EARTHMAT DESIGN Description 1.0 SYSTEM DATA Rms value of symmetrical fault current Fault clearing time for conductor selection 1.1 SOIL DATA Soil Resistivity (Average) Surface resistivity Thickness of Surface layer 1.2 GRID CONDUCTOR DATA The Conductor Selected is 25 mm dia MS Rod Max allowable temperature of the conductor Ambient temperature Reference temperature for material constant Coefficient of resistivity at Tr o C (Mild Steel) Resistivity of ground conductor Thermal capacity factor Diameter of grid conductor in m Spacing of grid conductor Chosen Depth of burial of Grid conductor Duration of shock 1.3 SWITCHYARD DATA (Refer Annexure-1 for Earthgrid layout ) Length of Rectangle -132/33 kV Side Width of Rectangle -132/33 kV Side Area of substation Grid conductor periphery length Maximum distance along grid length A Lp Lx m m Sq.m m m = 73 = 101.5 = 7409.5 = 349.0 = 73.00 Tm Ta Tr r r TCAP d D h ts -cm J/cm3/oC m m m Sec
o
Symbol
Unit
Value
I tr
kA sec
= 31.5 = 1
s hs
-m -m m
c c c
Page 2 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
Maximum distance along grid width 1.4 EARTH ELECTRODE DATA Diameter of Pipe/rod earth electrode in m Length of each rod conductor in m No.of Earth electrodes Total length of ground rods (Refer Annexure-1 for No. of Earth Electrodes) 2.0 METHODOLOGY:
Ly
= 101.5
De Lr N LR
m m Nos m
= 0.04 = 3 = 54 = 162
2.1 The Earthing Design Calculation is done as per the recommendations given in IEEE Std. 80,2000 2.2 The Corrosion Allowance is considered for Mild Steel as per the recommendations given in CBIP Manual on Earthing. 2.3 The Following are considered for determination of grounding conductor length Total length of Earthmat Length of Earth electrodes
Page 3 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
3.0 3.1
CALCULATION: Selection of cross section of grid conductor (A) The Cross-section of Conductor is given by A =
I TCAP.10 4 t . . r r r K +T m ln o K +T o a
mm2
mm2
Where K0 = 1 / ar - tr
K0
440 Sq.mm
= =
440 4 3.14
23.7 mm 25mm dia MS Rod
Selected Conductor Size Hence safe. 3.2 Determination of grounding conductor length: The Earth Mat spacing considered for safe Step & Touch Potential Area of Substation earthing Grid conductor periphery length Maximum distance along grid length Maximum distance along grid width Length of each ground rod Total length of ground rods Spacing of grid conductor chosen
= A Lp Lx Ly Lr
9mx9m
LR = 162 m D = 9.0 m
Page 4 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
Estimation of Grid Conductor Length Rectangle (73m x 101.5m) The number of conductors parallel to the length The number of conductors parallel to the width Length of Conductor for Rectangle The total length of the grid conductor along the Length & Width in the switchyard Grid conductor Combined Length (Lc) used in the switchyard Effective length of the buried Conductor in m = 12 = 9
}
LC LT
= 1790 m
= 1790 m = L C + LR = 1952 m
3.3
Where Df Sf If Decrement factor for Tf Current division factor Symmetrical Ground fault current = 1 = 0.73 = 31.5 kA
No of 132kV Transmission line shield wires = 4 No of 33kV Transmission line shield wires = 0 Sf = 0.73
Shock duration time ts = 0.5 sec 3.4 Calculation of Tolerable Touch voltage(Et) & Step voltage(Es)
Cs
0.09 1 2 h s
1 - s + 0.09
Cs
Cs
0.693
Page 5 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
Et50 =
(1000 + 6C S S ) 0.116
tS
Es50 = 3.5
2210 V
Rg
1 + LT
1 1 + 20 20 .A 1+ h A 1
Rg
33.36
1 1952
1 20 x 7410
1+ 1+0.6
1 20 7410 Ohm
Rg
0.188 Ohms
3.6
3.7
Where na =
L 2 C L P
2 x (1789.5 / 349) 10.26
= =
Page 6 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
nb
LP 4 A
349 4 x 7410 1.01
nc
0.7A L L L Y X Y = LX A
= 73 x 101.5 7410 = 1 1 (For Square,Rectangular & L-shaped grids) 1 = 10
( 0.7 x 7410)/(73 x101.5)
nd nd
= =
0.644 + (0.148 n )
( ) 0.644 + (0.148 x 10.00) 2.18
Where Kii =
1 (For a grid with earth electrodes along the perimeter or for grids with electrodes in grid corners as well as both along the perimeter and througout the grid area)
h 1 + ho
Kh
= =
1.265
Km
1 2x 3.14
ln
92 16 x 0.6 x 0.04
+ (9 + 2 x 0.6)2 8 x 9 x 0.04
0.6 4 x 0.04
1 1.265
ln
8 3.14 x (2 x (18.00-1))
Km
0.692
Page 7 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
1 1 1 1 + + 1 0.5 n 2 2h D + h D
1- 0.5(11-2)
1 3.14
1 2 x 0.6
+ 1 9 +0.6
1 9
Ks
0.334
3.7.5 Determination of the effective buried Length of conductor (Lm for Touch Voltage) For grids with Earth electrodes
+ 1.55 + 1.22 = LC L R L 2 + L 2 x y Lr
Lm
1790 +
1.55 + 1.22
3 732 + 101.52
162
Lm
2045 m
3.7.6 Determination of the effective buried Length of conductor (Ls for Step Voltage): Ls = = Ls = 0.75Lc + 0.85LR for grids with or without ground rods
Em
K K l m i G L m
= Em =
Es
K K l s i G L s
( 33.36x 0.334 x 2.18 x 23000) / 1480 377 V
= Es 4.0 a) b) c) =
CONCLUSION: Em vs Et50 The Calculated Mesh Voltage of 566 V is lower than the tolerable Touch Voltage 676 V. Es vs Es50 The Calculated Step Voltage of 377 V is lower than the tolerable Step Voltage 2210 V. Grid Resistance Rg The Calculated Grid Resistance of 0.188 Ohms is less than 1 Ohm Hence the design is safe.
Page 8 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
ANNEXURE - 1 Estimation of No. of Earth Electrodes for 132/33kV Jandaha New S/S
S.NO 1 1.1 1.2 1.3 1.4 2 2.1 2.2 3 4 DESCRIPTION 132kV SWITCHYARD SA CVT TOWERS WITH PEAK TRANSFORMER 33kV SWITCHYARD SA TOWERS WITH PEAK LIGHTNING MASTS GRID CORNERS Total No. of Earth Electrodes Length of Each Electrode Total Length of Earth Electrodes 6 9 2 4 54 3m 162 m 12 9 4 8 NO. OF EARTH ELECTRODES
Page 9 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005
0.73
0.188
Page 10 of 11
Doc.No.:SPL-BSTS-JANDAHA-EARTHMAT.CAL-005