©2006 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
Vent Offsets and paragraph 13.2.6 In summary, the NFGC allows offsets in
Elbows in Vents. When a vent has an single-appliance and multiple-appliance
offset, say in an attic, where the angle of vents. The offset in the eyes of the code
the offset is 45°, the code looks at what is the horizontal displacement of the
the vertical-centerline-to-vertical- vent. A horizontal vent may be
centerline, horizontal displacement is, measured directly. A vent on some
and uses that for the offset or lateral angle can be calculated as demonstrated
allowance. This is the dimension above, guessed at (bad idea), or
labeled “Offset” in the adjacent measured using a plumb bob from the
drawing. Typically, if the vent is for a displaced vertical. Whew!
single appliance, the sizing tables show
the horizontal offset allowance in the
column labeled “Lateral.” For multiple-
appliance common vents, the code
allows the horizontal offset to be no
more than 18 inches for each inch of
common vent diameter.
February 2007
When considering the use of wood floor changes in product performance. All
diffusers instead of the traditional metal Hart & Cooley floor diffusers (including
kind, one should consider how they wood) meet the International
perform, as well as how they look. Mechanical Code for strength. Since
wood is not as strong as steel, more
Wood floor diffusers can be an wood must be used in the diffuser to
aesthetically pleasing addition to a meet the strength requirements.
home. Solid wood or wood-faced floor
diffusers look nice, can be stained to Consequently, wood diffusers generally
match wood floors, and recessed flush have different performance character-
with a wooden floor surface (R403). istics than steel diffusers. Performance,
for the purpose of this Tech Talk, refers
to the effective area and throw pattern
of the diffuser. For example, the R400
(the wood equivalent to the steel
Hart & Cooley 421) has only 60% of the
R403 effective area of the 421. One must
consider the impact that lower effective
area (lower cfm delivery) will have on
However, when
considering the use of
wood floor diffusers
instead of the
traditional steel
R400
diffusers, one should
also account for
421
©2007 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
room comfort before selecting the
diffuser. A larger size wood diffuser or
additional floor diffusers may be
necessary to maintain the same cfm
delivery as a traditional steel diffuser.
by Dave Fetters
Air circulation and conditioning usually than other types of media and filtration
incorporate some form of filtration of methods. More important to the
airborne particulate matter. There are installer, most efficiency and pressure
many types of filtering mechanisms drop ratings are developed at only
and methods, but I want to limit my 300 feet-per-minute airflow velocity
remarks to the specific products we sell through the filter. The maximum
that allow air filtration. In our business, airflow recommended is usually around
this air filtering is accomplished with a 500 feet per minute, as published in the
filter grille. The vast majority of our literature for these types of filters.
filter grilles are designed to use the
readily available, 1-inch thick, Given the popularity of these types of
cardboard-edged, disposable, fiberglass filters, care must be given in selecting a
filters. Although we manufacture filter filter grille size to accommodate the
grilles that will accept thicker filters, desired total CFM, while keeping in
relatively few are sold. Even though mind the filter limitations of velocity.
hog hair, foam, and other types of Our recommendation for a maximum
media filters may do a better job of design face velocity is 400 feet per
filtration than the fiberglass, the minute (FPM). To size a filter grille,
universally available and inexpensive look at the engineering data for that
fiberglass filter is the most popular model. In the column less than 400
choice. FPM, find a CFM number that is equal
to or slightly higher than what is
These throwaway, one-inch panel filters desired or required. The size corres-
are relatively inefficient and are ponding to that rating is what should be
effective with comparatively large used.
particulate matter at low airflow rates
©2007 Hart & Cooley, Inc. All rights reserved (continued on reverse side)
A rough but safe rule of thumb to use in Obviously, as a filter collects dirt, its
the absence of available engineering resistance to flow increases and drives
data is to multiply the gross filter grille up the system pressure loss. For this
area in square inches by 2 CFM for each reason, it is vitally important for a
square inch. This will keep the face homeowner to establish a regular
velocity below 400 FPM. For instance, maintenance cycle to change out
if one thinks a 20 x 20 grille might be filters, so they do not affect the system
adequate, 20 x 20 = 400 gross square performance.
inches. Multiply this by 2 CFM per
square inch and the result is a CFM of
800.